2300 Series Vibration Monitors
2300 Series Vibration Monitors
2300 Series Vibration Monitors
Description
The 2300 Monitors feature two seismic channels and a speed
channel, providing continuous monitoring and protection for BOP
(Balance of plant) equipment. It is a perfect match for proactively
managing your assets, rather than waiting until production
outages to replace equipment.
Page 1 of 10
Monitor Key Features
2300/20 2300/25
Two 4-20mA outputs Trendmaster SPA interface
Two relay outputs with programmable setpoints Two relay outputs with programmable setpoints
Ethernet 10/100 Base-T communication for Ethernet 10/100 Base-T communication for
configuration using Bently Nevada Monitor configuration using Bently Nevada Monitor
Configuration software (included) Configuration software (included)
One dedicated speed and Keyphasor* channel One dedicated speed and Keyphasor channel
supporting Proximity probes, Magnetic pickup supporting Proximity probes, Magnetic pickup
and Proximity switch type sensors and Proximity switch type sensors
Three buffered transducer outputs (including Three buffered transducer outputs (including
Keyphasor signal) providing short circuit and EMI Keyphasor signal) providing short circuit and EMI
protection. Buffered outputs for each signal are protection. Buffered outputs for each signal are
through BNC connectors through BNC connectors
Continuous monitoring and protection Continuous monitoring and protection
LCD display showing vibration amplitude, LCD display showing vibration amplitude,
setpoints, and speed setpoints, and speed
Two acceleration inputs with synchronized Two acceleration inputs with synchronized
sampling for advanced diagnostics sampling for advanced diagnostics
Key measurements(Direct 0-pk, pk-pk, Direct rms, Key measurements(Direct 0-pk, pk-pk, Direct rms,
Derived pk, integrated direct pk, Speed) real-time Derived pk, integrated direct pk, Speed) real-time
provided with alarm configuration provided with alarm configuration
LEDs show the monitor status LEDs show the monitor status
Local contacts for positive engagement of Local contacts for positive engagement of
channel bypass, configuration lockout, and reset channel bypass, configuration lockout, and reset
Optional Modbus®1 over Ethernet Optional Modbus®1 over Ethernet
Page 2 of 10
Specifications Proximity Switch Interface:
o Supply Voltage: -10 to -24 VDC
o Lower Not Ok limit: -2.75 ±0.05 V
Inputs / Outputs
o Rpm range: 1 to 120,000
Power Input: Magnetic Pick up:
DC Input: 18~36VDC, max 7.5W o Input voltage up to ±125V (250Vp-p)
Supports 2 seismic channels: o Rpm range: 200 to 120,000
Supports ICP accelerometers Contact Inputs
o Bandpass variable: 0.2 Hz High pass, 20 kHz Monitor provides the capability of 3 contact inputs
Low pass with terminals. One is used for configuration lock,
o Scale Factor range: 5 to 575 mV/g one is for alarm reset function, and the 3rd one is
used for monitor Alarm/Relay Inhibit.
o Full scale range: 2 to 80 g peak
Activate: 0 to 10 kΩ
o Bias output voltage: -12VDC
De-activate: 150 kΩ to infinite
o Configurable Upper OK limit: -0.25 to -22 V
(greater than lower ok) Button Inputs
o Configurable Lower OK limit: -0.25 to -22 V External button to reset alarm and relay
(less than upper ok) One buried button provides 3 functions:
o Current Sink Source: 3.3 mA ± 5% o Display monitor information including:
o Open Circuit Voltage: -21 to -24 VDC User account/Password
o Accuracy: ±1% of full scale range IP address
Supports custom accelerometers (2 or 3 wires) FW/HW version
Independent 24-bit ADCs on both channels o LCD contrast adjustment
Speed/Keyphasor Inputs o Reset settings to default including:
Supported Keyphasor transducers include: User account name
o Proximity probe Password
o Proximity switch Network configuration
o Magnetic Pickup Jumper between COM & Chassis GND
Supports multiple events per revolution and There is a 2-pin terminal interface which allows
event ratios for speed inputs up to 20 kHz connection of COM and Chassis GND together.
Threshold voltage resolution: 0.1VDC Alternatively, COM can be connected to earth
Proximity Transducer Interface: ground separately through a terminal.
o Maximum Rated Current: 15 mA There are three buffered outputs available on the
monitor through BNC connectors:
o Short Circuit Current: 15.1 mA to 23.6 mA
o 2 Vibration Outputs
o Accuracy: ±1% of full scale range
o 1 Tachometer Output
o Input Impedance: 3-wire Voltage Mode, 10
kΩ
o Rpm range: 1 to 120,000
Page 3 of 10
Relay Output
There are two dry-contact relay outputs SPA Output (2300/25)2
May be normally energized or de-energized Input signal range
No output feedback determination o High AC: 8Vpp
Relay circuit specification in Non-Hazardous o Low AC: 1.6Vpp
area:
o DC GAP: 0 to -20Vdc (max measurable AC
o Type: Single pole, double throw signal is 1Vpp)
o Sealing: Epoxy sealed Accuracy
o Contact life: o AC: ±1% of Full-Scale at 100Hz
100,000 cycles @ 5 amps 250 VAC
o DC GAP: ±0.5V
200,000 @ 1 amp, 24 VDC
Frequency response
o Insulation resistance:
1000 MΩ minimum @ 500 VDC o 1.67Hz to 3000Hz (0% to -5%)
o Relay closed contact resistance: LEDs
1 Ω maximum
OK: Indicates when the monitor is operating
o Relay open contact resistance: properly
1 MΩ minimum
Protection fault: indicates a problem with the
o Maximum switched contact voltage: system preventing normal operation
250V AC /250V DC
User inhibit: indicates the relays have been
o Maximum breaking contact current: intentionally inhibited from operation
6A @250VAC / 6A @24VDC
Relay status: indicates if relays have been
o Maximum switched power: activated
1500VA AC / 150 Watts DC
TX/RX: Indicates the Ethernet status and monitor
Relay circuit specification in Hazardous area: communicating with remote software
o Maximum switched contact voltage and Speed channel status
current: 6A @24VAC / 5A @30VAC / 5.8A
Channel Alarm Status:
@24VDC / 4A @30VDC
o Alert LED: engages if any channel is in alert
4-20mA Output (2300/20)
state
Two 4-20mA outputs
o Danger LED: engages if any channel is in
4 to 20mA output values are proportional to the danger state
full-scale of the associated measurement
LCD
Each output can be software configured to
LCD display allows viewing machine speed, vibration
output any variable from channel 1 or 2
levels, setpoints, and configuration information.
Voltage compliance: 0 to +12Vdc range across
load
Load resistance: 0 to 600Ω Communications
Resolution: 0.3662uA
Ethernet
Accuracy: 1% over operating temperature range
Ethernet, 10Base-T and 100Base-TX. Conforms
Update rate: 100ms to IEEE802.3
2mA clamp current RJ-45 for 10Base-T/100Base-TX Ethernet cabling
No output feedback determination Cable length: 100 meters (328 ft.) maximum
Page 4 of 10
Environmental Limits Intrinsic Safety Parameters:
For Proximitor Transducer:
Operating Temperature:
Uo: 24VDC; Io: 46mA; Co: 200nF; Lo: 1mH
-30 °C to +65 °C (-22 °F to +149 °F)
For Accelerometer Transducer:
Storage Temperature:
Uo: 24VDC; Io: 3.3mA; Co: 200nF; Lo: 1mH
-40 °C to +85 °C (-40 °F to +185 °F)
Humidity:
Physical
Up to 95%, non-condensing
Battery Life for Real Time Clock: Dimensions (Width x Depth x Height)
Powered: 38 years @ 50°C (122 °F) 127mm x 127mm x 76.2mm (5in x 5in x 3in)
Un-powered: 12 years @ 50°C (122 °F) Weight
1.03kg (2.26lbs)
EMC
Standards:
EN61000-6-2 Immunity for Industrial Environments
EN61000-6-4 Emissions for Industrial Environments
EN61326-1 Electrical equipment for measurement,
control and laboratory use - EMC requirements
CSA/NRTL/C
Class I, Division 2/Zone 2
AEx/Ex nA nC [ic] IIC T4 Gc
Class I, Div. 2, Groups A, B, C, D
ATEX/IECEx
II 3 G
Ex nA nC [ic] IIC T4 Gc
Part Number: 105M0340-01
Rev. E (10/15)
Page 5 of 10
Ordering Information (Excluding Keyphasor sensor and 24VDC
power supply 3)
For a detailed listing of country and product
specific approvals, refer to the Approvals Quick 003
Reference Guide (document 108M1756) located at 1 - 2300/20 Monitor
the following website: www.GEmeasurement.com.
1 - 6 ft. shielded Ethernet cable
2300 Series Vibration Monitor 2 - Accelerometer sensors
2 - 12 ft. accelerometer cables
2300/20-AA: Monitor with 4-20ma Outputs
(Excluding Keyphasor sensor, enclosure
(including DIN rail mount assembly, manual and
and 24 VDC power supply 3)
monitor configuration software)
BB: Approvals Option
2300/25-AA: Monitor with SPA Outputs2 00
(including DIN rail mount assembly, manual and None
monitor configuration software)
02
AA: Approvals Option Multiple Explosive Atmosphere
00 Certifications (ATEX/IECEx/CSA)
None
02
3 We provide 3 kinds of power supplies with different temperature
Multiple Explosive Atmosphere
Certifications (ATEX/IECEx/CSA) range and different power. Please check Accessories below for
the details.
2300/20_KIT-AAA-BB: Bently Nevada 2300/20
Condition Monitoring System Kit
Page 6 of 10
105M6193-01 Fiberglass NEMA 4X/IP68 100M0741 Proximity Switch
weatherproof housing with window
in door (includes mounting plate for
monitor)
Dimensions:
(Width x Depth x Height)
338.3 x 389.1 x 209.8mm
(13.3 x 15.3 x 8.2in)
Proximity Probes
Page 7 of 10
CB2W100-AAA Cable for accelerometer Software
AAA:
016 16 ft. (4.8 m) 100M9465-01 BN Monitor Configuration SW/FW
032 32 ft. (9.8 m) DVD
064 64 ft. (19.5 m)
112 112 ft. (34.1 m) o BNMC version 4.0 or greater
125 125 ft. (38.1 m) o 2300 series monitor firmware
150 150 ft. (45.7 m)
200 200 ft. (61.0 m) (DVD including BNMC Configuration
250 250 ft. (76.2 m) Guide)
Note: Cable lengths greater than 30 meters (100 feet)
will experience some attenuation of amplitudes at
higher frequencies. User Manual
Ethernet Cables
Training Materials Link
138131-AAA Standard 10 Base-T/100 Base-TX http://ge-
Shielded Category 5 Cable with energy.turnstilesystems.com/ProgramDetail.aspx/23
RJ-45 connectors (solid conductor) 00Monitor
Spares
Page 8 of 10
Graphs and Figures
Page 9 of 10
Wiring Diagram
Note: 2300/20 and 2300/252 uses the same interface connector for recorder output or SPA output.