FEATURES
Auto-Ranging Input Voltage
UL: 24 - 600 Vac, 45 - 65 Hz
CE: 24 - 690 Vac, 45 - 65 Hz
AC Output MADE IN THE
8, 16, 32, 50, 80, 100, 130, 160, 200, 240, 320, 400 A USA
(@ 6000 ft [1829 m], 122°F [50°C])
Control Features
Microprocessor-based controller, phase lock loop timing
Firing modes:
Zero Cross, Phase Angle,
OPTIONAL FEATURES
Zero Cross Transformer (ZCT) Mode,
HiPER Mode, and Fast Zero Cross Mode
Feedback: Voltage, Current, True Power, External General Purpose Input
Adjustable Soft Start: Phase Angle Second Analog Input Channel
Output Limits: Voltage, Current, Power Additional Setpoint, Potentiometer Input, External
Missing Cycle Detection Feedback, or Pulse Width Modulation (PWM)
SYNC-GUARD™: Power-level multiple Zero-Cross controllers
TRANS-GUARD™: Prevent upstream transformer heating Alarm Relay
Dedicated Input Bit for Run/Stop Form C Relay Output
kWh Meter 2 x 16 Bit Analog Retransmits
Heater Bakeout Standard Setpoint Ranges: 0 - 5 Vdc, 4 - 20 mA
Resistance Measurement Field Scalable: 0 - 10 Vdc, 0 - 20 mA, or Potentiometer
Analog Interface (Up to Two Analog Inputs) Limit Control
Standard setpoint ranges: 0 - 5 Vdc, 4 - 20 mA Current, Power, and Voltage
Field Scalable: 0 - 10 Vdc, 0 - 20 mA, or Potentiometer
Remote Display
Available Internal Fieldbus Interfaces Handheld 2 line, 16 character text display
EtherNet/IP Modbus TCP (Ethernet) 1/4 Din Mount
PROFINET
High Performance
Easy Setup via Plug-n-Play USB True RMS Power, Load Voltage Feedback, Load Current
Load / Save Controller Configurations Feedback, High Resolution Control Loop
Chart Diagnostics and Log Operations Isolated I/O
500 Vac isolation from 24 Vdc control power to Analog
Two Year Warranty
Inputs, General purpose input, Run/Stop, and Retransmits
1 © Control Concepts Inc. 2022 www.ccipower.com 1-800-765-2799 MicroFUSION 3ø Brochure Rev. 5.8
DESCRIPTION
MicroFUSION is an ultra-compact high-performance microprocessor-based power controller, available in three phase 4
SCR, or three phase 6 SCR models to control AC loads.
Resistive or transformer-connected loads can be controlled in either Phase Angle, Zero Cross, Zero Cross Transformer
(ZCT), Fast Zero Cross (FZC), or HiPER Mode. Output is controlled linearly with respect to command signal and can be
set to the average or RMS value of the voltage and current, as well as true instantaneous power or external feedback.
MicroFUSION Series power controllers are available in current ratings from 8 - 400 A· AC. Auto-ranging voltage circuitry
enables main supply voltage from 24 - 600 Vac for UL/cUL or 24 - 690 Vac for CE, (45 - 65 Hz) eliminating the need for
hardware jumpers or stocking multiple controllers for international voltages. A separate 24 Vdc power source supplies the
control electronics and maintains critical communications to your control system when the mains are absent.
Status LEDs and a LED bar graph make operation and troubleshooting simple. A plug-n-play USB interface and free
Control Panel software for your PC further simplifies installing and configuring the controller to its designated application.
For multiple controllers, controller settings can be duplicated by simply loading a configuration file saved from a previous
unit.
Setpoints can be controlled through the standard analog or optional digital fieldbus interface. The factory-configured
analog setpoint signal ranges are 0 - 5 Vdc and 4 - 20 mA, both of which are field scalable from 0 - 10 Vdc or 0 - 20 mA.
The robust design of MicroFUSION allows for continuous full-frame current operation, without derating, up to
122°F [50°C], 6000 ft [1829 m] altitude. Cooling is accomplished through natural convection, forced air, or optional
external panel mount.
The optional IP65 Remote Display provides a clear readout of key parameters and alarm status. Setpoints, limits and
alarms are touchpad accessible and easily customized. For additional convenience, a panel mounting kit is available,
eliminating the need for external meters, indicators, switches and the associated costs of wiring and labor.
MicroFUSION 3ø Brochure Rev. 5.8 www.ccipower.com 1-800-765-2799 © Control Concepts, Inc. 2022 2
DIMENSIONS
Dimensions in Inches [mm]. 8 - 32 Amps
DIN Rail / Panel Mount
50 - 160 Amps
Panel Mount
200 - 240 A Weight: 18.00 lb [8.16 kg] 320 - 400 A Weight: 19.40 lb [8.80 kg]
3 © Control Concepts Inc. 2022 www.ccipower.com 1-800-765-2799 MicroFUSION 3ø Brochure Rev. 5.8
P1/P2 CONNECTOR
P1 Command Connector
P1 Connector P2 Command Connector
P2 Connector
24 Vdc Input-
+
+ * Retransmit 1
-
5 Vdc Output (onboard supply up to 10 mA) Output
* Retransmit 2 +
+ -
Analog Input SP 1 - Output
* PWM No Connection
+ NO
* Analog Input SP 2 -
* Relay (Form C) C
Common
NC
Run/Stop Input
*General Purpose Input
* Optional
FUSES FUSES
L C1 L C1
L O L O
L L
O A O O A O
A D A A D A
D D D D
B1 B1
L
L
O
O
A
A
D
LO AD LO AD
A1 A1
* PE GND PE GND
C LineC1
REF B2 B1 A2 A1 C2 C1 B2 B1 A2 A1
P2 P1 P2 P1
L C1
O
A
D
B1
L
L
O
O
A
A
D
A1
PE GND
*
C2 C1 B2 B1 A2 A1
REF
P2 P1
Three Phase, Delta or Wye, 50 - 400 A Three Phase, Four Wire Wye, 50 - 400 A Three Phase, Inside Delta, 50 - 400 A
FUSES
FUSES
C1
C1
B1
B1
A1 A1
PE GND PE GND
C1 B1 A1
C1 B1 A1
P2 P1
C2 B2 A2
P2 P1
L
LOAD
LOAD
LOAD
O
A C2 B2 A2
L D L
O O
A A
D D
L
L
O
O
A
A
D
LOAD
Equivalent circuit
Delta or Wye Load * Note: 0.60 mA maximum through C Ref connection at 600 Vac.
100-160
100 - 160 Inside Delta
See manual for recommended wire sizes.
5 © Control Concepts Inc. 2022 www.ccipower.com 1-800-765-2799 MicroFUSION 3ø Brochure Rev. 5.8
FEATURE COMPARISON
MicroFUSION is available with one of four performance options: SX-S (Standard board), SX-L (Standard board with
Current features), HX-L (High Performance board with Current and Voltage features) and HX-P (Fully populated High
Performance board)
= Included ¢ = Field Upgradable Option
= Option Available at Manufacturing Time - = Not available
MicroFUSION 3ø Brochure Rev. 5.8 www.ccipower.com 1-800-765-2799 © Control Concepts, Inc. 2022 6
FEATURE COMPARISON, CONTINUED
FEATURE LIST, CONTINUED SX-S SX-L HX-L HX-P
Zero Cross Transformer Firing Mode - - ¢ ¢
Retransmit (RTX): 2x High Resolution Analog Outputs 0 -10 Vdc or 0/4-20 mA - - ¢ ¢
Power Limit - - ¢
True Power Control - - ¢
Monitor True RMS Power - Provides true power data via software, display, or fieldbus - - ¢
High Resolution Control Loop - - ¢
Kwh Meter - - ¢
HiPER Mode - High performance low conduction angle firing mode - - ¢
Resistance Measurement - - ¢
SPECIFICATIONS
POWER
UL/cUL: 24 - 600 Vac (Nominal) (+10% / -15%) (Contact CCI for other options)
Line Voltage (Auto Ranging)
CE: 24 - 690 Vac (Nominal) (+10% / -15%) (Contact CCI for other options)
Line Frequency (Auto Ranging) 45 - 65 Hz
Frame Current Ratings (Amps) Continuous RMS (AC) 8 | 16 | 32 | 50 | 80 |100 | 130 | 160 |200 | 240 | 320 | 400
Current Rating - Peak Surge 20x frame rating for 10 ms
Minimum Hold/Latch Current 500 mA up to 160 A 1 A at 200 - 400 A
Max Leakage Current 10.6 mA @ 600 Vac 50/60 Hz
SCR Rating (PIV) 1600 V peak forward & reverse
Fusing Optional external Class T, branch-rated, touch-safe fusing
Thermal Integrated heat sink thermal sensor
Current Limit 105% (SX-S), 20 - 105% (SX-L, HX) of continuous rating of Frame Amp Rating
Current Trip 50 - 450% of continuous rating
Power Dissipation 1.3 W per A of load current per phase
Control Power / Operates 24 Vdc (+10 / -15%)
Internal Control Electronics
ENVIRONMENTAL
Surrounding Air Operating Temp 32°F [0°C] to 122°F [50°C] with derating for 140°F [60°C]
Humidity 20% to 90% RH Non-Condensing
Rated Operating Altitude Up to 6000 ft [1829 m] at full rated current
Contaminates RoHS Compliant, CE Pollution Degree 2 (only non-conductive pollution occurs)
Storage Temperature -4°F [-20°C] to 176°F [80°C]
7 © Control Concepts Inc. 2022 www.ccipower.com 1-800-765-2799 MicroFUSION 3ø Brochure Rev. 5.8
SPECIFICATIONS, CONTINUED
COOLING SCCR - TYPE 1 COORDINATION
Din Rail/Panel Mount Forced Air / Natural Convection Frame 1Ø / 3Ø Required Fusing * SCCR Rating **
8A 10 A Fast Acting J or T 100 kA
DC POWER CONSUMPTION 16 A 20 A Fast Acting J or T 100 kA
8 - 160 A Three Phase 24 W 32 A 40 A Fast Acting J or T 100 kA
200 - 400 A Three Phase 33 W 50 A 60 A Fast Acting J or T 100 kA
Onboard Fieldbus Module Add 0.7 W 80 A 100 A Fast Acting J or T 100 kA
100 A 125 A Fast Acting J or T 100 kA
130 A 175 A Fast Acting J or T 100 kA
ENCLOSURE PROTECTIVE RATING
160 A 200 A Fast Acting J or T 100 kA
International IP 20
200 A 250 A Fast Acting J or T 100 kA
Remote Display IP 65, UL Type 1 & 12
240 A 300 A Fast Acting J or T 100 kA
320 A 400 A Fast Acting J or T 100 kA
I2t DATA (8.3 - 10 msec) 400 A 500 A Fast Acting J or T 100 kA
Frame Size Conditions I t Data
2 * Maximum fuse Amps shown above, fuses with lower Amp rating can also be used.
** To meet SCCR rating Fast acting J or T fusing must be used.
2
0 - 32 Junction Temp 125°C 16200 A s
2
50 - 160 Junction Temp 125°C 80000 A s
2
200 - 240 Junction Temp 125°C 125000 A s ANALOG SETPOINT INPUTS
2
320 - 400 Junction Temp 125°C 320000 A s 0 - 10 Vdc
Voltage (0 to 65535)
Voltage 200 kΩ
ISOLATION Impedance
Signal to Line/Load 3750 Vac minimum
Max Voltage +/- 15 Vdc
Line/Load to Ground 2500 Vac minimum Update period:
Signal to Ground 1500 Vac minimum Current 0 - 20 mA 6 ms
Mode (0 to 32767)
Network 1500 Vac minimum
USB 2500 Vac minimum Current 249 Ω
Impedance
Signal to Processor 1500 Vac minimum
Max Current +/- 31 mA or
Remote Display 2500 Vac minimum +/- 7.8 Vdc
MicroFUSION 3ø Brochure Rev. 5.8 www.ccipower.com 1-800-765-2799 © Control Concepts, Inc. 2022 8
SPECIFICATIONS, CONTINUED
RELIABILITY
Mean Time Between Failure (MTBF) Designed for 50,000 Hours
TEMPERTURE DERATING
Surrounding Air Temperature effect on the Controller
PERFORMANCE
Standard High Performance Option
Setpoint Resolution 10k 10k or 64k
Internal Control Loop 16k 64k
Resolution
Output Resolution 12k @ 50 Hz, 10k @ 60 Hz 50k @ 50 Hz, 42k @ 60 Hz
Response Time Adjustable from 50 ms to 2 s Adjustable from 50 ms to 2 s
Accuracy (Full Conduction)
Voltage 3.0% of frame rating 0.5% of frame rating
Current 3.0% of frame rating 0.5% of frame rating
Power 3.0% of frame rating 1.0% of frame rating
Output Linearity 4.0% from (5 - 100%) output range 1.0% from (5 - 100%) output range
(+10% / -15%) line voltage change will +10% to -15% line voltage change will re-
Accuracy result in a max output change of 0.5% from sult in a max output change of 0.05% from
(5 - 100%) output range (5 - 100%) output range
Output shall not change greater than 0.5% Output shall not change greater than 0.2%
Temperature Drift per degree C max over the operating per degree C max over the operating
temperature range from (5 - 100%) output temperature range from (5 - 100%) output
range range
9 © Control Concepts Inc. 2022 www.ccipower.com 1-800-765-2799 MicroFUSION 3ø Brochure Rev. 5.8
ACCESSORIES
CCI Link Communications
MicroFUSION features CCI Link™, a proprietary deterministic digital bus that enables
multiple CONTROL CONCEPTS devices to communicate with each other.
0.5 ft [0.15 m] cable 0058003 - 0050 - 005
1 ft [0.30 m] cable 0058003 - 0050 - 01
3 ft [0.91 m] cable 0058003 - 0050 - 03
5 ft [1.52 m] cable: 0058003 - 0050 - 05
15 ft [4.57 m] cable: 0058003 - 0050 - 15
25 ft [7.62 m] cable: 00580003 - 0050 - 25
REMOTE DISPLAY
When the Remote Display is panel mounted it’s easy to view and customize limits, setpoints,
and alarm conditions via the 2 Line, 16 character text display. UL-type 1 & 12 ratings, IP65
5 ft [1.52 m] cable: SMAUFUSION - RDK5
15 ft [4.57 m] cable: SMAUFUSION - RDK15
25 ft [7.62 m] cable: SMAUFUSION - RDK25
USB CABLE
15 ft [4.92 m], Micro USB cable: 0058006-0000-15
OTHER ACCESSORIES
Contact our sales department for fuse sizing and other accessory needs via website, e-mail, or phone.
MicroFUSION 3ø Brochure Rev. 5.8 www.ccipower.com 1-800-765-2799 © Control Concepts, Inc. 2022 10
MODEL NUMBERS uF3 - -
Board Type
SX = Standard
HX = High performance
Load Config
4DY = 3 phase, 2 leg 64Y = 3 phase, 4 Wire Wye
6DY = 3 phase, Delta / Wye 6ID = 3 phase, Inside Delta
Frame Style
G = 8 A (Panel Mount / DIN Rail) K = 200 - 240 A (Panel Mount)
A = 16 - 32 A (Panel Mount / DIN Rail) L = 320 - 400 A (Panel Mount)
J = 50 - 160 A (Panel Mount)
Option Board
0 = None E = Modbus TCP
I = EtherNet/IP N = PROFINET
Amp Size
8 = 8 A 130 = 130 A
16 = 16 A 160 = 160 A
32 = 32 A 200 = 200 A
50 = 50 A 240 = 240 A
80 = 80 A 320 = 320 A
100 = 100 A 400 = 400 A
Performance
Available with SX:
S = Standard
L = Adjustable Current Limit and Current Feedback
Available with HX:
L = Adjustable Current Limit, Current Feedback, Load Voltage Feedback, & Voltage Limit
P = High Performance (Includes Load Voltage Feedback, True RMS Power Control,
Current Limit, Power Limit, and High Resolution Control Loop)
I/O
0 = None 3
1 = Alarm Relay (1x Form C)
2 = General Purpose Input, Analog Input Channel 2, Pulse Width Modulation Input 3
3 = Alarm Relay and General Purpose Input, Analog Input Channel 2, Pulse Width Modulation
4 = Isolated I/O 3
5 = Isolated I/O with Alarm Relay
6 = Isolated I/O with Gen. Purpose Input, Analog Input Channel 2, Pulse Width Modulation 3
7 = Isolated I/O with Alarm Relay and Gen. Purpose Input, Analog Input Channel 2 /
Pulse Width Modulation
Retransmits
0 = None
R = Retransmits 2 (Two 16-bit analog retransmits for voltage, load resistance, current, power)
Sync
0 = None
S = Digital SYNC-GUARD™
Zero Cross Transformer Mode (ZCT)
0 = None
Z = Zero Cross Transformer Mode 2
11 © Control Concepts Inc. 2022 www.ccipower.com 1-800-765-2799 MicroFUSION 3ø Brochure Rev. 5.8
CONTROL CONCEPTS has a worldwide presence in more than 51 countries
Algeria Finland Japan Portugal Taiwan
Australia France Latvia Romania Thailand
Austria Germany Lithuania Russia Turkey
Belgium Greece Malaysia Singapore United Kingdom
Bulgaria Hong Kong Mexico Slovakia United States
Canada Hungary Morocco Slovenia Ukraine
China India The Netherlands South Korea Vietnam
Czech Rep. Indonesia New Zealand South Africa
Denmark Ireland Norway Spain
Egypt Israel Philippines Sweden
Estonia Italy Poland Switzerland
CONTROL
CONCEPTS EUROPE
NORTH ASIA
PMA Controls
AMERICA
AFRICA
SOUTH
AMERICA
PACIFIC
Sales department for North & South America: Tel. +1(952) 474 - 6200 or +1(800) 765 - 2799
Europe / Africa / Asia / Pacific Web: www.ccipower.com
Email: info@ccipower.com
www.ccipower.com
Information furnished by CONTROL CONCEPTS INC. is believed to be accurate and reliable. However, no responsibility is assumed
by CONTROL CONCEPTS INC. for its use. CONTROL CONCEPTS INC. Reserves the right to change the design or operation of the
equipment described herein and any associated controller products without notice. CONTROL CONCEPTS INC. also assumes no
responsibility for any errors that may appear in this document. Information in this document is subject to change without notice.
MicroFUSION 3ø Brochure Rev. 5.8 www.ccipower.com 1-800-765-2799 © Control Concepts, Inc. 2022 12