Desuperheater Brochure
Desuperheater Brochure
Desuperheater Brochure
Desuperheaters
Blakeborough Pipe Desuperheaters
2 Weir Control & Choke Valves Engineered valves for protection & process control www.global.weir
Blakeborough Pipe Desuperheaters
www.global.weir Weir Control & Choke Valves Engineered valves for protection & process control 3
Blakeborough Pipe Desuperheaters
Typical arrangment B
using BV985 Mark II Filter
Shown with manually regulator
operated isolating From temperature loop
valve C A
Filter Positioner
regulator Water supply SPRAY
Positioner UNIT
BV985 Mark II Variable orifice multi-nozzle
Reduced/Desuperheated
Main steam
steam
supply From pressure loop Steam
BV500 flow D
Hopkinsons BV987
control valve
parallel slide Desuperheater pipe
pressure
valve reducing
4 Weir Control & Choke Valves Engineered valves for protection & process control www.global.weir
Blakeborough Pipe Desuperheaters
• Nozzle size designed for specific application Length (mm) 80 80 80 150 150 150 150
www.global.weir Weir Control & Choke Valves Engineered valves for protection & process control 5
Blakeborough Pipe Desuperheaters
500
450
200
Graphs
T2 Required outlet temperature °C (°F) 150
50
125 10
WW = W (h - h )
75
S 1 2 50
(h - h ) 2 F
25
Sizing of low pressure pipeline Should the recommended location for the temperature
This is the recommended pipe size for BV985, BV986 and sensing point coincide with a pipe bend, then the sensing
BV988 pipeline types, or the outlet size for the BV995 point should be moved a further two metres downstream.
design for efficient desuperheating. Examples on use of the above graphs
The pipe is sized so that the steam velocity does not exceed Steam pressure 10 bara. Saturation temperature 180°C.
90m/s (300ft/s) or, for BV985, BV986, BV988 types, fall below Required outlet temperature 200°C
4.5m/s (14ft/s). The preferred velocity is 75m/s (250ft/s). Steam Inlet enthalpy 3253kJ/kg
Steam Outlet enthalpy 2829kJ/kg
Enthalpy change
424 kJ/kg
}
The minimum pipe diameter is calculated using the
Final required degrees of superheat = 200-180 = 20°C
following formulae.
Draw line from enthalpy change to intercept degrees of
W xV W xV superheat line, read off minimum distance = 15.2 metres.
D = 18.8 mm or D = 0.225 in.
M S M S
recommended distance increases as the steam saturation (T - 210) °F < T < (T - 10)
SAT WATER °F Imperial SAT
6 Weir Control & Choke Valves Engineered valves for protection & process control www.global.weir
Blakeborough Pipe Desuperheaters
www.global.weir Weir Control & Choke Valves Engineered valves for protection & process control 7
Flow Control
Dubai, UAE
Hubli, India
Bangalore, India
Singapore/Malaysia
Johannesbug, S. Africa
Weir Power & Industrial Pte Ltd - Singapore Weir Valves & Controls South Africa
15 Tukang Innovation Drive, 31 Isando Road, Johannesburg,
Singapore 618299 Gauteng 1600
T +65 63020880 T +27 (0) 11 929 2906
F +65 63020881 F +27 (0) 11 929 2925
pacificrimenq@weirgroup.com powerindustrial@weirgroup.com
®
BLAKEBOROUGH and X-STREAMTM are trademarks and/or registered trademarks of Weir Valves & Controls UK Limited. WEIR is a trademark and/or registered trademark
of Weir Engineering Services Limited. Aspects of the X-STREAMTM control valve described in this publication are protected by patents pending or granted worldwide in the
name of Weir Valves & Controls UK Limited.
Copyright © 2016 Weir Valves & Controls UK Limited. All rights reserved.