Chapters
Chapters
Chapters
=================================================================
INTRODUCTION
=================================================================
1.1 Multiterminal transmission line
The power system consists of thousands of high voltage transmission lines transmitting
electrical power between generators and load centers which represent the foundation of the
power system. The majority of transmission line construction is of overhead type and therefore,
is easily susceptible to various transient and permanent faults. These faults can lead to damage
of the line itself and can cause power system instability. It is of the utmost importance that
protective relay systems are capable of clearing all faults within the designed operating time,
and have a high degree of dependability and security.
Typically, there are three types of line configurations used within the industry. These
line configurations include radial configuration that are (a) one-terminal, (b) two-terminal, and
(c) multi-terminal of which three-terminal is possibly the most prominent multi-terminal type. It
should be noted that "terminals" in this context, refers to source terminals and not-tapped
transformer terminals or stations. The two-terminal line configuration is the most dominant type
followed by radial, and the three-terminal lines are the exceptions.
Three-terminal and other multi-terminal line construction projects are generally a trade-
off of planning economics and protection complexities, and can lead to compromises in
reliability. Two-terminal lines with long tap(s) supplying remote load from the main line may
display many of the same protection and loadability issues as three-terminal lines. These types
of configurations and those with multiple tapped transformer stations (low voltage tie breaker
closed) are beyond the scope of this discussion. However, it should be noted that some of the
same types of complexities may be experienced with these types of configurations as three-
terminal lines.
There are a number of factors that influence the decision to configure a transmission line
with three terminals, such as economics, constrained lead time, regulatory approvals, right-of-
way availability, line overloads, and system performance requirements.
• There is an economic benefit in the construction of three terminals because it avoids the
expense of all or a portion of a substation and typically reduces the transmission line miles.
• Use of three-terminal lines may be more expeditious in addressing system needs.
• Right-of-way may be limited or not obtainable for new lines and stations.
• Regulatory approvals may be problematic. There may be opposition to the construction of new
facilities and the construction of a three-terminal line may reduce the overall project impact.
• Three-terminal line configuration may mitigate the possibility of transmission line overloads
due to single contingency events. However, this is very dependent on system topology.
Types of faults:
1. Symmetrical faults
2. Unsymmetrical faults
• Type of line: overhead, cable, line length, single line, parallel line, radial, two-ended, three-
ended, etc.
• Line function and importance effect on service continuity and timing requirement for isolation
from the system.
• Coordination and compatibility with associated lines and systems.
The three most commonly used communication assisted distance protection schemes in
the industry are Direct Under-reaching Transfer Trip (DUTT), Permissive Overreaching
Transfer Trip (POTT), and Directional Comparison Blocking (DCB).
DUTT has the advantages of minimal susceptibility to power system swings. DUTT has
the disadvantage of dependency on communication channels for faults external to overlapping
coverage regions.
The POTT scheme has the advantage of being more secure, as it requires permission
from the remote relays to trip, and it can provide higher-speed tripping. It has the disadvantage
of being dependent upon the communication channel time for all line faults.
The DCB is the most trip dependable, because its operation is not dependent on the
communication channel or operation of the remote relays. It is the least secure in that a loss of
communication can result in line trips for faults not on the line.
The conventional TL protection schemes (e.g., distance relays) are based on the
fundamental frequency components of the fault signals. It is well known that the fundamental
frequency components of the local signals do not provide the sufficient information required for
discriminating between the internal and external faults for a multiterminal TL. This is due to the
fact that the infeed or outfeed currents contributed from the tap points could affect the fault-loop
impedance estimated by a distance relay. As a result, the distance relay may under-reach or
overreach depending on the transmission system configuration and parameters [6].
Chapter-1: It includes the introduction, faults in overhead transmission lines, aim of fault
classification and it also includes the contribution of this dissertation and organization of
dissertation.
Chapter-3: It presents the concept of protection of multiterminal transmission line and fault
classification technique for multiterminal transmission line. Also presents the introduction of
wavelet transform. Discrete Wavelet Transform, wavelet multi-resolution analysis, and working
of wavelet transform.
Chapter-5: It presents the conclusions of the work presented in dissertation and future scope of
this work.
LITERATURE REVIEW
=================================================================
2.1 Use of wavelet transforms analysis for fault classification
In order to detach only faulted line, it is crucial to differentiate the faults zone precisely
and indicate exact fault type with the aid of one end data only [16]. Transient current waves
generated by faults contains distinct frequency bands and to capture two bands of frequencies
from the transient current signal discrete wavelet transform db1 as a mother wavelet is used.
Fault zone is determined by using the frequencies of these two bands. The mother wavelet Haar
is used to select faulted phase. Faulted phase was classified by computing the average value of
the coefficients of each current wave. A model signal is obtained using db6 as mother wavelet.
The decision regarding fault to be external or internal was taken by determining the ratio of two
energies for the modal signal. A new scheme for the solution of the parallel transmission line
protection problems which depends on the six phase line currents and three phase line voltages
of the two parallel circuit lines at both ends is proposed [17]. Fault analysis is done by wavelet
transform. And internal faults on double circuit line are recognized by comparing current
phasors magnitudes of corresponding phases on each line. It is shown that at different loading
conditions each type of fault can be properly recognized.
Power need to be transmitted from the power station to the load centers located far away
[21]. So, the possibility of fault in the transmission lines is considerable. Here, comes the use of
signal processing in the digital distance protection. Fourier transform and wavelet transforms are
used for locating faults. Simulation is done with MATLAB/SIMULINK. Simulation result
shows that wavelet method is more robust tool to locate the faults in the transmission lines.
Further it is showed that both wavelet transform and Fourier transform methods can be used to
find the characteristics of disrupt signals irrespective of the noise levels present.
The discrete wavelet analysis has been used for the protection of high speed EHV
transmission line [22]. An algorithm for fault detection and classification based on discrete
wavelet analysis has been presented. By comparing different wavelet coefficients of all three
phase signals, type of fault is identified. And simulation is done using ATP-EMTP and
MATLAB Wavelet toolbox. Such an algorithm is presented that is not dependent not only on
fault location but also on fault inception angle and fault impedance. The algorithm is suitable,
strong and quick and this is very prolific for EHV transmission line protection.
A new approach for protection of TEED transmission lines and use wavelet transforms
for accurate detection, classification and to locate faults in TEED transmission lines is presented
[24]. The three phase currents at each terminal are decomposed at single level by using Bior2.2
as mother wavelet to obtain D1 detail coefficients. Then these detail coefficients at the three
ends of TEED transmission line are added to obtain the resultant detail coefficients which are
further compared with threshold values to detect and classify distinct types of faults in TEED
transmission lines. The use of Fuzzy logic and neural network for protection of double circuit
series compensated transmission line is described [25]. Fuzzy logic and Neural Network are
used for accurate decision making and to estimate the actual power system condition
respectively, which increases the selectivity of protection system that further improves the
reliability of power system. Effect of mutual zero-sequence coupling, series compensation and
fault resistance is studied. The effect of the mutual coupling of parallel circuit and of series
capacitor impedance on the relays accuracy depends on actual condition of power system.
Ultimately, it is shown that with change in power system condition, the relay sensitivity is
reduced to almost zero with decision making system of Fuzzy logic.
The protection scheme of double circuit transmission line based on artificial neural
network (ANN) has been proposed [28]. Three stages are involved in this scheme to detect and
classify different types of faults. Data from one end of the double circuit transmission line has
been utilized to calculate the wavelet coefficients. The primary protection is provided to entire
transmission line by using one end data only. For forward and backward adjacent transmission
line, back up protection is provided. This technique improves the first zone reach setting up to
99% of the length of line for protection of transmission line.
A scheme based on wavelet transform for fault classification is proposed [29]. Currents
samples from the three lines are used to calculate dW Iabc. For different fault inception angles,
different fault locations, and different fault distances and for different fault parameters
simulation is done by EMTP software. It is shown that magnitude of wavelet transform is
valuable to set threshold to discriminate between different types of faults hence to classify the
faults.
The Back propagation neural network consists of three layers: an input layer with three
neurons, a hidden layer with two neurons and an output layer with two neurons. In the figure,
we see that the output of a neuron in a layer goes to all neurons in the following layer and each
neuron has its own weights. Initially the weights of the input layer are assumed to be 1 for each
input. The output of the back propagation neural network is reached by applying input values to
the input layer, passing the output of each neuron to the following layer as input.
The number of neurons in the input layer depends on the number of possible inputs we
have, while the number of neurons in the output layer depends on the number of desired outputs.
The number of hidden layers and how many neurons in each hidden layer cannot be well
defined in advance, and could change per network configuration and type of data. In general the
addition of a hidden layer could allow the network to learn more complex patterns, but at the
same time decreases its performance [32]. Ideally, we could start a network configuration using
a single hidden layer, and add more hidden layers if we notice that the network is not learning as
well as we like.
The Back propagation training algorithm [33] could be summarized as follows: The
Input data sample is first presented to the network and then the network’s output taken from the
output layer is compared with the desired output and the error is calculated in each output
neuron. And now for each neuron, a scaling factor called the local error is calculated which
indicates how much higher or lower the output must be adjusted to match the desired output.
A multiterminal TL is a line which ends at more than one terminal with sources behind
them and taps at the other locations of the line. Such a configuration poses some difficulties
from the protection point of view due to the possibility of multiple sources feeding short-circuit
faults [34].
The differential relaying scheme using a communication link between the TL ends could
provide a secure protection for multiterminal transmission lines (TLs) [2]–[4]. However, the
reliability of such a protection scheme depends upon the reliability of the communication link.
Moreover, the measurement infrastructure of the tapping lines could be poor or there could be
no communication channel for sending measurements from the far end of the tapping lines [4].
Therefore, a protection algorithm, which is based only on the local information obtained at the
relay bus, is greatly useful for the protection of multiterminal TLs. Even when a quite reliable
communication-based technique is employed for the protection of a TL, a second relay, which
makes the decision only based on the local information, would be helpful to increase the
reliability of the protection scheme.
The conventional TL protection schemes (e.g., distance relays) are based on the
fundamental frequency components of the fault signals. It is well known that the fundamental
frequency components of the local signals do not provide the sufficient information required for
discriminating between the internal and external faults for a multiterminal TL. This is due to the
fact that the infeed or outfeed currents contributed from the tap points could affect the fault-loop
impedance estimated by a distance relay. As a result, the distance relay may under-reach or
overreach depending on the transmission system configuration and parameters [6].
The traveling-wave positional protection technique uses polarities and time intervals
between arriving waves at the relay bus to estimate the fault location [9], [10]. Nevertheless, this
technique cannot be easily employed for protection of multiterminal lines due to the reflections
of traveling waves at the tap points.
Extensive simulation studies are carried out using the power system simulation toolbox
software MATLAB to evaluate the performance of the proposed algorithm under different
conditions. The current transformers (CTs) and capacitor voltage transformers (CVTs) are also
modeled precisely. The obtained results confirm that the proposed algorithm provides a
satisfactory and reliable scheme for the protection of the multiterminal TLs even for a small
amount of bus equivalent capacitance and variation of the power system parameters. The
proposed technique considerably improves the first zone coverage of the protective scheme and
covers almost the total length of the multiterminal TL under protection.
PROPOSED APPROACH
=================================================================
3.1 Fault classification scheme for Multiterminal transmission line
3.1.1 Objective of system
The dyadic wavelet transform (DWT) is used to decompose the fault signals into
different frequency bands. Then, the signal spectral energy within each frequency band is
computed. The Artificial Neural Network (ANN) is used to classify the faults into two
categories of internal and external faults according to their frequency spectrum.
For analyzing the frequency contents of any signal, FT can be applied efficiently.
Though, if the Fourier transform of the entire time axis is taken, then we cannot notify that at
what instant a specific frequency rises. Short Time Fourier Transform (STFT) which uses a
sliding window can also used to find information of both frequency and time. However, window
length limits the resolution of frequency. So, the Wavelet transform is the ultimate solution of
these problems. Small wavelets having limited duration are considered in wavelet transform.
Figure 3.1. Block diagram of fault classification scheme for multiterminal transmission line
The WT can detect the low frequency and high frequency components precisely. One of
the main properties of the WT that it has the great ability to locate the signals short-time high
frequency features and determine the low frequency performance.
The convolution of the signal f (t), which is under analysis, is taken with a wavelet 𝜓, to
obtain wavelet transform [41].
∞
C (Scale, position) = ∫ f(t)ψ (Scale, position, t) dt
−∞
Where,
𝜓 belongs to a special wavelets family to compare with f(t) is known as “mother wavelet”.
There are various types of wavelets i.e. Haar, Symlets, Meyer, Daubechies, and Discrete
Meyer. To analyze the portion of the signal which is not known using convolution, 𝜓 is selected
i.e. WT can detect if under a determined position and scale, the analyzed signal intimately
correlated with 𝜓. Basically, wavelet transform is used to evaluate the non-stationary signals,
those frequency response change in time.
Let V(t) is the original signal obtained from a measuring device. V(t) is decomposed into
detail and approximation. cA1 and cD1 are the decomposed signals of level 1 in the multi
resolution technique. Where, cA1 is the approximation of the original signal and the cD1 is the
detail version of the original signal. cA1 and cD1 are defined as given in equations (4.2) and
(4.3) respectively [46].
Where,
Ld is the low-pass filter and,
Hd is the high-pass filter.
These filters are related to mother wavelet 𝜓. High frequency components of the signal
are contained in cD1 whereas cA1 contains the low frequency components of the signal. When
the original signal V(t) is passed through the low pass and high pass filters, it gets decomposed
into cA1 and cD1 coefficients of the signal. Here the cA1 and cD1 are level1 coefficients.
Further approximation cA1 is decomposed into cA2 and cD2 coefficients of the signal which
are the level 2 coefficients. And this procedure is repeated again and again until the required
level is obtained for a particular application as shown in Figure 3.3.
Neural networks or more specifically, artificial neural networks are mathematical models
inspired from our understanding of biological nervous systems. They are attractive as
computation devices that can accept a large number of inputs and learn solely from training
samples. As mathematical models for biological nervous systems, artificial neural networks are
useful in establishing relationships between inputs and outputs of any kind of system.
1. Neurons are the elementary units in a nervous system at which information processing occurs.
2. Incoming information is in the form of signals that are passed between neurons through
connection links.
3. Each connection link has a proper weight that multiplies the signal trans- mitted.
4. Each neuron has an internal action, depending on a bias or fring threshold, resulting in an
activation function being applied to the weighted sum of the input signals to produce an output
signal.
Thus, when input signals x1, x2, . . . , xn reach the neuron through connection links with
associated weights w1,w2, . . .,wn, respectively, the resulting input to the neuron, called the net
input, is the weighted sum ∑𝑛𝑖=1 𝑤𝑖. 𝑥𝑖 . If the firing threshold is b and the activation function is f,
then the output of that neuron is
𝑦 = 𝑓(∑𝑛𝑖=1 𝑤𝑖. 𝑥𝑖 )
In the first computational model for artificial neurons, proposed by McCulloch and Pitts
[43], outputs are binary, and the function f is the step function.
𝑛 1 𝑖𝑓 ∑ 𝑤𝑖. 𝑥𝑖 ≥ 𝑏
𝑖=1
𝑓(∑(𝑤𝑖. 𝑥𝑖 − 𝑏) = 𝑛
𝑖=1
0 𝑖𝑓 ∑ 𝑤𝑖. 𝑥𝑖 < 𝑏
{ 𝑖=1
We will consider here only feed-forward neural networks, that is, information propagates
only forward as indicated by the direction of the arrows. Mathematically speaking, a
feedforward neural network is an acyclic weighted, directed graph. Viewing artificial consists of
an input layer of input nodes and one output layer consisting of
neurons. This is referred to as a single-layer neural network because the input layer is not a layer
of neurons, that is, no computations occur at the input nodes. This single-layer neural network is
called a perceptron.
A multi-layer neural network is a neural network with more than one layer of neurons.
Note that the activation functions of the different neurons can be different. The neurons from
one layer have weighted connections with neurons in the next layer, but no connections between
neurons of the same layer. A two-layer neural network is depicted in Figure 3.8. Note that
activation functions of different neurons can be different. The input layer (or layer 0) has n+ 1
node, the middle layer, called the hidden layer, has p nodes, and the output layer has m nodes.
This is called an n-p-m Neural network. Neurons (nodes) in each layer are somewhat similar.
Neurons in the hidden layer are hidden in the sense that we cannot directly observe their output.
From input patterns, we can only observe the output patterns from the output layer.
Off course, a multi-layer neural network can have more than one hidden layer. The two-
layer neural network depicted in Figure 3.8 is a typical multi-layer perceptron (MLP), a
multilayer neural network whose neurons perform the same function on inputs, usually a
composite of the weighted sum and a differentiable nonlinear activation function, or transfer
function, such as a hyperbolic tangent function. Multi-layer perceptrons are the most commonly
used neural network structures for a broad range of applications.
Unsupervised learning uses no external teacher and is based upon only local
information. It is also referred to as self-organization, in the sense that it self-organizes data
presented to the network and detects their emergent collective properties. Paradigms of
unsupervised learning are Hebbian learning and competitive learning.
From Human Neurones to Artificial Neuron Esther aspect of learning concerns the
distinction or not of a separate phase, during which the network is trained, and a subsequent
operation phase. We say that a neural network learns off-line if the learning phase and the
operation phase are distinct. A neural network learns on-line if it learns and operates at the same
-sigmoid f a 1 1 exp(a)
For linear units, the output activity is proportional to the total weighted output.
For threshold units, the output are set at one of two levels, depending on whether the total input
is greater than or less than some threshold value.
For sigmoid units, the output varies continuously but not linearly as the input changes. Sigmoid
units bear a greater resemblance to real neurons than do linear or threshold units, but all three
must be considered rough approximations.
We can teach a three-layer network to perform a particular task by using the following
procedure:
1. We present the network with training examples, which consist of a pattern of activities for the
input units together with the desired pattern of activities for the output units.
2. We determine how closely the actual output of the network matches the desired output.
3. We change the weight of each connection so that the network produces a better
approximation of the desired output.
In order to train a neural network to perform some task, we must adjust the weights of
each unit in such a way that the error between the desired output and the actual output is
reduced. This process requires that the neural network compute the error derivative of the
weights (EW). In other words, it must calculate how the error changes as each weight is
increased or decreased slightly. The back propagation algorithm is the most widely used method
for determining the EW.
Since backpropagation uses the gradient descent method, one needs to calculate the
derivative of the squared error function with respect to the weights of the network. Assuming
one output neuron, the squared error function is:
,
where
is the squared error,
is the target output for a training sample, and
y is the actual output of the output neuron.
.
The input to a neuron is the weighted sum of outputs of previous neurons. If the
neuron is in the first layer after the input layer, the of the input layer are simply the
inputs to the network. The number of input units to the neuron is . The variable
denotes the weight between neurons and .
In the last term of the right-hand side, only one term in the sum depends on , so that
.
The derivative of the output of neuron with respect to its input is simply the partial derivative
of the activation function (assuming here that the logistic function is used):
This is the reason why backpropagation requires the activation function to be differentiable.
However, if is in an arbitrary inner layer of the network, finding the derivative with
respect to is less obvious.
Considering as a function of the inputs of all neurons receiving input
from neuron ,
and taking the total derivative with respect to , a recursive expression for the derivative is
obtained:
Therefore, the derivative with respect to can be calculated if all the derivatives with respect
to the outputs of the next layer – the one closer to the output neuron – are known. Putting it
all together:
with
To update the weight using gradient descent, one must choose a learning rate. The change
in weight, which is added to the old weight, is equal to the product of the learning rate and the
gradient, multiplied by -1:
The -1 is required in order to update in the direction of a minimum, not a maximum, of the error
function.
The calculated signal energy at the defined frequency bands is normalized using the
signal energy at the fourth frequency band, and is used as the ANN inputs to discriminate
between internal and external faults. The ANN is well capable of constructing appropriate
hyperplanes for clustering the input data in a high dimension space.
The processing burden of the proposed algorithm is higher than that of some
conventional techniques employed in the impedance-based relays. Nevertheless, considering the
advancements in the digital technology and processing speed, this is not a serious problem.
Since the proposed algorithm uses a 1/4-cycle sliding data window to calculate the signal
spectrum energy, if an appropriate processor is used, the operation time of the proposed
algorithm would be about 1/4 cycle of the power system frequency.
This dissertation improves the performance of distance relay by introducing line traps for
providing discrimination between internal fault and external fault. Due to line trap impedance
relay can trip during internal fault only. It means that impedance distance relay protect the main
transmission line when fault occurs on that line, and not trip the line when external fault occur
in outside protected transmission line.
Protection is the art and science of the application of devices that monitor the power line
currents and voltages (relays) and generate signals to de-energize faulted sections of the power
network by circuit breakers. Goal is to minimize damage to equipment and property that would
be caused by system faults, if residues, and maintain the delivery of electrical energy to the
consumers. Many types of protective relays are used to protect power system equipments, they
are classified according to their operating principles; over current relay senses the extra (more
than set) current considered dangerous to a given equipment, differential relays compare in and
out currents of a protected equipment, while impedance relays measure the impedance of the
protected piece of planet. For a good performance of a relay in a power system it must have the
following characteristics; dependability, security, selectivity, sensitivity and speed.
Distance Relays: Distance relays, as the name sounds, should measure distance. In fact this is
true, as in case of transmission line, distance relay measures the impedance between the relay
point and the fault location. This impedance is proportional to the length of the conductor, and
hence to the distance between the relaying point and the fault.
Principle of operation: The basic principle as illustrated in figure 3.10, involves the division of
the voltage at the relaying point by the measured current. The apparent impedance is compared
with the reach point impedance. If the measured impedance is less than the reach point
impedance, it is assumed that a fault exists on the line between the relay and the reach point.
The reach point of the relay is the point along the line impedance locus that is intersected by the
The relay is connected at position, R and receives a secondary current, iF, equivalent to a
primary fault current, IF. The secondary voltage, VF, is equivalent to the product of the fault
current “IF” and impedance of the line up to the point of fault, ZF. The operating torque of this
relay is proportional to the fault current “IF”, and its restraining torque is proportional to the
voltage “VF”. Taking into account the number of turns of each coil, there will be a definite ratio
of V/I at which the torque will be equal. This is the reach point setting of the relay. The relay
will operate when the operating torque is greater than the restraining torque. Thus any increase
in current coil ampere-turns, without a corresponding increase in the voltage coil ampere-turns,
will unbalance the relay. This means the V/I ratio has fallen below the reach point. Alternatively
if the restrain torque is greater than the operating torque, the relay will restrain and its contacts
will remain open. In this case the V/I ratio is above the reach point. The reach of a relay is the
distance from the relaying point to the point of fault. Voltage on the primary of voltage
transformer, VT, is
Zones of protection: Basic distance protection will comprise instantaneous directional Zone 1
protection and one or more time delayed zones. Numerical distance relays may have up to five
zones, some set to measure in the reverse direction. Numerical relays usually have a reach
setting of up to 85% of the protected line impedance for instantaneous Zone 1 protection. The
resulting 15% safety margin ensures that there is no risk of the Zone 1 protection over-reaching
the protected line due to errors in the current and voltage transformers, inaccuracies in line
impedance data provided for setting purposes and errors of relay setting and measurement of the
distance protection must cover the remaining 15% of the line.
The reach setting of the Zone 2 protection should be at least 120% of the protected line
impedance. In many applications it is common practice to set the Zone 2 reach to be equal to the
protected line section +50% of the shortest adjacent line. Zone 3 reach should be set to at least
1.2 times the impedance presented to the relay for a fault at the remote end of the second line
section. Typical reach for a 3-zone distance protection are shown in Figure 3.11.
Residual factor: The measuring element of the distance relay is principally laid out such that
for each fault type the line impedance of the fault loop is determined. In three phase system the
zone-1 of the relay will have six elements responsible for detecting both phase and earth faults.
For phase faults elements, the difference between the two relevant phase signals are used, e.g. a-
b elements is supplied with samples of Va – Vb voltage and Ia - Ib current. For earth elements,
the relevant phase voltage is supplied e.g. Va, but the corresponding current is residually
compensated. The earth faults compensation factor may be calculated considering the sequence
networks connection for the phase A-to-ground fault on a transmission line. Table indicates
calculation formula for phase and line to line faults. In order for the relay to be correctly
operated, residual factor shall be introduced as shown in the following equations
𝑉𝑘
𝑅𝑘 =
𝐼𝑘 + 3 𝑅𝑒. (𝐾0). 𝐼𝑜𝑘
𝑉𝑘
𝑋𝑘 =
𝐼𝑘 + 3. 𝐼𝑚(𝐾𝑜). 𝐼0𝑘
Where; K0, is the compensation factor
I0, is zero sequence current
Vk, Ik are the sampled voltage and current respectively
Effect of fault resistance on relay coverage: The earth fault resistance reduces the effective
earth-fault reach of a mho Zone 1 element to such an extent that the majority of faults are
detected in Zone 2 time. Figure 3.12 illustrates the effect of arc resistance on the relay reach.
The effect of fault resistance on the reach of distance relays is better discussed with the
simulation results.
All circuit breaker systems have common features in their operation, although details
vary substantially depending on the voltage class, current rating and type of the circuit breaker.
The circuit breaker must detect a fault condition; in low voltage circuit breakers this is
usually done within the breaker enclosure. Circuit breakers for large currents or high voltages
are usually arranged with protective relay pilot devices to sense a fault condition and to operate
the trip opening mechanism. The trip solenoid that releases the latch is usually energized by a
separate battery, although some high-voltage circuit breakers are self-contained with current
transformers, protective relays and an internal control power source.
Once a fault is detected, contacts within the circuit breaker must open to interrupt the
circuit; some mechanically-stored energy (using something such as springs or compressed air)
contained within the breaker is used to separate the contacts, although some of the energy
required may be obtained from the fault current itself. Small circuit breakers may be manually
operated; larger units have solenoids to trip the mechanism, and electric motors to restore
energy to the springs.
The circuit breaker contacts must carry the load current without excessive heating, and
must also withstand the heat of the arc produced when interrupting (opening) the circuit.
Contacts are made of copper or copper alloys, silver alloys and other highly conductive
materials. Service life of the contacts is limited by the erosion of contact material due to arcing
while interrupting the current. Miniature and molded-case circuit breakers are usually discarded
When line traps are installed at the TL ends, most of the fault-induced HF components
are confined to the faulty transmission line regardless of configuration of the primary system
switchgear. As a result, a protective algorithm based on the spectral energy of the fault-induced
transients can well discriminate between internal and external faults. In other words, the line
trap provides the required high impedance at the high frequencies so that the reflection and
refraction coefficients of the TL termination points are not affected considerably by variation of
the substation parameters.
It should be considered that, in practice, there are some limitations in selection of the
values of the line trap parameters. Since the main coil carries the TL current, a high inductance
main coil could develop into a physically very large dimension.
Fig. 3.13 depicts the designed line trap installed at the protected TL ends. In this figure L1,R1
and C1, and denote the inductance, resistance, and the equivalent stray capacitance of the main
coil, R2 and C2 denote the resistor and tuning capacitor, respectively.
Figure 3.13. Circuit diagram and parameters of the designed line trap
It should be noted that, in practice, CVTs are also installed at the TL ends to measure the phase
voltages. CVTs are installed after the line trap at the TL side. Thus, in this Proposed approach,
CVTs are appropriately modeled to consider their influence on the frequency characteristics of
the line trap.
The design of potential transformer is quite similar to that of a power transformer but the
loading of potential transformer is always small, sometimes only a few volt-ampere. The
secondary winding is design so that a voltage of 100 to 120V is delivered to the instrument load.
The normal secondary voltage rating is 110V.
(3) Transformer 2; Power = 80e6 VA; Primary voltage = 34.5e3 V; Secondary voltage = 400 V;
Frequency = 50Hz
(4) Transformer 3; Power = 80e3 VA; Primary voltage = 34.5e3 V; Secondary voltage = 400 V;
Frequency = 50 Hz
(5) Transformer 4; Power = 80e3 VA; Primary voltage = 400 V; Secondary voltage= 34.5e3 V;
Frequency = 50Hz
(6) Transformer 5; Power = 80e3 VA; Primary voltage = 34.5e3 V; Secondary voltage = 400 V;
Frequency = 50Hz
(7) Transformer 6; Power = 100e6 VA; Primary voltage = 153e3 V; Secondary voltage = 34.5e3
V; Frequency = 50Hz
(8) Transformer 7; Power = 100e6 VA; Primary voltage = 153e3 V; Secondary voltage = 34.5e3
V; Frequency = 50Hz
(12) Load 1 ; Phase to phase voltage = 400 V; Frequency = 50 Hz; Active power = 0.1 W;
Inductive reactive power = 3.5 Positive VAR; Capacitive reactive power = 2.4 Negative VAR
(15) Transmission line model Phase to phase voltage 34.5 KV; Frequency = 50 Hz; Zone1 (AB)
= 50Km; Zone2 (BC) = 100Km; Zone3 (CD) = 60Km; Zone4 (EF) = 70 Km
The specification of each blocks in Discrete Wavelet Transform subsystem are following way:
(1)DWT block: Mother wavelet = Daubechies; Wavelet order = 2; Number of levels = 5; tree
structure = symmetric; output = multiple ports
(2)Buffer: output buffer size (per channel) = 128; buffer overlap = 0; initial condition = 0
Figure
4.7. DWT detail blocks in simulation model
Figure 4.10. Training information selection window for Neural Network training
Step (4): Observe the output of Neural Network for faultcase07 input.
Step (5): Again select another input data for testing Neural Network output for example
faultcase52.
The main function of the line trap is to present high impedance at the carrier frequency
band while presenting negligible impedance at the power system frequency. The high
impedance is required to reduce the carrier signal attenuation due to the division among the
several transmission lines terminated at the same bus.
Figure 4.23 depict the frequency spectrum of combine 3 phase current signal measured
at the relay location decomposed by DWT for case of external fault. In that case, an external
fault occurs at 30 km from bus B on transmission line AB. As can be seen, for external fault,
most of high frequency (HF) components involved in the current signal at frequencies above 20
kHz are not permitted to enter the transmission line under the protection.
Figure 4.23. Frequency spectrum of 3 phase current signal for an external fault at 30km from bus B on transmission
line AB.
Figure 4.24. Frequency spectrum of phase A current signal for an external fault at 30km from bus B on
transmission line AB.
Figure 4.26. Frequency spectrum of phase C current signal for an external fault at 30km from bus B on
transmission line AB.
Case (2): Internal LLG (ABG) fault at 75km from bus B on transmission line BE.
Figure 4.28. Frequency spectrum of phase A current signal for an internal fault at 75km from bus B on transmission
line BE.
Figure 4.30. Frequency spectrum of phase C current signal for an internal fault at 75km from bus B on transmission
line BE
As can be seen, the maximum fault classification accuracy is 93.63% for all the faults
cases. Table 4.1 present some of the fault cases for which the design ANN is not able to
correctly classify the fault. In this table, the fault location is given from bus B. Most of the
misclassified faults are those which occur very close to the remote buses C or E. Indeed, it is
difficult to distinguish between faults occurring close to the remote buses on the TL under
protection or on the next TLs.
Table 4.1. Results from Neural Network for different faults condition
Fault Ground
Fault Location resistance Resistance ANN ANN Target
Sr.No. type (km) (Ω) (Ω) Output error output
1 AG AB(30) 0.01 0.01 -1 -2.92E-07 -1
2 BG AB(30) 0.2 0.01 -0.9998 -0.0002 -1
3 CG AB(30) 0.25 0.01 -1 0 -1
4 ABG AB(30) 0.3 0.01 -1 -5.74E-10 -1
5 BCG AB(30) 0.2 0.01 -1 -1.36E-11 -1
6 ACG AB(30) 2 0.01 -1 0.00E+00 -1
7 ABCG AB(30) 0.3 0.01 -1 0.00E+00 -1
8 ABC AB(30) 5 0.01 -1 0.00E+00 -1
9 AG AB(45) 0.2 0.01 -1 -4.19E-13 -1
To increase the separating margin of the trained SVMs in discrimination between the
two classes of internal and external faults, in this paper, the training data set is modified so that
it does not contain fault cases occurring near the remote buses on the three-terminal TL under
In other words, by reducing the protected zone reach, the separating margin between the
signatures of internal and external faults increases which prevents the relay mal-operation for
external faults at the beginning of the next TLs.
4.6 Discussion
The performance of the proposed technique was further investigated using many other
fault cases. It was found that desirably the proposed relay never operates for external faults at
the beginning of the next TLs. However, as designed, some internal faults at the end parts of the
TL and some single-phase-to ground faults occurring at fault resistance may not be detected by
the trained ANN.
For faults occurring at the end part of the TL, the relay installed at the remote bus
operates quickly because the fault is seen as a close-up fault by this relay. Consequently, the
remote circuit breaker (CB) opens to isolate the fault. A supplementary algorithm based on
detecting the open switching of the remote CB can be used to cover the total length of the
protected TL [47]–[49]. It must be considered that if the conventional distance relay is used to
protect the three-terminal TL under study, its first protection zone could not be extended more
than 5–10 km over the tap point (i.e., only 50–54% of the CD transmission line is covered in the
first zone). This is due to the fact that the length of the tapping line is usually small and,
therefore, the reach of the first protection zone of the distance relay should be selected so that it
does not react for faults beyond the bus at the end of tapping line. Mean while, the proposed
In practice, short-circuit faults often occur when the instantaneous voltage is high.
Therefore, in most conditions, the designed classifier is well capable of identifying internal
faults occurring on the protected TL. For some rare conditions in which an internal fault occurs
at a fault resistance, similar to the other HF-based protection techniques, the designed classifier
may not be able to identify the fault because the generated HF transients are too small.
The performed simulation studies show that the ANN classifier provides the most
accurate result for discrimination between the internal and external faults. Using this algorithm,
the reach of the first protected zone can be extended so that only a very small portion at the
remote-end side is not covered by the proposed relay. For this small portion, a supplementary
algorithm based on the open switching of the remote CB can be used. This is done to maximize
the separating margin between the two classes of internal and external faults and provide the
required security for the protection scheme. The ANN classifier is able to reliably identify the
internal faults up to 96% of the TL length. The proposed algorithm provides high noise
immunity and works well even under changes in the power system parameters and conditions
due to the installation of appropriately designed line traps at the ends of the protected TL.
Based on this dissertation, the following area of work is suggested for further exploration:
[1] Mohammad, A.B., “Travelling Waves for Finding the Fault Location in Transmission
Lines,” Journal Electrical and Electronic Engineering, vol. 1, no. 1, pp.1-19, 2013.
[2] R. K. Aggarwal and A. T. Johns, “Digital differential relaying scheme for teed circuits
based on voltage and current signal comparison,” Proc. Inst. Elect. Eng., Gen., Transm.
Distrib., vol. 137, no. 6, pp. 414–423, Nov. 1990.
[3] R. K. Aggarwal and A. T. Johns, “The development of a new high speed 3-terminal line
protection scheme,” IEEE Trans. PowerDel., vol. PWRD-1, no. 1, pp. 125–134, Jan.
1986.
[4] H. Gao and P. A. Crossley, “A new current differential protection scheme for teed
transmission lines,” presented at the Power Eng. Soc. Gen. Meeting, Montreal, QC,
Canada, Oct. 2006.
[6] J. Daniel, R. K. Aggarwal, and A. T. Johns, “Three terminal line protection based on a
superimposed component impedance relay,” Proc. Inst. Elect. Eng., Gen., Transm.
Distrib., vol. 140, no. 6, pp. 447–454, Nov. 1993.
[7] V. Pathirana and P. G. McLaren, “A hybrid algorithm for high speed transmission line
protection,” IEEE Trans. Power Del., vol. 20, no. 4, pp. 2422–2428, Oct. 2005.
[8] W. Chen, O. P. Malik, X. Yin, D. Chen, and Z. Zhang, “Study of wavelet-based ultra
high speed directional transmission line protection,” IEEE Trans. Power Del., vol. 18,
no. 4, pp. 1134–1139, Oct. 2003.
[9] D. J. Zhang, Q. Henry Wu, Z. Q. Bo, and B. Caunce, “Transient positional protection of
transmission lines using complex wavelets analysis,” IEEE Trans. Power Del., vol. 18,
no. 3, pp. 705–710, Jul. 2003.
[11] N. Zhang and M. Kezunovic, “Transmission line boundary protection using wavelet
transformand neural network,” IEEE Trans. Power Del., vol. 22, no. 2, pp. 859–869,
Apr. 2007.
[13] R. K. Aggarwal, A. T. Johns, and Z. Q. Bo, “Non-unit protection technique for EHV
transmission systems based on fault generated noise part 2: Signal processing,” Proc.
Inst. Elect. Eng., Gen., Transm. Distrib., vol. 141, no. 2, pp. 141–147, Mar. 1994.
[15] D. Xingli, G. Yaozhong, and D. Xinzhou, “A wavelet and traveling waves based non-
communication high speed transmission line protection,” Autom. Elect. Power Syst.,
vol. 10, 2001.
[16] Sharma, R., Ahmad, A. and Shailendra, K. S., “Protection of Transmission Lines
using Discrete Wavelet Transform,” International Journal of Innovative Technology and
Exploring Engineering (IJITEE), vol. 3, Issue-1, June, 2013.
[17] Osman, A.H. and Malik, O.P., “Protection of Parallel Transmission Lines Using Wavelet
Transform” IEEE Transactions on power delivery, vol. 19, no. 1, 2004.
[19] Pandya, V. J. and Kanitkar, S.A., "A novel unit protection scheme for protection of
series compensated transmission line using wavelet transform," Power Engineering
Conference, 2007.
[20] Perez, F.E., Orduna, E. and Guidi, G., “Adaptive wavelets applied to fault classification
on transmission lines,” IET Generation, Transmission and Distribution, vol. 5, no. 7, pp.
694–702, 2011.
[21] Roshni, U., Niranjan, V., Prakash, C.D. and Srinivas, R., “Location of Faults In
Transmission Line Using Fast Fourier Transform And Discrete Wavelet Transform In
Power Systems,” Undergraduate Academic Research Journal (UARJ), vol. 1, Issue-1,
pp. 84-86, 2012.
[22] Solanki, M. and Song, Y.H., “Transient Protection of EHV Transmission Line Using
Discrete Wavelet Analysis,” Power Engineering Society General Meeting, IEEE, vol. 3,
pp. 1868-1873.
[24] Samapth, B. and Vijayabhaskar, K., “Wavelet Based Protection Schemes for TEED
Tramission Circuits,” International Journal of Engineering Research and Applications
(IJERA), vol. 2, no. 6, pp.931-940, Nov. - Dec., 2012.
[25] Nidhi, B., Kumar, R. and Sinha, A., “Neural Network and Fuzzy Logic Based Protection
of Series Compensated Double Circuit Transmission line” International Journal of
Engineering Research and Applications (IJERA), vol. 3, no. 1, pp.1545- 1551, 2013.
[26] Andrade, L.D. and de Leao, T.P., "Impedance-based fault location analysis for
transmission lines," Transmission and Distribution Conference and Exposition (T&D),
2012 IEEE PES, pp. 1-6, May, 2012.
[27] Saravanababu, K., Balakrishnan, P. and Sathiyasekar, K., “Transmission Line Faults
Detection, Classification, and Location Using Discrete Wavelet Transform,”
International Conference on Power, Energy and Control (ICPEC), pp. 233-238, 2013.
[28] Yadav, A. and Swetapadma, A., “Improved first zone reach setting of artificial neural
network-based directional relay for protection of double circuit transmission lines” IET
Generation, Transmission and Distribution., vol. 8, Issue-3, pp. 373-388, 2014.
[29] Youssef, O.A.S., “Fault classification based on wavelet transform,” Transmission and
Distribution Conference and Exposition IEEE/PES, vol. 1, pp. 531-536, 2001.
[30] Reddy, R.B., Kumar, M.V., Suryakalavathi, M. and Prasanth Babu, C., "Fault detection,
classification and location on transmission lines using wavelet transform," Electrical
Insulation and Dielectric Phenomena, pp.409-411, Oct., 2009.
[31] Robi Polikar, “The Engineer’s ultimate guide to Wavelet analysis: The Wavelet
Tutorial”, http://users.rowan.edu/~polikar/WAVELETS/WTtutorial.html
[34] S. M. Brahma, “New fault-location method for a single multiterminal transmission line
using synchronized phasor measurement,” IEEE Trans. Power Del., vol. 21, no. 3, pp.
1148–1153, Jul. 2006.
[36] Line Traps for Ac power Systems, IEC Standard 60353 Ed. 2.0 b, , 1989.
[37] “Line Traps, Product Catalog” Areva T&D Ltd. Co., India. [Online]. Available:
http://arevausitr.com
[38] Youssef, O.A.S., “Fault classification based on wavelet transform,” Transmission and
Distribution Conference and Exposition IEEE/PES, vol. 1, pp. 531-536, 2001.
[39] Shaaban, S.A. and Hiyama, T., “Transmission Line Faults Classification Using Wavelet
Transform,” 14th International Middle East Power Systems Conference (MEPCON’10),
Cairo University, Egypt, pp. 532-537, December, 2010.
[40] Saravanababu, K., Balakrishnan, P. and Sathiyasekar, K., “Transmission Line Faults
Detection, Classification, and Location Using Discrete Wavelet Transform,”
International Conference on Power, Energy and Control (ICPEC), pp. 233-238, 2013.
[41] Samapth, B. and Vijayabhaskar, K., “Wavelet Based Protection Schemes for TEED
Tramission Circuits,” International Journal of Engineering Research and Applications
(IJERA), vol. 2, no. 6, pp.931-940, Nov. - Dec., 2012.
[42] Martín, F. and Aguado, J.A., “Wavelet-Based ANN Approach for Transmission Line
Protection,” IEEE Transactions on power delivery, vol. 18, no. 4, pp. 1572-1574, Oct.,
2003.
[43] Megahed, A.I., Monem Moussa, A. and Bayoumy, A.E., "Usage of wavelet transform in
the protection of series-compensated transmission lines," Power Delivery, IEEE
Transactions on, vol. 21, no. 3, pp. 1213-1221, July, 2006.
[44] Chanda, D., Kishore, N.K. and Sinha, A.K., “Application of Wavelet Multi-resolution
Analysis for Classification of Faults on Transmission lines” Conference on convergent
Technologies for the Asia-Pacific Region, vol. 4, pp.1464 – 1469, 2003.
[45] Roshni, U., Niranjan, V., Prakash, C.D. and Srinivas, R., “Location of Faults In
Transmission Line Using Fast Fourier Transform And Discrete Wavelet Transform In
Power Systems,” Undergraduate Academic Research Journal (UARJ), vol. 1, Issue-1,pp.
84-86, 2012.
[46] Samapth, B. and Vijayabhaskar, K., “Wavelet Based Protection Schemes for TEED
Tramission Circuits,” International Journal of Engineering Research and Applications
(IJERA), vol. 2, no. 6, pp.931-940, Nov. - Dec., 2012.
[48] Z. Q. Bo, “Adaptive non-communication protection for power lines BO scheme 1- the
delayed operation approach,” IEEE Trans. Power Del., vol. 17, no. 1, pp. 85–91, Jan.
2002.
[49] Z. Q. Bo, “Adaptive non-communication protection for power lines BO scheme 2- the
instant operation approach,” IEEE Trans. Power Del., vol. 17, no. 1, pp. 92–96, Jan.
2002.
WEBSITES VISITED
Sr No. d1 d2 d3 d4 d5 Target
1 14.3168 8.5336 4.5292 2.8019 -0.557 -1
2 16.5785 11.869 5.0882 3.6668 -1.411 -1
3 25.8944 15.4392 8.1167 4.9237 -1.5395 -1
4 14.0217 8.6217 4.2892 2.6613 -0.5009 -1
5 23.5487 14.0459 7.2315 4.3085 -1.1615 -1
6 22.2599 11.8045 6.9637 3.7533 -0.5973 -1
7 21.4893 11.2049 6.3991 3.4425 -0.2273 -1
8 21.0086 11.0176 6.4235 3.3416 -0.3216 -1
9 21.3301 13.7054 6.7616 4.4767 -1.4705 -1
10 21.0248 13.6851 6.5606 4.4529 -1.5055 -1
Case (1): External LLL (ABC) fault at 30 km from bus B on transmission line AB.
Figure B.1. 3phase voltage and current at bus A for External fault LLL(ABC) at 30km from bus B on line AB
Figure B.2. 3phase voltage and current at bus B for External fault LLL(ABC) at 30km from bus B on line AB
Figure B.4. 3phase voltage and current at bus D for External fault LLL(ABC) at 30km from bus B on line AB
Case (2) : Internal LLG (ABG) fault at 75 km from bus B on transmission line BE.
Figure B.6. 3phase voltage and current at bus A for internal fault LLG(ABG) at 75km from bus B on line BE
Figure B.8. 3phase voltage and current at bus C for internal fault LLG(ABG) at 75km from bus B on line BE
Figure B.10. 3phase voltage and current at bus E for internal fault LLG(ABG) at 75km from bus B on
line BE