CET 5 Menu Structure

This document provides a summary of the menu structure and settings of a CET 5 motor protection relay: - The main menu includes sections for Meter, Events, Motor Monitor, Targets, and Set/Show. - The Meter section shows electrical measurements, thermal values, and motor load data. - Events displays logged events and their types. Reset Events erases the log. - Motor Monitor stores motor run time and start data that can be reset. - Targets sets warning and trip values across 10 rows for protection functions. - Set/Show configures protection, communication, I/O assignment, and device settings.

Uploaded by

kulukundungu
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
63 views

CET 5 Menu Structure

This document provides a summary of the menu structure and settings of a CET 5 motor protection relay: - The main menu includes sections for Meter, Events, Motor Monitor, Targets, and Set/Show. - The Meter section shows electrical measurements, thermal values, and motor load data. - Events displays logged events and their types. Reset Events erases the log. - Motor Monitor stores motor run time and start data that can be reset. - Targets sets warning and trip values across 10 rows for protection functions. - Set/Show configures protection, communication, I/O assignment, and device settings.

Uploaded by

kulukundungu
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

CET 5

Motor Protection Relay

Programming Menu
Structure
Menu navigation keys

Menu navigation
keys

Escape key. Returns to Enter key. Selects


previous menu. Also underlined setting
required to be pressed or stores entered
after programming is value.
completed to ensure
setting changes are
saved.

SET/SHOW RELAY
RELAY Main Settings
ESC

Move in the list OR

Select underlined
item in menu
Menu structure

Main Menu > Meter

Meter

Instantaneous
L 1 Current
L 1 Angle
L 2 Current
L 2 Angle
L 3 Current
L 3 Angle
GF Curr (Core B)
GF -CB Angle
GF Curr (Resid.)
GF -RES Angle
Average Current
Motor Load
Current Imbalance
VAB
VAB Angle
VBC
VBC Angle
VCA
VCA Angle
Ave Line Voltage Imb.
Real Power
Reactive Power
Apparent Powe r
Power Factor
Frequency

Thermal
Max Winding RTD
Max Bearing RTD
Ambient RTD
Max Other RTD
RTD 1
RTD 2
RTD 3
RTD 4
RTD 5
RTD 6
RTD 7
RTD 8
RTD 9
RTD 10
RTD 11
RTD 12
Motor Load
Therm Cap Used
RTD % TCU Used
Thermal Trip In
Time to Reset
Main Menu > Events

Events

Display Events
Date
Time
Type
Locked Rotor Torque
L1 Current
L2 Current
L3 Current
RES
CB
VAB
VBC
VCA
VG

Reset Events

Main Menu > Motor Monitor

Motor Monitor

Motor Use Data


Last Reset Date
Last Reset Time
Running Time
Stopped Time
Time Running
Number of Starts
Emergency Starts

Reset Statistics

Main Menu > Targets

Targets

ROW 1
ROW 2
ROW 3
ROW 4
ROW 5
ROW 6
ROW 7
ROW 7
ROW 8
ROW 9
ROW 10
Main Menu > Targets

Row 1 Row 6

49T (Overload Trip) VARA (VAR Warning)


LOSSTRIP (Undercurrent Trip) 37PA (Underpower Warning)
JAMTRIP (Jam Trip) 27P2T (Undervoltage Warning)
49UBT (Current Imbalance Trip) 59P2T (Overvoltage Warning)
50P1T (Short Circuit Trip) SPDSAL (Speed Switch Warning)
RTDT (RTD (Winding/Bearing) Trip) 81D1A (Frequency 1 Warning)
PTCTRIP (PTC Trip) 81D2A (Frequency 2 Warning)
50G1T (Ground Fault (Residual) Trip) OTH ALRM (RTD (Other) Warning)

Row 2 Row 7

VART (VAR Trip) VARA (VAR Warning)


37PT (Underpower Trip) 37PA (Underpower Warning)
27P1T (Undervoltage Trip) 27P2T (Undervoltage Warning)
59P1T (Overvoltage Trip) 59P2T (Overvoltage Warning)
47T (Phase Reversal Trip) SPDSAL (Speed Switch Warning)
55T (Power Factor Trip) 81D1A (Frequency 1 Warning)
SPDSTR (Speed Switch Trip) 81D2A (Frequency 2 Warning)
50N1T (Ground Fault (CB) Trip) OTH ALRM (RTD (Other) Warning)

Row 3 Row 8

SMTRIP (Start Time Trip) STOPPED (Stopped State)


81D1T (Frequency 1 Trip) RUNNING (Running State)
81D2T (Frequency 2 Trip) STARTING (Starting State)
OTH TRIP (RTD (Other) Trip) STAR (Star (Wye) Starting State)
AMBTRIP (RTD (Ambient) Trip) DELTA (Delta Starting State)
PTCFLT (PTC Error Trip) START (Start Command)
RTDFLT (RTD Error Trip) Reserved
MCMFLT (MCM Error Trip) Reserved

Row 4 Row 9

COMMIDLE (Comm Idle Trip) IN1 (Input 1 State)


COMMLOSS (Comm Loss Trip) IN2 (Input 2 State)
REMTRIP (Remote Trip) IN3 (Input 3 State)
COMMFLT (Comm Fault Trip) IN4 (Input 4 State)
Reserved IN5 (Input 5 State)
Reserved Reserved
Reserved Reserved
Reserved Reserved

Row 5 Row 10

49A (Overload Warning) TRIP (Trip Relay State)


LOSSALRM (Undercurrent Warning) AUX 1 (Auxiliary Relay 1 State)
JAMALRM (Jam Warning) AUX 2 (Auxiliary Relay 2 State)
46UBA (Current Imbalance Warning) AUX 3 (Auxiliary Relay 3 State)
RTDA (RTD (Wdg/Bearing) Warning) AUX 4 (Auxiliary Relay 4 State)
55A (Power Factor Warning) AUX 5 (Auxiliary Relay 5 State)
50N2T (Ground Fault (CB) Warning) AUX 6 (Auxiliary Relay 6 State)
50G2T (Ground Fault (CB) Warning) Reserved

Main Menu > Set/Show


Set/Show

RELAY
Main Settings
PORT Overload Set
PORT F Short Ckt Set
IO ASSIGN SPEED GF-CB Settings
TRIP RELAY ASSIGN DATA BITS GF-Res Settings
AUX1 ASSIGN PARITY Jam Settings
AUX2 ASSIGN STOP BITS Undercurrent Set
AUX3 ASSIGN PORT TIMEOUT Current Imb Set
AUX4 ASSIGN HDWR HAND SHAKING Prot. Disable
IN1 ASSIGN Start Monitoring
IN2 ASSIGN PORT 4 Star-Delta Set
COMM INTERFACE Start Inhibt Set
DATE/TIME PROTOCOL Speed Sw Set
DATE SPEED PTC Setting
TIME PARITY RTD Setting
MODBUS SLAVE ID Undervoltage Set
PASSWORD Overvoltage Set
New PW VAR Settings
Underpower Set
Power Factor Set
Freq Settings
Phase Rev Set
Load Control Set
I/O Settings
Trip Inhibit
Relay Behavior
Timer Settings
Front Panel Set
Display Set
Main Menu > Set/Show > Relay

Main Settings GF-Res Settings RTD Settings


UNIT ID LINE 1 GF-RES TRIP LEVL RTD ENABLE
UNIT ID LINE 2 GF-RES TRIP DLAY RTD RESET MODE
PHASE ROTATION GF-RES WARN LEVL RTD1 LOCATION
RATED FREQ. GF-RES WARN DLAY RTD1 TYPE
DATE FORMAT Jam Settings RTD1 TRIP LEVEL
PHASE CT RATIO JAM TRIP LEVEL RTD1 WARN LEVEL
MOTOR FLA JAM TRIP DELAY RTD2 LOCATION
TWO SPEED ENABLE JAM WARN LEVEL RTD2 TYPE
nd
CT RATIO-2 JAM WARN DELAY RTD2 TRIP LEVEL
nd
MOTOR FLA-2 Undercurrent Set RTD2 WARN LEVEL
CORE B. CT RATIO UC TRIP LEVEL RTD3 LOCATION
PHASE VT RATIO UC TRIP DELAY RTD3 TYPE
LINE VOLTAGE UC WARN LEVEL RTD3 TRIP LEVEL
XFMER CONNECTION UC WARN DELAY RTD3 WARN LEVEL
Overload Set UC START INHIBIT RTD4 LOCATION
OVERLOAD ENABLE Current Imb Set RTD4 TYPE
OL RESET MODE CI TRIP LEVEL RTD4 TRIP LEVEL
OL RESET LEVEL CI TRIP DELAY RTD4 WARN LEVEL
SERVICE FACTOR CI WARN DELAY RTD5 LOCATION
MOTOR LRC CI WARN DELAY RTD5 TYPE
LOCKD ROTOR TIME Prot. Disable RTD5 TRIP LEVEL
ACCEL FACTOR PROT INHIBT TIME RTD5 WARN LEVEL
RUN STATE TIME K OL INHIBT TIME RTD6 LOCATION
nd
MOTOR LRC-2 Start Monitoring RTD6 TYPE
nd
MOTOR LRT-2 START MOTOR TIME RTD6 TRIP LEVEL
nd
ACCEL FACT-2 Start-Delta Set RTD6 WARN LEVEL
nd
RUN ST TC-2 STAR-DELTA ENABL RTD7 LOCATION
OL WARN LEVEL MAX STAR TIME RTD7 TYPE
START INH. LEVEL Start Inhibt RTD7 TRIP LEVEL
STOP COOL TIME STARTS/HR. RTD7 WARN LEVEL
OL RTD BIASING? MIN. OFF TIME RTD8 LOCATION
Short Ckt Set RESTART BLK TIME RTD8 TYPE
SC TRIP LEVEL Speed Sw Set RTD8 TRIP LEVEL
SC TRIP DELAY SS TRIP DELAY RTD8 WARN LEVEL
SC WARN LEVEL SS WARN DELAY RTD9 LOCATION
SC WARN LEVEL PTC Setting RTD9 TYPE
GF-CB Setting PTC ENABLE RTD9 TRIP LEVEL
GF-CB TRIP LEVEL PTC RESET MODE RTD9 WARN LEVEL
GF-CB TRIP DELAY RTD10 LOCATION
GF-CB WARN LEVEL RTD10 TYPE
GF-CB WARN DELAY RTD10 TRIP LEVEL
RTD10 WARN LEVEL
RTD11 LOCATION
RTD11 TYPE
RTD11 TRIP LEVEL
RTD11 WARN LEVEL
RTD12 LOCATION
RTD12 TYPE
RTD12 TRIP LEVEL
RTD12 WARN LEVEL
WIND TRIP VOTING
BEAR TRIP VOTING
TMP RTD BIASING?
Main Menu > Set/Show > Relay Cont’d

Undervoltage Set Load Control Set


UV TRIP LEVEL LOAD CONTROL SEL
UV TRIP DELAY LD CTL CUR UPPER
UV WARN LEVEL LD CTL CUR LOWER
UV WARN DELAY LD CTL PWR UPPER
Overvoltage Set LD CTL PWR LOWER
OV TRIP LEVEL LD CTL TCU UPPER
OV TRIP DELAY LC CTL TCU LOWER
OV WARN LEVEL I/O Settings
OV WARN DELAY ANALOG OG OUT SEL
VAR Setting Trip Inhibit
NEG VAR TRIP CURRENT INBALANC
POS VAR TRIP JAM
VAR TRIP DELAY GROUND FAULT
NEG VAR WARN LEV SHORT CIRCUIT
POS VAR WARN LEV UNDERCURRENT
VAR WARN DELAY START INHIBIT
Underpower Set PTC
UP TRIP LEVEL RTD
UP TRIP DELAY Relay Behavior
UP WARN LEVEL TRIP FAIL-SAFE
UP WARN DELAY AUX1 FAIL-SAFE
Power Factor Set AUX2 FAIL-SAFE
PF LAG TRIP LEVEL AUX3 FAIL-SAFE
PF LD TRIP LEVEL AUX4 FAIL-SAFE
PF TRIP DELAY AUX5 FAIL-SAFE
PF LAG WARN LEVEL AUX6 FAIL-SAFE
PF LD WARN LEVEL Timer Settings
PF WARN DELAY ON DELAY T1
Freq Settings OFF DELAY T1
FREQ1 TRIP LEVEL ON DELAY T2
FREQ1 TRIP DELAY OFF DELAY T2
FREQ1 WARN LEVEL Front Panel Set
FREQ1 WARN DELAY LCD TIMEOUT
FREQ2 TRIP LEVEL LCD CONTRAST
FREQ2 TRIP DELAY Display Set
FREQ2 WARN LEVEL TIME & DATE
FREQ2 WARN DELAY GROUND CURRENT
Phase Rev Set CURRENT IMBALANC
PH REV. ENABLE FREQUENCY
THERM CAP USED
VOLTAGE IMBALANC
POWER
RTD TEMPERATURE
Main Menu > Status

Status

Definition
FID Firmware identifier string
CID Firmware checksum identifier
Identity Code Relay configuration identification
L1
L2
L3 DC offset in hardware circuits of current channels
RES
CB
VA
VB DC offset in hardware circuits of voltage channels
VC
PS_Vdc Power supply status
FPGA FPGA programming unsuccessful, or FPGA failed
GPSB General Purpose Serial Bus
HMI Front-Panel FGPA programming unsuccessful, or Front-Panel FPGA failed
RAM Volatile memory integrity
ROM Firmware integrity
CR_RAM Integrity of settings in RAM and code that runs in RAM
Non_Vol Integrity of data stored in nonvolatile memory
Clk_Bat Clock battery integrity
Clock Clock functionality
PTC Integrity of PTC
RTD Integrity of RTD module/communications
MCM/CWE Integrity of current board and MCM/CWE
Voltage Integrity of voltage board
I/O_Crd Integrity of I/O card
Com_Crd Integrity of DeviceNet card and network
MAC_ID DeviceNet card specific card identification
ASA Manufacturer identifier for DevieNet
DN_Rate DeviceNet card network communications data speed
DN_Status DeviceNet connection and fault status