Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

System Components: Separating and Protective Instruments

Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

System components Separating and protective

instruments

Overview 266
Separating instruments 268
Overvoltage arresters 270
Dimensions 274
System components - Separating and protective instruments

Separating instruments
For power supply and separation in Ex applications

Functional principle
Separating instruments separate intrinsically circuits from non-intrinsically
safe circuits. Differences are the kind of voltage supply as well as the size
of Ex-technical characteristics values.

Applications
These instruments are used in all applications where Ex-regulations have
to be met.

Overvoltage arresters
Protection against overvoltages
Functional principle
These protective instruments limit frequent failures and overvoltages in
plants to uncritical values so that failures or malfunctions of the
connected instruments cannot occur. The instrument selection depends
on the mounting and the protecting voltage supply or the control circuit.

Applications
These instruments are used in all areas of industrial measurement
technology.

266 - AL-EN System components - Separating and protective instruments


System components - Separating and protective instruments

Overview Separating instruments


VEGATRENN 149 AEx Separator Safety barrier
Type KFD0-CS-Ex 1.51P Type 9001

Applications: galvanically separated galvanic separation of intrinsically safe transmission


voltage supply intrinsically safe and of measuring current in
4 … 20 mA sensors non-intrinsically safe Ex Zone 1
4 … 20 mA circuits
HART signal transmission: yes no no
Sensors: 4 … 20 mA passive 4 … 20 mA passive 4 … 20 mA indication
Mounting: carrier rail carrier rail carrier rail

System components - Separating and protective instruments AL-EN - 267


System components - Separating and protective instruments

Overview Overvoltage arresters


B53-19 B61-300 B61-300FI

Applications: overvoltage protection overvoltage protection overvoltage protection


for conductive probes of supply and control cables of supply and control cables
with FI protective circuit
Mounting: carrier rail carrier rail carrier rail

B62-36G B62-30W

Applications: overvoltage protection overvoltage protection


in two-wire circuits for Profibus PA circuits
Mounting: carrier rail carrier rail

B63-48 B63-32

Applications: overvoltage protection overvoltage protection


in two-wire circuits for Profibus PA and Foundation
Fieldbus circuits
Mounting: direct mounting on field device direct mounting on field device

268 - AL-EN System components - Separating and protective instruments


Separating instruments

VEGATRENN 149A Ex
Ex-separator for 4...20 mA HART® sensors
For galvanically separated voltage supply of Ex approved 4...20 mA
sensors.

− HART® transmissible on the output side


− sockets in the front for communication with the HART® sensor
− sockets suitable for connection of VEGACONNECT
− separate power supply
− SIL2 qualified

Fastening : on carrier rail 35 x 7.5 according to


: EN 50022
Operating voltage : 20 ... 253 V AC/DC
Sensor voltage : 16.7 V at 20 mA
Output : 24 V, load 700 (450) Ohm

basic price:
Approval
EX.X ATEX II (1) G D [EEx ia] IIC ..........................................................................................................................

TRENN149A

Separator type KFD0-CS-Ex1.51P


Ex separator in two-wire technology for 4 ... 20 mA sensors
For galvanic separation between intrinsically safe and non-intrinsically
safe circuits

− for intrinsically safe power supply as well as for signal transmission of


Ex-approved sensors in hazardous areas in conjunction with signal
conditioning instruments without own Ex approval
− no additional power supply necessary, loop-powered
− transmission range 4 ... 20 mA

Mounting : on carrier rail 35 x 7.5 according to


: EN 50022 or on carrier rail 32
: according to EN 50035
Operating voltage : with > 24 V voltage field circuit > 15 V
Approval : ATEX II (1) GD [EEx ia] IIC

basic price:

KFD0-CS-EX1.51P

You find drawings at the end of this chapter

System components - Separating and protective instruments AL-EN - 269


Separating instruments • Overvoltage arresters

Safety barrier type 9001


Safety barrier for intrinsically safe measuring current
transmission in zone 1

Mounting : on carrier rail 35 x 7.5 according to


: EN 50022 or on carrier rail 32
: according to EN 50035
Approval : II (1/2)G [EEx ia/ib] IIC / IIB
Nominal data : 6 V, 73 Ohm

basic price:

TRENN9001.

B 53-19
Overvoltage arrester for the measuring cable of conductive
electrodes
For protection of the measurement technology against impermissible
high overvoltage

− also for intrinsically safe control circuits EEx ia IIC T6


− mounting directly in Ex area for protection of the field instruments
− interruption-free operation

Mounting : on carrier rail 35 x 7,5 according to


EN 50022 or on carrier rail 32
according to EN 50035
Characteristics value : max. 19 V AC

basic price:
Housing / Protection
X w ithout / IP20 ..................................................................................................................................................
GA mounted into alu-housing / IP65 ......................................................................................................................
GK mounted into plastic housing / IP65 .................................................................................................................

ÜSB53-19.X

You find drawings at the end of this chapter

270 - AL-EN System components - Separating and protective instruments


Overvoltage arresters

B 61-300
Overvoltage protection of the supply and control cable with 110 ...
300 V AC/DC, max. 16 A
For protection of the measurement technology against impermissible
high overvoltage

Mounting : on carrier rail 35 x 7.5 according to


EN 50022 or on carrier rail 32
according to EN 50035
Characteristics values : 110 … 300 V AC/DC, max. 16 A

basic price:
Housing / Protection
X w ithout / IP20 ................................................................................................................................................
GA mounted into alu-housing / IP65 ....................................................................................................................
GK mounted into plastic housing / IP65 ..............................................................................................................

ÜSB61-300.X

B 61-300 FI
Overvoltage protection of the supply and control cable with 110 ...
300 V AC/DC, max. 16 A
For protection of the measurement technology against impermissible
high overvoltage

− use in a circuit with leakage current protective circuit

Mounting : on carrier rail 35 x 7.5 according to


EN 50022 or on carrier rail 32
according to EN 50035
Characteristics values : 110 … 300 V AC/DC, max. 16 A

basic price:
Housing / Protection
X w ithout / IP20 .............................................................................................................................................
GA mounted into alu-housing / IP65 .................................................................................................................
GK mounted into plastic housing / IP65 ............................................................................................................

ÜSB61-300FI.X

You find drawings at the end of this chapter

System components - Separating and protective instruments AL-EN - 271


Overvoltage arresters

B 62-36 G
Supply and control cable protection for all instruments
For protection of the measurement technology against impermissible
high overvoltages

− protection for instruments in 2-wire technology


− also for intrinsically safe control circuits EEx ia IIC T6
− mounting directly in Ex area for protection of the field instruments

Mounting : on carrier rail 35 x 7.5 according to


EN 50022 or on carrier rail 32
according to EN 50035
Characteristics values : 12 ... 36 V DC, max. 450 mA

basic price:
Approval
CX ATEX II 1G, 1/2G, 2G EEx ia IIC T6 ..................................................................................................................
Housing / Protection
X w ithout / IP20 .........................................................................................................................................
GA mounted into alu-housing / IP65 .............................................................................................................
GK mounted into plastic housing / IP65 ........................................................................................................

ÜSB62-36G.

B 62-30 W
Supply and control cable protection for Profibus PA circuits
Suitable for connection to segment couplers, VEGALOG 571 EP and
transmitters

− also suitable for ia circuits (overvoltage protection requires no own


approval)
− interruption-free operation

Mounting : on carrier rail 35 x 7.5 according to


EN 50022 or on carrier rail 32
according to EN 50035
Characteristics values : 9 … 36 V DC, max. 400 m A

basic price:
Approval
CX ATEX II 1G, 1/2G, 2G EEx ia IIC T6 ..................................................................................................................
Housing / Protection
X w ithout / IP20 .........................................................................................................................................
GA mounted into alu-housing / IP65 .............................................................................................................
GK mounted into plastic housing / IP65 ........................................................................................................

ÜSB62-30W.

You find drawings at the end of this chapter

272 - AL-EN System components - Separating and protective instruments


Overvoltage arresters

B 63-48
Overvoltage protection in two-wire technology for the measuring
cable of 0/4 ... 20 mA circuits
For protection of the measurement technology against impermissible
high overvoltage

− also for intrinsically safe control circuits EEx ia IIC T6


− mounting directly in Ex area for protection of field devices
− easy mounting in the free cable gland on the field device

Characteristics values : 12 ... 48 V DC

basic price:
Thread
G M20 Iso thread ..................................................................................................................................................
N ½NPT thread .....................................................................................................................................................

ÜSB63-48.

B 63-32
Overvoltage protection in two-wire technology for Profibus PA
and Foundation Fieldbus circuits
For protection of the measurement technology against impermissible
high overvoltage

− also for intrinsically safe control circuits EEx ia IIC T6


− mounting directly in Ex area for protection of field devices
− easy mounting in the free cable gland on the field device

Characteristics values : max. 32 V DC

basic price:
Thread
G M20 Iso thread ..................................................................................................................................................
N ½NPT thread .....................................................................................................................................................

ÜSB63-32.

You find drawings at the end of this chapter

System components - Separating and protective instruments AL-EN - 273


Dimensions

VEGATRENN 149A Ex
114 mm (4.49") 22,5 mm
(0.89")
95 mm (3.74")
108 mm (4.25")

on

CONNECT

149AEx

Separator KFDO-CS-Ex1.51P Safety barrier type 9001

115 mm (4.53") 20 mm 71,5 mm


(0.79") (2.82") 12,2 mm
(0.48")
107 mm (4.21")

102 mm (4.02")
160

160

9001/01-
086-150
101

3 4

Overvoltage arrester type B53…, B61…, B62…,

11 1
13,5 mm
16 mm
(0.63")

(0.53")
84 mm (3.31")
84 mm (3.31")

42 mm
(1.65")
42 mm
(1.65")

59 mm 25 mm
64 mm (0.98")
(2.52") (2.32")

1 Carrier rail 32 according to EN 50035 1 Carrier rail 35 x 7.5 according to EN 50022

Overvoltage arrester type B63…


SW 27 mm
(1.06")

81 mm L min. 250 mm
(3.19") (9.84")

61,3 mm
(2.41")

1 Connection cables, length 300 mm, cross section 1 mm2

You find further drawings and charts under www.vega.com/downloads

274 - AL-EN System components - Separating and protective instruments