01 V5X VRF Service Manual PDF
01 V5X VRF Service Manual PDF
01 V5X VRF Service Manual PDF
Service
Manual
Series
V5 X VRF 50/60Hz
CONTENTS
CONTENTS
201608 1
Midea V5 X Series Service Manual
2
V5 X VRF 50/60Hz
201608
V5 X VRF 50/60Hz
Part 1
General Information
1 Indoor and Outdoor Unit Capacities ...................................................... 4
2 External Appearance.............................................................................. 6
201608 3
V5 X VRF 50/60Hz
1 Indoor and Outdoor Unit Capacities
1.1 Indoor Units
1.1.1 Standard indoor units
Table 1-1.1: Standard indoor unit abbreviation codes
Abbreviation Abbreviation
Type Type
code code
Q1 One-way Cassette T1 High Static Pressure Duct
Q2 Two-way Cassette G Wall-mounted
Q4-C Compact Four-way Cassette DL Ceiling & Floor
Q4 Four-way Cassette F Floor Standing
T3 Low Static Pressure Duct Z Console
T2 Medium Static Pressure Duct
1.8 0.6 18 18 — — — 18 — — — — 18 —
2.2 0.8 22 22 22 22 — 22 22 — 22 — 22 22
2.8 1 28 28 28 28 28 28 28 — 28 — 28 28
3.6 1.25 36 36 36 36 36 36 36 — 36 36 36 36
4.5 1.6 45 45 45 45 45 45 45 — 45 45 45 45
5.6 2 56 56 56 — 56 56 56 — 56 56 56 —
7.1 2.5 71 71 71 — 71 71 71 71 71 71 71 —
8.0 3 80 — — — 80 — 80 80 80 80 80 —
9.0 3.2 90 — — — 90 — 90 90 90 90 90 —
4 201608
V5 X VRF 50/60Hz
1.3 Outdoor Units
Table 1-1.5: Outdoor unit capacity range
Capacity 8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP
Model
X252W X280W X335W X400W X450W X500W X560W X615W
(MV5-*/V2GN1)
201608 5
V5 X VRF 50/60Hz
2 External Appearance
2.1 Indoor Units
2.1.1 Standard indoor units
Table 1-2.1: Standard indoor unit appearance
Q1 Q2
Q4-C Q4
T3 T2
T1 G
DL F
Console
6 201608
V5 X VRF 50/60Hz
2.2 Heat Recovery Ventilator
Table 1-2.3: Heat recovery ventilator appearance
Heat Recovery Ventilator
201608 7
V5 X VRF 50/60Hz
3 Outdoor Unit Combinations
Table 1-3.1: Outdoor unit combinations
1
System capacity Number Modules 2
Outdoor branch joint kit
kW HP of units 8 10 12 14 16 18 20 22
25.2 8 1 ●
28.0 10 1 ●
33.5 12 1 ●
40.0 14 1 ●
—
45.0 16 1 ●
50.0 18 1 ●
56.0 20 1 ●
61.5 22 1 ●
67.0 24 2 ●●
73.0 26 2 ● ●
78.0 28 2 ● ●
84.0 30 2 ● ●
89.5 32 2 ● ●
Midea V5 X Series Service Manual
95.0 34 2 ● ● FQZHW-02N1D
100.0 36 2 ●●
106.5 38 2 ● ●
111.5 40 2 ● ●
117.5 42 2 ● ●
123.0 44 2 ●●
128.5 46 3 ●● ●
134.5 48 3 ● ● ●
139.5 50 3 ● ● ●
145.5 52 3 ● ● ●
151.0 54 3 ● ●●
156.5 56 3 ● ●● FQZHW-03N1D
161.5 58 3 ●● ●
168.0 60 3 ● ●●
173.0 62 3 ● ●●
179.0 64 3 ● ●●
184.5 66 3 ●●●
190.0 68 4 ●● ●●
196.0 70 4 ● ● ●●
201.0 72 4 ● ● ●●
207.0 74 4 ● ● ●●
212.5 76 4 ● ●●●
229.5 82 4 ● ●●●
234.5 84 4 ● ●●●
240.5 86 4 ● ●●●
246.0 88 4 ●●●●
Notes:
1. The combinations of units shown in the table are factory-recommended. Other combinations of units are also possible.
2. For systems with two or more outdoor units, outdoor branch joints (sold separately) are required.
8 201608
V5 X VRF 50/60Hz
4 Combination Ratio
201608 9
Midea V5 X Series Service Manual
10
V5 X VRF 50/60Hz
201608
V5 X VRF 50/60Hz
Part 2
Component Layout and
Refrigerant Circuits
1 Layout of Functional Components ....................................................... 12
201608 11
V5 X VRF 50/60Hz
1 Layout of Functional Components
MV5-X252W/V2GN1 / MV5-X280W/V2GN1 / MV5-X335W/V2GN1
Figure 2-2.1: MV5-X252(280, 335)W/V2GN1 top view
Compressor top
temperature sensor
Midea V5 X Series Service Manual
Outdoor ambient
temperature sensor
Heat exchanger
temperature sensor
High pressure switch
12 201608
V5 X VRF 50/60Hz
MV5-X400W/V2GN1 / MV5-X450W/V2GN1 / MV5-X500W/V2GN1/ MV5-X560W/V2GN1 /
MV5-X615W/V2GN1
Figure 2-2.3: MV5-X400(450, 500, 560, 615)W/V2GN1 top view
201608 13
V5 X VRF 50/60Hz
2 Piping Diagrams
MV5-X252W/V2GN1 / MV5-X280W/V2GN1 / MV5-X335W/V2GN1
Figure 2-1.1: MV5-X252(280, 335)W/V2GN1 piping diagram
Solenoid
valve SV6 1-way valve
Heat exchanger
Filter
Liquid pipe
Electronic expansion valve Filter
Stop valve
Four-way
valve
Gas pipe
Stop valve
High
Accumulator
pressure
Midea V5 X Series Service Manual
Solenoid
Separator
valve SV2
Oil
Capillary
tube
Electronic
expansion valve
Liquid pipe
Electronic Filter
expansion valve Stop valve
Four-way
valve
Gas pipe
Stop valve
1-way
High pressure valve Pressure Solenoid
switch regulating valve SV5
valve
High Capillary
1-way pressure tube
Accumulator
valve sensor
Compressor
Compressor
Solenoid
Separator
valve SV2
Oil
valve SV4
Solenoid
14 201608
V5 X VRF 50/60Hz
Key components:
1. Oil separator:
Separates oil from gas refrigerant pumped out of the compressor and quickly returns it to the compressor. Separation
efficiency is up to 99%.
2. Accumulator:
Stores liquid refrigerant and oil to protect compressor from liquid hammering.
3. Electronic Expansion Valve (EXV):
Controls refrigerant flow and reduces refrigerant pressure.
4. Four-way valve:
Controls refrigerant flow direction. Closed in cooling mode and open in heating mode. When closed, the heat
exchanger functions as a condenser; when open, the heat exchanger functions as an evaporator.
5. Solenoid valve SV2:
Protects the compressor. If compressor discharge temperature rises above 100°C, SV2 opens and sprays a small
amount of liquid refrigerant to cool the compressor. SV2 closes again once the discharge temperature has fallen
201608 15
V5 X VRF 50/60Hz
3 Refrigerant Flow Diagrams
MV5-X252W/V2GN1 / MV5-X280W/V2GN1 / MV5-X335W/V2GN1
Cooling operation
Figure 2-3.1: MV5-X252(280, 335)W/V2GN1 refrigerant flow during cooling operation
High temperature, high pressure gas
High temperature, high pressure liquid
Low temperature, low pressure
Solenoid
valve SV6 1-way valve
Heat exchanger
Accumulator
pressure
"OFF"
1-way valve switch
FAN
M
OFF
Compressor
Solenoid
Separator
closed
1-way Stop valve
valve "ON"
valve SV4
Solenoid
FAN
Capillary M
ON
tube
Filter
closed
Heat exchanger
FAN
valve Pressure Solenoid M
ON
High pressure regulating valve SV5
sensor valve Filter
1-way pressure
valve switch "OFF"
FAN
M OFF
Compressor
Solenoid
Separator
1-way Filter
valve SV2
valve
Oil
300 steps
Stop valve
valve SV4
Solenoid
Filter "ON"
FAN
Capillary Low pressure M
ON
tube switch Filter Filter
300 steps
16 201608
V5 X VRF 50/60Hz
Oil return operation in heating mode and defrosting operation
Figure 2-3.3: MV5-X252(280, 335)W/V2GN1 refrigerant flow during oil return operation in heating mode and during defrosting operation
High temperature, high pressure gas
High temperature, high pressure liquid
Low temperature, low pressure
1-way valve
Heat exchanger
Stop valve Heat exchanger
Separator
Filter
Oil
480 steps
Stop valve
Filter
valve SV4
"ON"
Solenoid
FAN
Capillary M
OFF
Low pressure
tube Filter Filter
switch
480 steps
Heating operation
Figure 2-3.4: MV5-X252(280, 335)W/V2GN1 refrigerant flow during heating operation
High temperature, high pressure gas
High temperature, high pressure liquid
Low temperature, low pressure
Solenoid
1-way valve
Heat exchanger valve SV6
FAN
valve Pressure Solenoid M
ON
regulating valve SV5
High pressure valve Filter
sensor
High Normal control
Accumulator
1-way pressure
switch "OFF"
valve
FAN
Solenoid
M
OFF
Compressor
Separator
closed
Stop valve
Filter
valve SV4
"ON"
Solenoid
Capillary FAN
tube Low pressure
M
ON
switch Filter
closed
201608 17
V5 X VRF 50/60Hz
MV5-X400W/V2GN1 / MV5-X450W/V2GN1 / MV5-X500W/V2GN1/ MV5-X560W/V2GN1 /
MV5-X615W/V2GN1
Cooling operation
Figure 2-3.5: MV5-X400(450, 500, 560, 615)W/V2GN1 refrigerant flow during cooling operation
High temperature, high pressure gas
High temperature, high pressure liquid
Low temperature, low pressure
Solenoid 1-way
Heat exchanger valve SV6 valve
valve sensor
"OFF"
FAN
M
OFF
Compressor
Compressor
Solenoid
Separator
closed
Stop valve
Filter
valve SV4
"ON"
Solenoid
FAN
Capillary Low pressure
M
ON
tube switch Filter
closed
Oil return operation in cooling mode
Figure 2-3.6: MV5-X400(450, 500, 560, 615)W/V2GN1 refrigerant flow during oil return operation in cooling mode
Solenoid 1-way
Heat exchanger valve SV6 valve
FAN
High pressure switch Pressure Solenoid M
ON
regulating valve SV5
valve Filter
Normal control
High Solenoid
Accumulator
M
Compressor
Separator
Filter
Oil
300 steps
Stop valve
Filter
valve SV4
"ON"
Solenoid
FAN
Capillary Low pressure
M ON
tube switch Filter Filter
300 steps
18 201608
V5 X VRF 50/60Hz
Oil return operation in heating mode and defrosting operation
Figure 2-3.7: MV5-X400(450, 500, 560, 615)W/V2GN1 refrigerant flow during oil return operation in heating mode and during defrosting
operation
High temperature, high pressure gas
High temperature, high pressure liquid
Low temperature, low pressure
Solenoid 1-way
Heat exchanger valve SV6 valve
Electronic Heat exchanger
expansion valve
Filter Electronic Filter "ON"
Stop valve
expansion valve FAN
M
OFF
Filter
Four-way
valve Filter 480 steps
Stop "ON"
valve
480 steps
Accumulator
Solenoid
High valve SV2 "OFF"
pressure
sensor FAN
M
OFF
Compressor
Compressor
Separator
Filter
Oil
480 steps
Stop valve
Filter
valve SV4
"ON"
Solenoid
FAN
M
Capillary Low pressure OFF
tube switch Filter Filter
480 steps
Heating operation
Figure 2-3.8: MV5-X400(450, 500, 560, 615)W/V2GN1 refrigerant flow during heating operation
High temperature, high pressure gas
High temperature, high pressure liquid
Low temperature, low pressure
Solenoid 1-way
Heat exchanger valve SV6 valve
Electronic
Heat exchanger
expansion valve
Filter Electronic Filter "ON"
Stop valve
expansion valve FAN
M
ON
Filter
Four-way
valve Filter Normal control
Stop valve
"ON"
1-way FAN
Indoor unit operation
pressure
sensor valve SV2
"OFF"
FAN
M
OFF
Compressor
Compressor
Separator
1-way Filter
valve
Oil
closed
Stop valve
Filter
valve SV4
"ON"
Solenoid
FAN
Capillary Low pressure M
ON
Filter
tube switch Filter
closed
201608 19
Midea V5 X Series Service Manual
20
V5 X VRF 50/60Hz
201608
V5 X VRF 50/60Hz
Part 3
Control
1 General Control Scheme Flowchart ...................................................... 22
Part 3 - Control
7 Special Control..................................................................................... 32
201608 21
V5 X VRF 50/60Hz
1 General Control Scheme Flowchart
Sections 3-2 to 3-7 on the following pages detail when each of the controls in the flowchart below is activated.
2
Stop operation
Abnormal shutdown
System stops
A unit stops when the load demanded decreases
3 7
Standby control
Special control
Crankcase heater control
Thermo on
4
Startup control
Thermo on
Midea V5 X Series Service Manual
5
Normal operation control
Component control during normal operation
Conditions met
Compressor output control
for oil return
Compressor step control Oil return operation
Operation priority and rotation of compressors
Conditions met
Electronic expansion valve control
for defrosting
Outdoor fan control Defrosting operation
6
Protection control
High pressure protection control
Legend
Low pressure protection control Numbers in the top right-hand
Discharge temperature protection control corners of boxes indicate the
relevant section of text on the
Compressor and inverter module protection following pages.
control
Disable heating control
22 201608
V5 X VRF 50/60Hz
2 Stop Operation
The stop operation occurs for one of the three following reasons:
1. Abnormal shutdown: in order to protect the compressors, if an abnormal state occurs the system makes a 'stop with
thermo off' operation and an error code is displayed on the outdoor unit digital displays.
2. The system stops when the set temperature has been reached.
3. A unit stops when the load demanded by the indoor units decreases and can be handled by fewer outdoor units.
When a unit stops because the load demanded by the indoor units has decreased and can be handled by fewer outdoor
units, the unit's four-way valve remains on until the load demanded by the indoor units increases and the unit is required
to operate. When the whole system stops, all the units' four-way valves turn off.
3 Standby Control
3.1 Crankcase Heater Control
The crankcase heater is used to prevent refrigerant from mixing with compressor oil when the compressors are stopped.
The crankcase heater is controlled according to outdoor ambient temperature and discharge temperature. When the
outdoor ambient temperature is above 40°C, the crankcase heater is off; when the outdoor ambient temperature is below
35°C, the crankcase heater is controlled according to discharge temperature. Refer to Figures 3-3.1 and 3-3.2.
Part 3 - Control
Crankcase heater off
Crankcase heater on
201608 23
V5 X VRF 50/60Hz
4 Startup Control
4.1 Compressor Startup Delay Control
In initial startup control, compressor startup is delayed for 12 minutes in order to let the master unit search for the indoor
units’ addresses. In restart control (except in oil return operation and defrosting operation), compressor startup is delayed
such that a minimum of 7 minutes has elapsed since the compressor stopped, in order to prevent frequent compressor
on/off and to equalize the pressure within the refrigerant system.
DC fan motor A FANA ● ● Open once the four-way valve has opened,
controlled according to outdoor ambient
DC fan motor B FANB ● temperature and load requirement
Electronic expansion valve A EXVA ● ● Position (steps) from 0 (fully closed) to 480 (fully
Electronic expansion valve B EXVB ● open), controlled according to discharge superheat
Four-way valve ST1 ● ● On
Solenoid valve (liquid refrigerant injection) SV2 ● ● Off
Solenoid valve (oil balance) SV4 ● ● Closed for 200 secs, open for 600 secs, then closed
Solenoid valve (fast defrosting) SV5 ● ● Off
Solenoid valve (EXV bypass) SV6 ● ● Off
Solenoid valve (indoor units bypass) SV7 ● ● Off
Notes:
1. Refer to Table 3-5.3 in Part 3, 5.6 “Outdoor Fan Control” for more information on fan speed steps.
24 201608
V5 X VRF 50/60Hz
5 Normal Operation Control
5.1 Component Control During Normal Operation
Table 3-5.1: Component control during normal cooling operation
Wiring
Component 8-12HP 14-22HP Control functions and states
diagram label
Inverter compressor A COMP(INV) ● ●
Controlled according to load requirement
Inverter compressor B COMP(INV1) ●
Electronic expansion valve A EXVA ● ● Position (steps) from 0 (fully closed) to 480 (fully
open), controlled according to discharge
Electronic expansion valve B EXVB ●
temperature
Four-way valve ST1 ● ● Off
o
Solenoid valve (liquid refrigerant injection) SV2 ● ● Only open if discharge temperature > 100 C
Solenoid valve (oil balance) SV4 ● ● Open regularly
Solenoid valve (fast defrosting) SV5 ● ● Off
Solenoid valve (EXV bypass) SV6 ● ● Only open if pressure > 3.6MPa
Solenoid valve (indoor units bypass) SV7 ● ● Controlled according to load requirement
Part 3 - Control
Wiring
Component 8-12HP 14-22HP Control functions and states
diagram label
Inverter compressor A COMP(INV) ● ●
Controlled according to load requirement
Inverter compressor B COMP(INV1) ●
During operation the compressors are controlled according to the nominal capacity of indoor units currently running and
the indoor unit heat exchanger temperatures. If the actual load requirement can be provided by one unit alone, then only
one unit starts up. If the actual load requirement requires all outdoor unit modules to operate, the weighted average
actual load requirement is sent to each module and each module operates according to this distributed load
requirement.
201608 25
V5 X VRF 50/60Hz
5.3 Compressor Step Control
The running speed of the compressors in rotations per second (rps) is half the frequency (in Hz) of the electrical input to
the compressor motors. The compressor speed can be altered in increments of 1 rps.
BP BP1 BP2
Midea V5 X Series Service Manual
BP BP BP BP1 BP2 BP BP
① No. 1 No. 2 No. 3 No. 4 No. 5 ① No. 1 No. 2 No. 3 No. 4 No. 5 No. 6
② No. 4 No. 5 No. 1 No. 2 No. 3 ② No. 5 No. 6 No. 1 No. 2 No. 3 No. 4
③ No. 2 No. 3 No. 4 No. 5 No. 1 ③ No. 3 No. 4 No. 5 No. 6 No. 1 No. 2
BP1 BP2 BP1 BP2 BP BP1 BP2 BP1 BP2 BP1 BP2
26 201608
V5 X VRF 50/60Hz
Figure 3-5.4: Compressor priority and rotation – four outdoor units
BP BP BP BP
BP1 BP2 BP BP BP
Part 3 - Control
① No. 1 No. 2 No. 3 No. 4 No. 5 No. 6
201608 27
V5 X VRF 50/60Hz
In cooling mode:
When all outdoor units are in standby:
All EXVs are at position 352 (steps).
Midea V5 X Series Service Manual
When some outdoor units are running and some outdoor units are in standby:
EXVs on running outdoor units are controlled according to discharge temperature. EXVs of units in standby are
fully closed.
When all outdoor units are running:
All EXVs are controlled according to discharge temperature.
In heating mode:
When all outdoor units are in standby:
All EXVs are at position 352 (steps).
When some outdoor units are running and some outdoor units are in standby:
EXVs on running outdoor units are controlled according to discharge superheat. EXVs of units in standby are fully
closed.
When all outdoor units are running:
All EXVs are controlled according to discharge superheat.
28 201608
V5 X VRF 50/60Hz
5.6 Outdoor Fan Control
The speed of the outdoor unit fans is adjusted in steps, as shown in Table 3-5.3.
Table 3-5.3: Outdoor fan speed steps
Fan speed (rpm)
Fan speed index 14/16HP 18HP 20/22HP
8HP 10HP 12HP
FANA FANB FANA FANB FANA FANB
0 0 0 0 0 0 0 0 0 0
1 330 330 330 250 0 250 0 250 0
2 360 360 360 330 0 360 0 360 0
3 410 410 410 250 250 290 290 290 290
4 460 460 460 330 330 360 360 360 360
5 530 530 530 410 410 460 460 460 460
6 580 580 580 460 460 530 530 530 530
7 630 630 630 530 530 580 580 580 580
8 (super silent mode) 660 660 660 580 580 660 660 660 660
9 710 710 710 660 660 710 710 710 710
10 (silent mode) 760 760 760 710 710 850 760 850 760
11 800 800 800 800 800 890 800 890 800
12 850 850 850 980 890 1010 930 1010 930
13 (standard ESP mode) 870 870 870 980 890 1050 980 1050 980
14 (medium ESP mode) 930 930 930 980 890 1050 1010 1050 1010
Part 3 - Control
15 (high ESP mode) 930 930 930 1010 930 1050 1050 1050 1050
Abbreviations:
ESP: External static pressure
201608 29
V5 X VRF 50/60Hz
6 Protection Control
6.1 High Pressure Protection Control
This control protects the system from abnormally high pressure and protects the compressors from transient spikes in
pressure.
Figure 3-6.1: High pressure protection control
Normal operation
Notes:
1. Pc: Discharge pressure
This control protects the system from abnormally low pressure and protects the compressors from transient drops in
pressure.
Figure 3-6.2: Low pressure protection control
Normal operation
Discharge temperature
Compressor off
120oC
100oC SV2 on
SV2 off
90oC 90oC
When the discharge temperature rises above 120°C the system displays P4 protection and all units stop running. When P4
protection occurs 3 times in 100 minutes, the H6 error is displayed. When an H6 error occurs, a manual system restart is
required before the system can resume operation.
Normal operation
Normal operation
Part 3 - Control
Tf > 80oC When PL protection occurs 3 times
in 100 minutes, the C7 error is
displayed. When a C7 error occurs, a
Inverter module temperature protection,
manual system restart is required
error code PL is displayed
before the system can resume
Notes: operation.
1. Tf: Heat sink temperature
Heating operation
Outdoor ambient temperature > 25oC Outdoor ambient temperature < 23oC
Units stop
201608 31
V5 X VRF 50/60Hz
7 Special Control
7.1 Outdoor Unit Duty Cycling
In systems with multiple outdoor units, outdoor unit duty cycling is used to prevent compressor burn out due to
unbalanced oil levels between outdoor units.
Figure 3-7.1 shows an example of duty cycling in a system with 4 outdoor units.
1
Figure 3-7.1: Duty cycling in a system with 4 outdoor units
Outdoor unit Priority Priority Priority Priority Outdoor unit Priority Priority Priority Priority
duty cycling 1 2 3 4 duty cycling 4 1 2 3
Notes:
1. The address settings on the outdoor unit main PCBs for “master unit”, “slave unit 1”, “slave unit 2” and “slave unit 3” do not change.
Tables 3-7.1 and 3-7.2 show component control during oil return operation in cooling mode.
Table 3-7.1: Outdoor unit component control during oil return operation in cooling mode
Component Wiring diagram label 8-12HP 14-22HP Control functions and states
Inverter compressor A COMP(INV) ● ●
Controlled according to load requirement
Inverter compressor B COMP(INV1) ●
DC fan motor A FANA ● ●
Controlled according to discharge pressure
DC fan motor B FAN2 ●
Electronic expansion valve A EXVA ● ●
Fully open
Electronic expansion valve B EXVB ●
Four-way valve ST1 ● ● Off
Solenoid valve (liquid refrigerant injection) SV2 ● ● Normal control
Solenoid valve (oil balance) SV4 ● ● Normal control
Solenoid valve (fast defrosting) SV5 ● ● Off
Solenoid valve (EXV bypass) SV6 ● ● On
Solenoid valve (indoor units bypass) SV7 ● ● Normal control
32 201608
V5 X VRF 50/60Hz
Table 3-7.2: Indoor unit component control during oil return operation in cooling mode
Component Unit state Control functions and states
Thermo on Remote controller setting
Fan Standby Off
Thermo off Remote controller setting
Thermo on Normal control
Electronic expansion valve Standby 300 (steps)
Thermo off 300 (steps)
Tables 3-7.3 and 3-7.4 show component control during oil return operation in heating mode.
Table 3-7.3: Outdoor unit component control during oil return operation in heating mode
Component Wiring diagram label 8-12HP 14-22HP Control functions and states
Inverter compressor A COMP(INV) ● ●
Controlled according to load requirement
Inverter compressor B COMP(INV1) ●
Part 3 - Control
Solenoid valve (fast defrosting) SV5 ● ● Off
Solenoid valve (EXV bypass) SV6 ● ● On
Solenoid valve (indoor units bypass) SV7 ● ● Normal control
Table 3-7.4: Indoor unit component control during oil return operation in heating mode
Component Unit state Control functions and states
Thermo on Off
Fan Standby Off
Thermo off Off
Thermo on 480 (steps)
Electronic expansion valve Standby 480 (steps)
Thermo off 480 (steps)
201608 33
V5 X VRF 50/60Hz
7.3 Defrosting Operation
In order to recover heating capacity, the defrosting operation is conducted when the outdoor unit heat exchanger is
performing as an evaporator. The defrosting operation is controlled according to outdoor ambient temperature, outdoor
heat exchanger temperature, indoor heat exchanger temperature and outdoor units running time.
34 201608
V5 X VRF 50/60Hz
Part 4
Field Settings
1 Outdoor Unit Field Settings ................................................................. 36
201608 35
V5 X VRF 50/60Hz
1 Outdoor Unit Field Settings
1.1 PCB Switches and Switch Settings
Figure 4-1.1: Outdoor unit main PCB switches
PCB switches
S7 ENC2 S1 S7 S8 ENC2 S1
ENC4 S10
ENC4 S10
S4 S2 S5 S6
S4 S2 S5 S6
Midea V5 X Series Service Manual
Silent mode
Silent mode S3
S3 Super silent mode
S3
No silent mode
S4
36 201608
V5 X VRF 50/60Hz
Table 4-1.1: Outdoor unit main PCB switch settings (continued)
1
Switch Setting Switch positions Description
S5
ON
Heating priority (default)
123
S5
ON
Cooling priority
123
S5
3 ON
Priority mode VIP priority or voting priority
S5 123
S5
ON
Heating only
123
S5
ON
Cooling only
123
S6
ON
Auto addressing
123
S6
Addressing ON
4 Manual addressing (default)
S6 mode 123
S6
ON
Clear indoor unit addresses
123
S7
ON
Number of The number of indoor units is not manually set (default)
123
indoor units S7
S7 manually set ON
The number of indoor units is manually set on switches ENC3 and S12
12 3
S8/S10 Reserved
S12
201608 37
V5 X VRF 50/60Hz
1.2 Modes Set on Main PCB
1.2.1 Night silent time setting
Night silent mode is activated X hours after the peak daytime temperature, and is deactivated after Y hours, where X and Y
are as specified in Table 4-1.2.
Table 4-1.2: Night silent time setting
Switch Switch positions Description X Y
S2
Maximum
output
Load
6 hours 10 hours
Operation
sound dB Max. 15dB
reduction
8:00 14:00 20:00 6:00
38 201608
V5 X VRF 50/60Hz
1.2.2 Priority mode setting
Priority mode can only be set on the master unit. When an indoor unit is in mode conflict with the outdoor units the unit
displays the mode conflict error. If the indoor unit has a digital display, it will display error code E0; if the indoor unit
display board has LED indicators, the “DEF./FAN” LED will flash rapidly.
Figure 4-1.3: Indoor unit digital displays and LED indicators
201608 39
V5 X VRF 50/60Hz
1.2.3 Addressing mode setting
The V5 X supports two addressing modes, auto addressing and manual addressing:
If an indoor centralized controller (CCM03, CCM09 or CCM30) is connected directly to the master outdoor unit’s X Y E
terminals, the master unit must be set to auto addressing mode. If the installation situation requires that the indoor
unit addresses are set manually, first set the master unit to manual addressing mode then use a remote or wired
controller to set the indoor units’ addresses one by one, and then change the master unit to auto addressing mode.
(Changing to auto addressing mode will not affect indoor unit addresses that have already been set manually).
Figure 4-1.4: Indoor centralized controller connected to master outdoor unit
Auto addressing
mode
If an indoor centralized controller (CCM03, CCM09 or CCM30) is connected to the indoor units through X Y E terminals,
Midea V5 X Series Service Manual
the master unit can be set to auto addressing mode or manual addressing mode.
Figure 4-1.5: Indoor centralized controller connected to indoor units
XYE XYE XYE XYE
40 201608
V5 X VRF 50/60Hz
Part 5
Diagnosis and
Troubleshooting
1 Outdoor Unit Electric Control Box Layout............................................. 42
4 Troubleshooting .................................................................................. 49
201608 41
V5 X VRF 50/60Hz
1 Outdoor Unit Electric Control Box Layout
MV5-X252W/V2GN1 / MV5-X280W/V2GN1 / MV5-X335W/V2GN1
Figure 5-1.1: Bottom layer of electric control box Figure 5-1.2: Top layer of electric control box
Inverter module
Three-phase
bridge rectifier
Reactor
Fan module Contactor Power supply
Communication terminals
terminals block
Midea V5 X Series Service Manual
Three-phase
bridge rectifier Inverter
modules
Reactor
Fan modules
Contactor
Power supply
Communication terminals
terminals block
42 201608
V5 X VRF 50/60Hz
2 Outdoor Unit Main PCB
2.1 Types
There are four main PCB types for V5 X outdoor units. 8/10/12HP units share a main PCB type, 14/16HP share a main PCB
type, 18HP has a unique main PCB type, and 20/22HP share a main PCB type. The type label is affixed to the main PCB.
When changing a main PCB, be sure to use the right type of main PCB. Refer to Table 5-2.1.
Label
Notes:
1. The 20/22HP main PCB can also be used on 8/10/12HP units. The only difference is that the 20/22HP main PCB has two inverter modules whilst the
8/10/12HP main PCB has one inverter module. If a 20/22HP main PCB is used on an 8/10/12HP unit, the unit will run normally but LED6 will flash and LED7
will be continuously on.
2.2 Ports
ENC1 ENC3S12 S3
S7 ENC2 S1
ENC4 S10
S4 S2 S5 S6
Instruction
Type label
label
Notes:
1. Label descriptions are given in Table 5-2.2.
201608 43
V5 X VRF 50/60Hz
Table 5-2.2: Main PCB ports
Label in Port
Content Port voltage
Figure 5-2.1 code
Compressor top temperature sensor (single compressor units) or
1 CN10 compressor A compressor top temperature sensor (dual 0-5V DC (varying)
compressor units) connection
Discharge pipe temperature sensor (single compressor units) or
2 CN11 compressor B compressor top temperature sensor (dual 0-5V DC (varying)
compressor units) connection
3 CN4 Inverter module temperature sensor connection 0-5V DC (varying)
4 CN26 Reserved
5 CN25 Communication port 2.5-2.7V DC
6 CN30 Power input 380V
7 CN80 Reserved
8 CN31 No.1 transformer power input 220V
9 CN33 No.2 transformer power input 220V
10 CN66 Power supply to compressor A crankcase heater 220V
11 CN67 Power supply to compressor B crankcase heater 220V
Midea V5 X Series Service Manual
12 CN70 EVXA drive port First pin on the left: 12V DC; other four pins:
13 CN71 EVXB drive port varying
CN47-
14 Four-way valve drive ports 220V
CN49
CN41-
15 Solenoid valve drive ports 220V
CN45
16 CN54 Power output 220V
CN57-
17 Neutral terminals 0
CN59
Voltage between upper two pins: 13.5V AC;
18 CN32 No.1 transformer power output
voltage between lower two pins: 9V AC
Voltage between upper two pins: 14.5V AC;
19 CN34 No.2 transformer power output
voltage between lower two pins: 14.5V AC
20 CN39 Inverter module B control port Third pin on the left: 3.3V DC
21 CN38 Inverter module B voltage monitor port 540V DC, +15V DC, N
22 CN36 Inverter module A voltage monitor port 540V DC, +15V DC, N
23 CN37 Inverter module A control port Third pin on the left: 3.3V DC
24 CN35 5V DC, 12V DC power input GND, +5V, +12V, GND, 12V
25 CN19 Low pressure switch connection 0 or 5V
High pressure switch and discharge temperature switch(es)
26 CN18 0 or 5V
connections
27 CN28 Reserved
28 CN16 Reserved
29 CN15 Inverter compressor A and B current sensor connections 0-7.8V AC (varying)
30 CN17 High pressure sensor connection 0-5V DC (varying)
31 CN2 Reserved
Outdoor ambient temperature sensor and outdoor heat exchanger
32 CN1 0-5V DC (varying)
temperature sensor connections
33 CN20 Outdoor units communication port 2.5-2.7V DC
34 CN65 Fan B control port First pin on the left: 12V DC; other four pins:
35 CN64 Fan A control port varying
44 201608
V5 X VRF 50/60Hz
2.3 Components
2.3.1 Layout
Figure 5-2.2: Outdoor unit main PCB components
DSP1
DSP2
] Digital display Current sensors
Buttons
SW1/2/3/4
LED indicators
LED1/2/3
Main control chip LED indicators
LED6/7
Communication chip
ENC4 S10
LED indicators
S4 S2 S5 S6 LED4/5
Button Function
SW3 SW4
SW1 Force cooling
24 Number of indoor units currently in communication with master unit Actual value = value displayed
25 Number of indoor units currently operating Actual value = value displayed
26 Priority mode Refer to Note 4
27 Silent mode Refer to Note 5
28 Static pressure mode Refer to Note 6
29 DC voltage A Actual value = value displayed × 10
30 DC voltage B Actual value = value displayed × 10
31 Reserved
000 is displayed if no error or protection events
32 Most recent error or protection code
have occurred since start-up
33 Error clearance metric Actual value = value displayed
34 ---- End
Notes:
1. Outdoor unit capacity setting:
0: 8HP; 1: 10HP; 2: 12HP; 3: 14HP; 4: 16HP; 5: 18HP; 6: 20HP; 7: 22HP.
2. Operating mode:
0: off; 2: cooling; 3: heating; 4: forced cooling.
3. The fan speed index is related to the fan speed in rpm as described in Table 3-5.3 in Part 3, 5.6 “Outdoor Fan Control”.
4. Priority mode:
0: heating priority; 1: cooling priority; 2: VIP priority or voting priority; 3: heating only; 4: cooling only.
5. Silent mode:
0: night silent mode; 1: silent mode; 2: super silent mode; 3: no silent mode.
6. Static pressure mode:
0: standard static pressure; 1: low static pressure; 2: medium static pressure; 3: high static pressure.
46 201608
V5 X VRF 50/60Hz
2.3.4 Digital display output
Table 5-2.5: Digital display output in different operating states
Outdoor unit state Parameters displayed on DSP1 Parameters displayed on DSP2
The number of indoor units in DSP1
Standby Unit's address
communication with the outdoor units
For single Running speed of the compressor in
--
Normal compressor units rotations per second
operation For dual Running speed of compressor B in Running speed of compressor A in
compressor units rotations per second rotations per second
Error or protection -- or placeholder Error or protection code DSP2
System check Refer to Table 5-2.4 Refer to Table 5-2.4
201608 47
V5 X VRF 50/60Hz
Table 5-3.1: Error code table (continued)
1
Error code Content Remarks
Number of indoor units detected by master unit not same as number set
H7 Only displayed on the master unit
on main PCB
H8 Discharge pipe low pressure protection. Displayed on the unit with the error
yHd Slave unit malfunction Only displayed on the master unit
P0 Compressor temperature protection Displayed on the unit with the error
P1 Discharge pipe high pressure protection Displayed on the unit with the error
P2, H5 Suction pipe low pressure protection Displayed on the unit with the error
xP3 Compressor current protection Displayed on the unit with the error
P4, H6 Discharge temperature protection Displayed on the unit with the error
P5 Outdoor heat exchanger temperature protection Displayed on the unit with the error
P9, H9 Fan module protection Displayed on the unit with the error
PL, C7 Inverter module temperature protection Displayed on the unit with the error
PP, F0 Compressor discharge insufficient superheat protection Displayed on the unit with the error
xF1 DC bus voltage error Displayed on the unit with the error
dF Defrosting operation
Midea V5 X Series Service Manual
48 201608
V5 X VRF 50/60Hz
4 Troubleshooting
4.1 Warning
Warning
All electrical work must be carried out by competent and suitably qualified, certified and
accredited professionals and in accordance with all applicable legislation (all national, local and other laws,
standards, codes, rules, regulations and other legislation that apply in a given situation).
Power-off the outdoor units before connecting or disconnecting any connections or wiring, otherwise electric
shock (which can cause physical injury or death) may occur or damage to components may occur.
201608 49
V5 X VRF 50/60Hz
4.2 E0 Troubleshooting
4.2.1 Digital display output
4.2.2 Description
Communication error between outdoor units.
All units stop running.
Error code is only displayed on the slave unit with the error.
50 201608
V5 X VRF 50/60Hz
4.2.4 Procedure
E0
ODU addresses on switch ENC1 are set Yes Set the ODU addresses correctly
incorrectly1
No
Notes:
1. The master unit address should be set as 0, slave units addresses should be set from 1 to 3, and the addresses should not be repeated within one system.
Refer to Part 4, 1.1 “PCB Switches and Switch Settings”.
2. All the wires for H1, H2, E connections should be three-core shielded cable, the wiring should be connected according to polarity (H1 to H1, etc), the wiring
should not be open or short circuited. Refer to the V5 X Engineering Data Book, Part 2, 5 “Wiring Diagrams” and Part 3, 9.3 “Communication Wiring”.
3. Refer to Figures 5-1.2 and 5-1.4 in Part 5, 1 “Outdoor Unit Electric Control Box Layout” and to the V5 X Engineering Data Book, Part 2, 5 “Wiring Diagrams”.
4. Refer to Figures 5-1.2 and 5-1.4 in Part 5, 1 “Outdoor Unit Electric Control Box Layout”.
201608 51
V5 X VRF 50/60Hz
4.3 E1 Troubleshooting
4.3.1 Digital display output
4.3.2 Description
Phase sequence error.
All units stop running.
Error code is only displayed on the unit with the error.
52 201608
V5 X VRF 50/60Hz
4.3.4 Procedure
E1
The phase sequence of the 3-phase Yes Exchange any two of the 3 phase wires
power supply is incrorrect1
No
The power supply is abnormal Yes Check the power supply equipment
No
Notes:
1. The A, B, C terminals of the 3-phase power supply should match compressor phase sequence requirements. If the phase sequence is inverted, the
compressor will operate inversely. If the wiring connection of each outdoor unit is in A, B, C phase sequence, and multiple units are connected, the current
difference between C phase and A, B phases will be very large as the power supply load of each outdoor unit will be on C phase. This can easily lead to
tripped circuits and terminal wiring burnout. Therefore if multiple units are to be used, the phase sequence should be staggered, so that the current is
distributed among the three phases equally. Refer to Figures 5-1.2 and 5-1.4 in Part 5, 1 “Outdoor Unit Electric Control Box Layout”.
2. Loose power supply terminals can cause the compressors to operate abnormally and compressor current to be very large. Refer to Figures 5-1.2 and 5-1.4
in Part 5, 1 “Outdoor Unit Electric Control Box Layout”.
201608 53
V5 X VRF 50/60Hz
4.4 E2 Troubleshooting
4.4.1 Digital display output
4.4.2 Description
Communication error between indoor and master unit.
All units stop running.
Error code is only displayed on the master unit.
54 201608
V5 X VRF 50/60Hz
4.4.4 Procedure
E2
No
Interference from high voltage (220V or Yes Ensure the communication wires and
higher) wires4 high voltage wires are separated
No
The length of communication wire is over Yes Reduce the wire length to less than
1200m 1200m or strengthen the signal
No
Notes:
1. Measure the resistance among P, Q and E. The normal resistance between P and Q is 120Ω, between P and E is infinite, between Q and E is infinite. Refer
to Figures 5-1.2 and 5-1.4 in Part 5, 1 “Outdoor Unit Electric Control Box Layout” and to the V5 X Engineering Data Book, Part 3, 9.3 “Communication
Wiring”.
2. Refer to the V5 X Engineering Data Book, Part 3, 9.3 “Communication Wiring”.
3. Refer to Figures 5-1.2 and 5-1.4 in Part 5, 1 “Outdoor Unit Electric Control Box Layout” and to the V5 X Engineering Data Book, Part 2, 5 “Wiring Diagrams”.
4. Refer to the V5 X Engineering Data Book, Part 3, 9.1 “General” for required separation distances between communication wiring and power wiring.
5. Refer to Figures 5-1.2 and 5-1.4 in Part 5, 1 “Outdoor Unit Electric Control Box Layout”.
201608 55
V5 X VRF 50/60Hz
4.5 E4, E7 Troubleshooting
4.5.1 Digital display output
4.5.2 Description
E4 indicates an outdoor ambient temperature sensor error.
E7 indicates a compressor top temperature sensor or discharge pipe temperature sensor error.
All units stop running.
Error code is only displayed on the unit with the error.
Midea V5 X Series Service Manual
56 201608
V5 X VRF 50/60Hz
4.5.4 Procedure
E4 / E7
Temperature sensor connection on main Yes Ensure the sensor is connected properly
PCB is loose1
No
201608 57
V5 X VRF 50/60Hz
4.6 E5 Troubleshooting
4.6.1 Digital display output
4.6.2 Description
Abnormal power supply voltage.
All units stop running.
Error code is only displayed on the unit with the error.
58 201608
V5 X VRF 50/60Hz
4.6.4 Procedure
E5
Notes:
1. The normal voltage between A and N, B and N, and C and N is 198-242V.
2. Refer to Figures 5-1.1 to 5-1.4 in Part 5, 1 “Outdoor Unit Electric Control Box Layout” and to the V5 X Engineering Data Book, Part 2, 5 “Wiring Diagrams”.
3. The normal resistances of the inverter compressor are 0.7-1.5Ω among U V W and infinite between each of U V W and ground. If any of the resistances
differ from these specifications, the compressor has malfunctioned. Refer to Figures 5-4.6 and 5-4.7 in Part 5, 4.11.6 “xL0 troubleshooting”.
4. The normal resistances of the fan motor coil among U V W are less than 10Ω. If a measured resistance is 0Ω, the fan motor has short-circuited. Refer to
Part 2, 1 “Layout of Functional Components”.
5. Set a multi-meter to buzzer mode and test any two terminals of P N and U V W of the inverter module. If the buzzer sounds, the inverter module has
short-circuited. Refer to Figures 5-1.1 and 5-1.3 in Part 5, 1 “Outdoor Unit Electric Control Box Layout” and to Figure 5-4.1.
P U V W N
201608 59
V5 X VRF 50/60Hz
4.7 E8 Troubleshooting
4.7.1 Digital display output
4.7.2 Description
Outdoor unit address error.
All units stop running.
Error code is only displayed on the unit with the error.
60 201608
V5 X VRF 50/60Hz
4.7.4 Procedure
E8
The ODU's address is not in the valid Yes Slave units addresses should be set from
range1 1 to 3
No
Notes:
1. The master unit address should be set as 0, slave units addresses should be set from 1 to 3, and the addresses should not be repeated within one system.
Refer to Part 4, 1.1 “PCB Switches and Switch Settings”.
201608 61
V5 X VRF 50/60Hz
4.8 xE9 Troubleshooting
4.8.1 Digital display output
In the error code, 'x' is a placeholder for the compressor system (compressor and related electrical components), with 1
representing compressor system A and 2 representing compressor system B.
4.8.2 Description
1E9 indicates a compressor A EEPROM mismatch.
2E9 indicates a compressor B EEPROM mismatch.
All units stop running.
Error code is only displayed on the unit with the error.
62 201608
V5 X VRF 50/60Hz
4.8.4 Procedure
xE9
Notes:
1. When performing a manual restart of an outdoor unit, once the unit has been powered off it should not be powered on again until the digital display has
turned off.
201608 63
V5 X VRF 50/60Hz
4.9 xH0, H1 Troubleshooting
4.9.1 Digital display output
In the error code, 'x' is a placeholder for the compressor system (compressor and related electrical components), with 1
representing compressor system A and 2 representing compressor system B.
4.9.2 Description
1H0 indicates a communication error between the main control chip and the compressor A inverter driver chip.
2H0 indicates a communication error between the main control chip and the compressor B inverter driver chip.
H1 indicates a communication error between the main control chip and the communication chip.
All units stop running.
Midea V5 X Series Service Manual
64 201608
V5 X VRF 50/60Hz
4.9.4 Procedure
xH0 / H1
Power supply for main PCB and Yes Provide normal power supply
transformer is abnormal1
No
No
Notes:
1. Measure the voltages of ports CN31, CN33 and CN35 on the main PCB (labeled 8, 9 and 24, respectively, in Figure 5-2.1 in Part 5, 2.2 “Ports”). The normal
voltage between CN31 and CN33 terminals is 220V, between GND and the 5V pins of CN35 is 5V, between GND and 12V pins of CN35 is 12V. If one or more
of the voltages are not normal, the power supply for main PCB and transformer is abnormal.
2. Measure the voltages of ports CN32 and CN34 on the main PCB (labeled 18 and 19, respectively, in Figure 5-2.1 in Part 5, 2.2 “Ports”). The normal voltage
across the upper two pins of CN32 is 13.5V (AC), across the lower two pins is 9V (AC). The normal voltage across the upper two pins of CN34 is 14.5V (AC),
across the lower two pins is 14.5V (AC). If one or more of the voltages are not normal, the transformer has malfunctioned. Refer to Figure 5-4.2.
201608 65
V5 X VRF 50/60Hz
4.10 H2, H3 Troubleshooting
4.10.1 Digital display output
4.10.2 Description
H2 indicates that the number of slave units detected by master unit has decreased.
H3 indicates that the number of slave units detected by master unit has increased.
All units stop running.
Error code is only displayed on the master unit.
Midea V5 X Series Service Manual
66 201608
V5 X VRF 50/60Hz
4.10.4 Procedure
H2 / H3
Some outdoor units in the system are Yes Power on all the outdoor units
powered off1
No
The power supply is abnormal Yes Check the power supply equipment
No
201608 67
V5 X VRF 50/60Hz
4.11 xH4 Troubleshooting
4.11.1 Digital display output
In the error code, 'x' is a placeholder for the compressor system (compressor and related electrical components), with 1
representing compressor system A and 2 representing compressor system B.
4.11.2 Description
1H4 indicates compressor A inverter module protection.
2H4 indicates compressor B inverter module protection.
When an xH4 error occurs, a manual system restart is required before the system can resume operation. The cause of
an xH4 error should be addressed promptly in order to avoid system damage.
All units stop running.
Error code is only displayed on the unit with the error.
Midea V5 X Series Service Manual
68 201608
V5 X VRF 50/60Hz
Table 5-4.1: Specific error codes for error xH4
1
Specific error code Content
xL0 Inverter module protection
xL1 DC bus low voltage protection
xL2 DC bus high voltage protection
xL4 MCE error
xL5 Zero speed protection
xL7 Phase sequence error
xL8 Compressor frequency variation greater than 15Hz within one second protection
xL9 Actual compressor frequency differs from target frequency by more than 15Hz protection
Notes:
1. 'x' is a placeholder for the compressor system (compressor and related electrical components), with 1 representing compressor system A and
2 representing compressor system B.
The specific error codes xL0, xL1, xL2 and xL4 can also be obtained from the inverter module LED indicators. If an inverter
module error has occurred, LED5/7 is continuously on and LED4/6 flashes. Refer to Figure 5-4.4 and Table 5-4.2.
201608 69
V5 X VRF 50/60Hz
4.11.5 First troubleshooting step
To troubleshoot xH4 errors, first ensure that the DC bus wire is connected correctly. The DC bus wire should run from the N
terminal on the inverter module, through the current sensor (in the direction indicated by the arrow on the current
sensor), and end at the N terminal on the DC filter board.
Figure 5-4.5: DC detection wire connection method
Inverter module N
terminal
DC filter board N
terminal
DC bus wire
Current sensor
Midea V5 X Series Service Manual
Figure 5-4.6: Measuring resistances among compressor Figure 5-4.7: Measuring resistances between compressor terminals
terminals and ground
70 201608
V5 X VRF 50/60Hz
Figure 5-4.8: Inverter module terminals
N1
P1
P U V W N
P N
Check AC filter
board wiring
201608 71
V5 X VRF 50/60Hz
4.11.8 xL2 troubleshooting
Step 1: Check inverter module
Check the DC voltage between terminals P and N. The normal value is 510-580V, if the voltage is higher than 580V, go
to Step 2.
Figure 5-4.11: Inverter module terminals
P N
Midea V5 X Series Service Manual
4.11.10 Compressor replacement procedure Figure 5-4.14: Draining oil from a compressor
Step 1: Remove faulty compressor and remove oil
Remove the faulty compressor from the outdoor unit.
Before removing the oil, shake the compressor so as to not allow
impurities to remain settled at the bottom.
Drain the oil out of the compressor and retain it for inspection.
Normally the oil can be drained out from the compressor discharge
pipe. Refer to Figure 5-4.14.
201608 73
V5 X VRF 50/60Hz
Step 5: Check filters(s)
If the oil from a compressor is spoiled (lightly or heavily), check the filter between the gas stop valve and the 4-way
valve in that unit. If it is blocked, clean with nitrogen or replace.
Step 6: Replace the faulty compressor and re-fit the other compressors Figure 5-4.15: Compressor piping
Only use FV68H oil. Different compressors require different types of oil. Using the wrong type of oil leads to various
problems.
Add additional oil to the accumulators such that the total amount of oil is 5L in 8-12HP units and 7L in 14-22HP units.
74 201608
V5 X VRF 50/60Hz
Figure 5-4.17: Effects of spoiled compressor oil
Worn crankshaft
201608 75
V5 X VRF 50/60Hz
4.12 H7 Troubleshooting
4.12.1 Digital display output
4.12.2 Description
Number of indoor units detected by master unit not same as number set on main PCB.
All units stop running.
Error code is only displayed on the master unit.
76 201608
V5 X VRF 50/60Hz
4.12.4 Procedure
H7
Number of indoor units set on main PCB Change the setting on the PCB to be the
not same as actual number of indoor Yes same as the actual number of indoor
units1 units
No
Some indoor units are powered off Yes Power on all indoor units
No
After re-starting the ODUs and IDUs and Refer to indoor unit troubleshooting
then waiting 2 minutes, an IDU displays Yes guide. Resolving the indoor unit error
Notes:
1. The number of indoor units can be set on switches EN3 and S12 on the main PCB. Refer to Part 4, 1.1 “PCB Switches and Switch Settings”.
2. Indoor unit error code E1 indicates a communication error between indoor and master unit. Indoor unit error code FE indicates that an indoor unit has not
been assigned an address.
3. Indoor unit addresses can be checked and manually assigned using indoor unit remote/wired controllers. Alternatively, indoor unit addresses can be
automatically assigned by the master outdoor unit. Auto-addressing mode is selected by setting switch S6 on the main PCB. Refer to Part 4, 1.1 “PCB
Switches and Switch Settings”.
201608 77
V5 X VRF 50/60Hz
4.13 H8 Troubleshooting
4.13.1 Digital display output
4.13.2 Description
Discharge pipe low pressure protection. When the discharge pressure falls below 0.3MPa, the system displays H8
protection and all units stop running. When the discharge pressure returns to normal, H8 is removed and normal
operation resumes.
Error code is only displayed on the unit with the error.
78 201608
V5 X VRF 50/60Hz
4.13.4 Procedure
H8
ODU stop valves are closed Yes Open the stop valves
No
High pressure sensor connection on main Yes Ensure the sensor is connected properly
PCB is loose1
No
The low pressure side is blocked, caused Inspect the system and fix the error. If the
by crushed or bent pipe, closed EXV or Yes filter is blocked by ice, the piping should
dirty filter4 be cleaned
No
The evaporator heat exchange is poor5 Yes Inspect the system and fix the error
No
Notes:
1. High pressure sensor connection is port CN17 on the main PCB (labeled 30 in Figure 5-2.1 in Part 5, 2.2 “Ports”).
2. Measure the resistance among the three terminals of the pressure sensor. If the resistance is of the order of mega Ohms or infinite, the pressure sensor
has failed. Refer to Part 2, 1 “Layout of Functional Components”.
3. To check for insufficient refrigerant:
Re-start the outdoor units. If an r1, r2 or r3 error is displayed upon start-up, there is insufficient refrigerant in the system.
An insufficiency of refrigerant causes compressor discharge temperature to be higher than normal, discharge and suction pressures to be lower than
normal and compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. These issues disappear once
sufficient refrigerant has been charged into the system. For normal system parameters refer to Tables 5-5.4 and 5-5.5 in Part 5, 5.2 “Normal
Operating Parameters of Refrigerant System”.
4. A low pressure side blockage causes compressor discharge temperature to be higher than normal, suction pressure to be lower than normal and
compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. For normal system parameters refer to Tables 5-5.4 and
5-5.5 in Part 5, 5.2 “Normal Operating Parameters of Refrigerant System”.
5. In cooling mode check indoor heat exchangers, fans and air outlets for dirt/blockages. In heating mode check outdoor heat exchangers, fans and air outlets
for dirt/blockages.
201608 79
V5 X VRF 50/60Hz
4.14 yHd Troubleshooting
4.14.1 Digital display output
In the error code, 'y' is a placeholder for the address (1, 2 or 3) of the slave unit with the error.
4.14.2 Description
1Hd indicates an error on the slave unit with address 1.
2Hd indicates an error on the slave unit with address 2.
3Hd indicates an error on the slave unit with address 3.
All units stop running.
Error code is only displayed on the master unit.
80 201608
V5 X VRF 50/60Hz
4.14.4 Procedure
yHd
201608 81
V5 X VRF 50/60Hz
4.15 P0, P4, H6 Troubleshooting
4.15.1 Digital display output
4.15.2 Description
P0 indicates compressor temperature protection.
P4 indicates discharge temperature protection. When the discharge temperature rises above 120°C the system
Midea V5 X Series Service Manual
4.15.4 Procedure
P0 / P4 / H6
ODU stop valves are closed Yes Open the stop valves
No
Insufficient refrigerant caused by Yes Add refrigerant and inspect the system
refrigerant leakage3 for leaks
No
The condenser heat exchange is poor7 Yes Inspect the system and fix the error
No
Notes:
1. Compressor top temperature sensor and discharge pipe temperature sensor connections are ports CN10 and CN11 on the main PCB (labeled 1 and 2,
respectively, in Figure 5-2.1 in Part 5, 2.2 “Ports”). The discharge temperature switch connection is port CN18 on the main PCB (labeled 26 in Figure 5-2.1
in Part 5, 2.2 “Ports”).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Part 2, 1 “Layout of Functional Components” and to Table 5-5.2 in Part 5, 5.1 “Temperature Sensor
Resistance Characteristics”.
3. To check for insufficient refrigerant:
Re-start the outdoor units. If an r1, r2 or r3 error is displayed upon start-up, there is insufficient refrigerant in the system.
An insufficiency of refrigerant causes compressor discharge temperature to be higher than normal, discharge and suction pressures to be lower than
normal and compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. These issues disappear once
sufficient refrigerant has been charged into the system. For normal system parameters refer to Tables 5-5.4 and 5-5.5 in Part 5, 5.2 “Normal
Operating Parameters of Refrigerant System”.
4. A low pressure side blockage causes compressor discharge temperature to be higher than normal, suction pressure to be lower than normal and
compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. For normal system parameters refer to Tables 5-5.4 and
5-5.5 in Part 5, 5.2 “Normal Operating Parameters of Refrigerant System”.
5. An indoor load that is too large causes suction and discharge temperatures to be higher than normal. For normal system parameters refer to Tables 5-5.4
and 5-5.5 in Part 5, 5.2 “Normal Operating Parameters of Refrigerant System”.
6. Air or nitrogen in the system causes discharge temperature to be higher than normal, discharge pressure to be higher than normal, compressor current to
be higher than normal, abnormal compressor noise and an unsteady pressure meter reading. For normal system parameters refer to Tables 5-5.4 and 5-5.5
in Part 5, 5.2 “Normal Operating Parameters of Refrigerant System”.
7. In cooling mode check outdoor heat exchangers, fans and air outlets for dirt/blockages. In heating mode check indoor heat exchangers, fans and air outlets
for dirt/blockages.
201608 83
V5 X VRF 50/60Hz
4.16 P1 Troubleshooting
4.16.1 Digital display output
4.16.2 Description
Discharge pipe high pressure protection. When the discharge pressure rises above 4.4MPa, the system displays P1
protection and all units stop running. When the discharge pressure falls below 3.2MPa, P1 is removed and normal
operation resumes.
If the system has a 3-phase protector and the 3-phase protector is connected with the high pressure switch, the
system will display P1 protection when initially powered on, and P1 protection will disappear once the system reaches
a steady state.
Error code is only displayed on the unit with the error.
4.16.4 Procedure
P1
ODU stop valves are closed Yes Open the stop valves
No
High pressure sensor connection on main Yes Ensure the sensor is connected properly
PCB is loose1
No
84 201608
V5 X VRF 50/60Hz
… flowchart continued from previous page
The high pressure side is blocked, caused Yes Inspect the system and fix the error
by crushed or bent pipe or blocked EXV5
No
The condenser heat exchange is poor6 Yes Inspect the system and fix the error
No
Notes:
1. The high pressure sensor connection is port CN17 on the main PCB (labeled 30 in Figure 5-2.1 in Part 5, 2.2 “Ports”).
2. Measure the resistance among the three terminals of the pressure sensor. If the resistance is of the order of mega Ohms or infinite, the pressure sensor
has failed. Refer to Part 2, 1 “Layout of Functional Components”.
3. To check for excess refrigerant:
Re-start the outdoor units. If an R1 or R2 error is displayed upon start-up, there is excess refrigerant in the system.
Excess refrigerant causes discharge temperature to be lower than normal, discharge pressure to be higher than normal and suction pressure to be
higher than normal. For normal system parameters refer to Tables 5-5.4 and 5-5.5 in Part 5, 5.2 “Normal Operating Parameters of Refrigerant
System”.
4. Air or nitrogen in the system causes discharge temperature to be higher than normal, discharge pressure to be higher than normal, compressor current to
be higher than normal, abnormal compressor noise and an unsteady pressure meter reading. For normal system parameters refer to Tables 5-5.4 and 5-5.5
in Part 5, 5.2 “Normal Operating Parameters of Refrigerant System”.
5. High pressure side blockage causes discharge temperature to be higher than normal, discharge pressure to be higher than normal and suction pressure to
be lower than normal. For normal system parameters refer to Tables 5-5.4 and 5-5.5 in Part 5, 5.2 “Normal Operating Parameters of Refrigerant System”.
6. In cooling mode check outdoor heat exchangers, fans and air outlets for dirt/blockages. In heating mode check indoor heat exchangers, fans and air outlets
for dirt/blockages.
201608 85
V5 X VRF 50/60Hz
4.17 P2, H5 Troubleshooting
4.17.1 Digital display output
4.17.2 Description
P2 indicates suction pipe low pressure protection. When the suction pressure falls below 0.05MPa, the system
displays P2 protection and all units stop running. When the pressure rises above 0.15MPa, P2 is removed and normal
operation resumes.
H5 indicates P2 protection has occurred 3 times in 60 minutes. When an H5 error occurs, a manual system restart is
required before the system can resume operation.
If the system has a 3-phase protector and the 3-phase protector is connected to the low pressure switch, the system
Midea V5 X Series Service Manual
will display P2 protection when initially powered on, and P2 protection will disappear once the system reaches a
steady state.
Error code is only displayed on the unit with the error.
86 201608
V5 X VRF 50/60Hz
4.17.4 Procedure
P2 / H5
ODU stop valves are closed Yes Open the stop valves
No
Insufficient refrigerant caused by Yes Add refrigerant or inspect the system for
refrigerant leakage1 leaks
No
The low pressure side is blocked, caused Inspect the system and fix the error. If the
by crushed or bent pipe, blocked EXV, or Yes filter is blocked by ice, the piping should
dirty filter2 be cleaned
The evaporator heat exchange is poor5 Yes Inspect the system and fix the error
No
Notes:
1. To check for insufficient refrigerant:
Re-start the outdoor units. If an r1, r2 or r3 error is displayed upon start-up, there is insufficient refrigerant in the system.
An insufficiency of refrigerant causes compressor discharge temperature to be higher than normal, discharge and suction pressures to be lower than
normal and compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. These issues disappear once
sufficient refrigerant has been charged into the system. For normal system parameters refer to Tables 5-5.4 and 5-5.5 in Part 5, 5.2 “Normal
Operating Parameters of Refrigerant System”.
2. A low pressure side blockage causes compressor discharge temperature to be higher than normal, suction pressure to be lower than normal and
compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. For normal system parameters refer to Tables 5-5.4 and
5-5.5 in Part 5, 5.2 “Normal Operating Parameters of Refrigerant System”.
3. In cooling mode check indoor heat exchangers, fans and air outlets for dirt/blockages. In heating mode check outdoor heat exchangers, fans and air outlets
for dirt/blockages.
201608 87
V5 X VRF 50/60Hz
4.18 xP3 Troubleshooting
4.18.1 Digital display output
'x' is a placeholder for the compressor system (compressor and related electrical components), with 1 representing
compressor system A and 2 representing compressor system B.
4.18.2 Description
1P3 indicates current protection on compressor A.
2P3 indicates current protection on compressor B.
When the compressor current rises above the protection value (E705DHD-72: 23A; E655DHD-65: 21A; E405DHD-36:
12A; E405DHD-42: 15A), the system displays P3 protection and all units stop running. When the current returns to the
normal range, P3 is removed and normal operation resumes.
Error code is only displayed on the unit with the error.
Midea V5 X Series Service Manual
4.18.4 Procedure
xP3
ODU stop valves are closed Yes Open the stop valves
No
The power supply is abnormal Yes Check the power supply equipment
No
Sudden interruption of power to IDUs Yes Inspect the system and fix the error
No
Flowchart continued on next page …
88 201608
V5 X VRF 50/60Hz
… flowchart continued from previous page
The condenser heat exchange is poor4 Yes Inspect the system and fix the error
No
No
No
Notes:
1. An indoor load that is too large causes suction and discharge temperatures to be higher than normal. For normal system parameters refer to Tables 5-5.4
and 5-5.5 in Part 5, 5.2 “Normal Operating Parameters of Refrigerant System”.
2. To check for excess refrigerant:
Re-start the outdoor units. If an R1 or R2 error is displayed upon start-up, there is excess refrigerant in the system.
Excess refrigerant causes discharge temperature to be lower than normal, discharge pressure to be higher than normal and suction pressure to be
higher than normal. For normal system parameters refer to Tables 5-5.4 and 5-5.5 in Part 5, 5.2 “Normal Operating Parameters of Refrigerant
System”.
3. Air or nitrogen in the system causes discharge temperature to be higher than normal, discharge pressure to be higher than normal, compressor current to
be higher than normal, abnormal compressor noise and an unsteady pressure meter reading. For normal system parameters refer to Tables 5-5.4 and 5-5.5
in Part 5, 5.2 “Normal Operating Parameters of Refrigerant System”.
4. In cooling mode check outdoor heat exchangers, fans and air outlets for dirt/blockages. In heating mode check indoor heat exchangers, fans and air outlets
for dirt/blockages.
5. High pressure side blockage causes discharge temperature to be higher than normal, discharge pressure to be higher than normal and suction pressure to
be lower than normal. For normal system parameters refer to Tables 5-5.4 and 5-5.5 in Part 5, 5.2 “Normal Operating Parameters of Refrigerant System”.
6. Set a multi-meter to buzzer mode and test any two terminals of P N and U V W of the inverter module. If the buzzer sounds, the inverter module has
short-circuited. Refer to Figures 5-1.1 and 5-1.3 in Part 5, 1 “Outdoor Unit Electric Control Box Layout” and to Figure 5-4.1 in Part 5, 4.6 “E5
Troubleshooting”.
7. The normal resistances of the inverter compressor are 0.7-1.5Ω among U V W and infinite between each of U V W and ground. If any of the resistances
differ from these specifications, the compressor has malfunctioned. Refer to Figures 5-4.6 and 5-4.7 in Part 5, 4.11.6 “xL0 troubleshooting”.
201608 89
V5 X VRF 50/60Hz
4.19 P5 Troubleshooting
4.19.1 Digital display output
4.19.2 Description
Outdoor heat exchanger temperature protection. When the outdoor heat exchanger temperature rises above 65oC,
the system displays P5 protection and all units stop running. When the temperature returns to the normal range, P5 is
removed and normal operation resumes.
Error code is only displayed on the unit with the error.
90 201608
V5 X VRF 50/60Hz
4.19.4 Procedure
P5
ODU stop valves are closed Yes Open the stop valves
No
Outdoor heat exchanger temperature Yes Ensure the sensor is connected properly
sensor connection on main PCB is loose1
No
The condenser heat exchange is poor5 Yes Inspect the system and fix the error
No
The high pressure side is blocked, caused Yes Inspect the system and fix the error
by crushed or bent pipe or blocked EXV6
No
Notes:
1. Outdoor heat exchanger temperature sensor connection is port CN1 on the main PCB (labeled 32 in Figure 5-2.1 in Part 5, 2.2 “Ports”).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Part 2, 1 “Layout of Functional Components” and to Table 5-5.1 in Part 5, 5.1 “Temperature Sensor
Resistance Characteristics”.
3. An indoor load that is too large causes suction and discharge temperatures to be higher than normal. For normal system parameters refer to Tables 5-5.4
and 5-5.5 in Part 5, 5.2 “Normal Operating Parameters of Refrigerant System”.
4. Air or nitrogen in the system causes discharge temperature to be higher than normal, discharge pressure to be higher than normal, compressor current to
be higher than normal, abnormal compressor noise and an unsteady pressure meter reading. For normal system parameters refer to Tables 5-5.4 and 5-5.5
in Part 5, 5.2 “Normal Operating Parameters of Refrigerant System”.
5. In cooling mode check outdoor heat exchangers, fans and air outlets for dirt/blockages. In heating mode check indoor heat exchangers, fans and air outlets
for dirt/blockages.
6. High pressure side blockage causes discharge temperature to be higher than normal, discharge pressure to be higher than normal and suction pressure to
be lower than normal. For normal system parameters refer to Tables 5-5.4 and 5-5.5 in Part 5, 5.2 “Normal Operating Parameters of Refrigerant System”.
201608 91
V5 X VRF 50/60Hz
4.20 P9, H9 Troubleshooting
4.20.1 Digital display output
4.20.2 Description
P9 indicates fan module protection. All units stop running.
H9 indicates that P9 protection has occurred 3 times in 60 minutes. When an H9 error occurs, a manual system restart
is required before the system can resume operation. The cause of an H9 error should be addressed promptly in order
to avoid system damage.
Error code is only displayed on the unit with the error.
Midea V5 X Series Service Manual
4.20.4 Procedure
P9 / H9
The capacity set on switch ENC2 on the Ensure the setting on switch ENC2
main PCB and the capacity given on the matches the unit capacity given on the
unit’s nameplate do not match1 unit’s nameplate
No
92 201608
V5 X VRF 50/60Hz
… flowchart continued from previous page
The power supply is abnormal Yes Check the power supply equipment
No
201608 93
V5 X VRF 50/60Hz
4.21 PL, C7 Troubleshooting
4.21.1 Digital display output
4.21.2 Description
PL indicates inverter module temperature protection. When the main inverter module temperature rises above 80oC,
the system displays PL protection and all units stop running.
C7 indicates PL protection has occurred 3 times in 100 minutes. When a C7 error occurs, a manual system restart is
required before the system can resume operation.
Error code is only displayed on the unit with the error.
Midea V5 X Series Service Manual
94 201608
V5 X VRF 50/60Hz
4.21.4 Procedure
PL / C7
The inverter module heat sink is blocked Yes Clean or replace the heat sink
or dirty1
No
The screws connecting the heat sink to Yes Tighten the screws and make sure the
the inverter module are loose2 heat sink is well-connected
No
Inverter module temperature sensor Yes Ensure the sensor is connected properly
connection on main PCB is loose3
No
Notes:
1. Refer to Figures 5-1.1 and 5-1.3 in Part 5, 1 “Outdoor Unit Electric Control Box Layout”.
2. Refer to Figures 5-1.1 and 5-1.3 in Part 5, 1 “Outdoor Unit Electric Control Box Layout”.
3. Inverter module temperature sensor connection is port CN4 on the main PCB (labeled 3 in Figure 5-2.1 in Part 5, 2.2 “Ports”).
4. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Figures 5-1.1 and 5-1.3 in Part 5, 1 “Outdoor Unit Electric Control Box Layout” and to Table 5-5.3 in Part
5, 5.1 “Temperature Sensor Resistance Characteristics”.
201608 95
V5 X VRF 50/60Hz
4.22 PP, F0 Troubleshooting
4.22.1 Digital display output
4.22.2 Description
PP indicates compressor discharge insufficient superheat protection. When the discharge gas superheat is ≤0°C for 20
minutes or ≤5°C for 60 minutes, the system displays PP protection and all units stop running.
F0 indicates PP protection has occurred 3 times in 150 minutes. When an F0 error occurs, a manual system restart is
required before the system can resume operation.
Error code is only displayed on the unit with the error.
Midea V5 X Series Service Manual
96 201608
V5 X VRF 50/60Hz
4.22.4 Procedure
PP / F0
No
Notes:
1. Compressor top temperature sensor and discharge pipe temperature sensor connections are ports CN10 and CN11 on the main PCB (labeled 1 and 2,
respectively, in Figure 5-2.1 in Part 5, 2.2 “Ports”).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Part 2, 1 “Layout of Functional Components” and to Table 5-5.2 in Part 5, 5.1 “Temperature Sensor
Resistance Characteristics”.
3. To check for excess refrigerant:
Re-start the outdoor units. If an R1 or R2 error is displayed upon start-up, there is excess refrigerant in the system.
Excess refrigerant causes discharge temperature to be lower than normal, discharge pressure to be higher than normal and suction pressure to be
higher than normal. For normal system parameters refer to Tables 5-5.4 and 5-5.5 in Part 5, 5.2 “Normal Operating Parameters of Refrigerant
System”.
4. See Part 5, 4.16 “P1 Troubleshooting”.
201608 97
V5 X VRF 50/60Hz
4.23 xF1 Troubleshooting
4.23.1 Digital display output
'x' is a placeholder for the compressor system (compressor and related electrical components), with 1 representing
compressor system A and 2 representing compressor system B.
4.23.2 Description
1F1 indicates compressor A DC bus voltage error.
2F1 indicates compressor B DC bus voltage error.
When the DC bus voltage is outside the range 300-800V continuously for 10 seconds, the system displays the F1 error
code and all units stop running.
Error code is only displayed on the unit with the error.
Reactor damaged.
Power supply abnormal. DC filter board damaged.
Contactor damaged. Inverter module damaged.
Three-phase bridge rectifier damaged. Main PCB damaged.
4.23.4 Procedure
xF1
Wires between
inverter module
Voltage between +15V and N pins of voltage monitor port
inverter module voltage monitor port on Yes on main PCB and No Replace the inverter module
main PCB is abnormal1 voltage monitor port
on inverter module
are loose3
Yes
98 201608
V5 X VRF 50/60Hz
… flowchart continued from previous page
No
Wires between DC filter board and Yes Ensure the wires are
inverter module are loose connected properly
No
Voltage between
No No
Notes:
1. Inverter module voltage monitor ports are ports CN36 and CN38 on the main PCB (labeled 22 and 21, respectively, in Figure 5-2.1 in Part 5, 2.2 "Ports").
The normal voltage between the +15V and N pins is 15V DC. Refer to Figure 5-4.19.
2. Inverter module voltage monitor ports are ports CN36 and CN38 on the main PCB (labeled 22 and 21, respectively, in Figure 5-2.1 in Part 5, 2.2 "Ports").
The normal voltage between the P and N pins should be between 300V and 800V. Refer also to Figure 5-4.19.
Figure 5-4.19: Inverter module voltage monitor ports
300-800V 300-800V
15V 15V
201608 99
V5 X VRF 50/60Hz
3. Voltage monitor port is port CN5 on the inverter module. Refer to Figure 5-4.20.
P U V W N
4. Refer to Figures 5-1.1 to 5-1.4 in Part 5, 1 “Outdoor Unit Electric Control Box Layout” and to the V5 X Engineering Data Book, Part 2, 5 “Wiring Diagrams”.
5. Power output port is port CN54 on the main PCB (labeled 16, in Figure 5-2.1 in Part 5, 2.2 "Ports"). Neutral terminals are terminals CN57-59 on the main
PCB (labeled 17, in Figure 5-2.1 in Part 5, 2.2 "Ports")
Midea V5 X Series Service Manual
100 201608
V5 X VRF 50/60Hz
5 Appendix to Part 5
5.1 Temperature Sensor Resistance Characteristics
Table 5-5.1: Outdoor ambient temperature sensor and outdoor heat exchanger temperature sensor resistance characteristics
Temperature Resistance Temperature Resistance Temperature Resistance Temperature Resistance
(°C) (kΩ) (°C) (kΩ) (°C) (kΩ) (°C) (kΩ)
-20 115.3 20 12.64 60 2.358 100 0.6297
-19 108.1 21 12.06 61 2.272 101 0.6115
-18 101.5 22 11.50 62 2.191 102 0.5939
-17 96.34 23 10.97 63 2.112 103 0.5768
-16 89.59 24 10.47 64 2.037 104 0.5604
-15 84.22 25 10.00 65 1.965 105 0.5445
-14 79.31 26 9.551 66 1.896 106 0.5291
-13 74.54 27 9.124 67 1.830 107 0.5143
-12 70.17 28 8.720 68 1.766 108 0.4999
-11 66.09 29 8.336 69 1.705 109 0.4860
201608 101
V5 X VRF 50/60Hz
Table 5-5.2: Compressor top temperature sensor and discharge pipe temperature sensor resistance characteristics
Temperature Resistance Temperature Resistance Temperature Resistance Temperature Resistance
(°C) (kΩ) (°C) (kΩ) (°C) (kΩ) (°C) (kΩ)
102 201608
V5 X VRF 50/60Hz
Table 5-5.3: Inverter module temperature sensor resistance characteristics
Temperature Resistance Temperature Resistance Temperature Resistance Temperature Resistance
(°C) (kΩ) (°C) (kΩ) (°C) (kΩ) (°C) (kΩ)
201608 103
V5 X VRF 50/60Hz
5.2 Normal Operating Parameters of Refrigerant System
Under the following conditions, the operating parameters given in Tables 5-5.4 and 5-5.5 should be observed:
The master outdoor unit can detect all the indoor units.
The number of indoor units displayed on DSP2 is steady and is equal to the actual number of indoor units installed.
All stop valves are open and all indoor unit EXVs are connected to their unit’s PCB.
If the combination ratio is 100% or less, all the indoor units are currently running and if the combination ratio is more
than 100%, indoor units with total capacity equal to the total capacity of the outdoor units are currently running.
If the outdoor ambient temperature is high, the system is being run in cooling mode with the following settings:
temperature 17°C; fan speed high.
If the outdoor ambient temperature is low, the system is being run in heating mode with the following settings:
temperature 30°C; fan speed high.
The system has been running normally for more than 30 minutes.
104 201608
Commercial Air Conditioner Division
Midea Group
Add.: Midea Headquarters Building, 6 Midea Avenue, Shunde, Foshan, Guangdong, China
cac.midea.com global.midea.com
Note: Product specifications change from time to time as product improvements and
iOS Version Android Version iOS Version developments are released and may vary from those in this document.