Additional Reference
Cover Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V10-T5-18
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Tab 14
Accessories and Modifications . . . . . . . . . . . . . . . Tab 15
Technical Data and Specifications . . . . . . . . . . . . . Tab 17
EC S 90 S 1 C A A -
Modification Codes
See Tab 15
Type
S = Solid-state Disconnect Fuse Clip Ratings
A= None G = 100A/600V R N= 600A/600V R 5
B= 30A/250V R H = 200A/250V R P= 800A/600V L
Class Page C= 30A/600V R J = 200A/600V R Q= 1200A/600V L
D= 60A/250V R K = 400A/250V R R= 1600A/600V L
90 = Non-combination reduced voltage V10-T5-19 E= 60A/600V R L = 400A/600V R S= 2000A/600V L
soft starter—S801+ F= 100A/250V R M = 600A/250V R T= By description
91 = Combination reduced voltage V10-T5-23 Breaker
soft starter—fusible disconnect—S801+
A= None F = 50A K= 400A
92 = Combination reduced voltage V10-T5-27 B= 3A W = 70A L= 600A
soft starter—circuit breaker—S801+ C= 7A G = 100A P= 1200A
93 = Non-combination reduced voltage V10-T5-21 D= 15A H = 150A Q= 1600A
soft starter—S811+ E= 30A J = 250A
94 = Combination reduced voltage V10-T5-25
soft starter—fusible disconnect—S811+
95 = Combination reduced voltage V10-T5-29 Cover Control
soft starter—circuit breaker—S811+
See Page V10-T5-18 for options
Amps Voltage
S801+/S811+ B = 230V E = 200V
Enclosure Type C = 460V Q = 24 Vdc
Q= 37 Z = 240 5= 650
S= 66 1 = 304 6= 720 1= Type 1 D = 575V
V= 105 2 = 360 7= 850 2= Type 3R
W= 135 3 = 420 8= 1000 3= Type 4
Y= 180 4 = 500 4= Type 4X (304-Grade SS)
6= Type 7/9
8= Type 12
9= Type 4X 316-Grade SS)
Cover Control
Flange Control Kits Factory Installed Pilot
For on-the-job conversion of Devices
Type 1, 3R, 4, 4X and 12 To order factory installed pilot
enclosed starters. Knockouts devices, change the ninth
are provided on the Type 1 character of the catalog
flange. Type 3R, 4, 4X and 12 number to the alpha shown in
have prepunched holes with the table below. Example: To
removable hole plugs. order an ECS90J4CAA with
5 START/STOP pushbuttons
and a red pilot light, change
the A to a C, that is,
ECS90J4CCA.
Note
1 Add code letter from the table below to catalog number for voltage—kits only. Example: C400T9B.
Notes
1 Standard duty horsepower ratings are for 300% ramp current, 30 seconds ramp time, and three starts per hour. Consult Eaton for other ratings.
2 Based on 1.15 service factor.
3 All IT. soft starters are furnished with 24 Vdc coils and control power supplies. For 24 Vdc separate control, use modification code C35 and change
Example: ECS90S4EAA. To order Type 4X 316-Grade stainless steel, change that digit to 9. To order Type 4 painted steel, change that digit to 3.
To order non-metallic, change that digit to 5. For details on these alternate enclosures, see Tab 13.
Notes
1 Standard duty horsepower ratings are for 300% ramp current, 30 seconds ramp time, and three starts per hour. Consult Eaton for other ratings.
2 Based on 1.15 service factor.
3 All IT. soft starters are furnished with 24 Vdc coils and control power supplies. For 24 Vdc separate control, use modification code C35 and change
Example: ECS90S4EAA. To order Type 4X 316-Grade stainless steel, change that digit to 9. To order Type 4 painted steel, change that digit to 3.
To order non-metallic, change that digit to 5. For details on these alternate enclosures, see Tab 13.
Component Soft
Motor Coil Type 1 Type 3R Type 4X 5 Type 7/9 Type 12 Starter (Open)
Amps Voltage hp 23 Voltage 4 Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number
Frame Size—65 mm
37A 200V 10 24 Vdc ECS93Q1EAA ECS93Q2EAA ECS93Q4EAA ECS93Q6EAA ECS93Q8EAA S811+N37N3S
230V 10 ECS93Q1BAA ECS93Q2BAA ECS93Q4BAA ECS93Q6BAA ECS93Q8BAA
460V 20 ECS93Q1CAA ECS93Q2CAA ECS93Q4CAA ECS93Q6CAA ECS93Q8CAA
575V 30 ECS93Q1DAA ECS93Q2DAA ECS93Q4DAA ECS93Q6DAA ECS93Q8DAA 5
66A 200V 15 24 Vdc ECS93S1EAA ECS93S2EAA ECS93S4EAA ECS93S6EAA ECS93S8EAA S811+N66N3S
230V 20 ECS93S1BAA ECS93S2BAA ECS93S4BAA ECS93S6BAA ECS93S8BAA
460V 40 ECS93S1CAA ECS93S2CAA ECS93S4CAA ECS93S6CAA ECS93S8CAA
575V 50 ECS93S1DAA ECS93S2DAA ECS93S4DAA ECS93S6DAA ECS93S8DAA
Frame Size—110 mm
105A 200V 25 24 Vdc ECS93V1EAA ECS93V2EAA ECS93V4EAA ECS93V6EAA ECS93V8EAA S811+R10N3S
230V 30 ECS93V1BAA ECS93V2BAA ECS93V4BAA ECS93V6BAA ECS93V8BAA
460V 60 ECS93V1CAA ECS93V2CAA ECS93V4CAA ECS93V6CAA ECS93V8CAA
575V 75 ECS93V1DAA ECS93V2DAA ECS93V4DAA ECS93V6DAA ECS93V8DAA
135A 200V 30 24 Vdc ECS93W1EAA ECS93W2EAA ECS93W4EAA ECS93W6EAA ECS93W8EAA S811+R13N3S
230V 40 ECS93W1BAA ECS93W2BAA ECS93W4BAA ECS93W6BAA ECS93W8BAA
460V 75 ECS93W1CAA ECS93W2CAA ECS93W4CAA ECS93W6CAA ECS93W8CAA
575V 100 ECS93W1DAA ECS93W2DAA ECS93W4DAA ECS93W6DAA ECS93W8DAA
Frame Size—200 mm
180A 200V 50 24 Vdc ECS93Y1EAA ECS93Y2EAA ECS93Y4EAA ECS93Y6EAA ECS93Y8EAA S811+T18N3S
230V 60 ECS93Y1BAA ECS93Y2BAA ECS93Y4BAA ECS93Y6BAA ECS93Y8BAA
460V 125 ECS93Y1CAA ECS93Y2CAA ECS93Y4CAA ECS93Y6CAA ECS93Y8CAA
575V 150 ECS93Y1DAA ECS93Y2DAA ECS93Y4DAA ECS93Y6DAA ECS93Y8DAA
240A 200V 60 24 Vdc ECS93Z1EAA ECS93Z2EAA ECS93Z4EAA ECS93Z6EAA ECS93Z8EAA S811+T24N3S
230V 75 ECS93Z1BAA ECS93Z2BAA ECS93Z4BAA ECS93Z6BAA ECS93Z8BAA
460V 150 ECS93Z1CAA ECS93Z2CAA ECS93Z4CAA ECS93Z6CAA ECS93Z8CAA
575V 200 ECS93Z1DAA ECS93Z2DAA ECS93Z4DAA ECS93Z6DAA ECS93Z8DAA
304A 200V 75 24 Vdc ECS9311EAA ECS9312EAA ECS9314EAA ECS9316EAA ECS9318EAA S811+T30N3S
230V 100 ECS9311BAA ECS9312BAA ECS9314BAA ECS9316BAA ECS9318BAA
460V 200 ECS9311CAA ECS9312CAA ECS9314CAA ECS9316CAA ECS9318CAA
575V 250 ECS9311DAA ECS9312DAA ECS9314DAA ECS9316DAA ECS9318DAA
Notes
1 Digital Interface Module (DIM) is mounted on door as option.
2 Standard duty horsepower ratings are for 300% ramp current, 30 seconds ramp time, and three starts per hour. Consult Eaton for other ratings.
3 Based on 1.15 service factor.
4 All IT. soft starters are furnished with 24 Vdc coils and control power supplies. For 24 Vdc separate control, use modification code C35 and change
Example: ECS93S4EAA. To order Type 4X 316-Grade stainless steel, change that digit to 9. To order Type 4 painted steel, change that digit to 3.
To order non-metallic, change that digit to 5. For details on these alternate enclosures, see Tab 13.
Component Soft
Motor Coil Type 1 Type 3R Type 4X 5 Type 7/9 Type 12 Starter (Open)
Amps Voltage hp 23 Voltage 4 Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number
Frame Size—290 mm
360A 200V 100 24 Vdc ECS9321EAA ECS9322EAA ECS9324EAA ECS9326EAA ECS9328EAA S811+V36N3S
230V 125 ECS9321BAA ECS9322BAA ECS9324BAA ECS9326BAA ECS9328BAA
460V 250 ECS9321CAA ECS9322CAA ECS9324CAA ECS9326CAA ECS9328CAA
5 575V 300 ECS9321DAA ECS9322DAA ECS9324DAA ECS9326DAA ECS9328DAA
420A 200V 125 24 Vdc ECS9331EAA ECS9332EAA ECS9334EAA ECS9336EAA ECS9338EAA S811+V42N3S
230V 150 ECS9331BAA ECS9332BAA ECS9334BAA ECS9336BAA ECS9338BAA
460V 300 ECS9331CAA ECS9332CAA ECS9334CAA ECS9336CAA ECS9338CAA
575V 350 ECS9331DAA ECS9332DAA ECS9334DAA ECS9336DAA ECS9338DAA
500A 200V 150 24 Vdc ECS9341EAA ECS9342EAA ECS9344EAA ECS9346EAA ECS9348EAA S811+V50N3S
230V 150 ECS9341BAA ECS9342BAA ECS9344BAA ECS9346BAA ECS9348BAA
460V 350 ECS9341CAA ECS9342CAA ECS9344CAA ECS9346CAA ECS9348CAA
575V 450 ECS9341DAA ECS9342DAA ECS9344DAA ECS9346DAA ECS9348DAA
650A 200V 200 24 Vdc ECS9351EAA ECS9352EAA ECS9354EAA ECS9356EAA ECS9358EAA S811+V65N3S
230V 200 ECS9351BAA ECS9352BAA ECS9354BAA ECS9356BAA ECS9358BAA
460V 450 ECS9351CAA ECS9352CAA ECS9354CAA ECS9356CAA ECS9358CAA
575V 500 ECS9351DAA ECS9352DAA ECS9354DAA ECS9356DAA ECS9358DAA
720A 230V 250 24 Vdc ECS9361BAA ECS9362BAA ECS9364BAA ECS9366BAA ECS9368BAA S811+V72N3S
460V 500 ECS9361CAA ECS9362CAA ECS9364CAA ECS9366CAA ECS9368CAA
575V 600 ECS9361DAA ECS9362DAA ECS9364DAA ECS9366DAA ECS9368DAA
850A 230V 300 24 Vdc ECS9371BAA ECS9372BAA ECS9374BAA ECS9376BAA ECS9378BAA S811+V85N3S
460V 600 ECS9371CAA ECS9372CAA ECS9374CAA ECS9376CAA ECS9378CAA
575V 700 ECS9371DAA ECS9372DAA ECS9374DAA ECS9376DAA ECS9378DAA
1000A 230V 350 24 Vdc ECS9381BAA ECS9382BAA ECS9384BAA ECS9386BAA ECS9388BAA S811+V10N3S
460V 700 ECS9381CAA ECS9382CAA ECS9384CAA ECS9386CAA ECS9388CAA
575V 800 ECS9381DAA ECS9382DAA ECS9384DAA ECS9386DAA ECS9388DAA
Notes
1 Digital Interface Module (DIM) is mounted on door as option.
2 Standard duty horsepower ratings are for 300% ramp current, 30 seconds ramp time, and three starts per hour. Consult Eaton for other ratings.
3 Based on 1.15 service factor.
4 All IT. soft starters are furnished with 24 Vdc coils and control power supplies. For 24 Vdc separate control, use modification code C35 and change
Example: ECS93S4EAA. To order Type 4X 316-Grade stainless steel, change that digit to 9. To order Type 4 painted steel, change that digit to 3.
To order non-metallic, change that digit to 5. For details on these alternate enclosures, see Tab 13.
Notes
1 Standard duty horsepower ratings are for 300% ramp current, 30 seconds ramp time, and three starts per hour. Consult Eaton for other ratings.
2 Based on 1.15 service factor.
3 All IT. soft starters are furnished with 24 Vdc coils and control power supplies. For 24 Vdc separate control, use modification code C35 and change
Example: ECS91S4EAA. To order Type 4X 316-Grade stainless steel, change that digit to 9. To order Type 4 painted steel, change that digit to 3.
To order non-metallic, change that digit to 5. For details on these alternate enclosures, see Tab 13.
Notes
1 Standard duty horsepower ratings are for 300% ramp current, 30 seconds ramp time, and three starts per hour. Consult Eaton for other ratings.
2 Based on 1.15 service factor.
3 All IT. soft starters are furnished with 24 Vdc coils and control power supplies. For 24 Vdc separate control, use modification code C35 and change
Example: ECS91S4EAA. To order Type 4X 316-Grade stainless steel, change that digit to 9. To order Type 4 painted steel, change that digit to 3.
To order non-metallic, change that digit to 5. For details on these alternate enclosures, see Tab 13.
5 Consult Eaton.
Notes
1 Digital Interface Module (DIM) is mounted on door as option.
2 Standard duty horsepower ratings are for 300% ramp current, 30 seconds ramp time, and three starts per hour. Consult Eaton for other ratings.
3 Based on 1.15 service factor.
4 All IT. soft starters are furnished with 24 Vdc coils and control power supplies. For 24 Vdc separate control, use modification code C35 and change
Example: ECS94S4EAA. To order Type 4X 316-Grade stainless steel, change that digit to 9. To order Type 4 painted steel, change that digit to 3.
To order non-metallic, change that digit to 5. For details on these alternate enclosures, see Tab 13.
Notes
1 Digital Interface Module (DIM) is mounted on door as option.
2 Standard duty horsepower ratings are for 300% ramp current, 30 seconds ramp time, and three starts per hour. Consult Eaton for other ratings.
3 Based on 1.15 service factor.
4 All IT. soft starters are furnished with 24 Vdc coils and control power supplies. For 24 Vdc separate control, use modification code C35 and change
Example: ECS94S4EAA. To order Type 4X 316-Grade stainless steel, change that digit to 9. To order Type 4 painted steel, change that digit to 3.
To order non-metallic, change that digit to 5. For details on these alternate enclosures, see Tab 13.
6 Consult Eaton.
Notes
1 Standard duty horsepower ratings are for 300% ramp current, 30 seconds ramp time, and three starts per hour. Consult Eaton for other ratings.
2 Based on 1.15 service factor.
3 All IT. soft starters are furnished with 24 Vdc coils and control power supplies. For 24 Vdc separate control, use modification code C35 and change
Example: ECS92S4EAA. To order Type 4X 316-Grade stainless steel, change that digit to 9. To order Type 4 painted steel, change that digit to 3.
To order non-metallic, change that digit to 5. For details on these alternate enclosures, see Tab 13.
Notes
1 Standard duty horsepower ratings are for 300% ramp current, 30 seconds ramp time, and three starts per hour. Consult Eaton for other ratings.
2 Based on 1.15 service factor.
3 All IT. soft starters are furnished with 24 Vdc coils and control power supplies. For 24 Vdc separate control, use modification code C35 and change
Example: ECS92S4EAA. To order Type 4X 316-Grade stainless steel, change that digit to 9. To order Type 4 painted steel, change that digit to 3.
To order non-metallic, change that digit to 5. For details on these alternate enclosures, see Tab 13.
Notes
1 Digital Interface Module (DIM) is mounted on door as option.
2 Standard duty horsepower ratings are for 300% ramp current, 30 seconds ramp time, and three starts per hour. Consult Eaton for other ratings.
3 Based on 1.15 service factor.
4 All IT. soft starters are furnished with 24 Vdc coils and control power supplies. For 24 Vdc separate control, use modification code C35 and change
Example: ECS95S4EAA. To order Type 4X 316-Grade stainless steel, change that digit to 9. To order Type 4 painted steel, change that digit to 3.
To order non-metallic, change that digit to 5. For details on these alternate enclosures, see Tab 13.
Notes
1 Digital Interface Module (DIM) is mounted on door as option.
2 Standard duty horsepower ratings are for 300% ramp current, 30 seconds ramp time, and three starts per hour. Consult Eaton for other ratings.
3 Based on 1.15 service factor.
4 All IT. soft starters are furnished with 24 Vdc coils and control power supplies. For 24 Vdc separate control, use modification code C35 and change
Example: ECS95S4EAA. To order Type 4X 316-Grade stainless steel, change that digit to 9. To order Type 4 painted steel, change that digit to 3.
To order non-metallic, change that digit to 5. For details on these alternate enclosures, see Tab 13.
T1
01 L1 L1 T1
T2
02 L2 L2 T2 Motor
T3
03 L3 L3 T3
IT. Soft Start
5
L1 L2 L3
Power Supply
480 Vac–24 Vdc Applying Voltages other than
+ + – –
24 Vdc to Terminals P Through 4
May Cause Serious Damage
(–) to Soft Start Control Board
Terminal Board
–
(+)
+
MX P
1
1
2 24V Inputs
DC Only
Reset 3
4
4
13
Run
14 Internal 24 Vdc
Customer 95 Auxiliary or
(+) 2 96 Contacts 120 Vac
Control MX 96
Device 98
+ –
(Diode) Fault
L N
120 Vac
Power Supply
24 Vdc (+) (–)
(+) (–)
(+) (–)
Power
Supply
+ – L1 L2 L3
1 3 5
Line Terminals
+ (+) Output
2 (+) 24 Vdc
(+) Customer P IT. Soft Starter - (–) 2.3A
Control (–)
Device 3
1 DC On
Reset 1 L Input
IT. Input/Output Terminal Block 120 Vac
(G) +15%
4
4
Fault X2 N 0.13A +15%
50–60 Hz
24 Vdc
IT. Soft Starter
– + P 1 2 3 4 13 14 95 96 98
Jog Fwd
– + 2 3 4
OL Override
Speed
(–)
(+)
2 Stop
4 Reset
3 Start
AT
– + P 1 2 3 4 (+) 4
13 14 95 96 98
Jog Fwd
Stop
Override
Reset
Start
24 Vdc
Load
OL
2 4 6 Reset
Terminals T1 T2 T3
Speed
Fault
AT
24 Vdc Only
IT. Input/Output Terminal Block