Role of Automatic Generation Control (AGC) in Energy Management System
Role of Automatic Generation Control (AGC) in Energy Management System
INTRODUCTION
1.1 Overview
For large-scale power systems, which normally consist of interconnected control area, Load
Frequency Control (LFC) is important to keep the system frequency and the inter-area tie
power as close as possible to the scheduled values. The mechanical input power to the
generators is used to control the frequency of output electrical power and to maintain the
power exchange between the areas as scheduled. In a different kinds of uncertainties and
various disturbances due to increased complexity, system modelling errors changes power
system structure. A well designed and operated power system should come up with changes
in the load and with system disturbances, and it should provide acceptable high level of power
quality while maintaining both voltage and frequency within tolerable Limit.The early
stability problems of ac systems were experienced in 1920 when insufficient damping caused
spontaneous oscillations or hunting. These problems were solved using generator damper
winding and the use of turbine-type prime movers. The stability of a system refers to the
ability of a system to return back to its steady state when subjected to a disturbance. As power
is generated by synchronous generators that operates in synchronism with rest of the system.
A generator is synchronized with a bus only when both of them have same frequency, voltage
and phase sequence.
1.2 Objectives
The quality of the power supply is determined by the constancy of frequency and voltage.
Minimum frequency deviation and good terminal voltage response are the characteristics of a
reliable power supply. LFC is vital for any interconnected power system in order to maintain
constant frequency and tie line power flow between areas at prescheduled limits. The
conventional controllers used for this problem have large settling time, overshoot and
oscillations. The proposed PID controller and PID-PSS provides a satisfactory stability
between frequency overshoot and transient oscillations with zero steady state error.
1
CHAPTER-2
INTRODUCTION
3.1 Role Of Automatic Generation Control (AGC) in Energy Management System
(EMS)
In the modern Energy Management Systems (EMS) automatic load frequency control system
(ALFC) is part of Automatic Generation Control (AGC). In power systems, where automatic
control does not exist, manual control of set points is done on instructions from dispatch
centre. An EMS unit showing in fig.3.1, generally has a centralised digital computer system
connected to Remote Terminal Unit(RTU’s)via communication channels.Functions such as
contigency analysis ,optimal load flow ,security analysis expert systems,etc. are centrally
located.Data from various generating stations and substations is received by the central
computer.The software in the EMS analyses the off-circuit and the real time data and sends
appropriate instructions to various sub-station control room and generating station control
rooms. The EMS may also provide the interfaces with the Enterprise Business system with
the Business Process integration [21].
2
iii). Data monitoring equipment.
iv). Man/machine interface.
The data (information) regarding various power-system variables is necessary for
effectiveness supervision, operation and control [21, 35].Various components linked to
SCADA are showing in fig.3.2.
3.3 EMS Position in the Power Grid
Figure 3.3: Power system showing fault and its effect on stability [15]
External factors, such as lightning, can also cause disturbances to the power system. All these
disturbances are termed as faults. When a fault occurs, it causes the motor to lose
synchronism if the natural frequency of oscillation coincides with the frequency of oscillation
of the generators. With these factors in mind, the basic condition for a power system with
stability is synchronism. An important problem in stability of power systems is the excitation
control of synchronous machines. It is one of the most effective and economic techniques for
enhancing the dynamic performance and transient stability of power systems [28].The
stability problem is concerned with the behavior of the synchronous machines after a
5
disturbance .Broadly stability is of three types as in fig.3.4, but for convenience of analysis,
stability is generally divided into two major categories steady-state stability and transient
stability.
6
cater to more users at lower prices and better power efficiency [19]. Load demand also
increases linearly with the increase in users. Since stability phenomena limits the transfer
capability of the system, there is a need to ensure stability and reliability of the power system
due to economic reasons [16].
3.5.2 Stability Types
3.5.2.1 Transient (angle) stability
Cause: Occurs due to large disturbance angle stability imbalance between accelerating torque
and load torque on (groups of) generators caused by outage of major generator, line,
transformer, bus-bar, and load.
Effects: It leads to loss of synchronism, frequency instability, system separation and/or
blackout.
3.5.2.2 Small signal (angle) stability or small disturbance angle stability
Cause: Occurs due to insufficient damping of electro-mechanical dynamics causes
oscillations with low or negative damping.
Effects: It leads to transient instability, loss of synchronism, system separation and/or
blackout.
3.5.2.3 Voltage stability or Load stability or Transient Voltage stability or Small signal
Voltage stability
Cause: Occurs due to insufficient reactive power supply due to system overload.
Effects: It leads to voltage collapse, excessive currents, system separation and/or blackout.
3.5.2.4 Frequency stability
Cause: Occurs due to turbine controllers do not manage to stabilize system frequency.
Effects: It leads to system separation or blackout.
3.6 Stability Theories
The main objective of stability studies is to determine whether the rotor of the machines
being disturbed return to the original constant speed operation [19].There are three
assumptions that are made in stability studies:
i). Consider the synchronous currents and voltages in the stator windings and the power
system. DC offsets and harmonic components are neglected.
ii). To represent unbalanced faults, symmetrical components are used.
7
iii). The generated voltage is considered to be unaffected by the speed variations of the
Machine [18].
3.6.1 Swing Equation
The Swing Equation governs the rotational dynamics of the synchronous machine in stability
studies .Under normal operating conditions, the relative position of the rotor axis and the
resultant axis is fixed. The angle difference between the two axes is known as the power
angle [38]. During disturbance to the machine, the rotor accelerates or decelerates with
respect to the synchronous rotating air gap mmf. The “Swing” equation describes this relative
motion. If the rotor is able to resume its synchronous speed after this oscillation period, the
generator will maintain its stability. The rotor will return to its original position if the
disturbance is not created by any net changes in the power. However if the disturbance is
created by a change in generation, load or network conditions, the rotor will be in a new
operation power angle relative to the revolving field[20].
The Swing Equation (pu) is given as:
2 H d 2
Pm ( pu ) Pe ( pu ) ……. (3.1)
s dt 2
Where,
H is pu inertia constant
ωs is electrical synchronous speed
δ is electrical power angle
Pm is shaft mechanical power input
Pe is electrical power
d2δ /dt2 is angular acceleration
The swing equation is a non-linear function of the power angle. However, for small
disturbances, the swing equation may be linearized with little loss of accuracy.
3.6.2 Equal Area Criterion
Equal Area Criterion is a stability method used for quick prediction of stability [16]. Based
on the assumptions that the system is a purely reactive, In fig.3.5, a constant Pm and constant
voltage behind transient reactance, it is found that if the transient stability limit is not
exceeded the electrical power angle δ oscillates around the equilibrium point with constant
8
amplitude. Equal Area Criterion is the method which determines stability under transient
conditions [21].
Figure 3.5: Electric power input to a motor as a function of torque angle δ [21]
Originally the motor of the machine is operating at the synchronous speed with a torque angle
of δ0. The mechanical power output Pm0 is equal to the electrical power input Pe. When the
mechanical load is suddenly increased so that the power output is P m1, it is greater than the
electrical power input at δ0. The difference in the power comes from the kinetic energy stored
in the rotating system. Thus, it results in a decrease in speed. When the speed decreases, it
will cause the torque angle δ to increase [14].As δ increases, the electrical power received
will increase to a point where Pe = Pm1. The fig.3.6 shows when the load is suddenly increased
from Pm0 to Pm1 , the motor will oscillate around δ1 and between δ0 and δ2 E. It can be named
as Point B. After passing through Point B the electrical power P e is greater than P m1. This
will result in an increase in kinetic energy and speed. Thus between Point B and C, the speed
will increase accordingly with δ , until the synchronous speed is again reached at Point C. At
Point C, the torque angle is δm. Pe is still greater than P m1 and the speed of the motor will
continue to increase [21].
9
Figure 3.6: Electric power to a motor showing three points A,B,C [21]
However, δ will start to decrease as soon as the speed of the motor exceeds the synchronous
speed. Therefore the maximum value of δ is at Point C.As δ increases, Point B is reached
again with the speed above the synchronous speed. The torque angle δ will continue to
decrease until Point is achieved. This implies that the motor is again operating at synchronous
speed. The cycle is then repeated. When the accelerating area (AA) is equal to the
decelerating area (DA), the system is considered as stable [16].
3.7 Power system frequency control: Indian scenario
In India, the power system is divided into 5 regions. Load Dispatch Center in each region
monitors the frequency by interacting with State Load Dispatch Centers and generating
stations under the control of States and the generating companies like NTPC, NHPC. The
Regional Load Dispatch Centers (RLDC) functions under Power Grid Corporation of India.
So, for the purpose of frequency each region can be considered as one coherent unit. For
instance Southern RLDC comprises AP, TN, Karnataka, Kerala and Goa. SRLDC is located
in Bangalore [54].Frequency is controlled by balancing the load with generation. The
governors on every generator senses any change in the rotational speed and adjusts the
mechanical input power. This governor control is the primary control for maintaining
frequency. A secondary control to set the governor set-points is used to ensure that the steady
state always returns to 50Hz. The governor control is local at the generator and fast. The
secondary control is done over the whole system. This secondary control is done by the
central controller and is slow. This control is also known as Automatic Generation Control
(AGC) or Load Frequency Control (LFC) [17]. For the load frequency control the generating
10
units at Hydro power plant are normally adjusted as the response is faster to raise/lower the
power. Load–Generation imbalance causes frequency variation. Load is never constant.
Precise frequency control is possible only if there is a surplus generating capacity, which is
not the case in many states. Hence load shedding is resorted to for frequency management.
There is no automatic load frequency control in many regions as many utilities want to
generate to the maximum possible extent and would not like their generation levels adjusted
by ALFC [3]. Mostly manual control is only exercised to maintain frequency. In many cases,
generators are not allowed to participate in primary regulation also i.e., the natural tendency
of the governors to raise/ lower generation when frequency falls/rises is suppressed. With the
result, frequency is always less than the rated value of 50 Hz. When sudden disturbances
occur, system collapses causing blackouts [53].
3.8 Power System Stability
In power system both active and reactive power demands are never steady they continuously
changes with rising or falling trend. Steam input to turbo generators must therefore, be
continuously regulated to match the active power demand, failing which the machine speed
will vary with consequent change in frequency, which may be highly undesirable. In brief,
the changes in real power affects the system frequency, while reactive power is less sensitive
towards frequency and is mainly dependent on changes in voltage magnitude. The LFC [1]
(load frequency control) loop controls the real power and frequency and AVR [2] (automatic
voltage regulator) loop regulates the reactive power and voltage magnitude [36].
11
regular system, since such a large deviation from the nominal 50 Hz can be harmful for
certain components in the power supply system. If the frequency continues to drop, one runs
the risk of a total system blackout. Because of this, all power stations are equipped with a
frequency meter that measures the system frequency. The frequency signal is fed-back to a
piece of equipment called the turbine governor [18]. It shows that sees to that the guide vanes
are further opened or closed, depending on the sign of the frequency deviation. An
adjustment of the guide vanes of the hydro station means that the discharge through the
station is changed. That is, the mechanical power input will be changed as a response to the
varying power consumption [15]. This type of control is called droop or direct control, since
the change in mechanical input power will be directly proportional to the frequency
deviation. With droop control, In fig.3.7, the new mechanical input power becomes
ΔPm = −RΔω ……. (3.2)
where R is referred as the gain of the power system. The droop control in real power systems
is an automatic action that is usually referred to as primary control. The system gain is
divided between hundreds of generating units, many of them hydro units.
12
Figure.3.8: Block diagram of a Hydro-Power system with Primary control [35]
In power systems, this is accomplished by starting up a new generating unit or by changing
the production set values of the units which are already in operation. In secondary control, it
changes the set value of the generating unit in order to push the system back to nominal
frequency [18].
Figure 3.9: Block diagram of a hydro-power system with primary and secondary control [35]
The secondary control is in fig.3.9, simply represents the opportunity to feedback a set value
for the mechanical input power other than zero to the turbine governor.
3.8.1.2 Voltage Control
To control node voltages is by varying the excitation of the rotating generators. This is done
by a feedback control loop that changes the excitation current in the generator to maintain a
particular node voltage. This control is very fast. Another way to control node voltage is to
change the tap setting of a transformer connected to the node. Other ways are to switch shunt
capacitors or reactors at the nodes. These changes can be made manually by the operator or
automatically by implementing a feedback control that senses the node voltage and activates
the control. Unlike the generator excitation control, Transformer taps and shunt reactance can
only be changed in discrete quantities. Often this type of control schemes has time delays
13
built into them to avoid excessive control actions. More recently power electronic control
devices have been introduced in the shunt reactance Voltage control schemes. This makes the
control much more continuous and often is done it a much faster time frame than the usual
shunt switching. These static var controllers (SVC) are becoming more common. As is
obvious, voltage control is always a local control. However, controlling the voltage at one
node affects the neighbouring nodes.
14
CHAPTER-3
15
50 Hz or at specific value [38]. In an inter-connected power system, Load Frequency Control
(LFC) is an important to keep the system frequency and the inter-area tie-line power as close
as possible to the scheduled value. LFC constitutes an important function on power system
operation where the main objective is to regulate the output power of each generator at
prescribed levels while keeping the frequency fluctuations within pre-defined limits. LFC
problems are caused by small perturbations which continuously disturb the normal operation
of power system, hence generation rate of generators must be change until the frequency and
Tie-line power maintain close to specified values while it is desirable that the deviations of
frequency and tie-line power system become zero.
4.2 Levels of Automatic Generation Control and Their Performance
Power systems have usually many disturbances. These disturbances lead to bringing low
frequency oscillation in power system. The dynamic instability is caused if the torque in the
system is not sufficient. In any electrical system, the power production in one moment and
consumption in the same moment has to be the same otherwise a frequency deviation will
occur[15]. In fig.4.2 the turbine governing system with its load reference point is at the
lowest primary control level and all the commands from upper levels are executed at this
level. Primary control is decentralized because it is installed in power plants situated at
different geographical sites. Frequency control and tie-line control constitute secondary
control and force primary control to eliminate the frequency and net tie-line interchange
deviations.
16
In isolated systems secondary control is limited to frequency control and could be
implemented locally without the need for coordination by the central regulator. In
interconnected systems secondary control of frequency and tie-line flows is implemented
using a central computer. Secondary control should be slower than primary control. The task
of tertiary control is to ensure an appropriate bandwidth of secondary control. Obviously
tertiary control must be slower than both primary and secondary control. Hence it may be
neglected when considering the dynamics of coordination between primary and secondary
control [10]. Frequency control is classified into 3 types based on time frame of response:
i). Primary control
ii). Secondary control
iii). Tertiary control
4.2.1 Primary Control
Primary control is the control of power balance in the single control area by using Governor
Control System of generators to control the change of frequency or turbine speed after the
incidents. The time frame of primary response is seconds. The final frequency of primary
control is not equal 50 Hz as the response is the initial response. The system requires
secondary control to compensate the power mismatch. Primary Control is initialized when the
frequency deviation is above 0.05 Hz.(Dead Band is 0.05 Hz) of nominal value. The amount
of Primary Reserve is used when Primary Control is activated [15]. The following are the
requirement:
i). Primary control reserve has to used up to 50% capacity within 15 seconds and
ii). It will be used up to 100% by 30 seconds.
4.2.2 Secondary Control
Secondary control system is the control of power balance between real power produced by
generator and combination of load demand and losses in the single control area. Secondary
control system is operated from Automatic Generation Control located at dispatching center
by changing generation outputs of the generators. Secondary Control System will start by 30
seconds after the incidents (after the primary control) in order to maintain the system
frequency at the nominal value (50 Hz). The response of Secondary Control will be finished
by 15 minutes after the incident. The change of generation output depends upon the
secondary control reserve at that time [15].
17
4.2.3 Tertiary Control
Tertiary Control is any (automatic or) manual change in the network points of generators
(mainly by re-scheduling), in order to restore an adequate secondary control reserve at the
right time [15].Primary control is sufficient to stabilize the system where there is only a brief
power deficit or surplus. Primary control has been defined as an automated reestablishment of
the balance between generation and consumption within no less than 30 seconds following
such imbalance. If a longer disturbance occurs secondary control is activated after a defined
period (max 30 sec.) or simultaneously with the primary control, in order to relieve the
burden on the primary reserve and free it to perform the above function. In contrast to
primary control, which works at international level to maintain a stable frequency, secondary
control balances power deficits and surpluses within control areas. It can take several minutes
to restore frequency stability. If the power flow deviation lasts for an extended period (more
than 15 minutes) secondary gives way to tertiary control. The latter can also kick in during
secondary control already. Tertiary control is activated either automatically or manually. It
must be deployed in time to contribute to restoring balance no more than 15 minutes after the
start of the deviation in the control area. Restoration of the secondary control range can take
up to 15 minutes, whereas tertiary control may continue after this period. The available
tertiary control reserve must be at least as large as the capacity of the largest power station
unit in the control area [6]. In general Frequency control and tie-line control constitute
secondary control and force primary control to eliminate the frequency and net tie-line
interchange deviations. Hence this control may be neglected when considering the dynamics
of coordination between primary and secondary control. When there is a frequency change
primary control action is performed by the governors of prime movers. After few seconds
Secondary Control function by Automatic generation controller (AGC) is initiated.
4.3 Load Frequency Control Function (LFC)
The load frequency control (LFC) system monitors generation load, constantly looking for
imbalances. The LFC system needs to maintain frequency at the scheduled value, net power
interchanges with neighboring control areas at the scheduled values and power allocation
among generating units at economically desired values [38, 39]. Load frequency control in
power systems is very important in order to supply reliable electric power with good quality.
The goal of the LFC is to maintain zero steady state errors in a multi-area interconnected
18
power system. In addition, the power system should fulfil the proposed dispatch conditions.
Power systems are divided into control areas connected by tie lines. All generators are
supposed to constitute a coherent group in each control area. Complete block diagram of
ALFC is in fig.4.3.
LFC is classified into 2 systems:
i). Primary control system
ii). Secondary control system.
20
If the load on the system is increased, the turbine in fig.4.5, speed drops before the governor
can adjust the input of the steam to the new load. As the change in the value of speed
diminishes, the error signal becomes smaller and the position of the governor fly balls gets
closer to the point required to maintain a constant speed. However, the constant speed will
not be the set point, and there will be an offset. One way to restore the speed or frequency to
its nominal value is to add an integrator. The integral unit monitors the average error over a
period of time and overcome the offset. Because of its ability to return a system to its set
point, integral action is also known as the rest action. Thus as the system load changes
continuously the generation is adjusted automatically to restore the frequency to the nominal
value. This scheme is known as the automatic generation control (AGC).In an interconnected
system [4] consisting of several pools, the role of the AGC is to divide the loads among
system stations and generators so as to achieve maximum economy and correctly control the
scheduled interchanges of tie-line power while maintaining a reasonably uniform frequency.
Its implicitly assuming that the system is stable, so the steady-state is achievable. During
large transient disturbances and emergencies, AGC is bypassed and other emergency controls
are applied.In a single area mechanical power is produced by a turbine connected to a
synchronous generator. The turbine steam flow determines the frequency of the current and
voltage waveforms at the output of the generator. An exact forecast of real power demand is
impossible due to random changes in the load and therefore an imbalance occurs between the
real power generation and the load demand (plus losses). This causes kinetic energy of
rotation to be either added to or taken from the generating units (generator shaft either speed
up or slow down) and the frequency of system varies as a result. Therefore, a control system
is required to detect the load changes and command the steam valve to open or close more so
that the turbine increase or decrease its mechanical power production and stabilize the shaft
speed and hence the system frequency. Modern real power systems [5] constitute
interconnected neighbouring areas. A multi-area LFC system [6] constitutes a number of
single areas connected by a tie line. This tie line allows the flow of power between the areas.
Consequently, a disturbance in one area influences the frequency output of other areas as well
as the tie line power. The objective of the LFC system is to minimize deviations of both
frequency of all areas and tie line power interchanges. The ALFC is to control the frequency
21
deviation by maintaining the real power balance in the system. The main functions of the
ALFC are to
i). to maintain the steady frequency,
ii). to control the tie-line flows,
iii). to distribute the load among the participating generating units.
The control (input) signals are the tie-line deviation ∆Ptie (measured from the tie-line flows),
and the frequency deviation ∆f (obtained by means If the load on the system is increased), the
turbine speed drops before the governor can adjust the input of the steam to the new load. As
the change in the value of speed diminishes, the error signal becomes smaller and the position
of the governor fly balls gets closer to the point required to maintain a constant speed.
However, the constant speed will not be the set point, and there will be an offset. One way to
restore the speed or frequency to its nominal value is to add an integrator. The integral unit
monitors the average error over a period of time and overcome the offset. Because of its
ability to return a system to its set point, integral action is also known as the rest action. Thus
as the system load changes continuously the generation is adjusted automatically to restore
the frequency to the nominal value,during the angle deviation these error signals ∆f and ∆Ptie
are amplified, mixed and transformed to a real power signal which then controls the valve
position. Depending on the valve position, the turbine (prime mover) changes its output
power to establish the real power balance.
4.6 Linearized model of an LFC system
The model of Generator, Load, prime mover and governor is obtained by transfer function
method and combined to form a complete block diagram of an isolated power system,
4.6.1 Generator Model
Applying swing equation of a synchronous machine to small perturbation, we have
2 Hd 2
Pm Pe …….(4.1)
s dt 2
Expressing the speed deviation in pu
d 1
(Pm Pe ) …….(4.2)
dt 2H
This relation can be represented as shown in Fig 4.6
22
,
Figure 4.6: The block diagram representation of the Generator [4]
4.6.2 Prime mover model
The model for the turbine relates changes in mechanical power output ΔP m to changes in
steam valve position ΔP v. The simplest prime mover model in fig.4.7, for the non-reheat
steam turbine can be approximated with a single time constant τT, resulting in the transfer
function under equation(5).
Pm ( s) 1
Gt ( s) …….(4.3)
Pv ( s ) 1 sTt
23
4.6.3.1 Speed Changer
The speed changer consists of a servomotor which can be operated manually or automatically
for scheduling load at nominal frequency. By adjusting this set point, a desired load dispatch
can be scheduled at nominal frequency. For stable operation, in fig.4.8, the governors are
designed to permit the speed to drop as the load is increased. The speed governor mechanism
acts as a comparator whose output ΔPg is the difference between the references set power
ΔPref.
Figure 4.8: Block diagram for Speed Governing System of steam turbine.
4.6.4 Load Model
The load model on a power system consists of variety of electrical devices. For resistive
loads, such as lighting and heating loads, the electrical power is independent of frequency.
Motor loads are sensitive to changes in frequency. The speed-load characteristic of a
composite load is approximated by Pe P0 Pf where ΔPL is the non-frequency sensitive
load change, and DΔω is the frequency sensitive load change, D is expressed as per cent
change in load divided by per cent change in frequency. The load model and the generator
model is combined as shown in Fig.4 The load model on a power system consists of variety
of electrical. The block diagram of a steam turbine in Fig.2. The load on the system is
composite consisting of a frequency independent component and a frequency dependent
component. The load can be written as Pe P0 Pf where, Pe is the change in the load;
P0 is the frequency independent load component; Pf is the frequency dependent load
component. Pf D where, D is called frequency characteristic of the load (also called
as damping constant) expressed in per cent change in load for 1% change in frequency. If
D=1.5%, then a 1% change in frequency causes 1.5% change in load. The combined
24
generator and the load (constituting the power system) can then be represented as shown in
Fig.4.9.
Figure 4.9: The block diagram representation of the Generator and load [4]
Eliminating the simple feedback loop in Fig. 4.9. Resultant simplified block diagram is
shown in Fig.4.10.
Figure 4.10: Reduced block diagram representation of the Generator and load [4]
Combining the block diagrams of Fig. 4.6, 4.7, 4.8 and 4.10 results in the complete block
diagram of the load frequency control of an isolated power station as shown in Fig.4.11.
25
Figure 4.12: Combined block diagram representation of the ALFC [4]
4.7 Economic Dispatch Function (ED)
An important secondary function of the AGC is to allocate generation so that each generating
unit is loaded economically.ED system manages the generation of each power station to
minimize total operating cost of the system. AGC dispatches generation of participated
generators in Unit Control Automatic Economic Mode and Automatic Mode by computing
Economic Base Point and Participation Factors. The signal sent to adjust MW set point at
power stations.That is, each generating unit is to generate that amount to meet the present
demand in such a way that the operating cost gets minimized. This function is called
Economic Load Dispatch ELD [18].
The ALFC loop shown in Fig 4.13 is called the primary ALFC loop. It achieves the primary
V goal of real power balance by adjusting the turbine output Pm to match the change in load
demand PD . All the participating generating units contribute to the change in generation. But
a change in load results in a steady state frequency deviation f . The restoration of the
frequency its nominal value requires an additional control loop called the supplementary loop
[55]. This objective is met by using integral controller which makes the frequency deviation
zero. The ALFC with the supplementary loop is generally called the AGC. The block
diagram of an AGC is shown in Fig. The main objectives of AGC are
i). To regulate the frequency (using both primary and supplementary controls).
ii). To maintain the scheduled tie-line flows. A secondary objective of the AGC is to
distribute the required change in generation among the connected generating units
economically (to obtain least operating costs).
26
Figure 4.13: The block diagram representation of the AGC [55]
Figure 4.14: The block diagram representation of single area power system [55]
Although each generator will be having a separate speed governor, all the generators in the
control area are replaced by a single equivalent generator, and the ALFC for the area
corresponds to this equivalent generator.With the primary LFC loop, a change in the system
load will result in a steady-state frequency deviation, depending on the governor speed
regulation. In order to reduce the frequency deviation to zero, there should be a reset action.
27
The reset action can be achieved by introducing an integral controller to act on the load
reference setting to change the speed set point. The integral controller increases the system
type by 1 which forces the final frequency deviation to zero. The integral controller gain K 1
must be adjusted for a satisfactory transient response. The close loop transfer function of the
control system with only PL as input becomes [4]
28
4.11 Expression for Tie-Line Flow in a Two-Area Interconnected System
Consider a change in load PD1 in area-1. The steady state frequency deviation f is the same
for both the areas. That is f f1 f 2 .Thus, for area1, we have Pm1 PD1 P12 D1f
where, P12 is the tie line power flow from Area 1 to Area2 and for Area 2[38]
29
Solving for f ,
get
PD1 PD1
f ……..(4.8)
(1 / R1 D1 ) (1 / R2 D2 ) 1 2
PD1 2
And P1 2 ……..(4.9)
1 2
where, 1 and 2 are the composite frequency response characteristic of Area-1 and Area-2
respectively[19]. An increase of load in area1 by PD1 results in a frequency reduction in both
areas and a tie-line flow of P12 . A positive P12 is indicative of flow from Area-1 to Area-2
while a negative P12 means flow from Area-2 to Area-1. Similarly, for a change in Area-2
load by PD 2 , so we have
PD 2 PD 2 1
f And P12 P21
1 2 1 2
4.12 Area Control Error (ACE)
This comes under the system when control is of more than one area .In the Tie-line basic
control each area controls its own generation to match its load and the required net tie-line
interchange. The power flow through each tie-line is adjusted to required scheduled level
with permissible departure limits. Tie-line deviation reflects the contribution of regulation
characteristic of one area to another.A change of power in Area-1 is met by the increase in
generation in all the areas associated with a change in the tie-line power, and a reduction in
frequency. In normal operating state, the power system is operated so that the demands of
areas are satisfied at the normal frequency [56].
30
ACE<0 generation is increased.
As long as one frequency bias β≠0, if all areas have ACE=0: then Δω = 0 and all Δ Net
Interchange =0, Conventional LFC is based upon tie-line bias control, where each area tends
to reduce the area control error (ACE) to zero. The control error for each area consists of a
linear combination of frequency and tie-line error [57].
n
ACEi Pij Ki …….(4.10)
j 1
The area bias Ki determines the amount of interaction during a disturbance in the neighboring
areas. An overall satisfactory performance is achieved when K i is selected equal to the
frequency bias factor of that area, i.e. Bi = 1/ Ri+ Di. Thus, the ACEs for a two-area system
area
Where P12 and P21 are departures from scheduled interchanges. ACEs are used as actuating
signals to activate changes in the reference power set points and when steady-state is reached,
P12 and will be zero [56].
31
Figure 4.17: Schematic diagram of Interconnection of Three areas [57]
In multi-area power system, a group of generators are closely coupled internally and swing in
unison. The LFC loop represents the whole system called as control area. The AGC of multi-
area is realized by studying first the AGC of a three area system. Consider the three areas
represented by an equivalent generating unit interconnected by a lossless tie line with
reactance X tie. During normal operation, the real power transferred over the tie line is given
by
E1 E 2
P12 Sin 12 …….(4.13)
X 12
Where X12 = Xtie + X2, & 12 = 1 - 2. Equation (4.13) can be linearized for a small deviation
in the tie-line flow P12 from the nominal value.The tie-line power flow appears as a load
increase in one area and a load decrease in the other area, depending on the direction of flow.
The direction of flow is dictated by the phase angle difference.
32
CHAPTER – 4
Voltage changes continuously according to the varying electrical demand, transmission lines
utilization, system control by the control centers, and emergency situations occurred in the
system. Controlling the voltage is regional problems [4].
In other words, the voltage controlling problems are needed to be solved separately by each
control area. This can be achieved by providing sufficient reactive power sources for
controlling voltage level as specified by the agreement [58]. The voltage controlling problems
can be divided into two situations, which are normal situation, and emergency situation. The
reactive power sources are classified into two types, static and dynamic. The static type
consists of shunt capacitor, and shunt reactor. The control centers need to organize and
compile the constantly updated information concerning the availability of relevant equipment.
Also the control centers have to provide procedures, in writing, required for properly
controlling of the equipment in order to support normal situation, and emergency situation
that may lead to voltage collapse and cascade tripping both of which can cause a
blackout[47].
33
5.2 Linear Model of an AVR System
The role of an AVR is to keep constant the output voltage of the generator in a specified
range. A simple AVR consists of amplifier, exciter, generator and sensor. The block diagram
of AVR with PID controller is shown in fig.6.1. The linear models of the elements of the
AVR are given in Equations.
5.2.1 Amplifier model
The amplifier model is represented by a gain KA and a time constant τA, the transfer function
is
VR KA
…….(5.1)
VE 1 A s
Typical values of KA are in the range of 10 to 400. The amplifier time constant τA is very
small ranging from 0.02 to 0.1 s.
5.2.2 Exciter model
The transfer function of a modern exciter may be represented by a gain KE and a single time
constant τE
VF KE
.…….(5.2)
VR 1 E s
Typical values of KE are in the range of 10 to 400. The time constant τE is in the range of 0.5
to 1.0 s.
5.2.3 Generator model
In the linearized model, the transfer function relating the generator terminal voltage to its
field voltage can be represented by a gain KG and a time constant τG
Vt KG
…….(5.3)
VF 1 G s
These constants are load dependent, KG may vary between 0.7 to 1.0, and τG between 1.0 and
2s from full load to no load.
5.2.4 Sensor model
The sensor is modelled by a simple first-order transfer function, given by
VS KR
…….(5.4)
Vt 1 Rs
34
τR is very small, ranging from of 0.001 to 0.06 s.
5.3 Generator Voltage Control System
The voltage of the generator is proportional to the speed and excitation (flux) of the
generator, the speed being constant, the excitation is used to control the voltage. Therefore,
the voltage control system is also called as excitation control system or automatic voltage
regulator AVR. For the alternators, the excitation are provided by a device (another machine
or a static device) called exciter [59]. For a large alternator the exciter may be required to
supply a field current of as large as 6500A at 500V and hence the exciter is a fairly large
machine [16]. Depending on the way the dc supply is given to the field winding of the
alternator (which is on the rotor), the exciters are classified as:
i). DC Exciters
ii). AC Exciters
iii). Static Exciters.
A schematic of an excitation control system is shown in Fig.5.2.
As its in fig.5.2,the generator terminal voltage V t is compared with a voltage reference Vref to
obtain a voltage error signal V .This signal is applied to the voltage regulator shown as a
block with transfer function KA /(1+ τA s). The output of the regulator is then applied to
exciter shown with a block of transfer function KE / (1+ τE s). The output of the exciter VF is
then applied to the field winding which adjusts the generator terminal voltage. The generator
field can be represented by a block with a transfer function KG /(1+s τG)[57].
35
The total transfer function is
V G( s)
Vref 1 G ( s )
Where,
K A K E KG
G( s) …….(5.1)
(1 A s)(1 E s)(1 F s)
The stabilizing compensator shown in the diagram is used to improve the dynamic response
of the exciter. The input to this block is the exciter voltage and the output is a stabilizing
feedback signal to reduce the excessive overshoot.
Figure 5.3: A simplified block diagram of Voltage (Excitation) Control System [4]
The generator excitation system maintains generator voltage and controls the reactive power
flow. The generator excitation of older systems may be provided through slip rings and
brushes by means of dc generators mounted on the same shaft as the rotor of the synchronous
machine. However, modern excitation systems usually use AC a generator with rotating
rectifiers, and are known as brushless excitation [58].In fig.5.3, as a change in the real power
demand affects essentially the frequency, whereas a change in the reactive power affects
mainly the voltage magnitude. The interaction between voltage and frequency controls is
generally weak enough to justify their analysis separately. The sources of reactive power are
generators, capacitors, and reactors. The generator reactive powers are controlled by field
excitation. Other supplementary methods [20] of improving the voltage profile on electric
transmission systems are transformer load-tap changers, switched capacitors, step-voltage
regulators, and static VAR control equipment. The primary means of generator reactive
power control is the generator excitation control using automatic voltage regulator AVR. The
36
role of an AVR is to hold the terminal voltage magnitude of asynchronous generator at a
specified level. An increase in the reactive power load of the generator is accompanied by a
drop in the terminal voltage magnitude. The voltage magnitude is sensed through a potential
transformer on one phase. This voltage is rectified and compared to a DC set point signal.
The amplified error signal controls the exciter field and increases the exciter terminal voltage.
Thus, the generator field current is increased, which results in an increase in the generated
emf. The reactive power generation is increased to a new equilibrium, raising the terminal
voltage to the desired value [59].
37
CHAPTER-5
Figure 6.1: The block diagram of an AVR system with a PID controller
The method by which the automatic controller produces the control signal is called mode of
control or control action. The controller consists of an error detector and amplifier shows in
fig.6.1.The measuring element is a device in which converts the output variable such as
displacement, pressure or electrical signals which can be used for comparing the output to the
reference input signal.
6.2 Proportional Integral Derivative (PID) controllers
A proportional-integral-derivative controller (PID controller) is a generic control loop
feedback mechanism widely used in industrial control systems. A PID controller attempts to
correct the error between a measured process variable and a desired set point by calculating
and then outputting a corrective action that can adjust the process accordingly. The PID
controller calculation (algorithm) involves three separate parameters; the Proportional, the
Integral and Derivative values. The Proportional value determines the reaction to the current
error, the Integral determines the reaction based on the sum of recent errors and the Derivative
determines the reaction to the rate at which the error has been changing. The weighted sum of
these three actions is used to adjust the process via a control element such as the position of a
38
control valve or the power supply of a heating element. By "tuning" the three constants in the
PID controller algorithm the PID can provide control action designed for specific process
requirements. The response of the controller can be described in terms of the responsiveness of
the controller to an error, the degree to which the controller overshoots the setpoint and the
degree of system oscillation [4].
6.2.1 Proportional term
The proportional term makes a change to the output that is proportional to the current error
value. The proportional response can be adjusted by multiplying the error by a constant K p,
called the proportional gain. The proportional term is given by:
Pout K p et …….(6.1)
39
I out Ki t0 e d …….(6.2)
de(t )
D Kd
dt
41
6.3.1 Tuning method
Choosing a Tuning Method
P 0 0
PI 0
0.27
PID 0.6T
Table 6.3
These parameters give a response with an overshoot about 25% and good settling time. Start
fine-tuning the controller using the basic rules that relate each parameter to the response
characteristics. This concludes two things about PID controllers.
Relationships between Kp, Ki and Kd and important response characteristics, of which these
three are most useful:
i). Use Kp to decrease the rise time.
ii). Use Kd to reduce the overshoot and settling time.
iii). Use Ki to eliminate the steady-state error.
43
The PID controller transfer function is,
Ki
G C ( s) K P K DS
s
A PID controller is added in the forward path of AVR system in which proposal gain K P is
1.0 and KI and KD is adjusted until a step response with a minimum overshoot and a very
small settling time is obtained. An integral gain of KI is 0.25 and a derivative gain of KD is
0.28 is found to be satisfactory. The response settles in about 1.4 seconds with a negligibly
small overshoot. The controller reduces the steady-state error to zero. AVR is not robust to
variations of the power system parameters therefore, it is necessary to use PID controller To
increase the stability and performance of the AVR system. Fast tuning of optimum PID
controller parameter yield high quality solution.
Power System Stabilizer (PSS) which is installed in the Automatic Voltage Regulator of the
Generator can improve the power system stability. A PSS detects the changing of generator
output power, controls the excitation value, and reduces the power swing rapidly. The
reducing speed of the power swing can be compared in case of PSS OFF condition and PSS
ON [60].
Figure 6.5: Signal output in presence and absence of PSS controller [60]
44
Small signal instability occurs when a system perturbation, even a small one, excites a natural
Oscillatory mode of the power system. As it is shown in fig.6.5, these oscillations are slow,
usually under 1Hz. The main method used today to guard against small signal instability is
the off-line tuning of power system stabilizers (PSS). These PSS are local controllers on the
generators. Thus local controllers are used to mitigate system oscillation modes, a procedure
that is recognized to have significant disadvantages. A new control concept is to adaptively
change the PSS set points according to the power system operating conditions. This would be
analogous to the AGC control by introducing a secondary control scheme that would
periodically adjust the set points of the local PSS controllers as the system changes. The
challenge here is that the calculation of PSS set points requires large analytical calculations,
which are today done off-line. The speed of calculation is not a major concern as changing
the set points can be done quite infrequently, probably in minutes. In the fig. 6.6, linearized
model single machine connected to a large system through a tie-line is introduced.
45
of a generating unit. A PSS is also one of the most cost-effective methods of enhancing
power system stability. Power System Stabilizers (PSS) are designed to enhance damping of
power system oscillations in order to extend power transfer limits of the system and maintain
reliable operation of the grid. Power System Stabilizers (PSS) can modulate the Synchronous
machine's voltage to instantaneously take real power from the system or put real power into
the system by varying the angle between magnetic moment or the rotating field and the
rotating magnetic field of the three phase electric system reflected in the voltage on the
stationary part of the Synchronous machine. If the adjustments of the PSS are set correctly,
then power swings into or out of the Synchronous machine will act to dampen the system-
wide resonant power swings and improve system stability. If the adjustments are set
incorrectly, then the opposite is true.
Figure 6.7: Simple block diagram of an AVR compensated with a PSS controller [61]
The basic function of PSS is to add damping to the generator rotor oscillations by controlling
its excitation using auxiliary stabilizing signal. To provide damping, the stabilizer must
produce a component of electrical torque in phase it the rotor speed deviations. Damping can
be achieved by modulating the generator excitation so as to develop a component of electrical
torque in phase with rotor speed deviations [61]. Shaft speed, integral of power and terminal
frequency are among the commonly used as input signals to the PSS. Small signal instability
occurs when a system perturbation, even a small one, excites a natural Oscillatory mode of
the power system. These oscillations are slow, usually under 1Hz. The main method used
today to guard against small signal instability is the off-line tuning of power system
stabilizers (PSS). These PSS are local controllers on the generators. Thus local controllers are
used to mitigate system oscillation modes, a procedure that is recognized to have significant
46
disadvantages [62]. Power systems are usually equipped with power system stabilizers PSS to
damp out low frequency oscillations. These oscillations are mainly caused by disturbances in
the system. The power systems are usually nonlinear. In fig. 6.8,conventional block diagram
is shown, The conventional method of design involves linearizing the model of synchronous
machine around a suitable operation point and then linear control theory is used in designing
a fixed parameter conventional PSS [59]. Power system stabilizers (PSS) must be capable of
providing appropriate stabilization signals over a broad range of operating conditions and
disturbances.[63].
Figure 6.8: Conventional block diagram of an AVR compensated with a PSS controller [61]
These cause unstable or poorly damped oscillations that have been observed more often in
power systems around the world. The reason for the lack of stability analysis is due to the
complexity of the power systems. A major effort has to be made to improve of power system
stabilization. Due to the rapid development of computer technology, the use of optimization
tools becomes feasible to help in the implementation of control signals in power system [62].
Control signal is given to sum point of AVR unit & will provide sufficient damping torque
for synchronous generator unit with extra enhanced in rise time & settling time & maximum
overshoot and finally robustness that makes it much suitable for interconnected nonlinear
synchronous generators.The action of a PSS is to extend the angular stability limits of a
power system by providing supplemental damping to the oscillation of synchronous machine
rotors through the generator excitation. This damping is provided by a electric torque applied
47
to the rotor that is in phase with the speed variation. Once the oscillations are damped, the
thermal limit of the tie-lines in the system may then be approached. This supplementary
control is very beneficial during line outages and large power transfers [63]. However, power
system instabilities can arise in certain circumstances due to negative damping effects of the
PSS on the rotor. The reason for this is that PSSs are tuned around a steady-state operating
point their damping effect is only valid for small excursions around this operating point.
During severe disturbances, a PSS may actually cause the generator under its control to lose
synchronism in an attempt to control its excitation field [59].
The PSS is provided to improve the power system oscillations. It provides the electrical
damping torque in phase with the speed deviation to improve power system damping. The
combination of pole placement and nonlinear programming techniques is considered to
design the PSS with PID configuration (PSS-PID)[44]. PID controller is used for stabilization
in this system. The input of this stabilizer is the speed changing being modeling from the
generator. The output of this controller is delivered to (stabilization voltage) the stimulation
block to stabilizer the power system. The aim is to control the angle between load and
generator speed. The nonlinear programming with the combination of pole placement is used
for PSS-PID design methodology[60]. Therefore, the open loop transfer function and
maximum peak responseparameter make the objective function which used to adjust PID
parameters[45].
48
REFERENCES
49