Wiringdiagram
Wiringdiagram
Wiringdiagram
Description
Sepam components
b Base unit 1
v A base unit connector:
- power supply
- output relays
- CSH30, 120, 200 or ACE990 input.
Screw-type connector shown (CCA620), or ring lug connector (CCA622)
v B 1 A/5 A CT current input connector (CCA630 or CCA634) or LPCT current input
connector (CCA670) or VT voltage input connector (CCT640)
v C communication module link connection (white)
v D remote inter-module link connection (black)
b Optional input/output module 2 (MES114)
v L M MES114 module connectors
DE52149 v K MES114 module connector.
CAUTION DANGER
LOSS OF PROTECTION OR RISK OF HAZARD OF ELECTRIC SHOCK, ELECTRIC ARC OR BURNS
NUISANCE TRIPPING b Only qualified personnel should install this equipment. Such work should be
If the Sepam is no longer supplied with power or performed only after reading this entire set of instructions.
is in fail-safe position, the protection functions b NEVER work alone.
are no longer active and all the Sepam output b Turn off all power supplying this equipment before working on or inside it.
relays are dropped out. Check that this operating Consider all sources of power, including the possibility of backfeeding.
mode and the watchdog relay wiring are b Always use a properly rated voltage sensing device to confirm that all power
compatible with your installation. is off.
Failure to follow these instructions can result b Start by connecting the device to the protective earth and to the functional
in equipment damage and unwanted earth.
shutdown of the electrical installation b Screw tight all terminals, even those not in use.
Failure to follow these instructions will result in death or serious injury.
Types S20/S23/S24/T20/T23/T24/M20
DE51144
CCA622
b 1 wire 0.2 to 2.5 mm2 (AWG 24-12)
b 2 wires 0.2 to 1 mm2 (AWG 24-18)
b Cross-section: 0.2 to 2.5 mm2 (AWG 24-12)
6
(1/4 in) b Stripped length: 6 mm (0.236 in)
b Tightening torque: 0.7 to 1 N.m (6 to 9 lb-in)
B Ring lug 4 mm CCA630/ b Cross-section: 1.5 to 6 mm2 (AWG 16-10)
(0.16 in) CCA634 b Stripped length: 6 mm (0.236 in)
b Tightening torque: 1.2 N.m (11 lb-in)
C RJ45 CCA612
D RJ45 b CCA770: L = 0.6 m (2 ft)
b CCA772: L = 2 m (6.6 ft)
b CCA774: L = 4 m (13 ft)
CCA630/
CCA634
The measurement of the 3 phase currents allows the calculation of residual current.
Parameters
Sensor type 5 A CT or 1 A CT
Number of CTs I1, I2, I3
Rated current (In) 1 A to 6250 A
CCA630/
CCA634
The measurement of phase currents 1 and 3 is sufficient to ensure all the
phase current-based protection functions.
The phase current I2 is only assessed for metering functions, assuming that I0 = 0.
Parameters
Sensor type 5 A CT or 1 A CT
Number of CTs I1, I3
Rated current (In) 1 A to 6250 A
CCA670 CCA670 connector. The connection of only one or two LPCT sensors is not allowed
and causes Sepam to go into fail-safe position.
The measurement of the 3 phase currents allows the calculation of residual current.
6 Parameters
Sensor type LPCT
Number of CTs I1, I2, I3
Rated current (In) 25, 50, 100, 125, 133, 200, 250, 320, 400, 500, 630, 666, 1000,
1600, 2000 or 3150 A
Note: Parameter In must be set 2 twice:
b Software parameter setting using the advanced UMI or the SFT2841 software tool
b Hardware parameter setting using microswitches on the CCA670 connector
Parameters
Residual current Rated residual current Measuring range
Sum of 3 Is In0 = In, CT primary current 0.1 to 40 In0
Parameters
Residual current Rated residual current Measuring range
2 A rating CSH In0 = 2 A 0.2 to 40 A
20 A rating CSH In0 = 20 A 2 to 400 A
b Terminal 7: 1 A CT
b Terminal 8: 5 A CT
Parameters
Residual current Rated residual current Measuring range
1 A CT In0 = In, CT primary current 0.1 to 20 In0
5 A CT In0 = In, CT primary current 0.1 to 20 In0
6
DE80048
Parameters
Residual current Rated residual current Measuring range
1 A CT In0 = In, CT primary current 0.1 to 20 In0
5 A CT In0 = In, CT primary current 0.1 to 20 In0
turns
turns
DE80116
turns
turns
Variant 5: residual current measurement by core balance CT with ratio of 1/n (n between 50 and 1500)
Description
The ACE990 is used as an interface between an MV core balance CT with a ratio of
DE51830
6 1/n (50 < n < 1500) and the Sepam residual current input.
This arrangement allows the continued use of existing core balance CTs on the
installation.
Parameters
Residual current Rated residual current Measuring range
ACE990 - range 1 In0 = Ik.n(1) 0.1 to 20 In0
(0.00578 y k y 0.04)
ACE990 - range 2 In0 = Ik.n(1) 0.1 to 20 In0
(0.0578 y k y 0.26316)
(1) n = number of core balance CT turns
k = factor to be determined according to ACE990 wiring and setting range
used by Sepam
Variant 1: residual current measurement by CTs on the neutral earthing link (with or without CSH30
interposing ring CT)
Description
Residual current is measured with a 1 A or 5 A CT on the neutral point.
Parameters
Residual current Rated residual current Measuring range
1 A CT In0 = neutral point CT In 0.1 to 20 In0
5 A CT In0 = neutral point CT In 0.1 to 20 In0
DE80952
DE80953
DE81047
N PE N
B B
A
19
18
CT 1 A: 2 turns
CT 5 A: 4 turns
Connection on TN-S network. Connection on TT network. Connection with CSH30.
Variant 2: residual current measurement by CSH120 or CSH200 core balance CT on the neutral earthing
link
Description
Residual current is measured with a core balance CT on the neutral point. Core
balance CTs are recommended for measuring very low fault currents provided that
the earth fault current remains below 2 kA. Above this value it is advisable to use the
standard variant 1.
Parameters
Residual current Rated residual current Measuring range 6
2 A rating CSH In0 = 2 A 0.1 to 20 In0
20 A rating CSH In0 = 20 A 0.1 to 20 In0
DE80864
DE80955
N PE N
A A
19 19
18 18
Variant 3: residual current measurement by sum of 3 phase currents and neutral current measurement by
CSH120 or CSH200 core balance CT
Description
Measurement by core balance CT is recommended for measuring very low fault
DE80956
currents.
Parameters
Residual current Rated residual current Measuring range
2 A rating CSH In0 = 2 A 0.1 to 40 A
20 A rating CSH In0 = 20 A 0.2 to 400 A
N
A
19
18
Variant 4: residual current measurement by sum of 3 phase currents and neutral current measurement by
1 A or 5 A CTs and CSH30 interposing ring CT
N Description
The phase and neutral CTs should have the same primary and secondary currents.
DE81052
Parameters
A Residual current Rated residual current Measuring range
19 1 A CT In0 = phase CT primary current In 0.1 to 20 In0
18 5 A CT In0 = phase CT primary current In 0.1 to 20 In0
6 CT 1 A: 2 turns
CT 5 A: 4 turns
Connection on TN-S and TT networks.
Variant 5: residual current measurement by sum of 3 phase currents and neutral current measurement by
1 A or 5 A CTs and CCA634 connector
N Description
The phase and neutral CTs should have the same primary and secondary currents.
DE80957
Parameters
Residual current Rated residual current Measuring range
1 A CT In0 = phase CT primary current In 0.1 to 20 In0
5 A CT In0 = phase CT primary current In 0.1 to 20 In0
B21/B22 types
DE51157
Ring lug
6.35 mm (1/4 in)
CCA622
b 2 wires 0.2 to 1 mm2 (AWG 24-18)
b Cross-section: 0.2 to 2.5 mm2 (AWG 24-12)
b Stripped length: 6 mm (0.236 in)
6
b Tightening torque: 0.7 to 1 N.m (6 to 9 lb-in)
B Screw-type CCT640 b 1 wire 0.2 to 2.5 mm2 (AWG 24-12)
b 2 wires 0.2 to 1 mm2 (AWG 24-18)
C RJ45 CCA612
D RJ45 b CCA770: L = 0.6 m (2 ft)
b CCA772: L = 2 m (6.6 ft)
b CCA774: L = 4 m (13 ft)
The phase and residual voltage transformer secondary circuits are connected to the
CCT640 connector (item B ) on Sepam series 20 type B units. The CCT640
connector contains 4 transformers which perform isolation and impedance matching
of the VTs and Sepam input circuits.
Variant 1: measurement of 3 phase-to-neutral voltages (standard connection)
Parameters
Voltages measured by VTs V1, V2, V3
DE51831
Functions available
Voltages measured V1, V2, V3
Values calculated U21, U32, U13, V0, Vd, f
Measurements available All
Protection functions available (according to type of Sepam) All
Functions available
Voltages measured V1, V2, V3, V0
Values calculated U21, U32, U13, Vd, f
Measurements available All
Protection functions available (according to type of Sepam) All
Functions available
Voltages measured V1, V2, V3
6 Values calculated
Measurements available
U13, Vd, f
U21, U32, U13, Vd, f
Protection functions available (according to type of Sepam) All except 59N, 27S
Functions available
Voltages measured U21, V0
Values calculated f
Measurements available U21, V0, f
Protection functions available (according to type of Sepam) All except 47, 27D, 27S
Functions available
Voltages measured U21
Values calculated f
Measurements available U21, f
Protection functions available (according to type of Sepam) All except 47, 27D, 59N, 27S
DE80969
N N
When a ground fault occurs on a TN-S or TN-C When a ground fault occurs on a TT or IT network, the neutral potential is affected:
network, the neutral potential is not affected: the neutral the neutral cannot act as a reference for the VTs, phase-to-phase voltages must be
can act as a reference for the VTs. used on both phases.