1. Reinforcing bar standards
USA
700
USA: ASTM A615 (2018) Standard specification for
600
deformed and plain carbon-steel bars for concrete
Min. YS (MPa)
400
Grade 40 280 420 11~12
300
Grade 60 420 620 7~9
200
Grade 75 520 690 6~7
Grade 80 550 725 6~7
100
Grade 100 690 790 6~7
※ Elongation depends on diameter of rebar 0
Vietnam Korea Japan USA EU
EU
☞ Most of country uses high strength rebar of
YS 600 MPa for cost effective design.
EU: EN 1992-1-1 (2004) Annex C
2/17
2. Allowable strength of reinforcing bar
KCI, 2012 ACI 318, 2014 TCVN 5574, JSCE, BDS, 2012 AASHTO, 22TCN-05
Member Eurocode2
(Building) (Building) 2012 (Building) 2007 (Bridge) 2017 (Bridge) (Bridge)
Building
Structure Building Bridge
/Bridge
Main 560
600
Flexural reinforcement (80 ksi)
member Shear 420 690
500 600
reinforcement (60ksi) (100 ksi,
(general)
general)
Main 560
600 500 600 490 500
reinforcement (80 ksi)
Flexural 560
and Tie 420 500
500 (80 ksi,
axial reinforcement (60 ksi) (earthquake)
earthquake)
member
Spiral 420
500
reinforcement (60 ksi)
☞ Korean building design code (KCI, 2012) allows the use of high strength rebar up to YS of 600 MPa.
※ Vietnam building design code (TCVN 5574, 2012) needs to be revised to consider newly updated rebar
standard TCVN 1651-2.
3/17
3. Case study of high strength rebar - Korea
Seung-Ho Cho, Seunguk Na (2017), The quantity variations of the high-strength
Case 1: Underground parking structure reinforcing bars on the underground parking in a rigid-fram building, Int. Journal of
Applied Engineering Research, Vol. 12, No. 8, pp. 1488-1499.
Rebar application
Wall O X
Retaining wall O X
Footing O X
Design code KCI: Korea Concrete Institute, KBC: Korea Building Code
4/17
3. Case study of high strength rebar - Korea
Case 1: Underground parking structure
Slab (Main rebar) Beam and Girder (Main rebar + Shear rebar)
Rebar Total Pure Rebar Connection/
Diameter Main Rebar (ton) Shear
grade (ton) (ton) Splice (ton)
Rebar Total
D10 0.99 0.93 0.06 Pure Connection/ Sub Rebar
grade (ton) 1)
SD400
D13 62.06 57.29 4.77 rebar Spice Total (ton)2)
D16 8.08 7.29 0.79
SD400 126.7 81.18 13.7 94.88 31.79
Sum 71.13 65.51 5.62
SD500 101.3 64.1 11.82 75.92 25.35
D10 19.37 18.07 1.3
D13 32.26 29.3 2.96 SD600 87.26 54.02 7.89 61.91 25.35
SD500
D16 3.51 3.02 0.49 1) D25, D22, D19 for SD400, SD500, SD600, respectively
Sum 55.14 50.39 4.75 2) D13, Max. allowable stregnth for shear is 500 MPa
D10 28.57 26.6 1.97
SD600 D13 21.05 18.66 2.39
Sum `
49.62 45.26 4.36
140
100% ` Shear rebar
80 120 Main rebar
100% Connection/Splice 80%
70 100
69%
Quantity (ton)
Pure rebar
60 78% 80
70%
Quantity (ton)
50
60
40
30 40
20 20
10
0
0
SD400 SD500 SD600
SD400 SD500 SD600
5/17
3. Case study of high strength rebar - Korea
Case 1: Underground parking structure
Quantity (ton)
25
Quantity (ton)
20
20
15 15
10 10
5
5
0
0 SD400 SD500 SD600
SD400 SD500 SD600
6/17
3. Case study of high strength rebar - Korea
Case 1: Underground parking structure
Sum `
127.89 99.33 28.56 Sub
Total
319.53 49.62 ` 87.26 23.83 30.93 127.89
180 100%
Connection/Splice Footing Wall Column Beam Slab
160 86% Pure rebar 500
100%
140 73%
400 84%
Quantity (ton)
120
74%
Quantity (ton)
100 300
80
60 200
40
100
20
0 0
SD400 SD500 SD600
SD400 SD500 SD600
7/17
3. Case study of high strength rebar - Korea
Case 1: Underground parking structure 1.080
SD400 SD500 SD600
Cost comparison (rebar, fabrication, labor) 1.060
Summary
- For slab, beam, footing, the effect of high strength rebar is large because the applied loads are large.
- When the structure with SD500, SD600 is designed in compliance with Korean codes, the total amount
of rebar can be reduced by 16%, 26%, respectively compared to SD400. The total cost (rebar, fabrication,
labor) can be reduced by 14%, 23% respectively.
- The combined use of SD400, SD500, SD600 can be considered for better handling of rebar size in the
construction site.
8/17
3. Case study of high strength rebar - Korea Seung-Ho Cho, Chang-Kil Ju, In-Kwan Park, Lan
Chung (2013), Economic analysis on the hig strength
reinforcing bar in the apartment, Journal of Seismic
Retrofitting Remodeling Research, Vol. 11, No. 2, pp.
Case 2: Living apartment (25 story with 1 underground story) 9-17 (in Korean).
14.6 m
Drawings Structure
11.3 m
Purpose: Living apartment
Structure type: RC
Footing type: Mat footing (bearing capacity of soil)
`
Concrete compressive strength:
fck = 24 MPa for 11F~RF Vertical member, B1~RF
Horizontal member, foundation
fck = 27 MPa for B1~10F Vertical member
Design code KCI: Korea Concrete Institute, KBC: Korea Building Code
9/17
3. Case study of high strength rebar - Korea
Case 2: Living apartment (25 story with 1 underground story)
Slab (Main rebar) Beam and Girder (Main rebar + Shear rebar)
Quantity (ton)
Quantity (ton)
100 40
80 30
60
20
40
10
20
0
0
SD400 SD500 SD600
SD400 SD500 SD600
10/17
3. Case study of high strength rebar - Korea
Case 2: Living apartment (25 story with 1 underground story)
Rebar Total
Vertical Rebar (ton) Horizontal Rebar (ton)
Rebar Total Pure Rebar Connection/
grade (ton) Diameter
Pure Connection/ Sub
Diameter
Pure Connection/ Sub
Diameter
D10
rebar
64.49
Spice
7.06
Total
71.55 D10
rebar
116.08
Spice
0.37
Total
116.45
grade (ton) (ton) Splice (ton)
D13 16.91 2.39 19.3 D13 6.97 0.12 7.09 D19 12.85 10.87 1.98
D16 18.1 3.25 21.35 sum 123.05 0.49 123.54
SD400 253.07
D19 13.33 3.31 16.64 SD400 D22 17.55 13.98 3.57
D22 0.53 0.16 0.69
sum 113.36 16.17 129.53 Sum 30.4 24.85 5.55
D10 68.25 9.29 77.54 D10 116.08 0.46 116.54
D13 12.27 2.2 14.47 D13 6.97 0.15 7.12 D16 0.36 0.36 0
SD500 247.55 D16 16.29 3.59 19.88 sum 123.05 0.61 123.66
D19 9.17 2.83 12 SD500 D19 25.06 20.39 4.67
sum 105.98 17.91 123.89
D10 69.61 11.2 80.81 Sum 25.42 20.75 4.67
D13 13.4 2.93 16.33
SD600 241.19 D16 12.63 3.42 16.05 Use SD500 Horizontal rebar D16 9.18 7.53 1.65
D19
sum
2.98
98.62
1.36
18.91
4.34
117.53
SD600 D19 13.06 10.35 2.71
Sum 22.24 17.88 4.36
` `
300 35
100% Horizontal rebar
100% Connection/Splice
98% Vertical rebar 30
250 95% Pure rebar
84%
25 73%
Quantity (ton)
Quantity (ton)
200
20
150
15
100
10
50
5
0 0
SD400 SD500 SD600
SD400 SD500 SD600
11/17
3. Case study of high strength rebar - Korea
Case 2: Living apartment (25 story with 1 underground story)
Grade Total (ton) Slab(ton) Beam (ton) Wall (ton) Footing (ton) Total quantity
Pure
439.85 139.83 38.76 236.41 24.85
rebar
Footing Wall Beam Slab
Connection/
SD400 45.36 6.77 16.38 16.66 5.55 500
Spice
100% 102% 90%
Sub
485.21 146.6 55.14 253.07 30.4
Total 400
Pure
426.97 122.05 55.14 229.03 20.75
Quantity (ton)
rebar
300
Connection/
SD500 68.07 7.18 37.7 18.52 4.67
Spice
Sub 200
495.04 129.23 92.84 247.55 25.42
Total
Pure
392.97 122.05 31.37 221.67 17.88 100
rebar
Connection/
SD600 45.22 8.57 12.77 19.52 4.36
Spice 0
Sub
`
SD400 SD500 SD600
438.19 130.62 44.14 241.19 22.24
Total
Case study
13/17
3. Case study of high strength rebar - Vietnam
8-story office building
Foundation Column
[Case 1-CB300, CB400] [Case 2-CB500, CB600]
[Case 1-CB300, CB400] Grade Diameter Weight(ton) Grade Diameter Weight(ton)
Grade Diameter Weight(ton) CB300 D10 13.96 CB500 D10 15.69
CB400 D12 3.46 CB300 D12 0.81 CB500 D12 1.35
CB400 D16 0.34 CB300 D16 2.40 CB600 D16 4.88
CB400 D18 0.30 CB400
CB400
D16
D18
2.42
0.34
` CB600
CB600
D18
D20
9.49
14.98
CB400 D20 1.61
CB400 D22 1.44 CB400 D20 17.06 CB600 D22 1.05
CB400 D25 2.94 CB400 D22 16.96 CB600 D25 4.96
CB400 D28 2.59 CB400 D25 2.85 CB600 D28 0.88
Sum 12.67 CB400 D28 3.76 Sum 53.28
Sum 60.55
[Case 2-CB500, CB600] • 12% reduction in weight
` Grade Diameter Weight(ton)
CB600 D12 3.46
CB600 D14 0.34 Slab
CB600 D18 1.60
CB600 D20 0.42
[Case 1-CB300, CB400] [Case 2-CB500, CB600]
CB600 D22 0.94 Grade Diameter Weight(ton) Grade Diameter Weight(ton)
CB600 D25 5.01 CB400 D10 74.31 CB600 D10 68.38
Sum 11.76 CB400 D12 29.67 CB600 D12 25.63
CB400 D16 19.07 ` CB600 D16 17.03
CB400 D18 67.49 CB600 D18 25.13
• 7% reduction in weight
CB400 D20 1.61 CB600 D22 6.16
CB400 D22 6.55 Sum 142.33
Sum 198.71
14/17
3. Case study of high strength rebar - Vietnam
8-story office building
15/17
3. Case study of high strength rebar - Vietnam
8-story office building
Total
Slab
495
Beam Material
(100%)
Retainig wall 17% Fabricaion
372
(75%) Column
Slab 4% Construction
Foundation
Beam
Retainig wall
`
Case 1 Case 2
[Total rebar quantities (ton)] [Cost composition of Case 1]
Summary
- The effect of high strength rebar for slab and beam (more than 80% of total amount of required rebar)
is large, so the total amount of rebar is reduced as 25%.
- The fabrication and construction cost of rebar is proportional to weight of rebar, so the fabrication and
construction cost of Case 2 can be reduced 25% which is around 5% of total construction cost of Case 1.
- The material cost also can be reduced for Case 2 because of 25% reduction in total amount of required
rebar.
16/17
4. Conclusions
High strength rebar CB600
Recently, rebar standard of Vietnam (TCVN 1651-2) has been revised to incorporate high strength rebar,
i.e., CB600 (YS 600 MPa).
Cost effective design is possible using high strength rebar by reducing the total required amount of rebar
(reduce diameter and/or amount).
When the amount of rebar is reduced, the fabrication and installation cost of rebar will be reduced
simultaneously.
※ Currently, Only SS VINA can produce high strength rebar, i.e., CB600.
The total amount and cost are reduced as 26% and 23%, respectively for underground parking lot when
compared to SD400 application.
The total amount and cost are reduced as 10% and 6%, respectively for 25-story living apartment when
compare to SD400 application.
Vietnam case – CB600
The total amount is reduced as 25% for 8-story office building when compared to CB400 application.
☞ The effect of high strength rebar depends on the structure type as well as loading conditions.
17/17