Rear Panel Layout: Description Item
Rear Panel Layout: Description Item
Rear Panel Layout: Description Item
Cut-Out: 66 x 66 ± 0.5 mm
The Model GCU-10 is an Automatic Engine Control Module,
designed to meet the demand of the generator industry. The Adjustment
module starts and stops the generator, and at the same time In the back, the GCU-10 has five adjustment pots that changes
indicates the operation status and fault conditions, if it senses a five common time delay functions.
fault it will automatically shuts down the engine and indicates the
● A - Engine Pre-Heat Adjustable from 2 to 30sec
engine failure by means of eight LED’s. The technician can
program the module according to different generator ● B - Starter Cranking time Adjustable from 1 to 15sec
requirements complying with different conditions and protections. ● C - Energize to STOP Adjustable from 1 to 15sec
● D - Engine Idle (Elec. Governor) Adjustable from 0 to 300sec
Protection Setting ● E - Engine Cool-down Adjustable from 0 to 300sec
Engine fail to start reattempt
Engine tries 3 times to start Function Setting
Engine High Water temperature Protection
On the back of the control we have five pins dipswitches that set
Shutdown activated after 3 sec delay by NO Contacts
the specification of the genset.
Engine Low Oil Pressure Protection
Shutdown activated after 3 seconds SW 1: Generator Frequency
Oil Pressure Switch Type: NO or NC Contacts ON-50Hz - OFF-60Hz
Engine Over-speed Protection SW 2: Battery Voltage
Shutdown activated after 3 seconds ON-12V - OFF-24V
At 50Hz activation at 55 Hz - 60Hz activation at 66 Hz SW 3: Fuel Solenoide
Engine Underspeed Protection ON: Energize to Start - OFF: Energize to Stop
Shutdown activated after 5 seconds SW 4: Oil Pressure Switch Type
At 50Hz activation at 55 Hz - 60Hz activation at 66 Hz ON - Normal Open Sensor - OFF - Normal Close Sensor
Emergency Shutdown SW 5: Oil Pressure Switch (Used For Crank Disconnect)
Shutdown activated by NO Contacts ON - Disabled, not used for crank disconnect
Spare / User define Shutdown OFF - Enable, used for crank disconnect
Shutdown activated after 5 sec delay by NO Contacts
Low Battery Voltage Warning Specification
Activated after 5 seconds delay
For 12VDC activated at 10VDC - 24VDC activated at 20DCV ITEM DESCRIPTION
DC Supply 9.0 to 36 VDC
Icon Reference Table Alternator Input Range 5 ~ 300VAC
ICON DESCRIPTION ICON DESCRIPTION Alternator Input Frequency 50/60 Hz
Fuel Solenoid Signal Output 5 Amp @ 12/24VDC
Power Source Over-speed Start Signal Output 5 Amp @ 12/24VDC
Warm up Signal Output 5 Amp @ 12/24VDC
Engine Running Under-speed Alarm Signal Output 5 Amp @ 12/24VDC
Idle Control Conductor Capacity 5 Amp @ 12/24VDC
Start Failure Emergency Stop
Operating Temperature -20 °C to +70 °C
By moving the knob to the OFF position, the genset will STOP
immediately.
Standard Wiring Diagram
5A 5A 5A 5A
J1-1 J1-2 J1-3 J2-13 J2-12 J2-8 J2-9 J1-7 J1-6 J1-4 J2-11 J2-10 J2-5 J2-14 J2-15
Emergency Stop
Remote Start
AC 5V - 300V
AUX. Alarm
TEMP SW
OIL SW
Idel Control
Idel Control
10A
0.5A
Alternator
Accessory “ON”
+
Pre-Heat
Electronic
Battery
STOP
Governor
Start
B+
FUEL B+
STOP
Button
Remote
Start Extra input Temperature
STOP/FUEL Sensor
START
EXTRA OUTPUT
G AC 5v to 300Vac
Engine
Pre-Heat
B+
Oil Pressure
Sensor
STOP
Button
Remote
Start Extra input Temperature
Sensor
Oil Pressure
Sensor
5 to 300 Volts
B+
FUEL
Engine
Pre-Heat
G
Starter