Characterization of Phase Resolved Partial Discharge Waveforms From Instrument Transformer Using Statistical Signal Processing Technique
Characterization of Phase Resolved Partial Discharge Waveforms From Instrument Transformer Using Statistical Signal Processing Technique
Characterization of Phase Resolved Partial Discharge Waveforms From Instrument Transformer Using Statistical Signal Processing Technique
*
TNB Research Sdn. Bhd.
Lorong Ayer Itam, 43000 Kajang, Selangor
5
yogendra@tnbr.com.my
Abstract—Partial Discharge (PD) detection is one of the IT. The failures due to PD may result into violent explosions
important methods used to evaluate the insulation condition of that cause personal injuries and damage to nearby equipment.
in-service high voltage (HV) electrical equipment. On-site PD This may then require high equipment replacement costs and
detection methods are preferred compared to other methods as increases unexpected expenditure [3, 4]. Therefore, condition
non-intrusive sensors are easier to install and have no
assessment of in-service high voltage instrument transformer
interruptions on the operation. An electrical PD testing utilizing
High Frequency Current Transformer (HFCT) installed at the should be carried out to assess the condition of the IT in order
ground terminal of the in-service instrument transformer was to avoid unexpected failures.
used to detect partial discharge activities. However, the limitation Electrical partial detection (PD) detection is one of the
of this method is the measurement often lacks of accuracy due to important methods used to monitor and evaluate the condition
interference in the measured PD waveforms. Therefore, such PD of in-service high voltage electrical equipment. On-line partial
signals are hard to be distinguished from the stochastic noise discharge testing is performed during real operating condition
pulses. Hence, the characteristics of PD signals and interference with normal operating voltage. This is a non-destructive test;
signals are studied in the Phase Resolved Partial Discharge therefore non-intrusive sensors which are easy to install and
(PRPD) pattern in order to identify the extent of PD occurrence
require no interruptions on the operation of the high voltage
in the signals. The discharge magnitude could increase
significantly because of the noise signals superposed with PD (HV) equipment are preferred for on-site PD detection. Hence,
signals. Therefore a method that can remove high magnitude in this research, electrical PD test utilizing High Frequency
noise will be proposed by using statistical signal processing Current Transformer (HFCT) installed at the ground terminal
technique. of the instrument transformer was used to detect partial
Keywords—partial discharge; instrument transformer; discharge activities [5].
inteferences; phase resolved partial discharge pattern; statistical As defined by IEC60270, ‘Partial discharge is a localized
signal processing technique electrical discharge that only partially bridges the insulation
between conductors and which can or cannot occur adjacent to
I. INTRODUCTION a conductor [6]. PD usually started within voids and cracks.
Instrument transformers (IT) are used to transform voltage Since PDs are limited to only a portion of the insulation, the
or current from high to low values that can be utilized by discharges only partially bridge the distance between
electrical equipment for monitoring or metering purposes in electrodes. PD can also occur along the boundary between
transmission or distribution systems. It is also designed to different insulating materials. The electric field across the void
safely isolate the utilization current or voltage for secondary is significantly higher than that across an equivalent distance of
end device from the primary supply voltage [1, 2]. IT plays an dielectric due to the dielectric constant of the void is
important role in electrical system; however, IT in services are considerably less than the surrounding dielectric. If the voltage
exposed to stresses, such as electrical, thermal and mechanical stress across the void is increased above the corona inception
stresses that can cause degradation or deterioration of the voltage (CIV) for the gas within the void, PD activity will start
insulating system in IT. Those stresses and environmental within the void [7].
condition will affect the performances of IT and lead to failure. In this research, electrical PD detection is used to monitor
Partial discharge (PD) is one of the cause of severe failure in the status of IT. However, PD measurement performed on-site
355
2015 IEEE International Conference on Signal and Image Processing Applications (ICSIPA)
and under noisy condition is a challenging task. The this characteristics can also be used for further analysis of the
measurement often lacks of accuracy due to interference in PD PRPD pattern obtained from HFCTs.
signals [8]. PD signals are often superposed with stochastic
noise pulses or even multiple PD sources, which leads to a
complex phase resolved PD patterns that are not easy to
analyze and distinguish. Therefore, characteristics of PD and
noise in the PRPD patterns are studied in order to differentiate
between PD signals and noise.
According to IEEE standard (IEEE Std C57.113-2010),
noise that could be encountered from on-site PD measurement
are harmonics, radio frequency (RF) noise, corona and
sparking which are generated by several different kinds of
sources [9]. Analysis of possible interference patterns is
essential to distinguish PD from interferences in the PRPD
pattern. The discharge magnitude could be increased
significantly because of the noise signals superposed with PD
signals. Therefore, a technique that can remove high magnitude
noise using statistical signal processing will be proposed.
However, in some cases, the noise signals cannot be removed
completely and analysis on the filtered signals will be essential.
Fig. 1. Sequence of cavity breakdown under alternating voltages: (a) voltage
II. PHASE RESOLVED PARTIAL DISCHARGE (PRPD) waveforms and (b) PD Pulses [13]
356
2015 IEEE International Conference on Signal annd Image Processing Applications (ICSIPA)
357
2015 IEEE International Conference on Signal and Imagee Processing Applications (ICSIPA)
400pC
Fig. 4. PRPD pattern from the exxperimental setup: (a) exp132332 (b)
exp154523 (c) exp150246 (d) exp1538818
358
2015 IEEE International Conference on Signal and Image Processing Applications (ICSIPA)
Fig. 5 illustrates the possible noise identified from the maximum value for ı per cycle. If q falls in the range, then a
PRPD measurement obtained from KL North Bay 405 which ‘low’ descriptor will be produced, otherwise a ‘high’. The
are in accordance with the possible noise that can exist in an results are summarized in Table II and Table III.
on-site PD measurement as stipulated by the IEEE Standard
(IEEE Std C57.113-2010). Hence, it is necessary to eliminate TABLE II. PARAMETERS FOR THE APPARENT CHARGE FROM THE
EXPERIMENTAL DATA
the noise in the on-site PD measurement data before any
further diagnosis can be made on the severity of the PD Before Noise Elimination After Noise Elimination
TABLE III. PARAMETERS FOR THE APPARENT CHARGE FROM THE ON-
SITE DATA
359
2015 IEEE International Conference on Signal and Image Processing Applications (ICSIPA)
statistical signal processing technique for eliminating applied to on-site data to test the practicality of the technique
disturbances that exist on site during PD measurement. and the results obtained are the same as expected. Therefore,
the proposed statistical signal processing technique is capable
TABLE IV. SUMMARY OF RESULTS FROM STATISTICAL ANALYSIS and appropriate to be used for a more reliable diagnosis of PD
Statistical for on-site measurement of ITs.
Analysis
DATA Actual Status ACKNOWLEDGEMENT
after
Filtration This project is funded by TNB Research SDN. BHD. The
exp132332 High PD High PD
research work is carried out in collaboration with UNITEN
exp154523 Low PD Low PD
Experimental
exp150246 High PD High PD R&D SDN. BHD.
exp153818 Low PD Low PD
Satisfactory REFERENCES
KL405 Low PD
Condition [1] GE Digital Energy ITI, Instrument Transformer Basic Technical
Satisfactory Information and Application, pp. 3.
Site KL136 Low PD
Condition [2] ABB, Instrument Transformers Technical Information and Application
Satisfactory Guide, pp. 4.
Perak205 Low PD [3] V. R. Garcia-Colon, R. Linan-Garcia, M. A. Jacobo, “On-line condition
Condition
assessment of high voltage current transformers,” Electrical Insulation,
2004. Conference Record of the 2004 IEEE International Symposium
on, vol., no., pp. 182, 185, 19-22 Sept. 2004.
VI. CONCLUSION [4] T. R. Blackburn, B. T. Phung, Z. Liu, R. E. James, “On-line partial
In conclusion, partial discharge (PD) detection is an discharge measurement on instrument transformers,” Electrical
important method to evaluate the insulation condition of an Insulating Materials, 1998. Proceedings of 1998 International
Symposium on, vol., no., pp. 497, 500, 27-30 Sept 1998.
instrument transformer (IT). Electrical partial discharge [5] Guomin Luo, Daming Zhang, “Study on Performance of HFCT and
measurement using high frequency current transformer (HFCT) UHF Sensors in Partial Discharge Detection,” 2010. IPEC 2010 on
is an alternative technique for PD detection as PD pp.630.
measurement can be done on in-service IT and non-intrusive, [6] IEC 60720, “Partial Discharge Measurements”, Third Edition, 2000-12.
[7] A. Mehta, R. N. Sharma, S. Chauhan, “Partial discharge study by
without the IT to be offline. However, the limitation of monitoring key gases of power transformers,” Electronics Computer
electrical PD measurement is that it is highly susceptible to Technology (ICECT), 2011 3rd International Conference on, vol. 4, no.,
electromagnetic interference and noise found in any substations pp. 183, 186, 8-10 April 2011.
which may superposed with PD signals. Hence, this could also [8] A. Kraetge, S. Hoek, K. Rethmeier, M. Kruger, P. Winter, “Advanced
be the reason for high PD activities detected during on-site noise suppression during PD measurement by real-time pulse-waveform
analysis of PD pulses and pulse-shaped disturbances,” Electrical
measurement of the instrument transformers. DGA test carried Insulation (ISEI), Conference Record of the 2010 IEEE International
out on three of the instrument transformers showed that the Symposium on, vol., no., pp. 1, 6, 6-9 June 2010.
instrument transformers were in good or acceptable condition [9] IEEE Standard C57.113, “IEEE Recommended Pratice for Partial
although the PRPD measurement showed high values of PD. Discharge Measurement in Liquid-Filled Power Transformers and Shunt
As such in this research, a study has been carried out to Reactors,” 2010.
[10] Mohamad Ghaffarian Niasar, “Partial Discharge Signatures of Defects in
study the characteristics of PD to identify noise from on-site Insulation Systems Consisting of Oil and Oil-impregnated Pape,” KTH
electrical PD measurement data obtained from MPD 600 PD Electrical Engineering, pp. 11-20, 27, 28, 2012.
measurement system. Initially, the electrical PD measurement [11] Gabe Paolettie, P.E. and Alex Golubev, PhD, “Partial Discharge Theory
which was in the form of PRPD pattern were visualized and and Applications to Electrical Systems. Pulp and Paper,” 1999. Industry
Technical Conference Record of 1999 Annual, pp.128, 138, 21-25 June
evaluated. Then, the types of noise that could interfere with the 1999.
measured PD signals were identified. [12] M. S. Naidu, V. Kamaraju, High Voltage Engineering, Fourth Edition,
Furthermore, a statistical signal processing technique is The McGraw-Hill Companies, pp. 99-101.
proposed for eliminating disturbances using statistical [13] E. Kuffel, W. S. Zaengl, High Voltage Engineering Fundamentals,
parameters. The technique is designed to eliminate outlier Pergamon Press, pp. 409.
[14] Y. R. Chaudhari, N. R. Bhosale, P. M. Kothoke, “Composite analysis of
discharges based on criteria of two standard deviation (μ ± 2ı). phase resolved partial discharge patterns using statistical techniques,”
According to normal distribution curve, criteria for two International Journal of Modern Engineering Research on, vol. 3, pp.
standard deviation eliminates only about 4.6% of the 1947-1457, Jul-Aug 2013.
distribution and it will not affect the PD signal, as it has been [15] F. H. Kreuger, E. Gulski, A. Krivda, “Classification of partial
proven by laboratory experiments. The statistical analysis is discharges,” Electrical Insulation, IEEE Transactions on, vol. 28, no. 6,
pp. 917, 931, Dec 1993.
applied before and after the elimination of the PD data, in order [16] C. G. Azcarraga, V.R. Garcia-Colon, and A. Nava G, “On-site Testing
to give a clearer perspective on the measured data and analyze of Instrument Transformers,” 2006 Annual Report Conference on
the differences. Electrical Insulation and Dielectric Phenomena, pp. 39, 42, 2006.
Statistical analysis on experimental results after the [17] British Standard BS EN 60270:2001, IEC 60270:2000. “High-voltage
test techniques – Partial discharge measurements,” British Standard
application of the proposed technique has clearly proven the Institution (BSI), London, 2001.
effectiveness of this technique to eliminate noise pulses from [18] Open Stax College, A Single Population Mean using Normal
PRPD measurement. Moreover, this technique has been Distribution, Nov 2014.
360