Test Report For Transformer Main Protection Relay: ND ND
Test Report For Transformer Main Protection Relay: ND ND
Test Report For Transformer Main Protection Relay: ND ND
DIFF / 003
TR.No. IPSE / BLR /102
PROJECT : ANNUAL MAINTENANCE TESTING OF 10MW SOLAR PLANT SHEET OF
Stable
Phase HV Side LV Side
Id(A) Ib(A) Result
Ref Injected current(A) Injected current(A)
R 0.265 ∟0 0.700 ∟150
Y 0.265 ∟-120 0.700 ∟30 0.02 0.98 Stable
B 0.265 ∟120 0.700 ∟270
HV pickup
LV pickup
Phase HV Side LV Side
Id(A) Ib(A) Trip time
Ref Injected current(A) Injected current(A)
R 0 ∟0 0.180 ∟210
Y 0 ∟-120 0.180 ∟90 0.20 0.10 36.6 ms
B 0 ∟120 0.180 ∟330
Slope : 30%
HV Side LV Side
Phase Ref Id(A) Ib(A) Slope(Id/Ib)
Injected current(A) Injected current(A)
R 0.265 ∟0 0.530 ∟150
Y 0.265 ∟-120 0.530 ∟30 0.24 0.86 27%
B 0.265 ∟120 0.530 ∟270
High set
HV Side LV Side
Phase Ref Id(A) Ib(A)
Injected current(A) Injected current(A)
R 5.1 ∟0 0 ∟150
Y 5.1 ∟-120 0 ∟30 5.1 2.6
B 5.1 ∟120 0 ∟270