Lab Report On Single Phase Transformer
Lab Report On Single Phase Transformer
By (Firstname Lastname)
Electrical Engineering
Professor (Tutor)
March 5, 2019
LAB REPORT ON SINGLE PHASE TRANSFORMER 2
Objective
The lab aim was is develop a good understanding of practical transformer features and to study
Introduction
between different current levels and alternating Current (AC) voltage levels. Transformer
performance laws and rules are very simple but some real transformer devices features seems to
be more complex than expected relating to the simple theories. The key issue is to learn both
This lab experiment involves applying and using the modern power frame training kits. The kit is
specifically designed for use in studying electrical machines and a transformer is included as
well.
Theory
Transformer contains magnetic core having many windings on both secondary and primary
section. This is shown in the figure below. Magnetic field is created when the current is passed
over the primary coil. The magnetic field induction takes place by enhancement of the magnetic
core, which confines the magnetic field flux to the flux path inside the core.
LAB REPORT ON SINGLE PHASE TRANSFORMER 3
The magnetic field flux alternate with equal frequency of the voltage when voltage is passed to
the primary coils. On reaching the secondary coils, EMF is created due to electromagnetic
induction. The number of turns on the coil as well as the rate of change of flux dictates the
Ideal Transformer
The equation used to express the voltage across both the primary and secondary coils are given
by equations below
LAB REPORT ON SINGLE PHASE TRANSFORMER 4
In the case of ideal transformer, the flux produce on the primary coiling is directly proportional
The ratio N1:N2 is called the turn ratio. In the case where the voltage in the secondary
coil/winding is higher than that in the primary coil/winding or the value of the turn ratio is less
than 1, the transformer is referred to as the step up transformer. While a transformer with turn
Ideal transformer has no power loss and therefore P1 = P2, where Power P = V*I hence V1I1 =
V2I2
Winding Polarity
The polarity of the secondary coil is dependent on the nature by which the coils are wounded
around the secondary coil. Same polarity is arrived at when the coils wound on the same
direction either clockwise or anticlockwise. The figures below illustrate the polarity of the
various coiling. The polarity affects the resulting voltage (Hughes & Smith, 2005). The polarity
of two windings can be determined by connecting the windings of the common terminals and
taking the measurement of the two non-common terminals. Voltage of the terminals having same
LAB REPORT ON SINGLE PHASE TRANSFORMER 5
amount with the difference of the individual voltages have same polarity. In the case the of the
voltage is sum or is equal to individual voltage, the polarities are opposite (Gates, 2013)
Output voltages and currents can be changed through connecting the secondary coils either in
series or parallel directions (Dingle & ooley, 2007). Secondary coils having same turn’s ratio are
connected in parallel. The polarity must be the same to stop destruction of the heavy currents.
Real transformers
LAB REPORT ON SINGLE PHASE TRANSFORMER 6
Real transformer have power loses. Looking at the figure below, the real transformer has
components that accounts for the loses. These loses recorded are seen causing the phase shift.
(Care, 2010)
Leakages of reactance caused by incomplete flux between the coils and represented by
X1 and X2
Phasor Diagrams
The figure below shows an illustration of the phasor diagram. The diagram describes the voltage
regulation
LAB REPORT ON SINGLE PHASE TRANSFORMER 7
Apparatus
Apparatus
One Oscilloscope
Experimental Procedures
The following steps are followed before the main experiment is carried out
LAB REPORT ON SINGLE PHASE TRANSFORMER 8
Powering the multichannel I/O unit is powered and switch on. This is kept on until the
experiment end. The voltmeter's switches were set at 500V while those of ammeters are
set at 1A. The earth terminal is connect to the universal power supply
The 3-phase power cable was plugged into the main socket thereafter switched on. The
The program was then started on the windows whereby the command used involved
measurement were activated. LED on the I/O unit was lit to show meters were in
operation. The other windows were used to check on other information such as apparent
Familiarization
The set up was familiarized by determine the effect of lad on the transformer.
The circuit was set up as shown with primary voltage of 40V. the readings recored
The turn number for the secondary coiling was determined since the primary core turns
The circuit was assembled as shown in the figure below. A resistance load of 546
ohms was set using the three phase resistive load. To achieve 546 ohm, 950 1950
and 3770 ohms are connected in parallel. the load switch was kept on and primary
The resistivity of the load was then disconnected by putting of the load switch,
The current and voltage ratios were computed and comparison made with the
Both the input and output power values were computed, differences noted and
Transformer Polarity
The polarities of all the winding of the transformers was established by the following steps
Firstly, the circuit was assembled as shown in the figure below, with the connection links. The
value of the primary voltage was placed at 40V. The readings were recorded and tabulated
below.
The experiment was repeated placing different connection and different value of the primary
voltage
The winding polarity was thereafter established for all the configurations. A circuit diagram with
a. Resistive load
A combination of switches were chosen together with a total load of 1822 ohms for the
The circuit was connected as shown in the figure below. Virtual instrumentation was
amended to enable taking and reading of power factors. The primary voltage is increased
The load switcher was then switched off by disconnecting the load.
Voltage regulation was determined by using output voltage on full load and at zero load
The power efficiency of the transformer at full load was then computed
LAB REPORT ON SINGLE PHASE TRANSFORMER 12
(V1/V2)
B 40 12.5 3.2
C 40 25 1.6
D 40 43 0.93
LAB REPORT ON SINGLE PHASE TRANSFORMER 13
From the results above it can be seen that averagely, the ratio is greater than 1, hence the
The voltage and current ratios were determined and tabulated in the tables below
Voltage ratios were computed and recorded as shown below with the polarity mentioned
V1 V2 Ratio (V)
Parallel Connection
V1 V2 I1 I2
Series connection
V1 V2 I1 I2
LAB REPORT ON SINGLE PHASE TRANSFORMER 14
Core-loss loop
V I
5 2.5
10 4.3
15 5.7
20 6.8
25 7.6
30 8.4
35 9.1
40 9.7
45 10.3
50 10.9
Low = 5
Medium = 25
High = 50
LAB REPORT ON SINGLE PHASE TRANSFORMER 15
LAB REPORT ON SINGLE PHASE TRANSFORMER 16
V1 V2 I1
V1 I1 I2
26 0.440 0.802
Phasor Diagram
Magnetizing Current waveform for low, medium and high primary voltages
LAB REPORT ON SINGLE PHASE TRANSFORMER 17
LAB REPORT ON SINGLE PHASE TRANSFORMER 18
a.
V1 V2 I1 I2
b.
V1 V2 I1 I2
c.
V1 V2 I1 I2
LAB REPORT ON SINGLE PHASE TRANSFORMER 21
Conclusion
The experiment was successful and the following conclusion was made.
The aim of the experiment was achieved since there were no serious anomalies, which
were met during the experiment. The understanding of the practical transformer features
were realized whereby a lot of methods used to evaluate transformer performance was
exhausted
LAB REPORT ON SINGLE PHASE TRANSFORMER 22
References
Care, C., 2010. Technology for Modelling: Electrical Analogies, Engineering Practice, and the
Gates, E. D., 2013. Introduction to Basic Electricity and Electronics Technology. s.l.:Cengage
Learning.
Hughes, E. & Smith, I. M., 2005. Hughes electrical technology. Pennsylvania State University: