Earthing
Earthing
Earthing
Installation
Electrical Earthing, Grounding, Methods Of Earthing, Types of Earthing, Components of
Earthing And Its Specifications In Respect To Electrical Earthing for Electrical Installations.
Table of Contents
In other words, to connect the metallic parts of electric machinery and devices to the earth plate
or earth electrode (which is buried in the moisture earth) through a thick conductor wire (which
has very low resistance) for safety purpose is known as Earthing or grounding.
To earth or earthing rather, means to connect the part of electrical apparatus such as metallic
covering of metals, earth terminal of socket cables, stay wires that do not carry current to the
earth. Earthing can be said as the connection of the neutral point of a power supply system to
the earth so as to avoid or minimize danger during discharge of electrical energy.
Electrical Earthing and Grounding
Good to know
Difference between Earthing, Grounding and Bonding
Let me clear the confusion among earthing, grounding and bonding.
Earthing and Grounding are the same terms used for earthing. Grounding is the commonly word
used for earthing in the North American standards like IEEE, NEC, ANSI and UL etc while,
Earthing is used in European, Common wealth countries and Britain standards like IS and IEC
etc.
The word Bonding used for jointing two wires (as well as conductors, pipes or appliances
together. Bonding is known as connecting the metallic parts of different machines which is not
considered to be carrying electric current during normal operation of the machines to bring them
at the same level of electric potential.
When the metallic part of electrical appliances (parts that can conduct or allow passage of
electric current) comes in contact with a live wire, maybe due to failure of installations or failure
in cable insulation, the metal become charged and static charge accumulates on it. If a person
touches such a charged metal, the result is a severe shock.
To avoid such instances, the power supply systems and parts of appliances have to be earthed
so as to transfer the charge directly to the earth. This is why we need Electrical Earthing or
Grounding in electrical installation systems.
To protect human lives as well as provide safety to electrical devices and appliances from
leakage current.
To keep voltage as constant in the healthy phase (If fault occurs on any one phase).
To Protect Electric system and buildings form lighting.
To serve as a return conductor in electric traction system and communication.
To avoid the risk of fire in electrical installation systems.
Different Terms used in Electrical Earthing
Earth: The proper connection between electrical installation systems via conductor to the buried
plate in the earth is known as Earth.
Earthed: When an electrical device, appliance or wiring systems connected to the earth through
earth electrode, it is known as earthed device or simple “Earthed”.
Solidly Earthed: When an electric device, appliance or electrical installation is connected to the
earth electrode without a fuse, circuit breaker or resistance/Impedance, It is called “solidly
earthed”.
Earth Electrode: When a conductor (or conductive plate) buried in the earth for electrical
earthing system. It is known to be Earth Electrode. Earth electrodes are in different shapes like,
conductive plate, conductive rod, metal water pipe or any other conductor with low resistance.
Earthing Lead: The conductor wire or conductive strip connected between Earth electrode and
Electrical installation system and devices in called Earthing lead.
Earth Continuity Conductor: The conductor wire, which is connected among different electrical
devices and appliances like, distribution board, different plugs and appliances etc. in other
words, the wire between earthing lead and electrical device or appliance is called earth
continuity conductor. It may be in the shape of metal pipe (fully or partial), or cable metallic
sheath or flexible wire.
Sub Main Earthing Conductor: A wire connected between switch board and distribution board
i.e. that conductor is related to sub main circuits.
Earth Resistance: This is the total resistance between earth electrode and earth in Ω (Ohms).
Earth resistance is the algebraic sum of the resistances of earth continuity conductor, earthing
lead, earth electrode and earth
Points to be Earthed
Earthing is not done anyhow. According to IE rules and IEE (Institute of Electrical Engineers)
regulations,
Earth pin of 3-pin lighting plug sockets and 4-pin power plug should be efficiently and
permanently earthed.
All metal casing or metallic coverings containing or protecting any electric supply line or
apparatus such as GI pipes and conduits enclosing VIR or PVC cables, iron clad switches, iron
clad distribution fuse boards etc should be earthed (connected to earth).
The frame of every generator, stationary motors and metallic parts of all transformers used for
controlling energy should be earthed by two separate and yet distinct connections with the
earth.
In a dc 3-wire system, the middle conductors should be earthed at the generating station.
Stay wires that are for overhead lines should be connected to earth by connecting at least one
strand to the earth wires.
Related Post: Testing Electrical and Electronics Components and Devices with Multimeter
The resistance of the earth continuity conductor is very low. According to IEEE rules, resistance
between consumer earth terminal and earth Continuity conductor (at the end) should not be
increased than 1Ω. In simple words, resistance of earth wire should be less than 1Ω.
Size of the Earth Continuity Conductor or Earth Wire depends on the cable size used in the
wiring circuit.
Generally, the size of the bare copper wire used as earth continuity conductor is 3SWG. But
keep in mind that, don’t use less than 14SWG as earth wire. Copper strip is also can be used as
earth continuity conductor instead of bare copper wire but don’t go for it until manufacture
recommend it.
Related Post: How to Find The Suitable Size of Cable & Wire for Electrical Wiring Installation?
Earthing Lead or Earthing Joint
The conductor wire connected between earth continuity conductor and earth electrode or earth
plate is called earthing joint or “Earthing lead”. The point where earth continuity conductor and
earth electrode meet is known as “connecting point” as shown in the above fig.
Earthing lead is the final part of the earthing system which is connected to the earth electrode
(which is underground) through earth connecting point.
There should be minimum joints in earthing lead as well as lower in size and straight in the
direction.
Generally, copper wire can be used as earthing lead but, copper strip is also used for high
installation and it can handle the high fault current because of wider area than the copper wire.
A hard drawn bare copper wire is also used as an earthing lead. In this method, all earth
conductors connected to a common (one or more) connecting points and then, earthing lead is
used to connect earth electrode (earth plat) to the connecting point.
To increase the safety factor of installation, two copper wires are used as earthing lead to
connect the device metallic body to the earth electrode or earth plate. I.e. if we use two earth
electrodes or earth plats, there would be four earthing leads. It should not be considered that
the two earth leads are used as parallel paths to flow the fault currents but both paths should
work properly to carry the fault current because it is important for better safety.
The largest size for earthing lead is 3SWG and the minimum size should not be less than
8SWG. If 37/.083 wire is used or the load current is 200A from the supply voltage, then it is
recommended to use copper strip instead of double earthing lead. The earth lead connection
methods is shown in the above fig.
Note: We will post additional article about Earth Plate size with simple calculations… Stay tune.
A metallic plate, pipe or rode can be used as an earth electrode which has very low resistance
and carry the fault current safely towards ground (earth).
In case of Iron
2′ x2′ x ¼” = 600x600x6 mm
It is recommended to bury the earth electrode in the moisture earth. If it is not possible, then put
water in the GI (Galvanized Iron) pipe to make possible the moisture condition.
In the earthing system, put the earth electrode in vertical position (underground) as shown in the
above fig. Also, put a 1 foot (about 30cm) layer of powdered charcoal and lime mixture around
the earth plate (don’t confuse with earth electrode and earth plate as both are the same thing).
This action makes the possible increase in the size of the earth electrode which leads a better
continuity in the earth (earthing system) and also helps to maintain the moisture condition
around earth plate.
P.S: We will post Example calculation about Earth Electrode Sizing… Stay tune.
Good to know:
Don’t use coke (after burning coal in the furnace to emit all the gases and other components,
the remaining 88% carbon is called coke) or stone coal instead of charcoal (wood coal) because
it causes to corrosion in the earth plate.
Since, the water level is different in the different areas; therefore, the depth for earth electrode
installation is also different in various areas. But, the depth for earth electrode installation should
not be less than 10ft (3 meter) and should below 1 foot (304.8mm) from the constant water
level.
Motors, Generator, Transformers etc should be connected from to earth electrode two different
places.
Related Post: All About Electrical Protection Systems, Devices And Units
Methods and Types of Electrical Earthing
Earthing can be done in many ways. The various methods employed in earthing (in house
wiring or factory and other connected electrical equipment and machines) are discussed as
follows.
Plate Earthing:
In plate earthing system, a plate made up of either copper with dimensions 60cm x 60cm x
3.18mm (i.e. 2ft x 2ft x 1/8 in) or galvanized iron (GI) of dimensions 60cm x 60cm x 6.35 mm (2ft
x 2ft x ¼ in) is buried vertical in the earth (earth pit) which should not be less than 3m (10ft) from
the ground level.
For proper earthing system, follow the above mentioned steps in the (Earth Plate introduction)
to maintain the moisture condition around the earth electrode or earth plate
Pipe Earthing:
A galvanized steel and a perforated pipe of approved length and diameter is placed vertically in
a wet soil in this kind of system of earthing. It is the most common system of earthing.
The size of pipe to use depends on the magnitude of current and the type of soil. The dimension
of the pipe is usually 40mm (1.5in) in diameter and 2.75m (9ft) in length for ordinary soil or
greater for dry and rocky soil. The moisture of the soil will determine the length of the pipe to be
buried but usually it should be 4.75m (15.5ft).
Rod Earthing
it is the same method as pipe earthing. A copper rod of 12.5mm (1/2 inch) diameter or 16mm
(0.6in) diameter of galvanized steel or hollow section 25mm (1inch) of GI pipe of length above
2.5m (8.2 ft) are buried upright in the earth manually or with the help of a pneumatic hammer.
The length of embedded electrodes in the soil reduces earth resistance to a desired value.
If at all round conductors are used, their cross-section area should not be too small, say less
than 6.0mm2 if it’s a galvanized iron or steel. The length of the conductor buried in the ground
would give a sufficient earth resistance and this length should not be less than 15m.
First of all, dig a 5x5ft (1.5×1.5m) pit about 20-30ft (6-9 meters) in the ground. (Note that, depth
and width depends on the nature and structure of the ground)
Bury an appropriate (usually 2’ x 2’ x 1/8” (600x600x300 mm) copper plate in that pit in vertical
position.
Tight earth lead through nut bolts from two different places on earth plate.
Use two earth leads with each earth plate (in case of two earth plates) and tight them.
To protect the joints from corrosion, put grease around it.
Collect all the wires in a metallic pipe from the earth electrode(s). Make sure the pipe is 1ft
(30cm) above the surface of the ground.
To maintain the moisture condition around the earth plate, put a 1ft (30cm) layer of powdered
charcoal (powdered wood coal) and lime mixture around the earth plate of around the earth
plate.
Use thimble and nut bolts to connect tightly wires to the bed plates of machines. Each machine
should be earthed from two different places. The minimum distance between two earth
electrodes should be 10 ft (3m).
Earth continuity conductor which is connected to the body and metallic parts of all installation
should be tightly connected to earth lead. Make sure to use the continuity by using continuity
test.
At last (but not least), test the overall earthing system through earth tester. If everything is going
about the planning, then fill the pit with soil. The maximum allowable resistance for earthing is
1Ω. If it is more than 1 ohm, then increase the size (not length) of earth lead and earth continuity
conductors. Keep the external ends of the pipes open and put the water time to time to maintain
the moisture condition around the earth electrode which is important for the better earthing
system.
SI specification for Earthing
Various specifications in respect to earthing as recommended by Indian Standards are given
below. Here are few;
An earthing electrode should not be situated (installed) close to the building whose installation
system is being earthed at least more than 1.5m away.
The earth resistance should be low enough to cause the flow of current sufficient to operate the
protective relays or blow fuses. It’s value is not constant as it varies with weather because it
depends on moisture (but should not be less than 1 Ohm).
The earth wire and earth electrode will be the same material.
The earthing electrode should always be placed in a vertical position inside the earth or pit so
that it may be in contact with all the different earth layers.
Related Posts:
I have seen a person killed simply because a live wire got cut from overhead pole and fell to the
ground while the ground was wet. Excessive current is earthed at generating stations and if at
all the earthing is not efficient due to fault, earth fault interrupters will be there to help. Fuse help
only when the power transmitted is above the rating of our appliances, it blocks the current from
reaching our appliances by blowing off and protecting our appliances in the process.
In our electrical appliances, if excessive currents are not earthed, we would experience severe
shock. Earthing takes place in electrical appliances only when there is a problem and it is to
save us from danger. If in an electronic installation, a metallic part of an electrical appliance
comes in direct contact with a live wire that results from maybe failure of installation or
otherwise, the metal will be charged and static charge will accumulate on it.
If you happen to touch the metallic part at that moment you will be zapped. But if the metallic
part of the appliance is earthed, the charge will be transferred to earth instead of accumulating
on the metallic part of the appliance. Current don’t flow through earth wires in electrical
appliances, it does so only when there is problem and only to direct the unwanted current to
earth in order to protect us from severe shock.
In addition, if a live wire touches accidentally (in a faulty system) to the metallic part of a
machine. Now, if a man touches that metallic part of the machine, then the current will flow
through their body to the ground, hence, he will get shocked (electrocuted) which may lead to
serious injuries even to death. That’s why earthing is so important?