DC Genset: For BACK UP (PV or Grid)
DC Genset: For BACK UP (PV or Grid)
DC Genset: For BACK UP (PV or Grid)
■ Standard □Optional
Date: 12/05/2016
1/4
2.0 Generator set specifications
2.1 DC Output nominal voltage -48 Vdc
2.2 Rated DC genset power 18 kW
2.3 Rated output to Load 18 kW
2.4 Controller Type Deep Sea
2.5 DC Output nominal range -44V to -58V
2.6 DC Output regulation (no load to full load) +/-1%
2.7 DC Output ripple 150 mVpp
2.8 DC Output protection Short circuit / Overload
2.9 Generator canopy material Galvanized steel
W L
Date: 12/05/2016
2/4
3.0 Typical Block Diagram
AMF
Control Panel
LCB
Engine DC Gen. To the load
V
Ig
The AMF integrated logic controller, Starts and Stops the Generator Set on Low /High load DC voltage thresholds. If a battery bank is
connected to the DC genset output, there will be NO CONTROL for its charging/discharging currents
3/4
4.2
Control functions
4.2.1 Autostart and stop, manual and auto mode
4.2.2 Engine and alternator monitoring, manual and auto mode
4.2.3 Engine and alternator protection, manual and auto mode
rd
4.5 Monitored Parameters via MODBUS (utilizing 3 party remote management system)
All the readings and alarms as per section 4.6.
4.6.18 DG alarm - Low Oil Pressure 4.6.25 DG alarm - Low DG battery voltage
4.6.19 DG alarm - High Temperature 4.6.26 DG alarm - Engine Over/Under speed
4.6.20 DG alarm - DC output overload 4.6.27 DG alarm - Auto Mode to Manual mode
4.6.21 DG alarm - DG fail to start 4.6.28 DG alarm - Emergency stop button pressed
4.6.22 DG alarm - DG fail to stop 4.6.29 DG alarm - Maintenance service required
500Hrs/1000Hrs/2000Hrs
4.6.23 DG alarm - Low fuel level pre alarm (configurable in controller) 4.6.30 DG alarm - O/P short circuit or reverse polarity
4.6.24 DG Alarm - Fuel End
4/4