Pt100-Temperature-Sensores Type TF

Pt100 Temperature Sensors Type TF101

General TF101 temperature sensors use sistance Thermometer offers the best overall advantages
EN 60751/IEC 60751 platinum in repeatability and stability over a long period. High
resistance temperature detectors
(RTD). For precise temperature
accuracy allows replacement of a sensor without any
need for re-adjust of the connected measuring devices
1
measurement the Platinum Re- or thermostats.

Types / Description

TF101N Platinum resistance temperature T0,9 in the air 10 s, in water <1 s.


-70°C...+500°C sensor on ceramic substrate
intended for installation into any Part number: 019061
housing depending to user’s re-

Ø0,25
quirements. Very small and quick

2
1
sensor, only suitable for further
treatment. Notice: do not cut the
sensor leads. Thermal response 1,5 2,3 10
time refer to manufacturer data:

TF101K Platinum resistance temperature With 2-wire connection and cable-length of 2 m there
-50°C...+170°C sensor on ceramic substrate pro- is a temperature-failure of approx. 0.51 Ω = 1.32 K
tected by a heat-shrinkable sleeve caused by the line resistance.
and with PTFE isolated stranded Cable length: 2000 mm
wire. The TF101K version can be Weight: 10 g
installed in motor or transformer
windings. When build-in into Part numbers: T223154 2-wire
windings do not pressure the T223134 3-wire
sensor element. Precautions
Ø 4,5

should be taken to protect sen- rot


sor and extension leads against rot
push and pull forces. Thermal
response time T0,9 in the air 100 weiß
s, in water 19 s. 2000 ±10 10

TF101U2 Sensors TF101U2 are encapsula- Weights: PVC: 2 m = 50 g, 10 m = 250 g,


-30°C...+105°C ted in a stainless-steel-shell V4A. 30 mm = 15 g
They are suitable for measuring PTFE: 2 m = 20 g
temperatures in fluids, at surfaces
or for inside or outside applicati- Part numbers:
ons. The protection class is IP 66. T223051 3-wire 2m PVC -30...+105 °C
The version with PVC-insulated T223058 3-wire 10 m PVC -30...+105 °C
cable (3 x 0,25 mm2 in one T223052 3-wire 2m PTFE -50...+170 °C
-50°C...+170°C cable) can be easily wired. The T223047 2-wire 30 mm PVC -30... +80 °C
maximum ambient temperature
is 105 °C.
The sensor with cable 30mm
(PVC) can be mounted in ter-
20 2000 ±10 10
minals in switchgear cabinets
Ø 4,5

to measure temperature in en-


-30°C...+80°C closure.
The version with PTFE-insulation rt / RD
rt / RD
(3 x 0,14 mm2 single wires) with- ws / WH
stands peak-temperatures up to
200 °C LIYWYW 3x 0,25 mm²

ZIEHL industrie-elektronik, 74523 Schwäbisch Hall, Germany, +49 791 504-0, info@ziehl.de, www.ziehl.de 2018-01-17 53
Pt 100-Temperature-Sensors Type TF

TF101G3 Platinum resistance temperature sensor on ceramic


-50°C...+170°C substrate built into a M6 brass threaded bush, especially
suitable for being screwed into metal, e.g. for monitoring
mit Gewinde temperature of heat sinks or heating plates.
Please note that there will be a measuring error due
to the design, as the sensor can loose heat via the
connection strand.
Cable length: 2000 mm
Weight: 21 g.
(Dimensions see Dimension illustrations)

Part number: T223143 3-wire

TF101ZG2 Platinum resistance temperature sensor built into steel


-50°C...+170°C tube V4A, 1/2 inch, suitable for installation in pipes.
Thermal response time T0,9 in the air 255 s, in water
45 s.
Suitable for transmission in 2- or 3-wire technique.
Weight 120 g
(Dimensions see Dimension illustrations)

Part number: T223137


110 mm depth of immersion

TF101R
-20...+70°C Sensor for measuring ambient temperatures inside or
outside.
Protection class IP 54. Cabling can be connected in
2- or 3- wire technique.
Housing W x H x D = 65 x 50 x 38 mm
Weight: app. 70 g

Part number: T223060

Technical Data Nominal resistance 100 Ω at 0 °C


Temperature coefficient 3,85 x 10 –3/K (see table)
Class B, DIN 43 760 ∆ϑ = ± (0,3 + 0,005 ϑ) [°C]
Test voltage 2,5 kV AC (not 019061 and T223047)
Extension leads PTFE; silver-plated stranded copper wire 0,14 mm2
or PVC isolated copper wire
Shrink sleeve Kynar
max. temperature at sensors 200 °C (max. 170 h)
with max. 170°C

54 ZIEHL industrie-elektronik, 74523 Schwäbisch Hall, Germany, +49 791 504-0, info@ziehl.de, www.ziehl.de 2018-05-18
Pt100-Temperature-Sensores Type TF

Cabling ZIEHL thermostats of TR series are generally insensitive to interference in the sensor line.
Occasionally, however, undesirable switching is unavoidable, especially when temperature
is near the switching point. For this reason it is highly recommended that cables are not
laid parallel to power current lines over long distances. When appropriate, cables should
be screened or twisted together.

Line-resistance With RTD sensors the resistance of the connecting cable should be considered, otherwise
there is an measuring error. The resistance must be compensated. The resistance of a
1
connecting cable can be calculated as follows:

R [Ω] = 2 x l/(k x A), l = cable length [m],


k = conductivity [S x m/mm2] e.g. Cu = 56,
A = cross sectional area [mm2]

For example copper-wire: I = 50 m, cross sectional area 1 mm2: R = 2 x 50/(56 x 1) = 1,79


Ω, Resulting error = 1,79 Ω/0,385 Ω x K = 4,6 K.

Linecompensation
2-wire technique
rot
red weiß
white With 2-wire connection the line resistance is compensated for by a potentiometer in the
thermostat, by programming (e.g. TR122D, TR600) or via wiring an external resistor. The
advantage of the possibly simpler and more economical running of just two wires is counter-
acted by the disadvantage of the manual compensation required in the case of longer wiring.
Differences in resistance caused by temperature changes cannot be compensated.

3-wire technique
red red
With 3-wire connection, a third wire (sense) connected to the sensor registers the drop in
rot rot weiß
white
voltage in one line. For compensation of line resistance it is assumed that the voltage drop
in the second line is identical (i.e. the same wire and same wire temperature). Compen-
sation is then performed automatically. Possible changes of resistance in the line due to
temperature changes are also compensated for.

4-wire technique
red red weiß white
white weiß
With 4-wire connection, impressed current flows via two wires to the sensor. Via a two
sensor line the drop in voltage is measured directly at the sensor. Possible differences
in the sensor connection wiring can be disregarded. A disadvantage is the higher costs
involved in running 4 wires.

Kombination of 2- and 3-wire technique


When connecting 2-wire-sensors to units with 3-wire input, the line resistance can be
compensated by connecting a compensation resistor (Rk) between ground and sense-
input. Rk must have the same value as the resistance of the line. The sensor then has
RL /2 RL /2 to be connected to the + and the sense- input. Rk must be lower than the permitted
resistance for 1 line of the 3-wire-input.
RK = RL
Units requiring 3-wire configurations can also be operated by 2-wire sensors. The sensor
input is simply shortened. The line resistance need not be compensated.
+
3-wire sensors can be used as 2-wire sensors, simply by omitting one wire.
2-wire sensors can be branched at any desired position in a 3 or 4-wire connection system.
In this case though, the line resistance of the two wires from the branching point to the
sensor is not compensated.

ZIEHL thermostats, series TR are designed for use with 2 or 3-wire connection.

ZIEHL industrie-elektronik, 74523 Schwäbisch Hall, Germany, +49 791 504-0, info@ziehl.de, www.ziehl.de 55
Pt100-Temperature-Sensors Type TF

Pt100 resistance table Basic values in Ω for measuring resistors Pt 100 according to DIN/ IEC 751

°C Ω °C Ω °C Ω °C Ω °C Ω °C Ω

-200 18,49 0 100,00 200 175,84 400 247,04 600 313,59 800 375,51
-190 22,80 10 103,90 210 179,51 410 250,48 610 316,80 810 378,48
-180 27,08 20 107,79 220 183,17 420 253,90 620 319,99 820 381,45
-170 31,32 30 111,67 230 186,82 430 257,32 630 323,18 830 384,40
-160 35,53 40 115,54 240 190,45 440 260,72 640 326,35 840 387,34
-150 39,71 50 119,40 250 194,07 450 264,11 650 329,51 850 390,26
-140 43,87 60 123,24 260 197,69 460 267,49 660 332,66
-130 48,00 70 127,07 270 201,29 470 270,86 670 335,79
-120 52,11 80 130,89 280 204,88 480 274,22 680 338,92
-110 56,19 90 134,70 290 208,45 490 277,56 690 342,03
-100 60,25 100 138,50 300 212,02 500 280,90 700 345,13
- 90 64,30 110 142,29 310 215,57 510 284,22 710 348,22
- 80 68,33 120 146,06 320 219,12 520 287,53 720 351,30
- 70 72,33 130 149,82 330 222,65 530 290,83 730 354,37
- 60 76,33 140 153,58 340 226,17 540 294,11 740 357,42
- 50 80,31 150 157,31 350 229,67 550 297,39 750 360,47
- 40 84,27 160 161,04 360 233,17 560 300,65 760 363,50
- 30 88,22 170 164,76 370 236,65 570 303,91 770 366,52
- 20 92,16 180 168,46 380 240,13 580 307,15 780 369,53
- 10 96,09 190 172,16 390 243,59 590 310,38 790 372,52

Pt1000 Temperature Sensor


The Pt1000 sensor is the "big brother" of the Pt100 sensor. Its nominal resistance at 0°C
is 1000 Ω. Resistance values of the whole series are higher by a factor of 10. The sensor
is used in the same way as the Pt100 sensor. Its dimensions are slightly larger (4 x 5 un-
insulated). Thermostats and sensors for Pt1000 on request.

Pt1000 resistance table values see Pt100, multiplicated by the factor of 10.

56 ZIEHL industrie-elektronik, 74523 Schwäbisch Hall, Germany, +49 791 504-0, info@ziehl.de, www.ziehl.de