EGT346
EGT346
EGT346
036/1
still 18 s 330 s
moving (3 m/s) 9s 60 s
in water, with prot. tube 1) Dead time Time const.
still 7s 28 s
moving (0,4 m/s) 6s 27 s
Accessories
0364439 . . . Protective tube LW 7, brass; see chapter 39
0226811 . . . Protective tube LW 7, inox; see chapter 39
0368840 000* Holder for fitting stem on wall
0368839 000* Holder for fitting stem in air duct
0313220 001 Heat-conducting paste, in a tube of 20 g
0313282 001 Clamp D = 15 mm / 7 mm, for fitting sensor into protective tube; separate delivery
0313346 001* Module 0-10 V for Ni1000; 24 V~; MV 505513; A08091, IP 00 (IP 42 when fitted in
housing) 4 temp. ranges: –50...0 °C; –50...50 °C; 0...50 °C; 0...100 °C
*) Dimension drawing or wiring diagram are available under the same number
Operation
The resistance value of the Ni measuring resistor changes with respect to temperature. The tempera-
ture coefficient is always positive, i.e. the resistance value increases as the temperature rises. See
table of values (DIN 43760) and curve. The elements are exchangeable (within the limits of the pre-
scribed tolerances)
In air ducts:
The detector is fitted directly onto the insula-
tion or onto the wall of the air duct.
Using the stem holder (accessory
no. 0368839) and the clamping ring (acces-
sory no. 0313282) the insertion depth can
be adjusted.
A01632
Accessories
0...10V 313346
24V~ xi EGT . . .
2 1 3
ON -50...0°C
-50..50°C
12
0...50°C
0...100°C
Ni1000
A08091a
368839
16
Ø55
38 M08527a
5,8
15,3
120° M00827a
368840
Ø 5,8
15,5
25,5
35
15,3
20
M00829a
Printed in Switzerland
Right of amendment reserved
N.B.: A comma between cardinal
numbers denotes a decimal point
© Fr. Sauter AG, CH-4016 Basle
Sauter Components 7136036003 03