Product Data Sheet: ZP7 Series Addressable 2-Way Monitored Output Unit
Product Data Sheet: ZP7 Series Addressable 2-Way Monitored Output Unit
Product Data Sheet: ZP7 Series Addressable 2-Way Monitored Output Unit
ZP752-2
ZP7 Series Addressable 2-way Monitored Output Unit
General
Fully monitored for open and short circuit faults Standard Features
Any number of ZP752-2 units (up to a max of 127) can be E Two monitored sounder circuits
connected to the ZP loop. In systems complying with the E Support for 3s response from manual call points
recommendations of BS5839-1, where sounder response to the E Addressable - connects to ZP loop
operation of a manual call point must be within 3 seconds, up to E Programmable for continuous or pulsed output
16 ZP752-2 output units, assigned to the first 16 addresses on
each loop can be operated within the time period.
Wiring is monitored for open and short circuit faults by means of
end of line resistors. Faults are automatically reported to the
control panel, together with the address of the ZP752-2
interface. An amber LED indicator on the front of the moulding
is illuminated to indicate the fault condition.
Designed for first and second fix installation, the unit comprises
an open back box containing all wiring terminals, together with a
front plate enclosure of high impact plastic, housing all
electronics, printed circuit boards and selection switches. The
two parts simply plug together prior to system completion.
All loop devices incorporate switch settings enabling them to be
assigned a unique address which is polled by the panel every
two seconds.
ZP752-2
ZP7 Series Addressable 2-way Monitored Output Unit
As a company of innovation, UTC Fire & Security reserves the right to change product
specifications without notice. For the latest product specifications, visit UTC Fire & Security
online or contact your sales representative.
ZP752-2-2018-07-15 06:41:44 Released :06-MAR-15