Multilin™

L90

Transmission Line Protection


LINE CURRENT DIFFERENTIAL SYSTEM

Phase segregated line current differential


and distance protection

KEY BENEFITS
• Phase segregated differential protection ensures secure • Advanced fault and disturbance recording, including internal
high-speed single pole tripping relay operating signals thus eliminating the need for external
• Complete IEC 61850 Process Bus solution providing resource recording devices
optimization and minimizing total P&C life cycle costs • Phasor Measurement Unit - Synchronized phasor information
• Reliable and secure protection on lines equipped with series according to IEEEC37.118 standard
compensation • Robust network security enabling Critical Infrastructure
• Increased sensitivity through dynamic charging current Protection through user command logging, and dual
compensation and communication channel asymmetry permission access control
compensation • Ambient temperature monitoring with alarming when outside
temperature exceeds upper thresholds
APPLICATIONS
• Overhead lines including series compensated lines and • Wide area system monitoring and control and using
underground cables of different voltage levels integrated protection and synchrophasor measurement
• Circuits with tapped transformer feeders • Single and dual-breaker circuits requiring single pole/three-
• Suitable for three terminal line configurations, with channel pole autoreclosing and independent synchrocheck supervision
redundancy and direct transfer tripping (DTT) • Distributed busbar protection

FEATURES
Protection and Control IEC 61850 Process Bus Interface
• Phase segregated line current differential with adaptive • Robust communications with up to 8 HardFiber Bricks
restraint & Ground differential, stub bus protection • Seamless integration with existing L90 functions
• Thermal protection, under /over frequency, broken conductor • Redundant architecture for dependability and security
• Phase Distance (three Zones) with independent compensation
settings for in-zone power transformers Monitoring and Metering
• Ground distance (three zones) with independent self and • Real time monitoring of remote, local and differential per
mutual zero sequence compensation, reverse power phase currents
• Reverse power, Out of Step tripping and power swing blocking • Oscillography - 64 samples/cycle, up to 64 records
• Thermal overload, phase, neutral and negative sequence • Event Recorder - 1024 time tagged events, with 0.5ms scan
directional overcurrent; and broken conductor of digital inputs
• Over, Under and rate of change of Frecuency, Synchronism • Data Logger - Up to 16 channels with user selectable
check for dual breaker applications sampling rate
• P & M Class synchrophasors of voltage, current and sequence
Communications components – 1 to 120 frames/sec
• Networking interfaces – 100Mbit Fiber Optic Ethernet, RS485, • Multi-ended fault location consistently providing 2%
RS232, RS422, G.703, C37.94 accuracy
• Multiple Protocols - IEC61850, DNP 3.0 Level 2, Modbus RTU,
Modbus TCP/IP, IEC60870-5-104, Ethernet Global Data (EGD) EnerVista™ Software
• Direct I/O – secure, high-speed exchange of data between • Graphical Logic Designer and Logic Monitor to simplify
L90s for Direct Transfer Trip applications designing and testing procedures
• Embedded Managed Ethernet Switch with 4 - 100 Mbit Fiber • Document and software archiving toolset to ensure
optic ports and 2 copper ports reference material and device utilities are up-to-date

g
• EnerVista™ Integrator providing easy integration of data in
the L90 into new or existing monitoring and control systems

Digital Energy
201
L90 Line Differential System

Protection and Control L90 - Protection, Metering, Monitoring and Control


The L90 is a high-end cost effective
line current differential protection relay
intended for transmission lines and cables
Transmission Line Protection

of different voltages levels providing


reliable and secure operation even under
the worst case power system conditions.
The L90 provides high-speed phase-
segregated fault clearance suitable for
single and three-pole tripping applications.
Part of the Universal Relay family, the L90
comes with a variety of versatile features
truly integrating protection, monitoring,
metering, communication and control in
one easy-to-use device. The Universal Relay
family offers a high degree of modularity
in its design and functionality providing
superior performance in protection and
The L90 is the single point for protection, control, metering, and monitoring in one integrated device
control meeting the toughest requirements that can easily be connected directly into DCS or SCADA monitoring and control systems like Viewpoint
of the marketplace. Monitoring as shown.

Segregated Current Differential and can detect faults within a half cycle synchronization. Clocks are phase
Protection plus channel delay. synchronized to each other and
The L90 is a phase segregated current The L90 innovative dual slope adaptive frequency synchronized to the power
differential protection relay, which uses restraint characteristic, based on system frequency. Each relay compares
superior and patented algorithms to estimates of measurement errors, allow its clock to the phase of the other clocks
address the challenges of bandwidth , the relay to be secure on severe external and makes appropriate adjustments. This
security, dependability and sensitivity in faults while maintaining sensitivity for allows for greater transient ride-through
current differential relaying. internal faults. The estimate of errors in for power system and communications
Bandwidth requirements are effectively the input currents permits more sensitive disturbances.
addressed by means of a patented new settings than those used in the traditional
data consolidation technique called Enhanced additional security is provided
percent differential schemes.
“phaselets”. This permits application within The L90 approach to clock synchronization by a sensitive current disturbance
a communications bandwidth of 64 Kbps, relies upon precise distributed detector, which can be used to supervise
the current differential element.

Functional Block Diagram ANSI Device Numbers & Functions


Device
Number Function
21G Ground
ANSI DEVICE NUMBERSDistanceAND FUNCTIONS
21P Phase Distance
DEVICE
52 FUNCTION
25NUMBER Synchronism Check
27P
21G Phase Undervoltage
Ground Distance
27X
21P Auxiliary
Phase Undervoltage
Distance
79 3225 Sensitive Reverse Power
Synchrocheck
Monitoring CLOSE TRIP 81U/O 4927P Phase
Thermal Undervoltage
Overload
50DD 50P 50_2 51P 51_2 50BF 87L 21P 67P 78 50N 51N 67N/G 21G 27X
50BF Auxiliary
Breaker Undervoltage
Failure
68
50BF
50DD Breaker Failure
Current Disturbance Detector
50DD Adaptive Fault Detector
32 49 50G Ground
(senstive Instantaneous
current Overcurrent
disturbance detector)
FlexElement
TM
Metering Transducer 50N
50G NeutralInstantaneous
Ground InstantaneousOvercurrent
Overcurrent
Data From/To Remote End
Inputs
59P 50N
50P Neutral InstantaneousOvercurrent
Phase Instantaneous Overcurrent
(via Dedicated Communications)
50P
50_2 Phase
NegativeInstantaneous Overcurrent Overcurrent
Sequence Instantaneous
27P 50_2 Negative Sequence Instantaneous Overcurrent
51G Ground Time Overcurrent
50G 51G 51G Ground Time Overcurrent
51N
51N NeutralTime
Neutral TimeOvercurrent
Overcurrent
59N
59X 51P
51P PhaseTime
Phase TimeOvercurrent
Overcurrent
27X
51_2 NegativeSequence
51_2 Negative SequenceTime TimeOvercurrent
Overcurrent
25 5252 ACACCircuit
CircuitBreaker
Breaker
L90 Line Differential System 59N
59N Neutral
NeutralOvervoltage
Overvoltage
831706AS.CDR
59P
59P Phase
PhaseOvervoltage
Overvoltage
59X Auxiliary Overvoltage
59X
67N Auxiliary
Neutral Overvoltage
Directional Overcurrent
67_2
67P Negative
Phase Sequence
Directional Directional Overcurrent
Overcurrent
67N Neutral Directional
67_2 Negative OvercurrentOvercurrent
Sequence Directional
68
67P Power Swing Blocking
Phase Directional Overcurrent
6878 Out-of-Step
Power Swing Tripping
Blocking
78
79 Automatic Recloser
Out-of-step Tripping
87L Segregated Line Current Differential
79 Automatic Recloser
81U/O Under /Over Frequency, df/dt
87L Segregated Line Current Differential

202 www.GEDigitalEnergy.com
L90 Line Differential System

Ground Differential “87G” link, acting either as master collecting functions in L90 come with three zones
The Ground Differential function “87G” data, making calculations and making of phase and ground distance (mho or
protects against low-current single line- all relevant trip and restraint decisions, quad). The phase distance elements
to-ground faults. It has a single slope or as slave only transmitting current come with built-in in-zone transformer

Transmission Line Protection


characteristic and uses the vectorial sum data to the one acting as master. For two compensation. The L90 also provides
of all in-zone phase currents to calculate terminal applications, use the redundant a load encroachment element , which
the Neutral differential current. with the communications capability of the L90 for supervises the distance elements under
maximum value of phase current being optimal reliability of the current differential heavy line loading conditions.
used as restraint. This function together line protection. For this scheme, data
is continuously transmitted over both Overvoltage and undervoltage
with the phase differential delivers
channels, so if a failure occurs, the L90 protection
enhanced sensibility and selectivity to the
protection scheme. will continue to provide current differential Long lines under lightly loaded conditions
protection. or no-load may experience voltages
Charging Current Compensation For three terminal applications, advanced exceeding rated per unit voltage level
inter-relay communication features of the line. Use the phase overvoltage
For long transmission lines and
eliminate the need for redundant element of the L90 to initiate a local trip as
underground cables, the charging current
communication channels due to the ability well as a remote trip using direct transfer
may be large and result in excessively high
of the L90 to automatically switch between trip.
pickup settings. The L90 can dynamically
master and slave mode, maintaining a
compensate the charging current thus
dependable system even with a failure of Overcurrent Functions
increasing its sensitivity to the fault current
one of the communication channels. TThe L90 provides thermal overload, time
on long transmission lines.
and instantaneous overcurrent elements
Enhanced Monitoring Features Distance for phase, neutral, ground, negative
Separate high-speed phase and ground sequence, phase and neutral directional.
The L90 uses an advanced error detection
distance elements are provided for optional Any of them can run in parallel with
and supervising functions to secure the
supervision with tapped transformers and primary differential protection or can be
L90 against misoperation due to erroneous
as a back-up during channel failures or programmed to run when the differential
data. High bit errors are addressed by
unavailability. The back-up distance the element is not available.
means of computing a 32 bit CRC check
sums effectively addressing the concerns
of multiple bit errors due to high channel Typical Applications
noise.
On multiplexed channels, channel
asymmetry may be expected due to path
switching spurious differential currents,
which can endanger the security of the
differential system. By using GPS time
synchronization, up to 10ms of channel
asymmetry can be compensated for. Extra
security has been implemented in the L90
to ensure proper operation on the event of
IRIG-B signal failure.
Integrated channel monitoring provides
real-time diagnostic data on the health
of the L90. Communications channel
deterioration or failure will activate an
alarm, and can be used to enable backup
protection. Channel propagation delay
is monitored and adjusted according to
variations in communication paths.

Communication Topologies
Relays can communicate through direct
fiber, RS422, G.703, IEEE C37.94 interfaces
at 64Kbps, with extensive channel
monitoring and diagnostics are included.
In a current differential scheme, the L90s
exchange data via the communication Typical two and three terminal application of L90. L90 supports a variety of media cards for signalling
between L90’s including direct multimode or single mode fibre, RS422, G.703 and IEEE C37.94.

www.GEDigitalEnergy.com 203
L90 Line Differential System

FlexLogicTM Designer bi-directional IEC 61850 fiber optic


communications. The HardFiber System
is designed to integrate seamlessly with
the existing Universal Relay applications,
Transmission Line Protection

including protection functions, FlexLogic,


metering and communications.
HardFiber System benefits:

• Communicates using open standard


IEC 61850 messaging
• Drastically reduces P&C design,
installation and testing labor by
eliminating individual copper
terminations
• Integrates with existing C70’s by
replacing traditional CT/VT inputs with
IEC 61850 Process Bus module
Flexlogic™ allows for customizing the L90 to operate and control the breakers and other auxiliary • Does not introduce new Cyber Security
devices needed to fit most line protection schemes and applications.
concerns

Single-Pole Tripping Breaker Failure


The L90 relay uses a state-of- the-art dual The L90 is able to provide fully independent Advanced Automation
phase selection algorithm that provides breaker failure protection for the breakers
The L90 incorporates advanced automation
fast and accurate fault type identification associated to the line when connected to
features including powerful FlexLogic™
even under weak-infeed conditions. a substation with a breaker-and-a-half or
programmable logic, communication, and
ring bus arrangement. The L90 provides
Direct transfer trip (DTT) SCADA capabilities that far surpass what
the required elements to perform two
is found in the average line relay. The L90
Use the direct transfer trip feature of L90 independent breaker failure functions.
integrates seamlessly with other UR relays
to trip remote breaker. Both single pole
for complete system protection.
and three pole direct transfer trips are Multiple Breaker Configurations
supported. Up to eight signals can be The L90 supports multi-breaker busbar FlexLogic™
sent over pilot communications channels configurations such as breaker-and-a-half
FlexLogic™ is the powerful UR-platform
selectable through user configurable or ring bus arrangements, providing dual
programming logic engine that provides
logic. breaker auto reclose, dual synch-check
the ability to create customized protection
elements, and dual independent Breaker
Autoreclosing and control schemes thereby minimizing
Failure elements. The design provides
the need, and associated costs, of auxiliary
The L90 provides multi-shot auto reclosing secure operation during external faults
components and wiring.
for single pole or three pole auto relcose with possible CT saturation
Using FlexLogic, the L90 can provide
on all types of faults with independently
required tripping and custom scheme logic
settable dead time for each shot. Auto- Special Applications - Distributed
for line breaker control and interlocking
reclose can be dynamically blocked by Busbar
and dynamic setting group changes.
user programmable logic. Four different Use the L90’s capability of supporting
auto-relcose modes are available enabling up to 4 directly connected CTs for
Scalable Hardware
the users to select the reclosing mode to applications where the use of conventional
The L90 is available with a multitude
suit specific applications. bus differential relaying is not practical
of I/O configurations to suit the most
or economically feasible. The L90 can
Synchronism Check demanding application needs. The
be used to protect both line and buses
expandable modular design allows for
The L90 monitors voltage difference, by measuring currents from the feeder
easy configuration and future upgrades.
phase angle difference and slip frequency CTs as shown. The L90 provides primary
to ensure proper breaker closure as per protection for both the buses and the
• Flexible, modular I/O covering a broad
user requirements. The L90 provides circuit connecting them.
range of input signals and tripping
additional enhancements in synchronizing
schemes
by allowing synchrocheck verification
between local and remote line terminal
IEC 61850 Process Bus • Mechanically latching outputs
voltages. The IEC 61850 Process Bus module can be used to develop secure
is designed to interface with the interlocking applications and replace
Multilin HardFiber™ System, allowing electromechanical lockout relays

204 www.GEDigitalEnergy.com
L90 Line Differential System

Monitoring and Metering Advanced Device Health • IEC61850


Diagnostics • DNP3.0
The L90 includes high accuracy metering
and recording for all AC signals. Voltage, The L90 performs comprehensive device • IEC 60870-5-104
current, and power metering are built into health diagnostic tests during startup
• Modbus RTU, Modbus TCP/IP

Transmission Line Protection


the relay as a standard feature. Current and continuously at runtime to test
and voltage parameters are available as its own major functions and critical
Interoperability with Embedded IEC
total RMS magnitude, and as fundamental hardware. These diagnostic tests monitor
61850
frequency magnitude and angle. for conditions that could impact security
and availability of protection, and present The L90 with integrated IEC 61850 can be
device status via SCADA communications used to lower costs associated with line
Fault and Disturbance Recording
and front panel display. Providing protection, control and automation. GE
The advanced disturbance and event
continuous monitoring and early detection Energy’s leadership in IEC 61850 comes
recording features within the L90 can
of possible issues helps improve system from thousands of installed devices and
significantly reduce the time needed for
uptime. follows on Multilin’s extensive development
postmortem analysis of power system
• Comprehensive device health experience with UCA 2.0.
events and creation of regulatory reports.
Recording functions include: diagnostic performed during startup
• Replace expensive copper wiring
• Monitors the CT/VT input circuitry to
between devices with direct transfer of
• Sequence of Event (SOE) validate the integrity of all signals
data using GOOSE messaging
- 1024 time stamped events
• Configure systems based on IEC 61850
• Oscillography,
Communications and also monitor and troubleshoot
- 64 digital & up to 40 Analog channels them in real-time with EnerVista™
The L90 provides for secure remote data
• Data Logger, disturbance recording – Viewpoint Engineer
and engineering access, making it easy
16 channels up to 1 sample / cycle / and flexible to use and integrate into • Integrate Multilin IEDs and generic IEC
channel new and existing infrastructures. Fiber 61850-compliant devices seamlessly in
• Fault Reports optic Ethernet provides high-bandwidth EnerVista™ Viewpoint Monitoring

- Powerful summary report of pre-fault communications allowing for low-latency


controls and high-speed file transfers of Multi-Language
and fault values
relay fault and event record information. The L90 supports English, French, Russian,
• Multi-ended fault location
The available redundant Ethernet option Chinese and Turkish Languages on the
- calculating fault location on two or and the embedded managed Ethernet front panel, EnerVista™ setup software,
three terminal lines with 2% accuracy switch provide the means of creating fault and product manual. Easily switch between
tolerant communication architectures in English and an additional language on
The very high sampling rate and large an easy, cost-effective manner. the local displays without uploading new
amount of storage space available for The L90 supports the most popular industry firmware.
data recording in the L90 can eliminate standard protocols enabling easy, direct
the need for installing costly standalone integration into monitoring and SCADA
recording equipment. systems.

CT1 CB1 CB2 CT2


L90-1
VT1 VT2
1PH
CT1 CT2 CT3 CT4 1PH

CB1 CB2 CB3 CB4


BUS1
Communication channel

L90

BUS2
CB5 CB6 CB7

CT5 CT6 CT7 VT3

L90-2
PROTECTED
LINE
831783A1.CDR

Example of Distributed Bus Differential Protection Application. L90 Breaker-and-a-Half Application example.

www.GEDigitalEnergy.com 205
L90 Line Differential System

EnerVistaTM Software • Guideform Specifications Viewpoint Maintenance


• Wiring Diagrams Viewpoint Maintenance provides tools that
The EnerVista™ Suite is an industry-
• FAQ’s will create reports on the operating status
leading set of software programs that
of the relay, simplify the steps to download
simplifies every aspect of using the L90 • Service Bulletins
fault and event data, and reduce the work
relay. The EnerVista™ suite provides all the
Transmission Line Protection

required for cyber-security compliance


tools to monitor the status of the protected Viewpoint Monitoring
audits. Tools available in Viewpoint
asset, maintain the relay, and integrate
Viewpoint Monitoring is a simple-to-use Maintenance include:
information measured by the L90 into
and full-featured monitoring and data
DCS or SCADA monitoring systems.
recording software package for small • Settings Security Audit Report
Convenient COMTRADE and Sequence
systems. Viewpoint Monitoring provides a
of Events viewers are an integral part • Device Health Report
complete HMI package with the following
of the UR Setup software included with • Single Click Fault Data Retrieval
functionality:
every UR relay, to carry out postmortem
event analysis to ensure proper protection EnerVista™ Integrator
• Plug-&-Play Device Monitoring
system operation.
EnerVista™ Integrator is a toolkit that
• System Single-Line Monitoring & Control
allows seamless integration of Multilin
EnerVista™ Launchpad • Annunciator Alarm Screens
devices into new or existing automation
EnerVista™ Launchpad is a powerful • Trending Reports systems. Included in EnerVista™ Integrator
software package that provides users with is:
• Automatic Event Retrieval
all of the setup and support tools needed
for configuring and maintaining Multilin • Automatic Waveform Retrieval
• OPC/DDE Server
products. The setup software within
Launchpad allows configuring devices in Viewpoint Engineer • Multilin Drivers
real-time by communicating using serial, Viewpoint Engineer is a set of powerful tools • Automatic Event Retrieval
Ethernet , or modem connections, or that will allow the configuration and testing • Automatic Waveform Retrieval
offline by creating setting files to be sent of UR relays at a system level in an easy-to-
to devices at a later time. use graphical drag-and-drop environment.
Included in Launchpad is a document Viewpoint Engineer provides the following User Interface
archiving and management system configuration and commissioning utilities:
The L90 front panel provides extensive
that ensures critical documentation is
local HMI capabilities. The local display
up-to-date and available when needed. • Graphical Logic Designer is used for monitoring, status messaging,
Documents made available include:
• Graphical System Designer fault diagnosis, and device configuration.
User configurable messages that combine
• Manuals & Brochures • Graphical Logic Monitor
text with live data, can be displayed when
• Application Notes • Graphical System Monitor user-defined conditions are met.

Power System Troubleshooting

Graphically view zone settings for


ground phase distance elements for
Record the operation of the internal L90 the selected zones and the power swing
elements and external connected devices detection element.
with 1ms time-stamped accuracy to identify
the Sequence of Operation of station devices Analyze line faults using both analog and digital power system quantities
during line faults and disturbances. that are measured and recorded up to a rate of 64 samples per cycle.

206 www.GEDigitalEnergy.com
L90 Line Differential System

Typical Wiring

A B C

52

Transmission Line Protection


N

OPTIONAL

F1a

F1b

F2a

F2b

F3a

F3b

F4a

F4b

F5a

F6a

F7a

F8a
F1c

F2c

F3c

F4c

F5c

F6c

F7c

F8c
VX
VB

VC
VA

VX
IG5

IG1

VB

VC
IG

VA
IA5

IA1

IB

IC
IA

IC5

IC1
IB5

IB1
8L

H5a 6G I H1a TC 1
H5c H1 H1b
V
H6a H1c
H6c I H2a
H5b H2 H2b
V
H2c
H7a
I H3a
H7c
H3 H3b TC 2
H8a V
H3c
H8c I H4a
H7b
H4 H4b
V
H8b SURGE H4c
U7a 6H I U1a
U7c U1 U1b
V
U8a U1c
U8c I U2a
U7b U2 U2b
V
U2c
U8b SURGE
I U3a
U3 U3b
V
U3c
I U4a
U4 U4b
V
U4c
Multilin I U5a
U5 U5b
V
U5c
L90 U6
I U6a
U6b
V
U6c
N1a
6K

N1 N1b
L1a
6D

N1c
L1c
N2a
L2a N2 N2b
L2c
N2c
L1b
N3a
L3a N3 N3b
L3c N3c
L4a N4a
L4c UR COMPUTER
N4 N4b
L3b 1 1 8
N4c
TXD 2 2 3 RXD
L5a N5a
N5 RXD 3 3 2 TXD
L5c N5b
N5c 4 4 20
L6a
SGND 5 5 7 SGND
L6c N6a
N6 N6b 6 6 6
L5b
N6c 7 7 4
L7a 8 8 5
N7a
L7c 9 9 22
N7 N7b
L8a
L8c N7c
L7b N8a
N8 CONNECTOR CONNECTOR
L8b N8b
SURGE
N8c
FIBER
INTER-RELAY

TO Tx1 Rx1
COMMS.
W7A

REMOTE S1a
6C

L90 FIBER RS-232 S1 S1b


Tx2 Rx2
DB-9 S1c
S2a
B1b (front) S2 PERSONAL
CRITICAL S2b
1

B1a FAILURE
COMPUTER
S2c
B2b
S3a
B3a S3 S3b
DC OUTPUT
B3b S3c
B5b HI S4a
CONTROL
B6b LO POWER S4 S4b
B6a S4c
B8a SURGE S5a
B8b FILTER S5 S5b
S5c
S6a
S6 S6b
S6c
* Optic
Fibre Tx1 10BaseFL
NORMAL S7a
Rx1 S7 S7b
Tx2 10BaseFL COM S7c
ALTERNATE
Rx2 1
S8a
Shielded S8 S8b
10BaseT
Remote S8c
Device D1a
RS485
D2a
D3a com
D4b
D4a IRIG-B
Input
Co-axial BNC

IRIG-B
Co-axial BNC Output

minimum

X W V U T S R P N M L K J H G F D B
7 6 6 6 6 6 8 9 1
Inputs/ Inputs/ Inputs/ Inputs/
PROVIDED
COM outputs outputs outputs outputs Inputs/ CT/VT CPU Power
* * * * outputs supply L90-H00-HCL-F8F-H6G-L6D-N6K-S6C-U6H-W7A

www.GEDigitalEnergy.com 207
L90 Line Differential System

Ordering
L90 - * 00 - H * * - F ** - H ** - L ** - N ** - S ** - U ** - W/X ** For Horizontal Mount
Base Unit L90 Base Unit
CPU E RS485 + RS485 (IEC61850 option not available)
G RS485 + Multi-mode ST 10BaseF
H RS485 + Mutli-mode ST Redundant 10BaseF
Transmission Line Protection

J RS485 + Multi-mode ST 100BaseFX


K RS485 + Multi-mode ST Redundant 100BaseFX
N RS485 + 10/100 BaseT
S RS485 + 6 port, 100 Mbps, Managed Ethernet Switch
Software 00 No Software Options
02 Breaker and Half software
03 IEC61850
05 Breaker and Half + IEC61850
06 Phasor Measurement Unit (PMU)
07 IEC61850 + Phasor Measurement Unit (PMU)
08 Breaker & Half + Phasor Measurement Unit (PMU)
09 Breaker & Half + IEC61850 + Phasor Measurement Unit (PMU)
Mount / Coating H Horizontal (19" rack) - Standard
A Horizontal (19" rack) - Harsh Chemical Environment Option
V Vertical (3/4 size) - Standard
B Vertical (3/4 size) - Harsh Chemical Environment Option
User Interface K Enhanced English Front Panel
L Enhanced English Front Panel with User-Programmable Pushbuttons
M Enhanced French Front Panel
N Enhanced French Front Panel with User-Programmable Pushbuttons
Q Enhanced Russian Front Panel
T Enhanced Russian Front Panel with User-Programmable Pushbuttons
U Enhanced Chinese Front Panel
V Enhanced Chinese Front Panel with User-Programmable Pushbuttons
F Vertical Front Panel with English display
W Enhanced Turkish Front Panel
Y Enhanced Turkish Front Panel with User-Programmable Pushbuttons
Power Supply H 125 / 250 V AC/DC
H RH 125/250 V AC/DC with redundant 125/250 V AC/DC
L 24 - 48 V (DC only)
CT/VT DSP 8L 8L Standard 4CT/4VT w/ enhanced diagnostics
8N 8N Standard 8CT w/ enhanced diagnostics
IEC 61850 Process Bus 81 8 Port IEC 61850 Process Bus Module
Digital I/O XX XX XX XX XX No Module
4A 4A 4A 4A 4A 4 Solid State (No Monitoring) MOSFET Outputs
4C 4C 4C 4C 4C 4 Solid State (Current w/opt Voltage) MOSFET Outputs
4D 4D 4D 4D 4D 16 Digital Inputs with Auto-Burnish
4L 4L 4L 4L 4L 14 Form-A (No Monitoring) Latchable Outputs
67 67 67 67 67 8 Form-A (No Monitoring) Outputs
6C 6C 6C 6C 6C 8 Form-C Outputs
6D 6D 6D 6D 6D 16 Digital Inputs
6E 6E 6E 6E 6E 4 Form-C Outputs, 8 Digital Inputs
6F 6F 6F 6F 6F 8 Fast Form-C Outputs
6K 6K 6K 6K 6K 4 Form-C & 4 Fast Form-C Outputs
6L 6L 6L 6L 6L 2 Form-A (Current w/ opt Voltage) & 2 Form-C Outputs, 8 Digital Inputs
6M 6M 6M 6M 6M 2 Form-A (Current w/ opt Voltage) & 4 Form-C Outputs, 4 Digital Inputs
6N 6N 6N 6N 6N 4 Form-A (Current w/ opt Voltage) Outputs, 8 Digital Inputs
6P 6P 6P 6P 6P 6 Form-A (Current w/ opt Voltage) Outputs, 4 Digital Inputs
6R 6R 6R 6R 6R 2 Form-A (No Monitoring) & 2 Form-C Outputs, 8 Digital Inputs
6S 6S 6S 6S 6S 2 Form-A (No Monitoring) & 4 Form-C Outputs, 4 Digital Inputs
6T 6T 6T 6T 6T 4 Form-A (No Monitoring) Outputs, 8 Digital Inputs
6U 6U 6U 6U 6U 6 Form-A (No Monitoring) Outputs, 4 Digital Inputs
6V 6V 6V 6V 6V 2 Form-A (Cur w/ opt Volt) 1 Form-C Output, 2 Latching Outputs, 8 Digital Inputs
Transducer I/O 5A 5A 5A 5A 5A 4 dcmA Inputs, 4 dcmA Outputs
5F 5F 5F 5F 5F 8 dcmA Inputs
Inter-Relay Communications 7A 820 nm, multi-mode, LED, 1 Channel
7B 1300 nm, multi-mode, LED, 1 Channel
7C 1300 nm, single-mode, ELED, 1 Channel
7H 820 nm, multi-mode, LED, 2 Channels
7I 1300 nm, multi-mode, LED, 2 Channels
7J 1300 nm, single-mode, ELED, 2 Channels
7S G.703, 2 Channels
7W RS422, 2 Channels
7V RS422, 2 Channels, Dual Clock
73 1550 nm, single-mode, LASER, 2 Channel
76 IEEE C37.94, 820 nm, multimode, LED, 1 Channel
77 IEEE C37.94, 820 nm, multimode, LED, 2 Channel
2B C37.94SM, 1300nm Singlemode, ELED, 2 Channel Single mode
2S 6 port, 100 Mbps, Managed Ethernet Switch, HI (125/250V AC/DC)
2T 6 port, 100 Mbps, Managed Ethernet Switch, LO (24-48 Vdc)

Ordering Notes:
1 - For vertical mounting order codes, please visit our online store
2 - To view the latest options available for the L90, or to order the UR Classic Front Panel, please visit our online store for more details.

Accessories for the L90 Visit www.GEMultilin.com/L90 to:


  •  UR Applications I Learning CD TRCD-URA1-C-S-1   •  View Guideform specifications
  •  Multilink Ethernet Switch ML2400-F-HI-HI-A2-A2-A6-G1   •  Download the instruction manual
  •  Viewpoint Engineer VPE-1   •  Review applications notes and support documents
  •  Viewpoint Maintenance VPM-1   •  Buy a L90 online
  •  Viewpoint Monitoring IEC61850 VP-1-61850   •  View the UR Family brochure