6 Hardware

No. ID Module description Remark


GOOSE and SV from merging unit by IEC61850-9-2 (NET-DSP
8 NR1136 option
module)
9 Human machine interface module (HMI module) standard

 MON module provides functions like communication with SAS, event record, setting
management etc.

 AI module converts AC current and voltage from current transformers and voltage
transformers respectively to small voltage signal.

 DSP module performs filtering, sampling, protection calculation and fault detector calculation.

 CH module performs information exchange with the remote device through a dedicated
optical fibre channel, multiplex optical fibre channel or PLC channel.

 BI module provides binary inputs via opto-couplers with rating voltage among
24V/110V/125V/220V/250V (configurable).

 BO module provides output contacts for tripping, and signal output contact for annunciation
signal, remote signal, fault and disturbance signal, operation abnormal signal etc.

 PWR module converts DC 250/220/125/110V into various DC voltage levels for modules of
the device.

 HMI module is comprised of LCD, keypad, LED indicators and multiplex RJ45 ports for user
as human-machine interface.

 NET-DSP module receives and sends GOOSE messages, sampled values (SV) from
merging unit by IEC61850-9-2 protocol.

PCS-931 series is made of a 4U height 19” chassis for flush mounting. Components mounted on
its front include a 320×240 dot matrix LCD, a 9 button keypad, 20 LED indicators and a multiplex
RJ45 port. A monolithic micro controller is installed in the equipment for these functions.

Following figures show front and rear views of PCS-931 respectively.

1 11
HEALTHY PCS-931
2 12
ALARM LINE DIFFERENTIAL RELAY
3 13

4 14
GRP

5 15

6 16 ENT
ESC

7 17

8 18

9 19

10 20

Figure 6.1-3 Front view of PCS-931

PCS-931 Line Differential Relay 6-3


Date: 2013-09-07