Lecture 2 (Three Phase Power Factor Correction and Unbalanced Polyphase Systems) (2018)
Lecture 2 (Three Phase Power Factor Correction and Unbalanced Polyphase Systems) (2018)
QcY = Vcap2 / Xc
Qcdelta = 3 Vcap2 / Xc
Therefore:
Ptotal = Pa + Pb + Pc
Qtotal = Qa + Qb + Qc
Stotal = Sa + Sb + Sc
Sample Problems
3. The unbalanced Y-load of Fig. 1 has balanced voltages of 100 V
and the acb sequence. Calculate the line currents and the neutral
current. Take ZA = 15 , ZB = 10 + j5 , ZC = 6 − j8 .
By matrix
SOLUTION
SOLUTION
SOLUTION
SOLUTION
Sample Problems
5. A 208V, 3 phase source supplies a delta connected impedance of
Zab=20cis0, Zbc=14cis-45 and Zca=14cis45, all in ohms. Determine
the line currents and the total complex power.
6. A four wire, three phase, 450V, 60Hz source supplies power to the
ff loads. Three impedances (13cis20) each connected in wye, an
unbalanced delta load consisting of 15cis45 between lines a and b,
3cis30 between lines c and a and 10cis60 between lines b and c. Draw
the power system diagram and calculate the line current in line ‘a’. Let
line ‘a’ voltage as reference.
SOLUTION
SOLUTION
Prob 6. SLD
SOLUTION
Three phase, three wire unbalanced
systems with parallel delta or Y loads
First, convert the Y-connected load
to a delta-connected load as shown
in Figure b. Notice, for
example, that both of the delta
connected loads in Figure b have an
impedance connected
between terminals A and B. These
impedances are in parallel and can
be replaced by a single
equivalent impedance. Replace the
parallel delta connected loads by a
single equivalent delta connected
load as shown in Figure c. Finally,
convert the delta connected load to
a Y-connected load as shown in
Figure d.
Problem Set 1
1. From no.6, Calculate the current Ib and Ic and the power factor at
the source side.
2. A delta connected load with impedances Zab=10, Zbc=10cis20 and
Zca=15cis30 is connected across 220V source. Suddenly, due to a
fault, line c is opened. Find the current at line b.
3. Using example no.4, convert the wye connected load to delta and
compute for the line currents.
4. A 100V source supplies a delta connected load of Zab=4cis0,
Zbc=2cis-30 and Zca=5cis60. A single phase load is then added at
phases a and b with a value of 5 ohms. Compute for the line
current at ‘a’ and the total power of the system.
Problem Set 1
5. Two balanced loads are supplied by an 840-V rms 60-Hz line. Load 1
is Y-connected with 30+j40 per phase, while load 2 is a balanced
three-phase motor drawing 57.9 hp with 90% efficiency at a power
factor of 0.8 lagging. Assuming the abc sequence, calculate: (a) the
complex power absorbed by the combined load, (b) the kVAR rating
of each of the three capacitors delta-connected in parallel with the
load to raise the power factor to unity, and (c) the current drawn from
the supply at unity power factor condition.