Universal Controller URE422 / URE424: Operating Manual
Universal Controller URE422 / URE424: Operating Manual
Universal Controller URE422 / URE424: Operating Manual
URE422 / URE424
Operating manual
WB-Elektronik GmbH
Mess- Steuer- Regeltechnik
Ottoweg12
D-64291 Darmstadt
Tel: 06151 377137
Fax:06151 377139
email: info@wb-elektronik.de
Internet:http://www.wb-elektronik.de
Operating manual URE422/URE424
The manufacturer reserves the right to revise this user´s manual and all
accompanying documentation and to make changes in the content without obligation
to notify or organisation of the revision or change.
IN NO EVENT WILL THE VENDOR BE LIABLE FOR DIRECT, INDIRECT, SPECIAL, INCIDENTIAL,
OR CONSEQUENTIAL DEMAGES ARISING OUT OF THE USE OR INABITLITY TO USE THIS
PORDUCT OR DOCUMENTATION, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH
DEMAGES. IN PARTICULAR, THE VENDOR SHALL NOT HAVE LIABILITY FOR ANY HARDWARE,
SOFTWARE, OR DATA STORED OR USED WITH THE PRODUCT, INCLUDING THE COST OF
REPAIRING, REPLACING, OR RECOVERING SUCH HARDWARE, SOFTWARE, OR DATA.
2001 by
WB-Elektronik GmbH
Messen - Steuern - Regeln
Ottoweg 12
D-64291 Darmstadt
Tel.: 06151 / 377137
Fax: 06151 / 377139
01/01 2 V3.0x
Operating manual URE422/URE424
Contents
1 GENERAL...........................................................................................................................5
5 ALARM - LEVEL...............................................................................................................11
7 INTRODUCTION ...............................................................................................................12
10 START OF SELFTUNING...............................................................................................12
01/01 3 V3.0x
Operating manual URE422/URE424
14 CONNECTORS ...............................................................................................................14
15 INPUTS............................................................................................................................14
16 OUTPUTS........................................................................................................................16
17 HARDWARE-CONFIGURATION ....................................................................................17
18 CONNECTION.................................................................................................................19
19 DIMENSIONS ..................................................................................................................19
20 SERVICE .........................................................................................................................20
01/01 4 V3.0x
Operating manual URE422/URE424
1 General
1.1 Display
The Universal Controller URE422/424 visualize its true value, limit values and parameter values on a
3½ digit digital display (1). A 3½ digit display is used for setpoint and funktionsdisplay (3), three LED
(2) to display the deviation and two LED (4) (URE424 has four) to display the binary output display.
1.2 Tasten
For the input of setpoint, manual output and to controll the parameters, two key (8) and (9) are
provided.
The button called Hand/Pgm ( 7 ) brings the controller to manual mode. If you are in the input mode
for parameters, this key toggles between select or adjust of the values.
With the We/Wi an exteral are a second internal setpoint can be selected (depending on configuration)
1.4 Sensordefect
A sensordefect is shows by flashing the true value and the output is set to a defined (Yb) value..
01/01 5 V3.0x
Operating manual URE422/URE424
1.5 Parameter
Prozessvalues, PID-parameters and the configuration-definitions are mapped in three layers. To enter
a layer, the buttons + and – are pressed simultaniously. The display shows „Co“ and the correct code
for the layer must be entered.
2 Operating instruction
01/01 6 V3.0x
Operating manual URE422/URE424
To provide a smooth switching from or to manual mode, the integral-value of PID is adapted. If only P-
function of the controller is selected the output bias Y0 is adapted.
Without manual mode ( Modus YH = 0 )
No manual mode is available, output value can only be displayed.
With manual mode ( YH = 1 )
To enter manual mode, press at first button Hand/Pgm. The output value is shows for 2 seconds.
Pressing + or – within this time enters the manual mode (LED (6) on). Now the output value can be set
with + and -.
To leave manual mode just press Hand/Pgm
3 Parameteter - Level
To enter the parameter level, the buttons + and – are pressed simultaniously. The display shows „Co“
and the correct code for the layer must be entered. Level access is confirmed by pressing button
Hand/Pgm. Default value for this level is 1. After successfull access the functional display show
parameter P. A wrong code leads back to operating level.
To change values in this level, select the parameter with + and -. To change the value press button
Hand/Pgm. Now the parameter-short in functional-display flashes and the value can be changed.
Pressing + or – for a longer time, increasing or decreasing is done automatical. The speed of changing
increases after 1 second. Pressing Hand/Pgm again stores the vaue and a selection of the next
parameter is possible.
To leave the level, select the parameter end or press + and – simutaniously.
01/01 7 V3.0x
Operating manual URE422/URE424
4 Configuration - Level
This level is entered in the same way as parameter level. Default code is 2. The follwing configurations
can be done:
Para Desciption Range Default User User
define define
E_ Controll - Range, Lower Limit -1999...1999 0
E¯ Controll - Range, Upper Limit -1999...1999 1000
E. Decimal Point .0.0.0 00.0
only available when ES 4...7 (mA/V)
Eo Input BIAS -1999 ..1999 0
EFi digital Inputfilter ( low pass of first order) [sec] 0.1 ... 100.0 1.0
ES Input Typ (X) 0...12 3
Important: refer to Pic.13.
0 Ö Pt100 0...600°C
1 Ö Pt100 0...199,9°C
2 Ö Pt100 -100...500°C
3 Ö Pt100 -100,0...+150,0°C
4 Ö 0...20mA
5 Ö 4...20mA
6 Ö 0...10Volt
7 Ö 2...10Volt
8 Ö Thermocouple NiCr-Ni 0...1232,0°C Typ K
9 Ö Thermocouple PtRh/Pt 0...1700,0°C Typ S
10 Ö Thermocouple Fe/CuNi 0...855,0°C Typ L
11 Ö Thermocouple Cu/CuNi 0...600,0°C Typ U
12 Ö Lambda Sonde 50..0mV (Hardware
modifikation necessary).
SPE Set Point Mode 0...10 0
0 Ö Winternal
1 Ö Wexternal
2 Ö Winternal + Wexternal (Setpoint-Addition)
3 Ö Winternal - Wexternal (Setpoint-Subtraction)
4 Ö Minimum selection between Winternal and
Wexternal.
5 Ö Maximum selection between Winternal and
Wexternal.
6 Ö Selection of Winternal and Wexternal by push
key "Wext/Wint"
7 Ö selection of Winternal and Wexternal by
digital input BE
8 Ö selection of Winternal and Wexternal by push
key "Wext/Wint" or digital input BE
9 Ö Quit Alarm1 (latched) by Push key "Wext/Wint"
10 Ö Quit Alarm1 (latched) by digital input BE
Note:
LED „on“ in push key "Wext/Wint" indicates Wext
active, otherwise Wint is active.
SP2 Second Set Point W2intern 0...1 0
0 Ö W2intern off.
1 Ö W2intern instead of Wextern in mode SPE.
01/01 8 V3.0x
Operating manual URE422/URE424
01/01 9 V3.0x
Operating manual URE422/URE424
01/01 10 V3.0x
Operating manual URE422/URE424
5 Alarm - Level
This level is entered in the same way as parameter level. Default code is 3. The follwing configurations
can be done:
.
Para Desciption Range Default User User
define define
A.1 Limit Comparator Value Alarm 1[as config.] 0
At 1.A = 1 bis 5 -1999...1999
At 1.A = 6 und 7 -100..100%
AH1 Hystereses 1[as config] 0
At 1.A = 1 bis 5 0...1999
At 1.A = 6 und 7 0..100%
Hysteres also available in Three-Point-Stepper
Mode
A.2 Limit Comparator Value Alarm 2[as config.] 0
At 2.A = 1 bis 5 -1999...1999
At 2.A = 6 und 7 -100..100%
AH2 Hystereses 2 [as config] 0
At 2.A = 1 bis 5 0...1999
At 2.A = 6 und 7 0..100%
A.3 Limit Comparator Value Alarm 3 [as config.] 0
(URE424 only)
At 3.A = 1 bis 5 -1999...1999
At 3.A = 6 und 7 -100..100%
AH3 Hystereses 3 [as config] (URE424 only) 0
At 3.A = 1 bis 5 0...1999
At 3.A = 6 und 7 0..100%
A.4 Limit Comparator Value Alarm 4 [as config.] 0
(URE424 only)
At 3.A = 1 bis 5 -1999...1999
At 3.A = 6 und 7 -100..100%
AH4 Hystereses 4 [as config] (URE424 only) 0
At 3.A = 1 bis 5 0...1999
At 3.A = 6 und 7 0..100%
01/01 11 V3.0x
Operating manual URE422/URE424
8 Selftuning Preparations
• Release manual mode (in configuriation level YH =1).
• Change Controller to manual mode (in operating level push key Pgm/Hand followed by× or Ø
within 2 seconds).
• Select manual output value with push key × or Ø.
10 Start of Selftuning
• In the system all building-ups should be completed.
• Push key Pgm/Hand
• The start of the selftuning is indicated by the display alternating SLF and Setpoint.
Changing the Setpoint in this condition is impossible.
11 End of Selftuning
01/01 12 V3.0x
Operating manual URE422/URE424
01/01 13 V3.0x
Operating manual URE422/URE424
14 Connectors
15 Inputs
Using switch S1(Pic 16) according to Pic 15 and input mode ES = 0 ..3, a
11 12 13 PE
Pt100-element in 2wire connectioncan be connected as shown. Use a
shielded wire and connect the shield to protective ground of the unit. For
wire-resitance calibration use zero adjust E0 in configuration layer.
Pic 5: Pt100 - in
2wire-connection
11 12 13 PE Using switch S1(Pic 16) according to Pic 15 and input mode ES = 0 ..3, a
Pt100-element in 3wire connectioncan be connected as shown. Use a shielded
wire and connect the shield to protective ground of the unit. A wire-resitance
calibration is not neccessary.
Pic 6: Pt100 - in
3wire-connection
01/01 14 V3.0x
Operating manual URE422/URE424
15.3 Input mA or V
mA
V
Pic 7: Inout
0(4) .. 20mA
15.4 Thermocouple
Pt100
Thermoelement Vergleichsstelle
Abb 8: Input Thermocouple
with Compensation
Using switch S1(Pic 16) according to Pic 15 and input mode SPN = 0 or 1, an
PE 16 17 instrument with mA output and with mode SPN = 2 or 3 an instrument with V
output can be connected as shown. Use a shielded wire and connect the
shield to protective ground of the unit.
mA
V
Pic 9:Input
0(4) .. 20mA or
0(2) .. 10V
01/01 15 V3.0x
Operating manual URE422/URE424
16 Outputs
16.1 Output Y mA or V
The analog output is optional and need the assembly of an additional board
(Pic 17). Using switch S1(Pic 16) according to Pic 15 and output mode Yn =
PE 21 22 0 ..2, a controll element with mA output can be connected as shown. Use a
shielded wire and connect the shield to protective ground of the unit.
The output signal can be selected on the board by a switch (0(4)...20mA or
0(2)...10V ).
mA
V Dot viewable -> mA output
Dot not viewable -> V-output
Pic 10: Output
0(4) .. 20mA or
0(2) .. 10V
01/01 16 V3.0x
Operating manual URE422/URE424
17 Hardware-Configuration
Most of configuration are controlled by software. Some few adaption must be done by hardware as
follows:
• Input X
• Externer Sollwert Wext
configuration with S1 and S2 (Pic 16) according to the table Pic 15
• analog output
the optional output modul (Pic 17) must be installed. The output signal is selected by a switch on
the modul.
01/01 17 V3.0x
Operating manual URE422/URE424
S2 S1
OFF
ON
Pkt. sichtbar -> BE aktiv LOW
Pkt. unsichtbar -> BE aktiv HIGH
Analogausgang
(optional)
mA V
01/01 18 V3.0x
Operating manual URE422/URE424
18 Connection
BE 10
11
12
X 13 L
Hilfenergie
14 + N 110..240V
mA mV 48..62Hz
V 15 PE
_
mA 16 45 41 Alarm 1
2Pkt-Ausgang
Wext V
BA3 Alarm 3 BA1
3Pkt-Schritt +
+ 17 46 42 (AUF)
mA + 21 47 43 Alarm 2
Y _ BA4 Alarm 4 BA2 3Pkt-Ausgang
3Pkt-Schritt -
V 22 48 44 (ZU)
Bei Eingang Thermoelement muß zur Vergleichsstellenkorrektur ein Pt100 Element an die Klemmen
12 und 13 angeschlossen werden und die Klemmen 11 und 12 müssen gebrückt werden.
19 Dimensions
96m m 92m m
3 .7 8 " 3 .6 2 “
110m m
4 .3 “ 96m m 92m m
7m m
125m m 3 .7 8 " 3 .6 2 “
0 .3 “ 4 .9 “
01/01 19 V3.0x
Operating manual URE422/URE424
20 Service