Transfer LC / AC-177
Transfer LC / AC-177
Transfer LC / AC-177
Feature codes
Following is an alpha-numeric listing of feature codes. Those identified as “NA” cannot be ordered as field installable
accessories. They must be selected on the original factory order.
Feature
code Description Accessory kit part number Instruction sheet
A005-7 Contactor-Mech Held Line NA NA
Each set of contacts (3 poles) on the normal power
source side is held mechanically.
A007-7 Contactor-Mech Held Both NA NA
Each set of contacts (3 poles) on both sides is held
mechanically.
A028-7 Poles-3 NA NA
This is a 3-pole switch with a solid neutral.
A035-7 Appl-Utility to Genset NA NA
This switch is designed for utility to generator set
applications.
A041-7 System-1 Phase,2-W or 3-W NA NA
The transfer switch is for 1 phase, 2-wire or 3-wire
power supply systems.
A042-7 System-3 Phase,3-W or 4-W NA NA
The transfer switch is for 3 phase, 3-wire or 4-wire
power supply systems.
A044-7 Frequency-60 Hertz NA NA
The transfer switch is set up at the factory for switching
60 Hertz electrical power sources.
A045-7 Frequency-50 Hertz NA NA
The transfer switch is set up at the factory for switching
50 Hertz electrical power sources.
A080-7 Certification-Seismic ATS NA NA
CERTIFICATION - SEISMIC ATS; FOR ALL AUTOMATIC
AND MANUALLY OPERATED CUMMINS TRANSFER
SWITCHES, INCLUDING ALL RANGES OF AVAILABLE
AMPERAGES, VOLTAGES, FREQUENCIES AND ALL
AVAILABLE NEMA TYPES OF ENCLOSURES
©2009 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation, Cummins and PowerCommand are registered
trademarks of Cummins Inc. “Our energy working for you.” and InPower are trademarks of Cummins Power Generation. Other company, product
or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
AC-177 (10/09)
Feature
code Description Accessory kit part number Instruction sheet
B001-7 Cabinet-Type 1 NA NA
The transfer switch is mounted in a Type 1, general
purpose, non- ventilated cabinet.
B002-7 Cabinet-Type 3r NA NA
The transfer switch is mounted in a Type 3R, non-
ventilated, rain proof cabinet.
B004-7 Construction - Open NA NA
The transfer switch, complete cabinet door assembly
and optional charger are shipped ready for mounting by
others in a suitable non-ventilated cabinet.
C021-7 Control-Switch, Package A NA NA
Electronic control consists of fixed time delays: TD
Start-3 seconds, TD Transfer-3 seconds, TD Retransfer-
5 minutes, TD Stop-5 minutes. Also included are single
phase normal and emergency voltage sensing with fixed
pickup and dropout settings. Not included are normal
connected/available lights, emergency
connected/available lights, momentary test switch,
instant retransfer switch, and seven day exerciser.
C022-7 Control-Switch, Package B NA NA
Electronic control consists of adjustable time delays: TD
Start 0-15 seconds, TD Transfer 0-120 seconds, TD
Retransfer 0-30 minutes, TD Stop 0-10 minutes. Also
included are, three phase normal and single phase
emergency under-voltage sensing with adjustable
pickup and dropout settings Normal
connected/available lights, Emergency
connected/available lights, momentary test switch,
instant retransfer switch, and 7 day exerciser clock with
a with/without load switch.
J027-7 Prgrm Transition-0.1-3.0S (NA on LTA) NA NA
An adjustable 0.1 to 3.0 second programmed time delay
is provided to drive the transfer switch to the neutral
position during transfer to allow residual voltages from
inductive loads to decay to a safe level before
continuing the transfer.
J028-7 Prgrm Transition-0.1-30S (NA on LTA) NA NA
An adjustable 0.1 to 30 second programmed time delay
is provided to drive the transfer switch to the neutral
position during transfer to allow residual voltages from
inductive loads to decay to a safe level before
continuing the transfer.
K001-7 Battery Charger-2A,12/24V
A 2 amp, 12/24 volt, SCR regulated float type battery
charger is provided for recharging the cranking batteries
during standby.
120 Vac 0300-6026-09 000C-0687
208 Vac 0300-6026-10 000C-0687
220/240 Vac 0300-6026-11 000C-0687
380 Vac 0300-6026-13 000C-0687
416/440 Vac 0300-6026-14 000C-0687
480 Vac 0300-6026-15 000C-0687
600 Vac 0300-6026-16 000C-0687
©2009 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation, Cummins and PowerCommand are registered
trademarks of Cummins Inc. “Our energy working for you.” and InPower are trademarks of Cummins Power Generation. Other company, product
or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
AC-177 (10/09)
Feature
code Description Accessory kit part number Instruction sheet
Literature List
Standard
LCA/B/C 0999-0014
LCD/E 0999-0015
LTA/B/C 0999-6145
LTD/E 0999-6146
Seismic
LCA/B/C 0999-0014-01
LCD/E 0999-0015-01
LTA/B/C 0999-6145-01
LTD/E 0999-6146-01
Warning: Back feed to a utility system can cause electrocution and/or property damage. Do not connect generator sets to any building
electrical system except through an approved device or after building main switch is open.
Warning: For professional use only. Must be installed by a qualified service technician. Improper installation presents hazards of electrical
shock and improper operation, resulting in severe personal injury and/or property damage.
©2009 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation, Cummins and PowerCommand are registered
trademarks of Cummins Inc. “Our energy working for you.” and InPower are trademarks of Cummins Power Generation. Other company, product
or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
AC-177 (10/09)