Wiring Diagram

This wiring diagram describes circuit connections for all


models of the VF1810 and K1810 Series Elite XT /
Sigma A-XT Releasing Fire Control Panel.

The operation of this product is intended for indoor use only.

Contents Page

Front View, Wire Gauge and Related Documentation..……...... 2

Connection Diagram………………………………………………….. 3

Main Supply Circuit ………………………………………………….. 4

Rechargeable Battery Circuit ………………………………………. 5

Ground Fault Indications ………………………………………........ 6

Power Output Circuits ……………………………………………….. 7

Limited-Energy Circuits ……………………………………………... 7

Supervised Circuits ………………………………………………….. 7

Initiating Device Circuit ……………………………………………… 8-9

Notification Appliance Circuit ……………………………………… 10 -13

Releasing-Device Circuits …………………………………………... 14

Abort Function ………………………………………………………... 15

Status Units (Data and Power) ……………………………………... 16

Relay Circuits …………………………………………………………. 17

AUX 24V ………………………………………………………………... 17

File: S8485, Part Number: Man-1147


Revision E07.14, Date: April 2017 1
Front View, Wire Gauge and Related Documentation
Of The Elite XT / Sigma A-XT Releasing Fire Control Panel

Front View

Wire Gauge
Connect 18 to 14 AWG wiring for all field terminations except the
AC input. Connect 14 AWG wiring for line, neutral and ground
terminations of the AC input.
Related Documentation
The following documents shall be used to provide additional
information for installing and operating the VF1810 or K1810
series Elite XT / Sigma A-XT Releasing Fire Control Panel:
 Installation and Operation Manual, Man-1145 (K / VF1812-00), Rev. E03.XX
 Operating Instructions, Man-1146 (K / VF1825-00), Rev. E01.XX
 UL Compliance Label, Lab-1846, Rev. E02.XX

File: S8485, Part Number: Man-1147


Revision E07.14, Date: April 2017 2
Connection Diagram
Of the Elite XT / Sigma A-XT Releasing Fire Control Panel

Revision E07.14, Date: April 2017


File: S8485, Part Number: Man-1147
3
Main Supply Circuit
Line Connection

Terminals Description Voltage

L AC Line 115 VAC @


50 / 60Hz

230 VAC @
50 / 60Hz

N AC Neutral

Earth-Ground

Power Supply

Rating 115 VAC - 125 VA


230 VAC - 126 VA

AC Input Fuse 1.6 Amp, 250 VAC,


slow-blow, 5 x 20mm

Input 115 or 230 VAC


(Supervised) 50/60Hz

Transfer Voltage 115 VAC transfer @


90 VAC, 230 VAC
transfer @ 180 VAC

File: S8485, Part Number: Man-1147


Revision E07.14, Date: April 2017 4
Rechargeable Battery Circuit
Standby-Battery Type Two 12 VDC, 7 AH, sealed
lead acid, batteries , flame
retardant UL94:V-0

Standby-Battery Charging Two standby batteries wired


in series

Charge Current 700 mA maximum

Output Current 0 - 2 Amps

Standby-Operating Time 24 Hours

Battery Charge Voltage 27.6 VDC

Fire Control Panel Current 100 mA with buzzer sounding


Draw From Battery
While In Mains Fail,
Standby And Not in Alarm

Maximum Current Draw 620 mA (Current does not


of FACP, In Alarm include loads from NACs,
Solenoid, Status Units,
Ancillary Boards and
Auxiliary equipment)

Maximum Current Draw 2 Amps


From Batteries

Caution
RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE.
DDISPOSE OF USED BATTERIES ACCORDING TO THE INSTRUCTIONS

File: S8485, Part Number: Man-1147


Revision E07.14, Date: April 2017 5
Ground Fault Indications
A ground fault indication occurs when 30K Ohms or less exists
between earth-ground and the following field terminals of the
Elite XT / Sigma A-XT Releasing Fire Control Panel:
 AUX 24V
 POWER, STATUS UNITS
 NAC 1, NAC 2 and NAC 3
 ZONE 1, ZONE 2, ZONE 3
 MODE SELECT
 MAN RELEASE
 ABORT
 REL. PRES. SWITCH
 EXTING.
 LOW P. SWITCH
 DATA, STATUS UNITS

File: S8485, Part Number: Man-1147


Revision E07.14, Date: April 2017 6
Power Output Circuits
Special application outputs are provided on the following
terminals of the Elite XT / Sigma A-XT Releasing Fire Control
Panel :
 NAC 1
 NAC 2
 NAC 3
 AUX 24V
 POWER, STATUS UNITS
 EXTING

Limited Energy Circuits


All circuits of the Elite XT / Sigma A-XT Releasing Fire Control
Panel are power limited except AC input/output, battery,
transformer input/output and bridge rectifier input/output.

Supervised Circuits
All circuits of the Elite XT / Sigma A-XT Releasing Fire Control
Panel are supervised except relay terminals for 1ST STAGE,
2ND STAGE, EXTRACT, TROUBLE RELAY, LOCAL FIRE and
FIRE RELAY.

File: S8485, Part Number: Man-1147


Revision E07.14, Date: April 2017 7
Initiating Device Circuit
Initiating Device Circuits are Class B, Style C

Authorized initiating devices are two-wire smoke and closed-


contact-type detectors.

Terminals

ZONE 1 Supervised input: 6.8K Ohm


EOL resistor S2027, 470 Ohm
ZONE 2 trigger resistor S2051 and 270
ZONE 3 Ohm trigger resistor S2052
Detectors – 470 Ohm
Pull Stations - 270 Ohm

MODE SELECT Supervised input: 6.8K Ohm


EOL resistor S2027 and 470
MAN. RELEASE Ohm trigger resistor S2051.
ABORT Mode Select must include the
REL. PRESS. SWITCH 6.8K Ohm EOL resistor
S2027 to maintain the
LOW PRESS. SWITCH supervised input.

EXTING. Supervised output: 1N504-G


EOL diode S2029

Pull stations authorized for use with the Elite XT and Sigma
A-XT Releasing Fire Control Panel are non-addressable
and UL listed.
File: S8485, Part Number: Man-1147
Revision E07.14, Date: April 2017 8
Initiating Device Circuit
Adjustable

Extinguishant Output Adjustable 0 to 60 seconds


Delay (+/- 10%) in 5 second intervals

Extinguishant Duration Adjustable 60 to 300 seconds (+/


- 10%) in 5 second intervals

Short Circuit Threshold Adjustable

Remote Control Inputs No Connect (NC) terminals.

Mode Select No Connect (NC) terminal

Ratings

Maximum Operating 21.6 VDC


Voltage

Maximum Short Circuit 65 mA


Current

Maximum Line 20.3 Ohms


Impedance

File: S8485, Part Number: Man-1147


Revision E07.14, Date: April 2017 9
Notification Appliance Circuit
Polarized NAC outputs of the Elite-XT / Sigma A-XT
Appliance Releasing Fire Control Panel accept
Requirement devices that are polarized only. A trouble
condition is reported when non-polarized
NAC devices are connected to these NAC
outputs. Field connections must include
symbol-markings for plus (+) and minus (-)
on all polarized appliance terminations.

Connection Rating

NAC 1 and Special Application: 18 to 28 VDC


NAC 2 ( + ), ( - ) @ 500 mA continuous
Regulated: 18 to 28 VDC
@ 50 mA continuous
Fused: Electronic 1.1 A
EOL Part
Supervision: Voltage reversing DC
#S2027
Short Circuit Threshold:
130 Ohms +/- 20%
Maximum line-voltage-drop: 2 VDC
Class B, Style Y operation

NAC 3 ( + ), ( - ) Releasing Output Only


Special Application: 18 to 28 VDC
@ 500 mA pulsed and continuous
Regulated: 18 to 28 VDC
@ 50 mA pulsed and continuous
EOL Part Fused: Electronic 1.1 A
#S2027 Supervision: Voltage reversing DC
Short Circuit Threshold:
130 Ohms +/- 20%
Maximum line-voltage-drop: 2 VDC
Class B, Style Y operation

File: S8485, Part Number: Man-1147


Revision E07.14, Date: April 2017 10
Notification Appliance Circuit
NAC Synchronization

The Elite XT / Sigma A-XT Releasing Fire Control Panel


supports special application outputs of NAC 1 and NAC 2
when operating:
 Amseco NAC devices with Amseco synchronization
modules
 Gentex NAC devices with Gentex synchronization modules
 System Sensor NAC devices with System Sensor
synchronization modules
 Wheelock NAC devices with Wheelock synchronization
modules

NAC channels 1 and 2 of the Elite XT / Sigma A-XT Releasing


Fire Control Panel provide single and dual circuit
synchronization. Single circuit synchronization provides a
synchronized output on one channel of two NAC channels.
Dual circuit synchronization provides a synchronized output on
NAC 1 and NAC 2.

Maximum Current

A maximum current of 1.5 Amps is available for powering


NAC 1, NAC 2 and NAC 3 when a maximum load of 500 mA
exists on any one of the NAC outputs.

File: S8485, Part Number: Man-1147


Revision E07.14, Date: April 2017 11
Notification Appliance Circuit
The following statements for NAC synchronization are
necessary for UL qualification and exclude device-loading
combinations that are common in most FACP installations:

Amseco NAC 1 and NAC 2 of the Elite XT / Sigma A-XT


Releasing Fire Control Panel can each operate
a maximum of seven Amseco SL-1224 strobes
when configured for 15cd outputs and
synchronized with an Amseco SMD10-3A
synchronization module.

Gentex NAC 1 and NAC 2 of the Elite XT / Sigma A-XT


Releasing Fire Control Panel can each operate
a maximum of six Gentex GES3-24 strobes
when configured for 15cd outputs and
synchronized with a Gentex AVSM
synchronization module.

System NAC 1 and NAC 2 of the Elite XT / Sigma A-XT


Sensor Releasing Fire Control Panel can each operate
a maximum of eight System Sensor S1224MC
strobes when configured for 15cd outputs and
synchronized with a System Sensor MDL
synchronization module.

Cooper/ NAC 1 and NAC 2 of the Elite XT / Sigma A-XT


Wheelock Releasing Fire Control Panel can each operate
a maximum of eight Cooper/Wheelock
RSS-24MCW strobes when configured for 15cd
outputs and synchronized with a Cooper/
Wheelock SM-24 synchronization module.

File: S8485, Part Number: Man-1147


Revision E07.14, Date: April 2017 12
Notification Appliance Circuit
NAC outputs of the Elite XT / Sigma A-XT Releasing Fire
Control Panel are not limited by conditions other than the
maximum rated current threshold. NAC outputs of the Elite XT /
Sigma A-XT Releasing Fire Control Panel can operate
combinations of VES authorized NAC devices as long as the
circuit load does not exceed 500 mA.
Reference manufacturer data sheets for individual device loads
and then total the loads to determine if the sum exceeds the
500 mA threshold of each NAC output.

File: S8485, Part Number: Man-1147


Revision E07.14, Date: April 2017 13
Releasing Device Circuits
Exting. Releasing output: 18 to 28 VDC, with 1.0 Amp
maximum load for 5 minutes and voltage reversing
DC. Maximum line-voltage-drop: 2.4 VDC
Fused at 1.6 Amps

Authorized Releasing Valves


Manufacturers Model
ASCO HV2185328

ASCO 8210G207

Viking 11591, 11592, 11595, 11596, 11601, 11602

Solenoid Solutions 2823A-2NB-A4F6—>Manufactured for:


Snap-Tite, Sevo Systems, Orient, Chemori

Sevo Systems SOL EA45, The SOL EA45 is equivalent to Sevo


Systems 510006 and TLX Technologies PA0036-3
Firetrace, TLX Linear Actuator-FTF500125 or 01-501462; TLX
Technologies Technologies PA0128-5

Kidde K-45-8017, The K-45-8017 is equivalent to Kidde-


Fenwall 486500-01

Kidde B6793-859, The B6793-859 is equivalent to Kidde-


Fenwall 81-100000-001
Victaulic Series 753-E FireLock

Fire Eater 305450 Ci IS8B Solenoid

Fire Eater 305451 Ci IS8B Solenoid and Manual

Safety Hi-Tech SH21006403

Safety Hi-Tech SH21006404

Janus 18481
The extinguishant release output of the Elite XT / Sigma A-XT Releasing Fire
Control Panel is 1 Amp. All solenoids must operate using 1 amp or less.
The solenoid releasing valves above are authorized for use as Fire Protection-
Service Valves on the Elite XT / Sigma A-XT Releasing Fire Control Panel.
File: S8485, Part Number: Man-1147
Revision E07.14, Date: April 2017 14
Special Releasing Accessories
Manufacturer Description Model

Kentec Electronics Sequential Activator FP-SA/GEN3.0


[Standard Cabinet]
VF/K1824-10 or -40
(Red or Gray)
FP-SA/GEN3.0
[Large Cabinet]
VF/K1824-11 or -41
(Red or Gray)
FirePro Fixed Condensed See Models
Aerosol Below
Extinguishing Units
FP-20SE (FNX-20S) FP-20T (FNX-20T),
FP-40S (FNX-40S), FP-40T (FNX-40T),
FP-80S (FNX-80S), FP-80T (FNX-80T),
FP-100S (FNX-100S),
FP-200S (FNX-200S),
FP-500S (FNX-500S),
FP-1200 (FNX-1200), FP-1200S (FNX-1200S),
FP-1200T (FNX-1200T), FP-1200TS (FNX-1200TS),
FP-2000 (FNX-2000), FP-2000S (FNX-2000S),
FP-2000T (FNX-2000T), FP-2000TS (FNX-2000TS),
FP-3000 (FNX-3000), FP-3000S (FNX-3000S),
FP-3000T (FNX-3000T), FP-3000TS (FNX-3000TS),
FP-4200T (FNX-4200T), FP-4200TS (FNX-4200TS),
FP-5700 (FNX-5700), FP-5700S (FNX-5700S),
FP-5700T (FNX-5700T), FP-5700TS (FNX-5700TS)

Please refer to instructions included with Sequential Activator for


proper wiring

File: S8485, Part Number: Man-1147


Revision E07.14, Date: April 2017 15
Abort Function

Override The abort function overrides the manual


Operation release when the manual release is activated
before the abort.
The manual release overrides the abort
function when the abort is activated before
the manual release.

Connection Monitored input EOL 6.8K Ohm +/- 5%


resistor, S2027, activation
impedance 470 Ohms

File: S8485, Part Number: Man-1147


Revision E07.14, Date: April 2017 16
Status Units (Data and Power)
Data

RS485 Serial Two-wire RS485, Maximum line impedance


Bus 120 Ohms, SLC Class B Style 4

Connector 14 to 18 AWG wire


Terminals

Maximum Maximum Number of Units 7 Status Units,


Number of 7 Ancillary Boards. A separate power source
Units must be used if the total-load-current at the
STATUS UNIT, POWER terminals exceed
500 mA.

Power

Maximum Maximum Output Rating 18 to 28 VDC, 1.1


Output Rating A electronic fuse, 500 mA maximum load

Connector 14 to 18 AWG wire


Terminals

Maximum Load dependant, 500 mA maximum in


Number of alarm
Units

File: S8485, Part Number: Man-1147


Revision E07.14, Date: April 2017 17
Relay Circuits
Operation Common

Current 1A maximum, volt free change over contact

Voltage 30 VDC

Power Factor 1.0 PF

AUX 24V
Terminal Rating

AUX 24V 18 – 28 VDC Special Application output,


(+ / R0V) 500 mA maximum

File: S8485, Part Number: Man-1147


Revision E07.14, Date: April 2017 18
File: S8485, Part Number: Man-1147
Revision E07.14, Date: April 2017 19
Man-1147
File: S8485, Part Number: Man-1147
Revision E07.14, Date: April 2017 20