Contents Page
Connection Diagram………………………………………………….. 3
Front View
Wire Gauge
Connect 18 to 14 AWG wiring for all field terminations except the
AC input. Connect 14 AWG wiring for line, neutral and ground
terminations of the AC input.
Related Documentation
The following documents shall be used to provide additional
information for installing and operating the VF1810 or K1810
series Elite XT / Sigma A-XT Releasing Fire Control Panel:
Installation and Operation Manual, Man-1145 (K / VF1812-00), Rev. E03.XX
Operating Instructions, Man-1146 (K / VF1825-00), Rev. E01.XX
UL Compliance Label, Lab-1846, Rev. E02.XX
230 VAC @
50 / 60Hz
N AC Neutral
Earth-Ground
Power Supply
Caution
RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE.
DDISPOSE OF USED BATTERIES ACCORDING TO THE INSTRUCTIONS
Supervised Circuits
All circuits of the Elite XT / Sigma A-XT Releasing Fire Control
Panel are supervised except relay terminals for 1ST STAGE,
2ND STAGE, EXTRACT, TROUBLE RELAY, LOCAL FIRE and
FIRE RELAY.
Terminals
Pull stations authorized for use with the Elite XT and Sigma
A-XT Releasing Fire Control Panel are non-addressable
and UL listed.
File: S8485, Part Number: Man-1147
Revision E07.14, Date: April 2017 8
Initiating Device Circuit
Adjustable
Ratings
Connection Rating
Maximum Current
ASCO 8210G207
Janus 18481
The extinguishant release output of the Elite XT / Sigma A-XT Releasing Fire
Control Panel is 1 Amp. All solenoids must operate using 1 amp or less.
The solenoid releasing valves above are authorized for use as Fire Protection-
Service Valves on the Elite XT / Sigma A-XT Releasing Fire Control Panel.
File: S8485, Part Number: Man-1147
Revision E07.14, Date: April 2017 14
Special Releasing Accessories
Manufacturer Description Model
Power
Voltage 30 VDC
AUX 24V
Terminal Rating