Sliding Door Operator Besam SL500 T Installation and Service Manual Original Instructions, NA
Sliding Door Operator Besam SL500 T Installation and Service Manual Original Instructions, NA
Sliding Door Operator Besam SL500 T Installation and Service Manual Original Instructions, NA
Besam SL500 T
CONTENTS
1 Revision ..................................................................................................................................................................................... 4
2 Important information ......................................................................................................................................................... 5
3 Technical specification .......................................................................................................................................................... 7
4 Design and function description ....................................................................................................................................... 8
5 Models ........................................................................................................................................................................................ 9
6 Identification ........................................................................................................................................................................... 10
7 Space required ........................................................................................................................................................................ 13
8 Mechanical Installation ........................................................................................................................................................ 14
9 Electrical connections ........................................................................................................................................................... 46
10 Break Out/Safety – Hold Beam Connection Diagram ................................................................................................. 59
11 Start-Up ..................................................................................................................................................................................... 60
12 Signage ....................................................................................................................................................................................... 70
13 Troubleshooting ..................................................................................................................................................................... 71
14 Maintenance/Service ............................................................................................................................................................. 76
15 Accessories ............................................................................................................................................................................... 78
16 Door Handing & Layout ........................................................................................................................................................ 82
17 ANSI / BHMA A156.10 - 2011 ............................................................................................................................................. 83
18 Glazing and Blocking of Glass ............................................................................................................................................. 85
1 Revision
2 Important information
It is easy to install for both new construction and retrofit application and can be adapted to a wide
range of overhead concealed or surface applied installations.
For use see Owners Manual 1008210.
3 Technical specification
Note: The mains power supply shall be installed with protection and an
all-pole mains switch with isolating capability of Category III, at least
1/8" (3 mm) between contacts, shall be installed according to local
regulations. These articles are not provided with the door.
Power consumption: Max. 250 W
Auxiliary voltage: 24 V DC, 1 A
Recommended max. Bi-parting Non-panic:
door weight: Besam SL500 T-2 220 lb./leaf (100 kg/leaf)
Bi-parting with panic:
Besam SL500 T-2: 220 lb/leaf (100 kg/leaf)
Single Slide Non-panic:
Besam SL500 T-R/L 220 lb./leaf (100 kg)
Single Slide with panic:
Besam SL500 T-R/L: 220 lb/leaf (100 kg/leaf)
Clear opening: Bi-parting:
Besam SL500 T-2: 593/16"- 1073/16" (1503 - 2723 mm)
Single Slide:
Besam SL500 T-R/L: 367/16"– 847/16" (926 – 2145 mm)
Opening and closing Bi-Parting:
speed: (Besam SL500 T-2) Variable up to approx. 4.5 ft/sec. (1.4m/s)
To be adjusted to comply with ANSI/BHMA A156.10. Note that local
codes may vary.
Hold open time: 0-60 s
To be adjusted to comply with ANSI/BHMA A156.10. Note that local
codes may vary.
Ambient temperature: -4°F to 122°F (-20 °C to +50 °C)
Relative humidity Max. 85%
(non-condensing):
The Besam SL500 T complies with: ANSI/BHMA A156.10, UL 325, UL 60730, NFPA 79
To be installed internally or with suitable weather protection externally.
Note: The glazing material of all doors shall comply with the requirements in the American National
Standard Performance Specification and Methods of Test for Safety Glazing Material Used in
Buildings, Z97.1-1975.
Design
The sliding door operator Besam SL500 T works electromechanically. The motor, control unit,
transmission – and optional emergency unit and electromechanical locking device – are all assembled
in a support beam with an integrated cover. The motor and gear box transmit movement to the
door leaves by means of a tooth belt. The door leaf is fitted to a door adapter/carriage wheel fitting
and hangs on a sliding track. The guiding at the bottom is carried out by means of floor guides (Full
Break-Out) or Side Panel Guides (Fixed Sidelites).
Function
Opening
When an OPENING IMPULSE is received by the control unit the motor starts and transmits movement
to the door leaves, which move to the open position.
Closing
The closing starts when no OPENING IMPULSE is received and the HOLD OPEN TIME has expired.
Emergency escape
The Besam SL500 T can be combined with an emergency unit that automatically opens or closes¹
the doors in the event of a power failure and can also be interfaced with the fire alarm or smoke
detector. Safety can be further reinforced by incorporating a break-out fitting. This enables the
doors and sidelites to swing outwards in an emergency situation by applying a light pressure at
the front edge.
Doors used for emergency escape in buildings such as hospitals and homes for elderly people may
not be locked or put in mode selection OFF.
¹ Electrical emergency operation unit only
Safety sensors
Safety sensors must be installed per ANSI A156.10 Standards for Power Operated Pedestrian Appli-
cations.
5 Models
Besam provides several layouts for the Besam SL500 T sliding door system. Operators can be bi-
parting or single slide (left or right handed) and sidelites may be installed fixed to the interior or
hinged to Break-out in emergencies. (See illustrations of various layouts in the "Installation Examples"
section on page 16.)
All Besam SL500 T systems are ready for installation when delivered. The sidelites and active leaves
are fully prepared and all hardware is installed. Operators are supplied with all mounting hardware,
and rivnuts have been installed in the side jambs.
Before installing the Besam SL500 T system, check to see that you have been supplied the correct
equipment and that, all necessary tools and hardware are at hand. Also, check the installation site
for any factors that might interfere with proper installation. (See "Installation Examples" section
on page 16.)
6 Identification
1
3
23 22
4 10
5
8
9
13 7
18 14
16 11
24
6
15
12
13
21
20
17
25
19
6.1 Options
6.1.1 Active Leaf Panic Break-Out System
10
9 2
8
6 11
SECTION A-A
7 Space required
8 Mechanical Installation
8.1 Checking
Make sure that the wall is properly reinforced at the installation points.
Check that the wall material has the necessary reinforcements and that the floor is level and smooth.
The beam/wall used to fix the support beam must be flat and smooth. If necessary use mounting
spacers behind the support beam to keep it straight.
Fastening requirements
Wall material Minimum requirements*
Steel 3/16" (5 mm)**
Aluminum 1/4" (6 mm)**
Reinforced concrete min. 2" (50 mm) from the edge
Wood 2" (50 mm)
Brick wall Expansion-shell bolt, min. 1/4" x 3 1/2", min. 2" (50 mm) from the edge
* Besam minimum recommended requirements. Building Codes may give different specifications
** Thinner wall profiles must be reinforced with rivnuts
After installation, final adjustment for proper operation of the door system, shall be performed in
the field.
For Surface Applied Standard Applications all narrow frame with 1/4” glass, both Single Slide and
Bi-parts, the overall frame height is 91”. (Overhead Concealed overall frame height is 89 ¾”.)
Mounting Clip
d Attach Jamb Tubes to Header. See "Checking – Marking Out – Fastening" on page 22.
e Lift Header and dry fit. Drill for attachment and attach to substrate or wall using standard con-
struction methods.
Note!
Attachment points will vary from application to applica-
tion. Use best building practices and appropriate hard-
ware in order to install beam and jambs securely.
h Layout the other half of the Filler Tube allowing the wire to be run up through Filler Tube to
Header, threading wire through wiring hole in Header.
Use care that all holes are deburred to prevent electrical shorts.
Filler Tube
Note: If there is any bowing to the Filler Tube, the Filler Tube halves will not snap securely in
place.
Break-Out
Sensor
Operation Mode
Selector placement
Self-Adhesive when factory prepped
Weather-Stripping
7/16" (11mm)
k Connect the breakout wires and operation mode selector cable, see "Connection of electrical
units" on page 50.
l To attach doors to Beam, see "Setting of Fast Leaves 1 (Full Break Out)" on page 33.
m To attach drive belt, see "Attachment /Adjustment of the Cable Tensioner/ Tooth Belt Fitting"
on page 36.
n To adjust Levelers and to attach anti-riser, see "Setting of Fast Leaves 1 (Full Break Out)" on page
33.
o To install Door Stops and make adjustments, see "Adjustment of the Leading Edge (to Avoid
Finger Traps)" on page 39.
p Once the doors are properly adjusted, adjust Break-Out Sensor in a manner that allows it to
sense the presences of the doors until doors are broke out. (This is accomplished by setting the
sensor so that it aligns with the magnetic strip in the door frame.)
q For sensor system connection, see "Connection of activation units" on page 51 to complete this
task.
r Secure cover and attach with screws. See "Installing/Removing the Cover" on page 45.
d Mount jambs to beam using five screws per jamb. (ASSA ABLOY Entrance Systems jambs are
factory prepared for Header installation.)
e Check that jamb and beam are aligned where indicated below.
f If the beam to jamb is not properly aligned, loosen the screws and align beam to jamb and
retighten screws.
Note: The header and jambs must be square and level to ensure a proper installation!
a Inspect the rough door opening, measuring from side to side and using a level, to find areas
where shims may be needed. Look for high spots in the floor, if there is a slight rise in the floor
at any point then the bottom of the jambs should be set level with the highest point of the floor,
with the header leveled across the opening. Also, check the floor in the break-out panel’s swing
area for being level. Any high spots will need to be considered when setting header height.
b Tilt header/jamb assembly up into rough opening in wall, being careful to pull power through
access hole in jamb.
c Start with one jamb. Loosely install the middle fastener, using a level on the outside of the frame
to plumb the jamb. Confirm that the header is level across the opening. Repeat for the opposing
jamb, loosely installing first the middle fastener, then the top and bottom. Return to the first
jamb and install the remaining top and bottom fasteners loosely.
d Starting with the top screws on both jambs, equally shim behind both jambs, leaving equal gaps
and centering the package in the door opening. Tighten the top fasteners. Use your level on the
inside of one jamb to determine shim requirements for the middle fastener, then shim and
tighten. Repeat for the bottom fastener. Shim and tighten the middle and bottom fasteners on
the other jamb in the same way. Check for jamb bowing with a straightedge and correct if
present.
e If the header and jambs are truly square, the top and bottom jamb-to-jamb measurements will
be identical and both diagonal measurements will be identical. If necessary, strings can be taped
from corner-to-corner on the outside of the jambs. The strings should cross in the center of the
door opening, slightly touching each other. If there is a gap between the strings or the strings
are pushing against each other, than the package is twisted and needs adjusting.
Note: It is important that the floor guide track is installed level, to prevent derailment of the floor
guide foot when the door is swung out and to provide proper door operation.
a Inspect the floor for conditions such as high and low spots that can cause the track to twist and
rock. High spots (such as small rocks) should be removed; shim the track assembly at the low
spots.
b Using a chalk line, snap a reference line from jamb to jamb on the side where the track is being
installed.
c Using the measurements provided (see "Site Inspection" on page 18), lay the track in place.
While standing on the track and keeping it in line with the chalk line, mark the holes to be
drilled.
d Secure the track to the floor with concrete anchors and screws, leveling it with shims from end
to end. If possible, a sealant should be used under the track assembly. To check for proper lev-
eling, measure from the top of the track to the bottom of the header, checking for the same
result at each fastener.
Note: All screws must be countersunk and fully tightened to avoid interference with guide
travel.
Note: Remove any glass stop or packing material from the sidelite before installation.
a End load the sidelite panel on the roller track guide. Depress the spring loaded pins located at
each end of the top door rail and guide into the mating holes located in the beam. Slide the
panel against the jamb, leaving 1/8" (3mm) gap. Check panel to ensure that both pins have en-
gaged into the header.
b For bi-part, install 2nd sidelite as above.
15. g Set the anti-risers on each carriage wheel to the “lock” position.
Note: Remove any glass stop or packing material from the sidelite before installation.
a Install and level any thresholds (surface or recessed) before installing any of the door panels.
b Check that jamb mounted bottom pivot is installed and tight. Also make sure that the pivot
plate is also secured to the floor.
c If the pivot base does not rest fully on the floor, support the pivot base with shims.
d Place the bearing washer on the pivot base.
e Set the sidelite on the pivot and tilt it into place. (There should be no more than 1/8" between
the bottom of the header and the top of the sidelite.)
f To adjust, raise or lower the bottom pivot by loosening the set screw at the side of the floor
portion of the pivot and turn the shaft clockwise to lower the sidelite and counter clockwise to
raise the sidelite; then retighten the set screw.
g With the sidelite on the bottom pivot, carefully push down the top spring-loaded pivot pin and
line it up with its receiving hole in the header portion of the pivot until the shaft pops into place.
h Check all clearances and adjust the Break-Out Latch (See "Adjusting Ball Catch" section on page
41 and "Adjusting Magnetic Catch (Option)" section on page 42).
i If the distance between the jamb and hinge stile needs to be adjusted, loosen the top and/or
bottom door portion pivot and slide left or right. Once adjusted properly, retighten screws.
j When all sidelite panels are installed, tighten top pivot security set screw to prevent depressing
(carding) pivot pin.
24. Slowly and carefully swing the door closed taking care not to damage the flooring or
threshold, adjusting horizontally such that the magnetic catch engages into the magnetic
catch
24. Slowly receiver.
and carefully swing the door closed taking care not to damage the flooring or
threshold,
25. Make sure i the
adjusting
that Slowly and carefully
horizontally
lead edge such
of thatswing
the door the thelead
door
and magnetic
the closed
catch
edge thetaking
of engages care
carrierinto not
the
is flush, to damage the flooring or threshold,
magnetic
adjusting
catch receiver. adjusting horizontally
the magnetic catch location if necessary. such that the magnetic catch engages into the magnetic catch receiver.
25. Make surethe
26. Open that the
door lead
j and edge
lock
Install down
end ofcap
theto
the door
#1 and
screw
lead the of
lead
(pivoting
edge edge
set of the
screw)
carrier. carrier
of the PSA is flush,
arm and adjusting
loosen
setscrews catch
the magnetic #3 & #4.
location if necessary.
27. Carefully k Make sure that the lead edge of the door and the lead edge of the carrier is flush, adjusting the
attempt to close thethe
door. You will(pivoting
notice that
26. Open the door and lock down #1 screw setthe door needs
screw) of the to be adjusted
PSA arm and loosen
vertically
setscrews #4. magnetic
#3so& that the magneticcatch
catchlocation if necessary.
can engage into the magnetic catch receiver without
obstruction.
27. Carefully attemptl toOpen
close the door You
the door. and lock downthat
will notice thethe
screw
door(1) (pivoting
needs set screw) of the PSA arm and loosen
to be adjusted
28. Adjust the #2 screw (PSA vertical adjustment screw) on the PSA arm to lift the lead edge of
vertically so that thesetscrews
magnetic (3) and
catch (4).
can engage into the magnetic catch receiver without
the door and magnetic catch. Note, if the has not been previously installed you will need to
obstruction.
recheck alignment once glass is in place and readjust as necessary.
m Carefully attempt to close the door. You will notice that the door needs to be adjusted vertically
28. Adjust the #2 screwso
(PSA
thatvertical adjustment
the magnetic screw)
catch on the PSA
can engage intoarm
the to lift the lead
magnetic edge
catch of
receiver without obstruction.
the door and magnetic catch. Note, if the has not been previously installed you will need to
n once
recheck alignment Adjust the is
glass screw (2) and
in place (PSAreadjust
verticalas
adjustment
necessary.screw) on the PSA arm to lift the lead edge of the
door and magnetic catch. Note, if the has not been previously installed you will need to recheck
alignment once glass is in place and readjust as necessary.
o Once adjustment is complete, tighten the remaining setscrews (3) and (4) on the PSA arm and
close the door engaging the magnetic catch. Confirm that the lead edge of the door and lead
edge of the carriers are still flush.
h Position
22. Position the t-block thethe
underneath t-block
pivot underneath
pin. the pivot pin.
i key,
23. Using a 3mm hex Using a 3 mm
loosen hexscrew
the set key, loosen the set
in the pivot pin screw in the
assembly pivot pin
to release theassembly
pivot pin.to release the pivot pin.
24. Slowly and carefully swing the door closed taking care not to damage the flooring or
Anti-Riser
threshold, adjusting Operation
horizontally such that the magnetic catch engages into the magnetic
catch receiver.
a To lock the anti-riser, depress both tabs and push until it engages on the wheel bracket.
25. Make sure that the lead edge of the door and the lead edge of the carrier is flush, adjusting
b To
the magnetic catch unlock
location anti-riser, depress both tabs and pull.
if necessary.
26. Open the door and Note:
lock down
Slowthe #12screw
leaf has caps (pivoting set screw)
that need to be of the PSAon
removed arm and loosen
carrier in order to access the anti-risers.
setscrews #3 & #4.
27. Carefully attemptSetting thethe
to close Active
door.Leaf
YouPin Guide
will Pivot
notice that(Full Break-Out)
the door needs to be adjusted
vertically so that the magnetic catch can engage into the magnetic catch receiver without
obstruction. Note: Before installing the active leaves, make the electrical connections in "Electrical connections"
on page 46. Do not apply mains power.
28. Adjust the #2 screw (PSA vertical adjustment screw) on the PSA arm to lift the lead edge of
the door and magnetic
Spring catch.
tensionNote,
has ifbeen
the has not been
factory previously
adjusted; it mayinstalled you will
be changed toneed to that pin stays engaged in
ensure
recheck alignment once glass is in place and readjust as necessary.
track. Readjustment requires removing the pivot from the door and adjusting the threaded slug.
For additional security, the pin guide may be locked at its highest point of travel along the floor
track, using the setscrew.
Note: If this option is selected, then you must level the floor track in order for the pin to stay com-
pletely engaged.
Height Adjustment
The height adjustment is to be carried out with the vertical adjustment screw as described in section
titled, "Setting of Fast Leaves 1 (Full Break Out)" on page 33.
• It is very important that the door leaf hangs vertically after the adjustment and that bi-parting
doors are parallel in the closed position (no gap at the top or bottom).
• The guide pin roller (frame doors) should not touch the upper edge of the door guide track or
become easily disengaged.
• If a weather brush is used on the lower edge of the door leaf, it should only lightly touch the
floor.
• Check that the door leaf is parallel with the fixed panel.
FFL
1/4” (6.4mm)
Note: Once the door height is adjusted, verify that doors do not exceed a force of 30 pounds applied
in either direction to prevent the door from closing.
Can use 10 mm nut driver or 6 mm hex key to adjust door height.
Fast leaf 1needs to be adjusted equal or below slow leaf 2.
e Orient the belt clamp on the belt such that it is centered on the upper transmission bracket
and slide onto the belt.
f Slide the belt clamp into the upper transmission bracket until it snaps in and is secured. It may
be necessary to slightly move the centerline slightly to the right or to the left to find the most
optimal position for the belt clamp.
g Loosen hex screw on left telescopic cable tensioner bracket in order to add slack to cable using
adjustable hex screw.
Adjustment
screw
Hex screw
Telescopic cable tensioner kit Cable loop
Telescopic
h Remove screws on left hand fast leaf 1 door telescopic pulley bracket and remove front piece
of bracket. Take slack cable and thread through front part of bracket. Re-install front piece of
bracket and re-tighten screws on bracket to hold cable.
Telescopic pulley
bracket
Cable loop
i Tighten cable using adjustable hex screw on cable tension bracket until the cable is tight and
has no slack.
j Re-tighten the hex screw on tensioner bracket.
k Loosen hex screw on right telescopic cable tensioner bracket in order to add slack to cable using
adjustable hex screw.
l Remove screws on right hand fast leaf 1 door telescopic pulley bracket and remove front piece
of bracket. Take slack cable and thread through front part of bracket. Re-install front piece of
bracket and re-tighten screws on bracket to hold cable.
m Tighten cable using adjustable hex screw on cable tension bracket.
n Re-tighten the hex screw on tensioner bracket.
o Check door panels for proper centering in the fully closed and opened positions.
Single-sliding operators
a Put all doors in fully closed position.
b Move the upper/lower transmission bracket that is factory installed to the belt until it is over
the carriage wheel fitting of the fast leaf 1 door. For RH FBO/LH FSL (SA), the bracket will attach
to carriage wheel on the leading edge of door leaf. For LH FBO/RH FSL (SA), the bracket will attach
to the trailing edge of the door leaf.
c Attach the tooth belt fitting to the carriage wheel fitting using the enclosed screws.
d Loosen hex screw on telescopic cable tensioner bracket in order to add slack to cable using
adjustable hex screw.
e Remove screws on fast leaf 1 door telescopic pulley bracket and remove front piece of bracket.
Take slack cable and thread through front part of bracket. Re-install front piece of bracket and
re-tighten screws on bracket to hold cable.
f Tighten cable using adjustable hex screw on cable tension bracket until the cable is tight and
has no slack.
g Re-tighten the hex screw on tensioner bracket.
h Check door panels for fully closed and opened positions.
3
2 1
1 Belt Wheel
2 Adjustment Screw
3 Washer
Magnet
Tension Adjustment
Sidelite
Fast Leaf Ball Catch
Ball Catch
Slow Leaf
Magnetic
Catch
Note: FSL (Fixed Sidelites) utilize break out beams mounted on the jambs. See Break Out/Safety –
Hold Beam Connection Diagram on page 59.
switch in the sidelite.
Gap between door-header/door-carrier should not exceed 1/8” gap in order for magnetic catch
to function properly.
Loosen screws shown to adjust magnets. Only loosen screws 2-3 turns each with a 4MM allen
key. Use plastic shim to adjust magnet away from clapper plate. Place plastic shim in center of
each magnet and tap shim in order to move magnet.
c Verify that plates that hold magnets are aligned so each contacts clapper plate at same time
while re-tightening screws. Tension of magnetic catch should be able to be adjusted down to
approx. 30 lbs.
Approx. 50 lbs.
Approx. 30 lbs.
Note: If the glass has not previously been installed, you will need to recheck alignment once
the glass is in place and readjust as necessary.
c Once the adjustment is complete, tighten remaining setscrews (3) and (4) on PSA arm and
close the door engaging the ball catch.
d Confirm that the lead edge of the door and lead edge of the carriers are still flush.
In all instances, where work is being done, the area is to be secured from
pedestrian traffic, and the power removed to prevent injury.
Cover latching can be achieved when the cover is in the full open position by pressing the cover
toward the unit. (Usually when opening the cover, it will latch with little effort, making it appear
to be an automatic function.)
To unlatch the cover, lift slightly, pull and the cover will rotate downward, thereby allowing it to
close.
To secure the cover, unlatch and close, then tighten the screws located in each end and/or the
center, ensuring that they fall in the slots on the cover latches.
To fully remove the cover, start by uninstalling each detachment guard. Next, disconnect wiring
coming from the sensors. Lift cover off of the hinge on the beam.
To install the cover, center the cover on the beam and mate the hinge portion of the cover to the
beam. Install the detachment guards equally spaced down the length of the beam. Re-connect any
wires that were disconnected.
Close and secure cover with screws, as shown below.
Detachment
Guards
Hinge Screw
9 Electrical connections
9.1 Installation
a Open the cover, see page 45.
b Install but do not connect activation units, presence sensors and accessories.
c Install and connect the mains cables, see page 47.
d Carry out Start-up, see page 60.
Installer must properly ground door package! Improper grounding can lead to
to risk of personal injury.
1
13
5
6
The main control unit has the connection for power supply, drive unit, operation mode selector,
activation units, electromechanical lock and batteries. Activation units can be connected with
connectors directly to the main control unit or via terminal blocks. An installer interface with a two
digit display and four push buttons is used for function selection, adjustments and for troubleshoot-
ing. See page 60 for details.
For extra functionality like Close impulse, Nurse impulse, Open/Close impulse, Emergency open
impulse (fireman’s opening), connection of optional operation mode selector and fire alarm an
I/O unit is used. This unit has also a relay output for external error or status indication, maximum
15W, 42VAC / 30 VDC (SELV), resistive load only.
(-) 0 V DC (COM)
(-) 0 V DC (COM)
(-) 0 V DC (COM)
(-) 0 V DC (COM)
Push Break-out
Plate Switch (NO)
(+) 24 V DC
(+) 24 V DC
(+) 24 V DC
(+) 24 V DC
(-) 0 V DC
(-) 0 V DC
(-) 0 V DC
(-) 0 V DC
Inner
15 16 17 15 15 16 17 15 15 16
Impulse
Outer
1 5 7 1 1 5 7 1 1 5
Impulse
Presence
15 9 14 8 8 9
Impulse 1
Presence
1 5* 11 14 8 8 11
Impulse 2
Key Impulse
8 12
Emergency Open
Side Presence
7 1 1 2
Impulse 1
Side Presence
7 1 1 4
Impulse 2
Stop
1 3
Impulse
* One-way Traffic-Side, not intended for use, must have a jumper in place
between Motion Signal Output (5) and Presence Impulse Input (11)
a Orient clips as shown and either snap or slide onto the cover.
Wire
Graphics for c.
d Locate a clip as shown spaced approximately ¼” (6mm) away from the end cover latch and run
the wire between this clip and the cover latch to the beam.
Graphics for d.
e Once the wire is ran into the beam, zip tie the wire to the jamb mounting plate as shown-
through both the small, upper hole on the backside of the 7/8” (22mm) main power hole and
the cutout.
Upper Hole
Sensor Wire
Zip Tie
Cut Out
f Run the sensor wire to the main control along the back wall of the beam using the factory in-
stalled rectangular plastic cable holders.
g Close and open the cover and ensure that the wire does not come into the path of any moving
parts. p48 graphic for e
MCU #1 MCU #2
Interconnection of operators
Issue 2013-06-27
interconnected operators interconnected operators
in common in common if Master is in Auto
1010767-US-1.0
9 Electrical connections
One or two operation mode selectors can be used. When having two operation mode selectors,
one will be a Master and will override the other, called Slave. While the Master is in AUTO the mode
selection can be made from the Slave. A Slave mode selector has a cut jumper. See illustration below.
The operation mode selector(s) can also be remotely controlled from e.g. a timer or an optional
operation mode selector. IOU required. The standard operation mode selector(s) will not indicate
the new selection made from the remote timer or operation mode selector.
Remove
With 5 buttons OPEN, AUTO PARTIAL, AUTO, ONE WAY and OFF functions can be obtained.
Text Function
OPEN The door is permanently open. The door can be
moved by hand e.g. for window cleaning. All activa-
tion units except for the emergency push button
(if fitted) are disconnected.
AUTO Two-way traffic, normal operation of the door. The
door can be opened with the inner and outer acti-
vation units and with a key switch/emergency push-
button (if fitted).
CLOSED This function is only used on emergency escape
doors after it is certain that all people have left the
building.
The door cannot be opened with inner and outer
activation units. The door is locked if an electrome-
chanical locking device has been fitted. The door
can be opened partially with a key switch (if fitted).
With an emergency push button (if fitted) the door
opens fully. The door can also be opened partially
from the operation mode selector if the arrow down
button is held for 2 seconds. No access code is
necessary for this and the key impulse is indicated
by briefly showing a blue light to the left of the open
on site
symbol or text and then a flashing blue light to the
ftware MS BwL 1007926
RING HARNESS MS BASIC RJ45 CABLE 1008972 *
left of the closed symbol or text for another 15
B Assembly Mode Selector Basic with LED 1008140 seconds.
cker 40x80 3 position 1008152 *
flush mounted MS 1008773
RESET By briefly pushing the globe of the logotype the
REW ISO 7049 C (RTS) ST2.9x16 FZB 4.8 724462 * door operator will make a RESET function with a
AME 40x80 Flush 1008102
system test, the door will return to the closed posi-
scription Art.no. Remark
Material Remark tion (if not in operation mode selection OPEN or if
an error is present) and is then ready for normal
Proj. method Scale Drawn Date Status operation.
1:1 ASE Approved
Description Rev. Size Sheet
Mode selector Basic with LED 3 POS SW 1.0 A3 1 (1)
Drawing No.
1008179
ystems AB
11 Start-Up
After installing the operator, the Start-up and adjustment must be carried out in the following order
(see also "Electrical connections" on page 46).
a Set the Program Selector to the “AUTO” position. With all accessories such as well adjusted
sensors and breakout switches connected, connect the main power plug to the control unit. If
the door is open and no opening or presence impulse is active, it will move to the closed position
with low speed.
b Push the Learn button, LB for 2 seconds to initiate a learn cycle. The display is flashing letter L.
See detailed description on next page.
c To check the door movement, give opening impulse by shorting the terminals speeds on the
main control unit (MCU).
d If necessary adjust the door speed parameters to the required speeds.
e Check that the installation complies with valid regulations and requirements from the authorities.
UP
SELECT
LEARN/
EXIT
DOWN
'on' = operation OK
E1 = flashing letter E followed by a digit is displaying an active error (0-9) and this digit is showing
the coarse type of error. It is alternating between this coarse error and a second two digit number
specifying the error.
If several errors are present they will be displayed in sequence.
Errors can be cleared by a RESET from the operation mode selector or by turning off and back on
the mains power. For a detailed description of errors, see "Troubleshooting" on page 71.
To the right of the display there are four push buttons, to the left a Learn/Exit button, to the right
a Select button, one Up and one Down button.
The Learn function can be of three different types.
• By pushing the Learn/Exit for one second each connected electronic module, including the op-
eration mode selector will be recognized.
• By pushing the Learn/Exit for two seconds the display will flash L and when the button is released
a complete Learn cycle will start. The main power supply type is also detected. The door will
first close, start to open a short distance and close again. It will sense if an electromechanical
lock is installed and also find out of which type it is. It will then open the door and during the
opening it will calculate the friction in the system. It will stop in the fully open position and
register the clear opening width. It will also register connected sensors and can judge whether
they are monitored or not. After a 4-10 seconds delay it will close again. During the closing it
will automatically calculate the door weight and adjust the speed accordingly.
Some parameters, like whether the door is biparting or single sliding, cannot be determined
automatically and have to be altered by the installer. If manual intervention is needed, the door
will reopen and the Learn will end with the display alternating between P and two digits repre-
senting the parameter(s) that must be altered manually. By pushing the right Select button
once you will enter this parameter and by pushing the Select button once again the value of
this parameter will be shown while flashing. By pushing the Up or Down buttons you can step
up or down the value within the allowed range. To confirm the selected value, push the right
Select button again. When all values are right, push the Learn/Exit button for 2 seconds and the
display will show 'on'. After a two seconds delay the door will close and is ready for operation
or for further adjustments.
• By pushing the Learn/Exit for ten seconds the operator will return to the default factory set pa-
rameters. While pushing, the display will flash L and when 'on' is displayed it indicates that you
have returned to the default parameters.
When pushing the right Select button the first time, each of the two display windows will make a
rotating test pattern. Verify that all seven segments of the two display windows will be lit during
the test. Otherwise there is a risk that you can misjudge the digits shown in a defective display.
When the display test is finalized the display will show two steady digits representing a parameter.
By pushing the up or down buttons you can step up or down to be able to select the parameter
you want to adjust. By pushing the right Select button again you will be able to read out the present
value of the parameter you have selected. It is shown as two flashing digits and can be adjusted
within an allowed range, by pushing the Up or Down buttons. When the proper value is selected
you push the right Select button again.
If you do not want to alter a new value you can always return to normal operation 'on' by pushing
the left Exit button. If you wait ten seconds without pushing any button you will also return to
normal operation 'on'.
Note: Some of the parameters below are not accessible, depending of different options installed.
For further explanations of parameters below marked with *, see 11.2.
Main control unit (MCU) parameters
Param. Description Range De-
ID fault
value
00 High Speed Opening 0.33- 2.30 ft/s 2.3
(10-70 cm/sec) (70)
01* Low Speed 0.16-2.30 ft/s 2.3
(05-70 cm/sec) (70)
02 High Speed Closing 0.33-2.30 ft/s 0.43
(10-70 cm/sec) (13)
03 Hold Open Time 00-60 sec 20
04 Key Hold Open Time 00-60 sec 70
05 Lock Configuration (main control). No lock(00) / LDP(01) / LD(02) 00-02 00
06* Lock Release. Off(00) / On(01) 00-01 00
07* Presence Input 1 Configuration (main control). NO(00) / NC(01) 00-01 00
08* Presence Input 2 Configuration (main control). NO(00) / NC(01) 00-01 00
09* Presence Impulse Monitoring 00-02 units 00
10* Emergency Unit Monitoring. Off(00) / On(01) 00-01 00
11 Partial Open Position 00-99 % 70
12 Opening Direction. CW(00) / CCW(01) 00-01 00
13* Hold Force 0.0-13.5 lbf (00-60 N) 0.0
(00)
14* Group / Parameter Set 00-99 00
15 Run Program. Smooth (01) to max performance (05) 01-05 05
20 Partial Hold Open Time 00-60 sec 02
21 Push & Go Hold Open Time 00-60 sec 02
22* Auto Width Activation Time 00-60 sec 10
23* Auto Width Resume Time 00-60 sec 10
24* Jam Hold Time 00-10 sec 02
25* Interlock Disable Time 00-60 sec 00
26* Presence Hold Open Time 00-60 sec 02
27 Side Presence Input 1 Configuration. NO(00) / NC(01) 00-01 00
28 Side Presence Input 2 Configuration. NO(00) / NC(01) 00-01 00
29* Side Presence Impulse Monitoring 00-02 units 00
30* Side Presence Activation Distance 0.0-32.5 ft (00-99 dm) 0.0
(00)
31* Sensor Type. 1-wire(00) / 2-wire(01) monitoring 00-01 01
32* Active Brake on Stop. Off(00) / On(01) 00-01 01
33 Push & Go in EXIT Mode Selection. Off(00) / On(01) 00-01 01
34 Hold Force in EXIT and OFF Mode Selection. Off(00) / On(01) 00-01 00
35* Toggle Operation Mode Selector after Stop. Off(00) / On(01) 00-01 01
Note: Some of the parameters below are not accessible, depending of different options installed.
For further explanations of parameters below marked with *, see 11.2.
Main control unit (MCU) parameters
Param. Description Range De-
ID fault
value
36* Emergency Action. Closing(00) / Opening(01) 00-01 01
37* Emergency Action in OFF Mode. Off(00) / On(01) 00-01 00
38* Convenience Battery. Off(00) / On(01) 00-01 00
39* Battery Wake-up. Open(00) / Open/Close(01) 00-01 00
40* Emergency Unit Test Interval 04-23 hours 04
41 Battery Type. No battery(00) / 12V(01) / 24V(02) 00-02 00
42* Remain Locked at Stop. Off(00) / On(01) 00-01 01
43* Opening Delay for Lock 00-99 sec x 0.1 00
44* Exit Lock. Off(00) / On(01) 00-01 01
45* Stop Function. Off(00) / On(01) 00-01 01
46* Stop Configuration. NO(00) / NC(01) 00-01 00
47* C-Switch Configuration. NO(00) / NC(01) 00-01 01
48* C-Switch Activation Distance 0.0-32.5 ft (00-99 dm) 0.33
(01)
49* Opening Max Force 4.5-42.7 lbf 33.7
(02-19 N x10) (15)
50* Closing Max Force 4.5-42.7 lbf 29.2
(02-19 N x10) (13)
51* Push & Close. Off(00) / On(01) 00-01 00
52* Push & Close Timeout 00-99 sec x10 60
53* Operator Type. Normal(00) / PCD(01) 00-01 00
54* Service Needed Operating Hours 00-60 h x1000 00
55* Service Needed Opening Cycles 00-50 cycles x100.000 00
56* Service Needed Locking Cycles 00-50 cycles x10.000 00
57 Low Speed Distance, Opening 0.0-39.9 inch (00-99 cm) 3.9
(10)
58 Low Speed Distance, Closing 0.0-39.9 inch (00-99 cm) 3.9
(10)
59* Open Position 0.0-32.5 ft (00-99 dm) 9.8
(30)
60* Learn. Off(00) / On(01) 00-01 01
61* Auto Width. Off(00) / On(01) 00-01 01
62* Partial Function. Opened(00) / Closed(01) 00-01 00
63* Partial Closed Position 0.0-11.8 inch (00-30 cm) 11.8
(30)
64 Power Supply Type. 65 W(00) / 150 W(01) 00-01 01
65* Sustainable Drive Mode. Off(00) / On(01) 00-01 00
Note: Some of the parameters below are not accessible, depending of different options installed.
For further explanations of parameters below marked with *, see 11.2.
Main control unit (MCU) parameters
Param. Description Range De-
ID fault
value
66 Stop Impulse Monitoring. Off(00) / On(01) 00-01 00
67 Door Type. Single sliding(00) / Biparting(01) 00-01 00
68* Door Weight 22-882 lbs (01-40 kg x10) 882
(40)
69 Friction 0.0-22.3 lbf (00-99 N) 0.0
(00)
6A Interlock Function. Off(00) / On(01) 00-01 00
6b Synchronizing Function. Off(00) / On(01) 00-01 00
6c* External Bus Device ID 2 01-99 01
6d* Extended Hold Open Time Function. Off(00) / On(01) 00-01 00
70 Motor Type. Normal Duty(00) / Heavy Duty(01) 00-01 01
71 Max Motor Power 03-15 W x10 15
80 Operation Mode Selector Variant, Basic Master. 00-04 04
Unspecified(00) / 3 buttons with AUTO(01) / 3 buttons with EXIT(02) / 4
buttons(03) / 5 buttons(04)
81 Operation Mode Selector Key Lock, Basic Master. Off(00) / Hold for two 00-02 00
sec(01) / Four pushes(02)
82 Operation Mode Selector Service Indication, Basic Master. Off(00) / On(01) 00-01 01
85 Operation Mode Selector Variant, Basic Slave. 00-04 04
Unspecified(00) / 3 buttons with AUTO(01) / 3 buttons with EXIT(02) / 4
buttons(03) / 5 buttons(04)
86 Operation Mode Selector Key Lock, Basic Slave. Off(00) / Hold for two 00-02 00
sec(01) / Four pushes(02)
87 Operation Mode Selector Service Indication, Basic Slave. Off(00) / On(01) 00-01 01
Note: Some of the parameters below are not accessible, depending of different options installed.
For further explanations of parameters below marked with *, see 66.
I/O Unit (IOU) parameters
Param. Description Range De-
ID fault
value
90* Nurse Function (I/O unit). Off(00) / On(01) 00-01 00
91* Open/Close Function (I/O unit). Off(00) / On(01) 00-01 01
92* Open/Close Timeout 00-60 min 00
93* Close Function (I/O unit). Off(00) / On(01) 00-01 01
94* Fire Impulse Function (I/O unit). Off(00) / On(01) 00-01 00
95* Emergency Open Impulse Function (I/O unit). Off(00) / On(01) 00-01 01
96* Emergency Button Configuration. NO(00) / NC(01) 00-01 00
97* Operation Mode Selector Function (I/O unit). Off(00) / On(01) 00-01 01
98* Lock Configuration (I/O unit). No lock(00) / LDB(01) / LDE(02) 00-02 00
CT Name Description
01 Low Speed The low speed is self adjusting to optimal operation if this parameter is set to
max. Depending on authority or installation requirements the low speed, low
speed distance opening and/or closing can be further reduced.
06 Lock Release If “Lock Release” is On, the door will apply force in the closing direction when
the lock is unlocked. This is made to prevent a lock from being stuck in locked
position when opening. Should be set to On when an electromechanical lock
is installed.
07, 08 Presence This parameter determines if a presence impulse is normally open (NO) or
Input Configura- normally closed (NC). The “Presence Impulse 1 and 2 Configuration” selected
tion with the function selector applies also to “Stop Configuration”.
09 Presence Im- Set to “00” if no monitoring of Presence impulse sensors is required or if no
pulse Monitoring presence impulse sensors are installed. Set to “01” if one Presence impulse
sensor that shall be monitored is installed (Presence impulse 1). Set to “02”
if two Presence impulse sensors that shall be monitored are installed (Presence
impulse 1 and 2).
10 Emergency The emergency unit will be tested by opening the door with the emergency
Unit Monitoring unit. The test is never done in program selection Open and also normally not
in Off, unless parameter 37 “Emergency Action In OFF Mode”, see below, is set
to On.
Authorities can demand that the emergency unit is monitored on a regular
basis, see parameter 40 “Emergency Unit Test Interval” below. Half an hour
before this time has elapsed, a ghost impulse will initiate the emergency unit
test.
The test is also always performed after a Reset and after changing program
selection from a position where a test is not done to a position where the test
is a demand.
13 Hold Force Adjustment of the force used to keep the door in closed position.
14 Group / Param- Preprogrammed parameter sets suitable for specific conditions.
eter Set
22 Auto Width If “Auto Width” is chosen this time determines when the door shall open from
Activation Time partial open width to full open width.
23 Auto Width Re- This parameter determines how long time that has to elapse before a new
sume Time opening impulse does not open the door to full open width instead of partial
open width after an Auto Width opening has been performed.
24 Jam Hold Time Sets how long time the door shall be stopped when a jam is detected during
opening and the time until the door can restart after a stop impulse.
25 Interlock Dis- This parameter controls the time the interlock input can prevent the actual
able Time door from opening. The time starts to count down at the moment a valid
opening impulse is activated, and the door is opened when the interlock input
is not active or the timer has elapsed. If the time is set to 00 the timer will not
elapse, which means that the door will stay interlocked as long as the interlock
input is active.
26 Presence Hold The time the door is held open before closing after having reversed on a
Open Time Presence impulse.
29 Side Presence This parameter is specifying how many presence sensors that shall be moni-
Impulse Monitor- tored. 00 = none, 01 = Presence impulse 1 only and 02 = Presence impulse 1
ing and 2.
CT Name Description
30 Side Presence If value 00 is selected an activated side presence impulse will slow down the
Activation Dis- entire door opening, from fully closed to fully open.
tance If a value in the range 00-99 dm is selected, an activated side presence impulse
will only slow down an opening door when the door leaf is within the config-
ured distance from the fully open position
31 Sensor Type Selection of sensor type. Choose between 1-wire (00) or 2-wire (01) monitor-
ing. 2-wire monitoring is default.
32 Active Brake on In selection Off (00) the operator is freewheeling to stop after a Stop impulse.
Stop In selection On (01) the operator will make an active brake during 1 second
after a Stop impulse.
35 Toggle Opera- The operator will stay in the present position after a Stop impulse in operation
tion Mode Selec- mode selection Off if this parameter is On (01) and will not move until the
tor after Stop operation mode selector is turned to another selection. In parameter setting
Off (00) the door will automatically close when the Stop impulse is restored.
36 Emergency Ac- Fire closing (00) or Emergency opening (01) with EEU battery power in case
tion of a mains power failure.
37 Emergency Ac- Decides if “Emergency Action” shall be performed also in program selection
tion In OFF Mode Off.
38 Convenience When this parameter is set to On (01), with a 24V (UPS) battery the operator
Battery will continue its normal operation in case of mains power failure. Monitoring
is not possible.
39 Battery Wake This parameter controls how the door is acting on Key impulse or Battery
Up wake up in program selection Off and without mains power. The parameter
“Emergency Action In OFF Mode” must also be set to Off (00).
If “Battery Wakeup” is set to Open (00) the impulse is opening the door fully
and stop there.
If “Battery Wakeup” is set to Open/Close (01) and parameter “Emergency Ac-
tion” is set to Opening (01) the impulse is opening the door fully, remains
open for the time set by parameter “Key Hold Open Time” (04) and will then
close, lock and disconnect the battery
40 Emergency The time set in this parameter controls the maximum time until the next au-
Unit Test Interval tomatic test of the emergency unit is performed.
42 Remain Locked If this parameter is set to On (01) the locked door remains locked when a stop
at “Stop” impulse is activated.
43 Opening Delay The time the opening is delayed (0.0-9.9 sec) after an opening impulse is given
For Lock in the program selections Off and Exit.
44 Exit Lock This parameter controls the electro-mechanical lock in the program selector
setting Exit. If “Exit Lock” is set to On (01) the electromechanical lock is locked.
If set to Off (00) the electro-mechanical lock is not locked in Exit.
45 Stop Function When this parameter is set to On (01) the Stop impulse is enabled, otherwise
it is disabled.
46 Stop Configuration of the Stop impulse. Choose between normally open (NO) or
Configuration normally closed (NC) Stop impulse.
47 C-Switch Con- Configuration of “C-Switch” (electronic limit switch) output, NO (00) or NC
figuration (01).
48 C-Switch Activa- This parameter is the belt travel from the fully closed position where the
tion Distance electronic limit switch is changing its state.
49, 50 Max Force These parameters are limiting the tractive force in the transmission belt during
opening and closing respectively
CT Name Description
51 Push & Close When this parameter is set to On (01), the door will in operation mode selec-
tions Off or Exit, try to close the door with the force selected by parameter 50
“Closing Max Force” if someone tries to open it manually.
52 Push and Close If someone tries to open the door in operation mode selections Off or Exit for
Timeout the time set by this parameter the door will open when this times has elapsed.
00 = will continuously try to close.
53 Operator Type Always use setting 00.
54, 55, 56 Service When the selected value is reached the yellow light will flash every other
Needed second, indicating that maintenance is needed. Also parameters 82 and 87
are related.
59 Open Position Opening width of one door leaf (unit=dm). The parameter can be set manu-
ally, or it can be set automatically by performing a learn cycle.
60 Learn If this parameter is set to Off (00) the possibility to perform a learn cycle is
disabled.
61 Auto Width If this function is active (01) and the program selection Auto partial is selected
the door will open from partial open width to full open width if an opening
impulse has been active for the selected 22 “Auto Width Activation Time”.
62 Partial Function With this function the door can be selected to be partially opened or partially
closed (see below 63 “Partial Closed Position”).
63 Partial Closed “Partial closed position” (Auto airing function) can be obtained by selecting
Position “Partial Function” Closed (01). A fictive closed position of the door can be set
between 0-30 cm (0-0.98 ft) measured from the real closed position. The
program selector is to be set to Auto partial and the closed position of the
doors will then be the “Partial Closed Position” set.
65 Sustainable When selected the sensors are shut off in operation mode selection Off. The
Drive Mode electromechanical lock is not powered in operation mode selection Exit (only
in Off). The hold force used to keep an already closed door closed is minimized.
The acceleration and braking of the door is smoother. All are actions to lower
the power consumption.
68 Door Weight During an initial Learn the operator is sensing the weight of the door to be
able to adjust, acceleration, braking and speed profiles.
6c External Bus When two or more operators are interconnected with each other (e.g. using
Device ID 2 a common operation mode selector, interlocking, synchronizing etc.) this
parameter must be different in each operator.
6d Extended Hold When On, the operator hold open time is increased to prevent repeated re-
Open Time Func- opening of the closing door during heavy traffic.
tion
90 Nurse Function When this parameter is set to On (01) the Nurse impulse will give a pedestrian
partial opening in operation mode selections Exit, Auto and Auto partial. I/O
unit required.
91 Open / Close When this parameter is set to On (01) a single button toggling Open / Close
Function impulse is available. I/O unit required.
92 Open / Close The time set in this parameter controls when a door shall start closing auto-
Timeout matically if left open by an Open/Close impulse. 00 min = no automatic closing.
I/O unit required.
93 Close Function When this parameter is set to On (01) the security Close impulse is enabled.
This impulse will immediately close the door, even during opening, and remain
closed as long as the Close impulse is active. The electro-mechanical lock will
lock the closed door. If parameter “Inner Impulse Monitoring” is set to On the
Close impulse will be disabled to prevent unintended closing of an escape
route door. I/O unit required.
CT Name Description
94 Fire Impulse When On, an external alarm loop can be connected. An active alarm will per-
Function form the selected 36 Emergency Action (emergency open or fire close). I/O
unit required.
95 Emergency When On, an external Emergency open impulse (Fireman’s opening) can be
Open Function connected. An active impulse will always open the door (with electrical
emergency unit also during a mains power failure). I/O unit required.
96 Emergency Decides whether the Emergency open impulse used has NO or NC contact.
Button Configura- I/O unit required.
tion
97 Operation When On, a standard switch or timer can be connected to the different oper-
Mode Selector ation mode selection inputs of the I/O module. The Reset input is always active
Function (also when 97 is Off).
98 Lock Configura- Used to select special electromechanical locks only, bistable or espagnolette
tion type of locks. I/O unit required.
12 Signage
ANSI/BHMA standard 156.10 and Besam standards specify that caution signs must be affixed to
both sides of any power operated pedestrian door. With double doors, signs should be applied to
each door. Sliding doors with swinging (Break-out leaves) shall be provided with signs reading “IN
EMERGENCY PUSH TO OPEN”. The signs shall have red backgrounds with contrasting letters one-
inch high minimum. The signs shall read horizontally and be located adjacent to the lockstile on a
centerline 36 inches minimum and 60 inches maximum from the floor, applied to the side appro-
priate for egress. ANSI/BHMA A156.10. In addition, the sign “AUTOMATIC DOOR” with letters 1/2”
high minimum will be applied to the door, visible from both sides. If switch activated, use “AUTO-
MATIC DOOR - ACTIVATE SWITCH TO OPERATE”.
Note: The kit decals are double-sided and normally will only need to be applied to one side of a
clear glass door. If the decals are not clearly visible on the other side due to the condition of the
glass (e.g., tinted or textured glass), the decals should be placed on both sides.
ACTIVATE
SWITCH TO AUTOMATIC DOOR - STAND CLEAR
OPERATE
x2
AUTOMATIC
CAUTION IN EMERGENCY PUSH TO OPEN
DOOR
x2 x2 Clip arrow point on break-out pivot end.
AUTOMATIC AUTOMATIC
AUTOMATIC DOOR - STAND CLEAR CAUTION CAUTION AUTOMATIC DOOR - STAND CLEAR
DOOR DOOR
AAE923
Check that all required signage is applied and intact. Mandatory indicates that the signage is required
by European directives and equivalent national legislation outside the European Union.
13 Troubleshooting
Before starting the troubleshooting, check that the operation mode selector setting is correct and
then RESET the operator. Start the troubleshooting by checking the mechanical and electrical parts
of the operator in the following order.
The electromechanical parts are fixed in the support beam. To replace, the complete unit is to be
loosened and replaced.
UP
SELECT
LEARN/
EXIT
DOWN
'on' = operation OK
14 Maintenance/Service
Regular inspections should be made according to national regulations and product documentation
by a ASSA ABLOY Entrance Systems-trained and qualified technician. The number of service occasions
should be in accordance with national requirements and product documentation. This is especially
important when the installation concerns a fire-approved door or a door with an emergency
opening function.
a Remove dust and dirt from the operator. Dirt on the sliding track should be removed with
methylated spirits. If necessary replace the sliding track.
b None of the parts need lubrication.
c The tooth belt must be kept dry and clean. Check the belt tension.
d Check that all nuts and bolts are tightened well.
e Adjust, if necessary, the door leaf speed, the HOLD OPEN TIME and the door leaf position to
comply with valid regulations and requirements.
f Check that the function of emergency escape units always is operational.
g If an electromechanical lock, LDP (locked with power) or LDB (bi-stable), is installed check the
function as follows:
• Set the operation mode selector to EXIT. The door should open and close without any sound
from the lock.
• Set the operation mode selector to OFF. Make sure the door can not be opened by pulling
the door leaf in the opening direction.
• When the operation mode selector is set back to EXIT, two clicking sounds (LDB) or one
clicking sound (LDP) indicate that the lock is unlocked. The door should then open and close
without any sound from the lock.
15 Accessories
Your BesamSL500 T can be further improved with the following add-ons (please contact your local
Besam company for detailed description).
• Motion and presence sensors, see separate manuals or installation drawings.
• Operation mode selectors
Flush or surface mounted. Master and slave operation mode selectors, see page 55.
• Electrical locks
Locked with power LDP (Fail Safe) or locked without power LD (Fail Secure).
• Interlocking
Used between two operators when the first operator must close before the other one can open
(typical to reduce energy losses and not for security reasons). Interconnection cable required.
• Synchronization
Used between the operators of two single sliding doors, working together in very large openings.
Interconnection cable required.
• I/O functions:
- Fire alarm connection
Used to emergency open or fire close the door with mains power on.
- External error indication
Obtained if a lamp or a buzzer is connected.
- Open / Close function
A one button impulse, will alternate between Open and Close. The door will stand open
until next impulse or can after an adjustable time delay automatically start to close even if
a new impulse is not received.
- Nurse function
A pedestrian partial opening in operation mode selections Exit, Auto and Auto partial. The
Nurse impulse hold open time is adjustable.
- Night mode
Remotely put door into exit only via an automated system. Requires a NO contact.
Two basicTwo
Two guide systems are available:
a The standard
Two pin guide
Two
- Twoor Full Break Out) with guide track
(FBO,
- TheTwo
roller guide (FSL, or Fixed Sidelite) with fixed sidelite track
Twopin guide has several options for guide tracks, including:
b The FBO
- Two
Recessed track (flush with floor level)
Two
- Recessed threshold and surface threshold
See Installation
Two Requirements section for guide installation.
From American National Standard for power-operated pedestrian doors. Please refer to full standard
if necessary, obtainable through BHMA at (212) 661-4261. All figures referred to below can be
found in the full standard. Excerpts reprinted with BHMA permission.
8.3.2.3 If overhead presence sensors are installed on each side of the sliding door opening (See
Figure A-18C.):
(1) They shall not have an inactive area more than 5 in. extending out from the face of the door. If
the inactive area exceeds 3 in. from the face of the door, it shall have a minimum of two photo
electric beams on one side of the door, with the lower beam installed 6-28 in., and top beam 45-
55 in. from the floor; and
(2) The detection zone shall remain active from open to within 6 in. of closed.
(3) If beams are required they shall be installed within 3 in. from the centerline of the slide door
and remain active from fully open to within 6 in. of closed.
(4) The door shall remain fully open for 1.5 seconds minimum after loss of detection.
8.3.2.4 If photo electric beams are used on one side of the door and an overhead presence sensor
is installed on the opposite side of the sliding door opening (See Figure A-18D):
(1) A minimum of two photo electric beams shall be installed on one side of the door with the
lower beam installed 6-28 in. and top beam 45-55 in. from the floor; and
(2) The beams shall be installed within 3 in. from the centerline of the slide door; and
(3) The overhead presence sensor installed on the side opposite the beams shall not have an inactive
area more than 5 in. extending out from the face of the door; and
(4) The beams and overhead presence sensor must remain active from fully open to within 6 in. of
closed; and
(5) The door shall remain fully open for 2.5 seconds minimum after loss of detection.
8.3.3 Sliding doors used for one way traffic shall be provided with a secondary activating zone on
the side not intended for approach. The secondary activating zone shall extend a minimum of 24
in. from the face of the door and be effective to within 5 in. from the face of the door measured at
the center of the door opening. The zone shall have a minimum width equal to the width of the
clear opening measured at 8 inches perpendicular from the face of the closed door.
10. ENTRAPMENT PROTECTION
10.1 Sliding Doors
10.1.1 A sliding door shall be adjusted so that the closing speed is one foot per second maximum
per leaf to latch check for doors weighing up to and including 160 lbs (71 kg):
For doors weighing more than 160 lbs (71 kg):
V= √(161 / W) where:
V = Velocity in ftlsec
W = Weight of Door in lbs
10.1.2 Latch check shall occur for sliding doors at no less than 2 in. from the closed position of
each sliding door leaf.
10.1.3 A stopped sliding door shall not require more than 30 lbf (133 N), measured at the leading
edge, to prevent it from closing at any point in the closing cycle.
10.1.4 Sliding doors provided with a break away device shall require no more than a 50 lbf (222
N) applied 1 inch (25 mm) from the leading edge of the lock stile for the break out panel to open.
Break away devices (swinging panels) for doors that slide on the egress side of an opening shall be
equipped with a self closing device or interrupt automatic operation when used in the break out
mode. Break away devices incorporating swing out sidelites shall interrupt automatic operation
when used in the break out mode.
10.1.5 Sliding doors utilizing sensors or control mats shall remain fully open a minimum of 1.5
seconds after loss of detection, unless otherwise specified within this standard.
10.1 Entrapment Protection measures shall be taken under neutral air conditions.
11. Signage
For Signage, see full standard.