THALIA P

Controller for all 24V Bft swing gate operators


programming port

lcd display

expansion board port

board overview
control board wiring
70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85

Safety devices inputs

L N 10 11 14 15 20 21 22 23 24 25 26 27 28 29 40 41 42 43 44 45 50 51 52 60 61 62 63 64 65

Line voltage Motor power


120 V AC output Tr a v e l l i m i t s / 24V Command inputs
encoder inputs accessory
power

terminal blocks overview


Thalia Thalia
Motor
Type Operator Description Wire color terminals for terminals for
terminal
Motor 1 Motor 2

Motor + n/a Brown 10 14


Motor - n/a Blue 11 15
1 Eli 250 BT Limit common n/a White 41 41
Close limit n/a Brown 42 44
Open limit n/a Brown 43 45

Limit output 1 White 42 43


2 Phobos BT Motor + 2 Red 10 14
Motor - 3 Black 11 15

Limit output 1 White 42 43


3 Igea BT Motor + 2 Red 10 14
Motor - 3 Black 11 15

Motor + 1 Red 10 14
Motor - 2 Black 11 15
4 Lux BT 2B
Encoder Com 3 Green 41 41
Encoder Out 4 White 42 43

Motor + 1 Red 10 14
Motor - 2 Black 11 15
5 Lux G BT 2B
Encoder Com 3 Green 41 41
Encoder Out 4 White 42 43

Limit output n/a White 42 43


6 Sub BT Motor + n/a Red 10 14
Motor - n/a Black 11 15

motor connections
auxiliary outputs
TERMINAL NAME DEFAULT

20
24V LIGHT 24 V DC COURTESY LIGHT OUTPUT ( 25W MAX)
21
22 120V OUTPUT - COURTESY LIGHT. POWERED DURING AND FOR
AUX 1
23 90 SECONDS AFTER OPERATION

24 GATE OPEN INDICATOR – OPEN CONTACT – CLOSES WHEN


AUX 2
25 GATE IS NOT CLOSED. FLASHES DURING THE CLOSING CYCLE

26
AUX 3 RADIO RECEIVER 2ND CHANNEL OUTPUT (N.O.)
27
28 LOCK
12V DC OUTPUT FOR SOLENOID LOCK
29 OUTPUT

command inputs
TERMINAL NAME DEFAULT DESCRIPTION

60 COM COMMON
61 IC 1 START OPENS, STOPS AND CLOSES
62 IC 2 PED PARTIAL OPENING
63 COM COMMON
64 IC 3 OPEN OPEN ONLY COMMAND
65 IC 4 CLOSE CLOSE ONLY COMMAND

auxiliary outputs & command inputs


safety inputs
TERMINAL NAME DEFAULT DESCRIPTION

70 COM COMMON
71 STOP STOP STOP BUTTON INPUT
72 SAFE 1 PHOT OBSTRUCTION SENSOR INPUT – ALWAYS ACTIVE
73 FAULT 1 SUPERVISION CIRCUIT 1
74 SAFE 2 BAR SAFETY EDGE INPUT
75 FAULT 2 SUPERVISION CIRCUIT 2
76 COM COMMON
77 SAFE 3 PHOT OP OBSTRUCTION SENSOR – ACTIVE ONLY WHILE OPENING
78 FAULT 3 SUPERVISION CIRCUIT 3
79 SAFE 4 PHOT CL OBSTRUCTION SENSOR – ACTIVE ONLY WHILE CLOSING
80 FAULT 4 SUPERVISION CIRCUIT
81 COM COMMON
82 SAFE 5 PHOT OBSTRUCTION SENSOR INPUT – ALWAYS ACTIVE
83 FAULT 5 SUPERVISION CIRCUIT
84 SAFE 6 BAR SAFETY EDGE INPUT
85 FAULT 6 SUPERVISION CIRCUIT

safety inputs
quick start menu
PRESS THE [OK] BUTTON THE SCREEN WILL DISPLAY ...PRESS THE [-] BUTTON TO NEXT YOU SELECT THE TYPE
ONCE TO ENTER THE QUICK “LANG” (LANGUAGE)... SCROLL DOWN TO “ENG” OF MOTOR...
START MENU. (ENGLISH) AND THEN PRESS [OK]

TYPE
{PRESS}

PRESS THE [-] BUTTON TO STEP 1... ...2... ...3... ...4...


SCROLL DOWN...

THEN SELECT THE NUMBER OF “1” OR “2” AND PRESS [OK] NEXT, DETERMINE THE OPENING select “int” for pull-to-
MOTORS CONNECTED... DIRECTION... open, or, “ext” for push-to-
ELI 250 BT... open. Then press [ok]

PHOBOS BT...

...6... ...7... ...8... ...9...


IGEA BT...

LUX BT...

LUX G BT...

SUB BT...

...AND THEN PRESS THE [OK]


BUTTON ONCE YOU HAVE
SELECTED YOUR OPERATOR

...5...

quick start menu


The screen will then
scroll down using the [-] button and select your preset, “ar”, “sr”, “ac”, “sc” or “ind” based
display “preset”...
on the logic features on the table below.

logic presets AR SR AC SC IND


AUTOMATIC SEMI-AUTOMATIC AUTOMATIC SEMI-AUTOMATIC
INDUSTRIAL
RESIDENTIAL RESIDENTIAL COMMERCIAL COMMERCIAL

AUTOMATIC CLOSING TIMER x x


...10...
PRE-ALARM x x
[ok].
...then press [ok]. UNINTERRUPTED OPEN CYCLE x x
INSTANT REVERSE ON CLOSING x x
HOLD TO RUN x

...12... QUICK REMOTE PROGRAMMING x x x x

quick start menu


THE SCREEN WILL THEN READ “OPM1” (OPEN MOTOR 1) WILL ...then press [ok] IF 2 MOTORS WERE SELECTED, IF 2 MOTORS WERE SELECTED,
“LSW ADJUST” IF LUX OR LUX G BE DISPLAYED ON THE SCREEN to set the limit. “OPM2” WILL SHOW. PRESS “CLM2” (close motor 2) WILL
WAS SELECTED. [+] to bring the 2nd gate to SHOW. press the [-] button
the fully open position... to close the gate.
press the [+]
button until
the gate has if “ersw” is
reached it
displayed, you
open limit.
have EXCEEDED
THE OPERATOR
...13... ...14... LIMIT. ...15...
...15... press [ok] to set limit ...16... press [ok] to set limit ...17...

“clm1” (close motor 1) is THE SCREEN WILL READ “OK” . THE WORD “AUTOSET” WILL UPON PRESSING [OK], THE GATE NEXT, THE SCREEN WILL THEN
displayed. press the [-] PRESS [OK] TO CONTINUE.. SCROLL ACROSS THE SCREEN WILL OPEN AND CLOSE READ “MEM REMOTES”
button to bring the gate to AUTOMATICALLY 1 TO 3 TIMES
it's fully closed position

press [ok] to set limit


...18... ...19... ...20... ...21... ...22...

SIMULTANEOUSLY PRESS THE SCREEN WILL THEN READ THE SCREEN WILL DISPLAY PRESS [OK] TO FINISH
WHEN THE SCREEN READS
“HIDDEN BUTTON”... AND HOLD THE 2 BUTTONS “DESIRED BUTTON”. PRESS “OK” AND THE NUMBER OF THE SETUP
THE BUTTON YOU WANT TO REMOTE IN MEMORY. REPEAT THE
ON YOUR REMOTE UNTIL THE
OPERATE THE GATE WITH PROCESS FOR ADDITIONAL
SCREEN READS “RELEASE”
REMOTES

E
U'R
YO E!!!
N
DO
...23... ...24... ...25... ...26...

quick start menu


programming menu
The programming menu is navigated using the 3 buttons found on the
upper right corner of the control board, next to the LCD screen. The top
MAIN
button is the UP button. It is also used to increase displayed values in the PARAMETERS
MENU SUB-MENU
programming menu. The middle button is the DOWN button. It is also
used to decrease displayed values in the programming menu. The lower PARAMETERS OPEN DELAY TIME
button is the ENTER button.
Pressing the UP & DOWN button at the same time serves as the BACK
button LOGIC
SUB-MENU

LOGIC MOTOR TYPE CLS DELAY TIME

UP
BACK
DOWN

ENTER RADIO AUTO CLOSE AUTO CLS TIME

To enter the QUICK SETUP MENU, press the ENTER button once.
FAST CLS
To enter the MAIN MENU, press ENTER twice quickly.
To exit programming, press BACK (UP + DOWN) from the Main Menu.

menu navigation
MAIN PROGRAMMING MENU
MAIN SELECTION

PARAM > SUB-MENU – ADJUSTMENT OF ALL NUMERICAL VALUES (TIME, TORQUE & PERCENTAGES)

LOGIC > SUB-MENU – ADJUSTMENT AND/OR SELECTION OF ALL FEATURES AND BEHAVIOR LOGICS

RADIO > SUB-MENU – BUILT-IN 2 CHANNEL RECEIVER PROGRAMMING

DEFAULT Restores board to factory settings. No effect on RADIO

LANGUAGE > PROGRAMMING MENU LANGUAGE SELECTION

AUTOSET Operates motor(s) several times and automatically adjust its FORCE settings

L. SW ADJ Limit of travel adjustment. Only available with type 4 and 5 motors

STAT > BOARD INFORMATION AND DIAGNOSTICS

PASSWORD Password setting for wireless programmer

main programming menu overview


MAIN SELECTION DESCRIPTION DEFAULT RANGE
PARAM > OPEN DELAY TIME Motor 2 opening delay in seconds 1 0-10
CLS DELAY TIME Motor 1 closing delay in seconds 1 0-10
TCA Auto-close time adjustment in seconds 10 1-180
TRF. LGHT.CLR. T Traffic zone clear time adjustment in seconds 40 1-180
OP. DIST. SLOWD Slowdown starting distance from end of open travel expressed in percentage 10 0-50
CL. DIST. SLOWD Slowdown starting distance from end of close travel expressed in percentage 10 0-50
DIST. DECEL Slowdown starting distance from end of open and close travel expressed in percentage 15 0-50
OP. FORCE Percentage of opening force exerted over the AUTOSET value before obstruction is sensed 50 1-99
CLS. FORCE Percentage of closing force exerted over the AUTOSET value before obstruction is sensed 50 1-99
OP SPEED Motor opening speed expressed in percentage 99 15-99
CL SPEED Motor closing speed expressed in percentage 99 15-99
SLOW SPEED Slowdown speed expressed in percentage from maximum speed. 25 15-99

parameters sub-menu
MAIN SELECTION DESCRIPTION DEFAULT RANGE
LOGIC > MOTOR TYPE 1=Eli 250; 2=Phobos BT, 3=Igea BT; 4=Lux BT; 5=Lux G BT; 6=Sub BT 0 0-6
TCA Timer to Close Automatically. 0=OFF / 1=ON 0 0-1
FAST CLS. Closes when sensors are cleared. 0=OFF / 1=ON 0 0-1
STEP-BY-STEP MOVEMENT *
PRE-ALARM
Determines how the system reacts when a START command is received during operation
Gate running output (AUX value=6) closes 3 sec. before gate movement. 0=OFF / 1=ON
0
0
0-2
0-1
*
HOLD-TO-RUN Requires continuous OPEN or CLOSE command input for gate to operate. 0=OFF / 1=ON 0 0-2
IBL OPEN Ignores START input during the opening cycle. 0=OFF / 1=ON 0 0-1
IBL TCA Ignores the START input while counting down for automatic closing. 0=OFF / 1=ON 0 0-1
IBL CLOSE Ignores the START input during the closing cycle. 0=OFF / 1=ON 0 0-1
RAM BLOW C. OP Pushes gate against physical stop before opening 0 0-1
RAM BLOW C. CL Pushes gate against physical stop before closing 0 0-1
BLOC PERSIST Hourly push against physical stop 0 0-1
PRESS SWC Pushes gate against physical stop for .5 seconds after close limit has been reached. 0 0-1
ICE Continuos force learning on every operation. 0 0-1
1 MOT. ON Single Motor operation. 0= (2)motors; 1=(1)motor. 0 0-1
OPEN IN OTHER DIRECT. 0 = Pull to open; 1 = Push to open 0 0-1
SAFE 1 * Configuration of safety input terminal 72. Defaulted as Phot (Obstruction) 0 0-8
*
SAFE 2 * Configuration of safety input terminal 74. Defaulted as Bar(Safety Edge) 6 0-8
*
SAFE 3 * Configuration of safety input terminal 77. Defaulted as Phot Op (Opening Obstruction) 2 0-8
*
SAFE 4 * Configuration of safety input terminal 79. Defaulted as Phot Cl (Closing Obstruction) 4 0-8
*
SAFE 5 * Configuration of safety input terminal 82. Defaulted as Phot (Obstruction) 0 0-8
*
SAFE 6 * Configuration of safety input terminal 84. Defaulted as Bar(Safety Edge) 6 0-8
*
IC 1 * Configuration of command input terminal 61. Defaulted as Start E 0 0-6
*
IC 2 * Configuration of command input terminal 62. Defaulted as Ped (Partial open) 4 0-6
*
IC 3 * Configuration of command input terminal 64. Defaulted as Open 2 0-6
*
IC 4 * Configuration of command input terminal 65. Defaulted as Close 3 0-6
*
AUX 1 * Configuration of auxiliary output terminals 22 & 23 . Defaulted as Gate not closed contacts. 3 0-8
*
AUX 2 * Configuration of auxiliary output terminals 24 & 25 . Defaulted as Mag-lock contacts. 1 0-8
*
AUX 3 * Configuration of auxiliary output terminals 26 & 27. Defaulted as 2nd channel contacts. 0 0-8
*
LOCK *
FIXED CODE
Terminal 28 and 29 output selection. Defaulted as 12v Solenoid lock
Rolling code defeat. 0 = rolling code; 1 = fixed code
0
0
0-3
0-1
*
RADIO PROG Quick remote programming. 0 = disabled; 1 = enabled 1 0-1
SERIAL MODE 0 = Slave unit; 1 = Master unit 0 0-1
ADDRESS Unit's network identification number. 0 0-127

*
EXPI 1 * Configuration of Expansion board input 1. Defaulted as Start command. 1 0-14
EXPI 2 * Configuration of Expansion board input 2. Defaulted as Start command. 0 0-10
*
*
EXPO 1 * Configuration of Expansion board output 1. Defaulted as Traffic light control.. 9 0-9
EXPO 2 *
TRAFFIC LIGHT PREFLASHING
Configuration of Expansion board output 2. Defaulted as Traffic light control..
Red light flashes for 3 sec. at every start. 0 = Off; 1 = On
9
0
0-9
0-1
*
TRAFFIC LIGHT RED LAMP ALWAYS ON Red light remains on when gate is closed. 0 = Off; 1 = On 0 0-1

* see advanced logic programming for additional information

logic sub-menu
MAIN SELECTION DESCRIPTION DEFAULT RANGE
RADIO > ADD START Learns transmitter button as START command
ADD 2CH Learns transmitter button as 2nd channel
ERASE 64 Erase complete memory
COD RX Show receiver ID Code
WK W LINK.

MAIN SELECTION DESCRIPTION DEFAULT RANGE


LANGUAGE > ITA Italian
FRA French
DEU German
ENG English
ESP Spanish

MAIN SELECTION DESCRIPTION DEFAULT RANGE


STAT > VERS Displays board firmware version.
N. CYCLES Displays number of hundreds of cycles (001=100; 010=1000; 100=10,000)
N. REMOTES Displays the number of remotes in memory.
ERR Displays the last 30 board errors in decending order.

other main menu options


advanced logic programming
STEP-BY-STEP LOGICS
VALUE 0 1 2
LOGIC 4-STEP 3-STEP 2-STEP
OPENING STOPS + TCA STOPS + TCA REVERSES
CLOSING STOPS REVERSES REVERSES

SAFE LOGICS
VALUE FUNCTION DESCRIPTION
0 PHOT OBSTRUCTION SENSOR INPUT, NON-CONTACT
1 PHOT TEST OBSTRUCTION SENSOR INPUT, NON-CONTACT, SUPERVISED
2 PHOT OP OPENING OBSTRUCTION SENSOR INPUT, NON-CONTACT
3 PHOT OP TEST OPENING OBSTRUCTION SENSOR INPUT, NON-CONTACT, SUPERVISED
4 PHOT CL CLOSING OBSTRUCTION SENSOR INPUT, NON-CONTACT
5 PHOT CL TEST CLOSING OBSTRUCTION SENSOR INPUT, NON-CONTACT, SUPERVISED
6 BAR SAFETY EDGE (CONTACT OBSTRUCTION) INPUT
7 BAR TEST SAFETY EDGE (CONTACT OBSTRUCTION) INPUT, SUPERVISED
8 BAR 8K2 SAFETY EDGE (CONTACT OBSTRUCTION) EOL RESISTOR SUPERVISED INPUT

IC & EXPI LOGICS


VALUE FUNCTION IC 1 – 4 EXPI 1 EXPI 2
0 START – EXTERNAL ● ● ●
1 START – INTERNAL ● ● ●
2 OPEN ● ● ●
3 CLOSE ● ● ●
4 PED (PARTIAL OPEN) ● ● ●
5 TIMER (HOLD OPEN) ● ● ●
6 TIMER PED (HOLD PARTIAL OPEN) ● ● ●
7 OBSTRUCTION ● ●
8 OPENING OBSTRUCTION ● ●
9 CLOSING OBSTRUCTION ● ●
10 SAFETY EDGE ● ●
11 OBSTRUCTION, SUPERVISED ●
12 OPENING OBSTRUCTION, SUPERVISED ●
13 CLOSING OBSTRUCTION, SUPERVISED ●
14 SAFETY EDGE, SUPERVISED ●

advanced logic programming values


AUX LOGICS
VALUE FUNCTION
0 2ND CHANNEL RECEIVER OUTPUT
1 GATE OPEN LIGHT. CONTACTS CLOSE WHEN GATE IS NOT CLOSED. FLASHES WHILE CLOSING
2 COURTESY LIGHT. CONTACTS CLOSE DURING AND FOR 90 SECONDS AFTER OPERATION.
3 GATE NOT CLOSED. CONTACTS CLOSE UNTIL CLOSE LIMIT IS REACHED
4 START OF CYCLE. CONTACTS CLOSE FOR 1 SECOND AT THE BEGINNING OF EACH CYCLE
5 GATE OPEN ALARM. CONTACTS CLOSE IF GATE IS HELD OPEN FOR MORE THAN DOUBLE THE TIMER TO CLOSE TIME
6 GATE RUNNING. CONTACTS CLOSE WHILE MOTORS ARE POWERED
7 SOLENOID LOCK. CONTACTS CLOSE FOR 2 SECOND AT THE BEGINNING OF OPEN CYCLE
8 MAGNETIC LOCK. CONTACTS CLOSE WHEN GATE IS CLOSED
9 TRAFFIC LIGHT CONTROL (EXPANSION BOARD OUTPUT WITH TLB BOARD ONLY)

LOCK LOGICS
VALUE FUNCTION
0 12V DC SOLENOID LOCK OUTPUT
1 12V DC MAGNETIC LOCK OUTPUT
2 24V DC SOLENOID LOCK OUTPUT
3 24V DC MAGNETIC LOCK OUTPUT

advanced logic programming values