Tutorial 1: BEE 4213 - Semester 2, Session 2010/2011
Tutorial 1: BEE 4213 - Semester 2, Session 2010/2011
Tutorial 1
Review Questions
1.2 Describe the major differences between American and European distribution systems in
terms of cost, flexibility, safety, and reliability.
1.3 State and explain the functions of each substation (4 levels) found in the primary
distribution system.
Page 1 of 4
BEE 4213 – Semester 2, Session 2010/2011
Questions
1.1 A generating station has a maximum demand of 35,500 kW and has a connected load of
65,000 kW. The number of units annually generated is 2.56 x 10 8 kWh. Calculate the
demand factor and the load factor. [Ans. 0.45; 0.823]
1.2 A power generation station supplies the following loads to various consumers: 15,000 kW,
12,000 kW, 8,500 kW, 6,000 kW and 450 kW. The station has a maximum demand of
22,000 kW. The annual load factor of the station is 0.48. Calculate (a) the number of units
supplied annually, (b) the demand factor, and (c) the diversity factor. [Ans. (a) 9.25 x 10 7
units, (b) 0.252 and (c) 1.907]
1.3 A factory has its monthly (take 30 days) electric power consumptions as follows:
Calculate:
a) The total monthly energy consumption (in kWh and kVArh) of the factory [Ans.
86625.06 kWh + j47653.92 kVArh]
b) The maximum demand for this factory if the load factor is considered as 72% [Ans.
167.1 kW]
c) Average power factor and the total monthly bill charge [Ans. 0.88, RM22,489.21]
Page 2 of 4
BEE 4213 – Semester 2, Session 2010/2011
1.4 A load profiling data has been extracted from a distribution area consisting of 3 groups of
individual consumers. Table 1-1 depicts the 10 days average energy consumption (in kVA)
for those individual consumers.
Table 1-1
Individual
1st 2nd 3rd 4th 5th 6th 7th 8th 9th 10th
Group
1 42 53 126 34 65 76 90 23 55 80
2 256 128 112 89 134 178 136 184 105 160
3 89 78 63 77 95 72 69 167 111 125
Calculate the diversity factor for the distribution area. What is the nearest standard size of
the distribution transformer that serving the distribution area? [Ans. 1.42, 400 kVA]
1.6 A 100 MW power station delivers 100 MW for 2 hours, 50 MW for 6 hours and is shut
down for the rest of each day. It is also shut down for maintenance for 45 days each year
Calculate its annual load factor. [Ans. 20.8%]
If the maximum demand on the station is 2500 kW and the number of kWh generated per
year is 45 x 105, determine (i) the diversity factor and (ii) annual load factor. [Ans. (i) 1.12,
(ii) 20.5%]
Page 3 of 4
BEE 4213 – Semester 2, Session 2010/2011
If the overall system diversity factor is 1.35, determine (i) the maximum demand and (ii)
connected load of each type. [Ans. (i) 10,000 kW, (ii) Connected domestic load = 2250 kW,
Connected commercial load = = 2444 kW, Connected industrial load = 12500 kW]
1.9 It has been desired to install a diesel power station to supply power in a sub-urban area
having the following particulars:
(i) 1000 houses with average connected load of 1.5 kW in each house. The demand
factor and diversity factor being 0.4 and 2.5 respectively
(ii) 10 factories having overall maximum demand of 90 kW
(iii) 7 tubewells of 7 kW each and operating together in the morning
The diversity factor among above three types of consumers is 1.2. What should be the
minimum capacity of power station? [Ans. 316 kW]
1.10 The daily demands of three consumers connected to a station are given below:
Plot the load curve and find (i) maximum demand of individual consumer, (ii) load factor
of individual consumer, (iii) diversity factor and (iv) the station load factor. [Ans. (i) 800 W,
1000 W, 1200 W, (ii) 45.8%, 16.7%, 13.8%, (iii) 1.25, (iv) 29.1%]
Page 4 of 4