Goodrive 200A: Inver Ter
Goodrive 200A: Inver Ter
Preface
Thanks for choosing our products.
Goodrive200A series inverters are newly-designed by our company for controlling
asynchronous AC inductance motors. Applying the most advanced speedless sensor vector
control technology, DSP control system, and our product enhances its reliability to meet the
adaptability to the environment, customized and industrialized design with more optimized
functions, more flexible application and more stable performance.
The vector control performance of Goodrive200A series inverters is as outstanding as that of
the leading sophisticated inverters on worldwide market. Its speed and torque control can be
simultaneously, comparing with the other kinds, its function of anti-trip and strong
adaptability to worse grid, temperature, humidity and dust make it meet the high
performance requirement of the customer application.
Goodrive200A series inverters apply modularized design to meet the specific demand of
customers, as well as the demand of the whole industry flexibly and follow the trend of
industrial application to the inverters on the premise of meeting general need of the market.
Powerful speed control, torque control, simple PLC, flexible input/output terminals, pulse
frequency reference, traverse control can realize various complicate high-accuracy drives
and provide integrative solution for the manufacturers of industrial devices, which
contributes a lot to the cost reducing and improves reliability.
Goodrive200A series inverters can meet the demand of environmental protection which
focuses on low noise and weakening electromagnetic interference in the application sites for
the customers.
This manual provides installation and configuration, parameters setting, fault diagnoses and
daily maintenance and relative precautions to customers. Please read this manual carefully
before the installation to ensure a proper installation and operation and high performance of
Goodrive200A series inverters.
If the product is ultimately used for military affairs or manufacture of weapon, it will be listed
on the export control formulated by Foreign Trade Law of the People's Republic of China.
Rigorous review and necessary export formalities are needed when exported.
Our company reserves the right to update the information of our products.
1
Goodrive200A inverters Contents
Contents
Preface.............................................................................................................................. 1
Contents............................................................................................................................ 2
Safety Precautions 1 ................................................................ 1
1.1 What this chapter contains .................................................................................. 1
1.2 Safety definition .................................................................................................. 1
1.3 Warning symbols ................................................................................................ 1
1.4 Safety guidelines ................................................................................................ 2
Quick Start-up 2 ..................................................... 4
2.1 What this chapter contains .................................................................................. 4
2.2 Unpacking inspection .......................................................................................... 4
2.3 Application confirmation ...................................................................................... 4
2.4 Environment ....................................................................................................... 4
2.5 Installation confirmation ...................................................................................... 5
2.6 Basic commission ............................................................................................... 5
Product Overview 3 ................................................................ 6
3.1 What this chapter contains .................................................................................. 6
3.2 Basic principles ................................................................................................... 6
3.3 Product specification ........................................................................................... 7
3.4 Name plate ......................................................................................................... 8
3.5 Type designation key .......................................................................................... 9
3.6 Rated specifications ............................................................................................ 9
3.7 Structure diagram ............................................................................................. 10
Installation Guidelines 4 ................................................................... 12
4.1 What this chapter contains ................................................................................ 12
4.2 Mechanical installation ...................................................................................... 12
4.3 Standard wiring ................................................................................................. 16
4.4 Layout protection .............................................................................................. 23
Keypad Operation Procedure 5........................................................... 25
5.1 What this chapter contains ................................................................................ 25
5.2 Keypad ............................................................................................................. 25
5.3 Keypad displaying ............................................................................................. 27
5.4 Keypad operation.............................................................................................. 27
Function Parameters 6 ........................................................... 29
6.1 What this chapter contains ................................................................................ 29
6.2 Goodrive200A general series function parameters ............................................ 29
Basic Operation Instruction 7 ................................................................ 95
7.1 What this chapter contains ................................................................................ 95
7.2 First powering on .............................................................................................. 95
7.3 Vector control.................................................................................................... 97
7.4 Torque control ................................................................................................... 98
7.5 Parameters of the motor ................................................................................... 99
7.6 Start-up and stop control ..................................................................................100
2
Goodrive200A inverters Contents
7.7 Frequency setting ............................................................................................101
7.8 Simple PLC .....................................................................................................103
7.9 Multi-step speed running ..................................................................................103
7.10 PID control .....................................................................................................104
7.11 Pulse counter .................................................................................................106
Fault Tracking 8 ..................................................... 108
8.1 What this chapter contains ...............................................................................108
8.2 Alarm and fault indications ...............................................................................108
8.3 How to reset ....................................................................................................108
8.4 Fault history .....................................................................................................108
8.5 Fault instruction and solution............................................................................108
8.6 Common fault analysis ..................................................................................... 113
8.7 Inverter system interference troubleshooting .................................................... 117
8.8 Maintenance and hardware diagnostics ........................................................... 118
Communication Protocol 9 ................................................... 123
9.1 What this chapter contains ...............................................................................123
9.2 Brief instruction to MODBUS protocol ..............................................................123
9.3 Application of the inverter .................................................................................124
9.4 RTU command code and communication data illustration .................................127
9.5 The definition of data address ..........................................................................133
9.6 Example of writing and reading ........................................................................139
Technical Data Appendix A ........................................... 143
A.1 What this chapter contains...............................................................................143
A.2 Ratings............................................................................................................143
A.3 Electric power network specification ................................................................144
A.4 Motor connection data .....................................................................................144
A.5 Applicable standards .......................................................................................145
A.6 EMC regulations ..............................................................................................145
Dimension Drawings Appendix B ............................................ 147
B.1 What this chapter contains...............................................................................147
B.2 Keypad structure .............................................................................................147
B.3 Inverter chart ...................................................................................................148
Peripheral Options and Parts Appendix C ............................................. 152
C.1 What this chapter contains ..............................................................................152
C.2 Peripheral wiring .............................................................................................152
C.3 Power supply ..................................................................................................153
C.4 Cables ............................................................................................................153
C.5 Breaker, electromagnetic contactor and leakage protection switch ...................156
C.6 Reactors .........................................................................................................158
C.7 Filters ..............................................................................................................159
C.8 Braking system ...............................................................................................160
C.9 Other optional parts .........................................................................................163
Further Information Appendix D ............................................. 164
3
Goodrive200A inverters Safety precautions
Safety Precautions 1
1
Goodrive200A inverters Safety precautions
1.4 Safety guidelines
Only qualified electricians are allowed to operate on the inverter.
Do not carry out any wiring and inspection or changing components when the
power supply is applied. Ensure all input power supply is disconnected
before wiring and checking and always wait for at least the time designated
on the inverter or until the DC bus voltage is less than 36V. Below is the table
of the waiting time:
Inverter model Minimum waiting time
380V 1.5kW-110kW 5 minutes
380V 132 kW-315 kW 15 minutes
380V above 350 kW 25 minutes
Do not refit the inverter unauthorized; otherwise fire, electric shock or other
injury may occur.
The base of the heat sink may become hot during running. Do not touch to
avoid hurt.
The electrical parts and components inside the inverter are electrostatic. Take
measurements to avoid electrostatic discharge during relevant operation.
2
Goodrive200A inverters Safety precautions
with proper techniques and ensure the grounding resistor is less than 10Ω. The
conductivity of PE grounding conductor is the same as that of the phase conductor
(with the same cross sectional area).
R, S and T are the input terminals of the power supply, while U, V and W are the motor
terminals. Please connect the input power cables and motor cables with proper
techniques; otherwise the damage to the inverter may occur.
There are heavy metals in the inverter. Deal with it as industrial effluent.
3
Goodrive200A inverters Quick start-up
Quick Start-up 2
2.4 Environment
Check as followings before the actual installation and usage:
1. Check that the ambient temperature of the inverter is below 40℃ . If exceeds, derate 1%
for every additional 1℃ . Additionally, the inverter can not be used if the ambient
temperature is above 50℃.
Note: for the cabinet inverter, the ambient temperature means the air temperature inside
the cabinet.
2. Check that the ambient temperature of the inverter in actual usage is above -10℃. If not,
add heating facilities.
4
Goodrive200A inverters Quick start-up
Note: for the cabinet inverter, the ambient temperature means the air temperature inside
the cabinet.
3. Check that the altitude of the actual usage site is below 1000m. If exceeds, derate1% for
every additional 100m.
4. Check that the humidity of the actual usage site is below 90% and condensation is not
allowed. If not, add additional protection inverters.
5. Check that the actual usage site is away from direct sunlight and foreign objects can not
enter the inverter. If not, add additional protective measures.
6. Check that there is no conductive dust or flammable gas in the actual usage site. If not,
add additional protection to inverters.
Product Overview 3
3.1 What this chapter contains
The chapter briefly describes the operation principle, product characteristics, layout, name
plate and type designation information.
3.2 Basic principles
Goodrive200A series inverters are wall, flange and mountable devices for controlling
asynchronous AC inductance motors.
The diagram below shows the main circuit diagram of the inverter. The rectifier converts
three-phase AC voltage to DC voltage. The capacitor bank of the intermediate circuit
stabilizes the DC voltage. The converter transforms the DC voltage back to AC voltage for
the AC motor. The brake pipe connects the external braking resistor to the intermediate DC
circuit to consume the feedback energy when the voltage in the circuit exceeds its maximum
limit.
6
Goodrive200A inverters Product overview
7
Goodrive200A inverters Product overview
Function Specification
interface resolution
Terminal switch input
≤ 2ms
resolution
1 channels ( AI2) 0~10V/0~20mA and 1 channel
Analog input
(AI3) -10~10V
Analog output 2 channels (AO1, AO2) 0~10V /0~20mA
8 channels common input, the Max. frequency:
1kHz, internal impedance: 3.3kΩ;
Digital input
1 channel high speed input, the Max. frequency:
50kHz
1 channel high speed pulse output, the Max.
Digital output frequency: 50kHz;
1 channel Y terminal open collector pole output
2 channels programmable relay output
RO1A NO, RO1B NC, RO1C common terminal
Relay output
RO2A NO, RO2B NC, RO2C common terminal
Contactor capability: 3A/AC250V,1A/DC30V
Mountable method Wall, flange and floor mountable
Temperature of the
-10~50℃, derate above 40℃
running environment
Ingress protection IP20
Cooling Air-cooling
Built-in braking unit for inverters below 30kW
Others
Braking unit (including 30kW)
External braking unit for others
Built-in C3 filter: meet the degree requirement of
IEC61800-3 C3
EMC filter
External optional filter:meet the degree requirement
of IEC61800-3 C2
Key Instructions
A GD200A : abbreviation of Goodrive200A
3-digit code: output power. “R” means the decimal point; ”011”:11kW;
B, D
“015”:15kW
C G:Constant torque load
C, E
E P:Variable torque load
Input voltage degree:
2: AC 3PH 220V(-15%)~240V(+10%)
F
4: AC 3PH 380V(-15%)~ 440V(+10%)
6: AC 3PH 520V(-15%)~690V(+10%)
1 6
7
2 8
9
3 10
11
12
13
10
Goodrive200A inverters Product overview
11
Goodrive200A inverters Installation guidelines
Installation Guidelines 4
Only qualified electricians are allowed to carry out what described in this
chapter. Please operate as the instructions in Safety Precautions. Ignoring
these may cause physical injury or death or damage to the devices.
Ensure the power supply of the inverter is disconnected during the operation.
Wait for at least the time designated until the POWER indicator is off after the
disconnection if the power supply is applied. It is recommended to use the
multimeter to monitor that the DC bus voltage of the drive is under 36V.
The installation and design of the inverter should be complied with the
requirement of the local laws and regulations in the installation site. If the
installation infringes the requirement, our company will exempt from any
responsibility. Additionally, if users do not comply with the suggestion, some
damage beyond the assured maintenance range may occur.
12
Goodrive200A inverters Installation guidelines
Environment Conditions
The maximum relative humility should be equal to or less than
60% in corrosive air.
Storage
-30~+60℃
temperature
The installation site of the inverter should:
keep away from the electromagnetic radiation source;
keep away from contaminative air, such as corrosive gas, oil mist
Running and flammable gas;
environment ensure foreign objects, such as metal power, dust, oil, water can
condition not enter into the inverter(do not install the inverter on the
flammable materials such as wood);
keep away from direct sunlight, oil mist, steam and vibration
environment.
Below 1000m
Altitude If the sea level is above 1000m, please derate 1% for every
additional 100m.
Vibration ≤ 5.8m/s2(0.6g)
The inverter should be installed on an upright position to ensure
Installation direction
sufficient cooling effect.
Note:
Goodrive200A series inverters should be installed in a clean and ventilated
environment according to enclosure classification.
Cooling air must be clean, free from corrosive materials and electrically conductive
dust.
13
Goodrive200A inverters Installation guidelines
15
Goodrive200A inverters Installation guidelines
16
Goodrive200A inverters Installation guidelines
17
Goodrive200A inverters Installation guidelines
Terminal name
Terminal Function
≤30kW ≥37kW
1 braking unit terminal 1 terminals of braking unit.
(-) / Braking unit terminal 2 PB and (+) are connected with the
Braking resistor This terminal is terminals of braking resistor.
PB
terminal 2 inexistent.
Protective grounding terminals, every
machine is provided 2 PE terminals as
380V:the grounding resistor is less
PE the standard configuration. These
than 10Ohm
terminals should be grounded with
proper techniques.
Optional parts (external 220V control
A1 and A2 Control power supply terminal
power supply)
Note:
Do not use an asymmetrically constructed motor cable. If there is a symmetrically
constructed grounding conductor in the motor cable in addition to the conductive
shield, connect the grounding conductor to the grounding terminal at the inverter
and motor ends.
Braking resistor, braking unit and DC reactor are optional parts.
Route the motor cable, input power cable and control cables separately.
If the terminal is not appeared, the machine does not provide the terminal as the
external terminal.
19
Goodrive200A inverters Installation guidelines
20
Goodrive200A inverters Installation guidelines
21
Goodrive200A inverters Installation guidelines
PE Grounding terminal
Provide the input switch working power supply from external to internal.
PW
Voltage range: 12~24V
The inverter provides the power supply for users with a maximum output
24V
current of 200mA
COM +24V common terminal
S1 Switch input 1
1. Internal impedance:3.3kΩ
S2 Switch input 2
2. 12~30V voltage input is available
S3 Switch input 3
3. The terminal is the dual-direction input terminal
S4 Switch input 4
supporting both NPN and PNP
S5 Switch input 5
4. Max input frequency:1kHz
S6 Switch input 6
5. All are programmable digital input terminal. User
S7 Switch input 7
can set the terminal function through function codes.
S8 Switch input 8
Except for S1~S8, this terminal can be used as high frequency input channel.
HDI
Max. input frequency:50kHz
1. Switch input:200mA/30V
HDO
2. Output frequency range:0~50kHz
COM +24V common terminal
CME Common terminal of HDO and Y1, short-connected with COM in factory
1.Swtich capability:200mA/30V
Y1
2.Output frequency range:0~1kHz
485+ 485 communication interface and 485 differential signal interface
If it is the standard 485 communication interface, please use twisted pairs or
485-
shield cable.
23
Goodrive200A inverters Installation guidelines
24
Goodrive200A inverters Keypad operation procedure
5.2 Keypad
The keypad is used to control Goodrive200A series inverters, read the state data and adjust
parameters.
A B
Fig 5-1 Keypad
Note: The keypad of 0.75~15kW as show in Fig 5-1 A, and 18.5~500kW as show in Fig 5-1
B; The inverters of 0.75~30kW can choose optional LED keypad and 0.75~500kW can
choose optional LCD keypad . The LCD keypad supports several languages, parameters
copy, high-definition display and its installation dimension is compatible with the LED.
Use strew or installation bracket to fix the external keypad. The inverters of 0.75~30kW have
standard bracket, while the inverters of 37~500kW have optimal bracket.
No. Name Description
LED off means that the inverter is in the
stopping state; LED blinking means the
RUN/TUNE inverter is in the parameter autotune
state; LED on means the inverter is in
State
1 the running state.
LED FED/REV LED
LED off means the inverter is in the
FWD/REV
forward rotation state; LED on means
the inverter is in the reverse rotation
25
Goodrive200A inverters Keypad operation procedure
Function Parameters 6
29
Goodrive200A inverters Function parameters
password freely and the inverter will work as the last setting one. When P07.00 is set to 0,
the password can be canceled. If P07.00 is not 0 during powering on, then the parameter is
protected by the password. When modify the parameters by serial communication, the
function of the password follows the above rules, too.
Function Default
Name Detailed instruction of parameters Modify
code value
P00 Group Basic function group
1: Sensorless vector control mode 1 (applying to
AM)
No need to install encoders. It is suitable in cases
with high speed control accuracy for accurate
speed and torque control at all power ratings.
Speed 2:SVPWM control
P00.00 2 ◎
control mode No need to install encoders. It can improve the
control accuracy with the advantages of stable
operation, valid low-frequency torque boost and
current vibration suppression and the functions of
slip compensation and voltage adjustment.
Note: AM-Asynchronous motor
Select the run command channel of the inverter.
The control command of the inverter includes:
start-up, stop, forward, reverse, jogging and fault
reset.
0:Keypad running command
channel(“LOCAL/REMOT” light off)
Carry out the command control by RUN,
STOP/RST on the keypad.
Set the multi-function key QUICK/JOG as
FWD/REV shifting function (P07.02=3) to change
Run the running direction; press RUN and
P00.01 command STOP/RST simultaneously in running state to 0 ○
channel make the inverter coast to stop.
1:Terminal running command channel
(“LOCAL/REMOT” flickering)
Carry out the running command control by the
forward rotation, reverse rotation and forward
jogging and reverse jogging of the multi-function
terminals
2:Communication running command channel
(“LOCAL/REMOT” on);
The running command is controlled by the upper
monitor via communication.
30
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
Communicati 0: MODBUS communication
P00.02 0 ○
on selection 1~3: Reserved
This parameter is used to set the Maximum
output frequency of the inverter. Users should
Max. output pay attention to this parameter because it is the 50.00
P00.03 ◎
frequency foundation of the frequency setting and the Hz
speed of acceleration and deceleration.
Setting range: P00.04~400.00Hz
The upper limit of the running frequency is the
upper limit of the output frequency of the inverter
Upper limit of
which is lower than or equal to the maximum 50.00
P00.04 the running ◎
frequency. Hz
frequency
Setting range:P00.05~P00.03 (Max. output
frequency)
The lower limit of the running frequency is that of
the output frequency of the inverter.
The inverter runs at the lower limit frequency if
Lower limit of the set frequency is lower than the lower limit
P00.05 the running one. 0.00Hz ◎
frequency Note: Max. output frequency ≥ Upper limit
frequency ≥ Lower limit frequency
Setting range:0.00Hz~P00.04 (Upper limit of the
running frequency)
A frequency Note: Frequency A and frequency B cannot use
P00.06 0 ○
command the same frequency setting mode. The frequency
source can be set by P00.09.
0:Keypad data setting
Modify the value of P00.10 (set the frequency by
keypad) to modify the frequency by the keypad.
1:Analog AI1 setting(The inverter(≤15kW) can
be set by the analog potentiometer on the keypad
and AI1 setting is not available for the device
B frequency which is 18.5kW or higer than 18.5kW)
P00.07 2 ○
command 2:Analog AI2 setting
3:Analog AI3 setting
Set the frequency by analog input terminals.
Goodrive200A series inverters provide 3
channels analog input terminals as the standard
configuration, of which AI1/AI2 are the
voltage/current option (0~10V/0~20mA) which
can be shifted by jumpers; while AI3 is voltage
31
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
input (-10V~+10V).
Note: when analog AI1/AI2 select 0~20mA input,
the corresponding voltage of 20mA is 10V.
100.0% of the analog input setting corresponds
to the maximum frequency (function code
P00.03) in forward direction and -100.0%
corresponds to the maximum frequency in
reverse direction (function code P00.03)
4:High-speed pulse HDI setting
The frequency is set by high-speed pulse
terminals. Goodrive200A series inverters provide
1 channel high speed pulse input as the standard
configuration. The pulse frequency range is
0.00~50.00kHz.
100.0% of the high speed pulse input setting
corresponds to the maximum frequency in
forward direction (P00.03) and -100.0%
corresponds to the maximum frequency in
reverse direction (P00.03).
Note: The pulse setting can only be input by
multi-function terminals HDI. Set P05.00 (HDI
input selection) to high speed pulse input, and
set P05.49 (HDI high speed pulse input function
selection) to frequency setting input.
5:Simple PLC program setting
The inverter runs at simple PLC program mode
when P00.06=5 or P00.07=5. Set P10 (simple
PLC and multi-step speed control) to select the
running frequency, running direction, ACC/DEC
time and the keeping time of corresponding step.
See the function description of P10 for detailed
information.
6: Multi-step speed running setting
The inverter runs at multi-step speed mode when
P00.06=6 or P00.07=6. Set P05 to select the
current running step, and set P10 to select the
current running frequency.
The multi-step speed has the priority when
P00.06 or P00.07 does not equal to 6, but the
setting step can only be the 1~15 step. The
setting step is 0~15 if P00.06 or P00.07 equals to
32
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
6.
7: PID control setting
The running mode of the inverter is process PID
control when P00.06=7 or P00.07=7. It is
necessary to set P09. The running frequency of
the inverter is the value after PID effect. See P09
for the detailed information of the preset source,
preset value, and feedback source of PID.
8:MODBUS communication setting
The frequency is set by MODBUS
communication. See P14 for detailed information.
9~11: Reserved
0:Maximum output frequency, 100% of
B frequency setting corresponds to the maximum
B frequency output frequency
P00.08 command 1: A frequency command, 100% of B frequency 0 ○
reference setting corresponds to the maximum output
frequency. Select this setting if it needs to adjust
on the base of A frequency command.
0: A, the current frequency setting is A frequency
command
1: B, the current frequency setting is B frequency
command
2: A+B, the current frequency setting is A
frequency command + B frequency command
3: A-B, the current frequency setting is A
Combination
frequency command - B frequency command
P00.09 of the setting 0 ○
4: Max (A, B): the bigger one between A
source
frequency command and B frequency is the set
frequency.
5: Min (A, B): The lower one between A
frequency command and B frequency is the set
frequency.
Note:The combination manner can be shifted by
P05(terminal function)
When A and B frequency commands are selected
as “keypad setting”, this parameter will be the
Keypad set 50.00
P00.10 initial value of inverter reference frequency ○
frequency Hz
Setting range:0.00 Hz~P00.03
(the Max. frequency)
33
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
ACC time means the time needed if the inverter
speeds up from 0Hz to the Max. One (P00.03). Depend
P00.11 ACC time 1 DEC time means the time needed if the inverter on ○
speeds down from the Max. Output frequency to model
0Hz (P00.03).
Goodrive200A series inverters define four
groups of ACC/DEC time which can be selected
Depend
by P05. The factory default ACC/DEC time of the
P00.12 DEC time 1 on ○
inverter is the first group.
model
Setting range of P00.11 and P00.12:0.0~3600.0s
0: Runs at the default direction, the inverter runs
in the forward direction. FWD/REV indicator is
off.
1: Runs at the opposite direction, the inverter
runs in the reverse direction. FWD/REV indicator
is on.
Modify the function code to shift the rotation
direction of the motor. This effect equals to the
shifting the rotation direction by adjusting either
two of the motor lines (U, V and W). In keypad
Running control, the motor rotation direction can be
P00.13 0 ○
direction changed by QUICK/JOG on the keypad. Refer to
parameter P07.02.
Note: When the function parameter comes back
to the default value, the motor’s running direction
will come back to the factory default state, too. In
some cases it should be used with caution after
commissioning if the change of rotation direction
is disabled.
2: Forbid to run in reverse direction: It can be
used in some special cases if the reverse running
is disabled.
Carrier Depend
P00.14 frequency on ○
setting model
34
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
The relationship table of the motor type and
carrier frequency:
Factory setting of
Model
carrier frequency
1.5~11kW 8kHz
15~55kW 4kHz
Above 75kW 2kHz
The advantage of high carrier frequency: ideal
current waveform, little current harmonic wave
and motor noise.
The disadvantage of high carrier frequency:
increasing the switch loss, increasing inverter
temperature and the impact to the output
capacity. The inverter needs to derate on high
carrier frequency. At the same time, the leakage
and electrical magnetic interference will increase.
Applying low carrier frequency is contrary to the
above, too low carrier frequency will cause
unstable running, torque decreasing and surge.
The manufacturer has set a reasonable carrier
frequency when the inverter is in factory. In
general, users do not need to change the
parameter.
When the frequency used exceeds the default
carrier frequency, the inverter needs to derate
10% for each additional 1k carrier frequency.
Setting range:1.0~15.0kHz
0:No operation
1:Rotation autotuning
Comprehensive motor parameter autotune
It is recommended to use rotation autotuning
when high control accuracy is needed.
Motor
2:Static autotuning 1
P00.15 parameter 0 ◎
It is suitable in the cases when the motor can not
autotuning
de-couple from the load.
3:Static autotuning 2
It is suitable in the cases when the motor can not
de-couple form the load. But only for parts of
parameters.
P00.16 AVR function 0:Invalid 1 ○
35
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
selection 1:Valid during the whole procedure
The auto-adjusting function of the inverter can
cancel the impact on the output voltage of the
inverter because of the bus voltage fluctuation.
0:G type, for the constant torque load of rated
parameters
1:P type; for the variable torque load of rated
P00.17 Inverter type parameters (fans and water pumps) 0 ◎
GD200A series inverters can use G/P type, the
available motor power of G type is small one
power file than that of P type.
0:No operation
1:Restore the default value
2:Clear fault records
Function
Note: The function code will restore to 0 after
P00.18 restore 0 ◎
finishing the operation of the selected function
parameter
code.
Restoring to the default value will cancel the user
password, please use this function with caution.
P01 Group Start-up and stop control
0:Start-up directly:start from the starting
frequency P01.01
1:Start-up after DC braking: start the motor from
the starting frequency after DC braking (set the
parameter P01.03 and P01.04). It is suitable in
the cases where reverse rotation may occur to
the low inertia load during starting.
P01.00 Start mode 0 ◎
2: Start-up after speed tracking: start the rotating
motor smoothly after tracking the rotation speed
and direction automatically. It is suitable in the
cases where reverse rotation may occur to the
big inertia load during starting.
Note: This function is available for the inverters of
4kW and above.
Starting frequency of direct start-up means the
Starting
original frequency during the inverter starting.
P01.01 frequency of 0.50Hz ◎
See P01.02 for detailed information.
direct start
Setting range: 0.00~50.00Hz
Retention Set a proper starting frequency to increase the
P01.02 0.0s ◎
time of the torque of the inverter during starting. During the
36
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
starting retention time of the starting frequency, the
frequency output frequency of the inverter is the starting
frequency. And then, the inverter will run from the
starting frequency to the set frequency. If the set
frequency is lower than the starting frequency,
the inverter will stop running and keep in the
stand-by state. The starting frequency is not
limited in the lower limit frequency.
37
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
1: S curve
ACC time of
the starting
P01.06 0.1s ○
step of S
curve
0.0~50.0s
DEC time of
the ending
P01.07 0.1s ○
step of S
curve
0: Decelerate to stop: after the stop command
becomes valid, the inverter decelerates to reduce
the output frequency during the set time. When
the frequency decreases to 0Hz, the inverter
P01.08 Stop mode stops. 0 ○
1: Coast to stop: after the stop command
becomes valid, the inverter ceases the output
immediately. And the load coasts to stop at the
mechanical inertia.
Starting Starting frequency of DC braking: start the DC
P01.09 frequency of braking when running frequency reaches starting 0.00Hz ○
DC braking frequency determined by P1.09.
Waiting time Waiting time before DC braking: Inverters block
P01.10 before DC the output before starting the DC braking. After 0.00s ○
braking this waiting time, the DC braking will be started
DC braking so as to prevent over-current fault caused by DC
P01.11 braking at high speed. 0.0% ○
current
DC braking current:The value of P01.11 is the
percentage of rated current of inverter. The
bigger the DC braking current is, the greater the
DC braking braking torque is.
P01.12 0.00s ○
time DC braking time: The retention time of DC brake.
If the time is 0, the DC brake is invalid. The
inverter will stop at the set deceleration time.
38
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
Dead time of
P01.13 FWD/REV 0.0s ○
rotation
39
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
40
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
Note: The time is the total value when the set
frequency is above the lower limit one.
Delay time of
P01.24 the stop 0.0s ●
speed
41
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
0: Output without voltage
0Hz output
P01.25 1: Output with voltage 0 ●
selection
2: Output at the DC braking current
P02 Group Motor 1
Depend
Rated power
P02.01 0.1~3000.0kW on ◎
of AM 1
model
Rated
50.00
P02.02 frequency of 0.01Hz~P00.03(the Max. frequency) ◎
Hz
AM 1
Depend
Rated speed
P02.03 1~36000rpm on ◎
of AM 1
model
Rated Depend
P02.04 voltage of 0~1200V on ◎
AM 1 model
Depend
Rated current
P02.05 0.8~6000.0A on ◎
of AM 1
model
Stator Depend
P02.06 resistor of 0.001~65.535Ω on ○
AM 1 model
Rotor Depend
P02.07 resistor of 0.001~65.535Ω on ○
AM 1 model
Leakage Depend
P02.08 inductance of 0.1~6553.5mH on ○
AM 1 model
Mutual Depend
P02.09 inductance of 0.1~6553.5mH on ○
AM 1 model
Non-load Depend
P02.10 current of AM 0.1~6553.5A on ○
1 model
0: No protection
1: Common motor (with low speed
compensation). Because the heat-releasing
Motor 1
effect of the common motors will be weakened,
P02.26 overload 2 ◎
the corresponding electric heat protection will be
protection
adjusted properly. The low speed compensation
characteristic mentioned here means reducing
the threshold of the overload protection of the
42
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
motor whose running frequency is below 30Hz.
2: Variable frequency motor (without low speed
compensation) Because the heat-releasing effect
of the specific motors won’t be impacted by the
rotation speed, it is not necessary to adjust the
protection value during low-speed running.
Times of motor overload M = Iout/(In*K)
In is the rated current of the motor, Iout is the
output current of the inverter and K is the motor
protection coefficient.
So, the bigger the value of K is, the smaller the
value of M is. When M =116%, the fault will be
reported after 1 hour, when M =200%, the fault
Motor 1 over
will be reported after 1 minute, when M>=400%,
load
P02.27 the fault will be reported instantly. 100.0% ○
protection
coefficient
43
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
Speed loop PI parameters
P03.04 integral time (P03.00,P03.01) 0.200s ○
2
(P03.03,P03.04)
44
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
dynamic response speed and control accuracy
Current loop directly. Generally, users do not need to change
P03.10 integral the default value. 1000 ○
coefficient 1 2 Only apply to SVC control mode 0(P00.00=0).
Setting range:0~65535
This parameter is used to enable the torque
control mode, and set the torque.
0:Torque control is invalid
1:Keypad setting torque(P03.12)
2:Analog AI1 setting torque(The inverter( ≤
15kW) can be set by the analog potentiometer on
the keypad and AI1 setting is not available for the
Torque
device which is 18.5kW or higer than 18.5kW)
P03.11 setting 0 ○
3:Analog AI2 setting torque
method
4:Analog AI3 setting torque
5:Pulse frequency HDI setting torque
6:Multi-step torque setting
7:MODBUS communication setting torque
8~10:Reserved
Note: Setting modes 2~10, 100% corresponds to
three times of the rated current of the motor.
Keypad Setting range: -300.0%~300.0%(rated current of
P03.12 50.0% ○
setting torque the motor)
Torque
P03.13 reference 0.000~10.000s 0.010s ○
filter time
Upper 0:Keypad
frequency of (P03.16 sets P03.14,P03.17 sets P03.15)
P03.14 forward 1: AI1 (The inverter(≤15kW) can be set by the 0 ○
rotation in analog potentiometer on the keypad and AI1
vector control setting is not available for the device which is
18.5kW or higer than 18.5kW)
2: AI2
3: AI3
Upper
4:Pulse frequency HDI setting upper-limit
frequency of
frequency
P03.15 reverse 0 ○
5:Multi-step setting upper-limit frequency
rotation in
6:MODBUS communication setting upper-limit
vector control
frequency
7~ 9: Reserved
Note: Setting method 1~9, 100% corresponds to
45
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
the maximum frequency
Keypad
setting for
upper
P03.16 50.00 Hz ○
frequency of
This function is used to set the upper limit of the
forward
frequency. P03.16 sets the value of P03.14;
rotation
P03.17 sets the value of P03.15.
Keypad
Setting range:0.00 Hz~P00.03 (the Max. output
setting for
frequency)
P03. upper
50.00Hz ○
17 frequency of
reverse
rotation
Upper electro This function code is used to select the electro
motion motion and braking torque upper-limit setting
P03.18 0 ○
torque source selection.
source 0:Keypad setting upper-limit frequency
(P03.20 sets P03.18, P03.21 sets P03.19)
1: AI1 (The inverter(≤15kW) can be set by the
analog potentiometer on the keypad and AI1
setting is not available for the device which is
Upper
18.5kW or higer than 18.5kW)
braking
P03.19 2: AI2 0 ○
torque
3: AI3
source
4: HDI
5:MODBUS communication
Note: setting mode 1~9,100% corresponds to
three times of the motor current.
Keypad
setting of
P03.20 180.0% ○
electromotion
The function code is used to set the limit of the
torque
torque.
Keypad
Setting range:0.0~300.0%(motor rated current)
setting of
P03.21 180.0% ○
braking
torque
Weakening
coefficient in
P03.22 The usage of motor in weakening control. 0.3 ○
constant
power zone
46
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
Lowest
weakening
P03.23 point in Function code P03.22 and P03.23 are effective 20% ○
constant at constant power. The motor will enter into the
power zone weakening state when the motor runs at rated
speed. Change the weakening curve by
modifying the weakening control coefficient. The
bigger the weakening control coefficient is, the
steeper the weak curve is.
The setting range of P03.22:0.1~2.0
The setting range of P03.23:10%~100%
P03.24 set the Max. Voltage of the inverter, which
Max. voltage
P03.24 is dependent on the site situation. 100.0% ◎
limit
The setting range:0.0~120.0%
Reactivate the motor when the inverter starts up.
Build up a magnetic field inside the inverter to
Pre-exciting
P03.25 improve the torque performance during the 0.300s ○
time
starting process.
The setting time:0.000~10.000s
Weak
0~8000
magnetic
P03.26 Note: P03.24~P03.26 are invalid for vector 1000 ○
proportional
mode.
gain
Vector 0: Display the actual value
P03.27 0 ○
control speed 1: Display the setting value
Compensatio
0.0~100.0%
n coefficient
P03.28 Adjust P03.28 to compensate the coefficient of 0.0% ○
of static
static friction. Only valid when setting in 1Hz.
friction
Compensatio
0.0~100.0%
n coefficient
P03.29 Adjust P03.29 to compensate the coefficient of 0.0% ○
of dynamic
static friction. Only valid when setting in 1Hz.
friction
P04 Group SVPWM control
Motor 1 V/F These function codes define the V/F curve of
P04.00 0 ◎
curve setting Goodrive200A motor 1, and meet the need of
47
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
different loads.
0:Straight line V/F curve;applying to the constant
torque load
1:Multi-dots V/F curve
2:1.3th power low torque V/F curve
3:1.7th power low torque V/F curve
4:2.0th power low torque V/F curve
Curves 2~4 apply to the torque loads such as
fans and water pumps. Users can adjust
according to the features of the loads to achieve
a best energy-saving effect.
5:Customized V/F(V/F separation); in this mode,
V can be separated from f and f can be adjusted
through the frequency reference channel set by
P00.06 or the voltage reference channel set by
P04.27 to change the feature of the curve.
Note: Vb in the below picture is the motor rated
voltage and fb is the motor rated frequency.
48
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
49
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
below:
△f=fb-n*p/60
Of which, fb is the rated frequency of the motor, its
function code is P02.02; n is the rated rotating
speed of the motor and its function code is
P02.03; p is the pole pair of the motor. 100.0%
corresponds to the rated slip frequency△f.
Setting range:0.0~200.0%
Motor 1 low
frequency In the SVPWM control mode, current fluctuation
P04.10 10 ○
vibration may occur to the motor on some frequency,
control factor especially the motor with big power. The motor
Motor 1 high can not run stably or overcurrent may occur.
frequency These phenomena can be canceled by adjusting
P04.11 10 ○
vibration this parameter.
control factor The setting range of P04.10:0~100
Motor 1 The setting range of P04.11:0~100
vibration The setting range of P04.12:0.00Hz~P00.03
P04.12 30.00 Hz ○
control (the Max. frequency)
threshold
0:No action
Energy-savin
1:Automatic energy-saving operation
P04.26 g operation 0 ◎
Motor on the light load conditions, automatically
selection
adjusts the output voltage to save energy
Select the output setting channel at V/F curve
separation.
0: Keypad setting voltage: the output voltage is
determined by P04.28.
1:AI1 setting voltage(The inverter(≤15kW) can
be set by the analog potentiometer on the keypad
and AI1 setting is not available for the device
Voltage
which is 18.5kW or higer than 18.5kW)
P04.27 setting 0 ○
2:AI2 setting voltage;
channel
3:AI3 setting voltage;
4:HDI setting voltage;
5:Multi-step speed setting voltage;
6:PID setting voltage;
7:MODBUS communication setting voltage;
Note: 100% corresponds to the rated voltage of
the motor.
P04.28 Keypad The function code is the voltage digital set value 100.0% ○
50
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
setting when the voltage setting channel is selected as
voltage “keypad selection”
The setting range:0.0%~100.0%
Voltage Voltage increasing time is the time when the
P04.29 increasing inverter accelerates from the output minimum 5.0s ○
time voltage to the output maximum voltage.
Voltage decreasing time is the time when the
Voltage
inverter decelerates from the output maximum
P04.30 decreasing 5.0s ○
voltage to the output minimum voltage.
time
The setting range:0.0~3600.0s
Maximum Set the upper and low limit of the output voltage.
P04.31 output The setting range of P04.31:P04.32~100.0% 100.0% ◎
voltage (the rated voltage of the motor)
The setting range of P04.32:0.0%~ P04.31
(the rated voltage of the motor)
Minimum
P04.32 output 0.0% ◎
voltage
Weaking
coefficient at
P04.33 1.00 ●
constant
power
51
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
S2 terminal 3: 3-wire control
P05.02 function 4: Forward jogging 4 ◎
selection 5: Reverse jogging
S3 terminal 6: Coast to stop
P05.03 function 7: Fault reset 7 ◎
selection 8: Operation pause
S4 terminal 9: External fault input
P05.04 function 10:Increasing frequency setting(UP) 0 ◎
selection 11:Decreasing frequency setting(DOWN)
S5 terminal 12:Cancel the frequency change setting
P05.05 function 13:Shift between A setting and B setting 0 ◎
selection 14:Shift between combination setting and A
S6 terminal setting
P05.06 function 15:Shift between combination setting and B 0 ◎
selection setting
S7 terminal 16:Multi-step speed terminal 1
P05.07 function 17:Multi-step speed terminal 2 0 ◎
selection 18:Multi-step speed terminal 3
S8 terminal 19:Multi- step speed terminal 4
P05.08 function 20:Multi- step speed pause 0 ◎
selection 21:ACC/DEC time option 1
22:ACC/DEC time option 2
23:Simple PLC stop reset
24:Simple PLC pause
25:PID control pause
26:Traverse Pause(stop at the current frequency)
27:Traverse reset(return to the center frequency)
28:Counter reset
29:Torque control prohibition
30:ACC/DEC prohibition
HDI terminal
31:Counter trigger
P05.09 function 0 ◎
32:Length reset
selection
33:Cancel the frequency change setting
temporarily
34:DC brake
36:Shift the command to the keypad
37:Shift the command to the terminals
38:Shift the command to the communication
39: Pre-exciting command
40:Clear the power
41:Keep the power
52
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
61: PID pole switching
53
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
enabling ones. The direction depends on the
state of the defined REV.
54
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
SB1
FWD
SB2
SIn
REV
SB3
COM
OFF→ ON Forward
ON
ON OFF Reverse
ON OFF→ Forward
ON
OFF ON Reverse
ON→ Decelerat
OFF e to stop
55
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
S3 terminal
P05.18 switching-on 0.000s ○
delay time
S3
terminal
P05.19 0.000s ○
switching-off
delay time
S4 terminal
P05.20 switching-on 0.000s ○
delay time
S4
terminal
P05.21 0.000s ○
switching-off
delay time
S5
terminal
P05.22 0.000s ○
switching-on
delay time
S5
terminal
P05.23 0.000s ○
switching-off
delay time
S6
terminal
P05.24 0.000s ○
switching-on
delay time
S6
terminal
P05.25 0.000s ○
switching-off
delay time
S7
terminal
P05.26 0.000s ○
switching-on
delay time
S7
terminal
P05.27 0.000s ○
switching-off
delay time
S8
P05.28 terminal 0.000s ○
switching-on
56
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
delay time
S8
terminal
P05.29 0.000s ○
switching-off
delay time
HDI
terminal
P05.30 0.000s ○
switching-on
delay time
HDI
terminal
P05.31 0.000s ○
switching-off
delay time
Lower limit of The inverter(≤15kW) can be set by the analog
P05.32 0.00V ○
AI1 potentiometer on the keypad and AI1 setting is
Correspondin not available for the device which is 18.5kW or
g setting of higer than 18.5 kW.
P05.33 0.0% ○
the lower The function code defines the relationship
limit of AI1 between the analog input voltage and its
Upper limit of corresponding set value. If the analog input
P05.34 10.00V ○
AI1 voltage beyond the set minimum or maximum
Correspondin input value, the inverter will count at the minimum
g setting of or maximum one.
P05.35 100.0% ○
the upper When the analog input is the current input, the
limit of AI1 corresponding voltage of 0~20mA is 0~10V.
AI1 input In different cases, the corresponding rated value
P05.36 0.100s ○
filter time of 100.0% is different. See the application for
Lower limit of detailed information.
P05.37 The figure below illustrates different applications: 0.00V ○
AI2
Correspondin
g setting of
P05.38 0.0% ○
the lower
limit of AI2
Upper limit of
P05.39 10.00V ○
AI2
Correspondin
g setting of
P05.40 100.0% ○
the upper Input filter time: this parameter is used to adjust
limit of AI2 the sensitivity of the analog input. Increasing the
P05.41 AI2 input 0.100s ○
57
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
filter time value properly can enhance the anti-interference
Lower limit of of the analog, but weaken the sensitivity of the
P05.42 -10.00V ○
AI3 analog input
Correspondin Note: Analog AI1 and AI2 can support 0~10V or
g setting of 0~20mA input, when AI1 and AI2 selects 0~20mA
P05.43 -100.0% ○
the lower input, the corresponding voltage of 20mA is 5V.
limit of AI3 AI3 can support the output of -10V~+10V.
Middle value The setting range of P05.32:0.00V~P05.34
P05.44 The setting range of P05.33:-100.0%~100.0% 0.00V ○
of AI3
Correspondin The setting range of P05.34:P05.32~10.00V
g middle The setting range of P05.35:-100.0%~100.0%
P05.45 0.0% ○
setting of The setting range of P05.36:0.000s~10.000s
AI3 The setting range of P05.37:0.00V~P05.39
Upper limit of The setting range of P05.38:-100.0%~100.0%
P05.46 The setting range of P05.39:P05.37~10.00V 10.00V ○
AI3
Correspondin The setting range of P05.40:-100.0%~100.0%
The setting range of P05.41:0.000s~10.000s
g setting of
P05.47 100.0% ○
the upper The setting range of P05.42:-10.00V~P05.44
limit of AI3 The setting range of P05.43:-100.0%~100.0%
The setting range of P05.44: P05.42~P05.46
The setting range of P05.45:-100.0%~100.0%
AI3 input The setting range of P05.46:P05.44~10.00V
P05.48 0.100s ○
filter time The setting range of P05.47:-100.0%~100.0%
The setting range of P05.48:0.000s~10.000s
The function selection when HDI terminals is
high-speed pulse input
0:Frequency setting input, frequency setting
HDI
source
P05.49 high-speed 0 ◎
1:Counter input, high-speed pulse counter input
pulse input
terminals
2:Length counting input, length counter input
terminals
Lower limit
0.000
P05.50 frequency of 0.000kHz~P05.52 ○
kHz
HDI
Correspondin
g setting of
P05.51 HDI low -100.0%~100.0% 0.0% ○
frequency
setting
58
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
Upper limit
50.00
P05.52 frequency of P05.50 ~50.00kHz ○
kHz
HDI
Correspondin
g setting of
P05.53 upper limit -100.0%~100.0% 100.0% ○
frequency of
HDI
HDI
frequency
P05.54 0.000s~10.000s 0.100s ○
input filter
time
P06 Group Output terminals
The function selection of the high-speed pulse
output terminals.
0: Open collector pole high speed pulse output:
The Max.pulse frequency is 50.0kHz. See
P06.00 HDO output 0 ◎
P06.27~P06.31 for detailed information of the
related functions.
1: Open collector pole output. See P06.02 for
detailed information of the related functions.
P06.01 Y1 output 0:Invalid 0 ○
P06.02 HDO output 1:In operation 0 ○
Relay RO1 2:Forward rotation
P06.03 1 ○
output 3:Reverse rotation
4: Jogging
5:The inverter fault
6:Frequency degree test FDT1
7:Frequency degree test FDT2
8:Frequency arrival
9:Zero speed running
10:Upper limit frequency arrival
Relay RO2
P06.04 11:Lower limit frequency arrival 5 ○
output
12:Ready for operation
13:Pre-magnetizing
14:Overload pre-alarm
15: Underload pre-alarm
16:Completion of simple PLC step
17:Completion of simple PLC cycle
18:Setting count value arrival
59
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
19:Defined count value arrival
20:External fault valid
21:Length arrival
22:Running time arrival
23:MODBUS communication virtual terminals
output
26: DC bus voltage establishment
27: Auxiliary motor 1
28: Auxiliary motor 2
The function code is used to set the pole of the
output terminal.
When the current bit is set to 0, input terminal is
Polarity
positive.
selection of
P06.05 When the current bit is set to 1, input terminal is 0 ○
output
negative.
terminals
BIT0 BIT1 BIT2 BIT3
Y HDO RO1 RO2
Setting range:0~F
Y1
P06.06 switching-on 0.000s ○
delay time
Y1
P06.07 switching-off 0.000s ○
delay time
HDO The function code defines the corresponding
P06.08 switching-on delay time of the electrical level change during 0.000s ○
delay time the programmable terminal switching on and off.
HDO
P06.09 switching-off 0.000s ○
delay time
RO1
P06.10 switching-on The setting range :0.000~50.000s 0.000s ○
delay time Note: P06.08 and P06.09 are valid only when
RO1 P06.00=1.
P06.11 switching-off 0.000s ○
delay time
RO2
P06.12 switching-on 0.000s ○
delay time
P06.13 RO2 0.000s ○
60
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
switching-off
delay time
P06.14 AO1 output 0:Running frequency 0 ○
P06.15 AO2 output 1:Setting frequency 0 ○
2:Ramp reference frequency
3:Running rotation speed
4:Output current
(relative to twice the inverter rated current)
5:Output current
(relative to twice the motor rated current)
6:Output voltage
7:Output power
9:Output torque
HDO
10:Analog AI1 input value (The inverter(≤15kW)
high-speed
P06.16 can be set by the analog potentiometer on the 0 ○
pulse output
keypad and AI1 setting is not available for the
selection
device which is 18.5kW or higer than 18.5 kW)
11:Analog AI2 input value
12:Analog AI3 input value
13:High speed pulse HDI input value
14:MODBUS communication set value 1
15:MODBUS communication set value 2
22: Torque current
(relative to triple the motor rated current)
23: Ramp reference frequency(with sign)
Lower limit of
P06.17 0.0% ○
AO1 output
Correspondin The above function codes define the relative
g AO1 output relationship between the output value and analog
P06.18 0.00V ○
to the lower output. When the output value exceeds the range
limit of set maximum or minimum output, it will count
Upper limit of according to the low-limit or upper-limit output.
P06.19 100.0% ○
AO1 output When the analog output is current output, 1mA
The equals to 0.5V.
correspondin In different cases, the corresponding analog
P06.20 g AO1 output output of 100% of the output value is different. 10.00V ○
to the upper Please refer to each application for detailed
limit information.
AO1 output
P06.21 0.000s ○
filter time
61
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
A
Lower limit of O
P06.22 10V (20m A) 0.0% ○
AO2 output
Correspondin
g AO2 output
P06.23 0.00V ○
to the lower
limit
0.0% 100.0%
Upper limit of
P06.24 Setting range of P06.18 0.00V~10.00V 100.0% ○
AO2 output
Setting range of P06.19 P06.17~100.0%
Correspondin
Setting range of P06.20 0.00V~10.00V
g AO2 output
P06.25 Setting range of P06.21 0.000s~10.000s 10.00V ○
to the upper
Setting range of P06.22 0.0%~P06.24
limit
Setting range of P06.23 0.00V~10.00V
AO2 output
P06.26 Setting range of P06.24 P06.22~100.0% 0.000s ○
filter time
Setting range of P06.25 0.00V~10.00V
Lower limit of
P06.27 Setting range of P06.26 0.000s~10.000s 0.00% ○
HDO output
Setting range of P06.27 0.000s~10.000s
Correspondin
Setting range of P06.28 0.00~50.00kHz
g HDO
P06.28 Setting range of P06.29 P06.27~100.0% 0.00kHz ○
output to the
Setting range of P06.30 0.00~50.00kHz
lower limit
Setting range of P06.31 0.000s~10.000s
Upper limit of
P06.29 100.0% ○
HDO output
Correspondin
g HDO 50.00
P06.30 ○
output to the kHz
upper limit
HDO output
P06.31 0.000s ○
filter time
P07 Group Human-Machine Interface
0~65535
The password protection will be valid when
setting any non-zero number.
00000: Clear the previous user’s password, and
make the password protection invalid.
User’s
P07.00 After the user’s password becomes valid, if the 0 ○
password
password is incorrect, users cannot enter the
parameter menu. Only correct password can
make the user check or modify the parameters.
Please remember all users’ passwords.
Retreat editing state of the function codes and
62
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
the password protection will become valid in 1
minute. If the password is available, press
PRG/ESCto enter into the editing state of the
function codes, and then “0.0.0.0.0” will be
displayed. Unless input right password, the
operator can not enter into it.
Note: Restoring to the default value can clear the
password, please use it with caution.
The function code determines the mode of
parameters copy.
0:No operation
1:Upload the local function parameter to the
keypad
2:Download the keypad function parameter to
local address(including the motor parameters)
3:Download the keypad function parameter to
Parameter
P07.01 local address (excluding the motor parameter of 0 ◎
copy
P02 group)
4:Download the keypad function parameters to
local address (only for the motor parameter of
P02 group)
Note: After completing the 1~4 operation, the
parameter will come back to 0 automatically, the
function of upload and download excludes the
factory parameters of P29.
0:No function
1: Jogging. Press QUICK/JOG to begin the
jogging running.
2: Shift the display state by the shifting key.
Press QUICK/JOGto shift the displayed function
code from right to left.
3: Shift between forward rotations and reverse
QUICK/JOG
rotations. Press QUICK/JOG to shift the direction
P07.02 function 1 ◎
of the frequency commands. This function is only
selection
valid in the keypad commands channels.
4: Clear UP/DOWN settings. Press QUICK/JOG
to clear the set value of UP/DOWN.
5: Coast to stop. Press QUICK/JOG to coast to
stop.
6: Shift the running commands source. Press
QUICK/JOG to shift the running commands
63
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
source.
7:Quick commission mode(committee according
to the non-factory parameter)
Note: Press QUICK/JOGto shift between
forward rotation and reverse rotation, the inverter
does not record the state after shifting during
powering off. The inverter will run according to
parameter P00.13 during next powering on.
When P07.02=6, set the shifting sequence of
Shifting running command channels.
sequence 0:Keypad control→terminals control
P07.03 selection of →communication control 0 ○
QUICK/JOG 1:Keypad control←→terminals control
commands 2:Keypad control←→communication control
3:Terminals control←→communication control
STOP/RST is valid for stop function. STOP/RST
is valid in any state for the fault reset.
0:Only valid for the keypad control
STOP/RST
P07.04 1:Both valid for keypad and terminals control 0 ○
stop function
2:Both valid for keypad and communication
control
3:Valid for all control modes
0x0000~0xFFFF
BIT0:running frequency (Hz on)
BIT1:set frequency(Hz flickering)
BIT2:bus voltage (Hz on)
BIT3:output voltage(V on)
BIT4:output current(A on)
BIT5:running rotation speed (rpm on)
BIT6:output power(% on)
Parameters BIT7:output torque(% on)
P07.05 0x03FF ○
state 1 BIT8:PID reference(% flickering)
BIT9:PID feedback value(% on)
BIT10:input terminals state
BIT11:output terminals state
BIT12:torque set value(% on)
BIT13:pulse counter value
BIT14:length value
BIT15:PLC and the current stage in multi-step
speed
P07.06 Parameters 0x0000~0xFFFF 0x0000
64
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
state 2 BIT0: AI1 (V on) (The inverter(≤15kW) can be
set by the analog potentiometer on the keypad
and AI1 setting is not available for the device
which is 18.5kW or higer than 18.5 kW)
BIT1: AI2 (V on)
BIT2: AI3 (V on)
BIT3: HDI frequency
BIT4: motor overload percentage (% on)
BIT5: the inverter overload percentage (% on)
BIT6: ramp frequency given value(Hz on)
BIT7: linear speed
BIT8: AC inlet current (A on)
BIT9: upper limit frequency (Hz on)
0x0000~0xFFFF
BIT0:set frequency
(Hz on, frequency flickering slowly)
BIT1:bus voltage (V on)
BIT2:input terminals state
BIT3:output terminals state
BIT4:PID reference (% flickering)
BIT5:PID feedback value(% flickering)
BIT6:reserved
The BIT7:analog AI1 value(V on) (The inverter(≤
P07.07 parameter in 15kW) can be set by the analog potentiometer on 0x00FF ○
the stop state the keypad and AI1 setting is not available for the
device which is 18.5kW or higer than 18.5 kW)
BIT8:analog AI2 value(V on)
BIT9: analog AI3 value(V on)
BIT10:high speed pulse HDI frequency
BIT11:PLC and the current step in multi-step
speed
BIT12:pulse counters
BIT13:length value
BIT14: upper limit frequency (Hz on)
Frequency 0.01~10.00
P07.08 1.00 ○
coefficient Displayed frequency=running frequency* P07.08
Rotation 0.1~999.9%
P07.09 speed Mechanical rotation speed =120*displayed 100.0% ○
coefficient running frequency×P07.09/motor pole pairs
Linear speed 0.1~999.9%
P07.10 1.0% ○
coefficient Linear speed= Mechanical rotation
65
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
speed×P07.10
Rectifier
bridge
P07.11 0~100.0℃ ●
module
temperature
Converter
P07.12 module 0~100.0℃ ●
temperature
Software
P07.13 1.00~655.35 ●
version
Local
P07.14 accumulative 0~65535h ●
running time
High bit of
Display the power used by the inverter.
P07.15 power ●
The power consumption of the inverter
consumption
=P07.15*1000+P07.16
Low bit of
Setting range of P07.15: 0~65535 kWh (*1000)
P07.16 power ●
Setting range of P07.16: 0.0~999.9 kWh
consumption
0: G type
P07.17 Inverter type ●
1: P type
The rated
P07.18 power of the 0.4~3000.0kW ●
inverter
The rated
P07.19 voltage of the 50~1200V ●
inverter
The rated
P07.20 current of the 0.1~6000.0A ●
inverter
Factory bar
P07.21 0x0000~0xFFFF ●
code 1
Factory bar
P07.22 0x0000~0xFFFF ●
code 2
Factory bar
P07.23 0x0000~0xFFFF ●
code 3
Factory bar
P07.24 0x0000~0xFFFF ●
code 4
Factory bar
P07.25 0x0000~0xFFFF ●
code 5
66
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
Factory bar
P07.26 0x0000~0xFFFF ●
code 6
0:No fault
1:IGBT U phase protection(OUt1)
2:IGBT V phase protection(OUt2)
3:IGBT W phase protection(OUt3)
4:OC1
Current fault
P07.27 5:OC2 ●
type
6:OC3
7:OV1
8:OV2
9:OV3
10:UV
11:Motor overload(OL1)
12:The inverter overload(OL2)
13:Input side phase loss(SPI)
14:Output side phase loss(SPO)
15:Overheat of the rectifier module(OH1)
16:Overheat fault of the inverter module(OH2)
Previous fault 17:External fault(EF)
P07.28 18:485 communication fault(CE) ●
type
19:Current detection fault(ItE)
20:Motor antotune fault(tE)
21:EEPROM operation fault(EEP)
22:PID response offline fault(PIDE)
23:Braking unit fault(bCE)
24:Running time arrival(END)
Previous 2
P07.29 25:Electrical overload(OL3) ●
fault type
26:Panel communication fault(PCE)
Previous 3
P07.30 27:Parameter uploading fault (UPE) ●
fault type
28:Parameter downloading fault(DNE)
Previous 4 32:Grounding short circuit fault 1(ETH1)
P07.31 ●
fault type 33:Grounding short circuit fault 2(ETH2)
Previous 5 36: Undervoltage fault(LL)
P07.32 ●
fault type
Running
P07.33 frequency at 0.00Hz ●
current fault
Ramp
P07.34 0.00Hz
reference
67
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
frequency at
current fault
Output
P07.35 voltage at the 0V
current fault
Output
P07.36 current at 0.0A
current fault
Bus voltage
P07.37 at current 0.0V
fault
The Max.
temperature
P07.38 0.0℃
at current
fault
Input
terminals
P07.39 0 ●
state at
current fault
Output ●
terminals
P07.40 0
state at
current fault
Running ●
P07.41 frequency at 0.00Hz
previous fault
Ramp ●
reference
P07.42 0.00Hz
frequency at
previous fault
Output ●
P07.43 voltage at 0V
previous fault
The output ●
P07.44 current at 0.0A
previous fault
Bus voltage ●
P07.45 at previous 0.0V
fault
P07.46 The Max. 0.0℃ ●
68
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
temperature
at previous
fault
Input ●
terminals
P07.47 0
state at
previous fault
Output ●
terminals
P07.48 0
state at
previous fault
Runnig ●
frequency at
P07.49 0.00Hz
previous 2
fault
Output ●
voltage at
P07.50 0.00Hz
previous 2
faults
Output ●
current at
P07.51 0V
previous 2
faults
Output
current at
P07.52 0.0A ●
previous 2
fault
Bus voltage ●
P07.53 at previous 2 0.0V
fault
The Max. ●
temperature
P07.54 0.0℃
at previous 2
fault
Input ●
terminals
P07.55 state at 0
previous 2
fault
Output ●
P07.56 0
terminals
69
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
state at
previous 2
fault
P08 Group Enhanced function
Depend
P08.00 ACC time 2 on ○
model
Depend
P08.01 DEC time 2 on ○
Refer to P00.11 and P00.12 for detailed model
definition. Depend
P08.02 ACC time 3 on ○
Goodrive200A series define four groups of
model
ACC/DEC time which can be selected by P5
Depend
group. The first group of ACC/DEC time is the
P08.03 DEC time 3 on ○
factory default one. model
Setting range:0.0~3600.0s Depend
P08.04 ACC time 4 on ○
model
Depend
P08.05 DEC time 4 on ○
model
This parameter is used to define the reference
Jogging frequency during jogging.
P08.06 5.00Hz ○
frequency Setting range: 0.00Hz ~P00.03
(the Max. frequency)
The jogging ACC time means the time needed if Depend
Jogging ACC
P08.07 the inverter runs from 0Hz to the Max. on ○
time
Frequency. model
The jogging DEC time means the time needed if
Depend
Jogging DEC the inverter goes from the Max. Frequency
P08.08 on ○
time (P0.03) to 0Hz.
model
Setting range:0.0~3600.0s
Jumping
P08.09 When the set frequency is in the range of 0.00Hz ○
frequency 1
jumping frequency, the inverter will run at the
Jumping edge of the jumping frequency.
P08.10 frequency The inverter can avoid the mechanical resonance 0.00Hz ○
range 1 point by setting the jumping frequency. The
Jumping inverter can set three jumping frequency. But this
P08.11 0.00Hz ○
frequency 2 function will be invalid if all jumping points are 0.
Jumping
P08.12 0.00Hz ○
frequency
70
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
range 2
Jumping
P08.13 0.00Hz ○
frequency 3
Jumping
P08.14 frequency 0.00Hz ○
range 3
Setting range: 0.00Hz ~P00.03
(the Max. frequency)
Traverse This function applies to the industries where
P08.15 0.0% ○
range traverse and convolution function are required
Sudden such as textile and chemical fiber.
jumping The traverse function means that the output
P08.16 0.0% ○
frequency frequency of the inverter is fluctuated with the set
range frequency as its center. The route of the running
Traverse frequency is illustrated as below, of which the
P08.17 5.0s ○
boost time traverse is set by P08.15 and when P08.15 is set
as 0, the traverse is 0 with no function.
Function Default
Name Detailed instruction of parameters Modify
code value
The setting range of P08.16: 0.0~50.0%
(relative to the traverse range)
The setting range of P08.17: 0.1~3600.0s
The setting range of P08.18: 0.1~3600.0s
Setting The counter works by the input pulse signals of
P08.25 counting the HDI terminals. 0 ○
value When the counter achieves a fixed number, the
multi-function output terminals will output the
signal of “fixed counting number arrival” and the
counter go on working; when the counter
achieves a setting number, the multi-function
output terminals will output the signal of “setting
counting number arrival”, the counter will clear all
numbers and stop to recount before the next
pulse.
Reference The setting counting value P08.26 should be no
P08.26 counting more than the setting counting value P08.25. 0 ○
value The function is illustrated as below:
72
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
decreasing the load. And it is mainly used to balance the
ratio of the power when several inverters drive one load.
dropping Setting range:0.00~10.00Hz
control
FDT1 When the output frequency exceeds the
electrical corresponding frequency of FDT electrical level,
50.00
P08.32 level the multi-function digital output terminals will ○
Hz
detection output the signal of “frequency level detect FDT”
value until the output frequency decreases to a value
FDT1 lower than (FDT electrical level—FDT retention
retention detection value) the corresponding frequency,
P08.33 5.0% ○
detection the signal is invalid. Below is the waveform
value diagram:
FDT2
electrical
50.00
P08.34 level ○
Hz
detection
value
73
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
74
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
0: Low-speed carrier frequency limit mode 1, the
carrier frequency will limit to 2k if it exceeds 2k at
low speed
1:Low-speed carrier frequency limit mode 2, the
carrier frequency will limit to 4k if it exceeds 4k at
low speed
2: No limit
0x00~0x11
LED ones ◎
Over 0: Invalid
P08.41 commission 1: Valid 0x01
selection LED tens
0: Light overcommission
1: Heavy overcommission
0x000~0x1223
LED ones:frequency enable selection
0:Both ∧/∨ keys and digital potentiometer
adjustments are valid
1:Only ∧/∨ keys adjustment is valid
2:Only digital potentiometer adjustments is valid
3:Neither ∧/∨ keys nor digital potentiometer
adjustments are valid
LED tens: frequency control selection
0:Only valid when P00.06=0 or P00.07=0
Keypad data 1:Valid for all frequency setting manner
P08.42 0x0000 ○
control 2:Invalid for multi-step speed when multi-step
speed has the priority
LED hundreds: action selection during stopping
0:Setting is valid
1:Valid during running, cleared after stopping
2:Valid during running, cleared after receiving the
stop command
LED thousands: ∧/∨ keys and digital
potentiometer integral function
0:The integral function is valid
1:The integral function is invalid
Integral ratio
of the keypad
P08.43 0.01~10.00s 0.10s ○
potentiomete
r
P08.44 UP/DOWN 0x00~0x221 0x000 ○
75
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
terminals LED ones: frequency control selection
control 0:UP/DOWN terminals setting valid
1:UP/DOWN terminals setting valid
LED tens: frequency control selection
0:Only valid when P00.06=0 or P00.07=0
1:All frequency means are valid
2:When the multi-step are priority, it is invalid to
the multi-step
LED hundreds: action selection when stop
0:Setting valid
1: Valid in the running, clear after stop
2: Valid in the running, clear after receiving the
stop commands
UP terminals
frequency 0.50
P08.45 0.01~50.00Hz/s ○
increasing Hz/s
integral ratio
DOWN
terminals 0.50
P08.46 0.01~50.00 Hz/s ○
frequency Hz/s
integral ratio
0x000~0x111
LED ones: Action selection when power off.
0:Save when power off
1:Clear when power off
LED tens: Action selection when MODBUS set
Action when
frequency off
P08.47 the frequency 0x000 ○
0:Save when power off
setting is off
1:Clear when power off
LED hundreds:The action selection when other
frequency set frequency off
0:Save when power off
1:Clear when power off
High bit of This parameter is used to set the original value of
P08.48 initial power the power consumption. 0° ○
consumption The original value of the power consumption
Low bit of =P08.48*1000+ P08.49
P08.49 initial power Setting range of P08.48: 0~59999 kWh (k) 0.0° ○
consumption Setting range of P08.49:0.0~999.9 kWh
Magnetic flux This function code is used to enable magnetic
P08.50 0 ●
braking flux.
76
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
0: Invalid.
100~150: The bigger the coefficient, the stronger
the braking is.
This inverter is used to increase the magnetic flux
to decelerate the motor. The energy generated
by the motor during braking can be converter into
heat energy by increasing the magnetic flux.
The inverter monitors the state of the motor
continuously even during the magnetic flux
period. So the magnetic flux can be used in the
motor stop, as well as to change the rotation
speed of the motor. Its other advantages are:
Brake immediately after the stop command. It
does not need to wait the magnetic flux weaken.
Better cooling for motors. The current of the
stator other than the rotor increases during
magnetic flux braking, while the cooling of the
stator is more effective than the rotor.
Input power This function code is used to adjust the displayed
P08.51 factor of the current of the AC input side. 0.56 ○
inverter Setting range:0.00~1.00
P09 Group PID control
When the frequency command selection
(P00.06, P00. 07) is 7 or the voltage setting
channel selection (P04.27) is 6, the running
mode of the inverter is procedure PID controlled.
The parameter determines the target reference
channel during the PID procures.
0:Keypad digital reference(P09.01)
1:Analog channel AI1 reference (The inverter
PID (≤15kW) can be set by the analog potentiometer
P09.00 reference on the keypad and AI1 setting is not available for 0 ○
source the device which is 18.5kW or higer than 18.5kW)
2:Analog channel AI2 reference
3:Analog channel AI3 set
4:High speed pulse HDI set
5:Multi-step speed set
6:MODBUS communication set
The setting target of procedure PID is a relative
one, 100% of the setting equals to 100% of the
response of the controlled system.
77
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
The system is calculated according to the relative
value (0~100.0%).
Note:
Multi-step speed reference, it is realized by
setting P10 group parameters.
When P09.00=0, set the parameter whose basic
Keypad PID
P09.01 value is the feedback value of the system. 0.0% ○
preset
The setting range:-100.0%~100.0%
Select the PID channel by the parameter.
0:Analog channel AI1 feedback (The inverter(≤
15kW) can be set by the analog potentiometer on
the keypad and AI1 setting is not available for the
device which is 18.5kW or higer than 18.5 kW)
PID feedback 1:Analog channel AI2 feedback
P09.02 0 ○
source 2:Analog channel AI3 feedback
3:High speed HDI feedback
4:MODBUS communication feedback
Note: The reference channel and the feedback
channel can not coincide, otherwise, PID can not
control effectively.
0: PID output is positive: When the feedback
signal exceeds the PID reference value, the
output frequency of the inverter will decrease to
balance the PID. For example, the strain PID
PID output control during wrap-up
P09.03 0 ○
feature 1: PID output is negative: When the feedback
signal is stronger than the PID reference value,
the output frequency of the inverter will increase
to balance the PID. For example, the strain PID
control during wrap-down
The function is applied to the proportional gain P
of PID input.
P determines the strength of the whole PID
adjuster. The parameter of 100 means that when
Proportional
P09.04 the offset of PID feedback and reference value is 1.00 ○
gain (Kp)
100%, the adjusting range of PID adjustor is the
Max. Frequency (ignoring integral function and
differential function).
The setting range:0.00~100.00
Integral This parameter determines the speed of PID
P09.05 0.10s ○
time(Ti) adjustor to carry out integral adjustment on the
78
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
deviation of PID feedback and reference.
When the deviation of PID feedback and
reference is 100%, the integral adjustor works
continuously after the time (ignoring the
proportional effect and differential effect) to
achieve the Max. Frequency (P00.03) or the
Max. Voltage (P04.31). Shorter the integral time,
stronger is the adjustment
Setting range: 0.01~10.00s
This parameter determines the strength of the
change ratio when PID adjustor carries out
integral adjustment on the deviation of PID
feedback and reference.
If the PID feedback changes 100% during the
Differential
P09.06 time, the adjustment of integral adjustor (ignoring 0. 00s ○
time(Td)
the proportional effect and differential effect) is
the Max. Frequency (P00.03) or the Max. Voltage
(P04.31). Longer the integral time, stronger is the
adjusting.
Setting range: 0.00~10.00s
This parameter means the sampling cycle of the
feedback. The modulator calculates in each
Sampling
P09.07 sampling cycle. The longer the sapling cycle is, 0.100s ○
cycle(T)
the slower the response is.
Setting range: 0.000~10.000s
The output of PID system is relative to the
maximum deviation of the close loop reference.
As shown in the diagram below, PID adjustor
stops to work during the deviation limit. Set the
function properly to adjust the accuracy and
stability of the system.
PID control
P09.08 0.0% ○
deviation limit
Setting range:0.0~100.0%
79
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
Output upper These parameters are used to set the upper and
P09.09 100.0% ○
limit of PID lower limit of the PID adjustor output.
100.0 % corresponds to Max. frequency or the
Output lower Max. voltage of ( P04.31)
P09.10 0.0% ○
limit of PID Setting range of P09.09: P09.10~100.0%
Setting range of P09.10: -100.0%~P09.09
Feedback Set the PID feedback offline detection value,
offline when the detection value is smaller than or equal
P09.11 0.0% ○
detection to the feedback offline detection value, and the
value lasting time exceeds the set value in P09.12, the
inverter will report “PID feedback offline fault” and
the keypad will display PIDE.
Feedback
offline
P09.12 1.0s ○
detection
time
Function Default
Name Detailed instruction of parameters Modify
code value
forcedly.
1:Opposite to the setting direction
LED hundreds: P00.08 is 0
0: Limit to the maximum frequency
1: Limit to frequency A
LED thousands:
0:A+B frequency, the buffer of A frequency is
invalid
1:A+B frequency, the buffer of A frequency is
valid
ACC/DEC is determined by ACC time 4 of
P08.04
Proportional
gain at low
P09.14 0.00~100.00 1.00 ○
frequency
(Kp)
PID
command of
P09.15 0.0~1000.0s 0.0s ○
ACC/DEC
time
PID output
P09.16 0.000~10.000s 0.000s ○
filter time
P10 Group Simple PLC and multi-step speed control
0: Stop after running once. The inverter has to be
commanded again after finishing a cycle.
1: Run at the final value after running once. After
finish a signal, the inverter will keep the running
P10.00 Simple PLC 0 ○
frequency and direction of the last run.
2: Cycle running. The inverter will keep on
running until receiving a stop command and then,
the system will stop.
0: Power loss without memory
Simple PLC
P10.01 1:Power loss memory;PLC record the running 0 ○
memory
step and frequency when power loss.
Multi-step
100.0% of the frequency setting corresponds to
P10.02 0.0% ○
speed 0 the Max. frequency P00.03.
The running When selecting simple PLC running, set
P10.03 time of step P10.02~P10.33 to define the running frequency 0.0s ○
0 and direction of all steps.
81
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
Multi-stepNote: The symbol of multi-step determines the
P10.04 0.0% ○
speed 1 running direction of simple PLC. The negative
The running value means reverse rotation.
P10.05 0.0s ○
time of step 1
Multi-step
P10.06 0.0% ○
speed 2
The running
P10.07 0.0s ○
time of step 2
Multi-step
P10.08 0.0% ○
speed 3
The running Multi-step speeds are in the range of --fmax~fmax
P10.09 0.0s ○
time of step 3 and it can be set continuously.
Multi-step Goodrive200A series inverters can set 16 steps
P10.10 speed, selected by the combination of multi-step 0.0% ○
speed 4
The running terminals 1~4, corresponding to the speed 0 to
P10.11 0.0s ○
time of step 4 speed 15.
Multi-step
P10.12 0.0% ○
speed 5
The running
P10.13 0.0s ○
time of step 5
Multi-step
P10.14 0.0% ○
speed 6
The running
P10.15 0.0s ○
time of step 6
Multi-step
P10.16 0.0% ○
speed 7
The running
P10.17 0.0s ○
time of step 7 When S1=S2=S3=S4=OFF, the frequency input
Multi-step manner is selected via code P00.06 or P00.07.
P10.18 When all S1=S2=S3=S4 terminals aren’t off, it 0.0% ○
speed 8
The running runs at multi-step which takes precedence of
P10.19 0.0s ○
time of step 8 keypad, analog value, high-speed pulse, PLC,
Multi-step communication frequency input. Select at most
P10.20 16 steps speed via the combination code of S1, 0.0% ○
speed 9
S2, S3, and S4.
The running
P10.21 The start-up and stopping of multi-step running is 0.0s ○
time of step 9
determined by function code P00.06, the
Multi-step
P10.22 relationship between S1,S2,S3,S4 terminals and 0.0% ○
speed 10
multi-step speed is as following:
The running
P10.23 S1 OFF ON OFF ON OFF ON OFF ON 0.0s ○
time of step
82
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
10 S2 OFF OFF ON ON OFF OFF ON ON
Multi-step S3 OFF OFF OFF OFF ON ON ON ON
P10.24 0.0% ○
speed 11 S4 OFF OFF OFF OFF OFF OFF OFF OFF
The running Step 0 1 2 3 4 5 6 7
P10.25 time of step S1 OFF ON OFF ON OFF ON OFF ON 0.0s ○
11 S2 OFF OFF ON ON OFF OFF ON ON
Multi-step S3 OFF OFF OFF OFF ON ON ON ON
P10.26 0.0% ○
speed 12 S4 ON ON ON ON ON ON ON ON
The running Step 8 9 10 11 12 13 14 15
P10.27 time of step Setting range of P10.(2n,1<n<17): 0.0s ○
12 -100.0~100.0%
Multi-step Setting range of
P10.28 0.0% ○
speed 13 P10.(2n+1,1<n<17):0.0~6553.5s(min)
The running
P10.29 time of step 0.0s ○
13
Multi-step
P10.30 0.0% ○
speed 14
The running
P10.31 time of step 0.0s ○
14
Multi-step
P10.32 0.0% ○
speed 15
The running
P10.33 time of step 0.0s ○
15
Simple PLC Below is the detailed instruction:
0~7 step Functio ACC/DE ACC/DE ACC/DE ACC/DE
P10.34 Binary bit Step 0x0000 ○
ACC/DEC n code C0 C1 C2 C3
BIT3 BIT2 1 00 01 10 11
BIT5 BIT4 2 00 01 10 11
BIT13 BIT12 6 00 01 10 11
BIT15 BIT14 7 00 01 10 11
83
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
BIT1 BIT0 8 00 01 10 11
BIT3 BIT2 9 00 01 10 11
BIT5 BIT4 10 00 01 10 11
BIT7 BIT6 11 00 01 10 11
P10.35
BIT9 BIT8 12 00 01 10 11
BIT11 BIT10 13 00 01 10 11
BIT13 BIT12 14 00 01 10 11
BIT15 BIT14 15 00 01 10 11
84
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
Sudden
power loss 0: Disable
P11.01 0 ○
frequency 1: Enable
decrease
Setting range: 0.00Hz/s~P00.03(max. frequency)
After the power loss of the grid, the bus voltage
drops to the sudden frequency-decreasing point,
the inverter begin to decrease the running
frequency at P11.02, to make the inverter
generate power again. The returning power can
maintain the bus voltage to ensure a rated
running of the inverter until power recovery.
Frequency
Voltage degree 220V 380V 660V
decrease
Frequency decrease 10.00
P11.02 ratio of ○
point at sudden power 260V 460V 800V Hz/s
sudden
loss
power loss
Note:
1. Adjust the parameter properly to avoid the
stopping caused by inverter protection during the
switching of the grid.
2. Disable input phase loss protection to enable
this function.
0:Disable
1:Enable
Overvoltage
P11.03 stall 1 ○
protection
Protection
voltage at 120~150%(standard bus voltage) (380V) 136%
P11.04 ○
overvoltage
stall 120~150%(standard bus voltage) (220V) 120%
Current limit The actual increasing ratio is less than the ratio
P11.05 action of output frequency because of the big load 01 ◎
selection during ACC running. It is necessary to take
measures to avoid overcurrent fault and the G:
Automatic inverter trips. 160.0%
P11.06 ◎
current limit During the running of the inverter, this function P:
will detect the output current and compare it with 120.0%
85
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
the limit defined in P11.06. If it exceeds the level,
the inverter will run at stable frequency in ACC
running, or the inverter will derate to run during
the constant running. If it exceeds the level
continuously, the output frequency will keep on
decreasing to the lower limit. If the output current
is detected to be lower than the limit level, the
inverter will accelerate to run.
The
decreasing 10.00
P11.07 ◎
ratio during Hz/s
current limit
86
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
the rated current of the motor
1:Overload pre-alarm of the inverter, comply with
the rated current of the inverter
LED tens:
0:The inverter continues to work after underload
pre-alarm
1:The inverter continues to work after underload
pre-alarm and the inverter stops running after
overload fault
2: The inverter continues to work after overload
pre-alarm and the inverter stops running after
underload fault
3. The inverter stops when overloading or
underloading.
LED hundreds :
0:Detection all the time
1:Detection in constant running
Setting range of P11.09: P11.11~200%
Setting range of P11.10: 0.1~3600.0s
Detection
level of the If the inverter current or the output current is
P11.11 50% ○
underload lower than P11.11, and its lasting time is beyond
pre-alarm P11.12, the inverter will output underload
Detection pre-alarm.
time of the Setting range of P11.11: 0~P11.09
P11.12 1.0s ○
underload Setting range of P11.12: 0.1~3600.0s
pre-alarm
Select the action of fault output terminals on
undervoltage and fault reset.
0x00~0x11
Output
LED ones:
terminal
P11.13 0:Action under fault undervoltage 0x00 ○
action during
1:No action under fault undervoltage
fault LED tens:
0:Action during the automatic reset
1:No action during the automatic reset
0x00~0x11
LED ones:Voltage drop frequency-decreasing
Extension
selection
P11.16 functions 00 ○
0: Voltage drop frequency-decreasing selection
selection disable
1: Voltage drop frequency-decreasing selection
87
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
enable
LED tens: Step 2 ACC/DEC time option
0: Step 2 ACC/DEC time option disable
1: Step 2 ACC/DEC time option enable,when
running frequency more than P08.36, ACC/DEC
time switch to step 2 ACC/DEC time
P13 Group Reserved
Braking When P01.00=0 during the starting of the
P13.13 current of inverter, set P13.14 to a non-zero value to enter 0.0%
short-circuit the short circuit braking. ○
When the running frequency is lower than P01.09
Braking
during the stopping of the inverter, set 13.15 to a
retention time non-zero value to enter into stopping short
P13.14 0.00s
before circuited braking and then carry out the DC
○
starting braking at the time set by P01.12 (refer to the
instruction of P01.09~P01.12) .
The braking Setting range of P13.13: 0.0~150.0%
retention time (the inverter)
P13.15 0.00s
when Setting range of P13.14: 0.00~50.00s
stopping ○
Setting range of P13.15: 0.00~50.00s
P14 Group Serial communication
The setting range:1~247
When the master is writing the frame, the
communication address of the slave is set to 0;
the broadcast address is the communication
Local address. All slaves on the MODBUS fieldbus can
P14.00 communicati receive the frame, but the salve doesn’t answer. 1 ○
on address The communication address of the drive is
unique in the communication net. This is the
fundamental for the point to point communication
between the upper monitor and the drive.
Note: The address of the slave cannot set to 0.
Set the digital transmission speed between the
upper monitor and the inverter.
0:1200BPS
1:2400BPS
Communicati
P14.01 2:4800BPS 4 ○
on baud ratio
3:9600BPS
4:19200BPS
5:38400BPS
6:57600BPS
88
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
7:115200BPS
Note: The baud rate between the upper monitor
and the inverter must be the same. Otherwise,
the communication is not applied. The bigger the
baud rate, the quicker the communication speed.
The data format between the upper monitor and
the inverter must be the same. Otherwise, the
communication is not applied.
0: No check (N,8,1) for RTU
1: Even check (E,8,1) for RTU
2: Odd check (O,8,1) for RTU
3:No check (N,8,2) for RTU
4: Even check (E,8,2) for RTU
5: Odd check(O,8,2) for RTU
6: No check (N,7,1) for ASCII
Digital bit
P14.02 7: Even check (E,7,1) for ASCII 1 ○
checkout
8: Odd check (O,7,1) for ASCII
9:No check (N,7,2) for ASCII
10: Even check (E,7,2) for ASCII
11: Odd check(O,7,2) for ASCII
12: No check (N,8,1) for ASCII
13: Even check (E,8,1) for ASCII
14: Odd check (O,8,1) for ASCII
15:No check (N,8,2) for ASCII
16: Even check (E,8,2) for ASCII
17: Odd check(O,8,2) for ASCII
0~200ms
It means the interval time between the interval
time when the drive receive the data and sent it
to the upper monitor. If the answer delay is
Answer shorter than the system processing time, then the
P14.03 5 ○
delay answer delay time is the system processing time,
if the answer delay is longer than the system
processing time, then after the system deal with
the data, waits until achieving the answer delay
time to send the data to the upper monitor.
0.0(invalid), 0.1~60.0s
Fault time of When the function code is set as 0.0, the
P14.04 communicati communication overtime parameter is invalid. 0.0s ○
on overtime When the function code is set as non-zero, if the
interval time between two communications
89
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
exceeds the communication overtime, the
system will report “485 communication faults”
(CE).
Generally, set it as invalid; set the parameter in
the continuous communication to monitor the
communication state.
0:Alarm and stop freely
1:No alarm and continue to run
Transmission
2:No alarm and stop according to the stop means
P14.05 fault 0 ○
(only under the communication control)
processing
3:No alarm and stop according to the stop means
(under all control modes)
LED ones:
0: Operation with response: the drive will respond
to all reading and writing commands of the upper
monitor.
1:Operation without response;The drive only
Communicati
responds to the reading command other than the
P14.06 on 0x00 ○
writing command of the drive. The
processing
communication efficiency can be increased by
this method.
LED tens:
0: Communication encrypting valid
1: Communication encrypting invalid
P16 Group Ethernet function
P17 Group Monitoring function
Setting Display current set frequency of the inverter
P17.00 ●
frequency Range: 0.00Hz~P00.03
Output Display current output frequency of the inverter
P17.01 ●
frequency Range: 0.00Hz~P00.03
Ramp Display current ramp reference frequency of the
P17.02 reference inverter ●
frequency Range: 0.00Hz~P00.03
Output Display current output voltage of the inverter
P17.03 ●
voltage Range: 0~1200V
Output Display current output current of the inverter
P17.04 ●
current Range: 0.0~3000.0A
Display the rotation speed of the motor.
P17.05 Motor speed ●
Range: 0~65535RPM
P17.08 Motor power Display current motor power ●
90
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
Range:-300~300%
Output Display the current output torque of the inverter.
P17.09 ●
torque Range: -250.0~250.0%
Evaluated
Evaluated frequency of motor rotor
P17.10 motor ●
Range: 0.00Hz~ P00.03
frequency
DC bus Display current DC bus voltage of the inverter
P17.11 ●
voltage Range: 0.0~2000.0V
Display current Switch input terminals state of the
inverter
ON-OFF
BIT8 BIT7 BIT6 BIT5
input
P17.12 HDI S8 S7 S6 ●
terminals
BIT4 BIT3 BIT2 BIT1 BIT0
state
S5 S4 S3 S2 S1
Range: 0000~00FF
Display current Switch output terminals state of
ON-OFF
the inverter
output
P17.13 BIT3 BIT2 BIT1 BIT0 ●
terminals
RO2 RO1 HDO Y
state
Range: 0000~000F
Display the adjustment through the keypad of the
Digital
P17.14 inverter. ●
adjustment
Range : 0.00Hz~P00.03
Display the torque given, the percentage to the
torque current rated torque of the motor.
P17.15 ●
reference Setting range: -300.0%~300.0%
(the rated current of the motor)
Display the current linear speed of the inverter.
P17.16 Linear speed ●
Range: 0~65535
Display the current length of the inverter.
P17.17 Length ●
Range: 0~65535
Display the current counting number of the
Counting
P17.18 inverter. ●
value
Range: 0~65535
The inverter(≤15kW) can be set by the analog
potentiometer on the keypad and AI1 setting is
AI1 input not available for the device which is 18.5kW or
P17.19 ●
voltage higer than 18.5 kW.
Display analog AI1 input signal
Range: 0.00~10.00V
91
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
AI2 input Display analog AI2 input signal
P17.20 ●
voltage Range: 0.00~10.00V
AI3 input Display analog AI2 input signal
P17.21 ●
voltage Range: -10.00~10.00V
HDI input Display HDI input frequency
P17.22 ●
frequency Range: 0.000~50.000kHz
PID
Display PID reference value
P17.23 reference ●
Range: -100.0~100.0%
value
PID feedback Display PID response value
P17.24 ●
value Range: -100.0~100.0%
Power factor Display the current power factor of the motor.
P17.25 ●
of the motor Range: -1.00~1.00
Current Display the current running time of the inverter.
P17.26 ●
running time Range:0~65535min
Simple PLC
and the
Display simple PLC and the current step of the
current step
P17.27 multi-step speed ●
of the
Range: 0~15
multi-step
speed
AC input Display the input current in AC side.
P17.35 ●
current Range: 0.0~5000.0A
Display the output torque. Positive value is in the
Output electromotion state, and negative is in the power
P17.36 ●
torque generating state.
Range : -3000.0Nm~3000.0Nm
Counting of
P17.37 the motor 0~100 (100 is OL1 fault) ●
overload
P17.38 PID output -100.00~100.00% 0.00% ●
Wrong
P17.39 download of 0.00~99.99 0.00 ●
parameters
P24 Group Water supply
Water
0: Disabled
P24.00 supply 0 ◎
1: Enabled
selection
Press 0: AI1 setting value (The inverter(≤15kW) can be
P24.01 0 ○
feedback set by the analog potentiometer on the keypad
92
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
source and AI1 setting is not available for the device
which is 18.5kW or higer than 18.5 kW)
1: AI2 setting value
2: AI3 setting value
3: HDI setting value
Hibernation 0: Hibernate as the setting frequency﹤P24.03
P24.02 0 ◎
check 1: Hibernate as the feedback pressure﹥P24.04
Starting
frequency of 10.00
P24.03 0.00~P0.03(the Max. frequency) ○
the Hz
hibernation
Starting
P24.04 pressure of 0.00~100.0% 50.0% ○
hibernation
Hibernation
P24.05 0.0~3600.0s 5.0s ○
delay time
Hibernation 0: Awake as the setting frequency﹥P24.07
P24.06 0 ◎
awake 1: Awake as the feedback pressure﹤P24.08
Awake 20.00
P24.07 0.00~P0.03(the Max. frequency) ○
frequency Hz
Setting value
P24.08 of hibernation 0.00~100.0% 10.0% ○
awake
Mini
P24.09 hibernation 0.0~3600.0s 5.0s ○
time
Valid P24.10~P24.12 can make three motors to form a
P24.10 auxiliary simple system of water supply. 0 ○
motor
P24.11 Start/stop
delay time of
5.0s ○
auxiliary
motor 1
P24.12 Start/stop
delay time of
auxiliary
motor 2 5.0s ○
93
Goodrive200A inverters Function parameters
Function Default
Name Detailed instruction of parameters Modify
code value
0: No auxiliary motor
1: Auxiliary motor 1 valid
2: Auxiliary motor 2 valid
3: Auxiliary motor 1 and 2 valid
Setting range of P24.10: 0.0~3600.0s
Setting range of P24.11: 0.0~3600.0s
94
Goodrive200A inverters Basic operation instruction
Below diagram shows the first operation: (take motor 1 as the example)
95
Goodrive200A inverters Basic operation instruction
Note: If fault occurs, please do as the “Fault Tracking”. Estimate the fault reason and settle
the issue.
Besides P00.01 and P00.02, terminal command setting can also used to set the running
command channel.
96
Goodrive200A inverters Basic operation instruction
Multi-function Multi-function
Current running Multi-function
terminal 37 terminal 38
command terminal 36
Shifting the Shifting the
channel Shifting the
command to command to
P00.01 command to keypad
communication communication
Communication
Keypad running Terminal running
/ running command
command channel command channel
channel
Communication
Terminal running Keypad running
/ running command
command channel command channel
channel
Communication
Keypad running Terminal running
running command /
command channel command channel
channel
Note: “/” means the multi-function terminal is invalid on the current reference channel.
Relative parameters table:
97
Goodrive200A inverters Basic operation instruction
98
Goodrive200A inverters Basic operation instruction
The control performance of the inverter is based on the established accurate motor model.
The user has to carry out the motor autotune before first running (take motor 1 as the
example).
Note:
1. Set the motor parameters according to the name plate of the motor.
2. During the motor autotune, de-couple the motor form the load if rotation autotune is
selected to make the motor is in a static and empty state, otherwise the result of autotune is
incorrect. The asynchronous motors can autotune the parameters of P02.06~P02.10.
3. During the motor autotune 1, do not to de-couple the motor form the load if static autotune
is selected. Because only some parameters of the motor are involved, the control
performance is not as better as the rotation autotune. The asynchronous motors can
autotune the parameters of P02.06~P02.10.
4. During the motor autotune 2, do not to de-couple the motor form the load if static autotune
is selected. Because only some parameters of the motor are involved, the control
performance is not as better as the rotation autotune. The asynchronous motors can
99
Goodrive200A inverters Basic operation instruction
autotune the parameters of P02.06~P02.08. It is suitable in the cases which SVPWM control
is applied.
DE
AC
C
C
DE
AC
2. The starting logic figure of starting after the restarting function becomes valid during the
normal powering on
3. The starting logic figure of starting after the automatic fault reset
100
Goodrive200A inverters Basic operation instruction
101
Goodrive200A inverters Basic operation instruction
Goodrive200A series inverters support the shifting between different reference channels and
the detailed shifting rules is as below:
Multi-function Multi-function Multi-function terminal
Current
terminal function 13 terminal function 14 function 15
reference
Shifting from A Shifting from Shifting from
channel
channel to B combination setting combination setting to
P00.09
channel to A channel B channel
A B / /
B A / /
A+B / A B
A-B / A B
Max(A,B) / A B
Min(A,B) / A B
Note: “/” means the multi-function terminal is invalid under the current reference channel.
When select multi-function terminal UP (10) and DOWN (11) to set the internal assistant
frequency, P08.44 and P08.45 can be set to increase or decrease the set frequency quickly.
102
Goodrive200A inverters Basic operation instruction
103
Goodrive200A inverters Basic operation instruction
P10.02 multi-stage speed 0 BIT0
P10.03 the running time of stage 0 BIT1 P10.34
Terminal function 16
Multi-stage speed OFF ON OFF ON OFF ON OFF ON The ACC/DEC time selection
terminal 1
of Stage 0~7 of PLC
Terminal function 17 P10.04 multi-stage speed 1 BIT2
Multi-stage speed OFF OFF ON ON ON OFF OFF ON
P10.05 the running time of stage 1 BIT3
terminal 21
Terminal function 18
Multi-stage speed OFF OFF OFF OFF ON ON ON ON 00 P00.10 ACC time 1
terminal 3 P10.06 multi-stage speed 2 BIT4 P00.12 DEC time 1
P10.07 the running time of stage 2 BIT5
Terminal function 19
Multi-stage speed OFF OFF OFF OFF OFF OFF OFF OFF
terminal 4
01 P08.00 ACC time 2
P10.08 multi-stage speed 3 BIT6 P08.01 DEC time 2
Multi-stage 0 1 2 3 4 5 6 7
P10.09 the running time of stage 3 BIT7
speed
Multi-stage
speed 0
Multi-stage P10.14 multi-stage speed 6 BIT12
speed 1 P10.15 the running time of stage 6 BIT13
Terminal function 18
Multi-stage speed 00
terminal 3 P00.10 ACC time 1
P10.22 multi-stage speed 10 P00.12 DEC time 1
BIT4
P10.23 the running time of stage
Terminal function 19 BIT5
10
Multi-stage speed
terminal 1
01 P08.00 ACC time 2
P10.24 multi-stage speed 11 P08.01 DEC time 2
BIT6
P10.25 the running time of stage
BIT7
11
Terminal function 16
Multi-stage speed OFF ON OFF ON OFF ON OFF ON 10 P08.02 ACC time 3
terminal 1 P10.26 multi-stage speed 12 P08.03 DEC time 3
BIT8
P10.27 the running time of stage
12 BIT9
Terminal function 17
Multi-stage speed OFF OFF ON ON ON OFF OFF ON
terminal 2
11 P08.04 ACC time 4
Terminal function 18 P10.28 multi-stage speed 13 P08.15 DEC time 4
BIT10
Multi-stage speed OFF OFF OFF OFF ON ON ON ON P10.29 the running time of stage BIT11
terminal 3 13
Terminal function 19
Multi-stage speed ON ON ON ON ON ON ON ON
terminal 4 P10.30 multi-stage speed 14
BIT12
P10.31 the running time of stage
BIT13
14
Multi-stage 8 9 10 11 12 13 14 15
speed
104
Goodrive200A inverters Basic operation instruction
When P00.06, P00. 07=7 or P04.27=6, the running mode of the inverter is procedure PID
control.
7.15.1 General steps of PID parameters setting:
a Ensure the gain P
When ensure the gain P, firstly cancel the PID integration and derivation (set Ti=0 and Td=0,
see the PID parameter setting for detailed information) to make proportional adjustment is
the only method to PID. Set the input as 60%~70% of the permitted Max. Value and
increase gain P from 0 until the system vibration occurs, vice versa, and record the PID
value and set it to 60%~70% of the current value. Then the gain P commission is finished.
b Ensure the integration time
After ensuring the gain P, set an original value of a bigger integration time and decrease it
until the system vibration occurs, vice versa, until the system vibration disappear. Record the
Ti and set the integration time to 150%~180% of the current value. Then integration time
commission is finished.
c Ensure the derivation time
Generally, it is not necessary to set Td which is 0.
If it needs to be set, set it to 30% of the value without vibration via the same method with P
and Ti.
d Commission the system with and without load and then adjust the PID parameter until it is
available.
7.15.2 PID inching
After setting the PID control parameters, inching is possible by following means:
Control the overshoot
Shorten the derivation time and prolong the integration time when overshoot occurs.
105
Goodrive200A inverters Basic operation instruction
107
Goodrive200A inverters Fault tracking
Fault Tracking 8
108
Goodrive200A inverters Fault tracking
Fault code Fault type Possible cause What to do
Over-current when The acceleration or Increase the ACC time
OC1
acceleration deceleration is too fast Check the input power
Over-current when The voltage of the grid is Select the inverter with a
OC2
deceleration too low larger power
The power of the inverter Check if the load is short
is too low circuited (the grounding
The load transients or is short circuited or the wire
abnormal short circuited) or the
Over-current when The grounding is short rotation is not smooth
OC3 constant speed circuited or the output is Check the output
running phase loss configuration.
There is strong external Check if there is strong
interference interference
The overvoltage stall Check the setting of
protection is not open relative function codes
Over-voltage Check the input power
OV1
when acceleration Check if the DEC time of
Over-voltage the load is too short or the
OV2 The input voltage is
when deceleration inverter starts during the
abnormal
rotation of the motor or it
There is large energy
needs to add the dynamic
feedback
Over-voltage bracking components
No braking components
OV3 when constant Install the braking
Braking energy is not open
speed running components
Check the setting of
relative function codes
The voltage of the power Check the input power of
DC bus supply is too low the supply line
UV
Under-voltage The overvoltage stall Check the setting of
protection is not open relative function codes
The voltage of the power Check the power of the
supply is too low supply line
The motor setting rated Reset the rated current of
OL1 Motor overload
current is incorrect the motor
The motor stall or load Check the load and adjust
transients is too strong the torque lift
The acceleration is too Increase the ACC time
fast Avoid the restarting after
Reset the rotating motor stopping
The voltage of the power Check the power of the
OL2 Inverter overload
supply is too low supply line
The load is too heavy Select an inverter with
The motor power is too bigger power
small Select a proper motor
109
Goodrive200A inverters Fault tracking
Fault code Fault type Possible cause What to do
The inverter will report
Check the load and the
OL3 Electrical overload overload pre-alarm
overload pre-alarm point.
according to the set value
Check input power
Phase loss or fluctuation
SPI Input phase loss Check installation
of input R,S,T
distribution
Check the output
U,V,W phase loss input(or
distribution
SPO Output phase loss serious asymmetrical
Check the motor and
three phase of the load)
cable
110
Goodrive200A inverters Fault tracking
Fault code Fault type Possible cause What to do
Error of controlling the
Press STOP/RST to reset
write and read of the
EEP EEPROM fault Change the main control
parameters
panel
Damage to EEPROM
Check the PID feedback
PID feedback offline
signal
PIDE PID feedback fault PID feedback source
Check the PID feedback
disappear
source
Braking circuit fault or
Check the braking unit and
damage to the braking
change new braking pipe
bCE Braking unit fault pipes
Increase the braking
The external braking
resistor
resistor is not sufficient
Grounding The output of the inverter
ETH1 Check if the connection of
shortcut fault 1 is short circuited with the
the motor is normal or not
ground
Change the hoare
There is fault in the current
Change the main control
Grounding detection circuit
ETH2 panel
shortcut fault 2 The actual motor power
Set motor parameters
sharply differs from the
correctly.
inverter power.
Check the load and
ensure it is normal
Velocity deviation The load is too heavy or Increase the detection
dEu
fault stalled time
Check whether the control
parameters are normal
Check the load and
The control parameters of
ensure it is normal
the synchronous motors
Check whether the control
not set properly
Maladjustment parameter is set properly
STo The autoturn parameter is
fault or not
not right
Increase the
The inverter is not
maladjustment detection
connected to the motor
time
The actual running time of
Ask for the supplier and
Time reach of the inverter is above the
END adjust the setting running
factory setting internal setting running
time
time
111
Goodrive200A inverters Fault tracking
Fault code Fault type Possible cause What to do
The connection of the
Check the keypad wires
keypad wires is not good
and ensure whether there
or broken
is mistake
Keypad The keypad wire is too
Check the environment
PCE communication long and affected by
and avoid the interference
fault strong interference
source
There is circuit fault on the
Change the hardware and
communication of the
ask for service
keypad and main board
The connection of the
Check the keypad wires
keypad wires is not good
and ensure whether there
or broken
is mistake
Parameters The keypad wire is too
DNE Change the hardware and
downloading fault long and affected by
ask for service
strong interference
Repack-up the data in the
There is mistake on the
keypad
data storage of the keypad
The inverter will report the
Electronic Check the load and the
LL underload pre-alarm
underload fault underload pre-alarm point
according to the set value
112
Goodrive200A inverters Fault tracking
113
Goodrive200A inverters Fault tracking
8.6.3 Overvoltage
114
Goodrive200A inverters Fault tracking
115
Goodrive200A inverters Fault tracking
116
Goodrive200A inverters Fault tracking
8.6.8 Overcurrent
117
Goodrive200A inverters Fault tracking
floating processing; to verify whether the interference has been eliminated.
118
Goodrive200A inverters Fault tracking
Checking
Checking part Checking item Criterion
method
conductors caused by
overheating.
Ensure that there are no
crackles or Visual
NA
color-changing of the examination
protective layers.
Ensure that there is no Visual
Terminals seat NA
damage examination
Ensure that there is no
weeping, color-changing, Visual
NA
crackles and cassis examination
expansion.
Estimate the
usage time
Ensure the safety valve is according to the
NA
Filter capacitors in the right place. maintenance or
measure the
static capacity.
The static
Measure the capacity is
If necessary, measure the
capacity by above or equal
static capacity.
instruments. to the original
value *0.85.
Ensure whether there is Smelling and
replacement and splitting visual NA
caused by overheating. examination
Visual
examination or
Resistors
remove one The resistors are
Ensure that there is no
ending to in ±10% of the
offline.
coagulate or standard value.
measure with
multimeters
Hearing,
Ensure there is no
Transformers and smelling and
abnormal vibration, noise NA
reactors visual
and smelling,
examination
Ensure whether there is
Electromagnetism vibration noise in the Hearing NA
contactors and workrooms.
relays Ensure the contactor is Visual
NA
good enough. examination
Ensure there are no
Control
PCB and plugs loose screws and Fasten up NA
circuit
contactors.
119
Goodrive200A inverters Fault tracking
Checking
Checking part Checking item Criterion
method
Ensure there is no Smelling and
smelling and visual NA
color-changing. examination
Ensure there are no
Visual
crackles, damage NA
examination
distortion and rust.
Visual
examination or
Ensure there is no estimate the
weeping and distortion to usage time NA
the capacitors. according to the
maintenance
information
Hearing and
Estimate whether there is
Visual
abnormal noise and Stable rotation
examination or
vibration.
rotate with hand
Estimate there is no
Tighten up NA
losses screw.
Cooling fan Visual
examination or
Cooling
Ensure there is no estimate the
system
color-changing caused by usage time NA
overheating. according to the
maintenance
information
Ensure whether there is
stuff or foreign objection Visual
Ventilating duct NA
in the cooling fan, air examination
vent.
Consult the local service representative for more details on the maintenance. Visit the official
website of INVT: http://www.invt.com.cn and select Inverter Services – Maintenance and
Services.
120
Goodrive200A inverters Fault tracking
Wind
direction
Rotation Wind
direction direction
122
Goodrive200A inverters Communication protocol
Communication Protocol 9
123
Goodrive200A inverters Communication protocol
9.3.1 RS485
The interface of 2-wire RS485 works on semiduplex and its data signal applies differential
transmission which is called balance transmission, too. It uses twisted pairs, one of which is
defined as A (+) and the other is defined as B (-). Generally, if the positive electrical level
between sending drive A and B is among +2~+6V, it is logic“1”, if the electrical level is among
-2V~-6V; it is logic“0”.
485+ on the terminal board corresponds to A and 485- to B.
Communication baud rate means the binary bit number in one second. The unit is bit/s (bps).
The higher the baud rate is, the quicker the transmission speed is and the weaker the
anti-interference is. If the twisted pairs of 0.56mm(24AWG)is applied as the communication
cables, the Max. Transmission distance is as below:
Max. transmission Max. transmission
Baud rate Baud rate
distance distance
2400BPS 1800m 9600BPS 800m
4800BPS 1200m 19200BPS 600m
It is recommended to use shield cables and make the shield layer as the grounding wires
during RS485 remote communication.
In the cases with less devices and shorter distance, it is recommended to use 120Ω terminal
resistor as the performance will be weakened if the distance increase even though the
network can perform well without load resistor.
9.3.2 RTU mode
125
Goodrive200A inverters Communication protocol
setting of each byte.
The definition of even checkout: add an even check bit before the data transmission to
illustrate the number of “1” in the data transmission is odd number or even number. When it is
even, the check byte is “0”, otherwise, the check byte is”1”. This method is used to stabilize
the parity of the data.
The definition of odd checkout: add an odd check bit before the data transmission to illustrate
the number of “1” in the data transmission is odd number or even number. When it is odd, the
check byte is “0”, otherwise, the check byte is”1”. This method is used to stabilize the parity
of the data.
For example, when transmitting “11001110”, there are five “1” in the data. If the even
checkout is applied, the even check bit is “1”; if the odd checkout is applied; the odd check bit
is “0”. The even and odd check bit is calculated on the check bit position of the frame. And
the receiving devices also carry out even and odd checkout. If the parity of the receiving data
is different from the setting value, there is an error in the communication.
CRC check
The checkout uses RTU frame format. The frame includes the frame error detection field
which is based on the CRC calculation method. The CRC field is two bytes, including 16
figure binary values. It is added into the frame after calculated by transmitting device. The
receiving device recalculates the CRC of the received frame and compares them with the
value in the received CRC field. If the two CRC values are different, there is an error in the
communication.
During CRC, 0*FFFF will be stored. And then, deal with the continuous 6-above bytes in the
frame and the value in the register. Only the 8Bit data in every character is effective to CRC,
while the start bit, the end and the odd and even check bit is ineffective.
The calculation of CRC applies the international standard CRC checkout principles. When
the user is editing CRC calculation, he can refer to the relative standard CRC calculation to
write the required CRC calculation program.
Here provided a simple function of CRC calculation for the reference (programmed with C
language):
unsigned int crc_cal_value(unsigned char *data_value,unsigned char data_length)
{
int i;
unsigned int crc_value=0xffff;
while(data_length--)
{ crc_value^=*data_value++;
for(i=0;i<8;i++)
{
if(crc_value&0x0001)crc_value=(crc_value>>1)^0xa001;
else crc_value=crc_value>>1;
} }
return(crc_value);
}
In ladder logic, CKSM calculated the CRC value according to the frame with the table inquiry.
126
Goodrive200A inverters Communication protocol
The method is advanced with easy program and quick calculation speed. But the ROM
space the program occupied is huge. So use it with caution according to the program
required space.
130
Goodrive200A inverters Communication protocol
ASCII master command message ASCII slave response message (the
(the command sent from the master message sent from the inverter to
to the inverter the master)
START ‘:’ START ‘:’
‘0’ ‘0’
ADDR ADDR
‘1’ ‘1’
‘0’ ‘0’
CMD CMD
‘3’ ‘3’
High bit of starting ‘0’ ‘0’
Byte number
address ‘0’ ‘4’
Low bit of starting ‘0’ High bit of data ‘1’
address ‘4’ address 0004H ‘3’
High bit of data ‘0’ Low bit of data ‘8’
number ‘0’ address 0004H ‘8’
Low bit of data ‘0’ High bit of data ‘0’
number ‘2’ address 0005H ‘0’
LRC CHK Hi ‘F’ Low bit of data ‘0’
LRC CHK Lo ‘6’ address 0005H ‘0’
END Hi CR LRC CHK Hi ‘5’
END Lo LF LRC CHK Lo ‘D’
END Hi CR
END Lo LF
9.4.2.2 Command code: 06H (0000 0110), write one word (Word)
For instance: Write 5000 (1388H) to the 0004H address of the inverter whose slave address
is 02H, then the structure of this frame is listed as below:
ASCII master command message ASCII slave response message (the
(the command sent by the master to message sent by the inverter to the
the inverter) master)
START ‘:’ START ‘:’
‘0’ ‘0’
ADDR ADDR
‘2’ ‘2’
‘0’ ‘0’
CMD CMD
‘6’ ‘6’
High bit of write ‘0’ High bit of write ‘0’
data ‘0’ data ‘0’
Low bit of write ‘0’ Low bit of write ‘0’
data ‘4’ data ‘4’
High bit of data ‘1’ High bit of data ‘1’
content ‘3’ content ‘3’
Low bit of data ‘8’ Low bit of data ‘8’
content ‘8’ content ‘8’
LRC CHK Hi ‘5’ LRC CHK Hi ‘5’
LRC CHK Lo ‘9’ LRC CHK Lo ‘9’
END Hi CR END Hi CR
END Lo LF END Lo LF
9.4.2.3 Command code: 08H (0000 1000), diagnose function
Meaning of sub function code:
131
Goodrive200A inverters Communication protocol
Sub function code Instruction
0000 Return inquiry message data
For instance: carry out circuit detection on drive address 01H, the content of inquiry
message word string is the same with response message word string, its format is listed as
below:
ASCII master command message ASCII slave response message (the
(the command sent by the master to message sent by the inverter to the
the inverter) master)
START ‘:’ START ‘:’
‘0’ ‘0’
ADDR ADDR
‘1’ ‘1’
‘0’ ‘0’
CMD CMD
‘8’ ‘8’
High bit of write ‘0’ High bit of write ‘0’
data address ‘0’ data address ‘0’
Low bit of write ‘0’ Low bit of write ‘0’
data address ‘0’ data address ‘0’
High bit of data ‘1’ High bit of data ‘1’
content ‘2’ content ‘2’
Low bit of data ‘A’ Low bit of data ‘A’
content ‘B’ content ‘B’
LRC CHK Hi ‘3’ LRC CHK Hi ‘3’
LRC CHK Lo ‘A’ LRC CHK Lo ‘A’
END Hi CR END Hi CR
END Lo LF END Lo LF
9.4.2.4 Command code: 10H, continuous writing function
Command code 10H means the master write data to the inverter, the number of data being
written is determined by the command “data number”, the max. number of continuous writing
is 16 words.
For instance: Write 5000 (1388H) to 0004H of the inverter whose slave address is 02H, write
50 (0032H) to 0005H of the inverter whose slave address is 02H, then the structure of this
frame is listed as below:
ASCII master command message ASCII slave response message (the
(the command sent by the master to message sent by the inverter to the
the inverter) master)
START ‘:’ START ‘:’
‘0’ ‘0’
ADDR ADDR
‘2’ ‘2’
‘1’ ‘1’
CMD CMD
‘0’ ‘0’
High bit of starting ‘0’ High bit of starting ‘0’
address ‘0’ address ‘0’
Low bit of starting ‘0’ Low bit of starting ‘0’
address ‘4’ address ‘4’
High bit of data ‘0’ High bit of data ‘0’
number ‘0’ number ‘0’
132
Goodrive200A inverters Communication protocol
ASCII master command message ASCII slave response message (the
(the command sent by the master to message sent by the inverter to the
the inverter) master)
Low bit of data ‘0’ Low bit of data ‘0’
number ‘2’ number ‘2’
‘0’ LRC CHK Hi ‘E’
Byte number
‘4’ LRC CHK Lo ‘8’
High bit of data ‘1’ END Hi CR
0004H content ‘3’ END Lo LF
Low bit of data ‘8’
0004H content ‘8’
High bit of data ‘0’
0005H content ‘0’
Low bit of data ‘3’
0005H content ‘2’
LRC CHK Hi ‘1’
LRC CHK Lo ‘7’
END Hi CR
END Lo LF
Note: P29 group is the factory parameter which can not be read or changed. Some
parameters can not be changed when the inverter is in the running state and some
parameters can not be changed in any state. The setting range, unit and relative instructions
should be paid attention to when modifying the function code parameters.
133
Goodrive200A inverters Communication protocol
Besides, EEPROM is stocked frequently, which may shorten the usage time of EEPROM.
For users, some functions are not necessary to be stocked on the communication mode.
The needs can be met on by changing the value in RAM. Changing the high bit of the
function code form 0 to 1 can also realize the function. For example, the function code
P00.07 is not stocked into EEPROM. Only by changing the value in RAM can set the
address to 8007H. This address can only be used in writing RAM other than reading. If it is
used to read, it is an invalid address.
135
Goodrive200A inverters Communication protocol
136
Goodrive200A inverters Communication protocol
Code high 8
Meaning Code low 8 bit Meaning
bit
0x09 GD35-H1 vector inverters
0x0a GD300 vector inverters
0x0b GD100 simple vector inverters
0x0c GD200A general inverters
0x0d GD10 mini inverters
Note: the code is consisted of 16 bit which is high 8 bits and low 8 bits. High 8 bits mean
the motor type series and low 8 bits mean the derived motor types of the series. For
example, 0110H means Goodrive200A vector inverters.
9.5.3 Fieldbus ratio values
The communication data is expressed by hex in actual application and there is no radix point
in hex. For example, 50.12Hz can not be expressed by hex so 50.12 can be magnified by
100 times into 5012, so hex 1394H can be used to express 50.12.
A non-integer can be timed by a multiple to get an integer and the integer can be called
fieldbus ratio values.
The fieldbus ratio values are referred to the radix point of the setting range or default value in
the function parameter list. If there are figures behind the radix point (n=1), then the fieldbus
n
ratio value m is10 . Take the table as the example:
If there is one figure behind the radix point in the setting range or the default value, then the
fieldbus ratio value is 10. if the data received by the upper monitor is 50, then the
“hibernation restore delay time” is 5.0 (5.0=50÷10).
If MODBUS communication is used to control the hibernation restore delay time as 5.0s.
Firstly, 5.0 can be magnified by 10 times to integer 50 (32H) and then this data can be sent.
After the inverter receives the command, it will change 50 into 5 according to the fieldbus
ratio value and then set the hibernation restore delay time as 5s.
Another example, after the upper monitor sends the command of reading the parameter of
hibernation restore delay time ,if the response message of the inverter is as following:
Because the parameter data is 0032H (50) and 50 divided by 10 is 5, then the hibernation
restore delay time is 5s.
137
Goodrive200A inverters Communication protocol
138
Goodrive200A inverters Communication protocol
address data of the inverter function codes, there will be following function codes:
0 0 0 0 0 0 1 1 (Hex 03H)
For normal responses, the slave responds the same codes, while for objection responses, it
will return:
1 0 0 0 0 0 1 1 (Hex 83H)
Besides the function codes modification for the objection fault, the slave will respond a byte
of abnormal code which defines the error reason.
When the master receives the response for the objection, in a typical processing, it will send
the message again or modify the corresponding order.
For example, set the “running command channel” of the inverter (P00.01, parameter
address is 0001H) with the address of 01H to 03, the command is as following:
But the setting range of “running command channel” is 0~2, if it is set to 3, because the
number is beyond the range, the inverter will return fault response message as below:
Abnormal response code 86H means the abnormal response to writing command 06H; the
fault code is 04H. In the table above, its name is operation failed and its meaning is that the
parameter setting in parameter writing is invalid. For example, the function input terminal can
not be set repeatedly.
ASCII mode:
The command sent to the inverter:
The data content is 0003H. From the table 1, the inverter stops.
9.6.2 Example of writing command 06H
Example 1: make the inverter with the address of 03H to run forward. See table 1, the
address of “communication control command” is 2000H and forward running is 0001. See
the table below.
RTU mode:
The command sent by the master:
If the operation is successful, the response may be as below (the same with the command
sent by the master):
ASCII mode:
The command sent to the inverter:
Example 2: set the Max. Output frequency of the inverter with the address of 03H as100Hz.
See the figures behind the radix point, the fieldbus ratio value of the Max. output frequency
(P00.03) is 100. 100Hz timed by 100 is 10000 and the corresponding hex is 2710H.
RTU mode:
The command sent by the master:
140
Goodrive200A inverters Communication protocol
If the operation is successful, the response may be as below (the same with the command
sent by the master):
ASCII mode:
The command sent to the inverter:
141
Goodrive200A inverters Communication protocol
ASCII mode:
The command sent to the inverter:
Example 2: set the ACC time of 01H inverter as 10s and the DEC time as 20s
ACC Depend on
P00.11 ○
time 1 Setting range of P00.11 and model
P00.12:
DEC Depend on
P00.12 0.0~3600.0s ○
time 1 model
The corresponding address of P00.11 is 000B, the ACC time of 10s corresponds to 0064H,
and the DEC time of 20s corresponds to 00C8H.
RTU mode:
The command sent to the inverter:
ASCII mode:
The command sent to the inverter:
Note: the blank in the above command is for illustration. The blank can not be added in the
actual application unless the upper monitor can remove the blank by themselves.
142
Goodrive200A inverters Appendix A
A.2 Ratings
A.2.1 Capacity
Inverter sizing is based on the rated motor current and power. To achieve the rated motor
power reference in the table, the rated current of the inverter must be higher than or equal to
the rated motor current. Also the rated power of the inverter must be higher than or equal to
the rated motor power. The power ratings are the same regardless of the supply voltage
within one voltage range.
Note:
1. The maximum allowed motor shaft power is limited to 1.5 · PN. If the limit is exceeded,
motor torque and current are automatically restricted. The function protects the input bridge
of the drive against overload.
2. The ratings apply at ambient temperature of 40 °C
3. It is important to check that in Common DC systems the power flowing through the
common DC connection does not exceed PN.
A.2.2 Derating
The load capacity decreases if the installation site ambient temperature exceeds 40 °C, the
altitude exceeds 1000 meters or the switching frequency is changed from 4 kHz to 8, 12 or
15 kHz.
A.2.2.1 Temperature derating
In the temperature range +40 °C…+50 °C, the rated output current is decreased by 1% for
every additional 1 °C. Refer to the below list for the actual derating.
143
Goodrive200A inverters Appendix A
For 3-phase 200 V drives, the maximum altitude is 3000m above sea level. In altitudes
2000…3000 m, the derating is 1% for every 100 m.
A.2.2.3 Carrier frequency derating
For Goodrive200A series inverters, different power level corresponds to different carrier
frequency range. The rated power of the inverter is based on the factory carrier frequency,
so if it is above the factory value, the inverter needs to derate 10% for every additional 1 kHz
carrier frequency.
A.5.1 CE marking
The CE mark is attached to the drive to verify that the drive follows the provisions of the
European Low Voltage (2006/95/EC) and EMC Directives (2004/108/EC).
145
Goodrive200A inverters Appendix A
but it defines the step, installation and commission. The professional electrician has
necessary skills in installing and/or commissioning power drive systems, including their EMC
aspects.
Inverter of category C3: inverter of rated voltage less than 1000 V and used in the second
environment other than the first one.
Inverter of category C4: inverter of rated voltage more than 1000 V or the rated current is
above or equal to 400A and used in the complicated system in second environment.
A.6.1 Category C2
The emission limits are complied with the following provisions:
1. The optional EMC filter is selected according to the options and installed as specified in
the EMC filter manual.
2. The motor and control cables are selected as specified in this manual.
3. The drive is installed according to the instructions reference in this manual.
4. For the maximum motor cable length with 4 kHz switching frequency, see EMC
compatibility and motor cable length
A.6.2 Category C3
The immunity performance of the drive complies with the demands of IEC/EN 61800-3,
second environment.
The emission limits are complied with the following provisions:
1. The optional EMC filter is selected according to the options and installed as specified in
the EMC filter manual.
2. The motor and control cables are selected as specified in this manual.
3. The drive is installed according to the instructions reference in this manual.
4. For the maximum motor cable length with 4 kHz switching frequency, see EMC
compatibility and motor cable length
A drive of category C3 is not intended to be used on a low-voltage
public network which supplies domestic premises. Radio frequency
interference is expected if the drive is used on such a network.
146
Goodrive200A inverters Appendix B
键盘安装架 客户安装尺寸
147
Goodrive200A inverters Appendix B
148
Goodrive200A inverters Appendix B
149
Goodrive200A inverters Appendix B
150
Goodrive200A inverters Appendix B
151
Goodrive200A inverters Appendix C
Note:
1. The inverters (≤15kW) have standard film keypad and the inverters (≥18.5kW) have
standard LED keypad.
2.The inverter below 30kW (including 30kW) are embedded with braking unit.
3. Only the inverter above 37kW (including 37kW) have P1 terminal and are connected
with DC reactors.
4. The braking units apply standard braking unit DBU series in. Refer to the instruction of
DBU for detailed information.
Pictures Name Descriptions
Check that the voltage degree of the inverter complies with the voltage
of the supply power voltage.
C.4 Cables
C.4.1 Power cables
Dimension the input power and motor cables according to local regulations.
• The input power and the motor cables must be able to carry the corresponding load
currents.
• The cable must be rated for at least 70 °C maximum permissible temperature of the
conductor in continuous use.
• The conductivity of the PE conductor must be equal to that of the phase conductor
(same cross-sectional area).
• Refer to chapter Technical Data for the EMC requirements.
A symmetrical shielded motor cable (see the figure below) must be used to meet the EMC
requirements of the CE.
A four-conductor system is allowed for input cabling, but a shielded symmetrical cable is
153
Goodrive200A inverters Appendix C
recommended. Compared to a four-conductor system, the use of a symmetrical shielded
cable reduces electromagnetic emission of the whole drive system as well as motor bearing
currents and wear.
Note: A separate PE conductor is required if the conductivity of the cable shield is not
sufficient for the purpose.
To function as a protective conductor, the shield must have the same cross-sectional area as
the phase conductors when they are made of the same metal.
To effectively suppress radiated and conducted radio-frequency emissions, the shield
conductivity must be at least 1/10 of the phase conductor conductivity. The requirements are
easily met with a copper or aluminum shield. The minimum requirement of the motor cable
shield of the drive is shown below. It consists of a concentric layer of copper wires. The
better and tighter the shield, the lower the emission level and bearing currents.
A double-shielded cable is the best alternative for low-voltage digital signals, but a
single-shielded or unshielded twisted multi-pair cable (Figure b) is also usable. However, for
frequency input, always use a shielded cable.
The relay cable needs the cable type with braided metallic screen.
The keypad needs to connect with cables. It is recommended to use the screen cable on
complex electrical magnetic condition.
Note: Run analog and digital signals in separate cables.
Do not make any voltage tolerance or insulation resistance tests (for example hi-pot or
megger) on any part of the drive as testing can damage the drive. Every drive has been
tested for insulation between the main circuit and the chassis at the factory. Also, there are
voltage-limiting circuits inside the drive which cut down the testing voltage automatically.
Check the insulation of the input power cable according to local regulations before
154
Goodrive200A inverters Appendix C
connecting to the drive.
Note: Check the insulation of the input power cables according to local regulations
before connecting the cables.
155
Goodrive200A inverters Appendix C
156
Goodrive200A inverters Appendix C
or more.
It is necessary to add fuse for the avoidance of overload.
It is appropriate to use a breaker (MCCB) which complies with the inverter power in the
3-phase AC power and input power and terminals (R, S and T). The capacity of the inverter
should be 1.5-2 times of the rated current.
Due to the inherent operating principle and construction of circuit
breakers, independent of the manufacturer, hot ionized gases may
escape from the breaker enclosure in case of a short-circuit. To ensure
safe use, special attention must be paid to the installation and
placement of the breakers. Follow the manufacturer’s instructions.
157
Goodrive200A inverters Appendix C
C.6 Reactors
If the distance between the inverter and the motor is longer than 50m, frequent overcurrent
protection may occur to the inverter because of high leakage current caused by parasitic
capacitance effects from the long cables to the ground. In order to avoid the damage of the
motor insulation, it is necessary to add reactor compensation. If the distance between the
inverter and motor is 50~100m, see the table below for model selection; if it exceeds 100m,
consult with INVT technical support.
The power of the inverter Input reactor DC reactor Output reactor
GD200A -0R7G-4 ACL2-1R5-4 / OCL2-1R5-4
GD200A -1R5G-4 ACL2-1R5-4 / OCL2-1R5-4
GD200A -2R2G-4 ACL2-2R2-4 / OCL2-2R2-4
GD200A -004G/5R5P-4 ACL2-004-4 / OCL2-004-4
GD200A -5R5G/7R5P-4 ACL2-5R5-4 / OCL2-5R5-4
GD200A -7R5G/011P-4 ACL2-7R5-4 / OCL2-7R5-4
GD200A -011G/015P-4 ACL2-011-4 / OCL2-011-4
GD200A -015G/018P-4 ACL2-015-4 / OCL2-015-4
GD200A -018G/022P-4 ACL2-018-4 / OCL2-018-4
GD200A -022G/030P-4 ACL2-022-4 / OCL2-022-4
GD200A -030G/037P-4 ACL2-030-4 / OCL2-030-4
GD200A -037G/045P-4 ACL2-037-4 DCL2-037-4 OCL2-037-4
GD200A -045G/055P-4 ACL2-045-4 DCL2-045-4 OCL2-045-4
GD200A -055G/075P-4 ACL2-055-4 DCL2-055-4 OCL2-055-4
GD200A -075G/090P-4 ACL2-075-4 DCL2-075-4 OCL2-075-4
GD200A -090G/110P-4 ACL2-090-4 DCL2-090-4 OCL2-090-4
GD200A -110G/132P-4 ACL2-110-4 DCL2-110-4 OCL2-110-4
GD200A -132G/160P-4 ACL2-132-4 DCL2-132-4 OCL2-132-4
GD200A -160G/185P-4 ACL2-160-4 DCL2-160-4 OCL2-160-4
GD200A -185G/200P-4 ACL2-200-4 DCL2-200-4 OCL2-200-4
GD200A -200G/220P-4 ACL2-200-4 DCL2-200-4 OCL2-200-4
GD200A -220G/250P-4 ACL2-250-4 DCL2-280-4 OCL2-250-4
GD200A -250G/280P-4 ACL2-250-4 DCL2-280-4 OCL2-250-4
GD200A -280G/315P-4 ACL2-280-4 DCL2-280-4 OCL2-280-4
GD200A -315G/350P-4 ACL2-315-4 DCL2-315-4 OCL2-315-4
GD200A -350G/400P-4 Standard DCL2-350-4 OCL2-350-4
GD200A -400G-4 Standard DCL2-400-4 OCL2-400-4
GD200A -500G-4 Standard DCL2-500-4 OCL2-500-4
Note:
1. The rated derate voltage of the input reactor is 2%±15%.
2. The power factor of the input side is above 90% after adding DC reactor.
3. The rated derate voltage of the output reactor is 1%±15%.
4. Above options are external, the customer should indicate when purchasing.
158
Goodrive200A inverters Appendix C
C.7 Filters
C3 filters are optional for Goodrive200A 0.75~110kW inverters. If you need to configure C3
filters, connect them to J10.
160
Goodrive200A inverters Appendix C
Never use a brake resistor with a resistance below the minimum value
specified for the particular drive. The drive and the internal chopper are
not able to handle the overcurrent caused by the low resistance.
161
Goodrive200A inverters Appendix C
162
Goodrive200A inverters Appendix C
163
Goodrive200A inverters Appendix D
164
66001- 00342
201701(V2.1)