TABLE - 68

A.C. RESISTANCE AND REACTANCE VALUES FOR XLPE INSULATED CABLES


XLPE Insulated Cables (600/1000 V Grade)
Nominal Cross- A.C Resistance at 90 °C Reactance at 50 Hz
sectional area of
conductor Single Core Cables Multi Core Cables Single Core Cables Multi Core Cables
Copper Aluminium Copper Aluminium Armoured Unarmoured
mm² Ohm/km Ohm/km Ohm/km Ohm/km
1.5 15.43 ------- 15.43 ------- ------- 0.147 0.105

2.5 9.45 ------- 9.45 ------- ------- 0.137 0.099

4 5.88 ------- 5.88 ------- ------- 0.128 0.093

6 3.93 ------- 3.93 ------- ------- 0.119 0.089

10 2.33 ------- 2.33 ------- ------- 0.111 0.084

16 1.47 2.45 1.47 2.45 ------- 0.103 0.081

25 0.927 1.54 0.927 1.54 ------- 0.103 0.081

35 0.668 1.11 0.669 1.11 ------- 0.098 0.079

50 0. 494 0.822 0.494 0.822 0.114 0.093 0.078

70 0.342 0.568 0.343 0.569 0.106 0.088 0.074

95 0.247 0.411 0.248 0.411 0.102 0.086 0.072

120 0.196 0.325 0.197 0.326 0.097 0.085 0.072

150 0.160 0.265 0.160 0.265 0.099 0.085 0.073

185 0.128 0.212 0.129 0.212 0.095 0.083 0.072

240 0.0990 0.162 0.100 0.163 0.093 0.082 0.071

300 0.0805 0.130 0.0815 0.131 0.092 0.079 0.071

400 0.0645 0.102 0.0660 0.103 0.090 0.080 0.070

500 0.0525 0.0815 ------- ------- 0.089 0.078 -------

630 0.0430 0.0650 ------- ------- 0.087 0.078 -------

800 0.0365 0.0530 ------- ------- 0.086 0.076 -------

1000 0.0320 0.0445 ------- ------- 0.085 0.075 -------