Woodward - Iom - Eg-6p, Eg-6pc, Eg-10p, Eg-10pc Actuator 825
Woodward - Iom - Eg-6p, Eg-6pc, Eg-10p, Eg-10pc Actuator 825
Woodward - Iom - Eg-6p, Eg-6pc, Eg-10p, Eg-10pc Actuator 825
Manual 82566
WARNING
Read this entire manual and all other publications pertaining to the work to be
performed before installing, operating, or servicing this equipment. Practice all
plant and safety instructions and precautions. Failure to follow instructions can
cause personal injury and/or property damage.
The engine, turbine, or other type of prime mover should be equipped with an
overspeed shutdown device to protect against runaway or damage to the prime
mover with possible personal injury, loss of life, or property damage.
The overspeed shutdown device must be totally independent of the prime mover
control system. An overtemperature or overpressure shutdown device may also be
needed for safety, as appropriate.
CAUTION
To prevent damage to a control system that uses an alternator or battery-charging
device, make sure the charging device is turned off before disconnecting the
battery from the system.
IMPORTANT DEFINITIONS
WARNING—indicates a potentially hazardous situation which, if not avoided, could
result in death or serious injury.
NOTE—provides other helpful information that does not fall under the warning or
caution categories.
Woodward Governor Company reserves the right to update any portion of this publication at any time. Information
provided by Woodward Governor Company is believed to be correct and reliable. However, no responsibility is
assumed by Woodward Governor Company unless otherwise expressly undertaken.
© Woodward 1983
All Rights Reserved
Manual 82566 EG-6P/PC, EG-10P/PC Actuator
Contents
REGULATORY COMPLIANCE NOTES AND WARNINGS .................................... II
CHAPTER 1. GENERAL INFORMATION ........................................................... 1
Description..............................................................................................................1
Governor System....................................................................................................1
References .............................................................................................................2
Specifications .........................................................................................................2
Regulatory Compliance ..........................................................................................4
CHAPTER 2. INSTALLATION.......................................................................... 6
Storage ...................................................................................................................6
Installation ..............................................................................................................6
EG-6P, EG-10P Actuator (with Compensation) .....................................................7
Oil Supply ...............................................................................................................8
CHAPTER 3. PRINCIPLES OF OPERATION ................................................... 15
Introduction...........................................................................................................15
Oil Pump Model ....................................................................................................15
Oil Motor Model ....................................................................................................16
Voltage Change....................................................................................................17
Compensation System .........................................................................................17
CHAPTER 4. TROUBLESHOOTING ............................................................... 19
CHAPTER 5. REPLACEMENT PARTS ........................................................... 21
Parts Information ..................................................................................................21
Parts For Figure 5-1 .............................................................................................21
Parts For Figure 5-2 .............................................................................................24
CHAPTER 6. SERVICE OPTIONS ................................................................. 27
Product Service Options.......................................................................................27
Returning Equipment for Repair...........................................................................28
Replacement Parts ...............................................................................................29
How to Contact Woodward...................................................................................29
Engineering Services ...........................................................................................30
Technical Assistance............................................................................................31
DECLARATIONS ......................................................................................... 33
Woodward i
EG-6P/PC, EG-10P/PC Actuator Manual 82566
Regulatory Compliance
Notes and Warnings
NOTE
These hazardous locations listings are limited to those units bearing the UL, CSA,
or LCIE agency identification, specific hazardous locations markings, and the CE
marking. If the unit will be used in hazardous locations, refer to the product
nameplate or contact the Woodward Account Manager for more information.
The EG-10P actuator is suitable for use in Class I, Division 1, Groups B, C, and
D per UL for the US or non-hazardous locations only.
The EG-10P actuator is suitable for use in Class I, Division 2, Groups B, C, and
D per UL for the US or non-hazardous locations only.
The EG-10P actuator is suitable for use in Class I, Division 2, Groups B, C, and
D per CSA for Canada and UL for the US or non-hazardous locations only.
Each EG-10P Zone 1 actuator must be provided with a 900 mA maximum fuse to
be installed before the actuator.
WARNING
Explosion Hazard—Do not remove covers or connect/disconnect electrical
connectors unless power has been switched off or the area is known to be
non-hazardous.
AVERTISSEMENT
Risque d'explosion—Ne pas enlever les couvercles, ni raccorder /
débrancher les prises électriques, sans vous en assurez auparavant que le
système a bien été mis hors tension; ou que vous vous situez bien dans une
zone non explosive.
ii Woodward
Manual 82566 EG-6P/PC, EG-10P/PC Actuator
Chapter 1.
General Information
Description
The controlling element of the EG-6 and EG-10 Proportional Actuators is an
electrohydraulic transducer which controls oil flow to and from the power piston
through the action of a polarized solenoid. The position of the actuator output
shaft is proportional to the input current of the solenoid coil controlling the
hydraulic pilot-valve plunger.
The EG-6/10 Proportional Actuator is available with either a drive shaft or an oil
motor. The drive shaft is driven by the prime mover to provide relative rotation
between the pilot-valve plunger and bushing, and also to rotate the oil pump
gears. The direction of rotation (clockwise or counterclockwise) is determined by
the placement of plugs in oil passages in the actuator to maintain the operating
oil pressure at about 1724 kPa (250 psi) above supply pressure in the EG-6 and
about 2758 kPa (400 psi) above supply pressure in the EG-10.
The EG-10P actuators that do not have an oil pump are equipped with an oil
motor. Oil under pressure must be supplied to the actuator: to provide working
pressure for the actuator and to rotate the pilot-valve bushing. Work output of the
EG-10P actuator equipped with an oil motor depends upon the pressure of the oil
supplied to the actuator.
The EG-10P can be equipped with either a Pickering or Kerfott RVDT for
operation of a gas valve, mechanical load sharing, pitch control, or any
application where valve or fuel-rack position is a function of the control. A
minimum-position switch is available for applications which require this
protection.
Governor System
The governor system includes:
• A Woodward electronic governor
• A magnetic pickup
• A speed-setting potentiometer (optional)
• A proportional electrohydraulic EG actuator described in this manual
Output pulses (proportional to prime mover speed) from the magnetic pickup are
processed by the speed sensor section of the electric governor and are applied as
a dc voltage (proportional to prime mover speed) to the summing point of the
control amplifier section of the electric governor. This speed voltage is compared to
a dc reference voltage from the speed-setting potentiometer, which corresponds to
the prime mover speed desired. The governor output voltage increases, causing
the actuator output shaft to rotate in the increase-fuel direction.
Woodward 1
EG-6P/PC, EG-10P/PC Actuator Manual 82566
References
Manual 25071 Oils for Hydraulic Controls
Manual 56105 EG-10P, EG-10PC Repair Procedure
Manual 82510 Magnetic Pickups and Proximity Switches for Electronic
Controls
Specifications
Radiation Resistance Radiation-resistant parts are available for special
applications.
Position Feedback A position feedback transducer (RVDT) is available
to monitor output shaft position.
NOTE
Unless otherwise specified, these actuators are tested and shipped for
vertical operation. When used in a horizontal application, these actuators
will have an 8-degree shift in terminal shaft calibration.
Compensation
Many EG actuators operate with oil supplied directly from the prime mover.
Certain multiviscosity motor oils require a compensation system within the
actuator to provide needed stability. A needle valve is included in the
compensation system to allow response adjustment.
NOTE
EG-10P oil-motor models with Class 1, Groups C and D approval are limited
to a maximum of 3448 kPa (500 psi) inlet pressure.
All Models
Output Shaft 0.375”-36 serrations (standard/EG-3P) both sides of
the case; 0.500”-36 serrations (standard/
EG-6P/10P) either side of the case. Special output
shafts are available.
Angular Travel 42° nominal travel available with 28° travel from no
load to full load at rated speed recommended
Calibration 2° to 3° off minimum shaft position at 20 mA. 36°
±3°additional travel at 160 mA. Special calibrations
are available with a minimum of 80 mA required for
full stroke.
Hysteresis Within 3% of maximum stroke
Linearity Within 0.5%
Temperature Drift Nominally ±1° of output per 56 °C/100 °F
Transducer Coil
Resistance 30 to 35 Ω (at 20 °C/68 °F)
Nominal Coil Input
Current Range 20 to 160 mA for single or two actuators operating
from one electric control
Electrical Connector 4-pin MS-33682-14S-2P. UL design does not have
connector
2 Woodward
Manual 82566 EG-6P/PC, EG-10P/PC Actuator
Hydraulic Oil Supply Fluid Hydrocarbon oil. Consult Woodward for
recommended synthetic oils. If multiviscosity oils are
used, the compensated model is suggested.
Hydraulic Oil Viscosity 100 to 200 SUS at operating temperature
recommended. 50 SUS minimum, 3000 SUS
maximum (7.5 CST to 850 CST)
Oil Temperatures of
Continuous Operation 60 to 93 °C (140 to 200 °F) depending on oil
viscosity.
Ambient Temperature
Range –29 to +93 °C (–20 to +200 °F). The primary
temperature concern is for the hydraulic fluid
properties in the actuator.
Case and Base
Construction Cast or ductile iron
Cover, Subcap, and
Drain Adapter Cast aluminum
Mounting Configuration Vertical (or horizontal with proper adjustments; non-
interchangeable).
Mounting Studs Four 5/16” diameter (approx. 7.9 mm)
Woodward 3
EG-6P/PC, EG-10P/PC Actuator Manual 82566
–1/2 1/2
Time Constant 1.06P + 0.0059P s
where P=supply pressure in psig (1 psig=6.895 kPa)
Supply Pressures 552 to 3448 kPa (80 to 500 psi). Pressures outside
this range are not recommended.
Supply Flow Peak demand of 15 L/min (4 US gal/min) during
transients. Steady-state flow 5.3 L/min (1.4 US
gal/min) maximum, depending on orifice size and
operating pressure.
Filter 10 to 15 µm (nominal)
Pressure Inlet 0.250”-18 NPTF to pilot valve
Orifice (to oil motor supply):
Supply Pressure Orifice Diameter
80 to <100 552 to <690 0.076 1.93
100 to 175 690 to 1207 0.062 1.57
>175 to 300 >1207 to 2068 0.055 1.40
>300 to 500 >2068 to 3448 0.047 1.19
Regulatory Compliance
The listings in this section are limited to EG-10P Units.
Zone 1
ATEX – Potentially Declared to 94/9/EEC COUNCIL DIRECTIVE of 23
Explosive March 1994 on the approximation of the laws of the
Atmospheres Member States concerning equipment and
Directive: protective systems intended for use in potentially
explosive atmospheres.
LCIE 02.ATEX6221X
Zone 2
ATEX – Potentially Declared to 94/9/EEC COUNCIL DIRECTIVE of 23
Explosive March 1994 on the approximation of the laws of the
Atmospheres Member States concerning equipment and
Directive: protective systems intended for use in potentially
explosive atmospheres.
4 Woodward
Manual 82566 EG-6P/PC, EG-10P/PC Actuator
North American Compliance:
Woodward 5
EG-6P/PC, EG-10P/PC Actuator Manual 82566
Chapter 2.
Installation
This chapter provides information for the receiving, storage, and installation of
the EG-10P actuator. See Figures 2-2, and 2-3 for typical outline drawings.
Storage
For short-term storage, fill the actuator with a good rust and oxidation inhibited
oil.
Installation
WARNING
Due to typical noise levels in turbine environments, hearing protection
should be worn when working on or around the EG-10P.
Burn Hazard—The surface of this product can become hot enough or cold
enough to be a hazard. Use protective gear for product handling in these
circumstances. Temperature ratings are included in the specification section
of this manual.
CAUTION
Explosion Hazard—External fire protection is not provided in the scope of
this product. It is the responsibility of the user to satisfy any applicable
requirements for their system.
Attitude
For installation dimensions, see the outline drawing (Figures 2-2 and 2-3). The
actuator must fit evenly on the mounting pad. The four mounting bolts must be
evenly torqued, and there must be no movement or rocking of the actuator on its
mounting surface.
Drive Connection
The drive shaft of the oil pump actuator must fit into the drive coupling with a
free-slip fit. Do not apply external force. Be sure the drive does not bind or have
too much side load or end play. Two types of couplings are available:
• 9/16-6 spline internal-to-external
• 9/16-6 spline internal-to-internal
The coupling is first installed on the engine drive, then the actuator is added to
the internal spline on the coupling.
6 Woodward
Manual 82566 EG-6P/PC, EG-10P/PC Actuator
Control Linkage
The output shaft will rotate 42 degrees. Use 2/3 (28 degrees) travel between no
load and full load. The additional “overtravel” should be split and used at both
ends to provide overfuel for transients and to assure shutdown at minimum
actuator position. The linkage must be free of binding, without backlash. If there
is a collapsible member in the linkage, it must not yield when the actuator moves
the linkage rapidly. The linkage may be spring-loaded to remove looseness.
Electrical Connection
CAUTION
Due to the hazardous location listings associated with this product, proper
wire type and wiring practices are critical to operation.
Connect wiring to the actuator according to the plant wiring instructions included
with the control and with the actuator. Most installations call for jumpering
contacts C and D in the mating plug. RVDT or minimum-position switch features
will require different electrical connections. Actuators designed for use in
hazardous environments have conduit boxes permanently attached.
Woodward 7
EG-6P/PC, EG-10P/PC Actuator Manual 82566
Oil Supply
Clean Supply
Dirt in the oil can cause the actuator to malfunction.
Many oil pump model actuators are installed with a direct line from either the
engine pressure oil system or from the engine oil sump. A 20 to 25 µm absolute
filter should be installed in the line from the engine. Many units operate
satisfactorily without this filter, depending upon the engine filter to protect against
contamination. In case of control problems with an unfiltered oil supply, clean the
actuator and install the prescribed filter in the oil supply line.
Install a 10 to 15 µm absolute filter in the supply line to the oil motor model.
Flow rates of a maximum demand of 7.6 L/min (2.0 US gal/min) during transients
with a steady-state of 0.9 L/min (0.25 US gal/min) at 2758 kPa (400 psi) and 60
SUS are required.
Some engines have the oil supply built into the mounting pad. In these cases the
0.250 pipe-tapped connection is plugged. No filter can be installed in these units,
and the actuator depends upon the engine filter for protection.
Most oil-pump actuators drain through the mounting base to sump. If a special
drain is used, the drain line must be adequate to prevent any back pressure on
the actuator.
NOTE
Back pressure from the drain may cause jiggle or instability in the actuator.
The oil motor requires an orifice to restrict oil supply flow. Normally the orifice is
internal in the actuator and comes with the actuator. When specified by the
customer, the oil motor supply may be a separate external line with an
appropriate orifice installed in the connection with the oil motor. The orifice size
must be matched to the oil pressure supplied to the actuator (see Table 2-1). The
10 to 15 µm absolute filter must service this supply line as well as the pilot-valve
supply line.
8 Woodward
Manual 82566 EG-6P/PC, EG-10P/PC Actuator
Adequate drain is important for dependable and stable operation of the oil motor
actuator. A minimum of 25 mm (1 inch) ID drain is needed with a continuous drop
for up to 3 m (10 ft) from the actuator. Drains longer than 3 m (10 ft) will probably
require larger ID pipe. No oil traps can occur in this drain line. It is important that
oil not back up to and into the actuator.
NOTE
Back pressure from the oil drain may cause actuator jiggle as hydraulic
resonance can occur.
Woodward 9
EG-6P/PC, EG-10P/PC Actuator Manual 82566
Figure 2-2. Outline Drawing of Typical EG-P Actuator (Oil Pump Model)
10 Woodward
Manual 82566 EG-6P/PC, EG-10P/PC Actuator
Figure 2-3. Outline Drawing of Typical EG-P Actuator (Oil Motor Model)
Woodward 11
EG-6P/PC, EG-10P/PC Actuator Manual 82566
12 Woodward
Manual 82566 EG-6P/PC, EG-10P/PC Actuator
Woodward 13
EG-6P/PC, EG-10P/PC Actuator Manual 82566
14 Woodward
Manual 82566 EG-6P/PC, EG-10P/PC Actuator
Chapter 3.
Principles of Operation
Introduction
The EG actuator consists of the following basic items:
Oil pump or oil motor
Relief valve (oil pump model only)
Pilot valve plunger and rotating bushing
Magnet (transducer assembly)
Feedback linkage
Centering and restoring springs
Power piston
Output shaft
See the schematic (Figure 3-1) for a better understanding of the operation of the
EG actuator.
Oil from the external supply source enters the suction side of the oil pump. The
pump gears carry the oil to the pressure side of the pump. Internal pressure is
maintained by the relief valve in the oil pump system.
The prime mover fuel or steam linkage is connected to the output shaft. The
output shaft is connected, through linkage, to the power piston. Constant
hydraulic pressure on top of the power piston tends to rotate the output shaft in
the decrease-fuel direction. However, the power piston cannot move down
unless control oil is released to sump.
The pilot-valve plunger regulates the flow of control oil to and from the power
piston. The pilot-valve plunger is centered when its control land covers the
control port in the pilot-valve bushing. Figure 3-1 shows the pilot-valve bushing.
Woodward 15
EG-6P/PC, EG-10P/PC Actuator Manual 82566
With the unit running on-speed under steady-state conditions, the resulting
spring force and the force from the current in the solenoid coils are equal but
opposite. This keeps the output shaft at a position to maintain the engine at the
required speed.
When equipped with an oil motor, the actuator does not require a drive shaft. An
outside source of pressure oil supplies the working pressure for the actuator.
This pressure oil also operates the oil motor, which rotates the pilot-valve
bushing. The oil pressure required to supply the necessary work force is
determined by the specified work requirement at the time the actuator is
purchased (see Table 1-1).
16 Woodward
Manual 82566 EG-6P/PC, EG-10P/PC Actuator
The oil motor portion of the actuator operates with a restriction to the pressure oil
supply in order to reduce the flow of pressure oil through the oil motor. The
orifice is normally fitted internally in the actuator. Some actuators are built without
an internal orifice and, in these cases, a separate oil supply and orifice is
required.
Voltage Change
In operation, a voltage change to the magnet causes a temporary change in the
location of the pilot-valve plunger in the rotating bushing and a resulting change
in the location of the power piston and terminal shaft. If the voltage decreases,
the magnetic force decreases and the centering spring raises the pilot-valve
plunger. This allows the power piston to be forced down, decreasing the fuel
setting. As the terminal shaft rotates, it moves linkage which adds to the restoring
spring force, urging the pilot-valve plunger to return to the centered position and
stop the rotation of the terminal shaft. A voltage increase will cause the terminal
shaft to increase fuel position. The increase in voltage forces the pilot-valve
plunger down, sending pressure oil under the power piston and adding to the fuel
setting. Again, the proportional linkage is moved, this time reducing the restoring
spring force and allowing the centering spring to bring the pilot-valve plunger
back to a centered position against the combined forces of the restoring spring
and magnet.
Compensation System
The EG proportional actuator can be supplied from the factory with a
compensation system. The compensation system will supply extra hydraulic
pressure to the pilot-valve plunger to assist its return to a normal, centered
position following a fuel change. Figure 3-2 shows a schematic of the
compensation system. The floating piston in the system is moved against one of
the springs any time the power piston moves, creating a slight difference in the
oil pressures on the two sides of the buffer piston. The higher oil pressure is on
the side of the piston opposite the spring being compressed. The oil pressure on
one side of the buffer piston is transmitted to the lower side of the compensation
land on the pilot-valve plunger—the pressure on the other side of the piston is
transmitted to the upper side of the compensation land. The difference in oil
pressures produces a net force upward or downward which assists the restoring
or centering spring in re-centering the pilot-valve plunger whenever a fuel
correction is made.
The compensation force is dissipated through the needle valve and the buffer
piston re-centers between the two springs in preparation for the next fuel change.
Woodward 17
EG-6P/PC, EG-10P/PC Actuator Manual 82566
18 Woodward
Manual 82566 EG-6P/PC, EG-10P/PC Actuator
Chapter 4.
Troubleshooting
This chapter gives instructions for checking the operation of the EG actuator.
See the appropriate manual for troubleshooting your electronic governor system.
The problems encountered with a new or factory rebuilt actuator are usually
limited to installation and supply oil problems. If you have an actuator problem,
check the following.
1. Be sure the drive to the actuator is rotating the drive shaft and pump gears in
the proper direction (see Figure 2-5).
2. Be sure the hydraulic supply pressure to the actuator is adequate, clean, and
is not foaming. Be sure the lines are not clogged and the filter is seated
properly in its housing. If you have an oil motor model, it may be necessary
to remove the drain adapter from the case to be sure the oil motor is rotating.
3. Check the linkage between actuator and prime mover for misalignment,
binding, or excessive backlash.
5. Use the circuit outlined in Figure 4-1 to check the actuator output. The
actuator should be at minimum fuel position at 0 mA, and it should be at
maximum position at 200 mA. The movement from minimum to maximum
should be even, and the output shaft should repeat to the exact same
location at the same current setting.
With the engine or turbine shut down, remove the linkage between the actuator
and the control valve or fuel rack. Start the prime mover under manual control if
necessary to provide drive or oil pressure to the actuator.
WARNING
The engine or turbine will not be under control of the governor system with
the actuator linkage removed. TO PROTECT AGAINST POSSIBLE
PERSONAL INJURY, LOSS OF LIFE and/or PROPERTY DAMAGE, BE
PREPARED TO MAKE AN EMERGENCY SHUTDOWN to protect against
runaway or overspeed.
Rotate the potentiometer and watch the output shaft as it moves through its
range of travel. The output shaft should take the same position each time the
potentiometer is set at the same location. If the output shaft has an erratic
movement, the problem may be caused by low oil pressure, dirty supply oil,
plugged oil filters, or possibly a restricted drain line.
Woodward 19
EG-6P/PC, EG-10P/PC Actuator Manual 82566
CAUTION
Do not circumvent safety features of the actuator when servicing or
troubleshooting an actuator designed for use in hazardous locations.
20 Woodward
Manual 82566 EG-6P/PC, EG-10P/PC Actuator
Chapter 5.
Replacement Parts
This chapter provides information for replacement parts for the EG-6P and
EG-10P actuators. Figure 5-1 shows parts for the EG actuator with an oil motor.
Figure 5-2 shows the EG actuator with an oil pump.
Parts Information
When ordering replacement parts, include the following information:
1. Serial number and part number shown on the nameplate.
2. Manual number (this is manual 82566).
3. Part number from parts list, and description or part name.
Woodward 21
EG-6P/PC, EG-10P/PC Actuator Manual 82566
Ref. No. Part Name............................................................ Quantity
82566-40 Washer ..............................................................................1
82566-41 Centering screw 6-32 x .375 ..............................................1
82566-42 Connector gasket ..............................................................1
82566-43 4 pin receptacle .................................................................1
82566-44 Lock washer no. 6..............................................................4
82566-45 Rd. hd. screw no. 6-32.......................................................4
82566-46 Restoring spring lever........................................................1
82566-47 Adjustable spring seat .......................................................1
82566-48 Link....................................................................................1
82566-49 Drilled headed pin..............................................................1
82566-50 Washer .296 O.D...............................................................2
82566-51 Cotter pin .060 x .500 ........................................................3
82566-52 Feedback adjustment bracket............................................1
82566-53 Transducer clamp bracket .................................................1
82566-54 Straight drilled pin..............................................................1
82566-55 Lock washer no. 10............................................................5
82566-56 Socket head cap screw, 10 x 2.250”..................................2
82566-57 Loading lever .....................................................................1
82566-58 Soc. hd. cap screw 10-32 x .625........................................1
82566-59 Drilled pin .250 x .656 ........................................................1
82566-60 Pin .....................................................................................1
82566-61 Output shaft .......................................................................1
82566-62 Output shaft collar .............................................................1
82566-63 Feedback lever ..................................................................1
82566-64 Short link............................................................................1
82566-65 Cover gasket .....................................................................2
82566-66 Sub cap .............................................................................1
82566-67 Roll pin...............................................................................1
82566-68 Steel washer .174 I.D. .......................................................2
82566-69 Lock washer ......................................................................2
82566-70 Fill. hd. machine screw ......................................................2
82566-71 Pin .....................................................................................2
82566-72 Screw.................................................................................2
82566-73 Cover .................................................................................1
82566-74 Washer.375 O.D. x 195 I.D. x .031....................................8
82566-75 Shakeproof washer no. 10.................................................8
82566-76 Fill. dr. screw no. 10-1.500 ................................................8
82566-77 Copper washer .265 I.D.....................................................1
82566-78 Hex screw .250-28 x .375 ..................................................1
82566-79 Shipping cap .875-20.........................................................1
82566-86 Orifice ................................................................................1
22 Woodward
Manual 82566 EG-6P/PC, EG-10P/PC Actuator
NOTE
Parts for UL connections, Pickering or Kerfott RVDT options, and minimum
position switch options, are not listed. Contact Woodward for information
about these options. The serial number and part number shown on the
nameplate of the individual control will determine the designs of these
special features.
Woodward 23
EG-6P/PC, EG-10P/PC Actuator Manual 82566
24 Woodward
Manual 82566 EG-6P/PC, EG-10P/PC Actuator
Ref. No. Part Name ............................................................Quantity
82566-162 Output shaft ...................................................................... 1
82566-163 Output shaft collar............................................................. 1
82566-164 Feedback lever ................................................................. 1
82566-165 Short link ........................................................................... 1
82566-166 Cover gasket..................................................................... 2
82566-167 Sub cap assembly............................................................. 1
82566-168 Roll pin .062 dia. x .312..................................................... 1
82566-169 Steel washer .174 I.D........................................................ 2
82566-170 Lock washer ...................................................................... 2
82566-171 Fill. hd. machine screw...................................................... 2
82566-172 Pin..................................................................................... 2
82566-173 Screw ................................................................................ 2
82566-174 Cover ................................................................................ 1
82566-175 Washer .375 O.D. x .195 I.D. ............................................ 8
82566-176 Shakeproof washer no. 10 ................................................ 8
82566-177 Fill. dr. screw no. 10 x 1.500 ............................................. 8
82566-178 Copper washer .265 I.D. ................................................... 1
82566-179 Hex screw .250-28 x .375 ................................................. 1
82566-180 Shipping cap .875-20 ........................................................ 1
82566-181 Drive coupling ................................................................... 1
82566-182 Rotation decal ................................................................... 1
82566-183 Spring................................................................................ 1
82566-184 Piston ................................................................................ 1
82566-185 Spring................................................................................ 1
Woodward 25
EG-6P/PC, EG-10P/PC Actuator Manual 82566
NOTE
Parts for UL connections, Pickering or Kerfott RVDT options, and minimum-
position switch options, are not listed. Contact Woodward for information
about these options.
Figure 5-2. Parts for the EG-P Actuator (Oil Pump Model)
26 Woodward
Manual 82566 EG-6P/PC, EG-10P/PC Actuator
Chapter 6.
Service Options
Replacement/Exchange
Replacement/Exchange is a premium program designed for the user who is in
need of immediate service. It allows you to request and receive a like-new
replacement unit in minimum time (usually within 24 hours of the request),
providing a suitable unit is available at the time of the request, thereby
minimizing costly downtime. This is also a flat rate structured program and
includes the full standard Woodward product warranty (Woodward Product and
Service Warranty 5-01-1205).
Charges for the Replacement/Exchange service are based on a flat rate plus
shipping expenses. You are invoiced the flat rate replacement/exchange charge
plus a core charge at the time the replacement unit is shipped. If the core (field
unit) is returned to Woodward within 60 days, Woodward will issue a credit for
the core charge. [The core charge is the average difference between the flat rate
replacement/exchange charge and the current list price of a new unit.]
Woodward 27
EG-6P/PC, EG-10P/PC Actuator Manual 82566
CAUTION
To prevent damage to electronic components caused by improper handling,
read and observe the precautions in Woodward manual 82715, Guide for
Handling and Protection of Electronic Controls, Printed Circuit Boards, and
Modules.
Packing a Control
Use the following materials when returning a complete control:
• protective caps on any connectors;
• antistatic protective bags on all electronic modules;
• packing materials that will not damage the surface of the unit;
• at least 100 mm (4 inches) of tightly packed, industry-approved packing
material;
• a packing carton with double walls;
• a strong tape around the outside of the carton for increased strength.
28 Woodward
Manual 82566 EG-6P/PC, EG-10P/PC Actuator
NOTE
We highly recommend that you make arrangement in advance for return
shipments. Contact a Woodward customer service representative at
1 (800) 523-2831 in North America or +1 (970) 482-5811 for instructions and
for a Return Authorization Number.
Replacement Parts
When ordering replacement parts for controls, include the following information:
• the part number(s) (XXXX-XXXX) that is on the enclosure nameplate;
• the unit serial number, which is also on the nameplate.
For assistance outside North America, call one of the following international
Woodward facilities to obtain the address and phone number of the facility
nearest your location where you will be able to get information and service.
You can also contact the Woodward Customer Service Department or consult
our worldwide directory on Woodward’s website (www.woodward.com) for the
name of your nearest Woodward distributor or service facility.
Woodward 29
EG-6P/PC, EG-10P/PC Actuator Manual 82566
Engineering Services
Woodward Industrial Controls Engineering Services offers the following after-
sales support for Woodward products. For these services, you can contact us by
telephone, by email, or through the Woodward website.
• Technical Support
• Product Training
• Field Service
Contact information:
Telephone—+1 (970) 482-5811
Toll-free Phone (in North America)—1 (800) 523-2831
Email—icinfo@woodward.com
Website—www.woodward.com
30 Woodward
Manual 82566 EG-6P/PC, EG-10P/PC Actuator
Technical Assistance
If you need to telephone for technical assistance, you will need to provide the following information.
Please write it down here before phoning:
General
Your Name
Site Location
Phone Number
Fax Number
Control/Governor Information
Please list all Woodward governors, actuators, and electronic controls in your system:
Serial Number
Serial Number
Serial Number
If you have an electronic or programmable control, please have the adjustment setting positions or
the menu settings written down and with you at the time of the call.
Woodward 31