Actuator Capacity Controller: Technical Specifications
Actuator Capacity Controller: Technical Specifications
Actuator Capacity Controller: Technical Specifications
FEATURES
• High level of modulating accuracy to remote control the pumps.
• Explosion-proof certified versions available: IECEx, CSA NEMA
7, ATEX
• Watertight IP68-NEMA 4
• Special offshore version for O&G applications
• Flexible adjustment for flow rate 1:10 ratio to meet API 675 standard
• 85V - 260VAC 1 Phase 50/60 Hz, 24VDC
• Mechanical position indicator integrated inside cover to conveniently
check levels
• Manual override integration for manual flow adjustment as needed
• IP68 (in compliance with EN 60529, FM 3616, CSA 213, CSA 25)
Weather Proof
• NEMA 4X (comply with NEMA250)
• IEC Ex db IIB T4/5/6. Temp. -4 to 160°F (-20 to +60°C) complying with
ISO 60079-0, ISO 60079-1, ISO 80079-36, ISO 80079-37
Explosion Proof • ATEX IIB T4/5/6. Temp. -4 to 160°F (-20 to +60°C) complying with
EN 60079-0, EN 60079-1, EN 80079-36, EN 80079-37
• NEC500. NEMA 7 Class I div 1 group C & D, Class II group E, F et G. T4/5/6
External Coating • In standard, C4 coating according to ISO 12966 (C5 coating in option)
Ambient
• -40 to +140°F / -40 to +60°C
Temperature Range
1
© 2019 Milton Roy, LLC. All Rights Reserved.
Technical Specifications ACC - ¾ Turn ACC - 10 Turns
Motor Technology • 24VDC motors with 2-wire connection to the control boards
MOTOR
Gear Design • The actuator is mechanically self-locking and lubricated for product lifetime
SPECIFICATIONS
MECHANICAL
Manual Emergency
• Manual emergency operation via a 10 mm hexagonal manual shaft
Operation
Output flange • The actuator flanges comply with ISO 5211 F05-F07
• The actuators are lubricated for the product lifetime and do not require any
Lubrication
special service
• The actuators can operate on a wide variety of single phase power supply
SPECIFICATIONS
Power Supply • From 85VAC to 260VAC 50/60 Hz and 24VDC (12VDC single power supply
ELECTRICAL
available on request)
Terminal • Push-in type terminals for controls and power supply
Compartment • Internal and external earth-grounding post
Control
• 4-20mA analog output feedback received through 2 wires
• Limit switches actuated by
adjustable cam-block
Operated by the analog positioner only
• 2 SPDT switches as standard
Travel Limit Systems (Open and Close)
• + 2 auxiliary switches (customer
feedback) 250VAC-5A / 48VDC- Operated by the analog positioner only
2.5A (resistive load)
ACC actuators comply with:
AND STANDARDS
EC DIRECTIVES
2
WIRING DIAGRAM
Actuator / Servomoteur
Power Board
Carte Puissance PE
1 L
2 N
A 24VDC +
B 24VDC -
C
Ouput J2
4
32 mA Position Transmitter
33 Recopie de position 4-20 mA
Switch J2
- +
12-32VDC
4
Input J3
Relay Board
Carte Relais
3
DIMENSIONS
100 *3
ø172
Cable entries
Raccordement �lectrique
219
Mechanical stops
Butées mécaniques
27
Manual command 75
77 Commande Manuelle
175 *1
Position indicator
Indicator de position
2
F05 Ø35f8
Centering ring
2
Rondelle de centrage
F07 Ø55f8
ISO 5211
F05/F07
View A of the flange
Vue A de la bride
45°
ø50
ø70
F07 = 4 × M8
Prof./Depth: 12
F05 = 8 × M6
Prof./Depth: 9
2×0.22 at 45°
4
ACC CODES
Pump Model Actuator Number Type of Actuator Description
PRIMEROY® K (PKG)
3051568500F mROY® A - Plunger F 3051568110F
PRIMEROYAL® K (PK)
PRIMEROY® L (PLG)
3051568600F mROY® B - Plunger K/L 3051568120F
PRIMEROYAL® L (PL)
MILROYAL® D 3051568300F mROY® B - Plunger R 3051568130F
www.miltonroy.com
5
MR_ACC_TechSpec_202009_Ver 1