28 Manual
28 Manual
28 Manual
Rectifier/Regenerating Unit
Sizes C to K
Conformity
We have checked the contents of this document for conformity with
the hardware and software described. However, this does not
absolutely preclude deviations, and we therefore cannot guarantee
complete conformity. The information in the document is subjected
to regular scrutiny. Any necessary corrections will be made in
subsequent editions. We also welcome any suggestions you may
have in the way of improvement. SIMOVERT Registered Trade Mark
Contents
Page
4 Start-Up............................................................................................................................ 4-1
4.1 Introduction and handling start-up .................................................................................... 4-1
4.1.1 Handling the start-up instructions ..................................................................................... 4-1
4.1.2 General explanation of the terminology and functional scope of the
rectifier/regenerating unit .................................................................................................. 4-1
4.2 Initial start-up .................................................................................................................... 4-4
4.2.1 Preparatory measures ...................................................................................................... 4-4
4.2.2 Parameterization "Standard application" .......................................................................... 4-5
4.2.3 Parameterization for "Expert application" ......................................................................... 4-7
4.2.5 Simple application examples for connecting process data with connection assignment.. 4-10
4.3 Start-up aids ..................................................................................................................... 4-11
4.3.1 Process data..................................................................................................................... 4-11
4.3.1.1 Control word (control word 1 and control word 2)............................................................. 4-11
4.3.1.1.1 Introduction and application example ............................................................................... 4-11
4.3.1.1.2 Overview of the control word (control word 1 and control word 2) ................................... 4-13
4.3.1.1.3 Selecting the source for control word 1 (bit 0-7) ............................................................... 4-14
4.3.1.1.4 Selecting the source for control word 1 (bit 8-15) ............................................................. 4-15
4.3.1.1.5 Selecting the source for control word 2 (bit 16-23) ........................................................... 4-16
4.3.1.1.6 Selecting the source for control word 2 (bit 24-31) ........................................................... 4-17
4.3.1.1.7 Significance of control word- (1 and 2) commands........................................................... 4-18
4.3.1.2 Status word (status word 1 and status word 2) ................................................................ 4-23
4.3.1.2.1 Introduction and application example ............................................................................... 4-23
4.3.1.2.2 Overview of the status word (status word 1 and status word 2) ....................................... 4-24
4.3.1.2.3 Selecting the destinations for the status word (bits 0 - 31) ............................................... 4-25
4.3.1.2.4 Significance of the status word messages........................................................................ 4-26
4.3.1.3 Setpoints........................................................................................................................... 4-28
4.3.1.4 Actual values .................................................................................................................... 4-29
4.3.2 Binary inputs ..................................................................................................................... 4-30
4.3.3 Binary outputs................................................................................................................... 4-30
4.3.5 Analog output.................................................................................................................... 4-31
4.3.6 Serial interfaces ................................................................................................................ 4-34
4.3.6.1.1 Basic converter interface SST1 ........................................................................................ 4-34
4.3.6.1.2 Basic converter interface SST2 (A2-X117), see Section 9.6, Options ............................. 4-34
4.3.6.2 Dual-port RAM (DPR for SCB, CB, TB)............................................................................ 4-34
4.3.9 Function selection (P052) .............................................................................................. 4-35
4.3.9.1 Generating the factory setting (P052 = 1)...................................................................... 4-35
4.3.9.2 Initialization (MLFB setting) (P052 = 2)........................................................................... 4-37
4.3.9.3 Download or upread (P052 = 3)....................................................................................... 4-39
4.3.9.4 Hardware configuration (P052 = 4)................................................................................ 4-40
4.3.9.5 Drive setting (P052 = 5) ................................................................................................. 4-41
4.3.9.6 Form DC link (P052 = 20) .............................................................................................. 4-42
4.3.9.7 Circuit identification (P052 = 21).................................................................................... 4-43
11 Blank
12 Logbook........................................................................................................................ 12-1
0 Definitions
QUALIFIED PERSONNEL
within the meaning of these operating instructions or the warning information on the product itself, are
persons who are entrusted with installation, assembly, commissioning and operation of the product and who
avail of qualifications corresponding to their activities, e.g.:
1. training or instruction or authorization to activate and deactivate, to earth and to mark circuits and
equipment in accordance with the standards of safety engineering.
2. training or instruction in accordance with the standards of safety engineering in the care and use of
suitable safety equipment.
3. training in First Aid
DANGER
within the meaning of these operating instructions or the warning information on the product itself, indicates
that death and/or substantial property damage will result if proper precautions are not taken.
WARNING
within the meaning of these operating instructions or the warning information on the product itself, indicates
that severe personal injury and/or substantial property damage will result if proper precautions are not taken.
CAUTION
within the meaning of these operating instructions or the warning information on the product itself, indicates
that slight personal injury or property damage will result if proper precautions are not taken.
NOTE
within the meaning of these operating instructions indicates important information about the product or the
respective part of the operating instructions to which attention is drawn.
NOTE
For reasons of clarity, these operating instructions do not contain all details of all types of the product and can
also not take into account every conceivable installation, operation or maintenance circumstances.
You can consult your local Siemens branch if you should require further information or if particular problem
occur that are not dealt with in adequate detail in the operating instructions.
Attention is also drawn to the fact that the contents of this instruction manual shall not become part of or
modify any prior or existing agreement, commitment or legal relationship. The sales contract, which also
contains the complete and solely valid warranty stipulations, contains the entire obligations of Siemens. These
contractual warranty stipulations are neither extended nor limited by the statements given in instructions and
documentation.
CAUTION
The equipment contains electrostatically sensitive devices. These components may be destroyed very easily
by improper handling. Please observe the following notes if you nevertheless have to work with electronic
modules:
Electronic modules should only be touched if absolutely necessary to carry out work on them.
If modules nevertheless have to be touched, you must discharge your own body directly beforehand (this is
best done by touching an earthed conductive object such as the PE contact of a socket).
Modules must not come into contact with highly insulating materials e.g. plastic films, insulating desktops
or synthetic fibber clothing items.
Modules must only be placed on conductive surfaces.
When soldering modules, the tip of the soldering iron must be earthed.
Modules and components must only be stored or dispatched in conductive packaging (e.g. metallized
plastic boxes or metal tins).
If packagings are not conductive, modules must be placed in a conductive envelopment prior to packaging.
In this case, use can be made of conductive foam rubber or domestic aluminum foil, for example.
The necessary protective measures for ESDs are elucidated once again in the following figure:
a = conductive floor d = ESD coat
b = ESD desk e = ESD armband
c = ESD shoes f = earthing terminal on cabinets
d d d
b b
e e
f f f f f
c a c
a a
WARNING
When operating electrical equipment, certain parts of such equipment are inevitably live.
Owing to the dc link capacitors, hazardous voltages are present on the equipment up to
5 min. after deenergization (power terminal and electronic power supply). This is why it is
not permitted to open the housing until after waiting for 5 minutes.
Non-observance of warning notices can result in death, severe personal injury or
considerable property damage.
Such personnel must be thoroughly acquainted with all warnings and maintenance
activities.
Perfect and safe operation of the equipment requires proper transport, expert storage,
installation and assembly and cautious operation and maintenance.
1 Description
1.1 Application
The rectifier/regenerating units of the SIMOVERT Master Drives 6SE70 series are power electronics devices for
supplying the DC voltage to the SIMOVERT Master Drives 6SEE70 series of inverters. The rectifier/regenerating
units convert the voltage of a three-phase system into a fixed DC voltage (depending on the operating mode and
voltage tolerance). This voltage is kept constant within a specified range even when the inverter is feeding power
back into the system. The following voltages are specified for the DC voltage output (DC link voltage):
The units with system input voltages of 208 to 230V are identical to the units with system input voltage of 380 to
460V. You only have to set the P071 to the corresponding system input voltage.
You can connect one or more inverters to the output. The total of the rated currents of the installed inverters may
then exceed the rated current of the rectifier/regenerating unit. When planning your system, however, make sure
that the aggregate DC load currents at no time exceed the rated DC current of the rectifier/regenerating unit
The output current can be increased by connecting power sections of size K in parallel. Up to 2 parallel units of
the same rated current can be connected in parallel with one basic unit (see Section 3.7 for further details on
parallel connection)
You can make technological adaptations and expansions over a defined interface in the control section.
Harmonic loading on the supply network can be reduced by coupling 2 units for "12-pulse mode" (for further
details on "12-pulse mode", see Section 3.8).
A 24 V external supply is required for operating the units (see Sections 3.5 and 9.3).
The rectifier/regenerating unit is suitable for connecting several inverters to a common DC bus. This permits the
exchange of energy between motoring and generating drives, and thus saves energy.
Once the DC link capacitors have been precharged, the inverters are ready for operation.
The rectifier/regenerating unit is controlled from an operator panel which is in the door of the unit for size C, and
on the electronics box for sizes E, H and K. The operator can also control the unit over a terminal block or
through a serial interface.
Optional interfaces and intelligent I/O modules are available in conjunction with programmable controllers and
other automation equipment for controlling the rectifier/regenerating units.
Avoid extreme vibrations and hard impacts during transport, e.g. when lowering the unit.
Pay attention to the notes on the packaging relating to transport, storage and proper handling.
The converter can be installed after unpacking it and checking the consignment for completeness and
damage.
The packaging consists of cardboard and corrugated cardboard for units of size C. The units of size E, H
and K are bolted onto pallets with fixing pieces in their usual operating position and packed with
cardboard. The packaging may be disposed of in accordance with local cardboard disposal regulations.
You should notify your freight forwarder immediately if you discover any transportation damage.
2.2 Storage
The units must be stored in clean dry rooms. Temperatures between 25 °C (13 °F) and + 70 °C (158 °F) are
permissible. Temperature fluctuations > 20 K per hour are not permissible.
WARNING
For safe operation of the unit, it is presumed it will be assembled and commissioned by
qualified personnel, paying attention to the warning notes given in these operating
instructions.
Particular note must be taken both of the general and national erection and safety
regulations regarding work on power installations (e.g. VDE) and regulations regarding the
proper use of tools and of personal protective equipment.
Non-observance of warning notices can result in death, severe personal injury or
considerable property damage.
The unit must be protected against the ingress of foreign matter as otherwise proper
functioning and safety will not be guaranteed.
WARNING
Dimension cabinet ventilation according to the
dissipated power! (Technical data in Chapter 14)
The unit’s ambient climate in operating rooms must not exceed the values
6SE70
of code 3K3 as detailed in DIN IEC 721 Part 3-3 /04.90. A reduction of
power as detailed in Chapters 14.1 and 14.2 is necessary in the event of
temperatures > 40 °C (104 °F) and altitudes >1000m. The terminal
voltage has to be reduced for altitudes > 2000m.
Carry out assembly in accordance with the dimension drawings in Cooling air
Section 2.4. ≤ 40 °C (50 °C)
NOTE
In the case of units of size H and K, all plastic covers must be mounted to ensure correct air flow and
cooling for the units.
3)
2) Exhaust air 6)
100
Z 1) Mounting hole for screw M6.
82 126,7
69 52
2) Hook (suspension) for mounting on a
16
SIEMENS g-rail according to EN50035
1 2 3 4 5
54
X9
U1 V1 W1 1PE C D X9
3) Space required for cooling the unit.
PMU X1
L1 L2 L3 L+ L-
A23 4) Screen connection for two cables.
X1
Siemens AG 6SE7087-6AK85-1AA0
Figure 2.2 Dimension drawing, size C
X300
V21+24 V25+22 5) Shock-hazard protection
V23+26
6) Connector for power supply DC24V and
A10 main contactor
R100
Dimension drawings
A10
600
600
No displacement of the centre of gravity
V11+14 V13+16 V15+12
SIEMENS
X20.1
X47
X48
R77
R78
A23
X30.1
X30.2
Detail Z
R75
R76
X4 4) max. 5,7
WARNUNG
X4
WARNUNG
1T1 1T2 1T3 DANGER
DANGER
54
43
23
25
34
90 56 Air intake 86
100
180 350
1) 3)
2-3
Transport, Unpacking and Assembly
5) 1) Mounting hole for screw M8
2-4
2) Mounting hole for power connections:
Front view M16 for 6SE7036-1EE85-1AA0, 6SE7035-4FE85-1AA0
350 6SE7034-2HE85-1AA0 and 6SE7035-3HE85-1AA0
9) 340 M12 for every other units
b
294 3) Connection for PE, mounted:
269 M16 for 6SE7036-1EE85-1AA0, 6SE7035-4FE85-1AA0
44,5 Exhaust air 6SE7034-2HE85-1AA0 and 6SE7035-3HE85-1AA0
180
1) M12 for every other units
2) 4) Hole for crane hook ∅30mm
PMU 4)
C/L+ D/L- PMU 5) Front cover only for design IP20
X300 5) 6) connector for power supply DC24V and main contactor
A10
Transport, Unpacking and Assembly
1025
1050
6SE7031-5FE85-1AA0 400 300
1000
F1 F2
941
6SE7032-4FE85-1AA0 450 350
X29 X19 6SE7032-7FE85-1AA0 450 350
X9 F3 F4 V21 to V26 6SE7033-5FE85-1AA0 500 400
6SE7034-2FE85-1AA0 500 400
148 6SE7035-4FE85-1AA0 600 500
6) 6SE7031-4HE85-1AA0 400 300
U1 V1 W1 7) E1 6SE7032-2HE85-1AA0 400 300
L1 L2 L3 6SE7032-7HE85-1AA0 400 300
94,5 6SE7034-2HE85-1AA0 500 400
41
352
6SE7035-3HE85-1AA0 600 500
286
2) 1U2 1V2 1W2
1T1 1T2 1T3 10) Remove transport plates before start-up
PE PE
147
25
No displacement of the centre of gravity
10
17 ∅17 ∅13 17 Air intake Weight: refer to section 14
30 10) 30 ∅13
100 9) a 70 Dimension: mm
10) 3) 1) 168,5 ∅17
237,5
292
Siemens AG 6SE7087-6AK85-1AA0
Front view
12.96
508 285
376 225
Mounting holes for wall mounting 26
234 40 119 155
with M8 bolts Exhaust air
7) 92 40 26 7) 130 7)
61 63 85
67
C/L+ D/L- D/L- C/L+
2)
26
250
252
1) Mounting hole for M12 screw
40
U1/L1 V1/L2 W1/L3 2) 2) M12 thread
Siemens AG 6SE7087-6AK85-1AA0
Figure 2.4 Dimension drawing, size H
W1 V1 U1
PE1
L3 L2 L1 3) Screen connection for cables
50
50
T1 4) Connector for 24 V DC power supply
PE1 T2 and main contactor
F11 F14 F13 F16 F15 F12
X300
A10
1400
1300
Options
A23
X27
F5 F1 F2
3) X9
When the units are installed in cabinets,it must
X9 4)
be ensured that the air intake and exhaust is
X19 adequate (for air requirements and intake air
X19 5) X9 temperature, see Section 14 "Technical Data").
80
45
1U2/1T1 1V2/1T2 1W2/1T3
40 50
119 270
92 40 70 6) Air intake 296
234 40 424
376 40 551
2-5
Transport, Unpacking and Assembly
2-6
Front view
40
400 665
340 555 3)
Mounting holes for wall mounting
40 with M8 bolts
270 420
200 310
40 Exhaust air
130 175
40 26 26 26 26
85 50
1)
26
1U 1V 1W 1C 1D
87
PE1 PE1
L1 L2 L3 L+ L- 1) Mounting hole for M12 screw
50 62
7b)
26
PMU 1U/L1 1C/L+ 1V/L2 1D/L- 1W/L3 2) M12 thread
X300
Transport, Unpacking and Assembly
1730
1650
7a)
137,5
112,5 50
25
Siemens AG 6SE7087-6AK85-1AA0
12.96 Transport, Unpacking and Assembly
PMU
27
43
82
Printed-circuit board
Front cover
44
Front of
enclosure
Printed-circuit board
Figure 2.6 Clearance between PCBs and front cover (size C) Figure 2.7 Clearance between PCBs and PMU (size E)
3 Connection
WARNING
The units are operated at high voltages.
Only carry out connection work after disconnecting the voltage!
All work on the unit must only be carried out by qualified persons.
Non-observance of warning notices can result in death, severe personal injury or
considerable property damage.
Damage or destruction can result if the unit is incorrectly connected.
As the result of the dc link capacitors in the connected SIMOVERT Master Drives, the unit
still contains a hazardous voltage up to 5 min. after isolation. This is why it is only permitted
to open the unit after observing an appropriate waiting time.
The power terminals and control terminals may carry a voltage even when the motor is at
standstill.
When working on the open unit, pay attention to the fact that live parts are exposed. The
unit may only be operated with the front covers attached.
The user is responsible for ensuring that the motor, converter, rectifier/regenerating unit
and other units are installed and connected in accordance with the technical regulations
recognized in the country of installation (in Germany: VDE, VBG4) and other regionally
valid regulations. In doing so, particular attention must be paid to cable dimensioning,
fusing, earthing, deactivation, isolation and overcurrent protection.
CAUTION
The power cables must be fixed in position mechanically outside the unit.
NOTES
An external 24 V power supply is required for operation of the units (see Chapters 3.5 and 9.3).
Operational range of the unit: 20 V to 30 V.
X19-1
X19-2
1T1 1T2 1T3
A23
1U2 Autotransformer/
1T1 regen. system Mains fan
1V2
1T2
PE PE
1W2
X1 1T3
Figure 3.1 Mains connection size C Figure 3.2 Mains connection size E
DC-link 1) DC-link 1)
(DC output) (DC output)
C/L+ D/L-
C/L+ D/L-
PE1
Mains 1)
U1/L1 V1/L2 W1/L3
U1/L1 V1/L2 W1/L3
PE1
Mains fan
X19
Mains 1)
Mains fan X9
X19
X9 PE2
Figure 3.3 Mains connection size H Figure 3.4 Mains connection size K
1) Due to the press-in nuts, cable lugs or DC rails can only be connected to the terminal rails from the front.
WARNING
The operating coils of contactors and relays that are connected to the same supply network
as the unit or that are located in close proximity of the unit must be connected to
overvoltage limiters, e.g. RC circuits.
An RCCB (residual-current-operated circuit-breaker) must not be used to protect the
rectifier/regenerating unit (DIN VDE 0160).
Voltage is only permitted to be applied to the unit when SIMOVERT Master Drives are
connected. Operation without a connected DC link capacitor is not permitted!
If the DC link terminals are connected incorrectly or short-circuited, the SIMOVERT Master
Drives inverter will be destroyed!
To reduce mains pollution, limit harmonics and reduce current ripple, the total system
inductance for the supply and feedback connection (incl. commutating reactor and, where
applicable, autotransformer must result in a total relative short-circuit voltage u k between
4% and 10%.
Connect the fan power supply to X19.
The fan continues to run for about four minutes or until a certain cooling element
temperature threshold is undershot (provided its power supply is connected) after the unit
has been switched off, following fault messages, on canceling the enable signal and after
isolating the system supply connection.
Despite switching the voltage off at the power terminals, a voltage may still exist on
terminal X19 due to the external fan supply.
NOTES
The supply voltages applied to the rectifier and regenerating power terminals (U1/L1, V1/L2, W1/L3 and
1U2/1T1, 1V2/1T2, 1W2/1T3) must have an identical phase angle and identical frequency.
Recommendation: The inductive components of the impedance drop uk of the (auto) transformer should lie
between 1.5 and 3% (see Table 3.4).
Commutating reactor: Selection of the reactors for 4 % uk should be based on the rated current in
regenerative mode on the line side (see Technical Data). In weak or low-power systems, the uk of the
commutating reactor must be decreased in order not to exceed the upper limit for the total uk of 10%.
A further measure in the case of extremely high uk values for the supply network can be implemented
by connecting the primary side of the autotransformer to the supply network directly (before the
commutating reactors), to ensure that the total uk value in the regenerating direction will not be too
high.
Rectification Rectification
DC link DC link
Regeneration Regeneration
Mains Mains
For the selection of the commutating reactors, see Table 3.5 and Catalog DA93.1.
With an extremely high total uk value in the regenerative direction, it may be necessary due to the
increased thyristor current commutating time, to reduce the inverter step limit (parameter P776). This
may mean it is necessary to reduce Ud.
Output reactors in the DC circuit are not permitted (even with the parallel connection of power sections or in
12-pulse mode), because the DC link voltage is measured at the unit output terminals.
Sizes C and E
Terminal X19 fused with fuse (F3 and F4):
T2A/250V time-lag 5x20 mm
(19198-T2A/250V Messrs. Wickmann-Werke GmbH or 0034.3993 FSD Messrs. Schurter)
or
T2A/250V time-lag 6.3x32 mm (¼“ x 1¼“)
(19343-T2A/250V Messrs. Wickmann-Werke GmbH or 0034.5231 FST Messrs. Schurter)
Sizes H and K
Terminal X19 fused with fuse (F3 and F4):
T2A/250V time-lag 6.3x32 mm (¼“ x 1¼“)
(19343-T7A/250V Messrs. Wickmann-Werke GmbH or 0034.5243 FST Messrs. Schurter)
The units are designed for permanent connection to the system in keeping with DIN VDE 0160 Section 6.5.2.1.
Protective conductor connection: Min. cross-sectional area 10 mm2 (see Table 3.2).
The conductor cross-sectional areas listed in Table 3.2 are maximum connectable cross-sections. The data is
given for multicore cable. The cross-sections actually connected must be determined in accordance with the
applicable regulations - e.g. DIN VDE 100 Part 523, DIN VDE 0276 Part 1000.
1) C=Cable, R=Rail
2) American Wire Gauge
3) Terminal connection area: Multicore10mm2 to 50mm2 AWG 8 to AWG 1/0
Stranded 3.5mm2 to 35mm2 AWG 12 to AWG 2
1) C=Cable, R=Rail
2) American Wire Gauge
Column 1, 2: Semiconductor protection only, lines are not reliably protected. Discriminative line protection is
assured only by correlating the line protection fuses to the installed conductor cross-section in
accordance with the applicable regulations - e.g. DIN VDE 0100 Teil 430.
1) Not a US standard
Single-core cables with conductor cross-sections of 0.2 to 2.5 mm2 (AWG: 24 PS Main contactor
to 14) can be connected to X9 (finely stranded 1.5 mm2 with core end ferrules). 24V DC control
P M
The main contactor is driven over isolated contacts X9.4 and X9.5. 1 2 3 4 5
X9
Technical specifications of main contact control circuit: 230V
Size C: max. 3A at p.f.0.4; max. making capacity 1500VA; with switching
voltage of 30 V DC, max 5A DC 230V AC
Size E, H, K: max. 5A at p.f.0.4; max. making capacity 3000VA; with
Figure 3.3 24 V DC and main
switching voltage of 30 V DC, max 8A DC
contactor control
connections
Table 3.8 Connector X9 pin assignments for auxiliary power supply and main contactor control
NOTE
The main contactor’s operating coil must be protected, for example, by RC elements (Chapter 9).
In the event of a line-side short-circuit in front of the super-fast built-in fuses, the power fed in from the supply
depends on the protective devices provided on the system-side (NH fuses or circuit-breakers).
To ensure that the forces and temperatures that result from short-circuits of this type can be kept within
acceptable limits for the units, the following values calculated in accordance with DIN VDE 0660 Part 500 must
be complied with by the supply and by the fuses or circuit-breakers connected before the unit.
Size H:
Rated short-time withstand current: Icw = 27.86 kA / 1s or Icw = 88.1 kA / 0,1s
Rated surge withstand current: Ipk =85 kA
The power rails must be mechanically buffered to absorb the short-circuit forces directly in front of their entry
point into the unit.
Size K:
Rated short-time withstand current: Icw = 69,86 kA / 1s or Icw = 220 kA / 0,1s
Rated surge withstand current: Ipk =85 kA
The power rails must be mechanically buffered to absorb the short-circuit forces directly in front of their entry
point into the unit.
WARNING
The rectifier/regenerating unit must be isolated before connecting the control leads to the
CUR
You can control the rectifier/regenerating unit over the following interfaces:
Control terminal block on the CUR electronic module
RS 485 serial interface on the CUR electronic module
Operator panel OP 1 (see Chapter 9 Options)
RS485 and RS232 serial interface on the PMU X300
CAUTION
The CUR incorporates ESD-endangered components that may be destroyed if improperly
handled. See also under the measures recommended to protect ESD-endangered
components in the introductory chapter entitled "General".
Conductors with cross-sectional areas of 0.14 to 1.5 mm2 (AWG: 26 to 16), or 1 mm2 (AWG: 18), finely stranded
with core end ferrules, can be connected to the connectors (Recommended: 0.5 mm2 (AWG: 20)).
NOTE
When installed, control leads must be shielded and isolated from the power cables, laying them at a minimum
spacing of 20 cm. The shield must be connected at both ends. On the unit's housing, the shield is
connected with shield clamps. Handling of these clamps is shown in Figure 3.4.
If they intersect, control and power cables must be run at an angle of 90° to each other.
Figure 3.6 Connecting the control leads and handling the shielding clamps
If two shielding clamps cannot cope with the number of control leads on the Size C unit, the "EMC shielding
enclosure" option should be used.
Order number:
Size C 6SE7090-0XC87-3CA0
R135
A10
CUR
PMU
X100 S1
S2
X101
X102
R136
X104
Setting elements:
DIP switches S1, S2: Both open: No bus termination for the RS485 interface (terminals X100-1 to X100-4)
Both closed: Bus termination for the RS485 interface active (1500 between
RS485P and RS485N, 3900 from RS485P to +5V supply, 390
from RS485N to earth)
R135 and R136: 0 resistances as earth-frame (M) connection
M is connected to earth when the unit is supplied. Remove these resistances only to
avoid faults due to earth loops, i.e. if the electronics frame is connected in some other
way to earth (e.g. through signal leads or the frame terminal of the power supply unit).
If option modules are used, a further earth-frame (M) connection may have to be
removed. (please refer to the description of these modules).
Electronics terminals:
X300
P 5 4 3 2 1
9 8 7 6
3-20
1AC 50-60Hz, 230V
Figure 3.9
Connection
K1
Filter
(optional)
binary selecting inputs
24V-power supply
RS485 ê OP1, SIMOVIS unit
RS232 ê SIMOVIS
6 7 8 9 10 11 12 13
X9-1 X9-2 X9-3 X9-4 X9-5
X101
X300
F1 F2
P24 M M
K1-2 PE X1: U1 V1 W1 X4: 1U2 1V2 1W2
Power supply L1 L2 L3 1T1 1T2 1T3
X308 X108 +24V
PMU A10
C98043-A1680 +5V +15V -15V +24V
Load
RESET
L_DSAVE
Option modules X107
X109 X239
BI
P5
5 M
S2
P5 390Ω
A23
R15 M C98043-A1681
X115 X30-1 R100 E1
P
analog outputs
Figure 3.10
K1
1
Filter
(optional)
binary selecting inputs
24V-power supply
RS485 ê OP1, SIMOVIS unit
RS232 ê SIMOVIS ϑ
1U1 2U1
6 7 8 9 10 11 12 13 1U1
X9-1 X9-2 X9-3 X9-4 X9-5 1V1 2V1
1V1
X101 1W1
X300 1W1 2W1
F1 F2
Siemens AG 6SE7087-6AK85-1AA0
P24 M M
K1-2 PE X1: U1 V1 W1 X4: 1U2 1V2 1W2
Power supply L1 L2 L3 1T1 1T2 1T3
X308 X108 +24V
PMU A10
Bürde
RESET
L_DSAVE
Option modules X107
X109 X239
BI
P5
5 M
S2
P5 390Ω
A23
R15 M C98043-A1681
analog outputs
3-21
Connection
3AC 50-60Hz, 400V
3AC 50-60Hz, 500V
3AC 50-60Hz, 690V
3-22
1AC 50-60Hz, 230V
Connection
Figure 3.11
K1
Filter
(optional)
binary selecting inputs
24V-power supply
RS485 ê OP1, SIMOVIS unit
RS232 ê SIMOVIS
6 7 8 9 10 11 12 13
X9-1 X9-2 X9-3 X9-4 X9-5
X101
X300
F1 F2
P24 M M
K1-2 PE X1: U1 V1 W1 X4: 1U2 1V2 1W2
Power supply L1 L2 L3 1T1 1T2 1T3
X308 X108
RESET
Bürde
L_DSAVE
X109 X239
Option modules X107
BI
P5
5 M
S2
P5 390Ω
A23
R15 M
C98043-A1682
X115 X30-1 R100 E1
P
Figure 3.12
K1
1
Filter
(optional)
binary selecting inputs
24V-power supply
RS485 ê OP1, SIMOVIS unit
RS232 ê SIMOVIS ϑ
1U1 2U1
6 7 8 9 10 11 12 13 1U1
X9-1 X9-2 X9-3 X9-4 X9-5 1V1 2V1
1V1
X101 1W1
X300 1W1 2W1
Siemens AG 6SE7087-6AK85-1AA0
F1 F2
P24 M M
K1-2 PE X1: U1 V1 W1 X4: 1U2 1V2 1W2
Power supply L1 L2 L3 1T1 1T2 1T3
X308 X108
RESET
Bürde
L_DSAVE
X109 X239
Option modules X107
BI
P5
5 M
S2
P5 390 Ω
A23
R15 M
C98043-A1682
3-23
Connection
3AC 50-60Hz, 400V
3AC 50-60Hz, 500V
3AC 50-60Hz, 690V
3-24
1AC 50-60Hz, 230V
Connection
Figure 3.13
K1
24V-power Filter
supply unit (optional)
binary selecting inputs
X9-1 X9-2 X9-3 X9-4 X9-5
RS485 ê OP1, SIMOVIS
RS232 ê SIMOVIS
6 7 8 9 10 11 12 13
X9-1 X9-2 X9-3 X9-4 X9-5
X101
X300
F5 F1 F2
P24 M M K1-2
PE X1: U1 V1 W1 X4: 1U2 1V2 1W2
L1 L2 L3 1T1 1T2 1T3
X308 X108
Power supply
PMU A10
C98043-A1680 +5V +15V -15V +24V
Bürde
RESET
X109 X239
L_DSAVE
Option modules X107
BI
P5
X100 390 Ω 12
Microprocessor selection:
RS485P
1 Open and closed-loop
2 control of the DC link
S1 12
RS485 3 150 Ω voltage A23
RS485N
4 C98043-A1685
5 M
S2
P5 390 Ω
M X30-1 ϑ E1 M
R15 1~
X30-2 R100
X115
P X31-1 ϑ
C98043-A1690 14 15 16 17 18 19 20
Figure 3.14
K1
24V-power 1
Filter
supply unit (optional)
binary selecting inputs
X9-1 X9-2 X9-3 X9-4 X9-5
RS485 ê OP1, SIMOVIS
RS232 ê SIMOVIS ϑ
1U1 2U1
6 7 8 9 10 11 12 13 1U1
X9-1 X9-2 X9-3 X9-4 X9-5 1V1 2V1
1V1
X101 1W1
X300 1W1 2W1
Siemens AG 6SE7087-6AK85-1AA0
F5 F1 F2
P24 M M K1-2
PE X1: U1 V1 W1 X4: 1U2 1V2 1W2
L1 L2 L3 1T1 1T2 1T3
X308 X108
Power supply
PMU A10
Bürde
RESET
X109 X239
L_DSAVE
Option modules X107
BI
P5
X100 390 Ω 12
Microprocessor selection:
RS485P
1 Open and closed-loop
2 control of the DC link
S1 12
RS485 3 150 Ω voltage A23
RS485N
4 C98043-A1685
5 M
S2
P5 390 Ω
M X30-1 ϑ E1 M
R15 1~
X30-2
C98043-A1690 14 15 16 17 18 19 20
3-25
Connection
3AC 50-60Hz, 400V
3AC 50-60Hz, 500V
3AC 50-60Hz, 690V
3-26
1AC 50-60Hz, 230V
Connection
Figure 3.15
K1
24V-power Filter
supply unit (optional)
binary selecting inputs
X9-1 X9-2 X9-3 X9-4 X9-5
RS485 ê OP1, SIMOVIS
RS232 ê SIMOVIS
6 7 8 9 10 11 12 13
X9-1 X9-2 X9-3 X9-4 X9-5
X101
X300
F5 F1 F2
P24 M M K1-2
PE X1: U1 V1 W1 X4: 1U2 1V2 1W2
L1 L2 L3 1T1 1T2 1T3
X308 X108
Power supply
PMU A10
C98043-A1680 +5V +15V -15V +24V
Bürde
RESET
X109 X239
L_DSAVE
Option modules X107
BI
P5
X100 390 Ω 12
Microprocessor selection:
RS485P
1 Open and closed-loop
2 control of the DC link
S1 12
RS485 3 150 Ω voltage A23
RS485N
4 C98043-A1685
5 M
S2
P5 390 Ω
X30-1 ϑ E2 M E1 M
R15 M 1~ 1~
X30-2 R100
X115
P X31-1 ϑ
Siemens AG 6SE7087-6AK85-1AA0
3AC 50-60Hz, 400V
3AC 50-60Hz, 500V
3AC 50-60Hz, 690V
12.95
Figure 3.16
K1
24V-power 1
Filter
supply unit (optional)
binary selecting inputs
X9-1 X9-2 X9-3 X9-4 X9-5
RS485 ê OP1, SIMOVIS
RS232 ê SIMOVIS ϑ
1U1 2U1
6 7 8 9 10 11 12 13 1U1
X9-1 X9-2 X9-3 X9-4 X9-5 1V1 2V1
1V1
X101 1W1
X300 1W1 2W1
Siemens AG 6SE7087-6AK85-1AA0
F5 F1 F2
P24 M M K1-2
PE X1: U1 V1 W1 X4: 1U2 1V2 1W2
L1 L2 L3 1T1 1T2 1T3
X308 X108
Power supply
PMU A10
Bürde
RESET
X109 X239
L_DSAVE
Option modules X107
BI
P5
X100 390 Ω 12
Microprocessor selection:
RS485P
1 Open and closed-loop
2 control of the DC link
S1 12
RS485 3 150 Ω voltage A23
RS485N
4 C98043-A1685
5 M
S2
P5 390 Ω
X30-1 ϑ E2 M E1 M
R15 M 1~ 1~
3-27
Connection
3-28
Figure 3.17
3.6
Connection
1
Power sections
E1
Termal sensor M
ϑ
on the heatsink
R100 X47-1
X20.1-1
X20.1-2
k
X20-1
X20-2
K k K X47-4
Load 2
T1 T2 X47-3
R76
R78
L l L l X47-2
X30-1
X30-2
Load 1
R75
R77
- +
X48-1
X239
K k K k X48-4
T3 T4 X48-3
L l L l F1
X48-2 T2A
+ X9-1
A10-X109
(C98043-A1680) F2
X24-1 T3,2A X9-2
-
X11-1 G1 G2 X24-2
X11-2
K X9-3
N.C.
Arrangement of thyristor modules K AK A A AK
X9-4
V11+V14 V21+V24 X21-2 K1-2
D/L- X14-2 G2 G1 X21-1
X1: U1/L1 V1/L2 W1/L3 C/L+ X9-5
X14-1
X26-1
X13-1 G1 G2 X26-2
T1 T2 X13-2
K
X24 X21 X26 X23 X22 X25 K AK A A AK
F10 V13+V16 V23+V26
G2 G1 G2 G1 G2 G1 X23-2
X16-2 G2 G1 X23-1
X16-1
A A A
X22-1
Rectifier/Regenerating Unit Operating instructions
X15-1 G1 G2 X22-2
K K K X15-2
K
K AK A A AK
AK AK AK
V15+V12 V25+V22 X25-2
V21+24 V23+26 V25+22
X12-2 G2 G1 X25-1
X12-1
Siemens AG 6SE7087-6AK85-1AA0
1W2
1U2
1V2
U1
W1
V1
K K K
A23
C C98043-A1681 D
A A A
A23 A23
C98043-A1681 C98043-A1681
G1 G2 G1 G2 G1 G2
12.95
12.95
Figure 3.18
E1
Termal sensor ϑ M
on the heatsink 1~
R100 X47-1
K k K k X47-4
230V~
T1 T2 X47-3
R76
R78
R80
L l L l X47-2
Load 2
X30-1
X30-2
X29-1
X29-2
X29-3
X19-1
X19-2
Siemens AG 6SE7087-6AK85-1AA0
R75
R77
R79
F3 F4
Load 1
K101-2 T3 T4 X48-3
L l L l F1
X48-2 T2A
+ X9-1
A10-X109
R11+R14
R13+R16
R21+R24
R23+R26
G2 G1 G2 G1 G2 G1
X24 X21 X26 X23 X22 X25
K2 A K1 K2 A K1 K2 A K1
A23 A23
C98043-A1682 C98043-A1682
U1.1
U1.2
V1.1
V1.2
A601
W1.1
W1.2
1U2.1
1U2.2
1V2.1
1V2.2
1W2.1
1W2.2
K K K
C
C98043-A1683
D
AK AK AK
U1/L1 1U2/1T1 V1/L2 1V2/1T2 W1/L3 1W2/1T3 X1: C/L+ X1: D/L-
3-29
Connection
3-30
X1: U1/ V1/ W1/ PE X4: 1U2/ 1V2/ 1W2/
L1 L2 L3 1T1 1T2 1T3
Connection
Figure 3.19
E1
Termal sensor ϑ M
on the heatsink 1~
R100 X47-1
K k K k X47-4
230V~
T1 T2 X47-3
R76
R78
R80
L l L l X47-2
Load 2
X30-1
X30-2
X29-1
X29-2
X29-3
X19-1
X19-2
R75
R77
R79
F3 F4
Load 1
K101-2 T3 T4 X48-3
L l L l F1
X48-2 T2A
+ X9-1
A10-X109
(C98043-A1680) F2
X11-1 X24-1 T3,2A X9-2
K1 G1
-
X11-2 G2 K2 X24-2
K AK A A AK K X9-3
N.C.
V11+V14 V21+V24 X9-4
K1-2
X14-2 K2 G2 G1 K1 X21-2
Arrangement of thyristor modules X14-1 X21-1 X9-5
R11+R14
R13+R16
R15+R12
R21+R24
R23+R26
R25+R22
G2 G1 G2 G1 G2 G1
X24 X21 X26 X23 X22 X25
K2 A K1 K2 A K1 K2 A K1
A23 A23
C98043-A1682 C98043-A1682
U1.1
U1.2
V1.1
V1.2
A601
W1.1
W1.2
1V2.1
1V2.2
1U2.1
1U2.2
1W2.1
1W2.2
K K K
C
C98043-A1683
D
AK AK AK
F10
T3 T4
U1/L1 1U2/1T1 V1/L2 1V2/1T2 W1/L3 1W2/1T3 X1: C/L+ X1: D/L-
Siemens AG 6SE7087-6AK85-1AA0
12.95
Figure 3.20
E1
Termal sensor ϑ M
on the heatsink 1~
R100 X47-1
K k K k X47-4
230V~
T1 T2 X47-3
R76
R78
R80
L l L l X47-2
Load 2
X30-1
X30-2
X29-1
X29-2
X29-3
X19-1
X19-2
Siemens AG 6SE7087-6AK85-1AA0
R75
R77
R79
F3 F4
Load 1
K101-2 T3 T4 X48-3
L l L l F1
X48-2 T2A
+ X9-1
A10-X109
K AK A A AK K X9-3
N.C.
V11+V14 V21+V24 X9-4
K1-2
X14-2 K2 G2 G1 K1 X21-2
Arrangement of thyristor modules X14-1 X21-1 X9-5
R11+R14
R13+R16
R15+R12
G2 G1 G2 G1 G2 G1
X24 X21 X26 X23 X22 X25
K2 A K1 K2 A K1 K2 A K1
A23 A23
C98043-A1682 C98043-A1682
U1.1
U1.2
V1.1
V1.2
A601
W1.1
W1.2
1V2.1
1V2.2
1U2.1
1U2.2
1W2.1
1W2.2
K K K
C
C98043-A1683
D
AK AK AK
F10
T3 T4
U1/L1 1U2/1T1 V1/L2 1V2/1T2 W1/L3 1W2/1T3 X1: C/L+ X1: D/L-
3-31
Connection
3-32
X1: U1/ V1/ W1/ PE X4: 1U2/ 1V2/ 1W2/
L1 L2 L3 1T1 1T2 1T3
Figure 3.21
Connection
E1
Termal sensor M
on the heatsink ϑ 1~
R100 X47-1
K k K k X47-4
230V~
T1 T2 X47-3
R76
R78
R80
L l L l X47-2
Load 2
X30-1
X30-2
X29-1
X29-2
X29-3
X19-1
X19-2
R75
R77
R79
F3 F4
Load 1
V13+V16 V23+V26
K K K X16-2 K2 G2 G1 K1 X23-2
X16-1 X23-1
V11+V14 V13+V16 V15+V12
X15-1 X22-1
AK AK AK
X15-2 K1 G1 G2 K2 X22-2
K AK A A AK K
T1 T2 V15+V12 V25+V22
X12-2 K2 G2 G1 K1 X25-2
X12-1 X25-1
K2 G2 G1 K1 K2 G2 G1 K1 K2 G2 G1 K1
R21
R24
R23
R26
R25
R22
R11+R14
R13+R16
R15+R12
A A A
A23 A23
C98043-A1682 C98043-A1682
U1.1
U1.2
V1.1
V1.2
A601
W1.1
W1.2
1V2.1
1V2.2
1U2.1
1U2.2
1W2.1
1W2.2
K K K
F10
T3 T4
Siemens AG 6SE7087-6AK85-1AA0
X1: U1/ V1/ W1/ PE X4: 1U2/ 1V2/ 1W2/
12.95
E1
Figure 3.22
Termal sensor M
ϑ 1~
on the heatsink X47-1
R100
K k K k X47-4
230V~ T1 T2 X47-3 R76
R78
R80
L l L l X47-2
Load 2
X30-1
X30-2
X29-1
X29-2
X29-3
X19-1
X19-2
R75
R77
R79
Load 1
F3 F4
T2A T2A X48-1
X239 K k K k X48-4
T3 T4 X48-3
K101-2 F1
Siemens AG 6SE7087-6AK85-1AA0
L l L l X48-2 T2A X9-1
A10-X109
F2
(C98043-A1680) X11-1 X24-1 T3,2A X9-2
X11-2 K1 G1 G2 K2 X24-2
K AK A A AK K X9-3
F10 K AK A A AK K
T1 T2
R11
R14
R13
R16
R15
R12
R21
R24
R23
R26
R25
R22
A23 A23
X24 X21 X26 X23 X22 X25
C98043-A1682 C98043-A1682
K2 G2 G1 K1 K2 G2 G1 K1 K2 G2 G1 K1
A A A
K K K
V1.1
V1.2
V1.1
V1.2
U1.1
U1.2
U1.1
U1.2
W1.1
W1.2
W1.1
W1.2
1V2.1
1V2.2
1V2.1
1V2.2
1U2.1
1U2.2
1U2.1
1U2.2
1W2.1
1W2.2
1W2.1
1W2.2
T3 T4
F10
U1/L1 1U2/1T1 V1/L2 1V2/1T2 W1/L3 1W2/1T3
3-33
Connection
PE X1: U1/L1 V1/L2 W1/L3 C/L+ D/L-
3-34
E1 M
1~ X47-1
Connection
Figure 3.23
Termal sensor K k K k X47-4
on the heatsink T1 T2
R75
R77
R79
X47-3
Load 2
L l L l X47-2
ϑ ϑ R76
R78
R80
X20-1
X20-2
Load 1
X29-1
X29-2
X29-3
X32-1
XU21
C24 R24 R21 C21
A10-X109
(C98043-A1680) XV13
G13 K16
X13-1 X16-2
G16
K13 V16 X16-1
X13-2 V13 K
K A A
X27
C13 R13 R16 C16
K26 G23
X26-2 X23-1
G26 K23
X26-1 V26 V23 X23-2
A K A K
F5
T2A XV23
C26 R26 R23 C23
F1
X9-1 T2A XW15
+ K12
G15 X12-2
24V-power F2 X15-1 G12
K15 V12 X12-1
supply unit T7A X15-2 V15
X9-2 K A K A
-
Siemens AG 6SE7087-6AK85-1AA0
12.95 Connection
Figure 3.24 Arrangement of the thyristor blocks, Size H (see dimension drawing in Section 2.4)
3-36
E2 M E1 M
1~ 1~ X47-1
Connection
Figure 3.25
Termal sensor K k K k X47-4
on the heatsink T1 T2
R75
R77
R79
X47-3
Load 2
L l L l X47-2
ϑ ϑ R76
R78
R80
R101 R100
X20-1
X20-2
Load 1
F112
F111
F141
F142
F132
F131
F161
F162
F152
F151
F121
F122
XU11
G11 K14
X11-1 X14-2
X31-1 K11 G14
X11-2 V11 V14 X14-1
X31-2 K A K A
X29-1
X29-2
X29-3
X32-1
XU21
C24 R24 R21 C21
A10-X109
(C98043-A1680) XV13
G13 K16
X13-1 X16-2
G16
K13 V16 X16-1
X13-2 V13 K
K A A
X27
C13 R13 R16 C16
K26 G23
Connections for X26-2 X23-1
G26 K23
parallel unit X26-1 V26 V23 X23-2
A K A K
F5
T2A XV23
C26 R26 R23 C23
F1
X9-1 T2A XW15
+ K12
G15 X12-2
24V-power F2 X15-1 G12
K15 V12 X12-1
supply unit T7A X15-2 V15
X9-2 K A K A
-
230V~ F3
T7A
X19-1
X48-2
L l L l X48-3
A23 T3 T4 X48-4 A23
C98043-A1685 K k K k X48-1 C98043-A1685
Siemens AG 6SE7087-6AK85-1AA0
12.95 Connection
Level A Level B
V11 V14
V13 V16
V15 V12
V24 V21
V26 V23
V22 V25
Figure 3.26 Arrangement of the thyristor blocks, view from right-hand side of unit, Size K (see dimension drawing in Section 2.4)
Figure 3.27
Connection
E1
Termal sensor M
ϑ
on the heatsink
R100 X47-1
K k K k X47-4
X20.1-1
X20.1-2
X20-1
X20-2
T1 T2 X47-3
R76
R78
L l L l X47-2
Load 2
X30-1
X30-2
- +
R75
R77
Load 1
X48-1
X239 k X48-4
K k K
T3 T4 X48-3
L l L l F1
X48-2 T2A
U1
K K K
W1
1U2
1V2
1W2
A23
C C98043-A1681 D
A A A
A23 A23
C98043-A1681 C98043-A1681
G1 G2 G1 G2 G1 G2
F10
T3 T4
X4:
1U2/1T1 1V2/1T2 1W2/1T3
X1: C/L+ X1: D/L-
Siemens AG 6SE7087-6AK85-1AA0
12.95
Figure 3.28
E1
Termal sensor ϑ M
on the heatsink 1~
R100 X47-1
K k K k X47-4
230V~
T1 T2 X47-3
R76
R78
R80
L l L l X47-2
Load 2
X30-1
X30-2
X29-1
X29-2
X29-3
X19-1
X19-2
Siemens AG 6SE7087-6AK85-1AA0
R75
R77
R79
F3 F4
Load 1
K101-2 T3 T4 X48-3
L l L l F1
X48-2 T2A
+ X9-1
A10-X109
G2 G1 G2 G1 X23 G2 G1
X24 X21 X26 X22 X25
R11+R14
R13+R16
R15+R12
K2 A K1 K2 A K1 K2 A K1
A23 A23
C98043-A1682 C98043-A1682
U1.1
U1.2
V1.1
V1.2
W1.1
W1.2
K K K A601
1V2.1
1V2.2
1U2.1
1U2.2
1W2.1
1W2.2
C
C98043-A1684
AK AK AK D
F10
T3 T4
3-39
Connection
3-40
X1: U1/ V1/ W1/ PE X4: 1U2/ 1V2/ 1W2/
L1 L2 L3 1T1 1T2 1T3
Connection
Figure 3.29
E1
Termal sensor ϑ M
on the heatsink 1~
X47-1
R100
K k K k X47-4
230V~ T1 T2 X47-3
R76
R78
R80
L l L l X47-2
Load 2
X30-1
X30-2
X29-1
X29-2
X29-3
X19-1
X19-2
R75
R77
R79
Load 1
F3 F4
T2A X48-1
T2A
X239 K k K k X48-4
T3 T4 X48-3
K101-2 F1
L l L l X48-2 T2A X9-1
A10-X109
F2
(C98043-A1680) X11-1 X24-1 T3,2A X9-2
X11-2 K1 G1 G2 K2 X24-2
K AK A A AK K X9-3
X13-1 X26-1
X13-2 K1 G1 G2 K2 X26-2
Arrangement of thyristor modules
K AK A A AK K
C/L+ D/L-
V13+V16 V23+V26
X16-2 K2 G2 G1 K1 X23-2
F10 X16-1 X23-1
K AK A A AK K
K K K
V15+V12 V25+V22
AK AK AK K2 G2
X12-2 G1 K1 X25-2
X12-1 X25-1
V11+ V14 V13+ V16 V15+ V12
T1 T2
R11
R14
R13
R16
R15
R12
R21
R24
R23
R26
R25
R22
A23 A23
C98043-A1682 C98043-A1682
G2 G1 G2 G1 G2 G1
X24 X21 X26 X23 X22 X25
K2 A K1 K2 A K1 K2 A K1
K K K
V1.1
V1.2
V1.1
V1.2
U1.1
U1.2
U1.1
U1.2
W1.1
W1.1
W1.2
W1.2
1V2.1
1V2.2
1V2.1
1V2.2
1U2.1
1U2.2
1U2.1
1U2.2
1W2.1
1W2.2
1W2.1
1W2.2
AK AK AK
Siemens AG 6SE7087-6AK85-1AA0
12.95
Figure 3.30
E1
Termal sensor M
on the heatsink ϑ 1~
X47-1
R100
K k K k X47-4
230V~ T1 T2 X47-3
R76
R78
R80
L l L l X47-2
Load 2
X30-1
X30-2
X29-1
X29-2
X29-3
X19-1
X19-2
R75
R77
R79
Load 1
F3 F4
T2A T2A X48-1
X239 K k K k X48-4
T3 T4 X48-3
K101-2
Siemens AG 6SE7087-6AK85-1AA0
L l L l F1
X48-2 T2A X9-1
A10-X109 F2
(C98043-A1680) X11-1 X24-1 T3,2A X9-2
X11-2 K1 G1 G2 K2 X24-2
F10 K AK A A AK K
T1 T2
R11
R14
R13
R16
R15
R12
R21
R24
R23
R26
R25
R22
A23 A23
X24 X21 X26 X23 X22 X25 C98043-A1682 C98043-A1682
K2 G2 G1 K1 K2 G2 G1 K1 K2 G2 G1 K1
A A A
U1.1
U1.2
U1.1
U1.2
W1.1
W1.2
W1.1
W1.2
1V2.1
1V2.1
1U2.1
1U2.2
1V2.2
1U2.1
1U2.2
1V2.2
1W2.1
1W2.2
1W2.1
1W2.2
T3 T4
F10
U1/L1 1U2/1T1 V1/L2 1V2/1T2 W1/L3 1W2/1T3
3-41
Connection
3-42
X1: U1/ V1/ W1/ PE X4: 1U2/ 1V2/ 1W2/
L1 L2 L3 1T1 1T2 1T3
Connection
Figure 3.31
E1
Termal sensor ϑ M
on the heatsink 1~
R100 X47-1
K k K k X47-4
230V~
T1 T2 X47-3
R76
R78
R80
L l L l X47-2
Load 2
X30-1
X30-2
X29-1
X29-2
X29-3
X19-1
X19-2
R75
R77
R79
F3 F4
Load 1
K AK A A AK K
V15+V12 V25+V22
T1 T2
X12-2 K2 G2 G1 K1 X25-2
X12-1 X25-1
R11
R14
R13
R16
R15
R12
K2 G2 G1 K1 K2 G2 G1 K1 K2 G2 G1 K1
A A A
A23 A23
C21 R21 R24 C24
C98043-A1682 C98043-A1682
U1.1
U1.2
V1.1
V1.2
W1.1
W1.2
K K K
C C23 R23 R26 C26
V21+V24 V23+V26 V25+V22 D
AK AK AK
A601 C25 R25 R22 C22
C98043-A1686
F10
T3 T4
U1/L1 1U2/1T1 V1/L2 1V2/1T2 W1/L3 1W2/1T3 X1: C/L+ X1: D/L-
Siemens AG 6SE7087-6AK85-1AA0
12.95
Figure 3.32
E1
Termal sensor ϑ M
on the heatsink 1~
R100 X47-1
K k K k X47-4
230V~
T1 T2 X47-3
R76
R78
R80
L l L l X47-2
Load 2
X30-1
X30-2
X29-1
X29-2
X29-3
X19-1
X19-2
Siemens AG 6SE7087-6AK85-1AA0
R75
R77
R79
F3 F4
Load 1
K101-2 T3 T4 X48-3
L l L l F1
X48-2 T2A X9-1
A10-X109
T1 T2 K AK A A AK K
V15+V12 V25+V22
X12-2 K2 G2 G1 K1 X25-2
X12-1 X25-1
K2 G2 G1 K1 K2 G2 G1 K1 K2 G2 G1 K1
A A A
R11+R14
R13+R16
R15+R12
R21+R24
R23+R26
R25+R22
A23 A23
C98043-A1682 C98043-A1682
U1.1
U1.2
V1.1
V1.2
W1.1
W1.2
K K K
1V2.1
1V2.2
A601
1U2.1
1U2.2
1W2.1
1W2.2
F10
T3 T4
3-43
Connection
3-44
X1: U1/ V1/ W1/ PE X4: 1U2/ 1V2/ 1W2/
L1 L2 L3 1T1 1T2 1T3
Figure 3.33
Connection
E1
Termal sensor ϑ M
on the heatsink 1~
X47-1
R100
K k K k X47-4
230V~ T1 T2 X47-3
R76
R78
R80
L l L l X47-2
Load 2
X30-1
X30-2
X29-1
X29-2
X29-3
X19-1
X19-2
R75
R77
R79
Load 1
F3 F4
T2A T2A X48-1
X239 K k K k X48-4
T3 T4 X48-3
K101-2 F1
L l L l X48-2 T2A X9-1
A10-X109
F2
(C98043-A1680) X11-1 X24-1 T3,2A X9-2
X11-2 K1 G1 G2 K2 X24-2
K AK A A AK K X9-3
K AK A A AK K
F10
V13+V16 V23+V26
G2 G1 G2 G1 G2 G1
X14 X11 X16 X13 X12 X15 X16-2 K2 G2 G1 K1 X23-2
K2 A K1 K2 A K1 K2 A K1
X16-1 X23-1
AK AK AK K AK A A AK K
R11
R14
R13
R16
R15
R12
R23
R25
R22
R21
R24
R26
A23 A23
X24 X21 X26 X23 X22 X25
C98043-A1682 C98043-A1682
K2 G2 G1 K1 K2 G2 G1 K1 K2 G2 G1 K1
A A A
K K K
V1.1
V1.1
U1.1
U1.2
V1.2
U1.1
U1.2
V1.2
W1.1
W1.2
W1.1
W1.2
1U2.1
1U2.2
1V2.1
1V2.2
1U2.1
1U2.2
1V2.1
1V2.2
1W2.1
1W2.2
1W2.1
1W2.2
T3 T4
F10
U1/L1 1U2/1T1 V1/L2 1V2/1T2 W1/L3 1W2/1T3
Siemens AG 6SE7087-6AK85-1AA0
12.95
Figure 3.34
E1
Termal sensor M
on the heatsink ϑ 1~
X47-1
R100
K k K k X47-4
230V~ T1 T2 X47-3
R76
R78
R80
L l L l X47-2
Load 2
X30-1
X30-2
X29-1
X29-2
X29-3
X19-1
X19-2
R75
R77
R79
Load 1
F3 F4
T2A T2A X48-1
X239 K k K k X48-4
T3 T4 X48-3
K101-2
Siemens AG 6SE7087-6AK85-1AA0
L l L l F1
X48-2 T2A X9-1
A10-X109
F2
(C98043-A1680) X11-1 X24-1 T3,2A X9-2
X11-2 K1 G1 G2 K2 X24-2
K AK A A AK K X9-3
F10 K AK A A AK K
T1 T2
R11
R14
R13
R16
R15
R12
R21
R24
R23
R26
R25
R22
A23 A23
X24 X21 X26 X23 X22 X25
C98043-A1682 C98043-A1682
K2 G2 G1 K1 K2 G2 G1 K1 K2 G2 G1 K1
A A A
K K K
V1.1
V1.2
V1.1
V1.2
U1.1
U1.2
U1.1
U1.2
W1.1
W1.2
W1.1
W1.2
1V2.1
1V2.2
1V2.1
1V2.2
1U2.1
1U2.2
1U2.1
1U2.2
1W2.1
1W2.2
1W2.1
1W2.2
T3 T4
F10
U1/L1 1U2/1T1 V1/L2 1V2/1T2 W1/L3 1W2/1T3
3-45
Connection
3-46
X1: U1/ V1/ W1/ PE X4: 1U2/ 1V2/ 1W2/
L1 L2 L3 1T1 1T2 1T3
Figure 3.35
Connection
E1
Termal sensor ϑ M
on the heatsink 1~
R100 X47-1
K k K k X47-4
230V~
T1 T2 X47-3
R76
R78
R80
L l L l X47-2
Load 2
X30-1
X30-2
X29-1
X29-2
X29-3
X19-1
X19-2
R75
R77
R79
F3 F4
Load 1
K101-2 T3 T4 X48-3
L l L l F1
X48-2 T2A X9-1
A10-X109
(C98043-A1680) F2
X11-1 X24-1 T3,2A X9-2
X11-2 K1 G1 G2 K2 X24-2
Arrangement of thyristor modules
K AK A A AK K X9-3
C/L+ D/L-
V11+V14 V21+V24 X9-4
K1-2
X14-2 K2 G2 G1 K1 X21-2
X14-1 X21-1 X9-5
F10
X13-1 X26-1
X14 X11 X16 X13 X12 X15 K1 G1
X13-2 G2 K2 X26-2
K2 G2 G1K1 K2 G2 G1 K1 K2 G2 G1 K1
K AK A A AK K
V13+V16 V23+V26
X16-2 K2 G2 G1 K1 X23-2
K K K
X16-1 X23-1
V11+V14 V13+V16 V15+V12 X15-1 X22-1
AK AK AK X15-2 K1 G1 G2 K2 X22-2
K AK A A AK K
V15+V12 V25+V22
T1 T2
X12-2 K2 G2 G1 K1 X25-2
X12-1 X25-1
K2 G2 G1 K1 K2 G2 G1 K1 K2 G2 G1 K1
A A A
R11
R14
R13
R16
R15
R12
A23 A23
C21 R21 R24 C24
C98043-A1682 C98043-A1682
K K K
C23 R23 R26 C26
V21+V24 V23+V26 V25+V22
V1.1
V1.2
U1.1
U1.2
W1.1
W1.2
1V2.1
1V2.2
1U2.1
1U2.2
1W2.1
1W2.2
AK AK AK
C25 R25 R22 C22
C
D
T3 T4
A601 C98043-A1684
F10
U1/L1 1U2/1T1 V1/L2 1V2/1T2 W1/L3 1W2/1T3
Siemens AG 6SE7087-6AK85-1AA0
12.95 Connection
The following table shows for each basic unit order number, the order number for the corresponding parallel unit
that can be connected in parallel.
Order No. for basic unit Order No. for parallel unit for
connecting in parallel
6SE7041-3EK85-1AA0 6SE7041-3EK85-1AD0
6SE7041-8EK85-1AA0 6SE7041-8EK85-1AD0
6SE7041-3FK85-1AA0 6SE7041-3FK85-1AD0
6SE7041-5FK85-1AA0 6SE7041-5FK85-1AD0
6SE7041-8FK85-1AA0 6SE7041-8FK85-1AD0
6SE7041-3HK85-1AA0 6SE7041-3HK85-1AD0
6SE7041-5HK85-1AA0 6SE7041-5HK85-1AD0
6SE7041-8HK85-1AA0 6SE7041-8HK85-1AD0
The parallel units have the same technical data as the corresponding basic units.
The parallel units do not include a CUR electronic module and are fitted with a C98043-A1695 (A23) Power
Interface module instead of a C98043-A1685 (A23) Power Interface module.
The parallel units do not require an external 24 V supply.
A 50-core ribbon cable is used to transfer firing pulse signals and monitoring signals. It also carries the power
supply for the parallel units.
The parallel unit(s) should be installed to the left of the basic unit (see Figure 3.36).
A23
A23 A23 C98043-A1685
C98043-A1695 C98043-A1695
X27 X27
X28 X28 X27
Figure 3.36 Connection of firing pulse signals and monitoring signals for the parallel units
NOTE
The permissible output current for a parallel arrangement is reduced (due to the current division between the
power sections) by 10% as compared with the sum of the rated currents of the separate power sections.
The following is required to ensure even current distribution between the basic unit and parallel unit(s).
Identical phases for the power section connections of the rectifier/regenerating units between the basic
units and parallel unit(s)
Use of identical power components (see above table for the corresponding parallel units and basic units)
Commutating reactors and autotransformers specific for each basic and parallel unit with identical technical
data. Each separate parallel path must have a minimum uk value of 2%.
In the case of extremely high uk values for the mains supply (low-power system), the primary side of the
autotransformer should be connected directly to the supply (before the commutating reactors), so that the
total uk value will not be too high in the regenerative direction.
With an extremely high total uk value in the regenerative direction, it may be necessary due to the increased
thyristor current commutating time, to reduce the inverter step limit (parameter P776). This may mean it is
necessary to reduce Ud.
.
Basic unit Basic unit
Rectification Rectification
Regeneration Regeneration
X27 X27
X28 X28
X28 X28
WARNING
Fault-free operation can only be guaranteed if the phases at the power section
terminals (U1/L1, V1/L2, W1/L3, 1U2/1T1, 1V2/1T2, 1W2/1T3, C/L+ and D/L-)
between the basic unit and parallel unit(s) are identical.
Non-compliance with this condition may result in destruction of the power
sections of the basic and parallel units.
The maximum permissible total cable length between the basic unit and parallel unit 1 or parallel unit 2 (if
present) is 15 m.
A 50-core ribbon cable, 2.6 m in length, is included in the scope of delivery of a parallel unit (spare parts order
No.: 6SY7010-8AA00).
Order No. for one cable "10 m round, screened": 6QX5368 (other lengths on request):
On connecting this round, 50-core cable with a diameter of 14 mm, its screen has to be laid bare by cutting away
the insulation and it must be connected to earth on both devices. To ensure the interference immunity of the
system, it is recommended that the cable is laid in an earthed metal pipe of at least 50 mm in diameter (to allow
the plug to be fed through).
The cable length within the unit from the connector on the A23 module (X27 or X28) to the top edge of the unit
on the rear panel (cabinet wall) is 1m to the left and 1.8 m to the right. This includes the spare length required for
removing the A23 module with its carrier board for service purposes.
WARNING
When the A23 module of a parallel unit is removed for servicing, the terminals of
the current transformers are open. The parallel unit must not be operated,
otherwise the current transformers of the parallel unit can be damaged by
currents from the snubber RC network.
Non-compliance may result in the destruction of the current transformer of a
parallel unit.
Parameterization:
Parameter P076 (configuration of the power section)
P076 = 1x...... 1 parallel unit is connected in parallel with the basic unit
P076 = 2x...... 2 parallel units are connected in parallel with the basic unit
NOTE
With the parameterization P076=0x, a connected parallel unit still receives firing pulses and carries current, it is
only the monitoring for current asymmetry (over-current or under-current in the parallel power section as
compared to the current in the basic unit, -F034) that is not active.
The results of the thyristor test (selected via P353) are only conditionally applicable when units are connected
in parallel.
Start-up:
The start-up procedure is exactly the same as in the case of a single basic unit. The final cabling (parallel
connection of the power sections and coupling via the 50-core ribbon cable) must however already exist
because the parallel units also carry current during circuit identification.
Note: In the case of 1 or 2 parallel units connected in parallel, the value of parameter P144 (DC link
capacitance) only represents a half or 1/3 of the actual DC link capacitance because parameter
P075 for the basic unit contains the rated current for a single power section.
LED display on the A23 power interface module (C98043-A1695) of a parallel unit:
Green LED (H11) lit: The power supply on this parallel unit is operating.
Yellow LED (H12) lit: On this parallel unit, the highest temperature of any power section connected in
parallel has been measured (this does not necessarily mean over-temperature). If the
yellow H12 LED is not lit on any of the parallel units, the highest temperature is
currently measured at the power section of the basic unit.
Red LED (H13) lit: A fuse has fused on this parallel unit.
3-50
1AC 50-60Hz, 230V
Connection
Figure 3.37
Parallel unit Basic unit
24V power K1
Filter supply unit Filter
(optional) Connection for (optional)
parallel unit
X9-1 X9-2 X9-3 X9-4 X9-5
K1-2
PE X1: U1 V1 W1 X4: 1U2 1V2 1W2 PE X1: U1 V1 W1 X4: 1U2 1V2 1W2
L1 L2 L3 1T1 1T2 1T3 L1 L2 L3 1T1 1T2 1T3
Load Load
X27 X28 X27
12 12
12 12
A23
C98043-A1685
ϑ ϑ ϑ ϑ
A23
C98043-A1695
Thermistor Thermistor
Single-line diagram with suggested circuit for parallel connection without autotransformer, size K
X239
X19-2 X19-1 X19-1 X19-2
X1: C/L+ X1: D/L- X1: C/L+ X1: D/L-
3.7.1 Single-line diagrams with suggested circuit arrangements for parallel connection
Siemens AG 6SE7087-6AK85-1AA0
3AC 50-60Hz, 400V
3AC 50-60Hz, 500V
3AC 50-60Hz, 690V
12.95
Figure 3.38
Parallel unit Basic unit
A10-X101 24V power K1 A10-X101
Filter supply unit Filter
(optional) Connection for (optional)
parallel unit
X9-1 X9-2 X9-3 X9-4 X9-5
ϑ ϑ
1U1 2U1 1U1 2U1
1U1 1U1
1V1 2V1 X9-1 X9-2 X9-3 X9-4 X9-5 1V1 2V1
1V1 1V1
1W1 1W1
1W1 2W1 1W1 2W1
K1-2
Siemens AG 6SE7087-6AK85-1AA0
PE X1: U1 V1 W1 X4: 1U2 1V2 1W2 PE X1: U1 V1 W1 X4: 1U2 1V2 1W2
L1 L2 L3 1T1 1T2 1T3 L1 L2 L3 1T1 1T2 1T3
12 12
12 12
A23
C98043-A1685
ϑ ϑ ϑ ϑ
A23
C98043-A1695
Thermistor Thermistor
Single-line diagram with suggested circuit for parallel connection with autotransformer, size K
Fan unit Fan unit
X239
X19-2 X19-1 X19-1 X19-2
X1: C/L+ X1: D/L- X1: C/L+ X1: D/L-
3-51
Connection
Connection 12.95
3.8 12-pulse mode (only possible with the optional RS485 interface)
3.8.1 General information on 12-pulse mode, application
12-pulse mode is implemented to reduce the harmonic loading on the mains supply.
Two 6SE70 units (rectifier/regenerating units) are connected in parallel on the output side and supplied on the
line side with two 3-phase AC supplies, galvanically isolated and with a phase offset of 30 degrees. One unit, the
"12-pulse master", controls the DC link voltage and provides the setpoint current for the other unit, the "12-pulse
slave".
Note: A unit described here as a "slave" is a completely normal rectifier/regenerating unit with a CUR electronic
module and is only transformed into a "12-pulse slave" by the appropriate parameterization. The term "12-pulse
slave" must not be confused with a "parallel unit" for the connection of power sections in parallel because the
latter does not contain a CUR electronic module and has a different order No. (see Section 3.7).
The two 3-phase galvanically isolated AC supplies with a phase offset of 30 degrees are usually generated using
a transformer with 2 different secondary systems (e.g. Y y6 d5, i.e. primary winding: star, secondary winding 1:
star, secondary winding 2: delta). A transformer of this type will be referred to below as a "12-pulse transformer".
To implement 12-pulse mode, the two rectifier/regenerating units must be coupled via a fast serial link. The
SST2 serial interface for the basic unit is used for this purpose which is however only available as an RS485
interface once the optional A2 submodule (C98043-A1690) has been plugged into the A10 CUR electronic
module (C98043-A1680). See Sections 9.6 and 3.8.7).
The transmission protocol used for SST2 is the "Peer-to-Peer" protocol.
The sub-currents of the 3-phase AC supplies are decoupled on the line side (line side with respect to the unit
terminals) through inductances (due to the secondary leakage inductance of the 12-pulse transformer,
commutating reactors and in the regenerative direction also due to the leakage inductance of the
autotransformers, if present).
Note: A 12-pulse transformer alone is not always sufficient for decoupling because the two secondary windings
of the transformer are magnetically coupled. When the "12-pulse master" and the "12-pulse slave" are directly
supplied from a "high-power" 12-pulse transformer (i.e. without the intermediate connection of commutating
reactors), the DC link currents (in non-pulsating operation) each comprise 30 degree current blocks because at
intervals of 30 degrees, a commutating process takes place from secondary winding 1 to secondary winding 2 or
vice-versa. Additional commutating reactors can only be dispensed with when a 12-pulse transformer is used
that has a sufficiently large secondary leakage inductance (or sufficiently large uk value between secondary
winding 1 and secondary winding 2).
Figure 3.40 Power section supply with autotransformers, reduced DC link voltage
c) Example of a configuration for 12-pulse mode and parallel connection of units of size K to obtain the
maximum output current
In the following example of a power section arrangement with autotransformers and a reactor arrangement
for a "high-power supply", 2 groups of size K units operate in 12-pulse mode to obtain the maximum possible
output current. The first group of units comprises a basic unit parameterized as a "12-pulse master" to which
2 parallel units (not containing a CUR electronic module, see Section 3.7) are connected in parallel. The
second group of units comprises a basic unit parameterized as a "12-pulse slave" to which 2 parallel units are
also connected in parallel.
X28
Reactor
Parallel unit
Rectification
Reactor
Regeneration
Autotransformer X27
X28
Parallel unit
Rectification
"12-pulse transformer" Reactor
Regeneration
Autotransformer DC link
Mains
12-pulse slave
Rectification
Reactor
Regeneration
Autotransformer X117 X27
X28
Parallel unit
Rectification
Reactor
Regeneration
Autotransformer X27
X28
Parallel unit
Rectification
Reactor
Regeneration
Autotransformer
Figure 3.41 Example of a configuration for 12-pulse mode and parallel connection of units of size K to obtain the maximum output
current
In this application, two 6SE70 units (rectifier/regenerating units) are coupled via the SST2 serial interface
(optional RS485 interface PTP1) using "Peer-to-Peer" protocol. One unit is parameterized as a 12-pulse master
and one is parameterized as a 12-pulse slave.
Selection of the basic or reserve setting (index i001 or i002) of the appropriate "Source selection parameter“
(P554, P555, ...) is described in Section 4.1.2.
Function: Controls the DC link voltage and provides Function: In current control mode, receives the
the setpoint current for the 12-pulse slave unit via the setpoint current and control commands via the SST2
SST2 interface and control commands (and receives interface from the 12-pulse master (and sends
control commands). control commands).
P051= 3 (Access level: Expert mode) P051= 3 (Access level: Expert mode)
SST2 interface definition: SST2 interface definition:
P688= 1 (protocol selection "Peer-to-Peer") P688= 1 (protocol selection "Peer-to-Peer")
P684.i003= 13 (baudrate 187500 Bd) P684.i003= 13 (baudrate 187500 Bd)
(factory setting) (factory setting)
P686.i003= 2 (2 process data words) P686.i003= 2 (2 process data words)
(factory setting) (factory setting)
P687.i003= 1 ms (telegram failure time) P687.i003= 1 ms (telegram failure time)
(factory setting) (see Section 3.8.6) (factory setting) (see Section 3.8.6)
SST2 send channel: SST2 send channel:
P681.i001= 599 (1st process data item is P681.i001= 599 (1st process data item is
control/status word for 12-pulse mode) control/status word for 12-pulse mode)
(factory setting) (factory setting)
P681.i002= 34 (2nd process data item is the setpoint
current)
(factory setting)
Use of SST2 receive data: Use of SST2 receive data:
P573.i001 (or i002) = 6001 (1st receive data is P554.i001 (or i002) = 6001 (ON/OFF1)
source for "No external fault 3")
P555.i001 (or i002) = 6001 (not OFF2)
(but should only be parameterized when the 12-
(with the "fault" state for the 12-pulse master or when
pulse master is required to go into the "fault" state in
"no 12-pulse mode" is selected on the 12-pulse
the event of a 12-pulse slave fault - see Section
master (see P583.i001 or i002), OFF2 is signaled)
3.8.6)
P561.i001 (or i002) = 6001 (Run enable)
(the 12-pulse slave only receives the run enable
when the 12-pulse master is in the "run" state)
P566.i001 (or i002) = 6001 (RESET)
(Source 2 for reset... this facilitates an external reset
from the master)
P572.i001 (or i002) = 6001 (REGEN. ENABLE)
(to facilitate, e.g. Ud reduction)
P486.i001 (or i002) = 6002 (2nd receive data item is
the setpoint current)
Definition of the unit as a 12-pulse unit: Definition of the unit as a 12-pulse unit:
P583.i001 (or i002) = 1 (12-pulse mode is selected) P583.i001 (or i002) = 1 (12-pulse mode is selected)
Definition of the unit as a master or slave: Definition of the unit as a master or slave:
P587.i001 (or i002) = 0 (master) P587.i001 (or i002) = 1 (slave)
(factory setting)
Special functions: Special functions:
P354 = 0 (Earth short-circuit test deactivated when P354 = 0 (Earth short-circuit test deactivated when
the unit is supplied by a non-earthed supply - e.g. the unit is supplied by a non-earthed supply - e.g.
from the delta winding of the 12-pulse transformer) from the delta winding of the 12-pulse transformer)
Table 12 Parameterization for 12-pulse mode
3.8.4 Control/status word for 12-pulse mode (r599) and control word 2, bit 23
The following table shows how the bits of the control/status word for 12-pulse mode (r599) are formed from the
bits of control words 1 and 2 (r550, r551), the bits of status word 1 (r552), the bits of the first SST2 receive data
(r599 sent from the Peer-to-Peer partner) and the internal unit status with Boolean arithmetic or how these bits
are connected together (negation is represented with a slash) :
If only those parameter values that are dependent on P077 are required to be changed and all other
parameters should remain unchanged, the following procedure is necessary:
Set P051= 3 (expert mode)
Set P052= 2 (select "Initialize" function (set MLFB))
Note P070 and set P070= 0
Set P077= 5 or 6 (select the required P077-dependent parameter setting)
Set P052= 0 and press the <P> key (read in the parameter values dependent on P077)
Move the F060 error message into the "background" by pressing <P>+<H>
Set P052= 2 (select "Initialize" function (set MLFB) again)
P070= noted value (restore MLFB)
P052= 0 and press the <P> key (MLFB is read in and the dependent parameters P071, P075 and P076
are set)
Move the F060 error message into the "foreground" again by pressing <P>+<T>, and reset by pressing
the <P> key
Circuit identification:
Circuit identification should be carried out successively on the 12-pulse master and on the 12-pulse slave.
P052= 21 must be set on each unit for this purpose, and the switch-on command for the 12-pulse slave
comes from the 12-pulse master (the control word wiring ensures that the partner unit, in each case, does not
carry current or is held in the operating state r000= "--".
Circuit identification procedure for 12-pulse master:
Set P052= 21 on the 12-pulse master unit, switch on circuit identification is carried out on the 12-pulse
master
Circuit identification procedure for 12-pulse slave:
Set P052= 21 on the 12-pulse slave unit, switch on the 12-pulse master unit circuit identification is
carried out on the 12-pulse slave
Note: If circuit identification is carried out with the basic settings selected (operation as a 12-pulse slave,
all control is from the 12-pulse master), the switch-on command must come from the 12-pulse master and
the power terminals of the 12-pulse master unit must be connected to the supply voltage.
Note: When the reserve setting is selected on the 12-pulse slave unit (with appropriate parameterization of
index i002 of the "Source selection parameters" P554, P555, ...) it is also possible to issue the switch-on
command for circuit identification on the slave unit on-site via the PMU or OP1.
If both rectifier/regenerating units are rated such that each separate unit is capable of carrying the full load
current, the following possibilities are available with respect to redundant operation:
Uninterrupted changeover of the 12-pulse master unit to stand-alone 6-pulse mode in the event of
failure of the 12-pulse slave unit during 12-pulse mode:
If the 12-pulse master is required to continue to run in "normal" stand-alone 6-pulse mode in the event of
failure of the 12-pulse slave unit without interruption, "External fault 3" must not be "wired" to the Peer-to-Peer
interface, but instead the parameterization P573.i001 (or i002) = 1 is required on the 12-pulse master. If the
master unit is also required to continue to run without an interruption in the event of failure of the Peer-to-Peer
interface cable, the Peer-to-Peer telegram failure monitoring time also has to be switched off via P687.i003=
0 on the master.
Changeover of the 12-pulse slave unit to stand-alone 6-pulse mode in the event of failure of the 12-
pulse master unit:
In the event of failure of the master unit during 12-pulse mode, it is possible for the 12-pulse slave unit to
change over to stand-alone 6-pulse mode almost without interruption, because all external control commands
that are wired to the terminals of the master unit (e.g. ON command) are also carried to the terminals of the
12-pulse slave unit. Externally implemented logic must ensure that in the event of failure of the master unit,
the 12-pulse slave is switched from the basic to the reserve setting. The 12-pulse slave must be
parameterized appropriately in the reserve setting to facilitate stand-alone 6-pulse mode with external control.
The Peer-to-Peer telegram failure monitoring time also has to be switched off via P687.i003= 0 in this case.
Note:
With the parameterization P687.i003 = 0 AND P681.i001 = 599, in the event of telegram failure, bits 3 and 6
of the first SST2 Peer-to-Peer receive data (i.e. the control/status word for 12-pulse mode sent from the
partner unit) are set to 0.
The RS485 interface cable required for the serial Peer-to-Peer link on SST2 is in the form of a four-wire
connection.
A screened 4-core cable must be connected at the screw terminals of the 5-pole plug of terminal block -X117 on
submodule A2 (C98043-A1690). Submodule A2 is fitted to the CUR A10 electronics module (see Section 9.6).
The 4-core cable is not included in the scope of delivery.
X117 X117
Figure 3.42 Connecting cable for "Peer-to-Peer" communication on SST2 (between the terminals of the A2 submodule (C98043-A1690))
4 Start-Up
WARNING
Despite disconnecting the power terminals from the supply, voltage may still be
present on terminal X19 due to the external fan supply.
NOTE
Section 4.2 First start-up:
First start-up of the rectifier/regenerating unit
4.1.2 General explanation of the terminology and functions of the rectifier/regenerating unit
Abbreviations:
Abbreviations used: Refer to Section 15 "Information, notes "
Mode and automatic control variants of the rectifier/regenerating unit:
"Function block diagrams: Open and closed-loop control": see Section 4.4
Application: Power supply of the variable-voltage DC link of SIMOVERT converters of the
6SEE70 series
Mode variants:
a) The line voltage in the regenerative branch is stepped up by an (auto) transformer to prevent
having to reduce the DC link voltage in regenerating mode
b) Permanent reduction of the DC link voltage by phase angle control in rectifier mode in order
to always be able to feed power back into the system
P318 Reduced DC link voltage setpoint (e.g. = 80 %)
P571 = 0001 Permanent selection of reduced voltage
c) Reduction of the link voltage for regenerative mode only by means of open-loop control to be
able to exploit the line voltage fully in rectifier mode and not have to use an autotransformer
for feeding power back into the system. This type of power feedback is not intended for
dynamic operation, but only for setpoint-controlled operation in conjunction with external
open-loop control.
"Process data":
"Process data" are commands and setpoints from "outside" fed into the rectifier/regenerating
unit, as well as signals and actual values which are output from the rectifier/regenerating unit
Process data
Sources Destinations
- Binary inputs BE - Binary outputs BA
(terminals) (terminals)
- Parameterizing unit (PMU) Commands Messages - Parameterizing unit (PMU)
- Operator control panel (OP) "Control Word" "status word" - Operator control panel (OP)
- Serial interfaces - Serial interfaces
(SST1, SST2, SCB, CB, TB) e.g.: "ON command" Setpoint e.g.: "fault (SST1, SST2, SCB, CB, TB)
chanal
Op./cl-loop
control - Analog outputs AA
(terminals)
- Serial interfaces - Parameterizing unit (PMU)
Setpoints Actual values
(SST1, SST2, SCB, CB, TB) - Operator control panel (OP)
- Serial interfaces
Only: Id setpoint in e.g. output current
(SST1, SST2, SCB, CB, TB)
12-pulse operation
Rectifier/regenerating unit
"Indexed" parameters:
Several parameter values are assigned to one parameter number, which can be accessed via
the separate indices (in brief: i001, i002, etc.).
The meaning of the indices of the respective parameter (parameter number) is explained in the
parameter list in Chapter 5.
Index1
Example:
P683 i001 = 0 Bus address for serial interface SST1 (CUR)
Index2
i002 = 2 Bus address for serial interface on the SCB module
"Data sets":
Data sets for basic/reserve setting (B/R) can be selected via control word 2/bit 30
Associated source selection parameter: P590
Affected parameters: P486, P554 to P557, P561, P565 to P569, P571 to P575,
P578, P579, P583 and P586 to P589
e.g. for changing over between manual and automatic operation
4 changeover reserve data sets (RDS) 1, 2, 3 or 4, selectable via the bit combination
in control word 2/bits 18 and 19.
Associated source selection parameters: P578, P579
Affected parameters: P140 to P144, P160, P161, P310 to P320, P329, P408,
P517, P518, P773 to P777
Used, e.g. for alternating operation of different inverter types on one
rectifier/regenerating unit
The rectifier/regenerating unit is supplied with the "factory setting" (refer to Section 5 "Parameter list",
column 4) and access stage 2 (standard mode). That means:
- The settings of the rectifier/regenerating unit data correspond to the unit type according to the MLFB
(i.e. converter already initialized).
When supplied, the converter is controlled and parameterized by the parameterizing unit (PMU) located on the
front side of the converter.
Displays:
Statuses
faults, alarms,
parameter numbers,
index numbers,
parameter values
Raise/lower
Switch-on to select:
Switch-off Parameters
Indices
Fault acknowledgement and P Parameter values
changeover between:
Parameter number
Parameter index
Parameter value
A detailed description of the displays as well as the parameterizing and operator control possibilities of the
rectifier/regenerating unit via the PMU, is provided in Section 6 "operator control".
NOTE
It is possible to jump into the appropriate sequence step (in the following flow diagrams) if incorrect entries
have been made, taking into account the access stage (P051) and a function selection (P052) which may be
required. It is recommended that the following parameters and function steps after the jump-in position are re-
checked and executed due to the background calculations !
NOTE
To avoid oscillating of the link voltage in regenerative mode, it is advisable to set parameter P302 of the
SIMOVERT Master Drives FC, VC, SC (time constant for filtering the link voltage) to the value 3.
no
If the unit is to be switched on and off via the optional user-friendly
P554 = 2001 operator panel OP1:
P554=2001 Source for control command "ON/OFF1"
P555=2001 Source for control command "OFF2"
P555 = 2001
Drive setting
P052 = 5
Supply voltage [V]
P071 = Value of the rated voltage at the input bridge
Regen. no
Mode variants:
transformer?
a) The system voltage in the regenerative branch is stepped up by an
yes (auto) transformer in order not to have to reduce the link voltage in
regenerative mode
Permanent
reduction b) Permanent reduction of the link voltage by phase angle control in
rectifier mode to always be able to feed power back into the system
yes In accordance with the manufacturer setting P318=80%, it is reduced
to a setpoint of 80% of 1.35 x system voltage at the rectifier bridge 1)
P571 = 0001 P571 = 0001 permanent selection of reduced voltage
Idle time yes Forming the DC link (if necessary, see Section 4.3.9.6)
of converter - The rectifier/regenerating unit must be in status o009
>1year
less (give SWITCH ON command)
no - Set P408 (forming time: 1.0 to 600.0 minute)
- Select function (P052 = 20)
P408 =
- Press P key on the PMU
- Press the I key on the PMU
P052 = 20 - The DC link is formed.
- When forming is completed, the operating status
P key
display appears.
Switch-on
Forming
r000 ≤ o009
(see r006)
Wait to
Ud<50V Circuit identification
(see Section 4.3.9.7)
- The rectifier/regenerating unit must be in operating state
o009 or less (give SWITCH OFF command!).
- Select circuit identification (P052 = 21).
P052 = 21 r949.i009 = ? - Press the P key on the PMU
P key - Switch on: Press the I key on the PMU
- Circuit identification takes place (takes about 10 s)
Switch-on r000 ≤ o009 - Following circuit identification, the operating display is
activated.
Identification Acknowledge - If an error occurs during circuit identification, the
identification process must be repeated (error value r949
assigned to error memory r947 can provide more
information on the cause of error (if the error in index i009
yes Eliminate
Fault message has been reset) see Sections 5.16 and 7.1)
cause of fault
no
P053 =
Parameterization enable
e.g. with P053=6, the parameters from the parameterization unit (PMU)
yes
and from serial interface 1 of the basic unit (SST1- and therefore also from
Commands
via OP1? the optional user-friendly operator panel OP1) can be modified.
no Operator control
P554 = 2001
If the unit is to be switched on and off via the optional user-friendly operator
panel OP1:
P555 = 2001 P554=2001 Source for control command "ON/OFF1"
P555=2001 Source for control command "OFF2"
P052 = 5
Drive setting
P071 =
Supply voltage [V]
P076 = Value of the rated voltage at the rectifier bridge
Current limits:
P160 = Max. supply current (in % P075 rated current of
rectifier/regenerating unit (factory setting: +150% only briefly
available)
P161 = Max. regenerative current (in % of P075 rated current of
rectifier/regenerating unit (factory setting: -150% only briefly
available)
Mode variants:
Regen. no
a) The system voltage in the regenerative branch is
transformer?
stepped up by an (auto) transformer in order not to
yes
have to reduce the link voltage in regenerative mode
Permanent no b) Permanent reduction of the link voltage by phase angle
reduction control in rectifier mode to always be able to feed power
back into the system
yes
P318 Reduced DC link voltage setpoint (e.g. = 80 %)
P318 = P318 = P571 = 0001 Permanent selection of reduced voltage
c) Reduction of the DC link voltage in regenerative mode
only by external open-loop control in order to be able to
P571 = 0001 P319 = exploit the line voltage fully in rectifier mode and not
have to use an autotransformer for feeding power back
into the system
P571 = 1004
P318 reduced DC link voltage setpoint (e.g. = 80 %)
P571 = 1004 Reduction selected via terminal X101-12
P613 = 1001 P613 = 1001 Output "Link voltage reduced" message to
signaling relay X104-17/18 (ready for
regenerating)
P319 Hysteresis for the "DC link voltage reduced"
Idle time
message (ready for regenerating)
yes
of converter
>1year
no
P408 =
Forming the DC link (if necessary; see Section 4.3.9.6)
- The rectifier/regenerating unit must be in status o009 or
P052 = 20 less (give SWITCH OFF command!).
- Set P408 (forming time: 1.0 to 600.0 minutes).
P key
- Select function (P052 = 20)
Switch-on - Press the P key on the PMU
- Switch on: Press the I key on the PMU
- Forming of the DC link takes place
Forming - Following the forming process, the status display is
activated.
r000 ≤ o009
Wait to
(see r006)
Ud<50V
Circuit identification
(see Section 4.3.9.7)
P052 = 21 r949.i009 = ? - The rectifier/regenerating unit must be in operating state o009 or
P key less (give SWITCH OFF command!).
- Select circuit identification (P052 = 21).
Switch-on r000 ≤ o009 - Press the P key on the PMU
- Switch on: Press the I key on the PMU
Identification Acknowledge - Circuit identification takes place (takes about 10 s)
- Following circuit identification, the operating display is activated.
- If an error occurs during circuit identification, the identification
process must be repeated (error value r949 assigned to error
yes Eliminate
Fault message memory r947 can provide more information on the cause of error
cause of fault (if the error in index i009 has been reset) see Sections 5.16 and
7.1)
no
4.2.5 Simple application examples for connecting process data with connection assignment
Factory setting:
Switch-on/off via the PMU, messages and actual values via the terminal strip.
Terminal strip only operational if binary input 5 (BE5) is energized (high signal level corresponds to "reserve").
CUR PMU
-X101/6 P24
-X101/9 BE1 ON/OFF1 P554.2 = 1001
-X101/10 BE2 OFF2(pulse inhibit) P555.2 = 1002
-X101/11 BE3 Acknowledge P565.2 = 1003
-X101/12 BE4
-X101/13 BE5 Basic/reserve P590 = 1005
(activates above commands)
-X102/15 AAM
-X102/14 AA Actual Ud value P655.1 = 37
Manual/automatic operation:
Automatic operation (BE5 high signal level): Command input from the automation unit via serial interface
(SST1), the monitoring of external faults via a terminal strip also
possible.
Manual operation (BE5 low signal level): Command input via the terminal strip.
-X101/6 P24
-X101/9 BE1 ON/OFF1 P554.1 = 1001
-X101/10 BE2
-X101/11 BE3 Acknowledge P565.1 = 1003
-X101/12 BE4 Fault external 1 P575.1 = 1004 P575.2 = 1004 (always activ)
-X101/13 BE5 Basic/reserve P590 = 1005
-X102/15 AAM
-X102/14 AA Actual Ud value P655 = 37
Process data are commands and setpoints which are entered into the rectifier/regenerating unit from "outside"
as well as signals and actual values which the rectifier/regenerating unit outputs.
The two control words 1 (bits 0 to 15) and 2 (bits 16 to 31) output commands and external signals (messages) to
the rectifier/regenerating unit.
Their status can be read-out via parameter r550 or r967 (control 1) and r551 (control word 2).
An overview is provided in Section 4.3.1.1.2 "Overview of the control word".
The significance of the possible commands and signals, entered externally, is described in Section 4.3.1.1.7
"Significance of the control word commands".
Every control word bit is assigned a selection parameter, which defines from which source(s) this bit can be
changed (refer to Section 4.3.1.1.2, right-hand column).
The selection parameters for the sources are, with the exception of P590 (source selection for control word bit
30 "basic/reserve setting") and P591 (source selection for control word bit 31 "Main contactor checkback signal")
are indexed 2x as follows:
Index i001 Basic setting
i002 Reserve setting
An overview of possible sources, which are assigned fixed values (0-6005, non-consecutively), are provided in
Section 4.3.1.1.3 to 4.3.1.1.6 "Selecting the source for the control word".
In this overview, values 0 and 1 are an exception; sources are not selected with these values, but the bits are set
permanently to 0 (LOW) or 1 (HIGH) (also refer to select parameters P554 to P591 in Section 5 "parameter list").
NOTE
The control word commands "OFF2" (bit1), "OFF3" (bit2) and "Acknowledge" (bit7) are always simultaneously
effective from 3 sources (can be parameterized) !
"Acknowledge" (bit7) is also always effective from the PMU !
NOTE
If the "On" command (bit 0) is connected to a serial interface (SST1, CB/TB, SCB-SST), then the following
must be observed for safety-related reasons:
Additionally, an "OFF2" or "OFF3" command must be parameterized at the terminal strip/PMU, as otherwise
the converter cannot be shutdown with a defined command, when communications fail!
WARNING
When making any modifications to control or other wiring, make absolutely sure that no
dangerous situations can arise!
Example
If a terminal at logic H potential is programmed as the source for the ON/OFF1 command,
the rectifier/regenerating unit will enter the "Run" ("R") state when the P key is pressed
(activates the value set!).
Conversely, a rectifier/regenerating unit that is in the "R" state will enter the "Ready" ("B")
state if the terminal is at logic L potential.
Typical application:
0: OFF2
1: ON
Changeover using
control word bit 30
P590
Value 0000 0001 1001 1002 1003 1004 1005 1010 2001 2004 3001 to 4504 6001 to 6005
CUR, BE1
CUR, BE2
CUR, BE3
CUR, BE4
CUR, BE5
Constant-
Constant-
word 1 to
value = 1
value = 0
(Peer-to-
-X101:10
-X101:11
-X101:12
-X101:13
(Word1)
(Word4)
-X101:9
word 5
Source Options
SST1
SST1
SST1
Peer)
PMU
ON/OFF1: Basic set.: via PMU (keys I/0) Reserve set.: via bin. input 1 of CUR
Op. cond/OFF2: Basic set.: Constant value= 1= always op. cond. Reserve set.: Constant value = 1 = always op. cond.
NOTE
For OFF2 and OFF3, 3 selection parameters can be assigned differently in the same index!
Op. enable/inhibit: Basic set.: Constant value = 1 = always op. enable. Reserve set.: Constant value = 1 = via serial
interface SST1 of the CUR
4.3.1.1.2 Overview of the control word (control word 1 and control word 2)
15 13 11 9
14 12 10 8
7 5 3 1
6 4 2 0
PMU Display
"Control word 1" (visualization parameter r550 or r967)
Bit High Low Comments Source
selection
0 ON OFF1 (stop) (Priority OFF 2/1) P554
1 Operating condition OFF2 (electrical) 3 sources simultaneously effective; P555
(Priority OFF 2/1) P556
P557
2 always HIGH
3 Operating condition Inhibit operation Firing pulse enable P561
4 always High
5 always High
6 always High
7 Acknowledge Simultaneously effective from 3 P565
sources and PMU; P566
Positive edge evaluation P567
8 Inching 1 ON Inching 1 OFF Same effect as ON/OFF1 P568 1)
9 Inching 2 ON Inching 2 OFF Same effect as ON/OFF1 P569 1)
10 Control from the PLC No control Only effective via
CB,TB,SST1,SST/SCB
11 Ud reduction requested Ud reduction inactive P571 1)
12 Regenerating enabled Regenerating inhibited P572 1)
13 No fault, external 3 Fault, external 3 P573 1)
14 Motoring Generating Specification of the direction of supply P574 1)
15 No fault, external 1 Fault, external 1 P575
31 29 27 25
30 28 26 24
23 21 19 17
22 20 18 16
PMU Display
"Control word 2" (visualization parameter r551)
Bit High Low Comments Source
selection
16
17
18 RDS (reserve data set) bit 0 (LSB) Logic operation with bit 19 P578 1)
19 RDS (reserve data set) bit 1 (MSB) Logic operation with bit 18 P579 1)
20
21
22
23 12-pulse mode selected No 12-pulse mode P583 1)
24
25
26 No fault, external 2 Fault, external 2 P586
27 Slave S/F unit Master S/F unit Changeover Ud/Id control P587
28 No alarm, external 1 Alarm, external 1 P588
29 No alarm, external 2 Alarm, external 2 P589
30 Reserve setting for Basic setting for setpoints P590
setpoints and control word and control word
31 HS checkback signal No HS checkback signal
Can only connected at the converter P591
term. strip or SCB
1) This bit has a different meaning for the rectifier/regenerating unit as for the converter
Bit 0 1 2 3 4 5 6 7
Selection P. basic setting 554.1 555 to 557.1 561.1 565 to 567.1
Value Source
OPTIONS
3001 CB/TB (Word1) x x x x
3004 CB/TB (Word4)
4101 SCI 1 and 2, Slave 1,BE1 x x x x
4102 BE2 x x x x
... Consecutively to x x x x
4110 BE10 x x x x
4111 only SCI 2, Slave 1,BE11 x x x x
4112 BE12 x x x x
... Consecutively to x x x x
4116 BE16 x x x x
4201 SCI 1 and 2, Slave 2,BE1 x x x x
4202 BE2 x x x x
... Consecutively to x x x x
4210 BE10 x x x x
4211 only SCI 2, Slave 2,BE11 x x x x
4212 BE12 x x x x
... Consecutively to x x x x
4216 BE16 x x x x
4501 SCB-SST (USS /Peer-t-Peer) Word1 x x x x
4504 SCB-SST (USS /Peer-t-Peer) Word4
6001 SST2 (PTP1, A2-X117:1..5) Word 1 x x x x
... Consecutively to x x x x
6005 SST2 (PTP1, A2-X117:1..5) Word 5 x x x x
x: Value can be assigned for the selection parameters (BE can only be assigned once in the same index of all
selection parameters!)
1) Value 1010 cannot be set, but reset is always possible from PMU.
2) xG for P555, value 1010 is only possible for P555 to P557 when P554=1010.
Bit 8 9 10 11 12 13 14 15
Selection P. basic setting 568.1 569.1 571.1 572.1 573.1 574.1 575.1
Selection P. reserve setting 568.2 569.2 571.2 572.2 573.2 574.2 575.2
Value Source
OPTIONS
3001 CB/TB (Word1) x x x x x x x
3004 CB/TB (Word4)
4101 SCI 1 and 2, Slave 1,BE1 x x x x x x x
4102 BE2 x x x x x x x
... Consecutively to x x x x x x x
4110 BE10 x x x x x x x
4111 only SCI 2, Slave 1,BE11 x x x x x x x
4112 BE12 x x x x x x x
... Consecutively to x x x x x x x
4116 BE16 x x x x x x x
4201 SCI 1 and 2, Slave 2,BE1 x x x x x x x
4202 BE2 x x x x x x x
... Consecutively to x x x x x x x
4210 BE10 x x x x x x x
4211 only SCI 2, Slave 2,BE11 x x x x x x x
4212 BE12 x x x x x x x
... Consecutively to x x x x x x x
4216 BE16 x x x x x x x
4501 SCB-SST (USS /Peer-t-Peer) Word1 x x x x x x x
4504 SCB-SST (USS /Peer-t-Peer) Word4
6001 SST2 (PTP1, A2-X117:1..5) Word 1 x x x x x x x
... Consecutively to x x x x x x x
6005 SST2 (PTP1, A2-X117:1..5) Word 5 x x x x x x x
Bit 16 17 18 19 20 21 22 23
Selection P. basic setting 578.1 579.1 583.1
Value Source
OPTIONS
3001 CB/TB (Word1)
3004 CB/TB (Word4) x x x
4101 SCI 1 and 2, Slave 1, BE1 x x x
4102 BE2 x x x
... Consecutively to x x x
4110 BE10 x x x
4111 only SCI 2, Slave 1, BE11 x x x
4112 BE12 x x x
... Consecutively to x x x
4116 BE16 x x x
4201 SCI 1 and 2, Slave 2, BE1 x x x
4202 BE2 x x x
... Consecutively to x x x
4210 BE10 x x x
4211 only SCI 2, Slave 2, BE11 x x x
4212 BE12 x x x
... Consecutively to x x x
4216 BE16 x x x
4501 SCB-SST (USS /Peer-t-Peer) Word1
4504 SCB-SST (USS /Peer-t-Peer) Word4 x x x
6001 SST2 (PTP1, A2-X117:1..5) Word 1 x x x
... Consecutively to x x x
6005 SST2 (PTP1, A2-X117:1..5) Word 5 x x x
Bit 24 25 26 27 28 29 30 31
Selection P. basic setting 586.1 587.1 588.1 589.1 590 591
Value Source
OPTIONS
3001 CB/TB, Word1
3004 CB/TB, Word4 x x x x x
4101 SCI 1 and 2, Slave 1,BE1 x x x x x x
4102 BE2 x x x x x x
... Consecutively to x x x x x x
4110 BE10 x x x x x x
4111 only SCI 2, Slave 1,BE11 x x x x x x
4112 BE12 x x x x x x
... Consecutively to x x x x x x
4116 BE16 x x x x x x
4201 SCI 1 and 2,Slave 2,BE1 x x x x x x
4202 BE2 x x x x x x
... Consecutively to x x x x x x
4210 BE10 x x x x x x
4211 only SCI 2, Slave 2,BE11 x x x x x x
4212 BE12 x x x x x x
... Consecutively to x x x x x x
4216 BE16 x x x x x x
4501 SCB-SST (USS /Peer-t-Peer) Word1
4504 SCB-SST (USS /Peer-t-Peer) Word4 x x x x x
6001 SST2 (PTP1, A2-X117:1..5) Word 1 x x x x x
... Consecutively to x x x x x
6005 SST2 (PTP1, A2-X117:1..5) Word 5 x x x x x
The status of the rectifier/regenerating unit can be read in the operating display r000: e.g. READY-TO-SWITCH-
ON r000=009
The function sequences are described in the sequence in which they are realized.
Bit 0: ON command ( "ON")
The command is executed with a positive edge change from L to H (L H) only in the READY-TO-SWITCH-ON
(009).
After the command has been accepted:
Changeover to the status WAIT FOR LINE VOLTAGE (010)
The main contactor is closed.
Changeover to the status READY STATUS(011)
Changeover to the status TEST PHASE (012)
Takes place only if thyristor or ground-fault test (P353,P354) selected.
Changeover to the RUN status(014)
Pre-charging is carried out, followed by normal operation.
NOTE
The OFF2 command is simultaneously effective from three sources (P555, P556 and P557)!!
NOTE
Priority of the OFF commands OFF2 > OFF1
Bit 4 to 6: reserved
NOTE
The acknowledge command is simultaneously effective from three sources (P565, P566 and P567) and always
from the PMU!
Bit 10: Control from the PLC command (H "Control from the PLC")
The command is executed with an H signal
Process data PZD (control word, setpoints) originating from a PLC which were sent via the SST1 interface of
CU1, the CB/TB interface (option) and the SST/SCB interface (option), are only evaluated if the command was
accepted.
If several interfaces are operational, only the process data of the interfaces are evaluated, which transmit the
H signal.
For an L signal, the last values are retained in the appropriate dual port RAM of the interface.
An H signal appears in the visualization parameter r550 "control word 1", if one of the interfaces transmits an H
signal!
P318
Setpo int = 135
. USupply,rectifier
* * 100.00%
At the same time, the intermediate DC link voltage threshold for enabling the regenerating bridge is reduced
U Supply, regenerating
to the following value if an autotransformer is not present (i.e. when < 117
. ):
U Supply, rectifier
P318
135
. * U Supply, regenerating *
100.00%
This causes the signal "Regenerating ready" (status word 1, bit 10) to switch to low.
The DC link should now discharge.
When the DC link voltage drops below the following threshold value
P318 2%
135
. * U Supply, rectifier * + 135
. P071
100.00% 100% * *
the message "Ud reduced" (status word 1, bit 13) is issued, and a converter connected to the DC link can
regenerate. At the same time as the message "Ud reduced" is issued, for which the hysteresis of P319
applies, the regenerating bridge is enabled such that the DC link voltage threshold for the message
"Regenerating ready" is set to a higher value.
The appearance of a trailing edge of the Ud reduction command causes the output of the ramp-up/return
element (precharging time P329) to be set to the current value of DC link voltage so that the DC link voltage
setpoint can ramp up again from this value.
The L signal of the Ud reduction command causes the "Ud reduced" message (status word 1, bit 13) to be
held low (regardless of the DC link voltage level)
Bit 14: Power direction command (H " Motoring "; L " Generating ")
The command is used to specify the power direction.
With an H signal only the rectifier bridge can carry current, and with an L signal only the regenerating bridge.
NOTE
The values in the data sets must be meaningful. This is the case, for example, when current identification (see
Section 4.3.9.7) has been carried out for the currently selected reserve data set or when a valid data set has
been copied using copy parameters (see P055 in Section 5.3). Otherwise errors will be reported.
Bit 27: Master/slave changeover (H "Slave S/F unit"/L "Master S/F unit")
The command switches between slave and master mode.
Slave S/F unit: The closed-loop control operates with an external DC link current setpoint
Even when a thyristor test is selected (P353=1, 2 or 3) if Ud > 5% it does not wait in
state o012 and the thyristor test is not carried out.
Master S/F unit: The closed-loop control operates with an external DC link current setpoint
Bit 30: Selection, basic/reserve setting command (L "Basic setting / H "Reserve setting")
The command activates the BASIC SETTING with an L signal and the RESERVE SETTING with an H signal
After the command has been accepted:
The parameter settings of the basic or reserve setting for the control word itself, the setpoint channel, and the
closed-loop control are activated (see "Data sets" in Section 4.1.2 and "Selecting the data sets" in Section
4.4).
Bit 31: Main contactor checkback signal command (H "Main contactor checkback signal")
This command permits you to include an auxiliary contact of the main contactor in the unit control circuit (an H
signal implies that the main contactor has picked up).
After the command has been accepted:
An operating status > o010 is permitted
Status words 1 (bits 0 to 15) and 2 (bits 16 to 31) issue messages and commands from the rectifier/regenerating
unit to external destinations.
Their particular status can be read-out via parameters r552 or r968 (status word 1) and r553 (status word 2).
An overview is provided in Section 4.3.1.2.2 "Overview of the status word".
The significance of the possible messages and commands to the outside is described in Section 4.3.1.2.4
"Significance of the status word messages".
Each status word bit is assigned a selection parameter, which defines, to which destination this bit is sent (refer
to Section 4.3.1.2.2, right-hand column).
The selection parameters for the destinations are indexed twice as follows:
Index: i001 Selecting a terminal on the CU / PEU board (basic converter)
i002 Selecting a terminal on the SCI 1/2 board (option)
An overview of the possible destinations, which are assigned fixed values, is provided in Section 4.3.1.2.3
"Selecting the destinations for the status word".
NOTE
For the output of faults, alarms and switch-on inhibit of the status word (HIGH active) via the terminal strip,
then these are LOW active at the terminals (binary outputs) (i.e.: the relay drops out)!
This is also true for possible option boards!
Also refer to Section 4.3.3 "Binary outputs"
Example:
1: Prech. active
Meaning
0: n. ready
0: no fault
1: Ready
1: Fault
1: Run
Select
P600 P601 P602 P603 P... P... P631
parameter
Term on SCI 1/2 i002= i002= i002= i002= i002= i002= i002=
Value 0000 1001 1002 0000 4101 ... 4112 4201 ... 4205 ... 4212
-X104:17/18
-X104:19/20
SCI,Slave2
SCI,Slave1
SCI,Slave1
SCI,Slave2
SCI,Slave2
CUR, BA1
CUR, BA2
no dest.
no dest.
Dest.
BA12
BA12
BA1
BA1
BA5
Index 1 Index 2
Terminal on CUR Terminal on SCI 1/2
(Option)
4.3.1.2.2 Overview of the status word (status word 1 and status word 2)
15 13 11 9
14 12 10 8
7 5 3 1
6 4 2 0
PMU Display
"Status word 1" (visualization parameter r552 or r968)
Bit High Low Comments Dest.
selection
0 Ready-to-switch-on Not ready to switch on P600
1 Ready Not ready P601
2 Run Firing pulses inhibited P602
3 Fault No fault Inverted for terminal strips! P603
4 No OFF 2 OFF2 P604
5 always High
6 Switch-on inhibit No switch-on inhibit Inverted for terminal strips! P606
7 Alarm No alarm Inverted for terminal strips! P607
8 No setpt. act. val. deviation Setpt. act. value deviation Can be parameterized P608
9 PZD control requested always "High"
(for CB,TB,SST1,SST/SCB)
10 Regenerating ready Regenerating not ready P610 1)
11 Fault, undervoltage No undervoltage fault Inverted for terminal strips! P611
12 Main contactor energized Main contactor not Can only be connector for P612
energized terminals CUR or SCI!
13 Ud reduced Ud not reduced P613 1)
14 Motoring Generating P614 1)
15
31 29 27 25
30 28 26 24
23 21 19 17
22 20 18 16
PMU Display
"Status word 2" (visualization parameter r553)
Bit High Low Comments Dest.
selection
16
17
18 Current active Current limit not active Inverted for terminal strips! P618 1)
19 Fault, external 1 No fault, external 1 Inverted for terminal strips! P619
20 Fault, external 2 No fault, external 2 Inverted for terminal strips! P620
21 Alarm, external No alarm, external Inverted for terminal strips! P621
22 Alarm i2t power sections No alarm, i2t power section Inverted for terminal strips! P622
23 Fault, overtemp., p.s. No fault, overtemp. p.s. Inverted for terminal strips! P623
24 Alarm, overtemp., p.s. No alarm, overtemp., p.s. Inverted for terminal strips! P624
25
26
27
28
29
30
31 Pre-charging active Pre-charging not active P631
1) The meaning of this bit is different for the rectifier/regenerating unit than for the converter
4.3.1.2.3 Selecting the destinations for the status word (bits 0 - 31)
For the selection parameters P600 to P631, in which the destination of the appropriate bit can be specified, then
the indices are uniformly assigned as follows:
NOTE
When faults, alarms and switch-on inhibit of the status word are output (HIGH active) via the terminal strip,
then these are LOW active at the terminal strips (binary outputs) (i.e.: relay drops out)!
This is also valid for possible option boards!
Also refer to Section 4.3.3 "Binary outputs"
P318 2% + P319
135
. * U Supply, rectifier * + 135
. P071
100% 100% * *
The L signal is also output provided that in control word 1, bit 11=0 ("Ud reduction not requested").
4.3.1.3 Setpoints
The only possible setpoint selection that can be programmed on a rectifier/regenerating unit is the selection of
the Id setpoint for a rectifier/regenerating unit in slave mode (e.g. the slave rectifier/regenerating unit in 12-pulse
operation) using parameter
(See also Chapter 5 "Parameter list")
The control word command can be used for effecting the changeover:
"Basic and reserve settings"
See Section 4.4 "Function diagrams"
Value entry in Index1 i001 active when "basic setting" selected" (control word)
Index2 i002 active when "reserve setting" selected (control word)
OPTIONS
3002 CB/TB Word2
3003 Word3
3004 Word4 only if word 4 is not assigned for "control
word 2 with 3004 (Section 4.3.1.1)
... consecutively to
3016 Word16)
4101 SCB1 with SCI 1,Slave1, analog input AE1
4102 AE2
4103 AE3
4201 SCB1 with SCI 1,Slave2, analog input AE1
4202 AE2
4203 AE3
4501 SCB-SST (only Peer to Peer, Word1) only if word 1 is not assigned for "control
word 1 with 4501 (Section 4.3.1.1)
4502 USS /Peer to Peer, Word2
4503 USS /Peer to Peer, Word3
4504 USS /Peer to Peer, Word4 only if word 4 is not assigned for "control
word 2 with 4504 (Section 4.3.1.1)
4505 USS /Peer to Peer, Word5
4506 only USS, Word6
... consecutively to
4516 only USS, Word6
6002 SST2 (PTP1, A2-X117:1..5) Peer-to-Peer, Word2
6003 SST2 (PTP1, A2-X117:1..5) Peer-to-Peer, Word3
6004 SST2 (PTP1, A2-X117:1..5) Peer-to-Peer, Word4
6005 SST2 (PTP1, A2-X117:1..5) Peer-to-Peer, Word5
All available parameter numbers (0 to 999) can be entered into the actual value parameters, sorted according to
destinations (refer to the following).
The parameter value of the entered parameter number is output at the selected destination.
Note: - When specifying parameter numbers, which are indexed, the value of the first index (.i001) is always
output!
- When specifying "0", no output is made to the appropriate destination!
Destinations:
P655 "CUR-AA actual values"
Output via the CUR control terminal strip (Section 3.3)
Analog output 1 (-X102:14 / reference potential -X102:15)
(refer to Section 4.3.5 "analog output")
P680 "SST1 actual values"
Output via the basic converter interface SST1
Indices: i001 Word 01 of the telegram (PZD)
i016 Word 16 of the telegram (PZD)
(refer to Section 4.3.6.1 "basic converter interface SST1")
Destination, options:
P664 "SCI-AA actual values"
Output via the SCB1 interface with SCI1
(also refer to the Instruction Manual for the option boards)
Indexes i001 Destination: Analog output 1 from slave 1
i002 Destination: Analog output 2 from slave 1
i003 Destination: Analog output 3 from slave 1
i004 Destination: Analog output 1 from slave 2
i005 Destination: Analog output 2 from slave 2
i006 Destination: Analog output 3 from slave 2
P690 "SCB actual values"
Output via the SCB1 interface with peer-to-peer protocol or SCB2
(also refer to the Instruction Manual for the option boards)
Indexes: i001 Destination: Word 01 of the telegram (PZD)
i016 Destination: Word 16 of the telegram (PZD)
P694 "CB/TB actual values"
Output via the CB or TB interface
(also refer to the Instruction Manual for the option boards and Sections 4.3.6.2 "DPR")
Indices: i001 Destination: Word 01 of the telegram (PZD)
i016 Destination: Word 16 of the telegram (PZD)
NOTE
For telegram data transfer (P680,P690,P694), it is generally necessary/practical to assign "Word 01 of the
telegram (PZD)" with status word 1 (r968 or r552)!
5 binary inputs (24V) which can be parameterized at the control terminal strip (board CUR, -X101) to enter
commands, external faults/alarms as well as a checkback signal to the rectifier/ regenerating unit control word.
Connecting-up:
Refer to Section 3.3 "Control terminal strip"
Parameterization:
Refer to Section 4.3.1.1 "Control word"
Function of the binary inputs for factory setting with P077 = 0 (see Section 4.3.9.1):
2 binary outputs, which can be parameterized, for the output of signals and external commands of the
rectifier/regenerating unit status word.
Connecting-up:
Binary output 1 on the CUR control terminal strip (connector X104 / NO contact):
Refer to Section 3.3 "Control terminal strip "
Binary output 2 on the CUR control terminal strip (connector X104 / NO contact):
Refer to Section 3.3 "Control terminal strip"
Parameterization:
Refer to Section 4.3.1.2 "Status word "
Factory setting:
Binary output 1 No function (relay always de-energized)
X104 on the CUR
Binary output 2 Fault (status word bit 3)
X104 on the CUR
NOTE
When faults, alarms and switch-on inhibit of the status word (HIGH active) are output via the terminal strip,
these are LOW active at the terminal strip (binary outputs) (i.e. relay drops out)!
Also refer to Section 4.3.1.2 "Status word".
1 analog output, which can be parameterized, at the control terminal strip (board CUR, -X102 / Section 3.3) to
output actual values and other internal rectifier/regenerating unit quantities.
Analog output: - Voltage range: 10V
- Resolution: 39mV (8 bits + sign)
- Accuracy: 5%
- Smoothing: 20ms
- Output current: max. 5mA
- Short-circuit proof and non-floating
Connecting-up:
Refer to "Control terminal strip", Section 3.3
Parameterization:
Also observe "Function diagram, analog output CUR", Section 4.4!
Enter the parameter number (0 to 999) whose value is to output, in P655 "CUR-AA actual values".
The following is obtained for the calculation from the "Function diagram, analog output CUR":
Parameter value in [% ]
Uoff = × Gain in [V ] + Offset in [V ]
100 [% ]
The parameter value in [%] for the appropriate parameter number can be taken from the parameter list,
Chapter 5!
Configuring examples:
Required: Map the actual DC link voltage r037 between 400 and 600 V to 0.00V to
+10.00 V at the analog output
Uoff1 V − Uoff2 V × 100 % (0.00 V − 10.00 V) × 100 %
Gain factor [ V ] = =
PWE1 [%] − PWE2 [%] 74.05 % − 111.07 %
− 10,00 V × 100
= = 27.03 V
−37 %
Required: Map the output current r035 between -630 and +630 A to -10.00 V to
+10.00 A at the analog output
Uoff1 V − Uoff2 V × 100 % (−10.00 V − 10.00 V) × 100 %
Gain factor [V ] =
=
PWE1 [ %] − PWE2 [ % ] -150 % − 150 %
− 20.00 V × 100 %
= = 6.67 V
−300 %
The USS protocol (universal serial interface) is implemented at the basic converter interface SST1.
The following documentation is available depending on the particular application of the SST1 basic converter
interface:
NOTE
Communications can either be realized via the terminal strip of CUR -X100 (RS485 standard) or the interface
connector on PMU -X300 (9-pin SUB D connector / RS485)
Only one of the two possible connections (-X100 or -X300) may be used!
NOTE
The bus terminating resistors (total 150 ) must be switched-in at the last bus node (slave).
To realize this, jumpers of DIP-FIX switches S1 and S2 must be closed on board CUR!!
Parameterization:
Defining the interface: P683 to P687
Define the process data (control word, status word, setpoints, actual values) for the interface:
Refer to "Process data" Section 4.3.1
Enabling parameterization: P053 or P927
NOTE
The factory setting (refer to "Parameter list" Chapter 5) can be used if the SST1 basic converter interface is not
used!
4.3.6.1.2 Basic converter interface SST2 (A2-X117), see Section 9.6, Options
The dual-port RAM is the internal interface on the CUR (-X107) to connect possible option boards via the
backplane bus of the electronics box (LDA bus adapter required).
To connect possible option boards and parameterize the interface, also refer to the Section 3.5 "Recommended
circuits" as well as in the appropriate Instruction Manuals to the various option boards.
Additional information can be taken from Sections 4.3.1.1 to 4.3.1.4 "Control word, status word, setpoints, actual
values".
Function selection is activated via parameter P052 and permits various special functions during the start-up
phase.
Access stage 2 (P051 = 2) must be enabled and the rectifier/regenerating unit may only be in the "Run" (R)
status. Apart from this, P053 must be set for parameter enable (e.g. P053=6).
The "Generate factory setting", "Forming", and "Circuit identification" functions are automatically reset on
completion, i.e. P052 = 0 ("Return").
The other functions must be manually reset!
This function is used to reset the parameter values, in accordance with a) the parameter list (dispatch status for
the unit; see Section 5, column 4) and b) parameter P077 (see below). Only the settings of parameters P070
(MLFB) and P077 (type of factory setting) remain unchanged.
The MLFB-dependent parameters P071, P075 and P076 are set in accordance with the type of the
rectifier/regenerating unit (see Section 4.3.9.2 "Initialization").
The parameters dependent on P077 are set in accordance with the table shown below.
In the normal case (P070=0), the values listed in the parameter list in Section 5 are used as factory settings, so
the table shown below does not have to be considered.
For fast parameterization of special functions, using P077=1 to 6, an appropriate set of factory settings can be
selected for certain parameters in accordance with the table shown below. In this manner, for example, certain
terminals of the basic unit can be parameterized fast as sources for certain control word functions.
The following table shows the factory settings for the parameters that are dependent on P077:
In column 1, the parameters are listed for which the factory setting depends on P077. The right-hand columns
contain the factory settings for index 1 and 2 of these parameters depending on the value of parameter P077.
The values in the column "Normal factory setting" (P077=0) are the same as those listed in the parameter list in
Chapter 5 and are in accordance with the standard factory setting.
When P077 is set and the function "Generate factory setting" is selected, all parameters are set to their factory
settings, whereby the P077-dependent factory settings are taken into account.
"Generate factory setting" can be selected in the following statuses: "Switch-on inhibit" (008), "Ready-to-switch-
on" (009) or "Fault" (007).
Procedure:
If a special factory setting dependent on P077 is not required, i.e. P077=0, part a) of the following procedure is
not required and you start with part b).
a) Start of the procedure when a special factory setting is required, otherwise start at b) :
P077 Select the required P077-dependent parameter set in accordance with the
above table
P052 = 0 Terminate the function "Initialize"
- Factory setting for all parameters according to the parameter list in Chapter 5
(also the board configuration P090/P091) taking P077 into account
The operating display "Switch-on inhibit" (008) or "Ready-to-switch-on" (009) appears after the
factory setting has been completed.
This function is used to change the rectifier/regenerating unit MLFB (type setting).
The parameters P071, P075 and P076 are only set dependent on the new MLFB when changing the MLFB .
"Initialization" can be selected in the following statuses: "Switch-on inhibit" (008), "Ready-to-switch-on" (009) or
"Fault" (007).
Procedure:
P051 = 3 Access stage "Expert mode" to permit access to P070
P key The operating display appears and once the MLFB has been modified, the
following parameters are reassigned in accordance with the MLFB:
P071 Rated voltage at the input to the rectifier bridge
P075 Rated DC current
P076 Only the ones position is modified
Ones position = 2, when rectifier and regenerating mode is
possible
Ones position = 1, when only rectifier mode is possible
(only set when P070
101)
The operating display "Switch-on inhibit" (008) or "Ready-to-switch-on" (009) appears after
"Initialization" has been completed
MLFB table:
PWE MLFB I(n) U-Kl. BF
0 none 0.0 0 0
14 6SE7022-1EC85-1AA0 21.0 3AC 380-460V C
15 6SE7022-7FC85-1AA0 27.0 3AC 500-575V C
20 6SE7024-1EC85-1AA0 41.0 3AC 380-460V C
21 6SE7024-1FC85-1AA0 41.0 3AC 500-575V C
28 6SE7027-2FC85-1AA0 72.0 3AC 500-575V C
31 6SE7028-6EC85-1AA0 86.0 3AC 380-460V C
32 6SE7028-8FC85-1AA0 94.0 3AC 500-575V C
36 6SE7031-4HE85-1AA0 140.0 3AC 660-690V E
38 6SE7031-5FE85-1AA0 151.0 3AC 500-575V E
39 6SE7031-7EE85-1AA0 173.0 3AC 380-460V E
42 6SE7032-2EE85-1AA0 222.0 3AC 380-460V E
43 6SE7032-2HE85-1AA0 222.0 3AC 660-690V E
44 6SE7032-4FE85-1AA0 235.0 3AC 500-575V E
46 6SE7032-7FE85-1AA0 270.0 3AC 500-575V E
47 6SE7032-7HE85-1AA0 270.0 3AC 660-690V E
48 6SE7033-1EE85-1AA0 310.0 3AC 380-460V E
49 6SE7033-5FE85-1AA0 354.0 3AC 500-575V E
51 6SE7033-8EE85-1AA0 375.0 3AC 380-460V E
52 6SE7034-2FE85-1AA0 420.0 3AC 500-575V E
53 6SE7034-2HE85-1AA0 420.0 3AC 660-690V E
54 6SE7034-6EE85-1AA0 463.0 3AC 380-460V E
55 6SE7035-4FE85-1AA0 536.0 3AC 500-575V E
56 6SE7035-3HE85-1AA0 536.0 3AC 660-690V E
57 6SE7036-1EE85-1AA0 605.0 3AC 380-460V E
61 6SE7037-7FH85-1AA0 774.0 3AC 500-575V H
62 6SE7037-7HH85-1AA0 774.0 3AC 660-690V H
63 6SE7038-2EH85-1AA0 821.0 3AC 380-460V H
66 6SE7041-0EH85-1AA0 1023.0 3AC 380-460V H
67 6SE7041-0FH85-1AA0 1023.0 3AC 500-575V H
68 6SE7041-0HH85-1AA0 1023.0 3AC 660-690V H
71 6SE7041-3FK85-1AA0 1285.0 3AC 500-575V K
72 6SE7041-3HK85-1AA0 1285.0 3AC 660-690V K
73 6SE7041-3EK85-1AA0 1333.0 3AC 380-460V K
74 6SE7041-5FK85-1AA0 1464.0 3AC 500-575V K
75 6SE7041-5HK85-1AA0 1464.0 3AC 660-690V K
79 6SE7041-8EK85-1AA0 1780.0 3AC 380-460V K
80 6SE7041-8FK85-1AA0 1880.0 3AC 500-575V K
81 6SE7041-8HK85-1AA0 1880.0 3AC 660-690V K
P052 has to be set to 3 when a "download" (write) or "upload" (read) has to be carried out for the parameters of
the rectifier/regenerating unit at the basic unit interface (SST1) using USS protocol (e.g. using SIMOVIS).
Download" can be selected in the following statuses: "Switch-on inhibit" (008), "Ready-to-switch-on" (009) or
"Fault" (007).
Procedure:
P052 = 3 Function selection Download
P key
After return, the operating display appears, "Switch-on inhibit" (008) or "Ready-to-switch-on"
(009)
This function is used to select option boards (SCB, CB, TB) in the rectifier/regenerating unit electronics box.
In order to install these modules, an LBA bus coupling (Local Bus Adapter) is required for the electronics box
(see Section 9.1)!
All parameters, which can be written into the "Hardware configuration" status ("H", refer to the right-hand column
in the parameter list in Chapter 5), can be changed.
The "hardware configuration" selection can be realized in the "Switch-on inhibit", "Ready-to-switch" or "Fault"
status
Procedure:
P052 = 4 Function selection Hardware configuration
NOTE
Each of the option boards may only be used once in the electronics box!
When using the TB option board (e.g.: T300), this must always be inserted in slot 2 (at the RIGHT in the
electronics box!)
If only one option board is used, this must always be inserted at slot 2 (to the RIGHT in the electronics box)!
Additional parameters, depending on the option boards (refer to the associated Instruction
Manuals or Section 5)
P key The operating display appears (r000) while parameters and interval variables
are being re-assigned
- The hardware is initialized
If error/fault message F050, F070 or F080 appears: see Chapter 7
After the selected function selection has been completed, the "Switch-on inhibit" (008) or
"Ready-to-switch-on" (009) operating display appears.
This function is used to change the drive setting(rectifier/regenerating data, system data).
This includes all parameters that can be written in the "Drive setting" status ("A" ,see right-hand column of the
parameter list in Chapter 5).
Once you have completed the drive setting procedure, you can decide whether to implement the function
selection "Forming" (P052=20) or "Circuit identification" (P052 = 21) or whether just to reset the status (P052 =
0).
"Drive setting" can be selected in the following statuses: "Switch-on inhibit", "Ready-to-switch-on" or "Fault".
Procedure:
P052 = 5 Function selection Drive setting
P051 = 3 Access stage Expert mode - (if all parameters, which can be accessed in the
"drive setting" status (A) are required)
All parameters, which can be written into the "drive setting" (A) status (see
right-hand column of the parameter list in Chapter 5), can be changed.
The display appears (r000) while parameters and internal variables are being
de-assigned, depending on the function selected.
The "Switch-on inhibit" (008) or "Ready-to-switch-on" (009) operating display appears after the
selected function or selection has been completed
DANGER
The "Form DC link" function may only be implemented if the
rectifier/regenerating unit and the converter(s) connected have the
same voltage class (9th digit position of the MLFB).
If the converters have been left to stand idle for more than a year, the DC link capacitors must be re-formed. If
the converters are taken into service within a year of being delivered (factory number, rating plate); it is not
necessary to re-form the DC link capacitors. For more details on this subject, please refer to Section 4.3.12 of
the converter's operating instructions
The "Form DC link" function can be selected in the "Ready to switch on" status (009).
Procedure:
P408 Set the forming time (1.0 to 600.0 minutes; see Section 4.3.12 of the
converter's operating instructions
NOTE
The firing pulses are enabled, the rectifier/regenerating unit carries current and the DC link is charged!
During the forming procedure, the connected SIMOVERT Master Drives FC, VC, SC must not be switched on.
When this function has been completed, the "Ready to switch on" display (009) appears.
This function identifies the DC link and the supply and re-assigns certain control parameters.
Specific closed-loop control parameters are re-assigned in connection with this function..
Only the parameters of the reserve data sets currently selected are modified (see "Data sets" in Section 4.1.2
and "Selecting the data sets" in Section 4.4).
NOTE
Circuit identification (i.e. automatic setting of the appropriate parameters) must be carried out, otherwise error
message F061 will be generated when the unit is switched on.
While circuit identification is being carried out, the constellation of supply, and reactor and autotransformer
arrangement as well as the capacitive load connected to the DC link terminals of the rectifier/regenerating unit
must be identical to the constellation for normal operation later. The main reason being that the Ud controller
gain that is set depends on the measured intermediate circuit capacitance.
If more than one inverter of the series SIMOVERT Master Drives 6SE70 are to be operated with the
rectifier/regenerating unit, whereby the number of inverters connected to the DC link at any one time varies, it
is recommended that reserve data set selection is implemented. Up to 4 different configurations can be formed
for this purpose that are each assigned to a reserve data set. Circuit identification has to be carried out
separately for each of these reserve data sets. During circuit identification, the appropriate configuration must
exist for the selected data set.
Circuit identification must be carried out whenever the supply network changes and/or whenever the number of
connected inverters changes.
The "Circuit identification" function can be aborted at any time with an OFF command. This triggers fault
message F091 "Circuit identification aborted by external cause".
During circuit identification, which is carried out in a series of separate stages, code numbers appear on the
PMU that indicate the current working stage.
If an error occurs during a stage, the circuit identification function is aborted. The exact cause of the abort is
indicated in the fault value r949 assigned to the fault number memory r947 (for a non-reset fault in index i001
and if reset in index i009).
You will find a detailed description of the fault messages, associated fault values and a description on the
warning messages in Chapter 7 "Faults and Warnings".
You can select the "Circuit identification" function in the "Ready to switch on" status (009).
Procedure:
P052 = 21 Select the "Circuit identification" function
NOTE
The firing pulses are enabled, the rectifier/regenerating unit carries current and the DC link is charged up to a
certain limit! During circuit identification, the control angle is reduced until the generated separate current
crests reach an average value (with reference to an averaging time of 1/6 of the supply cycle time) of 25% of
P075 (with P160 = 150.0 %). By reducing P160 to 60.0 %, the required current crest size of up to 10 % of P075
can be reduced (with values P160 < 60.0 %, the threshold remains at 10 % of P075). Reduction of the size of
the generated current crests may be necessary when the sum of the rated currents of the inverters connected
to the rectifier/regenerating unit significantly drops below the rated current of the rectifier/regenerating unit.
The operating display appears. Circuit identification takes about 10 s with a discharged DC link
capacitor. The following parameters are set automatically:
On completion of the function, "Ready to switch on" (009) appears in the display.
NOTE
If a fault message occurs during circuit identification, the cause of the fault must be eliminated and the function
repeated (see Section 7.1).
Circuit identification for 12-pulse mode must be carried out in succession on the 12-pulse master and on the 12-
pulse slave units (see Section 3.8.5).
This function is used to display all parameters (regardless of the access stage) that differ from the factory setting
(i.e. plant-specific parameters). This function only works with operator control via the PMU but not with the OP1.
Adjustable parameters that have no factory setting (P070) or whose value depends on other parameters
(P071,...) are regarded as "modified".
Those parameters that are dependent on P077 (see Section 4.3.9.1 "Factory setting") whose values differ from
the setting for P077=0 are also regarded as modified.
"Modified" parameters for "special access" are also displayed that are only accessible to specially trained
personnel using P799.
The "Display modified parameters" function can be selected in all operating statuses.
Procedure:
P052 = 22 Select the "Display modified parameters" function
P key Only parameters that differ from the factory setting appear on the PMU (i.e.
plant-specific parameters), irrespective of the access stage (P051). It is not
possible to modify the parameter value here.
P key
NOTE
Parameters r990 and r991 provide a list of modified parameters for the PMU and also for the OP1.
4.3.10 Functions
The Automatic Restart function can be used for the automatic acknowledgment of faults and automatic restart of
the unit following a power failure (F003, F004, F005, F007, F009 or F010) without the operator having to
intervene.
If there is no voltage on one of the terminals 1U/L1, 1V/L2, 1W/L3, 1U2/1T1, 1V2/1T2, 1W2/1T3, X9.1, X9.2, or if
their values are not within the tolerance range and the DC link voltage has dropped below the threshold P074 *
1.35 * P071, the rectifier/regenerating unit responds as follows:
No automatic restart; the relevant fault message (F003, F004, F005, F007, F009 or F010) is initiated.
The rectifier/regenerating unit enters the operating status o008 (Switch-on inhibit) or o009 (when
switching on/off with the I/O keys of the PMU). On power recovery, a new ON command must be
given to enable the DC link to re-charge. The converter is not automatically restarted by the WEA
function.
P366 = 2 Restart after system recovery and pre-charging of the DC link after system recovery
While the system is down, the automatic controllers and firing pulses of the rectifier and regenerating
bridges are inhibited. The rectifier/regenerating unit enters the status o010. On power recovery, the
unit is automatically switched on again by the WEA. The DC link is re-charged.
The unit is only switched back on again if there is still an ON command (control word bit 0) active
following system recovery. The WEA function is therefore not possible with an ON command (control
word bit 0) programmed from the PMU or operator panel OP1 provided the external 24 V supply does
not fail.
IMPORTANT: External measures must be taken to guarantee safety on an automatic restart!
WARNING
In the event of system failures when the WEA function has been activated (P366 = 2), the
unit may restart on system recovery and re-charge the DC link.
If the WEA function (P366 = 2 or P366 = 3) of the converter has been activated, the
converter may also be switched back on. The drive may then stop for some considerable
time and may be erroneously assumed to be switched off.
Fatal injuries, severe bodily harm or damage to property and machinery may result if the
area surrounding the drive is entered while the drive is in this state.
NOTE
If the kinetic buffering function (KIP) is activated on a connected converter from the series SIMOVERT Master
Drives 6SE70, on the rectifier/regenerating unit, P366=2 must be parameterized.
If two rectifier/regenerating units for 12-pulse mode are coupled via peer-to-peer protocol via the basic unit
interface SST2, the peer-to-peer telegram failure time monitoring must be switched off via P687.i003=0 on the
"12-pulse master" unit, otherwise the automatic switch-on with the parameterization P366=2 (on both units) will
not work correctly if the electronics supply voltage fails.
P773
Rect.
P773
P774 0.05%
Regen.
Ud set
reduction
Siemens AG 6SE7087-6AK85-1AA0
P318
Shift αW
P774
I comp. = 0
Select
Kp TN Current limit in KP TN Stop I comp.
Function diagrams
Ud set Deadband
Pre-charging time P313 P314 rect. direction P310 P311
reduction pos. threshold αG MI 1
C
P144 Ud Uline
Filter time
P320
r006 r037
r035
P140 P141
Id RON LON
P142 P143
Rregen Lregen
4-47
1 2 3 4 5 6 7 8
4-48
Start-Up
P655
CU-AA actual values P656 P657
CU-AA gain CU-AA offset
Siemens AG 6SE7087-6AK85-1AA0
1 2 3 4 5 6 7 8
12.95
All grey-hatched background fields can be changed via the control word.
This is described in Figure 4.4.3.
P590
.i002 Q. base/reserve
.i001
Siemens AG 6SE7087-6AK85-1AA0
Base/reserve setting (Bas/Res) Control word bit 30
RESV
Parameters involved GRND 1
P486, P554 to P557, P561, P565 to P569 0
4-49
Start-Up 12.95
5 Parameter List
Example:
PNU OP1 - Parameter name Value range Display See
[phys. unit] Indices Modify
* : Conf. Description Selection text Factory (access/
setting status)
Par.
P329 Pre-charging time 0 to 9999 4 35)/ BR6)
1) [ms] 5009) 3/ BR7)
Pre-charging time of the DC link
8)
RDS parameter2)
14)
PNU=149Hex; Type=O2;3) Scaling: 1Hex
1) An
* under the parameter number means that this is a confirmation parameter, i.e. the modified value does
not become active until the P key is pressed.
2) Abbreviations for indexed parameters
RDS Reserve data set parameter with 4 indices; changeover with control word 2, bits 18 and 19
G/R Parameter with changeover feature for basic and reserve setting in control word 2, bit 30
1 Operator input
2 Standard mode
3 Expert mode
4 Factory-set parameters
6) 7) Operating states:
U MLFB input o000
H Hardware o002, o004
configuration
A Drive setting o005
B Ready (incl.: fault ) o007, o008, o009,
o010, o011, o012, o021
R (R) Run o014, o015, o018
8) An
** under the parameter number means that this parameter does not exist with a 6SE70 rectifier unit
(P070 (MLFB) 101).
9) A factory setting value in brackets means that the specified value only applies for P077=0. See Section
4.3.9.1 "Generate factory setting" for more details.
o014 Run
-- No thyristor bridge in circuit
I Rectifier bridge in circuit
II Regenerative bridge in circuit
o007 Fault
A fault message has been received.
o021 Download
A parameter download over SST1 can be executed
PNU=00Hex; 1
Type=O2; Scaling: 1Hex
PNU=1Hex; 1
Type=O2; Scaling: 1Hex
r006 DC Bus Volts 0 to 1000 - 2/ BR
[V] -
Actual DC link voltage
PNU=6Hex; 1V
Type=I2; Scaling: 1Hex
0 to 16384V
0 - 100%
r012 Base/Reserve 0 to 1 - 2/ BR
-
Base / reserve settings of the process data wiring for control word bits
0: Base setting
1: Reserve setting
1
PNU=0CHex; Type=O2; Scaling: 1Hex
r013 Operat. Hours 3 2/ BR
-
Display of operating hours with firing pulses enabled (Run status).
All times > about 0.1s are taken into account.
1
PNU=0DHex; Type=O2; Scaling: 1Hex
r030 Rectifier Volts 0.0 to 1000.0 - 2/ BR
[V] -
Display of the system voltage at the rectifier bridge (phase W-U)
0.1 V
PNU=1EHex; Type=O2; Scaling: 1Hex
0 to 1638.4V
0 - 100%
r031 Inverter Volts 0.0 to 1000.0 - 2/ BR
[V] -
Display of the system voltage at the regenerative bridge (average value of
the three phases)
PNU=1FHex; 0.1 V
Type=O2; Scaling: 1Hex
0 to 1638.4V
0 - 100%
PNU=23Hex; 1 %, 100%
Type=I2; Scaling: 1Hex P075
PZD gr.: 1
r036 DC Volts (set) 0 to 199 - 3/ BR
[%] -
Display of DC link voltage setpoint
The setpoint 1.35*r030, limited to values of P074 up to 106.8%.
PNU=24Hex; 1 %, 100%
Type=O2; Scaling: 1Hex 1.35 P071
*
PZD gr.: 1
r037 DC Volts (act) 0 to 199 - 2/ BR
[%] -
Display of actual DC link voltage
PNU=25Hex; 1 %, 100%
Type=O2; Scaling: 1Hex 1.35 P071
*
PZD gr.: 1
r038 DC Volts Deviat. -199.9 to 199.9 - 3/ BR
[%] -
Display of setpoint/actual-value deviation of DC link voltage controller
PNU=26Hex; 1 %, 100%
Type=I2; Scaling: 1Hex 1.35 P071
*
PZD gr.: 1
r039 AnalogOut Displ. -112.1 to 112.1 - 2/ BR
[%] -
Display of terminal X102-14 (analog output)
1
PNU=33Hex; Type=O2; Scaling: 1Hex
P052 Function Select 0 to 22 - 2/UHABR
0 2/UHAB
* Selection of several commissioning steps and special functions.
(See Section 4.3.9 for details)
0 = Return from on of the functions described below to the previous Return
status of the R/R unit
1 = Parameter-Reset: all parameters are reset to their original Param.Reset
settings (factory settings).
According to the Profibus profile for variable speed drives this
function is also accessible via parameter P970. After finishing
this function the parameter is automatically reset to 0.
2 = Release for MLFB setting (changing into the status 'MLFB Input MLFB
input'). To exit this function the parameter must be reset to 0.
3 = Download (Changing into the status 'Download'). To exit this Download
function the parameter must be reset to 0.
4 = Hardware configuration (Changing into the status 'Hardware HW Config.
settings'). To exit this function the parameter must be reset to 0.
5 = Drive setting (change to the status "Drive setting" for assigning
the plant data parameters. To exit this function the parameter System Set.
must be reset to 0.
20 = Forming of the DC link
21 = Circuit identification: Assigning the controller parameters of the FormingCaps
R/R unit Circuit ID
22 = Display only parameters with modified values
Important: This function can only be used in conjunction with Changed Par
operator control from the PMU. To exit this function the
parameter must be reset to 0 (Return).
PNU=34Hex; 1
Type=O2; Scaling: 1Hex
0: none
1: COM BOARD (CB)
2: BASE KEYPAD (PMU)
4: BASE SERIAL (SST1) (SST1 and OP)
8: Serial I/O (SCB with USS)) (SCB)
16: TECH BOARD (TB)
1
PNU=35Hex; Type=O2; Scaling: 1Hex
P054 Display Light 0 to 1 - 3/ BR
0 3/ BR
Backlight for the optional operation panel OP
0 = Backlight always ON always ON
1 = Backlight only ON during operation dur. operat.
1
PNU=36Hex; Type=O2; Scaling: 1Hex
P055 Copy Parameters 011 to 144 - 3/ B
012 3/ B
* This parameter permits the copying of data sets 1, 2, 3 or 4 to data sets 1,
2, 3 or 4.
Only those parameters specified in Section 4.4 "Selecting the data sets"
are affected by the copying process whereby each of these parameters has
4 indices that are assigned to the 4 data sets.
Data set 1 can be set with the parameters Pxxx i001
Data set 2 can be set with the parameters Pxxx i002
Data set 3 can be set with the parameters Pxxx i003
Data set 4 can be set with the parameters Pxxx i004
P055 is not stored in the EEPROM, and has the value "012" when the
electronic power supply is switched on.
PNU=37Hex; 1
Type=L2; Scaling: 1Hex
Enter the code of the corresponding MLFB here (see Section 4.3.9.2)
PNU=46Hex; Type=O2; Scaling: 1Hex 1
P071 Line Volts 100 to 1000 - 2/UABR
[V] acc. to P070 2/ A
* Line voltage of the rectifier bridge
RMS value of the rated voltage at which the power section is actually
operated
1
PNU=47Hex; Type=O2; Scaling: 1Hex
P074 Limit LowVoltage 10 to 100 - 2/ BR
[% of P071] 61 2/ BR
Response threshold for undervoltage disconnection and phase failure
or
monitoring and threshold for DC link voltage (ssee Section 4.3.10.1).
[% of 1.35*P071]
1
PNU=4AHex; Type=O2; Scaling: 1Hex
P075 Rtd Amps 0.0 to 3276.7 - 2/U BR
[A] acc. to P070 2/U
* Rated DC voltage of the R/R unit
Output DC current (average value) at the power terminals X1-C and X1-D.
0.1
PNU=4BHex; Type=O2; Scaling: 1Hex
P076 Config. PCircuit 01 to 22 - 3/ ABR
02 3/ A
* Configuration of the power section
x1 Motoring only
x2 Motoring and generating possible
0x No parallel power section connected
1x to 2x
Number of power sections connected in parallel
1
PNU=4CHex; Type=L2; Scaling: 1Hex
Parameter values:
0: Factory setting, acc. to "Parameter list", Chapter 5
1: With this setting, the following parameters are initialized differently as
compared to "0"
P554, P555
2: With this setting, the following parameters are initialized differently as
compared to "0"
P554, P555, P565, P566, P567, P575, P588, P607
4: With this setting, the following parameters are initialized differently as
compared to "0"
P554, P555, P565, P566, P575, P588, P607
5: With this setting, the following parameters are initialized differently as
compared to "0"
P486, P554, P555, P561, P565, P566, P567, P572, P575, P583, P587,
P588, 607
6: With this setting, the following parameters are initialized differently as
compared to "0"
P486, P554, P555, P561, P565, P566, P572, P575, P583, P587, P588,
P607
1
PNU=4DHex; Type=02; Scaling: 1Hex
r089 Module slot1 4 - 3/ B
-
Module in slot 1 (left) in the electronics box.
PNU=59Hex; 1
Type=02; Scaling: 1Hex
1
PNU=5AHex; Type=O2; Scaling: 1Hex
P091 Board Position 3 0 to 3 - 3/ HBR
0 3/ H
* PCB in position 3 (center) of the electronic box
Text as for P090
Description see P090(PCB position 2)
1
PNU=5BHex; Type=O2; Scaling: 1Hex
RDS parameter
0.001
PNU=6EHex; Type=O2; Scaling: 1Hex
P141 Rectifier Induct 0.00 to 327.67 4 3/ BR
[mH] 0.00 3/ BR
Circuit inductance of the rectifier bridge
This parameter is automatically set when circuit identification takes place
(P052=21)
RDS parameter
0.01
PNU=6FHex; Type=O2; Scaling: 1Hex
P142 Inverter Resist. 0.000 to 32.767 4 3/ BR
[ ] 0.000 3/ BR
** Circuit resistance of the regenerative bridge
This parameter is automatically set when circuit identification takes place
(P052=21)
RDS- parameter
0.001
PNU=70Hex; Type=O2; Scaling: 1Hex
P143 Inverter Induct. 0.00 to 327.67 4 3/ BR
[mH] 0.00 3/ BR
** Circuit inductance of the regenerative bridge
This parameter is automatically set when circuit identification takes place
(P052=21)
RDS parameter
0.01
PNU=71Hex; Type=O2; Scaling: 1Hex
P144 DC Bus Capacit. 0.00 to 327.67 4 3/ BR
[mF] 0.00 3/ BR
Capacitance of the DC link
This parameter is automatically set when circuit identification takes place
(P052=21)
RDS parameter
PNU=72Hex; 0.01
Type=O2; Scaling: 1Hex
5.7 Control
r150 Control Status 0 to 1818Hex - 3/ BR
Status word of the control
15 13 11 9
14 12 10 8
7 5 3 1
6 4 2 0
1
PNU=96Hex; Type=V2;Scaling: 1Hex
P160 Motor Curr Limit 0.0 to 150.0% of 4 3/ ABR
P075 150.0% 3/ A
Motoring current limit
[%]
The rectifier current is limited to the value set here
RDS parameter
0.1
PNU=0A0Hex; Type=O2; Scaling: 1Hex
P161 Regen Curr Limit -150.0 to 0.0% of 4 3/ ABR
P075 -150.0% 3/ A
** Generating current limit
[%]
The regenerating current is limited to the value set here.
RDS parameter
0.1
PNU=0A1Hex; Type=I2; Scaling: 1Hex
P310 DC Curr Reg Gain 0.01 to 1.00 4 3/ BR
0.15 3/ BR
Proportional gain of the DC link current controller
This parameter is automatically set when circuit identification takes place
(P052=21)
RDS parameter
0.01
PNU=136Hex; Type=O2; Scaling: 1Hex
P311 DC Curr Reg Time 0.001 to 1.000 4 3/ BR
[s] 0.015 3/ BR
Integral-action (reset) time of the DC link current controller
This parameter is automatically set when circuit identification takes place
(P052=21)
RDS parameter
0.001
PNU=137Hex; Type=O2; Scaling: 1Hex
P313 DC Volts RegGain 0.10 to 200.00 4 3/ BR
3.00 3/ BR
Proportional gain of the DC link voltage controller
This parameter is automatically set when circuit identification takes place
(P052=21)
RDS parameter
0.01
PNU=139Hex; Type=O2; Scaling: 1Hex
RDS parameter
0.01
PNU=13AHex; Type=O2; Scaling: 1Hex
P316 DC V-Reg +Limit 0.00 to 100.00 4 3/ BR
[%] of 1.35*P071 0.01 3/ BR
Positive threshold for the dead band of the setpoint/actual-value difference
of the Ud controller
A setpoint/actual-value deviation signal for the DC link voltage is not
applied to the Ud controller until the deviation of the DC link voltage
exceeds the value set here.
RDS parameter
0.01
PNU=13CHex; Type=O2; Scaling: 1Hex
P317 DC V-Reg -Limit -100.00 to 0.00 4 3/ BR
[%] of 1.35*P071 -1.00% 3/ BR
Negative threshold for the dead band of the setpoint/actual-value difference
of the Ud controller
A setpoint/actual-value deviation signal for the DC link voltage is not
applied to the Ud controller until the deviation of the DC link voltage drops
below the value set
RDS parameter
0.01
PNU=13DHex; Type=I2; Scaling: 1Hex
P318 DC V(set,red) 0.00 to 100.00 4 3/ ABR
[%] of 1.35* Supply 80.00 3/ A
DC link voltage setpoint when selecting the DC link voltage reduction
voltage at the
function
rectifier bridge
RDS parameter
0.01
PNU=13EHex; Type=O2; Scaling: 1Hex
P319 DC V(set,red)Hys 0.00 to 100.00 4 3/ ABR
[%] of 1.35xP071 6.00% 3/ ABR
Hysteresis for Ud < Ud(set,red)
(message "Ud reduced")
RDS parameter
0.01
PNU=13FHex; Type=O2; Scaling: 1Hex
P320 Smooth Load Amps 0 to 9999 4 3/ BR
[ms] 5 3/ BR
Smoothing time for feedforward load current injection
RDS parameter
1
PNU=140Hex; Type=O2; Scaling: 1Hex
P329 PreCharge Time 0 to 9999 4 3/ BR
[ms] 500 3/ BR
DC link pre-charging time
RDS parameter
1
PNU=149Hex; Type=O2; Scaling: 1Hex
Important: When units are connected in parallel (see Section 3.7), the
thyristor test results are only conditionally useful.
1
PNU=161Hex; Type=O2; Scaling: 1Hex
P354 Ground Fault Test 0 to 3 - 3/ BR
2 3/ B
* Checking the S/F unit for ground faults
This is not a protective function as defined by the VDE guidelines!
Note: The ground fault test is only carried out if the DC link voltage is
less than 50% of 1.35*P071; otherwise it is automatically
skipped!
1
PNU=162Hex; Type=O2; Scaling: 1Hex
1
PNU=16EHex; Type=O2; Scaling: 1Hex
P408 Caps FormingTime 1.0 to 600.0 4 2/ ABR
[min] 10.0 2/ AB
Forming time of the DC link
This parameter is used when forming the DC link (P052=20).
RDS parameter
0.1
PNU=198Hex; Type=O2; Scaling: 1Hex
P409 Contactor Delay 0.0 to +120.0 - 3/ BR
[s] 0.0 3/ B
Closing delay of the line contactor
Closing of the line contactor is delayed by the time set here with respect to
the "Switch on" command.
This parameter can be used to implement time grading when energizing the
line contactors of several drive units in order to prevent the inrush currents
of the autotransformers for regenerative mode overloading a supply
transformer.
0.1
PNU=199Hex; Type=O2; Scaling: 1Hex
Parameter values:
As per PZD wiring of the setpoint channel (see Section 4.3.1.3)
G/R parameter
1
PNU=1E6Hex; Type=L2; Scaling: 1Hex
P517 DC Volts Dev Lim 0.00 to 100.00 4 3/ BR
[%] of 1.35*P071 2.00 3/ B
Setpoint/actual-value deviation of Ud:
If the deviation between the Ud setpoint and the actual Ud is considerable,
the "Setpoint/actual-value deviation" message is generated (status word 1
Bit 8 (r552))
Compare P518 (min. duration of deviation)
RDS- parameter
0.01
PNU=205Hex; Type=O2; Scaling: 1Hex
P518 Deviation Time 0.00 to 10.00 4 3/ BR
[s] 0.10 3/ B
Min. deviation time:
If there is a deviation (P517), the "Setpoint/actual-value deviation" message
(status word 1 bit 8 (r552)) is generated after this minimum time has
elapsed
RDS parameter
0.01
PNU=206Hex; Type=O2; Scaling: 1Hex
15 13 11 9
14 12 10 8
7 5 3 1
6 4 2 0
1
PNU=226Hex; Type=V2;Scaling: 1Hex
r551 Control Word 2 - 2/ BR
31 29 27 25
30 28 26 24
23 21 19 17
22 20 18 16
1
PNU=227Hex; Type=V2;Scaling: 1Hex
r552 Status Word 1 - 2/ BR
15 13 11 9
14 12 10 8
7 5 3 1
6 4 2 0
1
PNU=228Hex; Type=V2;Scaling: 1Hex
r553 Status Word 2 - 2/ BR
Display of the status word 2 bits 16 to 31, see Section 4.3.1.2.2
31 29 27 25
30 28 26 24
23 21 19 17
22 20 18 16
1
PNU=229Hex; Type=V2;Scaling: 1Hex
P554 Src ON/OFF1 0 to 6005 2 2/ BR
(i001=1010) 2/ BR
* Source of the 'ON/OFF1' command (control word 1, bit 0)
(i002=1001)
0: OFF1
1: Not allowed
1001: CUR, binary input 1
1010: PMU ON/OFF keys
Other values: see allowed settings in Section 4.3.1.1 (process data
wiring of the control word)
B/R Parameter
1
PNU=22AHex; Type=L2; Scaling: 1Hex
P555 Src1 OFF2 1 to 6005 2 2/ BR
(i001=1010) 2/ BR
* Source 1 of the 'OFF2' command (control word 1, bit 1)
(i002=1002)
0: Not allowed
1: Condition for operation
1002: binary input 2 of the CUR board
Other values: see allowed settings in Section 4.3.1.1 (process data
wiring of the control word)
B/R Parameter
1
PNU=22BHex; Type=L2; Scaling: 1Hex
B/R Parameter
1
PNU=22CHex; Type=L2; Scaling: 1Hex
P557 Src3 OFF2 1 to 6005 2 2/ BR
1 2/ BR
* Source 3 of the 'OFF2' command (control word 1, bit 1)
B/R Parameter
1
PNU=22DHex; Type=L2; Scaling: 1Hex
P561 Src InvRelease 1 to 6005 2 2/ BR
(1) 2/ BR
* Source for the "Run enable" command (control word 1, bit 3)
0: Pulse inhibit
1: Automatic "Run enable" at end of waiting times
Other values: see allowed settings in Section 4.3.1.1 (process data
wiring of the control word)
B/R Parameter
1
PNU=231Hex; Type=L2; Scaling: 1Hex
P565 Src1 Fault Reset 0 to 6005 2 2/ BR
(i001=0) 2/ BR
* Source 1 of the 'Reset' command (control word 1, bit 7)
(i002=1003)
0: No source selected
1: Not allowed
1003: Binary input 3 of the CUR board
Other values: see allowed settings in Section 4.3.1.1 (process data
wiring of the control word) whereby "Reset" from the
PMU is always possible
1
PNU=235Hex; Type=L2; Scaling: 1Hex
P566 Src2 Fault Reset 0 to 6005 2 2/ BR
(0) 2/ BR
* Source 2 of the 'Reset' command (control word 1, bit 7)
B/R parameter
1
PNU=236Hex; Type=L2; Scaling: 1Hex
P567 Src3 Fault Reset 0 to 6005 2 2/ BR
(2001) 2/ BR
* Source 3 of the 'Reset' command (control word 1, bit 7)
B/R parameter
1
PNU=237Hex; Type=L2; Scaling: 1Hex
0: No Jog operation
1: Not allowed
Other values: see allowed settings in Section 4.3.1.1 (process data
wiring of the control word)
B/R-Parameter
1
PNU=238Hex; Type=L2; Scaling: 1Hex
P569 Src Jog2 ON 0 to 6005 2 2/ BR
0 2/ BR
* Source of the 'Jog 2' command (control word 1, bit 9)
B/R parameter
1
PNU=239Hex; Type=L2; Scaling: 1Hex
P571 Src Reduce DC V 0 to 6005 2 2/ ABR
0 2/ ABR
* Source for the "Reduce Ud" control command (control word 1, bit 11)
B/R parameter
1
PNU=23BHex; Type=L2; Scaling: 1Hex
P572 Src RegenRelease 0 to 6005 2 2/ BR
(1) 2/ BR
* Source for the "Regenerating enable" control command (control word 1, bit
12)
**
0: Regenerating inhibited
1: Regenerating enabled
Other values: see allowed settings in Section 4.3.1.1 (process data
wiring of the control word)
B/R parameter
1
PNU=23CHex; Type=L2; Scaling: 1Hex
P573 Src No ExtFault3 1 to 6005 2 2/ BR
1 2/ BR
* Source for the "External fault 3" control command (control word 1, bit 13)
L signal causes disconnection of the faulted drive.
0: Not allowed
1: No external fault 3
1003: Binary input 3 of the CUR board
Other values: see allowed settings in Section 4.3.1.1 (process data
wiring of the control word)
B/R parameter
1
PNU=23DHex; Type=L2; Scaling: 1Hex
B/R parameter
1
PNU=23EHex; Type=L2; Scaling: 1Hex
P575 Src No ExtFault1 1 to 6005 2 2/ BR
(1) 2/ BR
* Source for the "External fault 1" control command (control word 1, bit 15)
L signal causes disconnection of the faulted drive.
0: Not allowed
1: No external fault 1
1003: Binary input 3 of the CUR board
Other values:
see allowed settings in Section 4.3.1.1 (process data
wiring of the control word)
B/R parameter
1
PNU=23FHex; Type=L2; Scaling: 1Hex
P578 Src RDataSetBit0 0 to 6005 2 3/ BR
0 3/ BR
* Source for bit 0 (control word 2, bit 18) for selecting the reserve data set
(RDS)
B/R parameter
1
PNU=242Hex; Type=L2; Scaling: 1Hex
P579 Src RDataSetBit1 0 to 6005 2 2/ BR
0 2/ BR
* Source for bit 1 (control word 2, bit 19) for selecting the reserve data set
(RDS)
B/R parameter
1
PNU=243Hex; Type=L2; Scaling: 1Hex
0: No 12-pulse mode
1: 12-pulse mode is selected
Other values: see allowed settings in section 4.3.1.1 (process data
wiring of the control word)
B/R parameter
1
PNU=247Hex; Type=L2; Scaling: 1Hex
P586 Src No ExtFault2 1 to 6005 2 2/ BR
1 2/ BR
* Source of the 'External fault 2' message (control word 2, bit 26)
L signal causes disconnection of the faulted unit after a pre-charging time
of + 200ms if the rectifier/regenerating unit is in the "RUN" status.
0: Not allowed
1: No external fault
1004: Binary input 4 of the CUR board
Other values: see allowed settings in Section 4.3.1.1 (process data
wiring of the control word)
B/R parameter
1
PNU=24AHex; Type=L2; Scaling: 1Hex
P587 Src Master/Slave 0 to 6005 2 2/ BR
(0) 2/ BR
* Source for the master/slave drive changeover (control word 2, bit 27)
B/R parameter
1
PNU=24BHex; Type=L2; Scaling: 1Hex
P588 Src No Ext Warn1 1 to 6005 2 3/ BR
(1) 3/ BR
* Source of the 'External warning 1' message (control word 2, bit 28)
0: Not allowed
1: No external warning
Other values:
see allowed settings in Section 4.3.1.1 (process data wiring of
the control word)
B/R- parameter
1
PNU=24CHex; Type=L2; Scaling: 1Hex
P589 Src No Ext Warn2 1 to 6005 2 3/ BR
1 3/ BR
* Source of the 'external warning 2' message (control word 2, bit 29))
0: Not allowed
1: No external warning
Other values: see allowed settings in Section 4.3.1.1 (process data
wiring of the control word)
B/R parameter
1
PNU=24DHex; Type=L2; Scaling: 1Hex
0: Base setting
1: Reserve setting
1005: Binary input 5 of the CUR board
Other values: see allowed settings in Section 4.3.1.1 (process data
wiring of the control word)
1
PNU=24EHex; Type=L2; Scaling: 1Hex
P591 Src ContactorMsg 1 to 4216 - 3/ BR
1 3/ BR
* Source of the 'Main contactor energized' message(control word 2, bit 31)
0: Not allowed
1: No main contactor checkback signal
1001 to 1005: CUR terminals
4101 to 4116: SCB-SCI1- terminals (serial I/O)
4201 to 4216: SCB-SCI2- terminals (serial I/O)
Notes:
If the function is active, pulses are released as soon as the message is
available.
No base / reserve settings possible
1
PNU=24FHex; Type=L2; Scaling: 1Hex
r599 CW/SW 12-Pulse - 2/ BR
Display of control/status word for 12-pulse mode, bit 0 to 15, see Section
3.8.4.
15 13 11 9
14 12 10 8
7 5 3 1
6 4 2 0
1
PNU=257Hex; Type=V2;Scaling: 1Hex
P600 Trg Bit Ready On 0 to 4212 2 3/ BR
0 3/ BR
* Destination of the status bit 'ready for turn ON' (status word 1, bit 0)
Power is ON, the drive may be turned on.
1
PNU=258Hex; Type=L2; Scaling: 1Hex
P601 Trg Bit Rdy Oper 0 to 4212 2 3/ BR
0 3/ BR
* Destination of the status bit 'Ready for operation' (status word 1, bit 1)
All the settings specified in Section 4.3.1.2 (process data wiring of the
status word) are permissible, depending on the index selected
1
PNU=259Hex; Type=L2; Scaling: 1Hex
1
PNU=25AHex; Type=L2; Scaling: 1Hex
P603 Trg Bit Fault 0 to 4212 2 2/ BR
i001=1002 2/ BR
* Destination of the status bit 'Fault' (status word 1, bit 3)
i002=0
Note:
For issuing the fault message via a terminal the active status (bit has H-
level) is inverted (broken wire proof).
1
PNU=25BHex; Type=L2; Scaling: 1Hex
P604 Trg Bit No OFF2 0 to 4212 2 3/ BR
0 3/ BR
* Destination of the status bit 'No OFF2 command' (status word 1, bit 4)
1
PNU=25CHex; Type=L2; Scaling: 1Hex
P606 Trg BitONblocked 0 to 4212 2 3/ BR
0 3/ BR
* Destination of the status bit 'Turn-ON locked' (status word 1, bit 6)
Note:
For issuing the message via a terminal the active status (bit has H-level) is
inverted (broken wire proof).
1
PNU=25EHex; Type=L2; Scaling: 1Hex
P607 Trg Bit Warning 0 to 4212 2 2/ BR
(0) 2/ BR
* Destination of the status bit 'Warning' (status word 1, bit 7)
Note:
For issuing the message via a terminal the active status (bit has H-level) is
inverted (broken wire proof).
1
PNU=25FHex; Type=L2; Scaling: 1Hex
P608 Trg Bit Deviat. 0 to 4212 2 3/ BR
0 3/ BR
* Destination wiring of the status bit "Ud set = Ud act“ (status word 1, bit 8) -
cf. P517
1
PNU=260Hex; Type=L2; Scaling: 1Hex
P610 Trg Regen Ready 0 to 4212 2 3/ BR
0 3/ BR
* Destination wiring of the status bit "Regenerating ready" (status word 1,
Bit 10)
1
PNU=260Hex; Type=L2; Scaling: 1Hex
Note:
For issuing the message via a terminal the active status (bit has H-level) is
inverted (broken wire proof).
1
PNU=263Hex; Type=L2; Scaling: 1Hex
P612 Trg Bit Contact 0 to 4212 2 3/ BR
0 3/ BR
* Destination of the status bit 'Energize main contactor' (status word 1, bit 12)
H level: energize contactor!
1
PNU=264Hex; Type=L2; Scaling: 1Hex
P613 Trg DC V reduced 0 to 4212 2 3/ ABR
0 3/ ABR
* Destination wiring for the status bit "Ud reduced“
(status word 1, bit 13)
1
PNU=265Hex; Type=L2; Scaling: 1Hex
P614 Trg Motor/Regen 0 to 4212 2 3/ BR
0 3/ BR
* Destination wiring for the status bit "Regenerative/motoring mode" (status
word 1, bit 14)
**
Parameter values, Indices: as P600
1
PNU=266Hex; Type=L2; Scaling: 1Hex
P618 Trg Current Lim. 0 to 4212 2 3/ BR
0 3/ BR
* Destination wiring of the status bit "Current limit active"
(status word 2, bit 18)
Note:
For issuing the message via a terminal the active status (bit has H-level) is
inverted (broken-wire proof).
1
PNU=26AHex; Type=L2; Scaling: 1Hex
P619 Trg Bit Ext Flt1 0 to 4212 2 3/ BR
0 3/ BR
* Destination of the status bit 'External fault 1' (status word 2, bit 19)
Note:
For issuing the message via a terminal the active status (bit has H-level) is
inverted (broken wire proof).
1
PNU=26BHex; Type=L2; Scaling: 1Hex
1
PNU=26CHex; Type=L2; Scaling: 1Hex
P621 Trg Bit ExtWarn 0 to 4212 2 3/ BR
0 3/ BR
* Destination of the status bit 'External warning'
(status word 2, bit 21)
Note:
For issuing the message via a terminal the active status (bit has H-level) is
inverted (broken wire proof).
1
PNU=26DHex; Type=L2; Scaling: 1Hex
P622 Trg Bit i2t Inv 0 to 4212 2 3/ BR
0 3/ BR
* Destination of the status bit 'Warning unit overload'
(status word 2, bit 22);
Note:
For issuing the message via a terminal the active status (bit has H-level) is
inverted (broken wire proof).
1
PNU=26EHex; Type=L2; Scaling: 1Hex
P623 Trg BitFltTmpInv 0 to 4212 2 3/ BR
0 3/ BR
* Destination of the status bit 'Fault unit overtemperature'
(status word 2, bit 23
Note:
For issuing the message via a terminal the active status (bit has H-level) is
inverted (broken wire proof).
1
PNU=26FHex; Type=L2; Scaling: 1Hex
P624 Trg BitWarTmpInv 0 to 4212 2 3/ BR
0 3/ BR
* Destination of the status bit 'Warning unit overtemperature'
(status word 2, bit 24
Note:
For issuing the message via a terminal the active status (bit has H-level) is
inverted (broken wire proof).
1
PNU=270Hex; Type=L2; Scaling: 1Hex
Note:
For issuing the message via a terminal the active status (bit has H-level) is
inverted (broken wire proof).
1
PNU=277Hex; Type=L2; Scaling: 1Hex
1
PNU=28FHex; Type=O2; Scaling: 1Hex
P656 CUR AnaOut Gain 320,00 - 2/ BR
[V] 10.00 2/ BR
Gain for the analog output of the CUR (terminal X102-14)
0.01 V
PNU=290Hex; Type=I2; Scaling: 1Hex
P657 CUR AnaOutOffset -100.00 to 100.00 - 2/ BR
[V] 0.00 2/ BR
Offset for the analog output on the CUR (terminal X102-14)
The analog output can represent voltages of -10V to +10V.
0.01 V
PNU=291Hex; Type=I2; Scaling: 1Hex
P658 AnaOut Conf Curr 0 to 3 - 2/ BR
0 2/ BR
* Configuration of terminal X102-16 (actual current display)
0 Output with correct sign signed
(positive voltage: motoring current)
(negative voltage: regenerative current)
1 Output absolute value (positive voltage only) absoluteVal
inverted
2 Signed output, inverted
(positive voltage: motoring current)
(negative voltage: regenerative current)
inv. absVal
3 Output of absolute value, inverted (negative voltage only)
1
PNU=292Hex; Type=O2; Scaling: 1Hex
Notes:
Only one signal can be wired per input; alternatively voltage or current
signals can be evaluated.
Voltage and current signals must be connected to different terminals.
Settings 1 and 2 only allow unipolar signals, i. e. the internal process data
are also unipolar.
At setting 2 an input current < 2 mA causes a fault trip (broken wire proof)
The offset scaling of the analog inputs is done via P662.
Condition:
The related SCB board must be reported via P090 and P091, respectively
1
PNU=294Hex; Type=O2; Scaling: 1Hex
P661 SCI AnaInSmooth 0 to 15 6 3/ BR
2 3/ BR
Filter time constant of the SCI analog inputs
1
PNU=295Hex; Type=O2; Scaling: 1Hex
P662 SCI AnalogInOffs -320.00 to 320.00 6 3/ BR
[V] 0.00 3/ BR
Offset scaling of the SCI analog inputs
Description for setting see SCI manual
0.01 V
PNU=296Hex; Type=I2; Scaling: 1Hex
Condition:
The related SCB board must be reported via P090 and P091, respectively
1
PNU=298Hex; Type=O2; Scaling: 1Hex
P665 SCI AnaOut Gain -320.00 to 320.00 6 3/ BR
[V] 10.00 3/ BR
Proportional gain of the SCI analog outputs
0.01 V
PNU=299Hex; Type=I2; Scaling: 1Hex
P666 SCI AnaOut Offs -320.00 to 320.00 6 3/ BR
[V] 0.00 3/ BR
Offset of the SCI analog outputs
0.01 V
PNU=29AHex; Type=I2; Scaling: 1Hex
5.12 Communications
P680 Scom1 Act Value 0 to 999 16 3/ BR
i001=968 3/ B
* Process data assignment for actual-value output over serial interface SST1.
i002=0
Defines the parameter positions in the telegram.
...
i016=0
Notes:
Word 1 should be assigned status word 1 (r552=r968).
The length (number of words) of the process data part in the telegram is set
with P686, Index i001.
1
PNU=2A8Hex; Type=O2; Scaling: 1Hex
P681 Scom2 Act Value 0 to 999 5 3/ BR
i001=599 3/ B
* Selection of the process data to be transmitted over serial interface SST2
i002=34
(actual values) with peer-to-peer protocol selected (P688=1).
i003=0
Defines the parameter positions in the telegram.
i004=0
i005=0
Notes:
The length (number of words) of the process data part in the peer-to-peer
telegram is set with P686, Index i003.
1
PNU=2A9Hex; Type=O2; Scaling: 1Hex
P682 SCB Protocol 0 to 5 - 3/ HBR
0 3/ H
* SCB can be operated as
master for the SCI boards or as
serial communications board
(see SCB manual).
Condition:
SCB board must be reported via P090 and 0P91, respectively
1
PNU=2AAHex; Type=O2; Scaling: 1Hex
P683 SCom/SCB BusAddr 0 to 30 2 3/ BR
0 3/ B
* Bus address of the serial communication interfaces
1
PNU=2ABHex; Type=O2; Scaling: 1Hex
1
PNU=2ACHex; Type=O2; Scaling: 1Hex
P685 SCom/SCB #PKWDat 0 to 127 2 3/ BR
i001=127 3/ B
* Number of words (16 bit) of the parameter data part in the net data block of
i002=127
the telegram.
1
PNU=2ADHex; Type=O2; Scaling: 1Hex
P686 SCom/SCB # PrDat 0 to 16 3 3/ BR
2 3/ B
* Number of words (16 bits) of the process data part in the net data block of
the telegram.
PWE=0 means that no process data are expected in the USS protocol and
that none are sent.
1
PNU=2AEHex; Type=O2; Scaling: 1Hex
1ms
PNU=2AFHex; Type=O2; Scaling: 1Hex
P688 SST2 Protocol 0 to 1 - 3/ BR
0 3/ B
* Selection of the protocol for SST2 (serial interface 2 (CUR with PTP1
option))
1
PNU=2B0Hex; Typ=O2; Normierung: 1Hex
P689 SCB Peer2PeerExt 0 to 1 5 3/ BR
0 3/ BR
Immediate transfer on of data received via the peer to peer protocol of
SCB.
Mark of these words of the received peer to peer telegram which are to be
transferred on immediately.
CUR only
0: No immediate transfer (only to CUR) Transfer
1: Immediate transfer (and passing to CUR)
1
PNU=2B1Hex; Type=O2; Scaling: 1Hex
The length (number of words) of the process data part of the telegram is set
with P686, Index 02
1
PNU=2B2Hex; Type=O2; Scaling: 1Hex
P694 CB/TB Act Values 0 to 999 16 3/ BR
i001=968 3/ B
* Actual-value output over the serial interface of the CB and/or TB module
i002=0
Defines which parameter is to be transferred at which telegram address.
...
i016=0
Note:
Word 1 should be set for status word 1 (r552=r968)
If "0" is entered (factory setting from i002 to i016), the option module does
not pass the current value of r000 to the control system (e.g. SIMATIC), but
the constant value "0".
1
PNU=2B6Hex; Type=O2; Scaling: 1Hex
P695 CB/TB TlgOFFTime 0 to 6500 - 3/ BR
[ms] 20 3/ BR
* Telegram lag time of CB and TB
If no correct telegram is received within the parameterized time a fault trip
is set.
Monitoring is carried out at intervals of 20 ms, therefore it is only
appropriate to set values that are multiples of 20 ms.
1 ms
PNU=2B7Hex; Type=O2; Scaling: 1Hex
P696 CB Parameter 1 0 to 65535 - 3/ HBR
0 3/ H
Communication board parameter 1.
See manual of the used communication board.
1
PNU=2B8Hex; Type=O2; Scaling: 1Hex
P697 CB Parameter 2 0 to 65535 - 3/ HBR
0 3/H
Communication board parameter 2
see P696
1
PNU=2B9Hex; Type=O2; Scaling: 1Hex
1
PNU=2BAHex; Type=O2; Scaling: 1Hex
P699 CB Parameter 4 0 to 65535 - 3/ HBR
0 3/ H
Communication board parameter 4
See P696
1
PNU=2BBHex; Type=O2; Scaling: 1Hex
P700 CB Parameter 5 0 to 65535 - 3/ HBR
0 3/ H
Communication board parameter 5
See P696
1
PNU=2BCHex; Type=O2; Scaling: 1Hex
P701 CB Parameter 6 0 to 65535 - 3/ HBR
0 3/ H
Communication board parameter 6
See P696
1
PNU=2BDHex; Type=O2; Scaling: 1Hex
P702 CB Parameter 7 0 to 65535 - 3/ HBR
0 3/ H
Communication board parameter 7
See P696
1
PNU=2BEHex; Type=O2; Scaling: 1Hex
P703 CB Parameter 8 0 to 65535 - 3/ HBR
0 3/ H
Communication board parameter 8
See P696
1
PNU=2BFHex; Type=O2; Scaling: 1Hex
P704 CB Parameter 9 0 to 65535 - 3/ HBR
0 3/ H
Communication Board Parameter 9
See P696
1
PNU=2C0Hex; Type=O2; Scaling: 1Hex
P705 CB Parameter 10 0 to 65535 - 3/ HBR
0 3/ H
Communication board parameter 10
See P696
1
PNU=2C1Hex; Type=O2; Scaling: 1Hex
5.13 Diagnostics
r720 SW Version 3 3/U BR
Software version of the PCBs in positions 1, 2 and 3 of the electronic box.
Indices:
i001: Pos1: Software version of the PCB in position 1
i002: Pos2: Software version of the PCB in position 2 Pos1
i003: Pos3: Software version of the PCB in position 3 Pos2
Pos3
0.1
PNU=2D0Hex; Type=O2; Scaling: 1Hex
r721 SW Generat. Date 3 3/U BR
Software generation date of the CUR board.
1
PNU=2D1Hex; Type=O2; Scaling: 1Hex
r722 SW ID 3 3/U BR
Indices:
i001: SPL1: Software code of the PCB in position 1
i002: SPL2: Software code of the PCB in position 2
i003: SPL3: Software code of the PCB in position 3
0.1
PNU=2D2Hex; Type=O2; Scaling: 1Hex
r723 PCB Code 3 3/U BR
Identification code of the PCBs in positions 1, 2 and 3 of the electronic box
Indices:
i001: SPL1: PCB code of the PCB in position 1
i002: SPL2: PCB code of the PCB in position 2
i003: SPL3: PCB code of the PCB in position 3
PCB codes:
CUR: 105
CB: 140 - 149
TB: 130 - 139
SCB: 120 - 129
1
PNU=2D3Hex; Type=O2; Scaling: 1Hex
r725 HeadroomCalcTime 0 to 100% - 3/ BR
[%] - 3/
Headroom of the CPU on the CUR module.
1%
PNU=2D5Hex; Type=O2; Scaling: 1Hex PZD gr.: 1
100% computer time free
Analog output: 100%
SCB diagnostics
All values in HEX display
If a quantity is represented, overflow takes place at FF Hex.
The meaning of several Indices depends of the selected SCB protocol
(P682).
1
PNU=2DAHex; Type=L2; Scaling: 1Hex
r731 CB/TB Diagnostics 32 3/ HBR
For detailed information see manuals of the used communication boards
(CB) or technology boards (TB).
1
PNU=2DBHex; Type=L2; Scaling: 1Hex
r748 Fault Time 24 2/ BR
The instants at which faults occur (reading of the hours counter r013 at the
instant the fault occurs)
1
PNU=2ECHex; Type=O2; Scaling: 1Hex
5.14 Modulator
P773 Deadband Convert 0.01 to 100.00 4 3/ BR
[%] 0.01 3/ BR
The reversing threshold of the auto-reversing module (in rectifier direction)
If the (signed) setpoint of the DC link current (output of the DC link voltage
controller on the output side of the limiting module) exceeds the value of +
0.05% set with this parameter, the firing pulses of the rectifier bridge are
enabled. These pulses are inhibited if the setpoint of the DC link current
drops below the value set here.
RDS parameter
0.01 %
PNU=305Hex; Type=O2; Scaling: 1Hex
P774 Deadband Invert -100.00 to -0.01 4 3/ BR
[%] -3.00 3/ BR
** The reversing threshold of the auto-reversing module (in regenerating
direction)
If the (signed) setpoint of the DC link current (output of the DC link voltage
controller on the output side of the limiting module) exceeds the value of -
0.05% set with this parameter, the firing pulses of the rectifier bridge are
enabled. These pulses are inhibited if the setpoint of the DC link current
drops below the value set here..
RDS parameter
0.01
PNU=306Hex; Type=O2; Scaling: 1Hex
P775 Min Gating Angle 0 to 120 4 3/ BR
[el] 0 3/ BR
Alpha G limit (rectifier stability limit)
RDS parameter
1 el
PNU=307Hex; Type=O2; Scaling: 1Hex
P776 Max Gating Angle 120 to 165 4 3/ BR
[el] 150 3/ B
Alpha W limit (inverter stability limit)
RDS parameter
1 el
PNU=308Hex; Type=O2; Scaling: 1Hex
P777 Max Gating Angle Ramp 0.00 to 100.00 4 3/ BR
[%] of P075 20.00 3/ BR
Transition ramp of the alpha W limit from pulsating to continuous DC (for
currents < pulsating threshold, the control angle is limited to 165°, for
currents > (pulsating threshold+P777) to P776 with linear interpolation
inbetween)
RDS parameter
1%
PNU=309Hex; Type=O2; Scaling: 1Hex
2
0 Response of the i t monitor for the power section (i.e. 100% of
2
the i t value has been reached) results in an automatic
reduction of the limit for the current setpoint to the rated DC
current until the absolute value of the current setpoint has
dropped below the rated DC current before its limit, and the
calculated equivalent junction temperature rise is again below
the unit-specific response threshold. The current setpoint limit is
then raised again.
2
1 Response of the i t monitor for the power section (i.e. 100% of
2
the i t value has been reached) results in fault F022 and
disconnection.
1
PNU=311Hex; Type=O2; Scaling: 1Hex
P793 Line Voltage Delay 0.01 to 1.00 - 3/ BR
[s] 0.03 3/ BR
Stabilizing time for the line voltage
If the "Switch-on" command is given, the unit waits in status o010 for
voltage to be applied to the power section. The line voltage is not assumed
to be applied to the power terminals until amplitude, frequency and phase
symmetry lie within the permissible tolerance range for longer than the time
set with this parameter. The parameter applies to both the rectifier and
regenerative power terminals.
0.01 s
PNU=319Hex; Type=O2; Scaling: 1Hex
P799 Special Access 0 to 65535 - 3/U BR
3/ BR
Parameter for special access
1
PNU=31FHex; Type=O2; Scaling: 1Hex
Important:
When the control word is modified, spontaneous message buffers can be
deleted with the loss of spontaneous messages!
Setting help:
Each interface is coded with a number.
Enter the number and/or the sum of several numbers assigned to the
interfaces to enable the spontaneous message mechanism for the relevant
interface(s).
1
PNU=395Hex; Type=O2; Scaling: 1Hex
P918 CB Bus Address 3 to 126 - 3/ HBR
3 3/ H
Protocol depending bus address for communication board; see manual of
this board.
Notes:
The communication board checks, if the set value is valid. (The bus
addresses 0 to 2 are reserved for master stations and therefore cannot be
set). If the value is not accepted, the fault message 80 is issued with fault
value 5
Condition:
P090=1 or P091=1 (communication board installed)
1
PNU=396Hex; Type=O2; Scaling: 1Hex
P927 Parameter Access 0 to 31 - 3/ BR
6 3/ BR
* Release of interfaces for the parameterization.
This parameter performs the same function as P053.
Parameter P053 can always be modified.
1
PNU=39FHex; Type=O2; Scaling: 1Hex
P928 Src Base/Reserve 0 to 6005 - 3/ BR
1005 3/ BR
* Source of the switching command 'base / reserve settings' (control word 2,
bit 30)
This parameter performs the same function as P590.
1
PNU=3A0Hex; Type=L2; Scaling: 1Hex
Display of the faults which have occurred at the last trips. Each fault
number has a fault value and a fault time assigned to it (see Chapter 7 for
details of fault numbers and fault values). The relationship between the
responsible parameters is shown in the diagram below.
The fault numbers for the last (8 max.) faults are stored under the indices of
parameter r947. The fault number for the current (not yet reset) trip is
indicated by r947.001, the fault number for the last reset fault is indicated
by index 9, the fault number of the last-but-one reset fault is indicated by
index 17, etc. The entry "0" here means that no previous fault has occurred.
In contrast to the converter (SIMOVERT Master Drive FC, VC, SC), in the
case of the rectifier/regenerating unit only one fault can occur for each trip,
therefore the only significant indices are 1, 9, 17, 25, 33, 41, 49 and 57.
A fault value in the appropriate index of parameter r949 is assigned to
every fault number. This provides more detailed information on the type of
fault.
Apart from this, for each trip, the fault time which is the actual value of the
operating hours counter (r013) is stored in parameter r748. The data for the
current (not yet reset) trip is present as "day", "hours" and "seconds" in
indices 1 to 3. The data for the already reset, previous trips is present in
groups of 3 elements on the following indices.
Plain text describing the fault numbers is available under the corresponding
index of parameter r951.
If the electronics supply voltage fails, all fault numbers are saved, but only
those fault values and fault times relating to the last trip are stored. After
the supply voltage has been restored, the other indices have the value "0".
1
PNU=3B3Hex; Type=O2; Scaling: 1Hex
r949 Fault Value 64 2/ BR
Fault values of the faults; allows a more detailed diagnosis at several faults.
The fault values are saved in the same indices as the related fault numbers
(r947) - see parameter P947.
1
PNU=3B5Hex; Type=O2; Scaling: 1Hex
1
PNU=3B7Hex; Type=O2; Scaling: 1Hex
P952 # of Faults 0 to 8 - 2/ BR
0 2/ BR
Number of faults stored in the fault memory (max. 8).
If the parameter is set to '0', the diagnosis memory (r748 - trip times, r947 -
fault number, r949 fault value) is cleared.
1
PNU=3B8Hex; Type=O2; Scaling: 1Hex
r953 Warning Param 1 - 3/ BR
Warning Parameter 1
If a warning (numbers 1 to 16) is active, the related bar in the display is ON
16 14 12 10
15 13 11 9
8 6 4 2
7 5 3 1
1
PNU=3B9Hex; Type=V2;Scaling: 1Hex
r954 Warning Param 2 - 3/ BR
Warning Parameter 2
If a warning (numbers 17 to 32) is active, the related bar in the display is
ON
32 30 28 26
31 29 27 25
24 22 20 18
23 21 19 17
1
PNU=3BAHex; Type=V2;Scaling: 1Hex
r955 Warning Param 3 - 3/ BR
Warning Parameter 3
If a warning (numbers 33 to 48) is active, the related segment in the display
is ON
48 46 44 42
47 45 43 41
40 38 36 34
39 37 35 33
1
PNU=3BBHex; Type=V2;Scaling: 1Hex
r956 Warning Param 4 - 3/ BR
Warning Parameter 4
If a warning (numbers 49 to 64) is active, the related segment in the display
is ON
64 62 60 58
63 61 59 57
56 54 52 50
55 53 51 49
1
PNU=3BCHex; Type=V2;Scaling: 1Hex
80 78 76 74
79 77 75 73
72 70 68 66
71 69 67 65
1
PNU=3BDHex; Type=V2;Scaling: 1Hex
r958 Warning Param 6 - 3/ BR
96 94 92 90
95 93 91 89
88 86 84 82
87 85 83 81
1
PNU=3BEHex; Type=V2;Scaling: 1Hex
r959 Warning Param 7 - 3/ BR
1
PNU=3BFHex; Type=V2;Scaling: 1Hex
r960 Warning Param 8 - 3/ BR
1
PNU=3C0Hex; Type=V2;Scaling: 1Hex
r967 Control Word 1 - 2/ BR
Display parameter of control word 1 (bit 0-15)
Identical with r550 (control word 1)
1
PNU=3C7Hex; Type=V2;Scaling: 1Hex
r968 Status Word 1 - 2/ BR
Display parameter of status word 1 (bit 0-15)
Identical with r552 (status word 1)
1
PNU=3C8Hex; Type=V2;Scaling: 1Hex
P970 Factory Settings 0 to 1 - 3/ B
1 3/ B
* Parameter reset to factory settings
0: Parameter reset: all parameters are reset to their original values Param.Reset
(factory settings). After this the parameter is reset to '1'.
1: no parameter reset
Return
Note: This function can also be selected via P052=1.
1
PNU=3CAHex; Type=O2; Scaling: 1Hex
1
PNU=3CBHex; Type=O2; Scaling: 1Hex
r980 PNU-Lst. 1 avail 116 3/ BR
1
PNU=3D4Hex; Type=O2; Scaling: 1Hex
r981 PNU-Lst. 2 avail 116 3/ BR
See r980.
1
PNU=3D5Hex; Type=O2; Scaling: 1Hex
r990 PNU-Lst.1 chnged 116 3/ BR
1
PNU=3DEHex; Type=O2; Scaling: 1Hex
r991 PNU-Lst.2 chnged 116 3/ BR
See r990.
1
PNU=3DFHex; Type=O2; Scaling: 1Hex
6 Operator control
The rectifier/regenerating unit can be controlled via:
the PMU (Parameterization Unit) on the CUR module
the control terminal strip on the CUR (Section 3.3 “Control terminal strip“)
the OP1 operator control panel (Section 9.4 “Options/Operator control“)
the SST1 serial interface (RS485 and RS232) on PMU-X300
the optional SST2 serial interface (RS485) for peer-to-peer coupling
Operator control using the PMU (see diagram below) is described in this section.
Seven-segment displays
Reversing key
On key
Raise key
X300
6.2 Displays
Tables 6.2 and 6.3 below give an overview of the displays that can be shown on the PMU:
Basic converter
Setting
parameters Technology board
NOTE
The parameters are described in Chapter 5 and the fault and alarm messages are described in Chapter 7.
Once the electronics supply voltage has been switched on, either the PMU operating display shows the current
operating state of the rectifier/regenerating unit (e.g. o009) or a fault or alarm message is displayed (e.g. F060).
The operating states are described in Section 5.1 and the fault and alarm messages are described in Sections
7.1 and 7.2.
As described in Section 6.3 (Figures 6.2 and 6.3), it is possible to change over from one display level to another.
By pressing <P>, it is possible to change from the status display (e.g. o009) to the parameter number level in
which the separate parameters can be selected via <raise> or <lower>. The selected access level (P051) and
the operating state (r000, r001) determine here which parameters are displayed. All parameters are not always
visible (see Chapter 5/overview of the abbreviations/footnotes 5 to 8)!
Pressing <P> again switches to the index level for indexed parameters (see Section 4.1.2) but directly to the
parameter value level for all other parameters and the index or the value can be modified via <raise> and
<lower>. The same conditions apply for changing a parameter value as were described for the parameter
number, i.e. a parameter value can only be modified under an appropriate access level and an appropriate
operating state.
If the 4 characters of the seven-segment display are insufficient for displaying a parameter value, only 4 figures
will be displayed initially (see Figure 6.4). The presence of further figures to the right or left of this "window" is
indicated by flashing of the left-hand or right-hand figure. If <P>+<lower> or <P>+<raise> are pressed
simultaneously, this "window" can be moved to view the parameter value.
By pressing <P> again, it is possible to switch back to the parameter number level..
6.3 Structure
Ready-to-switch-on
Operating display
P
Parameter number level
P P
Fast changeover P P P Fast changeover
+ +
+ + +
P P P
Parameter no
indexed
yes
Index level
Highest
index
P P P
P P P
Return to parameter
After
delay
time
Fault Display before Alarm
fault/alarm
P P P P Alarm P Alarm P
+ + cause or cause or
Fault Fault removed removed
acknowledged acknowledged
with a fault or or
Fault Fault
not
condition
not
acknowledged acknowledged
Figure 6.3 Operator control structure of the PMU for alarms and faults
Handling of fault and alarm messages (reset, move into the "background" in order to parameterize) is described
in Chapter 7 in detail.
P
+
P
+
NOTE
A current fault message or alarm can be "moved into the background" by pressing the P + keys on the PMU
simultaneously, in order to parameterize or to read the fault value via r949.001. Via the optional operator panel
OP1, in spite of an active fault message or alarm it is still possible to parameterize. If no key is pressed on the
PMU for 30 s, the fault message which was moved into the background or active alarm appears automatically
on the PMU. The message can be brought back into the foreground by simultaneously pressing the P + keys
on the PMU at the parameter number level..
For detailed information on the organization of the fault memory, see r947 in Section 5.16.
If a fault message is not acknowledged before the electronics power supply is switched off, this fault message
will appear again the next time the power supply is switched on. The unit will not start up unless this message is
acknowledged (except if auto restart has been selected; see under P366 and Section 4.3.10.1).
F034 Par PwrSectF 1 Current asymmetry (overcurrent or - One of the thyristors is not firing
undercurrent in the parallel power - Different current ripple in the
Fault in power sections connected in
section compared with the current rectifier/regenerating unit and
parallel
in the rectifier/regenerating unit) parallel power section due to
different commutating reactors
At least one parallel power section is
- Cable connection between the
connected, has been selected with
rectifier/regenerating unit and a
parameter P076 and reports the fault
parallel power section is
message "Current asymmetry between
interrupted or faulted
rectifier/regenerating unit and parallel
power section".
F035 Ext Fault 1 - - - There is an "External fault 1"
signal at the selected binary input
External fault 1
(P575/source for "Ext. fault 1")
- The line to the corresponding
A parameter-programmable fault input has
binary input is interrupted.
become active.
F036 Ext Fault 2 - - - There is an "External fault 2"
signal at the selected binary input
External fault 2
(P586/source for "Ext. fault 2")
- The line to the corresponding
Active in the "RUN“ when the pre-charging
binary input is interrupted..
time (P329) + 3s (200 ms for SW<3.0) has
elapsed.
The warning message appears periodically as A=Alarm/Warning and a three-digit in the display of the PMU A
warning cannot be acknowledged. It extinguishes automatically when the cause of the warning is eliminated.
Several messages may occur at the same time, in which case they appear one after the other in the display
If the rectifier/regenerating unit is operated with the OP1 operator panel, the warning appears in the bottom line
of the display. The red LED starts blinking first (see the operating instructions for the OP1)
8 Maintenance
WARNING
The rectifier/regenerating units are operated with high voltages.
All work on the unit must be carried out in agreement with the national electrical regulations
(in Germany: VBG 4).
Maintenance and repair work must only be carried out by qualified personnel.
Use must only be made of the spare parts approved by the manufacturer.
It is imperative to observe the prescribed maintenance intervals and the repair and
replacement instructions.
As the result of the dc link capacitors in the connected SIMOVERT Master Drives, the unit
still contains a hazardous voltage up to 5 min. after isolation (power terminal and electronic
power supply). This is why it is only permitted to open the unit after observing an
appropriate waiting time.
The power and control terminals may still be live even in the event of motor standstill.
Despite disconnecting the power terminals from the supply, terminal X19 may still be live
due to the external fan supply.
If work on the activated unit is necessary:
do not touch any live parts.
use only proper measuring equipment and protective work clothing.
stand or sit on an unearthed and isolated surface that does justice to ESD requirements.
Non-observance of warning notices can result in death, severe personal injury or
considerable property damage.
You should know the order and factory numbers of your unit when consulting the service department. You will
find these numbers and other important data on the rating plate of the unit.
WARNING
The fan must only be replaced by qualified personnel.
As the result of the dc link capacitors in the connected SIMOVERT Master
Drives, the unit still contains a hazardous voltage up to 5 min. after isolation.
Non-observance of warning notices can result in death, severe personal injury or
considerable property damage.
Size C
X20
The fan is located on the underside of the unit
Size E
X29
The fan is located on the right underside of the unit.
Fan E1
Figure 8.2 Fan (AC 230V) for size E
Size H
M8 M8
The fan is located in the fan box on the top of the unit.
Unplug X20.
Fan E1
Undo both M8 (SW 13) fixing screws. X20
Loosen the two M4 fixing screws and swing the plastic
cover out sideways..
Pull the fan box out of the unit forwards as far as the
M4
stop.
Then lift it up over the stop (at the back) and remove it
completely from the unit. Figure 8.3 Fan (AC 230V) for size H
Size K
M8
The two fans are located in the fan box on the top of the
unit.
Unplug X20.
Undo both M8 (SW 13) fixing screws. Fan E1 Fan E2
Pull the fan box out of the unit forwards.
Installation is carried out in reverse order.
X20
WARNING
The fan box weighs approx. 16 kg for size H, and approx. 32 kg for size K. This must be
taken into account when removing the fan box.
Non-observance of warning notices can result in severe personal injury or considerable
property damage.
WARNING
Modules must only be replaced by qualified persons.
Modules must not be removed or inserted under a live voltage.
Non-observance of warning notices can result in death, severe personal injury or
considerable property damage.
CAUTION
The modules contain electrostatically sensitive devices. You must discharge your own body
before touching an electronic module. This is best done by touching a conductive earthed
object (e.g. a bare metal part of the control cabinet) directly beforehand.
Assigning the "Start-up" parameters for the CUR option module (A10)
F060
P070 = WARNING
Initialization is mandatory.
Specify the ID number of the MLFB in P070 of the
rectifier/regenerating unit (rating plate on the unit) as per
MLFB table Section 4.3.9.2.
P and Lower key Change back to fault display and acknowledge F060
P-key
See Section
4.2.2 or 4.2.3
WARNING
Replacing firing-circuit module A23
Carry out circuit identification after replacing the A23 (see Chapter 4).
Sizes H and K
The earth connection must be restored by tightening the screws marked with an earthing
sign on the electronics box (size H) or on the electronics slide-in unit (size K).
the front cover
Release the snaps on the front cover
Open-up the front cover
Withdraw connector X108 on the CUR
Snap catch
Carefully depress the latch upwards on the
inner side of the front cover using a PMU
screwdriver
Remove the PMU board
Install the new PMU board in the inverse
sequence. Figure 8.6 Rear side of the front cover with PMU board
Replacing the EPROM on the CUR module (upgrading to a new software version)
On setup and during servicing work, the current parameter settings in the logbook in Chapter 12 should be
saved For information on reading out the parameters changed from the factory settings easily, see Section
4.3.9.3 (saving the parameter values using SIMOVIS) and Section 4.3.9.8 (displaying modified parameters). It
should be checked that these entries are up-to-date before the EPROM is replaced because when the
electronics supply voltage is switched on again, the function "generate factory settings" is carried out
automatically (see Section 4.3.9.1). Then only the values of parameters P070 and P077 are retained.
WARNING
The EPROM must only be replaced by qualified persons. The EPROM must
not be removed or inserted under a live voltage.
Non-observance of warning notices can result in death, severe personal injury
or considerable property damage.
CAUTION
The modules contain electrostatically sensitive devices. You must discharge your own
body before touching an electronic module. This is best done by touching a conductive
earthed object (e.g. a bare metal part of the control cabinet) directly beforehand.
The thyristor modules are secured with self-tapping screws. When replacing the thyristor modules, it is
imperative to use original-length screws with locking elements to secure them.
Also use original-length screws when screwing the thyristor modules to the busbars.
8 8 13
2
13 8
7 7 7 7 12
G G G G G G G
K K K K K K K
12 7
5
Level B Level A
4
14 11 3
9 9 9
9
G G G
G 12
K
12 K
12 K
12 10 K
10
13 8
2
13 8 13 8 13 8
Front thyristor block, level A (weight of a thyristor block, approx. 9.5 kg)
Swing out the two doors by removing two M4 slit Torx screws in each case.
Detach cable from the modules and the screen fixture.
Remove 2 M6 hexagon-head bolts and swing out electronics box as far as the stop.
Only on disassembling the central thyristor block, open 4 twisted cables and detach cable for the two
thermistors that are only located on the central thyristor block.
Unplug the gate and cathode cables (G, K) .
Remove 3 M8 hexagon-head bolts
Loosen the two M8 hexagon-head screws , push rail approx. 150 mm upwards and swing the thyristor
block out forwards.
Loosen M6 nut 11 and pull the thyristor block out upwards at an angle.
Rear thyristor block, level B (weight of a thyristor block, approx. 9.5 kg)
Unplug the gate and cathode cables(G, K) 12.
Remove 3 M8 hexagon-head bolts 13.
Loosen M6 nut 14 and pull the thyristor block out upwards at an angle.
3
10
10
Level B Level A
GK GK GK GK GK GK 12 8
8 15
15
9
9 3
16 11
5
5
5
13 7
4 6 13 4
14 6
7
14 7 5
9 Options
NOTE
Only one of each option board type may inserted in the electronics box.
TB (technology boards, e.g. T300) must always be inserted at slot 2.
Option Description
OP1 User-friendly operator control panel with plain text
display
Order No.: 6SE7090-0XX84-2FF0
Fault
Table 9.5 Operator control options Run
1 2 3
0 +/- Reset
Option Description
Busbar option Size E For interconnecting the rectifier and regenerative bridges in operation without
autotransformer
(see Chapter 2, Figure 2.6)
Front door, bottom and Increases degree of protection to IP20
cover plates, and PC
covers for Size E
EMC screened housing For screened cables
Three different versions of this module (short designation PTP1, item number C98043-A1690-L1, equipment
identifier A2) can be ordered. The order numbers (MLFB) for these versions are:
Versions 1 and 2 require a CUR control electronics module of hardware version 06 or higher (indicated on the
fourth number block of the item number on the module: C98043-A1680-L1-06, C98043-A1680-L1-07, ...) and
software version 3.0 or higher (see the label on the EPROM, fourth number block must be 30 or higher: V98113-
A1800-A001-30, V98113-A1800-A001-31, ... The software version can also be read from parameter r720.01.
The contents must be 3.0 or greater).
9.6.2 Installation
À
Undo the fixing screws of the CUR (A10) above and below the
removal handles . Á
Remove the module carefully from the electronics box using the A10
handles . CUR
Version 3: The PTP1 and EPROM are already fitted to the CUR. X101
X102 X115
Slide CUR module (A10) with PTP1 (A2) into the electronics box A2
carefully along the guide rails as far as the stop. X117
X104 X116
Screw the module into position with the fixing screws above and
below the removal handles .
Á
À Â
See circuit diagram in Section 3.5 "Single-line diagrams with suggested circuit arrangements".
The bus termination resistors required for peer-to-peer mode are installed on the module:
150 between terminal X117-1 and terminal X117-2
390 from terminal X117-1 to +5V supply
390 from terminal X117-2 to ground
9.6.4 Parameterization
The following parameters influence the function of the SST2 interface for the basic unit (for details see Section
5.12):
P681 (i001 to i005) Selection of process data for transmission
P684.i003 Baudrate
P686.i003 Number of net data words for peer-to-peer link
P687.i003 Telegram failure time
P688 Selection of the protocol
Parameterization for "12-pulse mode" see Section 3.8.3.
9.7 SIMOVIS
WARNING
Only qualified personnel who are familiar with the SIMOVIS operating
instructions and with the operating instructions of the connected devices and
their safety instructions are permitted to intervene at the drive using the PC.
Incorrect use of the software can result in death, severe personal injury or
considerable property damage.
What is SIMOVIS?
SIMOVIS is a program that runs on standard PCs for the setup and diagnostics of converters.
The connection to this unit is implemented via the RS485 interface and USS protocol.
If your PC does not have an RS485 interface, you have to connect an RS232/RS485 interface converter to the
COM1 or COM2 RS 232 interface.
An interface converter of this type is supplied under the order number 6SX7005-0AA00.
SIMOVIS functions
Menu-driven setting up using the PC: all parameters can be set that are required for operation.
Setting and monitoring all parameters of the unit using graphical methods.
Evaluation of faults and alarms: Overview of faults and alarms for all equipment connected to the bus.
SIMOVIS is supplied with every unit, on diskette, in the diskette pocket at the back of the manual.
The installation and operating instructions for the software is supplied in the form of a Windows WRITE file and
as an ASCII text file on the installation disks:
If WINDOWS (Version 3.1 upwards) is installed on your PC, you can load ANLEITNG.WRI into MS-WRITE and
print it out (7 pages).
In order to accommodate the different number of lines per page for different printers, page divisions were
omitted.
Please note that an ASCII character set is active on a laser printer (e.g. PC-8) ; and that a printer with endless
paper is set to "Skip over perforation".
10 Spare-parts
For rectifier/regenerating units sizes C to K
12 Logbook
The logbook must be kept up-to-date by the operating personnel.
All service and maintenance work carried out on the rectifier/regenerating unit should be entered briefly in
keywords into the logbook.
Continuous entries are important for maintenance and could be significant when it comes to warranty claims.
Similarly, in the event of software upgrading, it is important that a record of the parameter settings is available,
because during this procedure all values are reset to their original factory settings.
Start-up settings
Start-up settings
change
13 Environmental Compatibility
Environmental aspects during development
The number of parts has been reduced substantially by the use of highly integrated components and by a
modular structure of the complete converter series. This reduces energy consumption during production.
Particular attention was paid to reducing volume, mass and type diversity of the metal and plastic parts.
PP: Hinge
Insulating plate
Handle
Bus retrofit
PC: Size E:
Protection against accidental contact
IP20 enclosure
Insulation of customer connections
Plastic part of fan box
On all essential parts, flame retardants containing halogen and insulating material containing silicone have been
substituted by materials that are devoid of noxious substances.
Environmental compatibility was an important criterion in the selection of externally source items.
Externally sourced items are mainly transported in returnable packaging. The packaging material itself is
recyclable, consisting mainly of cardboard.
Except for the hot-dip-galvanized enclosure for size E, H and K, no special surface coatings are used.
Production is emission-free.
The unit can be dismantled into recyclable mechanical components by means of easily removable screw and
snap joints.
The PC boards can be disposed of thermally. The number of components containing hazardous substances is
only slight.
The plastic parts are marked in conformity with DIN 54840 and bear the recycling symbol.
14 Technical Data
In the event of conditions of use other than those listed in this chapter, please contact your local Siemens branch
or national subsidiary.
The units can also be operated in load class II. The permissible values must be taken from the following tables.
I
(A)
Load class ΙΙ
136%
Load class Ι
100%
91%
60s 240s
t/(s)
Parallel units (-1AD0) of size K for connecting in parallel have the same technical data as the corresponding
"basic units" (-1AA0). Please note the unit correspondence and notes of Section 3.7!
The permissible output current in parallel mode is reduced (due to current division between the power sections)
by 10 % as compared to the sum of the rated currents of the separate power sections.
Parallel units (-1AD0) of size K for connecting in parallel have the same technical data as the corresponding
"basic units" (-1AA0). Please note the unit correspondence and notes of Section 3.7!
The permissible output current in parallel mode is reduced (due to current division between the power sections)
by 10 % as compared to the sum of the rated currents of the separate power sections.
Parallel units (-1AD0) of size K for connecting in parallel have the same technical data as the corresponding
"basic units" (-1AA0). Please note the unit correspondence and notes of Section 3.7!
The permissible output current in parallel mode is reduced (due to current division between the power sections)
by 10 % as compared to the sum of the rated currents of the separate power sections.
100
90
80
75
70
60
Coolant temperature
in °C
10 20 30 40 50
100 100
90 90
80 80
70 70
60 60
Figure 14.3 Maximum values for rated current and rated voltage depending on installation altitude
DIN VDE 0110 Part 1 and 2 Isolation coordination for electrical equipment in low-voltage installations
A01.89
DIN VDE 0160 E04.91 Equipping power installations with electronic equipment
DIN VDE 0298 Use of cables and insulated cables for power installations:
Part 2 A11.79 Recommended values for the current carrying capacity of cables with rated
voltages U0 / U to 18/30 kV
Part 4 A02.80 Recommended values for the current carrying capacity of cables
DIN VDE 0470 Part 1 A12.92 Types of protection, shock, foreign body and water protection for electrical
equipment (EN 60529: 1991)
DIN VDE 0558 Part1 A07.87 Semiconductor converters: general regulations and special regulations for
line-commutated converters
DIN 41494 Part 5 A9.80 Equipment practice for electronic facilities; subracks and modules
DIN 41651 Part 1 A9.89 Connectors for printed circuits for connecting ribbon cables with round
conductors; indirect insertion, grid dimension 2.54 mm
Sources
DIN standards and foreign standards: Beuth-Verlag GmbH
Burggrafenstraße 6
10787 Berlin
15 Index
To appear shortly
SIMOVIS
Disk 2
09.97
The following versions have appeared so far: Version Internal Part number
A C98130-A1234-A1-01-7647
B C98130-A1234-A1-02-7647
C C98130-A1234-A1-03-7647
E C98130-A1234-A1-05-7647
F C98130-A1234-A1-06-7647
Siemens AG 6SE7087-6AK85-1AA0
Rectifier/Regenerating Unit Operating Instructions