Manual IHM XINJE de Conectividade Com PLC Diversas Marcas
Manual IHM XINJE de Conectividade Com PLC Diversas Marcas
Manual IHM XINJE de Conectividade Com PLC Diversas Marcas
i
CATALOG
1 SERIAL PORT OF HMI .................................................................................................................... 1
ii
2.8 Siemens S7-300/400 series PLC........................................................................................... 32
2.8.1 Model ........................................................................................................................... 32
2.8.2 Parameters .................................................................................................................. 32
2.8.3 Cable making ............................................................................................................... 34
2.8.4 Device address ............................................................................................................ 35
2.9 OMRON SYSMAC series PLC............................................................................................ 36
2.9.1 Device model ............................................................................................................... 36
2.9.2 Parameters .................................................................................................................. 37
2.9.3 Cable making ............................................................................................................... 38
2.9.4 Device address ............................................................................................................ 39
2.10 Koyo S series PLC ............................................................................................................... 41
2.10.1 Device model ............................................................................................................. 41
2.10.2 Parameters ................................................................................................................ 42
2.10.3 Cable making ............................................................................................................. 43
2.10.4 Device address .......................................................................................................... 44
2.11 Koyo DL series PLC ............................................................................................................. 45
2.11.1 Device type ................................................................................................................ 45
2.11.2 Parameters................................................................................................................. 45
2.11.3 Cable making ............................................................................................................. 45
2.11.4 Device address .......................................................................................................... 46
2.12 Delta DVP series PLC.......................................................................................................... 47
2.12.1Model .......................................................................................................................... 47
2.12.2 Parameters ................................................................................................................ 47
2.12.3 Cable making ............................................................................................................. 47
2.12.4 Device address .......................................................................................................... 48
2.13 LG Master-K(CPU Direct) series PLC ................................................................................. 49
2.13.1 Device model ............................................................................................................. 49
2.13.2 Parameters ................................................................................................................ 49
2.13.3 Cable making ............................................................................................................. 50
2.13.4 Device address .......................................................................................................... 50
2.14 LG Master-K(Cnet) series PLC ............................................................................................ 52
2.14.1 Device model ............................................................................................................. 52
2.14.2 Parameters ................................................................................................................ 52
2.14.3 Cable making ............................................................................................................. 53
2.14.4 Device address .......................................................................................................... 54
2.15 LG Glofa(Cnet) series PLC .................................................................................................. 55
2.15.1 Device model ............................................................................................................. 55
2.15.2 Parameters ................................................................................................................ 55
2.15.3 Cable making ............................................................................................................. 57
2.15.4 Device address .......................................................................................................... 58
2.16 LG XGT(CPU Direct) series PLC......................................................................................... 60
2.16.1 Device model ............................................................................................................. 60
2.16.2 Parameters ................................................................................................................ 60
2.16.3 Cable making ............................................................................................................. 60
iii
2.16.4 Device address .......................................................................................................... 61
2.17 Matsushita MEWNET FP series PLC .................................................................................. 62
2.17.1Device model .............................................................................................................. 62
2.17.2 Parameters ................................................................................................................ 63
2.17.3 Cable making ............................................................................................................. 64
2.17.4 Device address .......................................................................................................... 65
2.18 Schneider PLC .................................................................................................................. 67
2.18.1Device model .............................................................................................................. 67
2.18.2 Parameters ................................................................................................................ 67
2.18.3 Cable making ............................................................................................................. 69
2.18.4 Device address .......................................................................................................... 69
2.19 Fatek FB series PLC ............................................................................................................ 70
2.19.1 Device model ............................................................................................................. 70
2.19.2 Parameters ................................................................................................................ 70
2.19.3 Cable making ............................................................................................................. 71
2.19.4 Device address .......................................................................................................... 72
2.20 Vigor VIGOR PLC ................................................................................................................ 73
2.20.1 Device model ............................................................................................................. 73
2.20.2 Parameters ................................................................................................................ 73
2.20.3 Cable making ............................................................................................................. 73
2.20.4 Device address .......................................................................................................... 75
2.21 Fuji SPB series PLC ............................................................................................................ 76
2.21.1 Device model ............................................................................................................. 76
2.21.2 Parameters ................................................................................................................ 76
2.21.3 Cable making ............................................................................................................. 76
2.21.4 Device address .......................................................................................................... 77
2.22 Keyence KV series PLC....................................................................................................... 79
2.22.1Device model .............................................................................................................. 79
2.22.2 Parameters ................................................................................................................ 79
2.22.3 Cable making ............................................................................................................. 79
2.22.4 Device address .......................................................................................................... 81
2.23 Emerson EC20 series PLC .................................................................................................. 82
2.23.1Device model .............................................................................................................. 82
2.23.2 Parameters ................................................................................................................ 82
2.23.3 Cable making ............................................................................................................. 82
2.23.4 Device address .......................................................................................................... 83
2.24 OEMax NX7 series PLC ...................................................................................................... 84
2.24.1 Device model ............................................................................................................. 84
2.24.2 Device address .......................................................................................................... 84
2.24.3 Cable making ............................................................................................................. 84
2.24.4 Device address .......................................................................................................... 86
2.25 Bosch Rexroth IndraControl L40 series PLC....................................................................... 87
2.25.1 Device model ............................................................................................................. 87
2.25.2 Parameters ................................................................................................................ 87
iv
2.25.3 Cable making ............................................................................................................. 87
2.25.4 Device address .......................................................................................................... 88
2.26 OPTO 22 SNAP series PLC ................................................................................................ 89
2.26.1 Device model ............................................................................................................. 89
2.26.2 Parameters ................................................................................................................ 89
2.26.3 Cable making ............................................................................................................. 89
2.26.4 Device address .......................................................................................................... 90
2.27 SAIA-Burgess PCD series PLC ........................................................................................... 91
2.27.1 Device model ............................................................................................................. 91
2.27.2 Parameters ................................................................................................................ 92
2.27.3 Cable making ............................................................................................................. 92
2.27.4 Device address .......................................................................................................... 96
2.28 Allen-Bradley series PLC ..................................................................................................... 96
2.28.1 Device model ............................................................................................................. 96
2.28.2 Parameters ................................................................................................................ 96
2.28.3 Cable making ............................................................................................................. 99
2.28.4 Device address .......................................................................................................... 99
2.29 Xinje V5 series inverter ...................................................................................................... 101
2.29.1 Device model ........................................................................................................... 101
2.29.2 Parameters .............................................................................................................. 101
2.29.3 Cable making ........................................................................................................... 102
2.30 SHIMADEN ........................................................................................................................ 103
2.30.1 Device model ........................................................................................................... 103
2.30.2 Parameters .............................................................................................................. 103
2.30.3 Cable making ........................................................................................................... 103
2.30.4 Device address ........................................................................................................ 104
2.31 Modbus RTU (panel is Master) .......................................................................................... 105
2.31.1 Device model ........................................................................................................... 105
2.31.2 Parameters .............................................................................................................. 105
2.31.3 Cable making ........................................................................................................... 105
2.31.4 Device address ........................................................................................................ 106
2.32 Modbus ASCII (Panel is Master)........................................................................................ 107
2.32.1Device model ............................................................................................................ 107
2.32.2 Parameters .............................................................................................................. 107
2.32.3 Cable making ........................................................................................................... 107
2.32.4 Device address ........................................................................................................ 108
2.33 Modbus slave (panel is Slave) ........................................................................................... 109
2.33.1Device model ............................................................................................................ 109
2.33.2 Parameters .............................................................................................................. 109
2.33.3 Cable making ........................................................................................................... 109
2.33.4 Device address .........................................................................................................110
2.34 ABB PLC ............................................................................................................................. 111
2.34.1Device model ............................................................................................................. 111
2.34.2 Parameters ............................................................................................................... 111
v
2.34.3 Cable making ............................................................................................................112
2.34.4 Device address .........................................................................................................113
2.35 IDEC ....................................................................................................................................114
2.35.1 Device type ...............................................................................................................114
2.35.2 Parameters ...............................................................................................................114
2.35.3 Cable making ............................................................................................................114
2.35.4 Device address .........................................................................................................115
2.36 TAIAN ..................................................................................................................................116
2.36.1 Device type ...............................................................................................................116
2.36.2 Parameters ...............................................................................................................117
2.36.3 Cable making ............................................................................................................117
2.36.4 Device address .........................................................................................................118
2.37 YuDian AI ............................................................................................................................119
2.37.1 Device address .........................................................................................................119
2.37.2 Parameters ...............................................................................................................119
2.37.3 Cable making ............................................................................................................119
2.37.4 Device address ........................................................................................................ 120
2.38 Inovance PLC..................................................................................................................... 121
2.38.1 Device type .............................................................................................................. 121
2.38.2 Parameter ................................................................................................................ 121
2.38.3 Cable making ........................................................................................................... 122
2.38.4 Device address ........................................................................................................ 122
2.39 HaiWell PLC .................................................................................................................... 124
2.39.1 Device type .............................................................................................................. 124
2.39.2 Parameters .............................................................................................................. 124
2.39.3 Cable making ........................................................................................................... 124
2.39.4 Device address ........................................................................................................ 125
2.40 Hollias PLC ...................................................................................................................... 126
2.40.1 Device type .............................................................................................................. 126
2.40.2 Parameters .............................................................................................................. 126
2.40.3 Cable making ........................................................................................................... 126
2.40.4 Device address ........................................................................................................ 127
2.41 Delta (temperature controller) ......................................................................................... 128
2.41.1 Device type .............................................................................................................. 128
2.41.2 Parameters .............................................................................................................. 128
2.41.3 Cable making ........................................................................................................... 128
2.41.4 Device address ........................................................................................................ 129
2.42 Siemens S7-1200 ............................................................................................................ 130
2.42.1 Device type .............................................................................................................. 130
2.42.2 Parameters .............................................................................................................. 130
2.42.3 Cable making ........................................................................................................... 135
2.42.4 Device address ........................................................................................................ 136
2.43 Mitsubishi FR series inverter ............................................................................................. 137
2.43.1 Device type .............................................................................................................. 137
vi
2.43.2 Parameters .............................................................................................................. 137
2.43.3 Cable making ........................................................................................................... 140
2.44 Sanken VM06 inverter ....................................................................................................... 141
2.44.1 Device type .............................................................................................................. 141
2.44.2 Parameters .............................................................................................................. 141
2.44.3 Cable making ........................................................................................................... 143
2.44.4 Device address ........................................................................................................ 143
2.45 XINJE XD/XE series .......................................................................................................... 145
2.45.1 Device type .............................................................................................................. 145
2.45.2 Parameters .............................................................................................................. 145
2.45.3 Cable making ........................................................................................................... 146
2.45.4 Device address ........................................................................................................ 147
2.46 LG XGB series PLC ........................................................................................................... 149
2.46.1 Device type .............................................................................................................. 149
2.46.2 Parameters .............................................................................................................. 149
2.46.3 Cable making ........................................................................................................... 153
2.46.4 Device address ........................................................................................................ 154
2.47 Koyo Click series ............................................................................................................... 155
2.47.1 Device type .............................................................................................................. 155
2.47.2 Parameter setting .................................................................................................... 155
2.47.3 Cable making ........................................................................................................... 156
2.47.4 Device address ........................................................................................................ 156
2.48 Mitsubishi Melsec protocol ................................................................................................. 157
2.48.1 Device type .............................................................................................................. 157
2.48.2 Parameter settings................................................................................................... 158
2.48.3 Cable making ........................................................................................................... 161
2.48.4 Device address ........................................................................................................ 162
2.49 Free type (panel is slave)................................................................................................... 162
2.49.1 Device type .............................................................................................................. 162
2.49.2 Parameter setting .................................................................................................... 163
2.49.3 Cable making ........................................................................................................... 165
2.49.4 Device address ........................................................................................................ 166
2.50 Modbus-TCP device .......................................................................................................... 166
2.50.1 Device type .............................................................................................................. 166
2.50.2 Parameter setting .................................................................................................... 166
2.50.3 Cable making ........................................................................................................... 172
2.50.4 Device address ........................................................................................................ 173
2.51 Mitsubishi FX5U series ...................................................................................................... 173
2.51.1 Device type .............................................................................................................. 173
2.51.2 Parameter setting .................................................................................................... 173
2.51.3 Cable making ........................................................................................................... 177
2.51.4 Device address ........................................................................................................ 178
2.52 Siemens S7-200 smart series............................................................................................ 179
2.52.1 Device type .............................................................................................................. 179
vii
2.52.2 Parameter setting .................................................................................................... 179
2.52.3 Cable making ........................................................................................................... 182
2.52.4 Device address ........................................................................................................ 184
2.53 Siemens S7-300 series ...................................................................................................... 185
2.53.1 Device type .............................................................................................................. 185
2.53.2 Parameter setting .................................................................................................... 185
2.53.3 Cable making ........................................................................................................... 188
2.53.4 Device address ........................................................................................................ 190
2.54 X-NET communication ....................................................................................................... 191
2.54.1 Device type .............................................................................................................. 191
2.54.2 HMI setting............................................................................................................... 191
2.54.3 XD series PLC setting (PLC hardware V3.2.2 and up) ........................................... 197
2.54.4 Cable making ........................................................................................................... 200
2.54.5 Device address ........................................................................................................ 202
2.55 Keyence KV5000 ............................................................................................................... 204
2.55.1 Device type .............................................................................................................. 204
2.55.2 Parameter setting .................................................................................................... 204
2.55.3 Cable making ........................................................................................................... 207
2.55.4 Device address ........................................................................................................ 208
2.56 LG XGT .............................................................................................................................. 209
2.56.1 Device type .............................................................................................................. 209
2.56.2 Parameter setting .................................................................................................... 209
2.56.3 Cable making ............................................................................................................211
2.56.4 Device address ........................................................................................................ 212
2.57 Haiwell ................................................................................................................................ 213
2.57.1 Device type .............................................................................................................. 213
2.57.2 Parameters .............................................................................................................. 213
2.57.3 Cable making ........................................................................................................... 215
2.57.4 Device address ........................................................................................................ 216
viii
1 Serial port of HMI
This chapter will introduce the serial port of HMI.
Download port:
Pin Name Explanation
1 NC Vacant
9 87 6 2 RXD RS232 receive
3 TXD RS232 send
4 A RS485 +
5 GND Ground
6 NC Vacant
5 4 3 2 1 7 B RS485 -
8 NC Vacant
9 NC Vacant
1
(b) For current project, please set it in the Touchwin software:
(1) Cut off the power of TP series HMI, connect pin5 and pin6 of TP download port.
(2) Power on the HMI, take away the connection cable, the download port will be in
communication mode.
Note: 1. if the HMI needs to download program, please restart the HMI.
2. Please connect the pin 5 and 6 directly.
2
1.2 PLC port
PLC port:
For real application, pelase refer to chapter 2 for cable making. Refer to chapter 1.1 for
Expand port:
Pin Definition Explanation
1 A RS485 +
9 87 6 2
3
4
5
6 B RS485 -
5 4 3 2 1 7
8
9
Note: only TH765-NT3/NU3 has this expand port.
1. choose expand port device
(1) Build a new project, click expand port, and choose the device
3
(2) For existed project, click File/setting/device/expand port to set the PLC model.
4
1.4 Ethernet port
RJ45 Ethernet port:
Pin Color Definitio Explanation
8 n
1 Orange
TXD+ Data send +
1 white
2 Orange TXD- Data send -
3 Green
RXD+ Data receive +
white
4 Blue - -
5 Blue
- -
white
6 Green RXD- Data receive -
7 Brown - -
5
white
8 Brown - -
Note: only TG765-ET/TG865-ET/TGA62-ET/TGC65-ET has Ethernet port.
1. Build a new project, choose TG model in the list.
2. Click next, choose net device. Set the IP address of TG series HMI.
6
3. Right click net device, build a new Ethernet device.
Note: this function support local area network, but not support wide area network
7
2 The connection of PLC and HMI
This chapter will introduce the connection between PLC and HMI.
Please don’t pull out or plug the cable when power on, the serial port may be damaged.
2.1.1Model
2.1.2 Parameters
HMI parameters:
Parameters Settings Choices for settings Item
PLC type FC series
Port RS232 RS232or RS485
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity Odd parity Odd/even/no parity
Baud rate 9600 4800/38400/9600/115200/19200/187500
Station No. 0 0~255
The default communication parameters of FC: 9600, 8, 1, odd parity, station No.0.
8
Fig1
(b) Connect to FC series PLC CPU (RS485 port)
Fig2
9
2.2 XINJE XC series PLC
2.2.1 Model
2.2.2 Parameters
HMI parameters:
Parameter Recommend settings Choices of settings Item
PLC type XC series FC/XC series
Port RS232 RS232 or RS485
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity Even parity Even/odd/no parity
Baud rate 19200 4800/38400/9600/115200/19200/187500
Station No. 1 0~255
10
2.2.3 Cable making
Fig1
Fig2
11
Fig3
Fig4
12
DX 0~52 Word Data register
DY 0~52 Word Data register
DS 0~1008 Word Data register
DM8XXX 0~496 Word Data register
DT 0~603 Word Data register
DC 0~619 Word Data register
ID 0~9999 Word//DWord Analog input
QD 0~9999 Word//DWord Analog output
13
2.3 Mitsubishi FXseries PLC
2.3.1Model
Connected Cable
Series CPU Port Device
module making
FX0N CPU direct Mitsubishi FX
RS422 Fig1
FX1N connection series PLC
FX2N RS232-BD RS232 Fig 2
Mitsubishi
FX1S RS485\422-B RS485 Fig 3
FXBD(232\485)
FX3U D RS422
FX
FX3G
CPU direct Mitsubishi FX
FX0 RS422 Fig 1
connection series PLC
FX1
CPU direct Mitsubishi FX
FX2 RS422 Fig 4
connection series PLC
2.3.2 Parameters
HMI settings:
Parameter Recommend Choices of settings Item
settings
PLC type FX series
Dat bit 7 7 or 8
Stop bit 1 1 or 2
Parity Even parity Even/odd/no parity
Baud rate 9600 4800/9600/19200/38400/56000/57600/11
5200/187500
Station No. 0 0~255
The default parameters of Mitsubishi FX series PLC: 9600, 7, 1, even, station No.0.
PLC settings:
14
2.3.3 Cable making
Fig1
Fig2
Fig3
15
(d) FX2 series PLC:
Fig4
16
2.4 Mitsubishi FX3U/G series PLC
2.4 .1 Model
FX3U Mitsubishi
FX CPU RS422 Fig 1
FX3G FX3U/G
2.4 .2 Parameters
HMI settings:
Parameter Recommended Choices of settings Notes
settings
PLC type Mitsubishi
FX3U/G series
Data bit 7
Stop bit 1
Parity Even parity
Baud rate 9600 4800/9600/19200/38400/56000/57600/115200/187500
Station 0
no.
The default parameters of Mitsubishi FX3U/G series PLC: 9600, 7, 1, even parity, station no.0
PLC settings:
17
2.4 .3 Cable making
18
S 0~999 Bit Stepper coil
T 0~255 Bit Timer
C 0~255 Bit Counter
C16 0~199 Word/DWord 16-bit counter
C32 200~255 DWord 32-bit counter
D 0~8255 Word/DWord Data register
T 0~255 Word/DWord Timer current value
X 0~177 Word/DWord Used as data register
Y 0~177 Word/DWord Used as data register
M 0~8255 Word/DWord Used as data register
S 0~999 Word/DWord Used as data register
19
2.5 Mitsubishi FX BD series PLC (RS232/485)
Note:
1. Do not hot plug the device!
2. The driver of 485-BD supports multi-station.
2.5.2 Parameters
HMI settings:
Paramete Recommend settings Choices of settings Notes
rs
PLC type Mitsubishi FX BD(232\485)
Data bit 7
Stop bit 1
Parity Even parity
Baud rate 9600 9600/19200/38400/56000/57600
/
115200/187500
Station 0 0~255
no.
The default paramreters of Mitsubishi FX BD (232/485): 9600, 7, 1, even parity, station no.0
PLC settings:
20
Note:
1. Please choose RS232 as H/W type when using 232-BD.
2. Please re-power on the PLC after changing the parameters.
Fig1
21
Fig2
22
2.6 Mitsubishi Q series PLC
2.6 .1 Model
MELSEC-Q series include the CPU unit of Q00, Q01, Q00U and so on. They can connect to the HMI
via programmable port or communication module (QJ71C24N).
Cable
Series CPU Connected module Port Device
making
Q00
CPU direct Mitsubishi Q
Q01 RS232 Fig 1
connection series
Q00U
Q00J,Q00,
Q
Q01,Q02H, RS232 Fig 2
Serial communication Mitsubishi Q
Q06H,Q12H,
module QJ71C24 series
Q25H,Q12PH, RS422 Fig 3
Q25PH
2.6.2 Parameters
HMI settings:
Parameter Recommend Choices of settings Item
setting
PLC type Q series
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity Odd parity Even/odd/no parity
Baud rate 19200 4800/9600/19200/38400/56000/57600/115200/187500
Station 0 0~255
No.
The default parameter of Q series PLC: 19200, 8, 1, odd parity, station No.0.
PLC settings:
1. Q01\Q00 PLC:
23
2.QJ71C24N serial port module
QJ71C24N can connect to CPU and communicate with other devices. Such as Q02CPU, the
settings are as the following:
PLC software version v8.26
(a) Double click PLC parameter, choose I/O assignment:
24
(d) Set the parameter as the following window:
(e) Click End button to finish the settings, then repower on the PLC.
25
For QJ71C24 module RS422, please set the parameter of CH2:
Fig1
26
(b) Q series PLC uses QJ71C24N module RS232:
Fig2
Fig3
27
Y 0~177 Word/DWord Data register
M 0~8255 Word/DWord Data register
S 0~999 Word/DWord Data register
28
2.7 Siemens S7-200 series PLC
2.7.1Model
S7-200 Siemens
Smart series CPU directly connect RS485 Fig1
smart S7-200
2.7.2 Parameters
HMI:
Parameters Recommend Choices of settings Item
settings
PLC type S7-200
Port RS485
Data bit 8
Stop 1
Parity Even parity
Baud rate 9600 9600/19200/187500
Station no. 2 Must use recommend
settings
The default communication parameters of Siemens S7-200 series PLC: 9600, 8, even parity,
station No.2.
PLC settings:
29
Notes:
1. Siemens PLC has 3 kinds of registers: 8-bitVB, 16-bit VW and 32-bit VD.
2. The space of registers are overlapped, the address of VW must be even numbers, for
example: VW0,VW2…., the address of VD must be the multiple of 4, such as VD0,VD4,
VD8…..
3.For Data block PSW single word → VW single word: as the high byte and low byte problem,
the received data maybe dislocated, please use register copy function.
4.For data block PSW single word → VD double words: as the unit is different, cannot trasfer
the data like this, please use register copy function.
Fig1
30
PLC address Range Data type Explanation
VB 0~4095 Byte variable byte data register
VW 0~4095 Word variable word data register
VD 0~4095 DWord variable double word data register
IB 0~15 Byte External input byte reflection register
IW 0~15 Word External input word reflection register
ID 0~15 DWord External input double words reflection
register
QB 0~15 Byte External output byte reflection register
QW 0~15 Word External output word reflection register
QD 0~15 DWord External output double words reflection
register
MB 0~31 Byte Internal auxiliary byte register
MW 0~31 Word Internal auxiliary word register
MD 0~31 DWord Internal auxiliary double words register
SMB 0~299 Byte Internal special auxiliary byte register
SMW 0~299 Word Internal special auxiliary word register
SMD 0~299 DWord Internal special auxiliary double words
register
SB 0~31 Byte Special auxiliary byte register
SW 0~31 Word Special auxiliary word register
SD 0~31 DWord Special auxiliary double words register
T 0~255 Word Register
C 0~255 Word Register
M 0~31 Bit Bit register
V 0~4095 Bit Variable register
I 0~15 Bit External input coil
Q 0~15 Bit External output coil
SM 0~299 Bit Special relay
S 0~31 Bit Sequence relay
T 0~255 Bit Timer
C 0~255 Bit Counter
31
2.8 Siemens S7-300/400 series PLC
2.8.1 Model
2.8.2 Parameters
HMI settings:
Parameter Recommend Choice of settings Note
settings
PLC type S7-300/400
Port RS485
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity Even parity Even/odd/no parity
Baud rate 19200 4800/38400/9600/115200/19200/187500
Station 2 Please use
no. recommend settings
The default parameters of Siemens S7-300\400: 19200, 8, even parity, station No.2.
PLC settings:
32
Communication notes for S7-300:
1. Siemens baud rate must set to 19200 kbps; don’t set the parameters of PG/PC adapter.
2. Don’t modify the “panel station no.” in the Touchwin software.
33
3. Cable: no need PG/PC adapter;
4. Please define the DB register in the PLC when testing the communication.
5. Please note that the port will be operated in PLC program by accident.
6. The default station No. of S7-300 is 2, please don’t modify it.
Example: MPI port of S7-300 connects to HMI, the PLC connects to SCADA software via
Ethernet module, PLC station no. is 8, module station no. is 3, HMI station no. is 0. The result is
that communication between SCADA and PLC will be cut off. Because the HMI cannot find
other devices and modules cannot be inserted in. please change the PLC station no. to 2.
These devices can form a loop:
34
SIEMENS PLC
S7-200/300/400
HMI 9-pin female port
PPI 9-pin male port
Pin Name Pin Name
4 AI 3 A
5 GND 8 B
7 BI 5 GND
Fig1
SIMATIC S7-300/400
PLC type Range Data type Explanation
I 0~9999 Byte/Word/DWord External input register
Q 0~9999 Byte/Word/DWord External output register
M 0~9999 Byte/Word/DWord Internal auxiliary register
DB0~DB20 0~9999 Byte/Word/DWord Data register
I 0~9999 Bit External input coil
Q 0~9999 Bit External output coil
M 0~9999 Bit Internal auxiliary relay
DB0~DB20 0~9999 Bit Internal auxiliary relay
35
2.9 OMRON SYSMAC series PLC
OMRON CPM1A, CQM1-CPU series CPU cannot support RS232. It can connect to the Touchwin
HMI via
CPM1-CIF01 adapter and modules including C500-LK203, C120-LK201-V1, C500-LK201-V1. The
PLC uses Hostlink protocol when communicating. Please change the PLC startup choice to
MONITOR RUN.
The PLC
Connected Communication device in
Series CPU Cable
module mode TouchWin
The PLC
Communication device in
Series CPU Connected module Cable
mode TouchWin
36
C C200HE
CPU direct connection
C200HX
C1000HF C500-LK203 (communication
module)
C120-LK201-V1(communication
RS232 Fig 1
module)
C500-LK201-V1(communication
C2000
module)
C500-LK203(communication Omron
module) CPM/CQM
CPM CPM2A
CPM2AE
CPU direct connection
CPM2AH-40CDR-A
CPM1H
CPM1A OMRON CIF01 (RS232) RS232 Fig 1
Communication adapter
CQM CQM1H-CPU21 CPU direct connection
CQM1-CPU OMRON CIF01 (RS232)
Communication adapter
2.9.2 Parameters
HMI:
The default parameters of OMRON CP/CJ/CS series PLC: 9600, 7, 2, even parity, station no.0.
The default parameters of OMRON CPM/CQM series PLC: 9600, 7, 2, even parity, station no.0.
37
2.9.3 Cable making
OMROM PLC
CPU CPM1-CIF01/C500-LK203
C120-LK201-V1/C500-LK203
HMI 9-pin female port RS232 9-pin male port
Fig1
Fig2
Note: If OMRON RS485 module CPIW-CIF11 uses 485-2 connection mode, turn OFF the SW1
switch on the module, turn ON SW2, 3, 5, 6. SW4 is selectable.
Fig3
38
Note: If OMRON RS485 module CP1W-CIF11 uses RS422 connection mode, turn OFF the
SW1~6 on the module.
39
CIO 0~9999 Word/DWor Register
d
D 0~99999 Word/DWor Register
d
H 0~9999 Word/DWor Register
d
W 0~9999 Word/DWor Register
d
A 0~9999 Word/DWor Register
d
T 0~9999 Word/DWor Register
d
C 0~9999 Word/DWor Register
d
40
2.10 Koyo S series PLC
Koyo KOSTA-S and Direct-Logic series PLC
(a) Kostac S series SH\SM\SN PLC (direct connect to the CPU module)
SH series SH-48RS
CPU
SM series SM24-T RS232 Fig1
SN series
Koyo S series
SU-6 RS232 Fig1
CPU
RS232 Fig1
SU-6B
RS422 Fig3
Note: Koyo SH-48RS doesn’t have Run, Stop switch, but only have one AMP port.
(b) Koyo Kostac S series SG-8, SU-5, SU-6, SR-21, SR-22… PLC (use communication module)
RS232 Fig 1
SG-8 G01-DM communication unit
RS422 Fig 3
SU-5 U01-DM communication unit
RS232 Fig 1 Koyo S series
SU-6 U01-DM communication unit
SR-21 E-02DM-R1 communication unit
RS422 Fig 3
SR-22
(c) Koyo Direct Logic series DL05, DL250…PLC (connect to CPU directly)
Series CPU Connected module Port Cable Device
DL05
DL105
DL230
Connect to RJ-11port(RS232) of CPU
DL240 RS232 Fig 2
Direct Logic Koyo S series
DL250
DL350
DL450
DL250 Connect to the port of CPU RS422 Fig 3
41
DL430 Connect to the port of CPU
DL440
RS232 Fig 2
DL450
DL350
Note: port2 of DL250CPU has RS232 and RS422; please indentify them when making the
cable.
2.10.2 Parameters
HMI:
Parameter Recommend settings Choices of settings Notes
PLC Koyo S series PLC
Port RS232 RS232 or RS422
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity Odd parity Even/odd/no parity
Baud rate 9600 4800/38400/9600/115200/19200/187500
Station no. 0 0~255
The default communication parameters of Koyo S series PLC: 9600, 8, 1, odd parity, station
no.0.
PLC:
42
Note: 1. Koyo K protocol cannot modify station no., the station no. is 0 in the HMI.
2. The register address starts from R2000.
Fig1
654 3 2 1
Fig2
RS422 connection:
43
Fig3
44
2.11 Koyo DL series PLC
Koyo Direct Logic series DL05, DL250 PLC (direct connect to CPU)
Series CPU Connected Port Cable Choose PLC type in
module Touchwin software
DL05
DL105 Connect to
DL230 CPU RJ-11 RS232 Fig 1
DL240 port
Direct
DL250 Koyo DL series
Logic
DL350
DL430 Connect to
RS422 Fig 2
DL440 CPU com port
DL450
Note: the port2 of DL250 has RS232 and RS422, please indentify the cable connection for them.
2.11.2 Parameters
HMI settings:
Parameter Recommend Choices of settings Note
s settings
PLC type Koyo DL series
Port RS232 RS232/RS422
Data bit 8 7/8
Stop bit 1 1/2
Parity Odd parity Even /odd /no parity
Baud rate 9600 4800/38400/9600/115200/19200/18750
0
Station no. 0 0-255
RS232 Connection:
45
Fig1
RS422 connection:
Fig2
46
2.12 Delta DVP series PLC
2.12.1Model
2.12.2 Parameters
HMI:
Parameters Recommend settings Choices of settings Notes
PLC type Delta DVP series
Port RS232 RS232 or RS485
Data bit 7 7 or 8
Stop bit 1 1 or 2
Parity Even parity Even/odd/no parity
Baud rate 9600 4800/38400/9600/115200/19200/187500
Station no. 1 0~255
The default communication parameters of Delta DVP series PLC: 9600, 7, 1, even parity, station
no.1.
Fig 1
47
(b) RS485 port on the CPU:
Fig2
48
2.13 LG Master-K(CPU Direct) series PLC
LG Master-K series PLC support CPU(RS232) and Cnet module communication mode. This
chapter will introduce CPU mode.
2.13.2 Parameters
HMI:
Parameters Recommend settings Choices of settings Notes
PLC type LG Master-K80/120 series
PLC
Port RS232 RS232
Dat bit 8 7 or 8
Stop bit 1 1 or 2
Parity No parity Even/odd/no parity
Baud rate 38400 4800/38400/9600/115200/19200/187500
Station no. 0 0~255
PLC:
49
2.13.3 Cable making
Fig1
50
TD 0~9999 Word/DWor Current value of timer
d
CD Word/DWor Current value of counter
0~9999
d
S 0~9999 Word/DWor Used as register
d
K 0~9999 Word/DWor Used as register
d
M 0~9999 Word/DWor Used as register
d
L 0~9999 Word/DWor Used as register
d
F 0~9999 Word/DWor Used as register
d
P 0~9999 Word/DWor Used as register
d
51
2.14 LG Master-K(Cnet) series PLC
LG Master-K80/120 series PLC Cnet communication module
LG Master-K series PLC support CPU(RS232) and Cnet expansion port communication mode. This
chapter will introduce Cnet mode.
Note:
1. For Master K-cnet communication, turn ON DIP switch 2, turn OFF DIP switch 1. For LG
Master KxxxS communication, keep the DIP switch to default settings.
2. LG Master KxxxS CPU only supports RS232 connection. Cnet communication module
supports RS232 and RS485 connection.
2.14.2 Parameters
HMI:
Parameters Recommend settings Choices of settings Notes
PLC type LG Master-K80/120 (Cnet) series PLC
Port RS232 RS232
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity Even parity Even/odd/no parity
Baud rate 9600 4800/38400/9600/115200
/19200/187500
Station no. 1 0~255
The default parameters of LG Master K-cnet : 9600, 8, 1, even parity, station no.1.
PLC:
Notes:
1. Turn on the switch BUILT-IN CNET on the PLC.
2. Choose the correct channel, protocol and mode.
0-RS232 communication:
52
1-RS485 communication:
53
Fig 1
Fig 2
54
2.15 LG Glofa(Cnet) series PLC
Note: please turn on DIP switch2 and turn off switch1 for LG Glofa -cnet communication.
2.15.2 Parameters
HMI:
Parameters Recommend settings Choices of settings Note
PLC type LG Glofa (cnet)
Port RS232 RS232
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity No parity Even/odd/no parity
Baud rate 19200 4800/38400/9600/115200/19200/187500
Station no. 0 0~255
PLC:
Note:
1. Turn on the switch BUILT-IN CNET on the PLC.
2. “Dedicated-slave” must be choosed in the PLC programming software.
3. The communication area of M must be set in the PLC programming software.
M area size:
55
56
2.15.3 Cable making
Fig 1
57
2.15.4 Device address
58
QW 0.0.0~0.0.3 Word/DWor Data register
d
0.1.0~0.1.3 Word/DWor Data register
d
0.2.0~0.2.3 Word/DWor Data register
d
0.3.0~0.3.3 Word/DWor Data register
d
0.4.0~0.4.3 Word/DWor Data register
d
0.5.0~0.5.3 Word/DWor Data register
d
0.6.0~0.6.3 Word/DWor Data register
d
0.7.0~0.7.3 Word/DWor Data register
d
MW 0~4095 Word Data register
0~4095 Regs Data register
MD 0~2047 DWord Data register
0~2038 Regs Data register
59
2.16 LG XGT(CPU Direct) series PLC
2.16.2 Parameters
HMI:
Parameter Recommend settings Choices of settings Note
PLC type LG XGT series(CPU Direct)
Port RS232 RS232
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity No parity Even/odd/no parity
Baud rate 115200 4800/38400/9600/115200/19200/187500
Station no. 1 0~255
The default parameters of LG XGT series PLC(CPU Direct): 115200, 8, 1, no parity, station
no.1
Note: XGT series(CPU Direct)only supports the baud rate 115200 and cannot modify the
station no.
Fig1
60
2.16.4 Device address
61
CS 65535 DWord Data register
2.17.1Device model
Matsushita- Mewnet FP series PLC include FP0, FP1, FP3, FP2SF, FP10SH and so on. They can
communicate with Xinje HMI via the programming port or communication port on the CPU.
FP0-CXXCXX only supports RS232 connection.
62
2.17.2 Parameters
HMI:
Parameters Recommend settings Choices of settings Note
PLC type matsushita FP series PLC
Port RS232
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity Odd parity Even/odd/no parity
Baud rate 9600 4800/38400/9600/115200/19200/187500
Station no. 1 0~255
The default parameters of Matsushita FP series PLC: 9600, 8, 1, odd parity, station no.1
PLC:
Note:
1.PLC soft component input example:
LC HMI
R45
Y1
63
2.When making the PLC program, set the switch to PPOG; set the switch to RUN when
communicating.
3.Do not choose <Common communication mode>, otherwise, the communication will
be error.
4.FP series PLC default station no. is 1, please note FP3 series PLC station no. must set
to 0.
Fig1
Fig2
64
(c) CPU 8-pin port:
Fig3
Fig4
65
C 100~143 Bit Counter
SV 0~143 Word/DWor Setting register
d
EV 0~143 Word/DWor Real value of counter or timer
d
DT 0~65535 Word/DWor Single/double words data
d register
66
2.18 Schneider PLC
2.18.1Device model
2.18.2 Parameters
HMI:
Parameters Recommend settings Choices of settings Note
PLC type Schneider Micro/NEZA
/Twido series PLC
Port RS485
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity Even parity Even/odd/no parity
Baud rate 19200 4800/38400/9600/115200/19200/187500
Station no. 1 0~255
The default parameters of Schneider Micro/NEZA/ Twido series PLC: 19200, 8, 1, even parity,
station no.1
67
PLC:
68
Note:
The object address of Twido PLC is dynamic and can be enlarged in the PLC
programming software. Please release the max coil address in the program. For example:
the max coil address is M127, please output M127 in the program.
Fig1
Fig2
69
2.19 Fatek FB series PLC
Note: MA series PLC needs to configure FB-DTBR or FB-DTBR-E module, uses RS232
or RS485 connection.
2.19.2 Parameters
HMI:
Parameters Recommend settings Choices of settings Note
PLC type Fatek MC/MA/MU series PLC
Port RS232 RS232 or RS485
Data bit 7 7 or 8
Stop bit 1 1 or 2
Parity Even parity Even/odd/no parity
Baud rate 9600 4800/38400/9600/115200
/19200/187500
Station no. 1 0~255
The default parameters of Fatek MC/MA/MU series PLC: 9600, 7, 1, even parity, station
no.1
70
2.19.3 Cable making
CPU port:
Fig1
Fig2
Fig3
71
(d)FB-DTBR/DTBR-E module RS232:
Fig4
Fig5
72
2.20 Vigor VIGOR PLC
2.20.2 Parameters
HMI:
Parameters Recommend Choices of settings Note
settings
PLC type Vigor VB series
PLC
Port RS232 RS232/RS485/RS422
Data bit 7 7 or 8
Stop bit 1 1 or 2
Parity Even parity Even/odd/no parity
Baud rate 19200 4800/38400/9600/115200/19200/187500
Station no. 0 0~255
The default parameters of Vigor VB series PLC: 19200, 7, 1, even parity, station no.0
73
(a) CPU RS232 USB-A:
Fig1
(b) CPU direct connection or RS232 extenstion card:
Fig2
(c) CPU direct connection or RS485 extenstion card:
1.RS422 connection
Fig3
2.RS485 connection
Fi4
74
2.20.4 Device address
75
2.21 Fuji SPB series PLC
2.21.2 Parameters
HMI:
Parameter Recommend Choices of settings Note
settings
PLC type Fuji SPB series PLC
Port RS232 RS232/RS485
Data bit 8 7/8
Stop bit 1 1/2
Parity Odd parity Even/odd/no parity
Baud rate 19200 4800/38400/9600/115200/19200/187500
Station no. 0 0~255
Fig1
76
(b) NW0LA-RS4 module RS485:
Fig2
Fig3
77
WM 0~63 Word/DWor Used as register
d
WL 0~255 Word/DWor Used as register
d
WSM 32768~3302 Word/DWor Used as register
3 d
D 0~8191 Word/DWor Data register
d
TW 0~511 Word/DWor Used as register
d
CW 0~255 Word/DWor Used as register
d
LD 0~10000 Word/DWor Used as register
d
SD 32768~3302 Word/DWor Used as register
3 d
78
2.22 Keyence KV series PLC
2.22.1Device model
2.22.2 Parameters
HMI:
Parameters Recommend Choices of settings Note
settings
PLC type keyence KV series
Port RS232 port RS232/RS422
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity Even parity Even/odd/no parity
Baud rate 9600 4800/38400/9600/115200/19200/187500
Station no. 1 0~255
The default parameters of Keyence KV series PLC: 9600, 8, 1, even parity, station
no.1
79
1 23 45 6
Fig1
Fig2
Fig3
Fig4
80
(e) Serial port module KV-L20(Port1, RS232)connects to Keyence KV-700 PLC:
Fig5
Fig6
Fig7
81
2.23 Emerson EC20 series PLC
2.23.1Device model
2.23.2 Parameters
HMI:
Parameters recommend settings Choices of settings Note
PLC type Emerson EC20 series PLC
Port RS232 RS232/RS485
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity Even parity Even/odd/no parity
Baud rate 19200 4800/38400/9600/115200
/19200/187500
Station no. 1 0~255
The default parameters of Emerson EC20 series PLC: 19200, 8, 1, even parity, station
no.1
Fig1
82
Fig2
Fig3
83
d
HMI:
Parameter Recommend settings Choices of settings Note
PLC type OEMax NX70 series PLC
Port RS232 RS232/RS485
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity No parity Even/odd/no parity
Baud rate 9600 4800/38400/9600/115200
/19200/187500
Staion no. 1 0~255
The default parameterso f OEMax NX7 PLC: 9600, 8, 1, no parity, station no.1
Fig1
84
(b) OEMax NX7 PLC COM1 (RS485):
Fig2
8 7 6 5 4 3 21
Fig3
(d) OEMax NX7 PLC COM2 is RJ-45 8-pin port, short pin1 and 3 means RS485+; short
pin2 and 4 means RS485- :
Fig4
OR
Fig5
85
2.24.4 Device address
86
2.25 Bosch Rexroth IndraControl L40 series PLC
Bosch Rexroth IndraControl L40 series PLC can communicate with Xinje HMI via
COM0 and COM1.
CPU Connected module Port Cable Device
Bosch Rexroth
IndraControl L40 Direct connect to CPU RS232 Fig 1 IndraControlL40
Series PLC
2.25.2 Parameters
HMI:
Parameters Recommend settings Choices of settings Note
PLC type IndraControl L40 series PLC
Port RS232 RS232
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity Even parity Even/odd/no parity
4800/38400/9600/115200
Baud rate 9600
/19200/187500
Station no. 1 0~255
The default parameters of IndraControl L40 series PLC: 9600, 8, 1, even parity,
station no.1
Fig1
87
2.25.4 Device address
88
2.26 OPTO 22 SNAP series PLC
2.26.2 Parameters
HMI:
Recommend
Parameters Choices of settings Note
settings
PLC type OPTO 22 series
Port PLC
RS232 RS232/RS485
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity No parity Even/odd/no parity
Baud rate 115200 4800/38400/9600/115200/19200/187500
Station no. 1 0~255
The default parameters of OPTO 22 series PLC: 115200, 8, 1, no parity, station no.1
Fig1
89
Fig2
Fig3
90
2.27 SAIA-Burgess PCD series PLC
SAIA—Burgess PCD series PLC communicates with Xinje HMI via socket A or socket B
port.
91
2.27.2 Parameters
HMI:
Parameters Recommend Choices of settings Note
settings
SAIA—Burgess
PLC type
PCD
Port Series PLC
RS232 RS232/RS485
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity No parity Even/odd/no parity
Baud rate 19200 4800/38400/9600/115200/19200/187500
Station no. 0 0~255
Fig1
92
Fig2
(c) Socket A port (PCD7.F120):
Fig3
Fig4
Fig5
93
Fig6
Fig7
Fig8
94
Fig9
Fig10
Fig11
95
2.27.4 Device address
2.28.2 Parameters
HMI:
Parameters Recommend Choices of settings Note
settings
PLC type AB Mircrologix, AB Mircrologix,
96
SLC series (DF1 SLC series (DF1 full-duplex)/Modbus
full-duplex) RTU(panel is master)
Port RS232 RS232
Data bit 8
Stop bit 1
Parity No parity
Baud rate 9600 9600/19200/38400
Station no. 1 0~255
PLC setting:
97
Condition B: in touchwin software, the PLC protocol is Modbus RTU (panel is master):
Note: for Modbus RTU communication, the address must set the mapping, PLC address 1
corresponds to Modbus address 0, PLC address 2 corresponds to Modbus address 1…
98
2.28.3 Cable making
Fig1
Fig2
99
T4ACC 0~999 Word Timer actual value
C5PRE 0~999 Word Counter preset value
C5ACC 0~999 Word Counter preset value
R6 0~999 Word Data register
N7 0~999 Word/Dword Data register
F8 0~999 Dword Floating number
register
R6LEN 0~999 Word
P6POS 0~999 Word
100
2.29 Xinje V5 series inverter
2.29.2 Parameters
HMI:
Parameters Recommend Choices of settings Note
settings
PLC type Thinget V5 series
inverter
Port RS485 RS485
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity Even parity Even/odd/no parity
Baud rate 19200 4800/38400/9600/115200/19200/187500
Station no. 1 0~255
Note: please set the communication wait time if the connection is error.
101
Inverter:
Function code Name Range Meaning
P0.01 Frequency setting channel 4 Serial port setting
P0.03 Run command channel 2 Run via serial port
P3.09 Communication settings 054 The unit:19200
Decade: 1-8-1, even parity
Hundred: no definition
RS485:
Fig1
102
2.30 SHIMADEN
Note: all the devices support Modbus protocol can communicate with Touchwin
HMI.
2.30.2 Parameters
HMI:
Parameters Recommend Choices of settings Note
settings
PLC type Modbus RTU
(panel is Master)
Port RS485 RS485
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity Even parity Even/odd/no parity
Baud rate 9600 4800/38400/9600/115200/19200/187500
Station no. 1 0~255
Note:
1. The parameters of device and HMI must be same.
2. Some devices need to add terminal resistor (sucha as SRS10 digital adjustor)
3. Meter parameter 018C must set to 1 (COM LED is ON), please use the “function
filed”(the button in the Touchwin software) to set the value of 018C(4x396=1).
RS485 connection:
103
Fig1
104
2.31 Modbus RTU (panel is Master)
2.31.2 Parameters
HMI:
Parameters Recommend Choices of settings Note
settings
PLC type Modbus RTU
(panel is Master)
Port RS485 RS485/RS232/RS422
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity Even parity Even/odd/no parity
Baud rate 9600 4800/38400/9600/115200/19200/187500
Station no. 1 0~255
Note:
1. Modbus RTU protocol supports broadcast function, station no is 0.
2. How to use the broadcast function in the HMI?
The broadcast function only sends command but not receives. It sends command by
“function field”, “function button” or “function block” in Touchwin software. The operand
must has no feedback command, such as “set on coil”, “setting data”, “reset coil”.
PLC:
Please choose Modbus RTU (Slave) in the software.
105
Fig1
Fig2
Fig3
106
3x 0~65535 Word/Dword R Used as data register
2.32.1Device model
2.32.2 Parameters
HMI
Parameters Recommend Choices of settings Note
settings
PLC type Modbus ASCII
(panel is Master)
Port RS485 RS485/RS232/RS422
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity Even parity Even/odd/no parity
Baud rate 9600 4800/38400/9600/115200/19200/187500
Station no. 1 0~255
PLC:
Please choose Modbus ASCII (Slave) protocol in the software.
Modbus RS485:
Fig1
107
Modbus RS232:
Fig2
Modbus RS422:
Fig3
108
2.33 Modbus slave (panel is Slave)
2.33.1Device model
2.33.2 Parameters
HMI:
Parameters Recommend Choices of settings Note
settings
PLC type Modbus slave
(panel is slave)
Port RS485 RS485/RS232/RS422
Data bit 8 7/8
Stop bit 1 1/2
Parity Parity Even/odd/no parity
Baud rate 9600 4800/38400/9600/115200/19200/187500
Station no. 1 0~255
Modbus RS485:
Fig1
Modbus RS232:
109
Fig2
Modbus RS422:
Fig3
110
2.34 ABB PLC
2.34.1Device model
2.34.2 Parameters
HMI:
Parameters Recommend Choices of settings Note
settings
PLC type ABB AC500
Port RS485 RS485
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity Even parity Even/odd/no parity
Baud rate 19200 4800/38400/9600/115200/19200/187500
Station no. 1 0~255
PLC:
111
2. Choose COM1 MODBUS, then set the operation mode to slave. Other
112
2.34.4 Device address
113
2.35 IDEC
2.35.2 Parameters
HMI settings:
Parameter Recommend Choices of settings Note
s settings
PLC type IDEC MicroSmart
Port RS232 RS232
Data bit 7 7/8
Stop bit 1 1/2
Parity Even parity Even /odd /no parity
Baud rate 9600 4800/38400/9600/115200/19200/187
500
Station no. 0
RS232 connection:
114
2.35.4 Device address
115
2.36 TAIAN
116
2.36.2 Parameters
HMI settings:
Parameter Recommend Choices of settings Note
s settings
PLC type TAIAN TP03
series
Port RS232 RS232/RS485
Data bit 8 7/8
Stop bit 2 1/2
Parity No parity Even /odd /no parity
Baud rate 19200 4800/38400/9600/115200/19200/187
500
Station no. 1 0-255
RS232 connection:
Fig1
RS485 connection:
Fig2
117
2.36.4 Device address
118
2.37 YuDian AI
2.37.2 Parameters
HMI settings:
Parameter Recommend Choices of settings Note
s settings
PLC type AI series
instrument
Port RS485 RS485
Data bit 8 7/8
Stop bit 1 1/2
Parity No parity Even /odd /no parity
Baud rate 9600 4800/38400/9600/115200/19200/187
500
Station no. 129
Note:
1. The parameters of HMI and meter must be the same.
2. How to set the station no. of meters?
HMI→129 meter→ 1+80H
HMI→130 meter→ 2+80H
RS485 connection:
119
2.37.4 Device address
120
2.38 Inovance PLC
H1U-0806MR\T
H1U H1U-1410MR\T
H1U-1614MR\T Mitsubishi FX
CPU RS422 Fig 1
series PLC
H2U-1616MR\T
H2U H2U-2416MR\T
H2U-3624MR\T
2.38.2 Parameter
HMI settings
Paramete Recommended Choices of settings Notes
r settings
PLC type FX series - -
Data bit 7 -
Stop bit 1 -
Parity Even parity Even/odd/no parity
Baud rate 9600 4800/9600/19200/38400/560
00/57600/
115200/187500
Station 0 -
no.
Inovance H1U\2U series default communication parameters: 9600, 7, 1, even, statio no.0
PLC settings:
121
2.38.3 Cable making
Fig1
122
C16 0~199 Word/DWord 16-bit counter
C32 200~255 DWord 32-bit counter
D 0~8255 Word/DWord Data register
T 0~255 Word/DWord Current value
X 0~177 Word/DWord Used as data register
Y 0~177 Word/DWord Used as data register
M 0~8255 Word/DWord Used as data register
S 0~999 Word/DWord Used as data register
123
2.39 HaiWell PLC
2.39.2 Parameters
HMI settings:
Paramete Recommend settings Choices of settings Notes
r
PLC type Modbus RTU (panel is - -
master)
Data bit 8 -
Stop bit 1 -
Parity Odd Even/odd/no parity
Baud rate 9600 4800/9600/19200/3840
0/56000/
57600/115200/187500
Station 1 -
no.
Haiwell E\S series default communication parameters: 9600, 8, 1, odd, station no.1
PLC settings:
Communication protocol: Modbus RTU.
124
Fig 1
Fig 2
125
2.40 Hollias PLC
PLC type in
Connected Cable
Series CPU Port Touchwin
module making
software
LM3109 RS232 Fig 1 Modbus RTU
LM CPU
LM3107 RS485 Fig 2 (panel is master)
2.40.2 Parameters
HMI settings:
Paramete Recommend Choices of settings Note
rs settings
PLC type Modbus RTU (panel - -
is master)
Data bit 8 -
Stop bit 1 -
Parity No parity Even/odd/no parity
Baud rate 38400 4800/9600/19200/38400/5600
0/
57600/115200/187500
Station 51 -
no.
Hollias LM series PLC default parameters: 38400, 8, 1, no parity, station no.51
Fig1
126
Fig2
127
2.41 Delta (temperature controller)
PLC type in
Connected
Series CPU Port Cable Touchwin
module
software
DTA4848
DTA9696VR Modbus RTU
DVP CPU RS485 Fig 1
DTC1000 (panel is master)
DTC2000
2.41.2 Parameters
HMI settings:
Paramete Choices of settings Notes
rs
PLC type Modbus RTU - -
(panel is master)
Data bit 7 -
Stop bit 1 -
Parity Even parity Even/odd/no parity
Baud rate 9600 4800/9600/19200/38400/56000/57600
/
115200/187500
Station 1 -
no.
Delta (temperature controller) default parameters: 9600, 7, 1, even parity, station no.1
128
Fig1
129
2.42 Siemens S7-1200
Communic Connection
Series PLC type in Touchwin software
ation type diagram
2.42.2 Parameters
2. PLC DB, M must be defined in the PLC before using. Click project-program
block-add new block, choose data block (DB), the type is global DB, not choose
only sign visit. DB number can be auto or manual.
130
3. Choose project-program block-data block can define the address in the data
block.
Note: for the software STEP Basic V12 and up version, please release the
communication protection:
(1) Choose the PLC model in the project tree, right click it, choose properties
(2) Please choose “permit access with PUT/GET communication from remote partner
(PLC, HMI, OPC)”. Then download the PLC program in the PLC.
131
HMI settings:
Only Touchwin software v2.d.1j and higher version support Siemens 1200 series
PLC.
Operation steps:
(1) Please select the HMI type, click next.
(2) Select Net device. The IP address in own devices is HMI IP address.
132
(3) Right click Net device, click New. Then input the project name.
(4) Right click the project name to delete or rename the project.
(6) The IP is S7-1200 IP address. Note: this IP can be set in PLC software. Port 102
cannot be changed.
133
(7) please choose “word exchange”, otherwise, the double word data will be error.
134
Note: please define the DB and M in the Siemens PLC, otherwise the communication
will be error.
(12) Notes:
A. Siemens PLC S7-1200 doesn’t have station number problem. It can build network with
HMI once the IP address is correct. The network mode can be multi-HMI-one-PLC,
one-HMI-multi-PLC, and multi-PLC-multi-HMI.
B. RX/TX lights when the communication is successful. RX/TX is shining when if is finding
the network.
C. Modbus TCP device is used to connect with TBOX-XINJE PLC; Siemens S7-1200
device can connect any device with Ethernet.
D. please define the DB and M in the Siemens PLC, otherwise the communication will be
error.
Diagram 1
135
Diagram 2
136
2.43 Mitsubishi FR series inverter
2.43.2 Parameters
Inverter parameters:
Function Name Default Range Debug
(FR) value parameters
P117 Station no. 0 0~31, 0~247 0
P118 Baud rate 19.2kbps 4800bps,9600bps,38400bps 19200
P119 Stop bit, data 1 0: 1 stop bit, 8 data bit 1: 2 stop bit, 8
bit 1: 2 stop bit, 8 data bit data bit
10: 1 stop bit, 7 data bit
11: 2 stop bit, 7 data bit
P120 Parity 2 0: no parity 2: even parity
1: odd parity
2: even parity
P121 Retry times 9999 9999
P122 Test time 0 0: RS485 0
137
9999: no communication
test
P123 Wait time 150ms 125
P124 R/LF 0 0: without CR, LF 0
1: with CR
2: with R, LF
P79 Mode selection 0 0~7 Set to 2, external
communication
mode, please cut
off the power of
inverter after
setting the
parameters
P340 Communication 0 0, 1, 10 Set to 1, start in
start mode network running
mode
138
Inverter parameters:
Functio Name Default Range Debug parameters
n value
(FR)
P117 Station no. 1 0~31, 0~247 1 (Modbus station no.
can not be 0)
P118 Baud rate 19.2kbps 4800bps,9600bps,384 19200
00bps
P119 Stop bit 1 0: 1 stop bit, 8 data bit 1: 2 stop bit, 8 data bit
1: 2 stop bit, 8 data bit
10: 1 stop bit, 7 data
bit
11: 2 stop bit, 7 data
bit
P120 Parity Even 0: no parity 2: even parity
1: odd parity
2: even parity
P121 Retry times 9999 9999
P122 Communicatio 0 0: RS485 0
n test 9999: no
communication test
P123 Waiting time 150ms 125
P124 CR/LF 0 0: without CR, LF 0
selection 0: with CR
0: with R, LF
139
549 protocol 1 Modbus-RTU Be valid after restart
selection the inverter
P79 Mode 0 0~7 Set to 2, external
selection communication mode,
please cut off the
power of inverter after
setting the parameters
P340 Communicatio 0 0, 1, 10 Set to 1, start in
n start mode network running mode
RS485 cable:
Diagram 1
140
2.44 Sanken VM06 inverter
2.44.2 Parameters
141
Inverter:
Function Name Content Debug
parameters
F1002 Frequency setting 1: operate panel 22
2: external analog voltage VIF1
(0~5V)
21: terminal stepper
22: communication
F1101 Running command 1. Operate panel 2. External 3
selection terminals 3. communication
F4002 RS232C/RS485 1: RS232C (default setting) Choose
2: RS485 according
to wiring
method
F4005 Serial communication 0: no function (default setting) 2
function 1: special protocol communication
2: Modbus communication
F4006 Inverter station no. 0~254: ModBus station no. 1
(1~32: RS485 communication)
1~32 is valid in special protocol
communication
F4007 Baud rate 1: 1200bps 2: 2400bps 4
3: 4800bps 4: 9600bps
5: 19200bps 6: 38400bps
7: 57600bps
F4008 Parity 0: no 1: odd (default setting) 2: even 2
142
F4009 Stop bit 1: 1 bit (default setting) 1
2: 2 bit
F4010 Stop code 0: CR+LF (default setting) 0
1: CR
※BINARY and Modbus without stop
code
RS485:
Diagram 1
143
144
2.45 XINJE XD/XE series
2.45.2 Parameters
1. HMI setting
Parameters Recommended Other settings for choice Notes
setting
PLC type XINJE XD/XE XINJE XD/XE series /Modbus RTU (panel is
series Master)
/Modbus ASCII (panel is Master)
Serial port RS232 RS232/RS485
Data bit 8
Stop bit 1
Parity Even parity
Baud rate 19200 4800/9600/19200/38400/115200
Station no. 1 0~255
145
2. PLC setting
146
Diagram 1
Diagram 2
147
HSC 0~31 Bit Counter, high speed counter
D 0~7999 Word//DWord Data register
ID 0~99 Word//DWord Analog input
ID1xxxx 0~1599 Word//DWord Extended module analog input
ID2xxxx 0~499 Word//DWord Extended BD analog input
QD 0~99 Word//DWord Analog output
QD1xxxx 0~1599 Word//DWord Extended module analog output
QD2xxxx 0~499 Word//DWord Extended BD analog output
SD 0~2047 Word//DWord Data register, special using
TD 0~575 Word//DWord Timer value
CD 0~575 Word//DWord Counter value
ETD 0~31 Word//DWord Timer value, precise timer
HD 0~999 Word//DWord Data register
HSD 0~499 Word//DWord Data register, power-off retentive
HTD 0~95 Word//DWord Timer value, power-off retentive
HCD 0~95 Word//DWord Counter value, power-off retentive
HSCD 0~31 Word//DWord Counter value, high speed counter
FD 0~6143 Word//DWord FlashROM reigster
SFD 0~1999 Word//DWord FlashROM register, special using
FS 0~47 Word//DWord Special security register
DM 0~7984 Word For data register
DX 0~60 Word For data register
DX1xxxx 0~1760 Word For data register, extended module
DX2xxxx 0~460 Word For data register, extended BD
DY 0~60 Word For data register
DY1xxxx 0~1760 Word For data register, extended module
DY2xxxx 0~460 Word For data register, extended BD
DS 0~1008 Word For data register
DSM 0~2032 Word For data register, special function using
DT 0~560 Word For data register
DC 0~560 Word For data register
DET 0~16 Word For data register, precise timer
DSE 0~16 Word For data register, WAIT instruction
DHM 0~944 Word For data register, power-off retentive
DHS 0~112 Word For data register, power-off retentive
DHT 0~80 Word For data register, power-off retentive
DHC 0~80 Word For data register, power-off retentive
DHSC 0~16 Word For data register, high speed counter
148
2.46 LG XGB series PLC
2.46.2 Parameters
1. Programming port
(1) HMI setting
Parameter Recommended setting Settings for Notes
choice
PLC type LG XGT/XGK series (CPU Direct)
Port RS232
Data bit 8
Stop bit 1
Parity No parity
Baud rate 115200
Station no. 0
LG XGT/XGK series (CPU Direct) default parameters:
149
Note: XGB series (CPU direct) only support baud rate 115200, cannot change the station no.
2. CNet port
(1) HMI setting
Parameter Recommended setting Settings for choice Notes
PLC type LG Master-K80/120 series (CNet)
Port RS232 RS232/RS485
Data bit 8
Stop bit 1
Parity No parity
Baud rate 9600 9600/19200/38400/115200/187500
Station no. 0 0~255
LG Master-K80/120 series (CNet) default parameters:
150
(2) PLC setting
a. RS232 communication
Tools-Network Manager to set parameters:
151
b. RS485 communication
Tools-Network Manager to set parameters:
152
2.46.3 Cable making
Diagram 1
153
Diagram 2
Diagram 3
154
N 65535 Word/DWord Data register
0.0~65535.F Bit Relay
R 65535 Word/DWord Data register
0.0~65535.F Bit Relay
ZR 65535 Word/DWord Data register
0.0~65535.F Bit Relay
TS 65535 Word Data register
CS 65535 DWord Data register
Koyo Direct Logic series DL05, DL250… (connect to CPU unit directly)
Series CPU Connection module Port Wiring The PLC type in
type diagram TouchWin
Connect to CPU RJ-11 port
Click RS232 Diagram 1 Koyo Click series
(RS232 port)
1. HMI setting
Parameter Recommended Optional settings Notes
setting
PLC type Koyo Click series
Port type RS232 RS232/RS422
Data bit 8
Stop bit 1
Parity Odd parity
Baud rate 38400 9600/19200/38400
Station no. 1 1~247
155
2. PLC setting
Please refer to Koyo S series PLC settings.
RS232 wiring:
156
X2 1~16 Bit I/O module 2 input
Y0 1~16 Bit Output
Y1 1~16 Bit I/O module 1 output
Y2 1~16 Bit I/O module 2 output
C 1~2000 Bit Control bit
T 1~500 Bit Timer
CT 1~250 Bit Counter
SC 1~1000 Bit System control bit
DS 1~4500 Word Data temporary storage
register, support double
words
DD 1~1000 Word/DWord Data temporary storage
register, support double
words
TD 1~500 Word Timer present value
CTD 1~250 Word/DWord Counter present value,
support double words
SD 1~1000 Word System data temporary
storage register
DH 1~500 Word/DWord Data temporary storage
register
DF 1~500 DWord Data temporary storage
register (double words)
XD 0 Word/DWord Input state temporary
storage register
YD 0 Word/DWord Input state temporary
storage register
TXT 1~1000 Word/DWord texts temporary storage
register
Communication
Series Cable diagram PLC model in Touchwin software
type
Mitsubishi L series
Mitsubishi Q series RJ45 Diagram 1 or 2 Mitsubishi Melsec
157
2.48.2 Parameter settings
Take Mitsubishi L series PLC as an example to explain the Melsec protocol device pararmeter
settings.
1. PLC software settings
Select project area-PLC parameter-Ethernet terminal setting, set the PLC IP address. The
communication data code please set to binary code communication. Select “permit write (FTP & MC
protocol) when running.
click “open the setting”, select ‘TCP” protocol and “MC” open mode, and set the station port no.
(range is 0401H~1387H, 1392H~FFFEH).
2. HMI setting
Please select the HMI type, click next.
158
Select Net device. The IP address in own devices is HMI IP address.
Right click Net device, click New. Then input the project name.
Select Mitsubishi Melsec series in the device list. The IP address is Mitsubishi PLC IP address,
159
the port 1025 is the station port no. setting in the Mitsubishi PLC.
Communication parameters: please use the default parameters. Communication status register: if
select this item, the status will occupy 4 registers. The register address can be set by user. If set the
address to PSW256, the register meanings are shown as the following.
PSW256: communication succeeded times
PSW257: communication failed times
PSW258: timeout times
PSW259: communication error times.
160
2.48.3 Cable making
Diagram 1
Diagram 2
161
2.48.4 Device address
Series Port type Cable The PLC model in the Touchwin software
making
The device with serial port RS485 diagram 1 Free type (panel is slave)
and support free type RS232 diagram 2
protocol RS422 diagram 3
162
2.49.2 Parameter setting
1. HMI setting
Parameter Recommended setting Optional setting Notes
PLC model Free type (panel is
slave)
Port type RS485 RS485/RS232/RS422
Data bit 8 7/8
Stop bit 1 1/2
Parity Even parity Even /odd /no
Baud rate 9600 4800/38400/9600/115200/19200/187500
Station no. 1 0~255
163
no.
Station no.: HMI station no. (0~255, 0 is broadcast mode, the HMI no need to reply)
Command: “R” is HMI read, “W” is HMI write
Address: index no., the index no. corresponding to HMI PSW256~PSW511 is 0~256
Length: PSW numbers (1~256) needs to read and write
Data: PSW value, there is no data for command “R”
Parity: add all the bytes from station no. to data (not include parity), get the remainder of 0x100 (if
the parity is 0x5A, ignore it, not check)
Data format:
PSWi PSWi PSWi+1 PSWi+1 PSWi+n-1 PSWi+n-1
……
(high) (low) (high) (low) (high) (low)
Address is I, length is n.
(3) Protocol
The controller sends a request to the HMI, the HMI will check the parity after receiving the request. If
the parity is correct, and the station no. is equal to the HMI, the HMI will reply the request. Otherwise,
the HMI will not reply.
The controller will check the overtime of HMI response. If the time is over 50ms, the controller will
resend the request.
The HMI will check the overtime of receiving data. If the time is over 25ms, the HMI will initialize the
communication and wait for the new request.
HMI
Station no. State Address Length Data Parity
Data: PSW value
164
Station “W” Address Length Data Parity
no.
HMI
Station no. State Parity
State: 0--- OK
(4) Application
a. The controller read HMI data PSW256=0, PSW257=12
Controller send: 01H 52H 00H 02H 55H
HMI reply: 01H 00H 00H 02H 00H 00H 00H 0CH 0FH
b. Controller write 256 in HMI PSW256
Controller send: 01H 57H 00H 01H 01H 00H 5AH
HMI reply: 01H 00H 01H
1. RS485 cable
Diagram 1
2. RS232 cable
Diagram 2
3. RS422 cable
165
Diagram 3
Series name Port type Cable making PLC model in Touchwin software
Ethernet device supporting RJ45 Diagram 1,
Modbus_TCP
Modbus TCP protocol diagram 2
Take Xinje T-BOX as an example to explain the Modbus TCP parameter setting.
166
1. Hardware configuration
Wiring as the above diagram. Turn off of the TBOX DIP switch S3, make sure T-BOX is connected to
the Ethernet. Power on the device. Make sure the PLC is connected to the Ethernet.
Version requirements:
T-BOX hardware version 2.10 please use PLC software XCPpro version 3.3
T-BOX hardware version 2.0 please use PLC software XCPpro version 3.0f.
Please turn off DIP switch S3 to make the Ethernet indentifing the T-BOX for the firt time using.
Please use fixed IP address (192.168.0.111) for the T-BOX and connect it in the Ethernet to
configure the parameters. The IP of PC must be in the same gateway of T-BOX (192.168.0.***). As
each T-BOX default IP is the same, only one T-BOX can be configured in the network at one time.
Otherwise, the IP will be conflict.
2. T-BOX configuration
(1) T-BOX Link LED always ON means it has connected to the Ethernet (no need connect to PC
via RS232) when it connected to the Ethernet cable. Please use PLC software XCPpro to
configure the T-BOX. Please turn off DIP switch S3 to make the Ethernet indentifing the
T-BOX for the firt time using. T-BOX is slave station, please turn on DIP switch S1.
(2) Open XCPpro software, click option/Ethernet module settings. Click “refresh list”, it will show
the T-BOX in the network. Double click the T-BOX to configure.
167
Log in name: set by user
Device ID: set by factory, cannot be changed
Remote log in: the purpose is to connect the TBOX with the Ethernet. If using Xinje server, the
parameters no need to change. If user can build server, please set the IP, port and server name of
the server.
Config network: the DIP switch S3 is OFF, please set the T-BOX IP, then turn ON S3. The network
will indentify the fixed IP of T-BOX.
Serial port: the parameters can be changed, but the parameters must be same to the device
connecting to the T-BOX.
Note: when it uses LAN, the remote log in address is:
(3) When the S2 switch is OFF, shut down the log in server, click option/comm mode setting, set
as the following to monitor the PLC.
168
When using Xinje company server, the remote log in address is:
Turn on S2 switch, startup the log in server, click option/comm mode setting, set as the following, it
can monitor the PLC after logging in server successfully.
(4) For the first time using, in order to make the network indentify the T-BOX, the S3 switch is
OFF. It can change the IP address after connecting successfully.
169
3. HMI software setting
(1) Select the HMI model TN(-ET), TG(-ET), TE(-ET), click next, select “Net device” in the list.
Please set the HMI IP address in the own devices. The IP cannot be conflict with other
device.
(2) Right click the “Net device”, select “New”. The new project name is device.
(3) Please select Modbus TCP device for communicating with T-BOX. This IP is T-BOX IP
address, the port 502 cannot be changed.
(4) The communication parameters please keep defaulted. If selecting communicate status
register, the PSW256~PSW259 represents communicate successful times, communication
170
failure times, communication overtime times, communication error times. User can change
the PSW address.
(5) Click next to finish the setting. Then enter the editing screen, put a data input button on the
screen, select “device”, the object type includes 4x(read and write, word object), 3x(read
only, word object), 0x(bit object, read and write), 1x(read only, bit object).
171
2.50.3 Cable making
Diagram 1
172
Diagram 2
PLC type in
Series Connection Communication
CPU unit Cable touchwin
name module type
software
HMI setting
173
Parity Odd
Baud rate 19200
Station no. 0 Please use the
recommended
settings
174
PLC setting
Please set the protocol format to MC protocol in RS485 serial port. The trasfer mode is set to
mode 5.
175
(2) Modbus RTU communication
The HMI please choose“Modbus RTU”protocol.
Please set the protocol format to Modbus RTU in RS485 serial port, and set the Modbus station no.
to non-zero number, the HMI parameters must be same to PLC settings.
Notes: PLC has fixed Modbus address in Modbus communication, it will read and write as
the address.
176
2.51.3 Cable making
Fig1
177
2.51.4 Device address
178
2.52 Siemens S7-200 smart series
PLC setting
179
Touchwin software setting
1. Choose the HMI type TN(-ET), TG(-ET) or TE(-ET), click next, choose Net device
in the list, please inputthe HMI IP address in the own devices.
2. Choose the net device, right click it, choose new, and name it as S7-200 smart.
3. Choose Siemens S7-200 smart series in the device list, in this example, the PLC
IP address is 192.168.0.1, the port is 102 which cannot be changed.
180
4. The communication parameters please use default settings. If communication
status register is choosen, and set to PSW256, then PSW256~PSW259 means
communication succeeded times, failed times, overtime times, error times. The
register address can be set by user.
5. Click next to finish the settings. Then enter the screen, for example, put a data
input button in the screen, choose the device S7-200 smart.
181
There is no station no. for Siemens S7-200 smart, set the correct IP address is ok. It can
make the networks of multi-HMI-one-PLC, one-HMI-multi-PLC, multi-HMI-multi-PLC.
Diagram 1
182
Diagram2
183
2.52.4 Device address
184
2.53 Siemens S7-300 series
PLC setting
HMI setting
1. Choose the HMI type TN(-ET), TG(-ET) or TE(-ET), click next, choose Net device
in the list, please inputthe HMI IP address in the own devices.
185
2. Choose the net device, right click it, choose new, and name it as S7-300.
3. Choose Siemens S7-300 series in the device list, in this example, the PLC IP
address is 192.168.0.5, the port is 102 which cannot be changed.
186
4. The communication parameters please use default settings. If communication
status register is choosen, and set to PSW256, then PSW256~PSW259 means
communication succeeded times, failed times, overtime times, error times. The
register address can be set by user.
5. Click next to finish the settings. Then enter the screen, for example, put a data
input button in the screen, choose the device S7-300.
187
There is no station no. for Siemens S7-300, set the correct IP address is ok. It can make
the networks of multi-HMI-one-PLC, one-HMI-multi-PLC, multi-HMI-multi-PLC.
Diagram 1
188
Diagram2
189
2.53.4 Device address
190
2.54 X-NET communication
X-NET bus is the bus protocol between TG/TE series HMI and XD series PLC. The TG
series -NT model is a dedicated screen for bus communication, which has faster
communication speed and better networking performance. It is recommended to choose
-NT model when bus communication.
PLC type in
Series Connection Communication Cable
CPU unit touchwin
name module type making
software
CPU direct RS485 Fig 1 or 2
connect Xinje Xnet
XD XD3/XDM/XDC
extension BD RS232 Fig 3 series
module
X-NET bus includes two connection modes: OMMS mode which is supported by
TG/TE series(single HMI mode including one HMI one device, one HMI multi-device);
TBN mode which is supported by NT model(multi-HMI mode including multi-HMI
one device, multi-HMI multi-device). The XD series PLC must be hardware v3.2.2
and up. The download port and PLC port is separate for TG/TE series HMI.
191
and the PLC station no. should be no. 2, baud rate must be 57600pbs.
The default is manual setting mode if auto match is not selected. In this case, it needs to
use xinje config tool to set the HMI parameters, PLC station no. and baud rate are not
limited, please choose them as you need.
1. Auto match
Touchwin software can automatic set the communication parameters in auto match mode,
only TG/TE series HMI PLC port OMMS mode support auto match mode.
When building the HMI program, PLC port please choose xinje Xnet series, PLC port
device please choose auto match, other no needs to set.
2. Manual set
(1) make a new HMI program, the download port please set to xinje Xnet series, PLC port
please set to xinje Xnet series, the screen contents can be anything, and download the
program in the HMI.
(2) connect the download port of HMI with PC, power on the HMI.
(3) open xinje config tool, click config/ find device
192
(4) choose the com port, which is the PC serial port, it will show the config tool main
interface after the connection is normal.
If the connection fails, a connection failure window will pop up. Please check whether the
RS232 serial port line is wrong and close other software that occupies the serial port. The
bus can be initialized if cannot connecting, set ON switch 4 on the back of the touch
screen, restart the touch screen, and download the newly created program again. After
the download, set OFF switch 4, and then repeat the connection operation.
(5) After the connection is successful, click config/single device/com port:
(6) set the serial port parameters and net id, click write config and close the window.
193
Com port no.: 1 means HMI download port, 2 meaqns HMI PLC port.
Choose Net: please choose X-NET.
Choose PHY(physical layer): RS232 communication (-NT model PLC port not support),
RS485 communication.
Net ID: the communication network no., all the devices in the same network should have
the same network no., the range is 1 to 32767.
Station no.: it must be 1 for OMMD mode HMI station no.
Net type: please choose OMMS mode (which is single HMI mode)
Baud rate: the max baud rate is 115200 for TG/TE series PLC port, download port, and
-NT model download port, the max baud rate is 3M for –NT model PLC port.
Cycle: please choose this when PLC supports motion bus.
OMMS_slaver list: all the slave station no. connecting the HMI. For example, one HMI
connects two PLCs, the station no. of the two PLCs are 2 and 3, it must set 0,2,3 here.
Otherwise it will not communicate.
(7) click config/single device/route
(8) first please read the HMI setting, then choose add item, set the parameters, then click
write.
194
Net: the net id in the serial port setting.
Com no.: com port no. in the serial port setting.
Gateway: it is 0 in the same network. For cross network communication, it is the
station no. that the cross network transfer equipment signal accesses the serial port.
(note: cross network communication must be PLC hardware v3.3 and up)
After setting, please restart the HMI to make the setting effective.
Com port no.: 1 means HMI download port, 2 meaqns HMI PLC port.
Choose Net: please choose X-NET.
Choose PHY(physical layer): RS232 communication (-NT model PLC port not support),
RS485 communication.
Net ID: the communication network no., all the devices in the same network should have
the same network no., the range is 1 to 32767.
195
Station no.: set any station no. for the PLC and HMI in the network.
Net type: please choose TBN mode (which is multi-HMI mode)
Baud rate: the max baud rate is 115200 for-NT model, the max baud rate is 3M for –NT
model PLC port.
Tokencycle time: the longest time the token passes one circle. The default time is
1000ms.
Max station no.: It refers to the largest station number in a network, and the
communication token will be searched from station 1 to the largest station number.
Considering the communication speed, it is suggested that the customer choose the
continuous station number when assigning station number, and the largest station number
cannot exceed 100.
(7) click config/single device/route
(8) first please read the HMI setting, then choose add item, set the parameters, then click
write.
After setting, please restart the HMI to make the setting effective.
196
Note: in the HMI program, the Net ID corresponds to the net numer in the serial port
configuration, station corresponds to the station number in the serial port
configuration.
Connect the PLC to the computer through USB cable or port1, power the PLC, and repeat
the OMMS manual configuration step 3-5. If PLC and computer communication is not
normal, the corresponding error message will appear. At this time, you need to restart
Config software and start the configuration again until the error message below appears.
197
Set the serial port parameters, net id, then click write config and close the window.
198
Port1 Port4 Port5
Serial port: PLC port no., please set as actual connection port no.
0 1 2 3 4 5 6 7
Xinje Electronic Co.,Ltd
PROGRAMMABLE CONTROLLER
DATE:20120701
TYPE:XD3-48R-E
SN:201208021525
0V ● ● ● Y0 Y1 Y2 Y3 Y4 COM5 Y7 Y10 Y12 COM7 Y15 Y17 Y20 Y22 COM9 Y25 Y27
24V ● A B COM0 COM1 COM2 COM3 COM4 Y5 Y6 COM6 Y11 Y13 Y14 Y16 COM8 Y21 Y23 Y24 Y26
USB USB port
Left extension ED
Port3 Developping 3
port
A B
RS232 port/RS485
Port3
Port4
USB口 Port2 port/optical fiber 4, 5
Port5 Up extension BD
port
(left Port4, right
Port5)
Station no.: the PLC station no. in the network, the range is 1 to 100. The operate object
station no. in the HMI corresponds to this station no. note: the PLC station no. must be 2
in OMMS auto match mode.
Net type: OMMS: one HMI one device, one HMI multi-device (fig. 3-1), multi-HMI
multi-device (fig. 3-2). Please choose it as the actual needs.
Baud rate: set the same baud rate for HMI and PLC.
Other settings please refer to the above HMI setting.
199
First read the settings, then click add item, set the parameters, then click write.
After finishing the configuration, restart the PLC to make the settings effective.
2.54.4.1 Cable
1. TE/TG and TG765-NT (V1.0) (RS485 mode)
Fig 1
200
2. –NT model (V1.1) PLC port RS485 mode
Fig 2
Note: use together with JA-NE-I, which is easy to wiring.
Fig 3
201
2.54.4.3 TBN wiring mode
202
SD 0~4999 Word//DWord Data register, special purpose
TD 0~4999 Word//DWord Timer value
CD 0~4999 Word//DWord Counter value
ETD 0~39 Word//DWord Timer value, precise timer
HD 0~24999 Word//DWord Data register
HSD 0~1999 Word//DWord Data register, hold during power off
HTD 0~1999 Word//DWord Timer value, hold during power off
HCD 0~1999 Word//DWord Counter value, hold during power off
HSCD 0~39 Word//DWord Counter value, high speed counter
FD 0~8899 Word//DWord FlashROM register
SFD 0~5999 Word//DWord FlashROM register, special purpose
FS 0~299 Word//DWord Special security register
DM 0~74984 Word Used as a data register
DX 0~60 Word Used as a data register
DX1xxxx 0~1760 Word Used as a data register, extension module
DX2xxxx 0~260 Word Used as a data register, extension BD
DY 0~60 Word Used as a data register
DY1xxxx 0~1760 Word Used as a data register, extension module
DY2xxxx 0~260 Word Used as a data register, extension BD
DS 0~7984 Word Used as a data register
DSM 0~4984 Word Used as a data register, special function
DT 0~4984 Word Used as a data register
DC 0~4984 Word Used as a data register
DET 0~24 Word Used as a data register, precise timer
DSE 0~16 Word Used as a data register, special for
sequence block wait instruction
DHM 0~11984 Word Used as a data register, hold during power
off
DHS 0~984 Word Used as a data register, hold during power
off
DHT 0~1984 Word Used as a data register, hold during power
off
DHC 0~1984 Word Used as a data register, hold during power
off
DHSC 0~24 Word Used as a data register, high speed
counter
203
2.55 Keyence KV5000
Communication
Series Cable making PLC model selection in touchwin
type
Keyence
RJ45 Fig 1 or 2 Keyence KV5000/5500/7500
KV5000
Take Keyence KV5000 PLC as an example to explain the settings of communication device.
225
HMI settings:
1. choose HMI model TN(-ET), TG(-ET) or TE(-ET), click next, then choose net device, fill in
the IP address of HMI. The HMI IP cannot be conflict with other devices in the network.
2. right click the net device, build a new project, and name it as keyence KV5000.
225
3. choose Keyence (KV5000/5500/7500) protocol in the list, and fill in the PLC IP address, the
port is PLC port no. set in the PLC software.
4. Please keep the communication parameters as default, if the communicate status regsiter
is selected,
PSW256~PSW259 respectively indicate communication successful times, failed times,
225
overtime times, error times. User can set the register address as needs.
5. click next to finish the settings and enter screen edit interface. Put a data input button on
the screen, and choose the keyence KV5000 in the device list.
Fig 1
225
Fig 2
225
2.56 LG XGT
Communication
Series name Cable making PLC model selection in touchwin
type
LG XGT series RJ45 Fig 1 or 2 LG XGT protocol
PLC settings:
Open the PLC software, set the PLC IP to 192.168.6.10 for example.
HMI settings:
1. choose HMI model TN(-ET), TG(-ET) or TE(-ET), click next, then choose net device,
fill in the IP address of HMI. The HMI IP cannot be conflict with other devices in the
network. The HMI IP is set to 192.168.6.11 for example.
2. right click the net device, build a new project, and name it as LG XGT.
225
3. choose LG XGT series protocol in the list, and fill in the PLC IP address, the port is PLC
port no. set in the PLC software.
4. Please keep the communication parameters as default, if the communicate status regsiter
is selected,
PSW256~PSW259 respectively indicate communication successful times, failed times,
overtime times, error times. User can set the register address as needs.
5. click next to finish the settings and enter screen edit interface. Put a data input button on
the screen, and choose the LG XGT in the device list.
225
2.56.3 Cable making
Fig 1
225
Fig 2
225
0.0~65535.F Bit Relay
ZR 0~65535 Word/DWord Data register
0.0~65535.F Bit Relay
TS 0~65535 Word/DWord Timer set value
CS 0~65535 Word/DWord Counter set value
2.57 Haiwell
Communication
Series name Cable making The PLC model in touchwin
type
Haiwell PLC RJ45 Fig 1 or 2 Haiwellbus TCP protocol
2.57.2 Parameters
PLC settings:
Open the PLC software, set the PLC IP to 192.168.1.111 for example.
HMI settings:
1. choose HMI model TN(-ET), TG(-ET) or TE(-ET), click next, then choose net device,
fill in the IP address of HMI. The HMI IP cannot be conflict with other devices in the
network. The HMI IP is set to 192.168.1.11 for example.
2. right click the net device, build a new project, and name it as Haiwellbus TCP.
225
3. choose Haiwellbus TCP protocol in the list, and fill in the PLC IP address, the port is PLC
port no. set in the PLC software.
4. Please keep the communication parameters as default, if the communicate status regsiter
is selected,
PSW256~PSW259 respectively indicate communication successful times, failed times,
225
overtime times, error times. User can set the register address as needs.
5. click next to finish the settings and enter screen edit interface. Put a data input button on
the screen, and choose the Haiwellbus tcp in the device list.
Fig 1
225
Fig 2
225
Que esse conteúdo tenha agregado valor e conhecimento pra você!
NOSSAS FILIAIS
225