Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Manual IHM XINJE de Conectividade Com PLC Diversas Marcas

Download as pdf or txt
Download as pdf or txt
You are on page 1of 225

HMI connection manual

i
CATALOG
1 SERIAL PORT OF HMI .................................................................................................................... 1

1.1 Download port .......................................................................................................................... 1


1.2 PLC port ................................................................................................................................... 3
1.3 Expand port .............................................................................................................................. 3
1.4 Ethernet port ............................................................................................................................ 5

2 THE CONNECTION OF PLC AND HMI ............................................................................................ 8

2.1 XINJE FC series PLC .............................................................................................................. 8


2.1.1Model .............................................................................................................................. 8
2.1.2 Parameters .................................................................................................................... 8
2.1.3 Cable making ................................................................................................................. 8
2.1.4 Device address .............................................................................................................. 9
2.2 XINJE XC series PLC ............................................................................................................ 10
2.2.1 Model ........................................................................................................................... 10
2.2.2 Parameters .................................................................................................................. 10
2.2.3 Cable making ................................................................................................................ 11
2.2.4 Device address ............................................................................................................ 12
2.3 Mitsubishi FXseries PLC ........................................................................................................ 14
2.3.1Model ............................................................................................................................ 14
2.3.2 Parameters .................................................................................................................. 14
2.3.3 Cable making ............................................................................................................... 15
2.3.4 Device address ............................................................................................................ 16
2.4 Mitsubishi FX3U/G series PLC .............................................................................................. 17
2.4 .1 Model .......................................................................................................................... 17
2.4 .2 Parameters ................................................................................................................. 17
2.4 .3 Cable making .............................................................................................................. 18
2.4 .4 Device address ........................................................................................................... 18
2.5 Mitsubishi FX BD series PLC (RS232/485) ........................................................................... 20
2.5.1 Device type .................................................................................................................. 20
2.5.2 Parameters .................................................................................................................. 20
2.5.3 Cable making ............................................................................................................... 21
2.5.3 Device address ............................................................................................................ 22
2.6 Mitsubishi Q series PLC......................................................................................................... 23
2.6 .1 Model .......................................................................................................................... 23
2.6.2 Parameters .................................................................................................................. 23
2.6.3 Cable making ............................................................................................................... 26
2.6.4 Device address ............................................................................................................ 27
2.7 Siemens S7-200 series PLC ............................................................................................... 29
2.7.1Model ............................................................................................................................ 29
2.7.2 Parameters .................................................................................................................. 29
2.7.3 Cable making ............................................................................................................... 30
2.7.4 Device address ............................................................................................................ 30

ii
2.8 Siemens S7-300/400 series PLC........................................................................................... 32
2.8.1 Model ........................................................................................................................... 32
2.8.2 Parameters .................................................................................................................. 32
2.8.3 Cable making ............................................................................................................... 34
2.8.4 Device address ............................................................................................................ 35
2.9 OMRON SYSMAC series PLC............................................................................................ 36
2.9.1 Device model ............................................................................................................... 36
2.9.2 Parameters .................................................................................................................. 37
2.9.3 Cable making ............................................................................................................... 38
2.9.4 Device address ............................................................................................................ 39
2.10 Koyo S series PLC ............................................................................................................... 41
2.10.1 Device model ............................................................................................................. 41
2.10.2 Parameters ................................................................................................................ 42
2.10.3 Cable making ............................................................................................................. 43
2.10.4 Device address .......................................................................................................... 44
2.11 Koyo DL series PLC ............................................................................................................. 45
2.11.1 Device type ................................................................................................................ 45
2.11.2 Parameters................................................................................................................. 45
2.11.3 Cable making ............................................................................................................. 45
2.11.4 Device address .......................................................................................................... 46
2.12 Delta DVP series PLC.......................................................................................................... 47
2.12.1Model .......................................................................................................................... 47
2.12.2 Parameters ................................................................................................................ 47
2.12.3 Cable making ............................................................................................................. 47
2.12.4 Device address .......................................................................................................... 48
2.13 LG Master-K(CPU Direct) series PLC ................................................................................. 49
2.13.1 Device model ............................................................................................................. 49
2.13.2 Parameters ................................................................................................................ 49
2.13.3 Cable making ............................................................................................................. 50
2.13.4 Device address .......................................................................................................... 50
2.14 LG Master-K(Cnet) series PLC ............................................................................................ 52
2.14.1 Device model ............................................................................................................. 52
2.14.2 Parameters ................................................................................................................ 52
2.14.3 Cable making ............................................................................................................. 53
2.14.4 Device address .......................................................................................................... 54
2.15 LG Glofa(Cnet) series PLC .................................................................................................. 55
2.15.1 Device model ............................................................................................................. 55
2.15.2 Parameters ................................................................................................................ 55
2.15.3 Cable making ............................................................................................................. 57
2.15.4 Device address .......................................................................................................... 58
2.16 LG XGT(CPU Direct) series PLC......................................................................................... 60
2.16.1 Device model ............................................................................................................. 60
2.16.2 Parameters ................................................................................................................ 60
2.16.3 Cable making ............................................................................................................. 60

iii
2.16.4 Device address .......................................................................................................... 61
2.17 Matsushita MEWNET FP series PLC .................................................................................. 62
2.17.1Device model .............................................................................................................. 62
2.17.2 Parameters ................................................................................................................ 63
2.17.3 Cable making ............................................................................................................. 64
2.17.4 Device address .......................................................................................................... 65
2.18 Schneider PLC .................................................................................................................. 67
2.18.1Device model .............................................................................................................. 67
2.18.2 Parameters ................................................................................................................ 67
2.18.3 Cable making ............................................................................................................. 69
2.18.4 Device address .......................................................................................................... 69
2.19 Fatek FB series PLC ............................................................................................................ 70
2.19.1 Device model ............................................................................................................. 70
2.19.2 Parameters ................................................................................................................ 70
2.19.3 Cable making ............................................................................................................. 71
2.19.4 Device address .......................................................................................................... 72
2.20 Vigor VIGOR PLC ................................................................................................................ 73
2.20.1 Device model ............................................................................................................. 73
2.20.2 Parameters ................................................................................................................ 73
2.20.3 Cable making ............................................................................................................. 73
2.20.4 Device address .......................................................................................................... 75
2.21 Fuji SPB series PLC ............................................................................................................ 76
2.21.1 Device model ............................................................................................................. 76
2.21.2 Parameters ................................................................................................................ 76
2.21.3 Cable making ............................................................................................................. 76
2.21.4 Device address .......................................................................................................... 77
2.22 Keyence KV series PLC....................................................................................................... 79
2.22.1Device model .............................................................................................................. 79
2.22.2 Parameters ................................................................................................................ 79
2.22.3 Cable making ............................................................................................................. 79
2.22.4 Device address .......................................................................................................... 81
2.23 Emerson EC20 series PLC .................................................................................................. 82
2.23.1Device model .............................................................................................................. 82
2.23.2 Parameters ................................................................................................................ 82
2.23.3 Cable making ............................................................................................................. 82
2.23.4 Device address .......................................................................................................... 83
2.24 OEMax NX7 series PLC ...................................................................................................... 84
2.24.1 Device model ............................................................................................................. 84
2.24.2 Device address .......................................................................................................... 84
2.24.3 Cable making ............................................................................................................. 84
2.24.4 Device address .......................................................................................................... 86
2.25 Bosch Rexroth IndraControl L40 series PLC....................................................................... 87
2.25.1 Device model ............................................................................................................. 87
2.25.2 Parameters ................................................................................................................ 87

iv
2.25.3 Cable making ............................................................................................................. 87
2.25.4 Device address .......................................................................................................... 88
2.26 OPTO 22 SNAP series PLC ................................................................................................ 89
2.26.1 Device model ............................................................................................................. 89
2.26.2 Parameters ................................................................................................................ 89
2.26.3 Cable making ............................................................................................................. 89
2.26.4 Device address .......................................................................................................... 90
2.27 SAIA-Burgess PCD series PLC ........................................................................................... 91
2.27.1 Device model ............................................................................................................. 91
2.27.2 Parameters ................................................................................................................ 92
2.27.3 Cable making ............................................................................................................. 92
2.27.4 Device address .......................................................................................................... 96
2.28 Allen-Bradley series PLC ..................................................................................................... 96
2.28.1 Device model ............................................................................................................. 96
2.28.2 Parameters ................................................................................................................ 96
2.28.3 Cable making ............................................................................................................. 99
2.28.4 Device address .......................................................................................................... 99
2.29 Xinje V5 series inverter ...................................................................................................... 101
2.29.1 Device model ........................................................................................................... 101
2.29.2 Parameters .............................................................................................................. 101
2.29.3 Cable making ........................................................................................................... 102
2.30 SHIMADEN ........................................................................................................................ 103
2.30.1 Device model ........................................................................................................... 103
2.30.2 Parameters .............................................................................................................. 103
2.30.3 Cable making ........................................................................................................... 103
2.30.4 Device address ........................................................................................................ 104
2.31 Modbus RTU (panel is Master) .......................................................................................... 105
2.31.1 Device model ........................................................................................................... 105
2.31.2 Parameters .............................................................................................................. 105
2.31.3 Cable making ........................................................................................................... 105
2.31.4 Device address ........................................................................................................ 106
2.32 Modbus ASCII (Panel is Master)........................................................................................ 107
2.32.1Device model ............................................................................................................ 107
2.32.2 Parameters .............................................................................................................. 107
2.32.3 Cable making ........................................................................................................... 107
2.32.4 Device address ........................................................................................................ 108
2.33 Modbus slave (panel is Slave) ........................................................................................... 109
2.33.1Device model ............................................................................................................ 109
2.33.2 Parameters .............................................................................................................. 109
2.33.3 Cable making ........................................................................................................... 109
2.33.4 Device address .........................................................................................................110
2.34 ABB PLC ............................................................................................................................. 111
2.34.1Device model ............................................................................................................. 111
2.34.2 Parameters ............................................................................................................... 111

v
2.34.3 Cable making ............................................................................................................112
2.34.4 Device address .........................................................................................................113
2.35 IDEC ....................................................................................................................................114
2.35.1 Device type ...............................................................................................................114
2.35.2 Parameters ...............................................................................................................114
2.35.3 Cable making ............................................................................................................114
2.35.4 Device address .........................................................................................................115
2.36 TAIAN ..................................................................................................................................116
2.36.1 Device type ...............................................................................................................116
2.36.2 Parameters ...............................................................................................................117
2.36.3 Cable making ............................................................................................................117
2.36.4 Device address .........................................................................................................118
2.37 YuDian AI ............................................................................................................................119
2.37.1 Device address .........................................................................................................119
2.37.2 Parameters ...............................................................................................................119
2.37.3 Cable making ............................................................................................................119
2.37.4 Device address ........................................................................................................ 120
2.38 Inovance PLC..................................................................................................................... 121
2.38.1 Device type .............................................................................................................. 121
2.38.2 Parameter ................................................................................................................ 121
2.38.3 Cable making ........................................................................................................... 122
2.38.4 Device address ........................................................................................................ 122
2.39 HaiWell PLC .................................................................................................................... 124
2.39.1 Device type .............................................................................................................. 124
2.39.2 Parameters .............................................................................................................. 124
2.39.3 Cable making ........................................................................................................... 124
2.39.4 Device address ........................................................................................................ 125
2.40 Hollias PLC ...................................................................................................................... 126
2.40.1 Device type .............................................................................................................. 126
2.40.2 Parameters .............................................................................................................. 126
2.40.3 Cable making ........................................................................................................... 126
2.40.4 Device address ........................................................................................................ 127
2.41 Delta (temperature controller) ......................................................................................... 128
2.41.1 Device type .............................................................................................................. 128
2.41.2 Parameters .............................................................................................................. 128
2.41.3 Cable making ........................................................................................................... 128
2.41.4 Device address ........................................................................................................ 129
2.42 Siemens S7-1200 ............................................................................................................ 130
2.42.1 Device type .............................................................................................................. 130
2.42.2 Parameters .............................................................................................................. 130
2.42.3 Cable making ........................................................................................................... 135
2.42.4 Device address ........................................................................................................ 136
2.43 Mitsubishi FR series inverter ............................................................................................. 137
2.43.1 Device type .............................................................................................................. 137

vi
2.43.2 Parameters .............................................................................................................. 137
2.43.3 Cable making ........................................................................................................... 140
2.44 Sanken VM06 inverter ....................................................................................................... 141
2.44.1 Device type .............................................................................................................. 141
2.44.2 Parameters .............................................................................................................. 141
2.44.3 Cable making ........................................................................................................... 143
2.44.4 Device address ........................................................................................................ 143
2.45 XINJE XD/XE series .......................................................................................................... 145
2.45.1 Device type .............................................................................................................. 145
2.45.2 Parameters .............................................................................................................. 145
2.45.3 Cable making ........................................................................................................... 146
2.45.4 Device address ........................................................................................................ 147
2.46 LG XGB series PLC ........................................................................................................... 149
2.46.1 Device type .............................................................................................................. 149
2.46.2 Parameters .............................................................................................................. 149
2.46.3 Cable making ........................................................................................................... 153
2.46.4 Device address ........................................................................................................ 154
2.47 Koyo Click series ............................................................................................................... 155
2.47.1 Device type .............................................................................................................. 155
2.47.2 Parameter setting .................................................................................................... 155
2.47.3 Cable making ........................................................................................................... 156
2.47.4 Device address ........................................................................................................ 156
2.48 Mitsubishi Melsec protocol ................................................................................................. 157
2.48.1 Device type .............................................................................................................. 157
2.48.2 Parameter settings................................................................................................... 158
2.48.3 Cable making ........................................................................................................... 161
2.48.4 Device address ........................................................................................................ 162
2.49 Free type (panel is slave)................................................................................................... 162
2.49.1 Device type .............................................................................................................. 162
2.49.2 Parameter setting .................................................................................................... 163
2.49.3 Cable making ........................................................................................................... 165
2.49.4 Device address ........................................................................................................ 166
2.50 Modbus-TCP device .......................................................................................................... 166
2.50.1 Device type .............................................................................................................. 166
2.50.2 Parameter setting .................................................................................................... 166
2.50.3 Cable making ........................................................................................................... 172
2.50.4 Device address ........................................................................................................ 173
2.51 Mitsubishi FX5U series ...................................................................................................... 173
2.51.1 Device type .............................................................................................................. 173
2.51.2 Parameter setting .................................................................................................... 173
2.51.3 Cable making ........................................................................................................... 177
2.51.4 Device address ........................................................................................................ 178
2.52 Siemens S7-200 smart series............................................................................................ 179
2.52.1 Device type .............................................................................................................. 179

vii
2.52.2 Parameter setting .................................................................................................... 179
2.52.3 Cable making ........................................................................................................... 182
2.52.4 Device address ........................................................................................................ 184
2.53 Siemens S7-300 series ...................................................................................................... 185
2.53.1 Device type .............................................................................................................. 185
2.53.2 Parameter setting .................................................................................................... 185
2.53.3 Cable making ........................................................................................................... 188
2.53.4 Device address ........................................................................................................ 190
2.54 X-NET communication ....................................................................................................... 191
2.54.1 Device type .............................................................................................................. 191
2.54.2 HMI setting............................................................................................................... 191
2.54.3 XD series PLC setting (PLC hardware V3.2.2 and up) ........................................... 197
2.54.4 Cable making ........................................................................................................... 200
2.54.5 Device address ........................................................................................................ 202
2.55 Keyence KV5000 ............................................................................................................... 204
2.55.1 Device type .............................................................................................................. 204
2.55.2 Parameter setting .................................................................................................... 204
2.55.3 Cable making ........................................................................................................... 207
2.55.4 Device address ........................................................................................................ 208
2.56 LG XGT .............................................................................................................................. 209
2.56.1 Device type .............................................................................................................. 209
2.56.2 Parameter setting .................................................................................................... 209
2.56.3 Cable making ............................................................................................................211
2.56.4 Device address ........................................................................................................ 212
2.57 Haiwell ................................................................................................................................ 213
2.57.1 Device type .............................................................................................................. 213
2.57.2 Parameters .............................................................................................................. 213
2.57.3 Cable making ........................................................................................................... 215
2.57.4 Device address ........................................................................................................ 216

viii
1 Serial port of HMI
This chapter will introduce the serial port of HMI.

1.1 Download port


The HMI of XINJE TP and TH series are configured PLC port and download port. Next, it will
introduce the port and function. The following diagram is the port of TP460-L.

Download port:
Pin Name Explanation
1 NC Vacant
9 87 6 2 RXD RS232 receive
3 TXD RS232 send
4 A RS485 +
5 GND Ground
6 NC Vacant
5 4 3 2 1 7 B RS485 -
8 NC Vacant
9 NC Vacant

1. Choose the device to communicate with download port


(a) Build a new project in Touchwin software, choose download port device

1
(b) For current project, please set it in the Touchwin software:

2. Mode switching for download port


The default mode of TH series download port is communication. But it is download mode for TP
series. If the download port of TP series needs to switch to communication mode, two pins of the
download port must be shorted. Please see the following diagram.

(1) Cut off the power of TP series HMI, connect pin5 and pin6 of TP download port.

(2) Power on the HMI, take away the connection cable, the download port will be in
communication mode.

Note: 1. if the HMI needs to download program, please restart the HMI.
2. Please connect the pin 5 and 6 directly.

2
1.2 PLC port
PLC port:

Pin Name Explanation


1 TD+ RS422 send -
9 87 6 2 RXD RS232 receive
3 TXD RS232 send
4 A RS485 +
5 GND Ground
6 TD- RS422 send -
5 4 3 2 1 7 B RS485 -
8 RDD- RS422 receive -
9 RDD+ RS422 receive +

For real application, pelase refer to chapter 2 for cable making. Refer to chapter 1.1 for

download port settings.

1.3 Expand port

Expand port:
Pin Definition Explanation
1 A RS485 +
9 87 6 2
3
4
5
6 B RS485 -
5 4 3 2 1 7
8
9
Note: only TH765-NT3/NU3 has this expand port.
1. choose expand port device
(1) Build a new project, click expand port, and choose the device

3
(2) For existed project, click File/setting/device/expand port to set the PLC model.

4
1.4 Ethernet port
RJ45 Ethernet port:
Pin Color Definitio Explanation
8 n
1 Orange
TXD+ Data send +
1 white
2 Orange TXD- Data send -
3 Green
RXD+ Data receive +
white
4 Blue - -
5 Blue
- -
white
6 Green RXD- Data receive -
7 Brown - -
5
white
8 Brown - -
Note: only TG765-ET/TG865-ET/TGA62-ET/TGC65-ET has Ethernet port.
1. Build a new project, choose TG model in the list.

2. Click next, choose net device. Set the IP address of TG series HMI.

6
3. Right click net device, build a new Ethernet device.

Note: this function support local area network, but not support wide area network

7
2 The connection of PLC and HMI
This chapter will introduce the connection between PLC and HMI.
Please don’t pull out or plug the cable when power on, the serial port may be damaged.

2.1 XINJE FC series PLC

2.1.1Model

Serie Connecte Cable


CPU Port Device
s d module making
CPU RS232 Fig1
XC32V2-CPU030427 direct RS485 Xinje FC
FC
-R5 connectio Fig2 series
n

2.1.2 Parameters

HMI parameters:
Parameters Settings Choices for settings Item
PLC type FC series
Port RS232 RS232or RS485
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity Odd parity Odd/even/no parity
Baud rate 9600 4800/38400/9600/115200/19200/187500
Station No. 0 0~255

The default communication parameters of FC: 9600, 8, 1, odd parity, station No.0.

2.1.3 Cable making

(a) Connect to FC series CPU (RS232 port)

8
Fig1
(b) Connect to FC series PLC CPU (RS485 port)

Fig2

2.1.4 Device address

PLC address Range Data type Explanation


X 0~337 Bit External input coil
Y 0~337 Bit External output coil
M 0~383 Bit Internal coil
SM 0~96 Bit Special coil
T 0~128 Bit Timer
C 0~128 Bit Counter
W 0~2047 Word/DWord Data register
FW 0~191 Word/DWord FlashROM register
TW 0~127 Word/ Timer register
CW 0~127 Word/ Counter register
SW 0~111 Word//DWord Special register
WX 0~13 Word//DWord Input coil register
WY 0~13 Word//DWord Output coil register
WM 0~23 Word//DWord Interla coil register

9
2.2 XINJE XC series PLC

2.2.1 Model

Series CPU Connected module Port Cable making Device


CPU direct RS232 Fig1
connection RS485 Fig 2
XC1\XC2\ Xinje XC
XC XC-RS485-BD RS232 Fig 3
XC3\XC5 series
(communication RS485
Fig 4
extension board)

2.2.2 Parameters

HMI parameters:
Parameter Recommend settings Choices of settings Item
PLC type XC series FC/XC series
Port RS232 RS232 or RS485
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity Even parity Even/odd/no parity
Baud rate 19200 4800/38400/9600/115200/19200/187500
Station No. 1 0~255

The default communication parameters of XC: 19200, 8, 1, even, station No.1.


PLC settings:
Open XCPpro software:

10
2.2.3 Cable making

(a) Connect to XC series PLC CPU (RS232 port)

Fig1

(b) Connect to XC series PLC CPU (RS485 port)

Fig2

(c) Connect via XC-RS485-BD (RS232)

11
Fig3

(d) Connect via XC-RS485-BD (RS485)

Fig4

2.2.4 Device address

PLC address Range Data type Explanation


X 0~543 Bit External input coil
Y 0~543 Bit External input coil
M 0~7999 Bit Internal coil
S 0~1023 Bit Internal coil
M8XXX 0~511 Bit Internal special register
T 0~639 Bit Timer
C 0~639 Bit Counter
D 0~7999 Word//DWord Data register
TD 0~639 Word//DWord Timer register
CD 0~639 Word//DWord Counter register
D8XXX 0~511 Word//DWord Special register
FD 0~1535 Word//DWord FlashROM register
FD8XXX 0~511 Word//DWord Output register
ED 0~36862 Word//DWord Extend register
DM 7984 Word Data register

12
DX 0~52 Word Data register
DY 0~52 Word Data register
DS 0~1008 Word Data register
DM8XXX 0~496 Word Data register
DT 0~603 Word Data register
DC 0~619 Word Data register
ID 0~9999 Word//DWord Analog input
QD 0~9999 Word//DWord Analog output

13
2.3 Mitsubishi FXseries PLC

2.3.1Model

Connected Cable
Series CPU Port Device
module making
FX0N CPU direct Mitsubishi FX
RS422 Fig1
FX1N connection series PLC
FX2N RS232-BD RS232 Fig 2
Mitsubishi
FX1S RS485\422-B RS485 Fig 3
FXBD(232\485)
FX3U D RS422
FX
FX3G
CPU direct Mitsubishi FX
FX0 RS422 Fig 1
connection series PLC
FX1
CPU direct Mitsubishi FX
FX2 RS422 Fig 4
connection series PLC

2.3.2 Parameters

HMI settings:
Parameter Recommend Choices of settings Item
settings
PLC type FX series
Dat bit 7 7 or 8
Stop bit 1 1 or 2
Parity Even parity Even/odd/no parity
Baud rate 9600 4800/9600/19200/38400/56000/57600/11
5200/187500
Station No. 0 0~255
The default parameters of Mitsubishi FX series PLC: 9600, 7, 1, even, station No.0.

PLC settings:

14
2.3.3 Cable making

(a) FX1N\2N\3U\3G\1S series PLC, RS422 port:

Fig1

(b) FX series PLC uses RS232-BD:

Fig2

(c) FX series PLC uses RS485BD:

Fig3

15
(d) FX2 series PLC:

Fig4

2.3.4 Device address

PLC address Range Data type Explanation


X 0~177 Bit External input coil
Y 0~177 Bit External output coil
M 0~8255 Bit Internal coil
S 0~999 Bit Stepper coil
T 0~255 Bit Timer
C 0~255 Bit Counter
C16 0~199 Word/DWord 16-bit counter
C32 200~255 DWord 32-bit counter
D 0~8255 Word/DWord Data register
T 0~255 Word/DWord Current value
X 0~177 Word/DWord Data register
Y 0~177 Word/DWord Data register
M 0~8255 Word/DWord Data register
S 0~999 Word/DWord Data register

16
2.4 Mitsubishi FX3U/G series PLC

2.4 .1 Model

Choose PLC type


Connected
Series CPU Port Cable in Touchwin
module
software

FX3U Mitsubishi
FX CPU RS422 Fig 1
FX3G FX3U/G

2.4 .2 Parameters

HMI settings:
Parameter Recommended Choices of settings Notes
settings
PLC type Mitsubishi
FX3U/G series
Data bit 7
Stop bit 1
Parity Even parity
Baud rate 9600 4800/9600/19200/38400/56000/57600/115200/187500
Station 0
no.

The default parameters of Mitsubishi FX3U/G series PLC: 9600, 7, 1, even parity, station no.0

PLC settings:

17
2.4 .3 Cable making

(a) FX3U\3G series PLC RS422:

2.4 .4 Device address

PLC address Range Type Explanation


X 0~177 Bit External input terminal
Y 0~177 Bit External output terminal
M 0~8255 Bit Internal auxiliary coil

18
S 0~999 Bit Stepper coil
T 0~255 Bit Timer
C 0~255 Bit Counter
C16 0~199 Word/DWord 16-bit counter
C32 200~255 DWord 32-bit counter
D 0~8255 Word/DWord Data register
T 0~255 Word/DWord Timer current value
X 0~177 Word/DWord Used as data register
Y 0~177 Word/DWord Used as data register
M 0~8255 Word/DWord Used as data register
S 0~999 Word/DWord Used as data register

19
2.5 Mitsubishi FX BD series PLC (RS232/485)

2.5.1 Device type

Connected PLC type in


Series CPU Port Cable
module Touchwin software

FX0N/1N/2 232-BD RS232 Fig1


N Mitsubishi FX
FX
FX1S BD(232\485)
FX3U/3G 485-BD RS485 Fig2

Note:
1. Do not hot plug the device!
2. The driver of 485-BD supports multi-station.

2.5.2 Parameters

HMI settings:
Paramete Recommend settings Choices of settings Notes
rs
PLC type Mitsubishi FX BD(232\485)
Data bit 7
Stop bit 1
Parity Even parity
Baud rate 9600 9600/19200/38400/56000/57600
/
115200/187500
Station 0 0~255
no.
The default paramreters of Mitsubishi FX BD (232/485): 9600, 7, 1, even parity, station no.0

PLC settings:

20
Note:
1. Please choose RS232 as H/W type when using 232-BD.
2. Please re-power on the PLC after changing the parameters.

2.5.3 Cable making

(a) FX series PLC RS232-BD:

Fig1

(b) FX series PLC RS485-BD:

21
Fig2

2.5.3 Device address

PLC Range Data type Explanation


address
X 0~177 Bit External input terminal
Y 0~177 Bit External output terminal
M 0~8255 Bit Internal auxiliary coil
S 0~999 Bi Stepper coil
T 0~255 Bit Timer
C 0~255 Bit Counter
C16 0~199 Word/DWord 16-bit counter
C32 200~255 DWord 32-bit counter
D 0~8255 Word/DWord Data register
T 0~255 Word/DWord Current value
X 0~177 Word/DWord Used as data register
Y 0~177 Word/DWord Used as data register
M 0~8255 Word/DWord Used as data register
S 0~999 Word/DWord Used as data register

22
2.6 Mitsubishi Q series PLC

2.6 .1 Model

MELSEC-Q series include the CPU unit of Q00, Q01, Q00U and so on. They can connect to the HMI
via programmable port or communication module (QJ71C24N).

Cable
Series CPU Connected module Port Device
making
Q00
CPU direct Mitsubishi Q
Q01 RS232 Fig 1
connection series
Q00U
Q00J,Q00,
Q
Q01,Q02H, RS232 Fig 2
Serial communication Mitsubishi Q
Q06H,Q12H,
module QJ71C24 series
Q25H,Q12PH, RS422 Fig 3
Q25PH

2.6.2 Parameters

HMI settings:
Parameter Recommend Choices of settings Item
setting
PLC type Q series
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity Odd parity Even/odd/no parity
Baud rate 19200 4800/9600/19200/38400/56000/57600/115200/187500
Station 0 0~255
No.
The default parameter of Q series PLC: 19200, 8, 1, odd parity, station No.0.

PLC settings:
1. Q01\Q00 PLC:

23
2.QJ71C24N serial port module
QJ71C24N can connect to CPU and communicate with other devices. Such as Q02CPU, the
settings are as the following:
PLC software version v8.26
(a) Double click PLC parameter, choose I/O assignment:

(b) Change the type of item1 to intelli.

(c) Click “switch setting” :

24
(d) Set the parameter as the following window:

(e) Click End button to finish the settings, then repower on the PLC.

PLC software version v8.8:


For QJ71C24 module RS232, please set the parameter of CH1:

25
For QJ71C24 module RS422, please set the parameter of CH2:

2.6.3 Cable making

(a) Q series PLC CPU unit, RS232 port:

Fig1

26
(b) Q series PLC uses QJ71C24N module RS232:

Fig2

(c) Q series PLC uses QJ71C24 module RS422:

Fig3

2.6.4 Device address

PLC address Range Data type Explanation


X 0~177 Bit External input coil
Y 0~177 Bit External output coil
M 0~8255 Bit Internal coil
S 0~999 Bit Stepper coil
T 0~255 Bit Timer
C 0~255 Bit Counter
C16 0~199 Word/DWord 16-bit counter
C32 200~255 DWord 32-bit counter
D 0~8255 Word/DWord Data register
T 0~255 Word/DWord Current value
X 0~177 Word/DWord Data register

27
Y 0~177 Word/DWord Data register
M 0~8255 Word/DWord Data register
S 0~999 Word/DWord Data register

28
2.7 Siemens S7-200 series PLC

2.7.1Model

Seris CPU Connected module Port Cable Device


CPU212,
CPU221,
Connect CPU RS485 port Siemens
S7-200 CPU222, RS485 Fig 1
directly S7-200
CPU224,
CPU226

S7-200 Siemens
Smart series CPU directly connect RS485 Fig1
smart S7-200

2.7.2 Parameters

HMI:
Parameters Recommend Choices of settings Item
settings
PLC type S7-200
Port RS485
Data bit 8
Stop 1
Parity Even parity
Baud rate 9600 9600/19200/187500
Station no. 2 Must use recommend
settings

The default communication parameters of Siemens S7-200 series PLC: 9600, 8, even parity,

station No.2.

PLC settings:

29
Notes:
1. Siemens PLC has 3 kinds of registers: 8-bitVB, 16-bit VW and 32-bit VD.
2. The space of registers are overlapped, the address of VW must be even numbers, for
example: VW0,VW2…., the address of VD must be the multiple of 4, such as VD0,VD4,
VD8…..
3.For Data block PSW single word → VW single word: as the high byte and low byte problem,
the received data maybe dislocated, please use register copy function.
4.For data block PSW single word → VD double words: as the unit is different, cannot trasfer
the data like this, please use register copy function.

2.7.3 Cable making

HMI connects to S7-200 via RS485:

Fig1

2.7.4 Device address

SIMATIC S7-200 series

30
PLC address Range Data type Explanation
VB 0~4095 Byte variable byte data register
VW 0~4095 Word variable word data register
VD 0~4095 DWord variable double word data register
IB 0~15 Byte External input byte reflection register
IW 0~15 Word External input word reflection register
ID 0~15 DWord External input double words reflection
register
QB 0~15 Byte External output byte reflection register
QW 0~15 Word External output word reflection register
QD 0~15 DWord External output double words reflection
register
MB 0~31 Byte Internal auxiliary byte register
MW 0~31 Word Internal auxiliary word register
MD 0~31 DWord Internal auxiliary double words register
SMB 0~299 Byte Internal special auxiliary byte register
SMW 0~299 Word Internal special auxiliary word register
SMD 0~299 DWord Internal special auxiliary double words
register
SB 0~31 Byte Special auxiliary byte register
SW 0~31 Word Special auxiliary word register
SD 0~31 DWord Special auxiliary double words register
T 0~255 Word Register
C 0~255 Word Register
M 0~31 Bit Bit register
V 0~4095 Bit Variable register
I 0~15 Bit External input coil
Q 0~15 Bit External output coil
SM 0~299 Bit Special relay
S 0~31 Bit Sequence relay
T 0~255 Bit Timer
C 0~255 Bit Counter

31
2.8 Siemens S7-300/400 series PLC

2.8.1 Model

SIMATIC S7-300/400 PLC (connect to CPU directly)


Series CPU Connected module Port Cable Device
S7-300 CPU312,CPU314,
Siemens SIMATIC
CPU315 RS485 port of CPU
RS485 fig 1 S7-300/400
S7-400 CPU412-1,CPU412-2,
PLC
CPU414-2,

2.8.2 Parameters

HMI settings:
Parameter Recommend Choice of settings Note
settings
PLC type S7-300/400
Port RS485
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity Even parity Even/odd/no parity
Baud rate 19200 4800/38400/9600/115200/19200/187500
Station 2 Please use
no. recommend settings
The default parameters of Siemens S7-300\400: 19200, 8, even parity, station No.2.

PLC settings:

32
Communication notes for S7-300:
1. Siemens baud rate must set to 19200 kbps; don’t set the parameters of PG/PC adapter.
2. Don’t modify the “panel station no.” in the Touchwin software.

33
3. Cable: no need PG/PC adapter;
4. Please define the DB register in the PLC when testing the communication.
5. Please note that the port will be operated in PLC program by accident.
6. The default station No. of S7-300 is 2, please don’t modify it.
Example: MPI port of S7-300 connects to HMI, the PLC connects to SCADA software via
Ethernet module, PLC station no. is 8, module station no. is 3, HMI station no. is 0. The result is
that communication between SCADA and PLC will be cut off. Because the HMI cannot find
other devices and modules cannot be inserted in. please change the PLC station no. to 2.
These devices can form a loop:

2.8.3 Cable making

HMI connects to S7-300/400 via RS485:

34
SIEMENS PLC
S7-200/300/400
HMI 9-pin female port
PPI 9-pin male port
Pin Name Pin Name
4 AI 3 A
5 GND 8 B
7 BI 5 GND
Fig1

2.8.4 Device address

SIMATIC S7-300/400
PLC type Range Data type Explanation
I 0~9999 Byte/Word/DWord External input register
Q 0~9999 Byte/Word/DWord External output register
M 0~9999 Byte/Word/DWord Internal auxiliary register
DB0~DB20 0~9999 Byte/Word/DWord Data register
I 0~9999 Bit External input coil
Q 0~9999 Bit External output coil
M 0~9999 Bit Internal auxiliary relay
DB0~DB20 0~9999 Bit Internal auxiliary relay

35
2.9 OMRON SYSMAC series PLC
OMRON CPM1A, CQM1-CPU series CPU cannot support RS232. It can connect to the Touchwin
HMI via
CPM1-CIF01 adapter and modules including C500-LK203, C120-LK201-V1, C500-LK201-V1. The
PLC uses Hostlink protocol when communicating. Please change the PLC startup choice to
MONITOR RUN.

2.9.1 Device model

The PLC
Connected Communication device in
Series CPU Cable
module mode TouchWin

CP CP1E-30N CPU direct


RS232 Fig 1
CP1H connection
CP1L Module
RS485 Fig 2
CP1W-CIF11
Module
RS422 Fig 3
CP1W-CIF11
CJ CJ1
CJ1G-CPU44 CPU direct
RS232 Fig 1
CJ1G-CPU45 connection
CJ2M-CPU11 Omron
CS1 CS1H-CPU63/64/65/66/67 CP/CJ/CS
CS1G-CPU42/43/44/45
CS1G-CPU42H
CS1G-CPU43H
CS1G-CPU44H
CPU direct
CS1G-CPU45H RS232 Fig 1
connection
CS1H-CPU63H
CS1H-CPU64H
CS1H-CPU65H
CS1H-CPU66H
CS1H-CPU67H

The PLC
Communication device in
Series CPU Connected module Cable
mode TouchWin

36
C C200HE
CPU direct connection
C200HX
C1000HF C500-LK203 (communication
module)
C120-LK201-V1(communication
RS232 Fig 1
module)
C500-LK201-V1(communication
C2000
module)
C500-LK203(communication Omron
module) CPM/CQM
CPM CPM2A
CPM2AE
CPU direct connection
CPM2AH-40CDR-A
CPM1H
CPM1A OMRON CIF01 (RS232) RS232 Fig 1
Communication adapter
CQM CQM1H-CPU21 CPU direct connection
CQM1-CPU OMRON CIF01 (RS232)
Communication adapter

2.9.2 Parameters

HMI:
The default parameters of OMRON CP/CJ/CS series PLC: 9600, 7, 2, even parity, station no.0.
The default parameters of OMRON CPM/CQM series PLC: 9600, 7, 2, even parity, station no.0.

Parameter Recommended settings Choices of settings Notes


PLC type OMRON CPM/CQM series OMRON CP/CJ/CS series
OMRON CP/CJ/CS series OMRON CPM/CQM series
Port RS232 RS232/RS485
Data bit 7 7 or 8
Stop bit 2 1 or 2
Parity Even parity Even/odd/ no parity
Baud rate 9600 4800/38400/9600/115200
/19200/187500
Station no. 0 0~255

37
2.9.3 Cable making

(a) CPU RS232 port:

OMROM PLC
CPU CPM1-CIF01/C500-LK203
C120-LK201-V1/C500-LK203
HMI 9-pin female port RS232 9-pin male port

Pin Name Pin Name


2 RXD1 3 RD
3 TXD1 2 SD
5 GND 9 GND
4 RTS
5 CTS

Fig1

(b) Through module CP1W-CIF11 RS485:

Fig2

Note: If OMRON RS485 module CPIW-CIF11 uses 485-2 connection mode, turn OFF the SW1
switch on the module, turn ON SW2, 3, 5, 6. SW4 is selectable.

(c) Through the module CP1W-CIF11 RS422:

Fig3

38
Note: If OMRON RS485 module CP1W-CIF11 uses RS422 connection mode, turn OFF the
SW1~6 on the module.

2.9.4 Device address

(a) SYSMAC CPM/CQM series


PLC address Range Data type Explanation
IR 0~65535 Bit I/O and internal relay
SR 244~65535 Bit Relay
HR 0~65535 Bit Holding relay
AR 0~65535 Bit Auxiliary relay
LR 0~65535 Bit Link relay
PV 0~65535 Bit Current value of timer and
counter
TC 0~65535 Bit Timer and counter
IR 0~65535 Word/DWor Register
d
SR 244~65535 Word/DWor Register
d
HR 0~65535 Word/DWor Register
d
AR 0~65535 Word/DWor Register
d
LR 0~65535 Word/DWor Register
d
PV 0~65535 Word/DWor Register
d
TC 0~65535 Word/DWor Register
d
DM 0~65535 Word/DWor Data register (single/double
d words)
(b) SYSMAC CP/CJ/CS series

PLC address Range Data type Explanation


CIO 0~9999 Bit
D 0~99999 Bit
H 0~9999 Bit
W 0~9999 Bit
A 0~9999 Bit
T 0~9999 Bit Timer
C 0~9999 Bit Counter

39
CIO 0~9999 Word/DWor Register
d
D 0~99999 Word/DWor Register
d
H 0~9999 Word/DWor Register
d
W 0~9999 Word/DWor Register
d
A 0~9999 Word/DWor Register
d
T 0~9999 Word/DWor Register
d
C 0~9999 Word/DWor Register
d

40
2.10 Koyo S series PLC
Koyo KOSTA-S and Direct-Logic series PLC

2.10.1 Device model

(a) Kostac S series SH\SM\SN PLC (direct connect to the CPU module)

Series CPU Connected module Port Cable Device

SH series SH-48RS
CPU
SM series SM24-T RS232 Fig1
SN series
Koyo S series
SU-6 RS232 Fig1
CPU
RS232 Fig1
SU-6B
RS422 Fig3
Note: Koyo SH-48RS doesn’t have Run, Stop switch, but only have one AMP port.

(b) Koyo Kostac S series SG-8, SU-5, SU-6, SR-21, SR-22… PLC (use communication module)

CPU Connected module Port Cable Device

RS232 Fig 1
SG-8 G01-DM communication unit
RS422 Fig 3
SU-5 U01-DM communication unit
RS232 Fig 1 Koyo S series
SU-6 U01-DM communication unit
SR-21 E-02DM-R1 communication unit
RS422 Fig 3
SR-22

(c) Koyo Direct Logic series DL05, DL250…PLC (connect to CPU directly)
Series CPU Connected module Port Cable Device

DL05
DL105
DL230
Connect to RJ-11port(RS232) of CPU
DL240 RS232 Fig 2
Direct Logic Koyo S series
DL250
DL350
DL450
DL250 Connect to the port of CPU RS422 Fig 3

41
DL430 Connect to the port of CPU
DL440
RS232 Fig 2
DL450
DL350
Note: port2 of DL250CPU has RS232 and RS422; please indentify them when making the
cable.

2.10.2 Parameters

HMI:
Parameter Recommend settings Choices of settings Notes
PLC Koyo S series PLC
Port RS232 RS232 or RS422
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity Odd parity Even/odd/no parity
Baud rate 9600 4800/38400/9600/115200/19200/187500
Station no. 0 0~255
The default communication parameters of Koyo S series PLC: 9600, 8, 1, odd parity, station
no.0.

PLC:

42
Note: 1. Koyo K protocol cannot modify station no., the station no. is 0 in the HMI.
2. The register address starts from R2000.

2.10.3 Cable making

(a) RS232 25-pin port on CPU or communication unit:

Fig1

RJ-11 6-pin RS232 female port on the CPU:

654 3 2 1

Fig2

RS422 connection:

43
Fig3

2.10.4 Device address

PLC address Range Data type Explanation


M 0~777 Bit Internal auxiliary coil
I 0~777 Bit External input coil
Q 0~777 Bit External output coil
SP 0~777 Bit Internal auxiliary coil
T 0~777 Bit Timer
C 0~777 Bit Counter
S 0~777 Bit Stepper coil
R 0~41200 Word/DWor Data register
d

44
2.11 Koyo DL series PLC

2.11.1 Device type

Koyo Direct Logic series DL05, DL250 PLC (direct connect to CPU)
Series CPU Connected Port Cable Choose PLC type in
module Touchwin software
DL05
DL105 Connect to
DL230 CPU RJ-11 RS232 Fig 1
DL240 port
Direct
DL250 Koyo DL series
Logic
DL350
DL430 Connect to
RS422 Fig 2
DL440 CPU com port
DL450
Note: the port2 of DL250 has RS232 and RS422, please indentify the cable connection for them.

2.11.2 Parameters

HMI settings:
Parameter Recommend Choices of settings Note
s settings
PLC type Koyo DL series
Port RS232 RS232/RS422
Data bit 8 7/8
Stop bit 1 1/2
Parity Odd parity Even /odd /no parity
Baud rate 9600 4800/38400/9600/115200/19200/18750
0
Station no. 0 0-255

2.11.3 Cable making

RS232 Connection:

45
Fig1

RS422 connection:

Fig2

2.11.4 Device address

Device address Range Data type Explanation


V 0~41200 Word/DWord Data register
C 0~777 Bit Counter
X 0~777 Bit Input
Y 0~777 Bit Output
SP 0~777 Bit Auxiliary relay
T 0~777 Bit Timer
CT 0~777 Bit Counter
S 0~777 Bit Auxiliary relay
V 0.0~41200.15 Bit Auxiliary relay

46
2.12 Delta DVP series PLC

2.12.1Model

Delta DVP series CPU Connected module Port Cable Deivce


RS232 Fig 1
ES\EH\EX
RS485 Fig 2
Direct connect to the CPU Delta DVP series
RS232 Fig 1
SS\SA\SC\SX
RS485 Fig 2

2.12.2 Parameters

HMI:
Parameters Recommend settings Choices of settings Notes
PLC type Delta DVP series
Port RS232 RS232 or RS485
Data bit 7 7 or 8
Stop bit 1 1 or 2
Parity Even parity Even/odd/no parity
Baud rate 9600 4800/38400/9600/115200/19200/187500
Station no. 1 0~255
The default communication parameters of Delta DVP series PLC: 9600, 7, 1, even parity, station
no.1.

2.12.3 Cable making

(a) The RS232 port on CPU:

Fig 1

47
(b) RS485 port on the CPU:

Fig2

2.12.4 Device address

PLC address Range Data type Explanation


X 0~377 Bit External input coil
Y 0~377 Bit External output coil
M 0~1279 Bit Internal auxiliary relay
S 0~1023 Bit Stepper coil
T 0~255 Bit Timer
C 0~255 Bit Counter
D 0~1279 Word/DWor Data register
d
TD 0~255 Word/DWor Current value of timer
d
CD 0~255 Word/DWor Current value of counter
d
S 0~1023 Word/DWor Data register
d
X 0~377 Word/DWor Data register
d
Y 0~377 Word/DWor Data register
d
M 0~127 Word/DWor Data register
d

48
2.13 LG Master-K(CPU Direct) series PLC
LG Master-K series PLC support CPU(RS232) and Cnet module communication mode. This
chapter will introduce CPU mode.

2.13.1 Device model

Series Connected module Port Cable Device


K80
CPU RS232 Fig 1 LG Master-K80/120 series
K120
Note: before communicating, please write “END” instruction to the PLC. Otherwise, the PLC
will report an error and the ERR LED will light.

2.13.2 Parameters

HMI:
Parameters Recommend settings Choices of settings Notes
PLC type LG Master-K80/120 series
PLC
Port RS232 RS232
Dat bit 8 7 or 8
Stop bit 1 1 or 2
Parity No parity Even/odd/no parity
Baud rate 38400 4800/38400/9600/115200/19200/187500
Station no. 0 0~255

The default communication parameters of LG Master K: 38400, 8, 1, no parity, station no.0.

PLC:

49
2.13.3 Cable making

Master-K 80\120 RS232:

Fig1

2.13.4 Device address

LGMaster-K80/120 series PLC


PLC address Range Data type Explanation
M 0~9999F Bit Internal auxiliary relay
L 0~9999F Bit Link relay
K 0~9999F Bit Holding relay
T 0~9999 Bit Timer
C 0~9999 Bit Counter
P 0~9999F Bit I/O coil
D 0~9999 Word/DWor Data register
d

50
TD 0~9999 Word/DWor Current value of timer
d
CD Word/DWor Current value of counter
0~9999
d
S 0~9999 Word/DWor Used as register
d
K 0~9999 Word/DWor Used as register
d
M 0~9999 Word/DWor Used as register
d
L 0~9999 Word/DWor Used as register
d
F 0~9999 Word/DWor Used as register
d
P 0~9999 Word/DWor Used as register
d

51
2.14 LG Master-K(Cnet) series PLC
LG Master-K80/120 series PLC Cnet communication module

LG Master-K series PLC support CPU(RS232) and Cnet expansion port communication mode. This
chapter will introduce Cnet mode.

2.14.1 Device model

Series Connected module Port Cable Device


K80 RS232 Fig 1
Cnet communication module LG Master-K80/120(Cnet) series
K120 RS485 Fig 2

Note:

1. For Master K-cnet communication, turn ON DIP switch 2, turn OFF DIP switch 1. For LG
Master KxxxS communication, keep the DIP switch to default settings.
2. LG Master KxxxS CPU only supports RS232 connection. Cnet communication module
supports RS232 and RS485 connection.

2.14.2 Parameters

HMI:
Parameters Recommend settings Choices of settings Notes
PLC type LG Master-K80/120 (Cnet) series PLC
Port RS232 RS232
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity Even parity Even/odd/no parity
Baud rate 9600 4800/38400/9600/115200
/19200/187500
Station no. 1 0~255
The default parameters of LG Master K-cnet : 9600, 8, 1, even parity, station no.1.

PLC:
Notes:
1. Turn on the switch BUILT-IN CNET on the PLC.
2. Choose the correct channel, protocol and mode.

0-RS232 communication:
52
1-RS485 communication:

2.14.3 Cable making

(a) Master K-cnet protocol RS232:

53
Fig 1

(b) Master K-cnet protocol RS485-2:

Fig 2

2.14.4 Device address

LGMaster-K80/120(Cnet) series PLC


PLC address Range Data type Explanation
M 0~9999F Bit Internal auxiliary relay
L 0~9999F Bit Link relay
K 0~9999F Bit Holding relay
T 0~9999 Bit Timer
C 0~9999 Bit Counter
P 0~9999F Bit I/O coil
D 0~9999 Word/DWor Data register
d
TD 0~9999 Word/DWor Current value of timer
d
CD Word/DWor Current value of counter
0~9999
d
S 0~9999 Word/DWor Used as register
d
K 0~9999 Word/DWor Used as register
d
M 0~9999 Word/DWor Used as register
d
L 0~9999 Word/DWor Used as register
d
F 0~9999 Word/DWor Used as register
d
P 0~9999 Word/DWor Used as register
d

54
2.15 LG Glofa(Cnet) series PLC

2.15.1 Device model

Series CPU Connected module Port Cable Device


Glofa G7M-DR20A CPU RS232 RS232 Fig 1 LG Glofa(Cnet)series

Note: please turn on DIP switch2 and turn off switch1 for LG Glofa -cnet communication.

2.15.2 Parameters

HMI:
Parameters Recommend settings Choices of settings Note
PLC type LG Glofa (cnet)
Port RS232 RS232
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity No parity Even/odd/no parity
Baud rate 19200 4800/38400/9600/115200/19200/187500
Station no. 0 0~255

The default parameters of LG Glofa –Cnet: 19200, 8, 1, no parity, station no.0

PLC:
Note:
1. Turn on the switch BUILT-IN CNET on the PLC.
2. “Dedicated-slave” must be choosed in the PLC programming software.
3. The communication area of M must be set in the PLC programming software.

M area size:

Protocol and mode settings:

55
56
2.15.3 Cable making

LG Glofa –Cnet RS232:

Fig 1

57
2.15.4 Device address

PLC type Range Data type Explanation


M 0~16383 Bit Internal auxiliary relay
IX 0.0.0-.0.0.11 Bit External input coil
0.0.12~0.0.6 Bit Internal auxiliary input coil
3
0.1.0~0.1.63 Bit Internal auxiliary input coil
0.2.0~0.2.63 Bit Internal auxiliary input coil
0.3.0~0.3.63 Bit Internal auxiliary input coil
0.4.0~0.4.63 Bit Internal auxiliary input coil
0.5.0~0.5.63 Bit Internal auxiliary input coil
0.6.0~0.6.63 Bit Internal auxiliary input coil
0.7.0~0.7.63 Bit Internal auxiliary input coil
QX 0.0.0~0.0.11 Bit External output coil
0.0.12~0.0.6 Bit Internal auxiliary output coil
3
0.1.0~0.1.63 Bit Internal auxiliary output coil
0.2.0~0.2.63 Bit Internal auxiliary output coil
0.3.0~0.3.63 Bit Internal auxiliary output coil
0.4.0~0.4.63 Bit Internal auxiliary output coil
0.5.0~0.5.63 Bit Internal auxiliary output coil
0.6.0~0.6.63 Bit Internal auxiliary output coil
0.7.0~0.7.63 Bit Internal auxiliary output coil
IW 0.0.0~0.0.3 Word/DWor Data register
d
0.1.0~0.1.3 Word/DWor Data register
d
0.2.0~0.2.3 Word/DWor Data register
d
0.3.0~0.3.3 Word/DWor Data register
d
0.4.0~0.4.3 Word/DWor Data register
d
0.5.0~0.5.3 Word/DWor Data register
d
0.6.0~0.6.3 Word/DWor Data register
d
0.7.0~0.7.3 Word/DWor Data register
d

58
QW 0.0.0~0.0.3 Word/DWor Data register
d
0.1.0~0.1.3 Word/DWor Data register
d
0.2.0~0.2.3 Word/DWor Data register
d
0.3.0~0.3.3 Word/DWor Data register
d
0.4.0~0.4.3 Word/DWor Data register
d
0.5.0~0.5.3 Word/DWor Data register
d
0.6.0~0.6.3 Word/DWor Data register
d
0.7.0~0.7.3 Word/DWor Data register
d
MW 0~4095 Word Data register
0~4095 Regs Data register
MD 0~2047 DWord Data register
0~2038 Regs Data register

59
2.16 LG XGT(CPU Direct) series PLC

2.16.1 Device model

Series CPU Connected module Port Cable Device


LG XGT series
XGT CPU RS232 RS232 Fig 1
(CPU Direct)

2.16.2 Parameters

HMI:
Parameter Recommend settings Choices of settings Note
PLC type LG XGT series(CPU Direct)
Port RS232 RS232
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity No parity Even/odd/no parity
Baud rate 115200 4800/38400/9600/115200/19200/187500
Station no. 1 0~255
The default parameters of LG XGT series PLC(CPU Direct): 115200, 8, 1, no parity, station

no.1
Note: XGT series(CPU Direct)only supports the baud rate 115200 and cannot modify the
station no.

2.16.3 Cable making

Fig1

60
2.16.4 Device address

PLC address Range Data type Explanation


P 0.0~65535.F Bit External I/O coil
65535 Word/DWor Data register
d
M 0.0~65535.F Bit Internal auxiliary output coil
65535 Word/DWor Data register
d
L 0.0~65535.F Bit External output coil
65535 Word/DWor Data register
d
F 0.0~65535.F Bit Data register
65535 Word/DWor Data register
d
T 65535 Word/DWor Data register
d
65535 Bit Counter
C 65535 Word/DWor Data register
d
65535 Bit Counter
D 65535 Word/DWor Data register
d
0.0~65535.F Bit Relay
S 65535 Bit Relay
K 65535 Word/DWor Data register
d
0.0~65535.F Bit Relay
Z 65535 Word/DWor Data register
d
0.0~65535.F Bit Relay
N 65535 Word/DWor Data register
d
0.0~65535.F Bit Relay
R 65535 Word/DWor Data register
d
0.0~65535.F Bit Relay
ZR 65535 Word/DWor Data register
d
0.0~65535.F Bit Relay
TS 65535 Word Data register

61
CS 65535 DWord Data register

2.17 Matsushita MEWNET FP series PLC

2.17.1Device model

Matsushita- Mewnet FP series PLC include FP0, FP1, FP3, FP2SF, FP10SH and so on. They can
communicate with Xinje HMI via the programming port or communication port on the CPU.
FP0-CXXCXX only supports RS232 connection.

Series CPU Connected module Port Cable Device


FP0 Direct connect to the CPU RS232 Fig 1
FP-M Direct connect to the CPU RS232 Fig 1
FP-X Direct connect to the CPU RS232 Fig 1
FP∑ Direct connect to the CPU RS232 Fig 1
Direct connect to the CPU RS232 Fig 1
FP2
CPU RS232 com port RS232 Fig 2
Direct connect to the CPU RS232 Fig 1
FP2SH Matsushita FP0/FP1
FP CPU RS232 com port RS232 Fig 2
series
CPU RS232 com port RS232 Fig 2
FP1 CPU RS232 programming RS422
Fig 3
port
CPU RS422 programming RS422
FP3 Fig 4
port
FP10SH
CPU RS232 com port RS232 Fig 2
FP10S
FP-E Direct connect to the CPU RS232 Fig 1

62
2.17.2 Parameters

HMI:
Parameters Recommend settings Choices of settings Note
PLC type matsushita FP series PLC
Port RS232
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity Odd parity Even/odd/no parity
Baud rate 9600 4800/38400/9600/115200/19200/187500
Station no. 1 0~255
The default parameters of Matsushita FP series PLC: 9600, 8, 1, odd parity, station no.1

PLC:

Note:
1.PLC soft component input example:
LC HMI
R45

Y1

63
2.When making the PLC program, set the switch to PPOG; set the switch to RUN when

communicating.

3.Do not choose <Common communication mode>, otherwise, the communication will

be error.

4.FP series PLC default station no. is 1, please note FP3 series PLC station no. must set

to 0.

2.17.3 Cable making

(a) CPU 5-pin DIN port:

Fig1

(b) CPU 9-pin port:

Fig2

64
(c) CPU 8-pin port:

Fig3

(d) CPU 15-pin port:

Fig4

2.17.4 Device address

PLC address Range Data type Explanation


X 0~12(0~F) Bit External input coil (bit)
WX 0~12 Word/DWor Single/double words register
d
Y 0~12(0~F) Bit External output coil (bit)
WY 0~12 Word/DWor Single/double words register
d
R 0~62, Bit Internal auxiliary coil (bit)
90~903
WR 0~65535 Word/DWor Single/double words register
d
T 0~99 Bit Timer
L 65535F Bit Link coil

65
C 100~143 Bit Counter
SV 0~143 Word/DWor Setting register
d
EV 0~143 Word/DWor Real value of counter or timer
d
DT 0~65535 Word/DWor Single/double words data
d register

66
2.18 Schneider PLC

2.18.1Device model

Series CPU Connected module Port Cable Device


Micro TSX 37-05 Direct connect to CPU RS485 Fig 1
TSX 37-08
TSX 37-10
TSX 37-21/22
Twido Twido series Direct connect to CPU RS485 Fig 1 Schneider Micro/
CPU NEZA/Twido
M M218 Direct connect to CPU RS485 Fig 2 Series PLC
M238
M258
TSX07 series Direct connect to CPU RS485 Fig 1
NEZA
CPU

2.18.2 Parameters

HMI:
Parameters Recommend settings Choices of settings Note
PLC type Schneider Micro/NEZA
/Twido series PLC
Port RS485
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity Even parity Even/odd/no parity
Baud rate 19200 4800/38400/9600/115200/19200/187500
Station no. 1 0~255
The default parameters of Schneider Micro/NEZA/ Twido series PLC: 19200, 8, 1, even parity,
station no.1

67
PLC:

68
Note:
The object address of Twido PLC is dynamic and can be enlarged in the PLC
programming software. Please release the max coil address in the program. For example:
the max coil address is M127, please output M127 in the program.

2.18.3 Cable making

(a) Direct connect to CPU:

Fig1

(b) M238 RJ-45 RS485:

Fig2

2.18.4 Device address

PLC address Range Data type Explanation


M 0~2047 Bit Internal coil
MW 0.00~65535.15 Bit Internal coil
MW 0~2047 Word/DWord Register

69
2.19 Fatek FB series PLC

2.19.1 Device model

Series CPU Connected module Port Cable Device


FBs -20MN RS232 Fig 1
FBs FBs -32MN
FBs -44MN RS485 Fig 2
20MC
Direct connect to CPU
28MC RS232 Fig 1
40MC Fatek MU
FB -MC
19MCT /MA series
26MCT RS485 Fig 2
36MCT
20MA RS232 Fig 3
FB-DTBR/DTBR-E
FB -MA 28MA RS232 Fig 4
module
40MA RS485 Fig 5

Note: MA series PLC needs to configure FB-DTBR or FB-DTBR-E module, uses RS232
or RS485 connection.

2.19.2 Parameters

HMI:
Parameters Recommend settings Choices of settings Note
PLC type Fatek MC/MA/MU series PLC
Port RS232 RS232 or RS485
Data bit 7 7 or 8
Stop bit 1 1 or 2
Parity Even parity Even/odd/no parity
Baud rate 9600 4800/38400/9600/115200
/19200/187500
Station no. 1 0~255
The default parameters of Fatek MC/MA/MU series PLC: 9600, 7, 1, even parity, station

no.1

70
2.19.3 Cable making

(a) FBs Port0 RS232:

CPU port:

Fig1

(b) CPU RS485:

Fig2

(c) FB-DTBR/DTBR-E module RS232:

Fig3

71
(d)FB-DTBR/DTBR-E module RS232:

Fig4

(e) FB-DTBR/DTBR-E module RS485:

Fig5

2.19.4 Device address

FATEK-FB series PLC


PLC address Range Data type Explanation
M 0~2001 Bit Internal auxiliary coil
X 0~255 Bit External input coil
Y 0~255 Bit External output coil
S 0~999 Bit Sequence control coil
T 0~255 Bit Timer
C 0~255 Bit Counter
R 0~9000 Word/Dword Register
X 0~255 Word/Dword Used as register
Y 0~255 Word/Dword Used as register
M 0~2001 Word/Dword Used as register
S 0~999 Word/Dword Used as register
D 0~3071 Word/Dword Used as register
TD 0~255 Word/Dword Used as register
C16 0~199 Word/Dword 16-bit counter
C32 200~255 Word/Dword 32-bit counter
T 0~255 Word/Dword Timer state

72
2.20 Vigor VIGOR PLC

2.20.1 Device model

Series CPU Connected module Port Cable Device


VB0-14M
VB0-20M Direct connect to the CPU RS232 Fig 1
VB0-28M
VB0-32M
RS232 Fig 2 Vigor VB
VB VB1-14MT-D
Series
VB1-24MT-D Connect to the extension
RS422 Fig 3 PLC
VB1-32MTMT-D card
VB2-16M
RS485 Fig 4
VB2-32M
VH VH -14MR Direct connect to the CPU RS232 Fig 1

2.20.2 Parameters

HMI:
Parameters Recommend Choices of settings Note
settings
PLC type Vigor VB series
PLC
Port RS232 RS232/RS485/RS422
Data bit 7 7 or 8
Stop bit 1 1 or 2
Parity Even parity Even/odd/no parity
Baud rate 19200 4800/38400/9600/115200/19200/187500
Station no. 0 0~255
The default parameters of Vigor VB series PLC: 19200, 7, 1, even parity, station no.0

2.20.3 Cable making

73
(a) CPU RS232 USB-A:

Fig1
(b) CPU direct connection or RS232 extenstion card:

Fig2
(c) CPU direct connection or RS485 extenstion card:
1.RS422 connection

Fig3
2.RS485 connection

Fi4

74
2.20.4 Device address

PLC address Range Data type Explanation


X 0~777 Bit External input coil
Y 0~777 Bit External output coil
M 0~9255 Bit Internal auxiliary coil
S 0~999 Bit Special auxiliary coil
TSTATUS 0~255 Bit Status of timer
CSTATUS 0~255 Bit Status of counter
TCOIL 0~255 Bit Timer coil
CCOIL 0~255 Bit Counter coil
C16 0~199 Word 16-bit counter
C32 200~255 DWord 32-bit counter
D 0~9255 Word/ Data register
DWord
TW 0~255 Word/ Current timer value
DWord
X 0~777 Word/ Used as register
DWord
Y 0~777 Word/ Used as register
DWord
M 0~9255 Word/ Used as register
DWord
S 0~999 Word/ Used as register
DWord

75
2.21 Fuji SPB series PLC

2.21.1 Device model

Fuji MICREX-SX SPB series PLC


Series CPU Connected module Port Cable Device

Communication adapter Fig 1


NW0P20 RS232
NW0LA-RS2 Fig 3 Fuji SPB
SPB NW0P30
Communication adapter Fig 2 series PLC
NW0P40 RS485
NW0LA-RS4 Fig 3

2.21.2 Parameters

HMI:
Parameter Recommend Choices of settings Note
settings
PLC type Fuji SPB series PLC
Port RS232 RS232/RS485
Data bit 8 7/8
Stop bit 1 1/2
Parity Odd parity Even/odd/no parity
Baud rate 19200 4800/38400/9600/115200/19200/187500
Station no. 0 0~255

2.21.3 Cable making

(a) NW0LA-RS2 module RS232:

Fig1

76
(b) NW0LA-RS4 module RS485:

Fig2

(c) RJ-45 RS422:

Fig3

2.21.4 Device address

PLC address Range Data type Explanation


X 0~15 Bit External input coil
Y 0~15 Bit External output coil
M 0~15 Bit Internal auxiliary coil
L 0~15 Bit Special auxiliary coil
T 0~511 Bit Timer
C 0~255 Bit Counter
SM 0~15 Bit Special auxiliary coil
WX 0~63 Word/DWor Used as register
d
WY 0~63 Word/DWor Used as register
d

77
WM 0~63 Word/DWor Used as register
d
WL 0~255 Word/DWor Used as register
d
WSM 32768~3302 Word/DWor Used as register
3 d
D 0~8191 Word/DWor Data register
d
TW 0~511 Word/DWor Used as register
d
CW 0~255 Word/DWor Used as register
d
LD 0~10000 Word/DWor Used as register
d
SD 32768~3302 Word/DWor Used as register
3 d

78
2.22 Keyence KV series PLC

2.22.1Device model

CPU Connected module Port Cable Device


KV-10DR
KV-24
Direct connect to the CPU RS232 Fig 1
KV-16
KV-40
RS232 Fig 2, fig 3 Keyence KV series
KZ-300 Serial port module KZ-L2
RS422 Fig 4
RS232 Fig 5, fig 6
KV-700 Serial port module KZ-L20
RS422 Fig 7

2.22.2 Parameters

HMI:
Parameters Recommend Choices of settings Note
settings
PLC type keyence KV series
Port RS232 port RS232/RS422
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity Even parity Even/odd/no parity
Baud rate 9600 4800/38400/9600/115200/19200/187500
Station no. 1 0~255
The default parameters of Keyence KV series PLC: 9600, 8, 1, even parity, station
no.1

2.22.3 Cable making

(a) CPU RS232 RJ-11:

79
1 23 45 6

Fig1

(b) Serial port module KZ-L2(Port1, RS232)connects to Keyence KZ-300 PLC:

Fig2

(c) Serial port module KZ-L2(Port2, RS232)connects to Keyence KZ-300 PLC:

Fig3

(d) Serial port module KZ-L2(Port2, RS422)connects to Keyence KZ-300 PLC:

Fig4

80
(e) Serial port module KV-L20(Port1, RS232)connects to Keyence KV-700 PLC:

Fig5

(f) Serial port module KV-L20(Port2, RS232)connects to Keyence KV-700 PLC:

Fig6

(g) Serial port module KV-L20(Port2, RS422)connects to Keyence KV-700 PLC:

Fig7

2.22.4 Device address

PLC address Range Data type Explanation


R 0~999 Bit Coil
DM 0~8000 word Data register

81
2.23 Emerson EC20 series PLC

2.23.1Device model

Series CPU Connected module Port Cable Device


COM0 port RS232 Fig 1
Emerson EC20
EC20 EC20 RS485 Fig 2
COM1 port Series PLC
RS232 Fig 3

2.23.2 Parameters

HMI:
Parameters recommend settings Choices of settings Note
PLC type Emerson EC20 series PLC
Port RS232 RS232/RS485
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity Even parity Even/odd/no parity
Baud rate 19200 4800/38400/9600/115200
/19200/187500
Station no. 1 0~255
The default parameters of Emerson EC20 series PLC: 19200, 8, 1, even parity, station

no.1

2.23.3 Cable making

(a) Emerson EC20 PLC COM0 (RS232):

Fig1

(b) Emerson EC20 PLC COM1 (RS232):

82
Fig2

(c) Emerson EC20 PLC COM1 (RS485):

Fig3

Note: Emerson EC20 PLC COM1 supports RS232 and RS485.

2.23.4 Device address

PLC address Range Data type Explanation


X 0~377 Bit External input coil
Y 0~377 Bit External output coil
M 0~2047 Bit Internal auxiliary coil
S 0~1023 Bit Special auxiliary coil
T 0~255 Bit Timer
C 0~255 Bit Counter
SM 0~9999 Bit Special internal auxiliary coil
D 0~7999 Word/DWor Data register
d
SD 0~255 Word/DWor Used as register
d
Z 0~15 Word/DWor Used as register
d
T 0~255 Word/DWor Used as register
d
C16 0~199 Word/DWor 16-bit counter
d
C32 200~255 Word/DWor 32-bit counter

83
d

2.24 OEMax NX7 series PLC

2.24.1 Device model

Series CPU Connected module Port Cable Device


RS232 Fig 1
COM0 port
RS232 Fig 2 OEMax NX7
NX7 NX7
RS485 Fig 3 Series PLC
COM1 port
RS232 Fig 4

2.24.2 Device address

HMI:
Parameter Recommend settings Choices of settings Note
PLC type OEMax NX70 series PLC
Port RS232 RS232/RS485
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity No parity Even/odd/no parity
Baud rate 9600 4800/38400/9600/115200
/19200/187500
Staion no. 1 0~255
The default parameterso f OEMax NX7 PLC: 9600, 8, 1, no parity, station no.1

2.24.3 Cable making

(a) OEMax NX7 PLC COM1 (RS232):

Fig1

84
(b) OEMax NX7 PLC COM1 (RS485):

Fig2

(c) OEMax NX7 PLC COM2 RJ-45 (RS232):

8 7 6 5 4 3 21

Fig3

(d) OEMax NX7 PLC COM2 is RJ-45 8-pin port, short pin1 and 3 means RS485+; short
pin2 and 4 means RS485- :

Fig4

OR

Fig5

85
2.24.4 Device address

PLC address Range Data type Explanation


R R000.00~R31.15 Bit External I/O coil
R32.00~R127.15 Bit Special coil
L L000.00~L063.15 Bit Internal coil
M M000.00~M127.15 Bit Internal auxiliary coil
K K000.00~K127.15 Bit Internal holding coil
F F000.00~F015.15 Bit Special coil
TC TC0~TC255 Bit Timer /counter coil
W 0~6000 Word/DWord Data register
R 0~127 Word/DWord Used as register
L 0~63 Word/DWord Used as register
M 0~127 Word/DWord Used as register
K 0~127 Word/DWord Used as register
F 0~15 Word/DWord Used as register
SV 0~255 Word/DWord Timer/counter settings
PV 0~255 Word/DWord Timer/counter current value
SR 0~511 Word/DWord Special register

86
2.25 Bosch Rexroth IndraControl L40 series PLC

2.25.1 Device model

Bosch Rexroth IndraControl L40 series PLC can communicate with Xinje HMI via
COM0 and COM1.
CPU Connected module Port Cable Device
Bosch Rexroth
IndraControl L40 Direct connect to CPU RS232 Fig 1 IndraControlL40
Series PLC

2.25.2 Parameters

HMI:
Parameters Recommend settings Choices of settings Note
PLC type IndraControl L40 series PLC
Port RS232 RS232
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity Even parity Even/odd/no parity
4800/38400/9600/115200
Baud rate 9600
/19200/187500
Station no. 1 0~255
The default parameters of IndraControl L40 series PLC: 9600, 8, 1, even parity,
station no.1

2.25.3 Cable making

IndraControl L40 PLC RS232:

Fig1

87
2.25.4 Device address

IndraControl L40 series PLC


PLC address Range Data type Explanation
X 0~9999 Bit External I/O coil
B 0~9999 Byte Used as register
W 0~9999 Word Used as register
D 0~9999 DWord Used as register
R 0~9999 DWord Used as register
SB 0~9999 Byte Used as register
SW 0~9999 Word Used as register
SD 0~9999 DWord Used as register

88
2.26 OPTO 22 SNAP series PLC

2.26.1 Device model

Series CPU Connected module Port Cable Device


RS232 Fig 1, fig 2
OPTO 22 SNAP Direct connect to CPU OPTO 22 series
RS485 Fig 3

2.26.2 Parameters

HMI:
Recommend
Parameters Choices of settings Note
settings
PLC type OPTO 22 series
Port PLC
RS232 RS232/RS485
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity No parity Even/odd/no parity
Baud rate 115200 4800/38400/9600/115200/19200/187500
Station no. 1 0~255

The default parameters of OPTO 22 series PLC: 115200, 8, 1, no parity, station no.1

2.26.3 Cable making

(a) RS232 connection:

Fig1

(b) RS485 connection:

89
Fig2

(c) RS232 connection:

Fig3

2.26.4 Device address

PLC address Range Data type Explanation


DI 0~9999 Bit External input coil
DO 0~9999 Bit External output coil
PID000~PID03
0~6 Bit
1
I 0~9999 DWord Used as register
F 0~9999 DWord Used as register
AI 0~9999 DWord Used as register
AO 0~9999 DWord Used as register

90
2.27 SAIA-Burgess PCD series PLC

2.27.1 Device model

SAIA—Burgess PCD series PLC communicates with Xinje HMI via socket A or socket B
port.

(a) Direct connect to CPU


CPU Connected module Port Cable Device
PCD1.M110
PCD1.M125 CPU PORT #0 RS232 Fig 1
PCD1.M135
PCD2.M120 SAIA—Burgess PCD
PCD2.M150 CPU PORT #0 series
PCD2.M170 RS485 Fig 2

PCD2.M480 CPU PORT #6

(b) Through serial port


CPU Connected Port Cable Device
module
PCD1.M125
RS485 Fig 4
PCD1.M135
PCD7.F110
PCD1.M110
RS422 Fig 5
PCD1.M120
PCD2.M480
PCD2.M170
PCD7.F120 RS232 Fig 3
PCD2.M150
Socket A
RS232 Fig 6
Socket PCD2.F520 SAIA—Burgess
RS485 Fig 7 PCD series
B1 PCD7.F772/F802
RS422 Fig 10
PCD2.M170
RS232 Fig 6
Socket PCD2.F520/F530
RS485 Fig 7
B2
PCD7.F772/F802 RS485 Fig 8
Socket Fig 9 or
RS232
A fig 11
PCD2.M480 PCD2.F520/F522
Socket
RS422 Fig 10
B

91
2.27.2 Parameters

HMI:
Parameters Recommend Choices of settings Note
settings
SAIA—Burgess
PLC type
PCD
Port Series PLC
RS232 RS232/RS485
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity No parity Even/odd/no parity
Baud rate 19200 4800/38400/9600/115200/19200/187500
Station no. 0 0~255

SAIA—Burgess PCD series PLC: 19200, 8, 1, no parity, station no.0

2.27.3 Cable making

(a) Direct connect to PGU RS232:

Fig1

(b) Direct PGU RS485:

92
Fig2
(c) Socket A port (PCD7.F120):

Fig3

(d) Through Socket A port (PCD7.F110):

Fig4

(e) Socket A port (PCD7.F110):

Fig5

(f) Socket B/B1 and B2 port (PCD2.F520/F530):

93
Fig6

(g) Socket B/B1 and B2 port (PCD2.F520/F530):

Fig7

(h) Socket B/B1&B2 port (PCD7.F772/F802):

Fig8

(i) Socket B/B1&B2 port (PCD2.520/F530):

94
Fig9

(j) Socket B/B1&B2 port (PCD2.F520/F530):

Fig10

(k) Socket B/B1&B2 port (PCD2.F520/F530):

Fig11

95
2.27.4 Device address

PLC address Range Data type Explanation


R 0~4095 DWord Used as register
T 0~1599 DWord Used as register
C 0~1599 DWord Used as register
F 0~8000 Bit Auxiliary coil
I 0~1023 Bit External input coil
O 0~1023 Bit External output coil

2.28 Allen-Bradley series PLC

2.28.1 Device model

Series CPU Connected Port Cable Device


module
Micrologix Micrologix1000 AB Mircrologix,
Micrologix1200 SLC series (DF1
Micrologix1500 Full duplex
(1762-L40BWA) protocol)
CPU
(1764-LSP,1764-LRP) Fig 1
RS232 RS232
Micrologix1400
(1766-L32BWAA)
Micrologix1500
(1764-LRP)
SLC 500 SLC5/03 CPU RS232
SLC5/04 RS232 Fig 2
SLC5/05
Mciro830 2080-LC30 Modbus RTU
CPU
RS232 Fig 1 (panel is master)
RS232

2.28.2 Parameters

HMI:
Parameters Recommend Choices of settings Note
settings
PLC type AB Mircrologix, AB Mircrologix,

96
SLC series (DF1 SLC series (DF1 full-duplex)/Modbus
full-duplex) RTU(panel is master)
Port RS232 RS232
Data bit 8
Stop bit 1
Parity No parity
Baud rate 9600 9600/19200/38400
Station no. 1 0~255

The default parameters of AB Mircrologix SLC series (DF1 full-duplex): 9600, 8, 1, no


parity, station no.0.

PLC setting:

Condition A: in touchwin software, the PLC protocol is AB Mircrologix, SLC series:

97
Condition B: in touchwin software, the PLC protocol is Modbus RTU (panel is master):

Note: for Modbus RTU communication, the address must set the mapping, PLC address 1
corresponds to Modbus address 0, PLC address 2 corresponds to Modbus address 1…

98
2.28.3 Cable making

(a) AB Mircrologix series RS232:

Fig1

(b) SLC500 RJ8 modular plug:

Fig2

2.28.4 Device address

Device address Range Object type Explanation


type
T4DN 0~999 Bit Timer
C5DN 0~999 Bit Counter
O 0.00~999.15 Bit Output
I 0.00~999.15 Bit Input
S 0.00~999.15 Bit
B3 0.00~999.15 Bit
R6 0.00~999.15 Bit
N7 0.00~999.15 Bit
O 0~999 Word Used as register
I 0~999 Word Used as register
S 0~999 Word Used as register
B3 0~999 Word Used as register
T4PRE 0~999 Word Timer preset value

99
T4ACC 0~999 Word Timer actual value
C5PRE 0~999 Word Counter preset value
C5ACC 0~999 Word Counter preset value
R6 0~999 Word Data register
N7 0~999 Word/Dword Data register
F8 0~999 Dword Floating number
register
R6LEN 0~999 Word
P6POS 0~999 Word

100
2.29 Xinje V5 series inverter

2.29.1 Device model

Series Connected module Port Cable Device


V5 CPU RS485 port RS485 Fig 1 Thinget V5 series inverter

2.29.2 Parameters

HMI:
Parameters Recommend Choices of settings Note
settings
PLC type Thinget V5 series
inverter
Port RS485 RS485
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity Even parity Even/odd/no parity
Baud rate 19200 4800/38400/9600/115200/19200/187500
Station no. 1 0~255

Note: please set the communication wait time if the connection is error.

101
Inverter:
Function code Name Range Meaning
P0.01 Frequency setting channel 4 Serial port setting
P0.03 Run command channel 2 Run via serial port
P3.09 Communication settings 054 The unit:19200
Decade: 1-8-1, even parity
Hundred: no definition

2.29.3 Cable making

RS485:

Fig1

102
2.30 SHIMADEN

2.30.1 Device model

Series Connected Port Cable Device


module
SRS10(SRS11/SRS13/SRS14) RS485 on the RS485 Modbus RTU
Fig 1
Digital adjustor cpu unit (panel is Master)

Note: all the devices support Modbus protocol can communicate with Touchwin

HMI.

2.30.2 Parameters

HMI:
Parameters Recommend Choices of settings Note
settings
PLC type Modbus RTU
(panel is Master)
Port RS485 RS485
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity Even parity Even/odd/no parity
Baud rate 9600 4800/38400/9600/115200/19200/187500
Station no. 1 0~255

Note:
1. The parameters of device and HMI must be same.
2. Some devices need to add terminal resistor (sucha as SRS10 digital adjustor)
3. Meter parameter 018C must set to 1 (COM LED is ON), please use the “function
filed”(the button in the Touchwin software) to set the value of 018C(4x396=1).

2.30.3 Cable making

RS485 connection:

103
Fig1

2.30.4 Device address

PLC address (Hex) Parameters Read/write Meaning


0100 PV Read Measured value
0101 SV Read Setting value
0102 OUT1 Read Output 1
0103 OUT2 Read Output 2
0104 EXE_FLG Read Status sign
0105 EV_FLG Read event output sign
0300 FIX SV1 Read/write Fixed value 1
0301 FIX SV2 Read/write Fixed value 2
0302 FIX SV3 Read/write Fixed value 3
030A SV_L Read/write Lower limit of settings
030B SV_H Read/write Upper limit of settings

104
2.31 Modbus RTU (panel is Master)

2.31.1 Device model

Series Port Cable Device


Devices support RS485 Fig 1 Modbus RTU (panel is Master)
Modbus RTU RS232 Fig 2
protocol RS422 Fig 3

2.31.2 Parameters

HMI:
Parameters Recommend Choices of settings Note
settings
PLC type Modbus RTU
(panel is Master)
Port RS485 RS485/RS232/RS422
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity Even parity Even/odd/no parity
Baud rate 9600 4800/38400/9600/115200/19200/187500
Station no. 1 0~255

Note:
1. Modbus RTU protocol supports broadcast function, station no is 0.
2. How to use the broadcast function in the HMI?
The broadcast function only sends command but not receives. It sends command by
“function field”, “function button” or “function block” in Touchwin software. The operand
must has no feedback command, such as “set on coil”, “setting data”, “reset coil”.
PLC:
Please choose Modbus RTU (Slave) in the software.

2.31.3 Cable making

(a) Modbus RS485:

105
Fig1

(b) Modbus RS232:

Fig2

(c) Modbus RS422:

Fig3

2.31.4 Device address

Device Range Data type Feature Explanation


address
0x 0~65535 Bit R/W External I/O /internal
coil
1x 0~65535 Bit R External I/O /internal
coil
4x 0~65535(0~15) Bit R/W External I/O /internal
coil
4x 0~65535 Word/Dword R/W Used as data register

106
3x 0~65535 Word/Dword R Used as data register

2.32 Modbus ASCII (Panel is Master)

2.32.1Device model

Series Port Cable Device


The device RS485 Fig 1 Modbus ASCII (panel is Master)
support Modbus RS232 Fig 2
ASCII protocol RS422 Fig 3

2.32.2 Parameters

HMI
Parameters Recommend Choices of settings Note
settings
PLC type Modbus ASCII
(panel is Master)
Port RS485 RS485/RS232/RS422
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity Even parity Even/odd/no parity
Baud rate 9600 4800/38400/9600/115200/19200/187500
Station no. 1 0~255

PLC:
Please choose Modbus ASCII (Slave) protocol in the software.

2.32.3 Cable making

Modbus RS485:

Fig1

107
Modbus RS232:

Fig2
Modbus RS422:

Fig3

2.32.4 Device address

Device Range Data type Explanation


address
0x 0~65535 Bit External I/O/internal coil
1x 0~65535 Bit External I/O/internal coil
4x 0~65535 Word/Dword Used as data register
3x 0~65535 Word/Dword Used as data register

108
2.33 Modbus slave (panel is Slave)

2.33.1Device model

Series Port Cable Device


The device support Modbus RS485 Fig 1 Modbus slave (panel is
protocol RS232 Fig 2 Slave)
RS422 Fig 3

2.33.2 Parameters

HMI:
Parameters Recommend Choices of settings Note
settings
PLC type Modbus slave
(panel is slave)
Port RS485 RS485/RS232/RS422
Data bit 8 7/8
Stop bit 1 1/2
Parity Parity Even/odd/no parity
Baud rate 9600 4800/38400/9600/115200/19200/187500
Station no. 1 0~255

2.33.3 Cable making

Modbus RS485:

Fig1

Modbus RS232:

109
Fig2

Modbus RS422:

Fig3

2.33.4 Device address

Device address Range Data type Features Explanation


0x 0~65535 Bit R/W External I/O/internal coil
1x 0~65535 Bit R External I/O/internal coil
4x 0~65535 Word/Dword R/W Used as data register
3x 0~65535 Word/Dword R Used as data register

110
2.34 ABB PLC

2.34.1Device model

ABB PLC can communicate with Touchwin HMI by Modbus protocol.

Series Port Cable Device


AC500 PM564-T-ETH Fig 1 ABB (AC500)

2.34.2 Parameters

HMI:
Parameters Recommend Choices of settings Note
settings
PLC type ABB AC500
Port RS485 RS485
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity Even parity Even/odd/no parity
Baud rate 19200 4800/38400/9600/115200/19200/187500
Station no. 1 0~255

PLC:

1. Choose Modbus in ABB AC500 PLC serial port:

111
2. Choose COM1 MODBUS, then set the operation mode to slave. Other

parameters should be the same to HMI.

2.34.3 Cable making

ABB COM1 (RS-485):

112
2.34.4 Device address

PLC address Range Data type Explanation


MX0 0.0.0~0.65535.7 Bit External I/O/internal coil
MX1 0.0.0~0.65535.7 Bit External I/O/internal coil
MW0 0~32767 Word//DWord Data register
MW1 0~32767 Word//DWord Data register
MD0 0~32767 Word//DWord Data register
MD1 0~32767 Word//DWord Data register

113
2.35 IDEC

2.35.1 Device type

Series Connected module Port Cable Choose PLC type in


Touchwin software
MicroSmart RS232 on the cpu unit RS485 Fig 1 IDEC MicroSmart

2.35.2 Parameters

HMI settings:
Parameter Recommend Choices of settings Note
s settings
PLC type IDEC MicroSmart
Port RS232 RS232
Data bit 7 7/8
Stop bit 1 1/2
Parity Even parity Even /odd /no parity
Baud rate 9600 4800/38400/9600/115200/19200/187
500
Station no. 0

2.35.3 Cable making

RS232 connection:

114
2.35.4 Device address

Device address Range Data type Explanation


D 0~8199 Word/DWord Data register
W 0~6 Word Data register
T 0~99 Word Timer
t 0~99 Word Timer
C 0~99 Word Counter
c 0~99 Word Counter
R 0~127 Word Data register
x 0.0~30.7 Bit Input
y 0.0~30.7 Bit Output
m 0.0~807.7 Bit Auxiliary relay
r 127 Bit Auxiliary relay

115
2.36 TAIAN

2.36.1 Device type

Series CPU Connected Port Cable Choose PLC type


module in Touchwin
software
RS232 on the RS232 TAIAN TP03 series
TP03-20HR-A Fig 1
CPU Unit
TAIAN RS485 on the RS485
TP03-30HR-A Fig 2
CPU Unit

116
2.36.2 Parameters

HMI settings:
Parameter Recommend Choices of settings Note
s settings
PLC type TAIAN TP03
series
Port RS232 RS232/RS485
Data bit 8 7/8
Stop bit 2 1/2
Parity No parity Even /odd /no parity
Baud rate 19200 4800/38400/9600/115200/19200/187
500
Station no. 1 0-255

2.36.3 Cable making

RS232 connection:

Fig1

RS485 connection:

Fig2

117
2.36.4 Device address

Device address Range Data type Explanation


D 0~8511 Word/DWord Data register
T 0~511 Word/DWord Timer
C 0~255 Word/DWord Counter
X 0~377 Bit Input
Y 0~377 Bit Output
M 0~1535 Bit Auxiliary relay
S 0~1023 Bit Auxiliary relay
T 0~511 Bit Timer
M8xxx 0~511 Bit Auxiliary relay
C 0~255 Bit Counter
S expansion 1024~4095 Bit Auxiliary relay
M expansion 1536~7679 Bit Auxiliary relay

118
2.37 YuDian AI

2.37.1 Device address

Series Connected module Port Cable Choose PLC type in


Touchwin software
AI RS485 on the cpu unit RS485 Fig 1 AI series instrument

2.37.2 Parameters

HMI settings:
Parameter Recommend Choices of settings Note
s settings
PLC type AI series
instrument
Port RS485 RS485
Data bit 8 7/8
Stop bit 1 1/2
Parity No parity Even /odd /no parity
Baud rate 9600 4800/38400/9600/115200/19200/187
500
Station no. 129
Note:
1. The parameters of HMI and meter must be the same.
2. How to set the station no. of meters?
HMI→129 meter→ 1+80H
HMI→130 meter→ 2+80H

2.37.3 Cable making

RS485 connection:

119
2.37.4 Device address

Device address Range Data type Explanation


PV 0~100 Read Measure value
SV 0 read\write Set value
MV 0 Read Output value
Flow meter MV 0 Read Output value of flow meter
S 0/1 Read Status bit

120
2.38 Inovance PLC

2.38.1 Device type

Connecte PLC type in


Series CPU Port Cable
d module touchwin software

H1U-0806MR\T
H1U H1U-1410MR\T
H1U-1614MR\T Mitsubishi FX
CPU RS422 Fig 1
series PLC
H2U-1616MR\T
H2U H2U-2416MR\T
H2U-3624MR\T

2.38.2 Parameter

HMI settings
Paramete Recommended Choices of settings Notes
r settings
PLC type FX series - -
Data bit 7 -
Stop bit 1 -
Parity Even parity Even/odd/no parity
Baud rate 9600 4800/9600/19200/38400/560
00/57600/
115200/187500
Station 0 -
no.

Inovance H1U\2U series default communication parameters: 9600, 7, 1, even, statio no.0
PLC settings:

121
2.38.3 Cable making

(a) H1U\2U series PLC RS422 port:

Fig1

2.38.4 Device address

PLC address Range Object Explanation


X 0~177 Bit External input terminal
Y 0~177 Bit External output terminal
M 0~8255 Bit Internal auxiliary coil
S 0~999 Bit Stepper coil
T 0~255 Bit Timer
C 0~255 Bit Counter

122
C16 0~199 Word/DWord 16-bit counter
C32 200~255 DWord 32-bit counter
D 0~8255 Word/DWord Data register
T 0~255 Word/DWord Current value
X 0~177 Word/DWord Used as data register
Y 0~177 Word/DWord Used as data register
M 0~8255 Word/DWord Used as data register
S 0~999 Word/DWord Used as data register

123
2.39 HaiWell PLC

2.39.1 Device type

Connected PLC type in


Series CPU Port Cable
module Touchwin software
HW-S16ZR220 RS232 Fig 1 Modbus RTU
E\S CPU
R RS485 Fig 2 (panel is master)

2.39.2 Parameters

HMI settings:
Paramete Recommend settings Choices of settings Notes
r
PLC type Modbus RTU (panel is - -
master)
Data bit 8 -
Stop bit 1 -
Parity Odd Even/odd/no parity
Baud rate 9600 4800/9600/19200/3840
0/56000/
57600/115200/187500
Station 1 -
no.
Haiwell E\S series default communication parameters: 9600, 8, 1, odd, station no.1

PLC settings:
Communication protocol: Modbus RTU.

2.39.3 Cable making

(a) E\S series PLC RS232:

124
Fig 1

(b) E\S series PLC RS485:

Fig 2

2.39.4 Device address

PLC Range Modbus Read/write Explanation


address address
X X0~X1023 0~1023 Read Input
Y Y0~Y1023 1536~2559 Read/write Output
M M0~M12287 3072~15359 Read/write Internal coil
T T0~T1023 15360~16383 Read/write Timer
C C0~C255 16384~16639 Read/write Counter
SM SM0~SM215 16896~17111 Read/write partly System state bit

S S0~S2047 28672~30719 Read/write Stepper state bit


CR 00~4F Read/write partly Register for analog and
special module
AI AI0~AI255 0000~00FF Read Input register for analog
AQ AQ0~AQ255 0100~01FF Read/write Output register for analog
V V0~V14847 0200~3BFF Read/write Internal register
TCV TCV0~TCV1023 3C00~3FFF Read/write Timer
CCV CCV0~CCV255 4000~40FF Read/write Counter
SV SV0~SV154 4400~448B Read/write partly System register

125
2.40 Hollias PLC

2.40.1 Device type

PLC type in
Connected Cable
Series CPU Port Touchwin
module making
software
LM3109 RS232 Fig 1 Modbus RTU
LM CPU
LM3107 RS485 Fig 2 (panel is master)

2.40.2 Parameters

HMI settings:
Paramete Recommend Choices of settings Note
rs settings
PLC type Modbus RTU (panel - -
is master)
Data bit 8 -
Stop bit 1 -
Parity No parity Even/odd/no parity
Baud rate 38400 4800/9600/19200/38400/5600
0/
57600/115200/187500
Station 51 -
no.
Hollias LM series PLC default parameters: 38400, 8, 1, no parity, station no.51

2.40.3 Cable making

(a) LM series PLC RS232:

Fig1

(b) LM series PLC RS485:

126
Fig2

2.40.4 Device address

Please refer to Hollias PLC Modbus address list.


The address is decimal value in HMI.
0x: read/write coil 1x: only read coil 4x: read/write register 3x: only read register

127
2.41 Delta (temperature controller)

2.41.1 Device type

PLC type in
Connected
Series CPU Port Cable Touchwin
module
software
DTA4848
DTA9696VR Modbus RTU
DVP CPU RS485 Fig 1
DTC1000 (panel is master)
DTC2000

2.41.2 Parameters

HMI settings:
Paramete Choices of settings Notes
rs
PLC type Modbus RTU - -
(panel is master)
Data bit 7 -
Stop bit 1 -
Parity Even parity Even/odd/no parity
Baud rate 9600 4800/9600/19200/38400/56000/57600
/
115200/187500
Station 1 -
no.
Delta (temperature controller) default parameters: 9600, 7, 1, even parity, station no.1

2.41.3 Cable making

(a) DVP RS485

128
Fig1

2.41.4 Device address

Please refer to Delta temperature controller Modbus address list.


The address is decimal in HMI.
0x: read/write coil 1x: only read coil 4x: read/write register 3x: only read register

129
2.42 Siemens S7-1200

2.42.1 Device type

Communic Connection
Series PLC type in Touchwin software
ation type diagram

Siemens S7-1200 RJ45 Diagram 1 or 2 Siemens S7-1200 series

2.42.2 Parameters

We take Siemens S7-1200 CPU1211C 6ES7 211-1BD30-0XB0 PLC as an example to


explain the settings.
PLC software settings:
1. Open project-devices&networks-normal-Ethernet IP, set the PLC IP address:

2. PLC DB, M must be defined in the PLC before using. Click project-program
block-add new block, choose data block (DB), the type is global DB, not choose
only sign visit. DB number can be auto or manual.

130
3. Choose project-program block-data block can define the address in the data
block.

Note: for the software STEP Basic V12 and up version, please release the
communication protection:
(1) Choose the PLC model in the project tree, right click it, choose properties

(2) Please choose “permit access with PUT/GET communication from remote partner
(PLC, HMI, OPC)”. Then download the PLC program in the PLC.

131
HMI settings:
Only Touchwin software v2.d.1j and higher version support Siemens 1200 series
PLC.
Operation steps:
(1) Please select the HMI type, click next.

(2) Select Net device. The IP address in own devices is HMI IP address.

132
(3) Right click Net device, click New. Then input the project name.

(4) Right click the project name to delete or rename the project.

(5) Select Siemens S7-1200 series in the device list.

(6) The IP is S7-1200 IP address. Note: this IP can be set in PLC software. Port 102
cannot be changed.

133
(7) please choose “word exchange”, otherwise, the double word data will be error.

(8) Communication parameters: please use the default parameters.


(9) Communication status register: if select this item, the status will occupy 4 registers.
The register address can be set by user. If set the address to PSW256, the register
meanings are shown as the following.
PSW256: communication succeeded times
PSW257: communication failed times
PSW258: timeout times
PSW259: communication error times.

(10) Then click next to finish the project setup.


(11) In the editing screen, when user defines the button object, please select device
1.

134
Note: please define the DB and M in the Siemens PLC, otherwise the communication
will be error.
(12) Notes:
A. Siemens PLC S7-1200 doesn’t have station number problem. It can build network with
HMI once the IP address is correct. The network mode can be multi-HMI-one-PLC,
one-HMI-multi-PLC, and multi-PLC-multi-HMI.
B. RX/TX lights when the communication is successful. RX/TX is shining when if is finding
the network.
C. Modbus TCP device is used to connect with TBOX-XINJE PLC; Siemens S7-1200
device can connect any device with Ethernet.
D. please define the DB and M in the Siemens PLC, otherwise the communication will be
error.

2.42.3 Cable making

RJ45 straight through cable (connect HUB) or RJ45 crossover cable:

Diagram 1

135
Diagram 2

2.42.4 Device address

PLC address Range Object type Explanation


type
I 0~9999 Byte/Word/DWord Input register
Q 0~9999 Byte/Word/DWord Output register
M Byte/Word/DWord Internal auxiliary
0~9999
register
DB0~DB20 0~9999 Byte/Word/DWord Data register
I 0.0~9999.7 Bit Input
Q 0.0~9999.7 Bit Output
M 0.0~9999.7 Bit Auxiliary relay
DB0~DB20 0.0~9999.7 Bit Auxiliary relay

136
2.43 Mitsubishi FR series inverter

2.43.1 Device type

Serie Connect Communicatio Cable PLC type in Touchwin


s module n type diagram software
Mitsubishi FR series inverter
RS485 port on
FR RS485 diagram 1 Modbus RTU (panel is
CPU unit
Master)

2.43.2 Parameters

Choose Mitsubishi FR series inverter:


HMI:
Parameter Recommended Choices of settings Notes
s setting
PLC type Mitsubishi FR - -
series
Port type RS485 RS485
Data bit 8 -
Stop bit 2 -
Parity Even parity -
Baud rate 19200 9600/115200/19200/187500
Station no. 0 0~31

Inverter parameters:
Function Name Default Range Debug
(FR) value parameters
P117 Station no. 0 0~31, 0~247 0
P118 Baud rate 19.2kbps 4800bps,9600bps,38400bps 19200
P119 Stop bit, data 1 0: 1 stop bit, 8 data bit 1: 2 stop bit, 8
bit 1: 2 stop bit, 8 data bit data bit
10: 1 stop bit, 7 data bit
11: 2 stop bit, 7 data bit
P120 Parity 2 0: no parity 2: even parity
1: odd parity
2: even parity
P121 Retry times 9999 9999
P122 Test time 0 0: RS485 0

137
9999: no communication
test
P123 Wait time 150ms 125
P124 R/LF 0 0: without CR, LF 0
1: with CR
2: with R, LF
P79 Mode selection 0 0~7 Set to 2, external
communication
mode, please cut
off the power of
inverter after
setting the
parameters
P340 Communication 0 0, 1, 10 Set to 1, start in
start mode network running
mode

Select Modbus RTU (Panel is Master):


HMI:
Parameter Recommended settings Choices of settings Note
PLC type Modbus Rtu (Panel is - -
Master)
Port type RS485 RS485
Data bit 8 -
Stop bit 2 -
Parity Even parity -
Baud rate 19200 9600/115200/19200/1875
00
Station no. 1 0~31

138
Inverter parameters:
Functio Name Default Range Debug parameters
n value
(FR)
P117 Station no. 1 0~31, 0~247 1 (Modbus station no.
can not be 0)
P118 Baud rate 19.2kbps 4800bps,9600bps,384 19200
00bps
P119 Stop bit 1 0: 1 stop bit, 8 data bit 1: 2 stop bit, 8 data bit
1: 2 stop bit, 8 data bit
10: 1 stop bit, 7 data
bit
11: 2 stop bit, 7 data
bit
P120 Parity Even 0: no parity 2: even parity
1: odd parity
2: even parity
P121 Retry times 9999 9999
P122 Communicatio 0 0: RS485 0
n test 9999: no
communication test
P123 Waiting time 150ms 125
P124 CR/LF 0 0: without CR, LF 0
selection 0: with CR
0: with R, LF

139
549 protocol 1 Modbus-RTU Be valid after restart
selection the inverter
P79 Mode 0 0~7 Set to 2, external
selection communication mode,
please cut off the
power of inverter after
setting the parameters
P340 Communicatio 0 0, 1, 10 Set to 1, start in
n start mode network running mode

2.43.3 Cable making

RS485 cable:

Diagram 1

140
2.44 Sanken VM06 inverter

2.44.1 Device type

Series Port type Cable PLC type in Touchwin software


diagram
Sanken VM06 inverter
VM06 RS485 diagram 1
Modbus RTU (Panel is master)

2.44.2 Parameters

Select Sanken VM06 inverter:


HMI:
Parameter Recommended setting Choices of setting Note
PLC type Sanken VM06 inverter - -
Port type RS485 RS485
Data bit 8 -
Stop bit 1 -
Parity Even parity -
Baud rate 9600 9600/115200/19200/187500
Station no. 1 0~31

Select Modbus RTU (Panel is master)


HMI:
Parameter Recommended setting Choices of setting Note
PLC type Modbus Rtu (Panel is - -
master)
Port type RS485 RS485
Data bit 8 -
Stop bit 1 -
Parity Even parity -
Baud rate 9600 9600/115200/19200/1875
00
Station no. 1 0~31

141
Inverter:
Function Name Content Debug
parameters
F1002 Frequency setting 1: operate panel 22
2: external analog voltage VIF1
(0~5V)
21: terminal stepper
22: communication
F1101 Running command 1. Operate panel 2. External 3
selection terminals 3. communication
F4002 RS232C/RS485 1: RS232C (default setting) Choose
2: RS485 according
to wiring
method
F4005 Serial communication 0: no function (default setting) 2
function 1: special protocol communication
2: Modbus communication
F4006 Inverter station no. 0~254: ModBus station no. 1
(1~32: RS485 communication)
1~32 is valid in special protocol
communication
F4007 Baud rate 1: 1200bps 2: 2400bps 4
3: 4800bps 4: 9600bps
5: 19200bps 6: 38400bps
7: 57600bps
F4008 Parity 0: no 1: odd (default setting) 2: even 2

142
F4009 Stop bit 1: 1 bit (default setting) 1
2: 2 bit
F4010 Stop code 0: CR+LF (default setting) 0
1: CR
※BINARY and Modbus without stop
code

2.44.3 Cable making

RS485:

Diagram 1

2.44.4 Device address

Inverter Modbus address

Function Upper limit frequency 33775 Data input/display


code Setting frequency 34869 Function button-set
data
Register Forward running 1001 Function button (2)
Reverse running 1001 Function button (8)
Setting frequency 1000 Function button

143
144
2.45 XINJE XD/XE series

2.45.1 Device type

Choose PLC type in


Series CPU Connection Communication Cable
Touchwin
Connect RS232 Diagram 1
XD/XE XD3/XE3 XINJE XD/XE series
CPU directly RS485 Diagram 2

2.45.2 Parameters

1. HMI setting
Parameters Recommended Other settings for choice Notes
setting
PLC type XINJE XD/XE XINJE XD/XE series /Modbus RTU (panel is
series Master)
/Modbus ASCII (panel is Master)
Serial port RS232 RS232/RS485
Data bit 8
Stop bit 1
Parity Even parity
Baud rate 19200 4800/9600/19200/38400/115200
Station no. 1 0~255

XINJE XD/XE series default parameters:

145
2. PLC setting

2.45.3 Cable making

1. XD/XE series PLC CPU (RS232 port)

146
Diagram 1

2. XD/XE series PLC CPU (RS485 port)

Diagram 2

2.45.4 Device address

PLC address type Range Object type Explanation


X 0~77 Bit Input relay
X1 xxxx 0~1777 Bit Extended module input relay
X2 xxxx 0~477 Bit Extended BD input relay
Y 0~77 Bit Output relay
Y1 xxxx 0~1777 Bit Extended module output relay
Y2 xxxx 0~477 Bit Extended BD output relay
M 0~7999 Bit Internal relay
S 0~1023 Bit Flow
SM 0~2047 Bit Internal relay, special using
T 0~575 Bit Timer
C 0~575 Bit Counter
ET 0~31 Bit Timer, precise timer
SE 0~31 Bit Sequence block wait instruction special coil
HM 0~959 Bit Internal relay, power-off retentive
HS 0~127 Bit Flow, power-off retentive
HT 0~95 Bit Auxiliary relay, power-off retentive
HC 0~95 Bit Counter, power-off retentive

147
HSC 0~31 Bit Counter, high speed counter
D 0~7999 Word//DWord Data register
ID 0~99 Word//DWord Analog input
ID1xxxx 0~1599 Word//DWord Extended module analog input
ID2xxxx 0~499 Word//DWord Extended BD analog input
QD 0~99 Word//DWord Analog output
QD1xxxx 0~1599 Word//DWord Extended module analog output
QD2xxxx 0~499 Word//DWord Extended BD analog output
SD 0~2047 Word//DWord Data register, special using
TD 0~575 Word//DWord Timer value
CD 0~575 Word//DWord Counter value
ETD 0~31 Word//DWord Timer value, precise timer
HD 0~999 Word//DWord Data register
HSD 0~499 Word//DWord Data register, power-off retentive
HTD 0~95 Word//DWord Timer value, power-off retentive
HCD 0~95 Word//DWord Counter value, power-off retentive
HSCD 0~31 Word//DWord Counter value, high speed counter
FD 0~6143 Word//DWord FlashROM reigster
SFD 0~1999 Word//DWord FlashROM register, special using
FS 0~47 Word//DWord Special security register
DM 0~7984 Word For data register
DX 0~60 Word For data register
DX1xxxx 0~1760 Word For data register, extended module
DX2xxxx 0~460 Word For data register, extended BD
DY 0~60 Word For data register
DY1xxxx 0~1760 Word For data register, extended module
DY2xxxx 0~460 Word For data register, extended BD
DS 0~1008 Word For data register
DSM 0~2032 Word For data register, special function using
DT 0~560 Word For data register
DC 0~560 Word For data register
DET 0~16 Word For data register, precise timer
DSE 0~16 Word For data register, WAIT instruction
DHM 0~944 Word For data register, power-off retentive
DHS 0~112 Word For data register, power-off retentive
DHT 0~80 Word For data register, power-off retentive
DHC 0~80 Word For data register, power-off retentive
DHSC 0~16 Word For data register, high speed counter

148
2.46 LG XGB series PLC

2.46.1 Device type

Series CPU Connection Communication Cable Choose PLC type


name in Touchwin
LG XGT/XGK
Programming
RS232 Diagram 1 series
XBC-DR10E port
(CPU Direct)
XGB XBC-DR20E
RS232 Diagram 2 LG
XBC-DR30E
CNet port RS485 Master-K80/120
Diagram 3
Series (CNet)

2.46.2 Parameters

1. Programming port
(1) HMI setting
Parameter Recommended setting Settings for Notes
choice
PLC type LG XGT/XGK series (CPU Direct)
Port RS232
Data bit 8
Stop bit 1
Parity No parity
Baud rate 115200
Station no. 0
LG XGT/XGK series (CPU Direct) default parameters:

149
Note: XGB series (CPU direct) only support baud rate 115200, cannot change the station no.

2. CNet port
(1) HMI setting
Parameter Recommended setting Settings for choice Notes
PLC type LG Master-K80/120 series (CNet)
Port RS232 RS232/RS485
Data bit 8
Stop bit 1
Parity No parity
Baud rate 9600 9600/19200/38400/115200/187500
Station no. 0 0~255
LG Master-K80/120 series (CNet) default parameters:

150
(2) PLC setting

a. RS232 communication
Tools-Network Manager to set parameters:

151
b. RS485 communication
Tools-Network Manager to set parameters:

152
2.46.3 Cable making

1. Programming port RS232

Diagram 1

2. CNet port RS232

153
Diagram 2

3. CNet port RS485

Diagram 3

2.46.4 Device address

PLC address Range Object type Explanation


P 0.0~65535.F Bit External I/O
65535 Word/DWord Data register
M 0.0~65535.F Bit Internal auxiliary output
65535 Word/DWord Data register
L 0.0~65535.F Bit External output
65535 Word/DWord Data register
F 0.0~65535.F Bit Data register
65535 Word/DWord Data register
T 65535 Word/DWord Data register
65535 Bit Timer
C 65535 Word/DWord Data register
65535 Bit Counter
D 65535 Word/DWord Data register
0.0~65535.F Bit Relay
S 65535 Bit Relay
K 65535 Word/DWord Data register
0.0~65535.F Bit Relay
Z 65535 Word/DWord Data register
0.0~65535.F Bit Relay

154
N 65535 Word/DWord Data register
0.0~65535.F Bit Relay
R 65535 Word/DWord Data register
0.0~65535.F Bit Relay
ZR 65535 Word/DWord Data register
0.0~65535.F Bit Relay
TS 65535 Word Data register
CS 65535 DWord Data register

2.47 Koyo Click series

2.47.1 Device type

Koyo Direct Logic series DL05, DL250… (connect to CPU unit directly)
Series CPU Connection module Port Wiring The PLC type in
type diagram TouchWin
Connect to CPU RJ-11 port
Click RS232 Diagram 1 Koyo Click series
(RS232 port)

2.47.2 Parameter setting

1. HMI setting
Parameter Recommended Optional settings Notes
setting
PLC type Koyo Click series
Port type RS232 RS232/RS422
Data bit 8
Stop bit 1
Parity Odd parity
Baud rate 38400 9600/19200/38400
Station no. 1 1~247

Koyo Click series default communication parameters:

155
2. PLC setting
Please refer to Koyo S series PLC settings.

2.47.3 Cable making

RS232 wiring:

2.47.4 Device address

Device type Range Object type Explanation


X0 1~16 Bit Input
X1 1~16 Bit I/O module 1 input

156
X2 1~16 Bit I/O module 2 input
Y0 1~16 Bit Output
Y1 1~16 Bit I/O module 1 output
Y2 1~16 Bit I/O module 2 output
C 1~2000 Bit Control bit
T 1~500 Bit Timer
CT 1~250 Bit Counter
SC 1~1000 Bit System control bit
DS 1~4500 Word Data temporary storage
register, support double
words
DD 1~1000 Word/DWord Data temporary storage
register, support double
words
TD 1~500 Word Timer present value
CTD 1~250 Word/DWord Counter present value,
support double words
SD 1~1000 Word System data temporary
storage register
DH 1~500 Word/DWord Data temporary storage
register
DF 1~500 DWord Data temporary storage
register (double words)
XD 0 Word/DWord Input state temporary
storage register
YD 0 Word/DWord Input state temporary
storage register
TXT 1~1000 Word/DWord texts temporary storage
register

2.48 Mitsubishi Melsec protocol

2.48.1 Device type

Communication
Series Cable diagram PLC model in Touchwin software
type
Mitsubishi L series
Mitsubishi Q series RJ45 Diagram 1 or 2 Mitsubishi Melsec

157
2.48.2 Parameter settings

Take Mitsubishi L series PLC as an example to explain the Melsec protocol device pararmeter
settings.
1. PLC software settings
Select project area-PLC parameter-Ethernet terminal setting, set the PLC IP address. The
communication data code please set to binary code communication. Select “permit write (FTP & MC
protocol) when running.

click “open the setting”, select ‘TCP” protocol and “MC” open mode, and set the station port no.
(range is 0401H~1387H, 1392H~FFFEH).

2. HMI setting
Please select the HMI type, click next.

158
Select Net device. The IP address in own devices is HMI IP address.

Right click Net device, click New. Then input the project name.

Select Mitsubishi Melsec series in the device list. The IP address is Mitsubishi PLC IP address,

159
the port 1025 is the station port no. setting in the Mitsubishi PLC.

Communication parameters: please use the default parameters. Communication status register: if
select this item, the status will occupy 4 registers. The register address can be set by user. If set the
address to PSW256, the register meanings are shown as the following.
PSW256: communication succeeded times
PSW257: communication failed times
PSW258: timeout times
PSW259: communication error times.

Then click next to finish the project setup.


In the editing screen, when user defines the button object, please select device 1.

160
2.48.3 Cable making

RJ45 straight through cable (connect HUB) or RJ45 crossover cable:

Diagram 1

Diagram 2

161
2.48.4 Device address

PLC address Range Object type Explanation


X 0~1fff Bit Input
Y 0~1fff Bit Output
M 0~8191 Bit Internal auxiliary relay
L 0~8191 Bit Lock relay
F 0~2047 Bit Alarm relay
V 0~2047 Bit Variable address relay
B 0~1fff Bit Link relay
TS 0~2047 Bit Timer relay
SS 0~2047 Bit Holding delay timer relay
CS 0~1023 Bit Counter relay
SB 0~7ff Bit Special link relay
S 0~2047 Bit Stepper relay
SM 0~2047 Bit Special relay
D 0~65535 Word/DWord Data register
W 0~1fff Word/DWord Link register
TC 0~2047 Word/DWord Timer coil
TN 0~2047 Word/DWord Timer present value
SC 0~2047 Word/DWord Holding delay timer coil
SN 0~2047 Word/DWord Holding delay timer present
value
CC 0~1023 Word/DWord Counter coil
CN 0~1023 Word/DWord Counter coil
SW 0~7ff Word/DWord Special link register
SD 0~2047 Word/DWord Special register
Z 0~19 Word/DWord Variable address register

2.49 Free type (panel is slave)

2.49.1 Device type

Series Port type Cable The PLC model in the Touchwin software
making
The device with serial port RS485 diagram 1 Free type (panel is slave)
and support free type RS232 diagram 2
protocol RS422 diagram 3

162
2.49.2 Parameter setting

1. HMI setting
Parameter Recommended setting Optional setting Notes
PLC model Free type (panel is
slave)
Port type RS485 RS485/RS232/RS422
Data bit 8 7/8
Stop bit 1 1/2
Parity Even parity Even /odd /no
Baud rate 9600 4800/38400/9600/115200/19200/187500
Station no. 1 0~255

Free type (panel is slave) default parameters:

2. Free type protocol


The HMI free type protocol is a simple protocol for connecting HMI with controller. The controller is
the master station, the HMI is slave station. It only needs to write simple communication program in
the controller but no need to make communication interruption service program.
The controller sends a request to the HMI, the HMI will reply after receiving the request. The max
data exchanging betweeen controller and HMI is 256 words, the HMI address range is
PSW256~PSW511. Each bit of the word can be used to coil. For example, coil PSWx.i (x=256~511,
i=00~15).
(1) Request format:
Station Command Address Length Data Parity

163
no.
Station no.: HMI station no. (0~255, 0 is broadcast mode, the HMI no need to reply)
Command: “R” is HMI read, “W” is HMI write
Address: index no., the index no. corresponding to HMI PSW256~PSW511 is 0~256
Length: PSW numbers (1~256) needs to read and write
Data: PSW value, there is no data for command “R”
Parity: add all the bytes from station no. to data (not include parity), get the remainder of 0x100 (if
the parity is 0x5A, ignore it, not check)

(2) Data response format:


Station State Address Length Data Parity
no.
State: communication state
0--- normal
1--- address error
2--- length error
3--- range error (address+length > 256)
4--- command error
When the command is “W” or abnormal, there is no address, length and data

Data format:
PSWi PSWi PSWi+1 PSWi+1 PSWi+n-1 PSWi+n-1
……
(high) (low) (high) (low) (high) (low)
Address is I, length is n.

(3) Protocol
The controller sends a request to the HMI, the HMI will check the parity after receiving the request. If
the parity is correct, and the station no. is equal to the HMI, the HMI will reply the request. Otherwise,
the HMI will not reply.
The controller will check the overtime of HMI response. If the time is over 50ms, the controller will
resend the request.
The HMI will check the overtime of receiving data. If the time is over 25ms, the HMI will initialize the
communication and wait for the new request.

Read (read HMI data)


Controller
Station no. “R” Address Length Data Parity

HMI
Station no. State Address Length Data Parity
Data: PSW value

Write(write data in HMI)


Controller

164
Station “W” Address Length Data Parity
no.

HMI
Station no. State Parity
State: 0--- OK

(4) Application
a. The controller read HMI data PSW256=0, PSW257=12
Controller send: 01H 52H 00H 02H 55H
HMI reply: 01H 00H 00H 02H 00H 00H 00H 0CH 0FH
b. Controller write 256 in HMI PSW256
Controller send: 01H 57H 00H 01H 01H 00H 5AH
HMI reply: 01H 00H 01H

2.49.3 Cable making

1. RS485 cable

Diagram 1

2. RS232 cable

Diagram 2

3. RS422 cable

165
Diagram 3

2.49.4 Device address

Address type Range Object type Property Notes


PSW 256.00~511.1 Bit R/W Internal coil
5
PSW 256~511 Word/Dwor R/W Data register
d

2.50 Modbus-TCP device

2.50.1 Device type

Series name Port type Cable making PLC model in Touchwin software
Ethernet device supporting RJ45 Diagram 1,
Modbus_TCP
Modbus TCP protocol diagram 2

2.50.2 Parameter setting

Take Xinje T-BOX as an example to explain the Modbus TCP parameter setting.

166
1. Hardware configuration
Wiring as the above diagram. Turn off of the TBOX DIP switch S3, make sure T-BOX is connected to
the Ethernet. Power on the device. Make sure the PLC is connected to the Ethernet.
Version requirements:
T-BOX hardware version 2.10 please use PLC software XCPpro version 3.3
T-BOX hardware version 2.0 please use PLC software XCPpro version 3.0f.

Please turn off DIP switch S3 to make the Ethernet indentifing the T-BOX for the firt time using.
Please use fixed IP address (192.168.0.111) for the T-BOX and connect it in the Ethernet to
configure the parameters. The IP of PC must be in the same gateway of T-BOX (192.168.0.***). As
each T-BOX default IP is the same, only one T-BOX can be configured in the network at one time.
Otherwise, the IP will be conflict.

2. T-BOX configuration
(1) T-BOX Link LED always ON means it has connected to the Ethernet (no need connect to PC
via RS232) when it connected to the Ethernet cable. Please use PLC software XCPpro to
configure the T-BOX. Please turn off DIP switch S3 to make the Ethernet indentifing the
T-BOX for the firt time using. T-BOX is slave station, please turn on DIP switch S1.
(2) Open XCPpro software, click option/Ethernet module settings. Click “refresh list”, it will show
the T-BOX in the network. Double click the T-BOX to configure.

The following is T-BOX setting window.

167
Log in name: set by user
Device ID: set by factory, cannot be changed
Remote log in: the purpose is to connect the TBOX with the Ethernet. If using Xinje server, the
parameters no need to change. If user can build server, please set the IP, port and server name of
the server.
Config network: the DIP switch S3 is OFF, please set the T-BOX IP, then turn ON S3. The network
will indentify the fixed IP of T-BOX.
Serial port: the parameters can be changed, but the parameters must be same to the device
connecting to the T-BOX.
Note: when it uses LAN, the remote log in address is:

(3) When the S2 switch is OFF, shut down the log in server, click option/comm mode setting, set
as the following to monitor the PLC.

168
When using Xinje company server, the remote log in address is:

Turn on S2 switch, startup the log in server, click option/comm mode setting, set as the following, it
can monitor the PLC after logging in server successfully.

(4) For the first time using, in order to make the network indentify the T-BOX, the S3 switch is
OFF. It can change the IP address after connecting successfully.

169
3. HMI software setting
(1) Select the HMI model TN(-ET), TG(-ET), TE(-ET), click next, select “Net device” in the list.
Please set the HMI IP address in the own devices. The IP cannot be conflict with other
device.

(2) Right click the “Net device”, select “New”. The new project name is device.

(3) Please select Modbus TCP device for communicating with T-BOX. This IP is T-BOX IP
address, the port 502 cannot be changed.

(4) The communication parameters please keep defaulted. If selecting communicate status
register, the PSW256~PSW259 represents communicate successful times, communication

170
failure times, communication overtime times, communication error times. User can change
the PSW address.

(5) Click next to finish the setting. Then enter the editing screen, put a data input button on the
screen, select “device”, the object type includes 4x(read and write, word object), 3x(read
only, word object), 0x(bit object, read and write), 1x(read only, bit object).

(6) Download the program in the HMI.


Note: T-BOX can connect multi-PLC through RS485, the station no. can be set in the XCPpro
software. Please set the “send delay” time to improve the communication speed.

171
2.50.3 Cable making

RJ45 straight through cable (connect HUB) or RJ45 crossover cable:

Diagram 1

172
Diagram 2

2.50.4 Device address

Address Range Object type propert Notes


y
0x 0~65535 Bit R/W I/O internal coil
1x 0~65535 Bit R I/O internal coil
4x 0.00~65535.1 Bit R/W I/O internal coil
5
4x 0~65535 Word/Dwor R/W Data register
d
3x 0~65535 Word/Dwor R Data register
d

2.51 Mitsubishi FX5U series

2.51.1 Device type

PLC type in
Series Connection Communication
CPU unit Cable touchwin
name module type
software

FX5U CPU unit Mitsubishi FX5U


RS485 Fig 1
series connect directly series

2.51.2 Parameter setting

HMI setting

Parameter Recommended Optional setting Notes


setting
PLC type Mitsubishi FX5U Mitsubishi FX5U series/ When choose Q
series Mitsubishi Q series series, the I/O is
decimal format
Port type RS485
Data bit 8
Stop bit 1

173
Parity Odd
Baud rate 19200
Station no. 0 Please use the
recommended
settings

Mitsubishi FX5U series communication parameter setting

Note: the HMI station no. is 0, it cannot change.

174
PLC setting

(1) MC protocol communication

Please set the protocol format to MC protocol in RS485 serial port. The trasfer mode is set to
mode 5.

175
(2) Modbus RTU communication
The HMI please choose“Modbus RTU”protocol.
Please set the protocol format to Modbus RTU in RS485 serial port, and set the Modbus station no.
to non-zero number, the HMI parameters must be same to PLC settings.

Notes: PLC has fixed Modbus address in Modbus communication, it will read and write as
the address.

176
2.51.3 Cable making

Please use the RS485 port on FX5U CPU unit.

Fig1

177
2.51.4 Device address

PLC Range Object type Explanation


address type
X 0~8191 Bit Input
Y 0~8191 Bit Output
M 0~8191 Bit Internal auxiliary relay
B 0~8191 Bit Linkage relay
SB 0~2047 Bit Internal special linkage relay
DX 0~8191 Bit Direct input
DY 0~8191 Bit Direct output
S 0~8191 Bit Step relay
SM 0~2047 Bit Internal special step relay
L 0~8191 Bit Locking relay
F 0~2047 Bit Alarm
V 0~2047 Bit Variable address relay
TS 0~2047 Bit Timer contactor
TC 0~2047 Bit Timer coil
SS 0~2047 Bit Accumulated timer contactor
SC 0~2047 Bit Accumulated timer coil
CS 0~1023 Bit Counter contactor
CC 0~1023 Bit Counter coil
D 0~12287 Word/DWord Data register
W 0~8191 Word/DWord Linkage register
SW 0~2047 Word/DWord Internal special linkage register
ZR 0~1042431 Word/DWord File register
SD 0~2047 Word/DWord Internal special register
TN 0~2047 Word/DWord Timer
SN 0~2047 Word/DWord Accumulated timer
CN 0~1023 Word/DWord Counter
Z 0~15 Word/DWord Variable register
R 0~32767 Word/DWord File register

178
2.52 Siemens S7-200 smart series

2.52.1 Device type

Series name Communication Cable PLC type in touchwin software


type making
S7-200 smart RJ45 fig 1 or fig 2 Siemens S7-200 smart series

2.52.2 Parameter setting

PLC setting

179
Touchwin software setting
1. Choose the HMI type TN(-ET), TG(-ET) or TE(-ET), click next, choose Net device
in the list, please inputthe HMI IP address in the own devices.

2. Choose the net device, right click it, choose new, and name it as S7-200 smart.

3. Choose Siemens S7-200 smart series in the device list, in this example, the PLC
IP address is 192.168.0.1, the port is 102 which cannot be changed.

180
4. The communication parameters please use default settings. If communication
status register is choosen, and set to PSW256, then PSW256~PSW259 means
communication succeeded times, failed times, overtime times, error times. The
register address can be set by user.

5. Click next to finish the settings. Then enter the screen, for example, put a data
input button in the screen, choose the device S7-200 smart.

181
There is no station no. for Siemens S7-200 smart, set the correct IP address is ok. It can
make the networks of multi-HMI-one-PLC, one-HMI-multi-PLC, multi-HMI-multi-PLC.

2.52.3 Cable making

RJ45 Straight Through Cable (connect HUB) or RJ45 Crossover Cable:

Diagram 1

182
Diagram2

183
2.52.4 Device address

Siemens S7-200smart series


PLC address Range Data type Explanation
VB 0~9999 Byte variable byte data register
VW 0~9999 Word variable word data register
VD 0~9999 DWord variable double word data register
IB 0~15 Byte External input byte reflection register
IW 0~15 Word External input word reflection register
ID 0~15 DWord External input double words reflection register
QB 0~15 Byte External output byte reflection register
QW 0~15 Word External output word reflection register
QD 0~15 DWord External output double words reflection register
MB 0~31 Byte Internal auxiliary byte register
MW 0~31 Word Internal auxiliary word register
MD 0~31 DWord Internal auxiliary double words register
SMB 0~299 Byte Internal special auxiliary byte register
SMW 0~299 Word Internal special auxiliary word register
SMD 0~299 DWord Internal special auxiliary double words register
SB 0~31 Byte Special auxiliary byte register
SW 0~31 Word Special auxiliary word register
SD 0~31 DWord Special auxiliary double words register
T 0~255 Word Register
C 0~255 Word Register
M 0.0~31.7 Bit Bit register
V 0.0~9999. Bit Variable register
7
I 0.0~15.7 Bit External input coil
Q 0.0~15.7 Bit External output coil
SM 0.0~299.7 Bit Special relay
S 0.0~31.7 Bit Sequence relay
T 0~255 Bit Timer
C 0~255 Bit Counter

184
2.53 Siemens S7-300 series

2.53.1 Device type

Series name Communication Cable making PLC type in touchwin


type software
S7-300 RJ45 Siemens S7-300
Fig 1 or fig 2
series

2.53.2 Parameter setting

PLC setting

HMI setting
1. Choose the HMI type TN(-ET), TG(-ET) or TE(-ET), click next, choose Net device
in the list, please inputthe HMI IP address in the own devices.

185
2. Choose the net device, right click it, choose new, and name it as S7-300.

3. Choose Siemens S7-300 series in the device list, in this example, the PLC IP
address is 192.168.0.5, the port is 102 which cannot be changed.

186
4. The communication parameters please use default settings. If communication
status register is choosen, and set to PSW256, then PSW256~PSW259 means
communication succeeded times, failed times, overtime times, error times. The
register address can be set by user.

5. Click next to finish the settings. Then enter the screen, for example, put a data
input button in the screen, choose the device S7-300.

187
There is no station no. for Siemens S7-300, set the correct IP address is ok. It can make
the networks of multi-HMI-one-PLC, one-HMI-multi-PLC, multi-HMI-multi-PLC.

2.53.3 Cable making

RJ45 Straight Through Cable (connect HUB) or RJ45 Crossover Cable:

Diagram 1

188
Diagram2

189
2.53.4 Device address

Siemens S7-300 series


PLC address Range Data type Explanation
VB 0~9999 Byte variable byte data register
VW 0~9999 Word variable word data register
VD 0~9999 DWord variable double word data register
IB 0~15 Byte External input byte reflection register
IW 0~15 Word External input word reflection register
ID 0~15 DWord External input double words reflection register
QB 0~15 Byte External output byte reflection register
QW 0~15 Word External output word reflection register
QD 0~15 DWord External output double words reflection register
MB 0~31 Byte Internal auxiliary byte register
MW 0~31 Word Internal auxiliary word register
MD 0~31 DWord Internal auxiliary double words register
SMB 0~299 Byte Internal special auxiliary byte register
SMW 0~299 Word Internal special auxiliary word register
SMD 0~299 DWord Internal special auxiliary double words register
SB 0~31 Byte Special auxiliary byte register
SW 0~31 Word Special auxiliary word register
SD 0~31 DWord Special auxiliary double words register
T 0~255 Word Register
C 0~255 Word Register
M 0.0~31.7 Bit Bit register
V 0.0~9999. Bit Variable register
7
I 0.0~15.7 Bit External input coil
Q 0.0~15.7 Bit External output coil
SM 0.0~299.7 Bit Special relay
S 0.0~31.7 Bit Sequence relay
T 0~255 Bit Timer
C 0~255 Bit Counter

190
2.54 X-NET communication
X-NET bus is the bus protocol between TG/TE series HMI and XD series PLC. The TG
series -NT model is a dedicated screen for bus communication, which has faster
communication speed and better networking performance. It is recommended to choose
-NT model when bus communication.

2.54.1 Device type

PLC type in
Series Connection Communication Cable
CPU unit touchwin
name module type making
software
CPU direct RS485 Fig 1 or 2
connect Xinje Xnet
XD XD3/XDM/XDC
extension BD RS232 Fig 3 series
module

2.54.2 HMI setting

Parameters Recommended Optional setting Notes


setting
PLC type Xinje Xnet series 1. PLC station
Communication RS485 RS485/RS232 no. must be
port 2 for auto
Data bit 8 matching
Stop bit 1 2. –NT model
Parity Even parity has no
Auto match baud 57600 57600 RS232 for
rate PLC port
Set baud rate 57600 9600~3M
manually
Stataion no. 1 1~100

X-NET bus includes two connection modes: OMMS mode which is supported by
TG/TE series(single HMI mode including one HMI one device, one HMI multi-device);
TBN mode which is supported by NT model(multi-HMI mode including multi-HMI
one device, multi-HMI multi-device). The XD series PLC must be hardware v3.2.2
and up. The download port and PLC port is separate for TG/TE series HMI.

2.54.2.1 OMMS mode


OMMS mode includes auto match and manual setting. If auto match is selected, there is
no need to set the parameters, this mode is fit for one HMI one device communication,

191
and the PLC station no. should be no. 2, baud rate must be 57600pbs.
The default is manual setting mode if auto match is not selected. In this case, it needs to
use xinje config tool to set the HMI parameters, PLC station no. and baud rate are not
limited, please choose them as you need.
1. Auto match
Touchwin software can automatic set the communication parameters in auto match mode,
only TG/TE series HMI PLC port OMMS mode support auto match mode.
When building the HMI program, PLC port please choose xinje Xnet series, PLC port
device please choose auto match, other no needs to set.

2. Manual set
(1) make a new HMI program, the download port please set to xinje Xnet series, PLC port
please set to xinje Xnet series, the screen contents can be anything, and download the
program in the HMI.
(2) connect the download port of HMI with PC, power on the HMI.
(3) open xinje config tool, click config/ find device

192
(4) choose the com port, which is the PC serial port, it will show the config tool main
interface after the connection is normal.

If the connection fails, a connection failure window will pop up. Please check whether the
RS232 serial port line is wrong and close other software that occupies the serial port. The
bus can be initialized if cannot connecting, set ON switch 4 on the back of the touch
screen, restart the touch screen, and download the newly created program again. After
the download, set OFF switch 4, and then repeat the connection operation.
(5) After the connection is successful, click config/single device/com port:

(6) set the serial port parameters and net id, click write config and close the window.

193
Com port no.: 1 means HMI download port, 2 meaqns HMI PLC port.
Choose Net: please choose X-NET.
Choose PHY(physical layer): RS232 communication (-NT model PLC port not support),
RS485 communication.
Net ID: the communication network no., all the devices in the same network should have
the same network no., the range is 1 to 32767.
Station no.: it must be 1 for OMMD mode HMI station no.
Net type: please choose OMMS mode (which is single HMI mode)
Baud rate: the max baud rate is 115200 for TG/TE series PLC port, download port, and
-NT model download port, the max baud rate is 3M for –NT model PLC port.
Cycle: please choose this when PLC supports motion bus.
OMMS_slaver list: all the slave station no. connecting the HMI. For example, one HMI
connects two PLCs, the station no. of the two PLCs are 2 and 3, it must set 0,2,3 here.
Otherwise it will not communicate.
(7) click config/single device/route

(8) first please read the HMI setting, then choose add item, set the parameters, then click
write.

194
Net: the net id in the serial port setting.
Com no.: com port no. in the serial port setting.
Gateway: it is 0 in the same network. For cross network communication, it is the
station no. that the cross network transfer equipment signal accesses the serial port.
(note: cross network communication must be PLC hardware v3.3 and up)

After setting, please restart the HMI to make the setting effective.

2.54.2.2 TBN mode


Only –NT model supports this mode. Repeat OMMS mode manual step 1 to 5.
(6) set the serial port parameters and net id, click write config and close the window

Com port no.: 1 means HMI download port, 2 meaqns HMI PLC port.
Choose Net: please choose X-NET.
Choose PHY(physical layer): RS232 communication (-NT model PLC port not support),
RS485 communication.
Net ID: the communication network no., all the devices in the same network should have
the same network no., the range is 1 to 32767.

195
Station no.: set any station no. for the PLC and HMI in the network.
Net type: please choose TBN mode (which is multi-HMI mode)
Baud rate: the max baud rate is 115200 for-NT model, the max baud rate is 3M for –NT
model PLC port.
Tokencycle time: the longest time the token passes one circle. The default time is
1000ms.
Max station no.: It refers to the largest station number in a network, and the
communication token will be searched from station 1 to the largest station number.
Considering the communication speed, it is suggested that the customer choose the
continuous station number when assigning station number, and the largest station number
cannot exceed 100.
(7) click config/single device/route

(8) first please read the HMI setting, then choose add item, set the parameters, then click
write.

After setting, please restart the HMI to make the setting effective.

196
Note: in the HMI program, the Net ID corresponds to the net numer in the serial port
configuration, station corresponds to the station number in the serial port
configuration.

2.54.3 XD series PLC setting (PLC hardware V3.2.2 and up)

Connect the PLC to the computer through USB cable or port1, power the PLC, and repeat
the OMMS manual configuration step 3-5. If PLC and computer communication is not
normal, the corresponding error message will appear. At this time, you need to restart
Config software and start the configuration again until the error message below appears.

197
Set the serial port parameters, net id, then click write config and close the window.

Fig. 3-1 OMMS mode

Fig. 3-2 TBN mode

198
Port1 Port4 Port5
Serial port: PLC port no., please set as actual connection port no.

XD series PLC port definition and functions:


● COM X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27 X31 X33 X35 X37 X41 X43
Port Appearance COM X0 X2 X4 X6
Port definition
X10 X12 X14 X16 X20 X22 X24 X26
Serial port no.
X30 X32 X34 X36 X40 X42

0 1 2 3 4 5 6 7
Xinje Electronic Co.,Ltd

PROGRAMMABLE CONTROLLER
DATE:20120701
TYPE:XD3-48R-E
SN:201208021525

Port1 RS232 port 1


PWR
COM0 X
RUN
XD3-60R-E ERR
Y

Port2 A, B RS485 port 0 1 2 3 4 5 6 7


2

0V ● ● ● Y0 Y1 Y2 Y3 Y4 COM5 Y7 Y10 Y12 COM7 Y15 Y17 Y20 Y22 COM9 Y25 Y27
24V ● A B COM0 COM1 COM2 COM3 COM4 Y5 Y6 COM6 Y11 Y13 Y14 Y16 COM8 Y21 Y23 Y24 Y26
USB USB port

Left extension ED
Port3 Developping 3
port
A B

RS232 port/RS485
Port3
Port4
USB口 Port2 port/optical fiber 4, 5
Port5 Up extension BD
port
(left Port4, right
Port5)

Station no.: the PLC station no. in the network, the range is 1 to 100. The operate object
station no. in the HMI corresponds to this station no. note: the PLC station no. must be 2
in OMMS auto match mode.
Net type: OMMS: one HMI one device, one HMI multi-device (fig. 3-1), multi-HMI
multi-device (fig. 3-2). Please choose it as the actual needs.
Baud rate: set the same baud rate for HMI and PLC.
Other settings please refer to the above HMI setting.

click config/single device/route:

199
First read the settings, then click add item, set the parameters, then click write.

After finishing the configuration, restart the PLC to make the settings effective.

2.54.4 Cable making

Model Hardware Communication PLC port cable Download port cable


version type making making
TG/TE RS485 Fig 1 Fig 1
RS232 Fig 3
TG765-NT V1.0 RS485 Fig 1 Fig 1
(TN765-ET) RS232 \ Fig 3
V1.1 and up RS485 Fig 2 Fig 1
RS232 \ Fig 3
TG865-NT V1.0 and up RS485 Fig 2 Fig 1
(TN865-ET) RS232 \ Fig 3
TGA63-NT V1.0 and up RS485 Fig 2 Fig 1
(TNA63-ET) RS232 \ Fig 3

2.54.4.1 Cable
1. TE/TG and TG765-NT (V1.0) (RS485 mode)

Fig 1

200
2. –NT model (V1.1) PLC port RS485 mode

Fig 2
Note: use together with JA-NE-I, which is easy to wiring.

3. TE/TG (dowload port) series RS232 mode

Fig 3

2.54.4.2 OMMS wiring mode (-NT model PLC port no RS232)

201
2.54.4.3 TBN wiring mode

2.54.5 Device address

PLC address Range Object type Notes


X 0~77 Bit Input
X1 xxxx 0~1777 Bit Extension module input
X2 xxxx 0~277 Bit Extension BD input
Y 0~77 Bit Output
Y1 xxxx 0~1777 Bit Extension module output
Y2 xxxx 0~277 Bit Extension BD output
M 0~4999 Bit Internal auxiliary relay
S 0~7999 Bit Status relay
SM 0~4999 Bit Special status relay
T 0~4999 Bit Timer
C 0~4999 Bit Counter
ET 0~39 Bit Timer, precise timer
SE 0~31 Bit Sequence block special coil for wait
instruction
HM 0~11999 Bit Internal relay, hold during power off
HS 0~999 Bit Process, hold during power off
HT 0~1999 Bit Auxiliary relay, hold during power off
HC 0~1999 Bit Counter, hold during power off
HSC 0~39 Bit Counter, high speed counter
D 0~4999 Word//DWord Data register
ID 0~99 Word//DWord Analog input
ID1xxxx 0~1599 Word//DWord Extension module analog input
ID2xxxx 0~299 Word//DWord Extension BD analog input
QD 0~99 Word//DWord Analog output
QD1xxxx 0~1599 Word//DWord Extension module analog output
QD2xxxx 0~499 Word//DWord Extension BD analog output

202
SD 0~4999 Word//DWord Data register, special purpose
TD 0~4999 Word//DWord Timer value
CD 0~4999 Word//DWord Counter value
ETD 0~39 Word//DWord Timer value, precise timer
HD 0~24999 Word//DWord Data register
HSD 0~1999 Word//DWord Data register, hold during power off
HTD 0~1999 Word//DWord Timer value, hold during power off
HCD 0~1999 Word//DWord Counter value, hold during power off
HSCD 0~39 Word//DWord Counter value, high speed counter
FD 0~8899 Word//DWord FlashROM register
SFD 0~5999 Word//DWord FlashROM register, special purpose
FS 0~299 Word//DWord Special security register
DM 0~74984 Word Used as a data register
DX 0~60 Word Used as a data register
DX1xxxx 0~1760 Word Used as a data register, extension module
DX2xxxx 0~260 Word Used as a data register, extension BD
DY 0~60 Word Used as a data register
DY1xxxx 0~1760 Word Used as a data register, extension module
DY2xxxx 0~260 Word Used as a data register, extension BD
DS 0~7984 Word Used as a data register
DSM 0~4984 Word Used as a data register, special function
DT 0~4984 Word Used as a data register
DC 0~4984 Word Used as a data register
DET 0~24 Word Used as a data register, precise timer
DSE 0~16 Word Used as a data register, special for
sequence block wait instruction
DHM 0~11984 Word Used as a data register, hold during power
off
DHS 0~984 Word Used as a data register, hold during power
off
DHT 0~1984 Word Used as a data register, hold during power
off
DHC 0~1984 Word Used as a data register, hold during power
off
DHSC 0~24 Word Used as a data register, high speed
counter

203
2.55 Keyence KV5000

2.55.1 Device type

Communication
Series Cable making PLC model selection in touchwin
type
Keyence
RJ45 Fig 1 or 2 Keyence KV5000/5500/7500
KV5000

2.55.2 Parameter setting

Take Keyence KV5000 PLC as an example to explain the settings of communication device.

PLC software settings:


1. Startup KV STUDIO, click the unit edit, choose KV 5000, set the label in the unit, execute
the Ethernet settings of KV5000, shown as below figure:

225
HMI settings:
1. choose HMI model TN(-ET), TG(-ET) or TE(-ET), click next, then choose net device, fill in
the IP address of HMI. The HMI IP cannot be conflict with other devices in the network.

2. right click the net device, build a new project, and name it as keyence KV5000.

225
3. choose Keyence (KV5000/5500/7500) protocol in the list, and fill in the PLC IP address, the
port is PLC port no. set in the PLC software.

4. Please keep the communication parameters as default, if the communicate status regsiter
is selected,
PSW256~PSW259 respectively indicate communication successful times, failed times,

225
overtime times, error times. User can set the register address as needs.

5. click next to finish the settings and enter screen edit interface. Put a data input button on
the screen, and choose the keyence KV5000 in the device list.

2.55.3 Cable making

RJ45 Straight Through Cable (connect HUB) or RJ45 Crossover Cable:

Fig 1

225
Fig 2

2.55.4 Device address

PLC address Range Object type Notes


MR 0.00~999.15 Bit Internal relay
LR 0.00~999.15 Bit
CR 0.00~39.15 Bit
T 0~3999 Bit Timer
C 0~3999 Bit Counter
DM 0~65534 Word/DWor Data register
d
TM 0~11998 Word Temporary data regsiter
EM 0~511 Word Expanded data memory
FM 0~65534 Word Flash data memory
CM 0~32766 Word
TDC 0~3999 Word
CDC 0~3999 Word
TS 0~3999 Word Timer
CS 0~3999 Word Counter

225
2.56 LG XGT

2.56.1 Device type

Communication
Series name Cable making PLC model selection in touchwin
type
LG XGT series RJ45 Fig 1 or 2 LG XGT protocol

2.56.2 Parameter setting

Take LG XGT series PLC as an example to explain the communication settings.

PLC settings:
Open the PLC software, set the PLC IP to 192.168.6.10 for example.

HMI settings:
1. choose HMI model TN(-ET), TG(-ET) or TE(-ET), click next, then choose net device,
fill in the IP address of HMI. The HMI IP cannot be conflict with other devices in the
network. The HMI IP is set to 192.168.6.11 for example.

2. right click the net device, build a new project, and name it as LG XGT.

225
3. choose LG XGT series protocol in the list, and fill in the PLC IP address, the port is PLC
port no. set in the PLC software.

4. Please keep the communication parameters as default, if the communicate status regsiter
is selected,
PSW256~PSW259 respectively indicate communication successful times, failed times,
overtime times, error times. User can set the register address as needs.

5. click next to finish the settings and enter screen edit interface. Put a data input button on
the screen, and choose the LG XGT in the device list.

225
2.56.3 Cable making

RJ45 Straight Through Cable (connect HUB) or RJ45 Crossover Cable:

Fig 1

225
Fig 2

2.56.4 Device address

PLC address Range Object type Notes


P 0.0~65535.F Bit Input/output
0~65535 Word/DWord Data register
M 0.0~65535.F Bit Internal auxiliary relay
0~65535 Word/DWord Data register
L 0.0~65535.F Bit Communication output
0~65535 Word/DWord Communication register
F 0.0~65535.F Bit Internal special relay
0~65535 Word/DWord Internal special data register
T 0~65535 Word/DWord Timer present value
0~65535 Bit Timer
C 0~65535 Word/DWord Counter present value
0~65535 Bit Counter
D 0~65535 Word/DWord Data register
0.0~65535.F Bit Bit of Data register
S 0~65535 Bit Step relay
K 0~65535 Word/DWord Retentive data register
0.0~65535.F Bit Retentive relay
Z 0~65535 Word/DWord Index data register
0.0~65535.F Bit Index relay
N 0~65535 Word/DWord Communication register
0.0~65535.F Bit Communication relay
R 0~65535 Word/DWord Data register

225
0.0~65535.F Bit Relay
ZR 0~65535 Word/DWord Data register
0.0~65535.F Bit Relay
TS 0~65535 Word/DWord Timer set value
CS 0~65535 Word/DWord Counter set value

2.57 Haiwell

2.57.1 Device type

Communication
Series name Cable making The PLC model in touchwin
type
Haiwell PLC RJ45 Fig 1 or 2 Haiwellbus TCP protocol

2.57.2 Parameters

Take Haiwell PLC as an example to explain the communication settings.

PLC settings:
Open the PLC software, set the PLC IP to 192.168.1.111 for example.

HMI settings:
1. choose HMI model TN(-ET), TG(-ET) or TE(-ET), click next, then choose net device,
fill in the IP address of HMI. The HMI IP cannot be conflict with other devices in the
network. The HMI IP is set to 192.168.1.11 for example.

2. right click the net device, build a new project, and name it as Haiwellbus TCP.

225
3. choose Haiwellbus TCP protocol in the list, and fill in the PLC IP address, the port is PLC
port no. set in the PLC software.

4. Please keep the communication parameters as default, if the communicate status regsiter
is selected,
PSW256~PSW259 respectively indicate communication successful times, failed times,

225
overtime times, error times. User can set the register address as needs.

5. click next to finish the settings and enter screen edit interface. Put a data input button on
the screen, and choose the Haiwellbus tcp in the device list.

2.57.3 Cable making

RJ45 Straight Through Cable (connect HUB) or RJ45 Crossover Cable:

Fig 1

225
Fig 2

2.57.4 Device address

PLC address Range Object type Notes


X 0~1023 Bit Digital input
Y 0~1023 Bit Digital output
M 0~12287 Bit Internal relay
T 0~1023 Bit Timer
C 0~255 Bit Counter
SM 0~215 Bit System status bit
S 0~2047 Bit Step relay
CR 0~255 Word/DWord Extended module parameter
AI 0~255 Word/DWord Analog input
AQ 0~255 Word/DWord Analog output
V 0~14847 Word/DWord Internal register
TV 0~1023 Word/DWord Timer
CV 0~255 Word/DWord Timer
SV 0~900 Word/DWord Step driver

225
Que esse conteúdo tenha agregado valor e conhecimento pra você!

Seu contato é importante para nós!


• www.kalatec.com.br
• Instagram - @kalateceautomação
• Facebook - kalatecautomação

NOSSAS FILIAIS

Matriz Campinas – SP Filial São Paulo – SP Filial Joinville – SC


Rua Salto, 99 Av. das Nações Unidas, R. Almirante Jaceguay,3659
Jd. Do Trevo 18.801 – 11º andar Bairro Costa e Silva
(19) 3045-4900 (11) 5514-7680 (47) 3425-0042

225

You might also like