Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

190037

Download as pdf or txt
Download as pdf or txt
You are on page 1of 82

DXM100-Bx Wireless Controller

Instruction Manual

Instruction Manual

Original Instructions
190037 Rev. C
21 October 2016
Banner Engineering Corp. All rights reserved

190037
DXM100-Bx Wireless Controller Instruction Manual

Contents
1 DXM Overview ................................................................................................................ 5
1.1 DXM100-Bx System Overview .....................................................................................................5
1.2 DXM Automation Protocols ......................................................................................................... 6
1.3 DXM Modbus Overview .............................................................................................................. 6
1.4 DXM Configuration Tool Overview ................................................................................................7
2 DXM Controller ............................................................................................................... 8
2.1 DXM Hardware Configuration Overview ........................................................................................ 8
3 ISM Radio Board ............................................................................................................. 9
3.1 ISM Radio Board (Modbus Slave ID 1) .........................................................................................9
3.1.1 DIP Switch Settings for the MultiHop HE5 Board Module ........................................................9
3.1.2 DIP Switch Settings for the Gateway PEx Board Modules ..................................................... 10
3.2 Binding and Conducting a Site Survey with the ISM Radio ............................................................11
3.2.1 Entering Binding Mode ....................................................................................................11
3.2.2 Conducting a Site Survey ................................................................................................11
3.3 Modbus Registers for the Gateway Performance 1 Watt Radio ........................................................11
3.3.1 Alternative Modbus Register Organization ......................................................................... 12
3.4 Modbus Registers for the MultiHop 1 Watt Radio Board ................................................................. 14
4 Processor Board ........................................................................................................... 15
4.1 SAM4 Processor Board ............................................................................................................ 15
4.1.1 DIP Switch Configuration ................................................................................................ 15
4.1.2 Button Operation ........................................................................................................... 16
4.1.3 LED Operation ...............................................................................................................16
4.2 Ethernet ................................................................................................................................16
4.3 USB ......................................................................................................................................16
4.4 Modbus Registers - Internal Local Registers (Modbus Slave 199) .................................................. 16
4.4.1 Local Registers 1850 (Internal Processor Memory, 32-bit, Unsigned) ...................................16
4.4.2 Local Registers 851900 (Data Flash, Non-volatile, 32-bit, Unsigned) ................................... 17
4.4.3 Local Registers 10011900 (32-bit IEEE Floating Point) ...................................................... 17
4.4.4 Virtual Registers ............................................................................................................ 17
4.4.5 Reset Codes ..................................................................................................................18
5 I/O Base Board for the DXM100-B1 Models .................................................................. 19
5.1 DXM100-B1 I/O Base Board Connections ................................................................................... 19
5.1.1 DIP Switches for the I/O Board ........................................................................................ 19
5.1.2 I/O Board Jumpers ........................................................................................................20
5.2 Applying Power to the DXM100-Bx Wireless Controller ..................................................................20
5.2.1 Using Courtesy Power or Switch Power ............................................................................ 20
5.2.2 Associating a Switched Power Output to an Input .............................................................. 21
5.2.3 Connecting a Battery to the DXM Controller .......................................................................23
5.2.4 Supplying Power from a Solar Panel ................................................................................. 23
5.3 Working with Solar Power ........................................................................................................24
5.3.1 Setting the DXM Controller for Solar Power ...................................................................... 24
5.3.2 Solar Components ........................................................................................................ 25
5.3.3 Recommended Solar Configurations ................................................................................ 26
5.3.4 Monitoring Solar Operation .............................................................................................26
5.4 Connecting the Communication Pins ..........................................................................................27
5.4.1 Modbus RTU Master/Modbus RTU Slave ........................................................................... 27
5.5 Modbus Master Port and Slave Port ........................................................................................... 27
5.5.1 Modbus Master and Slave Port Settings ............................................................................27
5.5.2 Modbus Slave Port ID .................................................................................................... 28
5.6 Inputs and Outputs ..................................................................................................................28
5.6.1 Universal Inputs ........................................................................................................... 29
5.6.2 NMOS Outputs ............................................................................................................. 30
5.6.3 Analog (DAC) Outputs ................................................................................................... 30
5.6.4 Modbus I/O Registers for the DXM100-B1 I/O Base Board ................................................... 31
5.7 Restoring Factory Default Settings ............................................................................................ 34
5.8 Setting the Modbus Slave ID on the I/O Base Board .....................................................................34
6 I/O Base Board for the DXM100-B2 Models .................................................................. 36
6.1 DXM100-B2 and S2 I/O Base Board Connections ........................................................................ 36
6.1.1 DIP Switches for the I/O Board ........................................................................................ 36
6.2 Applying Power to the DXM100-Bx Wireless Controller ..................................................................37
6.2.1 Using Courtesy Power or Switch Power ............................................................................ 37
6.2.2 Associating a Switched Power Output to an Input .............................................................. 38
6.2.3 Connecting a Battery to the DXM Controller .......................................................................40
DXM100-Bx Wireless Controller Instruction Manual

6.2.4 Supplying Power from a Solar Panel ................................................................................. 40


6.3 Working with Solar Power ........................................................................................................41
6.3.1 Setting the DXM Controller for Solar Power ...................................................................... 41
6.3.2 Solar Components ........................................................................................................ 41
6.3.3 Recommended Solar Configurations ................................................................................ 42
6.3.4 Monitoring Solar Operation .............................................................................................43
6.4 Connecting the Communication Pins ..........................................................................................43
6.4.1 Modbus RTU Master/Modbus RTU Slave ........................................................................... 44
6.5 Modbus Master Port and Slave Port ........................................................................................... 44
6.5.1 Modbus Master and Slave Port Settings ............................................................................44
6.5.2 Modbus Slave Port ID .................................................................................................... 45
6.6 Inputs and Outputs ..................................................................................................................45
6.6.1 Universal Inputs ........................................................................................................... 46
6.6.2 NMOS Outputs ............................................................................................................. 47
6.6.3 Analog (DAC) Outputs ................................................................................................... 47
6.6.4 DC Latching Outputs ...................................................................................................... 48
6.6.5 SDI-12 Interface .......................................................................................................... 48
6.6.6 Modbus I/O Registers for the DXM100-B2 I/O Base Board ................................................... 51
6.7 Restoring Factory Default Settings ............................................................................................ 53
6.8 Setting the Modbus Slave ID on the I/O Base Board .....................................................................53
7 Cellular CDMA ............................................................................................................... 55
7.1 Cellular Modem Board ............................................................................................................. 55
7.2 Cellular Power Requirements ....................................................................................................55
7.3 DXM Cellular Modem ................................................................................................................55
7.3.1 Configure the DXM Controller for a Cellular Modem ............................................................ 55
7.3.2 Cellular Activation Quick Start Guide ................................................................................ 56
7.3.3 DXM Cellular VPN Setup ..................................................................................................57
7.4 Accessing the DXM Using SMS ...................................................................................................57
7.4.1 HTTP Push .................................................................................................................... 57
7.4.2 Reboot ......................................................................................................................... 57
7.4.3 Get Register ..................................................................................................................57
7.4.4 Set Register ..................................................................................................................58
7.4.5 Configuring the DXM Controller for SMS Controlling ............................................................ 58
8 LCD and Menu System .................................................................................................. 59
8.1 Registers ...............................................................................................................................59
8.2 Push .....................................................................................................................................59
8.3 ISM Radio ............................................................................................................................. 60
8.4 System ................................................................................................................................. 61
8.4.1 ISM Radio .....................................................................................................................61
8.4.2 Ethernet ....................................................................................................................... 61
8.4.3 Provision Cell ................................................................................................................ 61
8.4.4 DXM Slave ID ................................................................................................................62
8.4.5 Power DC/Solar ............................................................................................................. 62
8.4.6 LCD Contrast ................................................................................................................ 62
8.4.7 Restart .........................................................................................................................62
8.5 System Info ...........................................................................................................................62
8.6 Using the Display LEDs ............................................................................................................63
8.7 Modbus Registers for the LCD Board (Modbus Slave ID 201) ......................................................... 64
9 Working with Modbus Devices ...................................................................................... 65
9.1 Overview ............................................................................................................................... 65
9.2 Assigning Modbus Slave IDs .....................................................................................................65
9.3 Modbus Operation .................................................................................................................. 66
9.4 Wireless and Wired Devices ..................................................................................................... 66
9.5 Modbus Timeouts ................................................................................................................... 66
9.5.1 MultiHop Networks vs DX80 Star Networks .......................................................................67
9.5.2 MultiHop Radios Powered by Battery ................................................................................ 67
9.5.3 MultiHop Radios Powered by 10-30 V DC ..........................................................................67
9.5.4 Adjusting the Receive Slots and Retry Count Parameters ....................................................67
9.5.5 DX80 Star Architecture Network Timeouts ........................................................................68
10 Configuration Instructions ......................................................................................... 69
10.1 Scheduler ............................................................................................................................ 69
10.1.1 Creating a Weekly Schedule .......................................................................................... 69
10.1.2 Defining One-Time Events ............................................................................................. 69
10.1.3 Creating a Holiday Schedule .......................................................................................... 70
10.1.4 Cycling Power During Schedules .....................................................................................70
10.2 Authentication Setup .............................................................................................................70
10.2.1 Cloud and Webserver Services Authentication ................................................................. 70
10.2.2 Mail Server Authentication ............................................................................................71
10.2.3 DXM Controller Configuration Authentication ...................................................................71
10.3 Register Flow and Configuration ............................................................................................. 72
DXM100-Bx Wireless Controller Instruction Manual

10.3.1 Basic Approach to Configuration ....................................................................................73


10.3.2 Troubleshooting a Configuration ....................................................................................73
10.3.3 Saving and Loading Configuration Files .......................................................................... 73
10.3.4 Uploading or Downloading Configuration Files ................................................................. 73
10.4 Setting Up EtherNet/IP ........................................................................................................74
10.4.1 Configuring the Host PLC ............................................................................................. 74
10.4.2 Configuring the DXM Controller ..................................................................................... 74
10.5 Setting up Email and Text Messaging ...................................................................................... 74
10.5.1 Define the Network Interface Settings ............................................................................74
10.5.2 Configure your Ethernet Connection .............................................................................. 75
10.5.3 Configure your Cellular Connection ................................................................................ 76
10.5.4 Set the Email and Messaging Parameters ....................................................................... 76
10.5.5 Define Threshold Rules for Email ................................................................................... 76
10.5.6 Define Log File Parameters for Emailing Log Files ............................................................ 77
10.6 Ethernet and Cellular Push Retries .......................................................................................... 77
10.6.1 Ethernet Push Retries .................................................................................................. 78
10.6.2 Cellular Push Retries ....................................................................................................78
10.6.3 Event/Action Rule or Log File Push Retries ...................................................................... 78
10.6.4 Email and Text Message Push Retries ............................................................................ 78
10.7 DXM Modbus Registers .......................................................................................................... 78
11 File System and Archive Process ................................................................................79
11.1 EEPROM Files ........................................................................................................................ 79
11.2 Micro SD Card Files ................................................................................................................79
12 DXM100 Dimensions ................................................................................................... 80
13 Contact Us ................................................................................................................. 81
14 Warnings .................................................................................................................... 82
14.1 Banner Engineering Corp. Limited Warranty ............................................................................. 82
DXM100-Bx Wireless Controller Instruction Manual

1 DXM Overview
1.1 DXM100-Bx System Overview
Banner's DXM Logic Controller integrates Banner's wireless radio, cellular connectivity, and local I/O to provide a platform
for the Industrial Internet of Things (IIoT).

I/O Connectivity Logic Controller User Interface


Universal Inputs Cellular Action Rules LCD Screen
Discrete Outputs Sure Cross Radios Programming Language LED Indicators
Courtesy Power Ethernet Scheduler
Switch Power USB Push to the Cloud
RS-485 Master Data Logging
RS-485 Slave SMS and Email
SMS Control

Inputs/OutputsOn-board universal and programmable I/O ports connect to local sensors, indicators, and control
equipment.
Universal Inputs
Discrete outputs
Courtesy power
Switch power
Battery backup
Solar controller
DC latching outputs (DXM100-B2 models only)
SDI-12 sensor interface (DXM100-B2 models only)
ConnectivityThe DXM Controller's wired and wireless connectivity options make it easy to share data between local and
remote equipment. The cellular modem option eliminates the need for IT infrastructures to connect remote equipment for
sensing and control. The integrated Sure Cross wireless radio enables Modbus connectivity to remote sensors, indicators,
and control equipment.

Wired Connectivity Wireless Connectivity


Ethernet: Modbus TCP or Ethernet/IP Sure Cross Wireless Radio: DX80 900 MHz, DX80 2.4
GHz, MultiHop 900 MHz, or MultiHop 2.4 GHz
Field Bus: Modbus RS-485 Master/Slave or CAN
Cellular modem: CDMA (Verizon) or GSM

Logic ControllerProgram the DXM Controller's logic controller using action rules and/or ScriptBasic language, which can
execute concurrently. The control functions allow freedom when creating custom sensing and control sequences. The logic
controller supports the Modbus protocol standards for data management, ensuring seamless integration with existing
automation systems.

Action Rules Scheduler


Supports simple logic, arithmetic and thresholding Time/calendar-based events
Low complexity solutions Astronomical clock
SMS text message Notifications Data Logging
E-mail Notifications Cyclic Data/Event logging
Push data on conditions E-mail log files
Text Programming Language SMS Commanding
ScriptBasic Read/Write Local Registers
Medium complexity solutions Force a push to the cloud
Reboot controller

www.bannerengineering.com - Tel: 763.544.3164 5


DXM100-Bx Wireless Controller Instruction Manual

User InterfaceA simple user interface consists of an LCD screen and four LED indicators. Use the LCD to access system
status and setup, view user selectable events or data, and to bind and perform site surveys for Sure Cross radios.
Configure the user programmable LEDs to indicate the status of the DXM Controller, processes, or equipment.

User programmable LCD User Defined LED indicators


Bind Sure Cross Radios
Site Survey
View Sensor Information
System Status

1.2 DXM Automation Protocols


The DXM Controller supports the following automation protocols.

Modbus RTU. The DXM Controller manages two separate physical ports running the Modbus RTU protocol. The DXM
Controller is the Modbus Master when operating the Modbus master RTU port. The DXM Controller uses the master Modbus
RTU bus to communicate with locally connected Modbus devices or uses the Banner wireless radio to communicate with
remote Modbus devices. The other Modbus RTU port is used by a host system to access the DXM Controller as a slave
device. The slave Modbus RTU port allows access all the internal registers concurrently with the master RTU port. By
default, the Modbus RTU ports are active. Configure the port parameters using the DXM Configuration Tool.

Modbus TCP/IP. A host system acting as a Modbus client can access the DXM Controller using the Modbus TCP/IP
protocol over Ethernet. Standard Modbus port 502 is used by the DXM Controller for all Modbus TCP/IP requests. All
internal registers are available to the host system concurrently with Modbus RTU. By default, Modbus TCP/IP is active.
EtherNet/IP. The Ethernet port is actively running EtherNet/IP. From the factory the DXM Controller is configured to
read and write registers on DX80 wireless devices 1 through 16. Custom configurations can be set using the DXM
Configuration Tool. By default, EtherNet/IP is active.

1.3 DXM Modbus Overview


The DXM Controller uses internal 32-bit registers to store information. The processor's internal Local Registers serve as the
main global pool of registers and are used as the common data exchange mechanism. External Modbus device registers
can be read into the Local Registers or written from the local data registers.
The DXM Controller, as a Modbus master device or slave device, exchanges data using the Local Registers. Modbus over
Ethernet (Modbus/TCP) uses the Local Registers as the accessible register data.
Using Action, Read/Write, and Threshold Rules allows you to manipulate the processor's Local Registers. The ScriptBasic
programming capabilities extends the use of Local Registers with variables to create a flexible programming solution for
more complex applications.
The processor's Local Registers are divided into three different types: integer, floating point, and non-volatile. When using
Local Registers internally, the user can store 32-bit numbers. Using Local Registers with external Modbus devices follows
the Modbus standard of a 16-bit holding register. Local Registers are accessible as Modbus ID 199.
Accessing the I/O Base and the LCD follows the same communication as an external Modbus device. Each device has an ID
number to uniquely identify itself. The I/O base is Modbus ID 200 and the LCD is Modbus ID 201.

6 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

DXM Processor
ISM Radio (Modbus ID 1)
Local Registers
(Modbus ID 199) Gateway / MultiHop
Local Registers Integer
I/O Base (Modbus ID 200)
Local Registers Float
I/O Base
Local Registers Non-Volatile

Display (Modbus ID 201)

Modbus Data LCD Display


Traffic Control

Action Rules
Rd/Wr Rules
Script Basic

1.4 DXM Configuration Tool Overview


The DXM Configuration Tool configures the DXM Controller by creating
an XML file that is transferred to the DXM Controller using a USB or
Ethernet connection. The DXM Controller can also receive the XML
configuration file from a Web server using a cellular or Ethernet DXM Configuration Software
connection.
Local Registers
This configuration file governs all aspects of the DXM Controller
operation. The wireless network devices are a separate configurable Register Mapping
system. Use the DX80 User Configuration Tool (UCT) to configure the Action Rules
internal DX80 wireless Gateway and the attached wireless Nodes. Use
the MultiHop Configuration Tool (MCT) if the internal radio is a Scheduler
MultiHop device.
Script Basic
All tools can be connected to the DXM Controller using a USB cable or
an Ethernet connection. System Register
Settings View Utility

USB
XML Config File Ethernet

www.bannerengineering.com - Tel: 763.544.3164 7


DXM100-Bx Wireless Controller Instruction Manual

2 DXM Controller
2.1 DXM Hardware Configuration Overview
The DXM100-Bx Wireless Controller can have multiple configurations. The DXM100-Bx Wireless Controller will have a
model number label on the housing. Use the model number and model table above to identify which boards are included in
the controller.

When opening the DXM100-Bx Wireless Controller, follow proper ESD grounding procedures. Refer to the ESD warning in
the appendix.

Cellular Antenna Housing Catch


Connection
Cellular Radio Board

SAM4 Processor Board


ISM Radio
Antenna MultiHop or Gateway
Connection Radio Board

DXM100 I/O Board

The DXM100-Bx Wireless Controller I/O base board provides connections for all inputs, outputs and power. The base board
also contains a 12 V solar controller that accepts connections to a solar panel and SLA battery. The battery connection can
also be used with line power to provide a battery backup in case of line power outages.
The ISM radio, either a MultiHop or DX80 Gateway, fits on the base board in the parallel sockets. Install the ISM radio so
the U.FL antenna connection is to the side with the SMA antenna connectors. Connect the U.FL cable from the ISM radio
U.FL to the right side U.FL connector. The ISM radio boards are available with either a 900 MHz radio or a 2.4 GHz radio.
The SAM4 processor board plugs into the base board using the two 20 pin socket connectors. The board sits above the ISM
radio socket and held by the base board standoffs. Position the processor board so the USB and RJ45 Ethernet connection
is to the front, away from the SMA antenna connections.
The top plugin PCB is the optional cellular radio. This plugs into the SAM4 processor board with the U.FL antenna
connection to the left. Attach the antenna cable from the cellular module to the left U.FL connection on the base board.
The top housing contains the LCD display board. The display board is connected to the base board using a ribbon cable
with a 20 pin connector.

In some DXM models, the cellular radio module may be replaced with an ISM radio. The top ISM radio antenna connection
will be to the left SMA connector.

8 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

3 ISM Radio Board


3.1 ISM Radio Board (Modbus Slave ID 1)
For the DXM100-S1R2x models, the ISM radio board installed in the I/O board is a MultiHop radio (DX80DR*M-HE5).

Plug the ISM radio into the I/O base board with the U.FL
antenna connector closest to the SMA connectors.
A
A - Antenna connector
B - Button
C - LED
D1 - DIP switches
D2 - DIP Switches

D1 D2
B
4

C
3 2 1

3 2 1
ON

ON

Button OperationFor DXM models without a LCD display, use the button (B) to bind the ISM radio. For models with a
LCD display, use the ISM menu to bind the radio.
LED OperationThe LED located on the ISM radio module indicates power and communications traffic.
Solid green DX80 ISM radio LED: Indicates power.
Flashing green MultiHop ISM radio LED indicates operation.
Red and green combined: Communications traffic and binding.

3.1.1 DIP Switch Settings for the MultiHop HE5 Board Module
D1 Switches D2 Switches

Device Settings 1 2 3 4 1 2 3 4

Serial line baud rate 19200 OR User defined receiver OFF* OFF*
slots

Serial line baud rate 38400 OR 32 receiver slots OFF ON

Serial line baud rate 9600 OR 128 receiver slots ON OFF

Serial line baud rate Custom OR 4 receiver slots ON ON

Parity: None OFF* OFF*

Parity: Even OFF ON

Parity: Odd ON OFF

Disable serial (low power mode) and enable the ON ON


receiver slots select for switches 1-2

Transmit power OFF*


900 MHz radios: 1.00 Watt (30 dBm)
2.4 GHz radios: 0.065 Watts (18 dBm) and 60 ms
frame

Transmit power ON
900 MHz radios: 0.25 Watts (24 dBm)
2.4 GHz radios: 0.065 Watts (18 dBm) and 40 ms
frame

www.bannerengineering.com - Tel: 763.544.3164 9


DXM100-Bx Wireless Controller Instruction Manual

D1 Switches D2 Switches

Device Settings 1 2 3 4 1 2 3 4

Application mode: Modbus OFF*

Application mode: Transparent ON

MultiHop radio setting: Repeater OFF* OFF*

MultiHop radio setting: Master OFF ON

MultiHop radio setting: Slave ON OFF

MultiHop radio setting: Reserved ON ON

* Default configuration

Application Mode
The MultiHop radio operates in either Modbus mode or transparent mode. Use the internal DIP switches to select the mode
of operation. All MultiHop radios within a wireless network must be in the same mode.

Modbus mode uses the Modbus protocol for routing packets. In Modbus mode, a routing table is stored in each parent
device to optimize the radio traffic. This allows for point to point communication in a multiple data radio network and
acknowledgement/retry of radio packets. To access a radio's I/O, the radios must be running in Modbus mode.

In transparent application mode, all incoming packets are stored, then broadcast to all connected data radios. The data
communication is packet based and not specific to any protocol. The application layer is responsible for data integrity. For
one to one data radios it is possible to enable broadcast acknowledgement of the data packets to provide better
throughput. In transparent mode, there is no access to the radio's I/O.

Baud Rate and Parity


The baud rate (bits per second) is the data transmission rate between the device and whatever it is physically wired to.
Set the parity to match the parity of the device you are wired to.

Disable Serial
If the local serial connection is not needed, disable it to reduce the power consumption of a data radio powered from the
solar assembly or from batteries. All radio communications remain operational.

Transmit Power Levels/Frame Size


The 900 MHz data radios can be operated at 1 watt (30 dBm) or 0.250 watt (24 dBm). For most models, the default
transmit power is 1 watt.
For 2.4 GHz radios, the transmit power is fixed at 0.065 watt (18 dBm) and DIP switch 5 is used to set the frame timing.
The default position (OFF) sets the frame timing to 60 milliseconds. To increase throughput, set the frame timing to 40
milliseconds. Note that increasing the throughput decreases the battery life.
Prior to date code 15341 and radio firmware version 3.6, the frame timing was 40 ms (OFF) or 20 ms (ON).

3.1.2 DIP Switch Settings for the Gateway PEx Board Modules
Transmit PowerThe 900 MHz radios transmit at 1 Watt (30 dBm) or 250 mW (24 dBm). While the Performance radios
operate in 1 Watt mode, they cannot communicate with the older 150 mW radios. To communicate with 150 mW radios,
operate this radio in 250 mW mode. For 2.4 GHz models, this DIP switch is disabled. The transmit power for 2.4 GHz is
fixed at about 65 mW EIRP (18 dBm), making the 2.4 GHz Performance models automatically compatible with older 2.4
GHz models.

DIP Switch Bank D1

DIP Switch 1

OFF * 1 Watt (30 dBm, 900 MHz models only)

ON 250 mW (24 dBm, 900 MHz models only), DX80 compatibility mode

* Default configuration

10 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

3.2 Binding and Conducting a Site Survey with the ISM Radio
The DXM Controller can have an internal MultiHop master radio or DX80 Gateway radio (star architecture) installed. Before
the ISM radio can communicate with DX80 Nodes, the DXM Controller must be bound to the other radios in the wireless
network. Use the DXM Controller LCD menu to bind radios to the internal DXM radio.

The LCD display and the processor applications share the external Modbus connection. If the processor is configured to
constantly interact with Modbus, it may cause issues with the LCD display attempting to use the functions of the ISM radio.
To alleviate the contention:

Load a DXM configuration file that slows down the read/write rules.
Disable the DXM configuration file from loading into the processor by setting DIP switch 4 to ON (on the processor
board). Reboot the device. When the processor starts back up, it will not load the configuration file and remains
idle. See the DXM100 Controller Instructional Manual (190037) for the processor DIP switch location.

3.2.1 Entering Binding Mode


Under the ISM Radio menu, use the down arrow button to highlight the Binding menu. Click ENTER.

The ISM Radio menu is slightly different for the two different types of internal radio. The ISM Type displays 'MultiHop'
when the MultiHop radio board is installed and 'DX' when the DX80 star architecture radio board is installed.

Use the up/down arrows to enter the device number to bind to. When binding to devices with rotary dials, the device
number has no effect. To bind to devices without rotary dials, the device number is saved as the device Modbus slave ID in
the MultiHop network or the Node number in a DX80 network.

After entering binding mode on the DXM Controller, put the end device into binding mode to execute the binding process.
Most end devices enter binding by triple-clicking button 2 on the device. For specific instructions on entering binding for a
specific device, refer to the individual datasheet for that device.
To bind more devices, click the back button, change the device number (if needed), then enter binding again.

3.2.2 Conducting a Site Survey


Although the MultiHop and DX80 devices are architecturally different, the site survey process is similar when conducted
from the DXM LCD menu. From the ISM Radio menu, use the down arrow to highlight the Site Survey menu. Click
ENTER.
Use the Up or Down arrows to select the Node number (DX80 network) or Modbus Slave ID (MultiHop network). Click
ENTER to run the site survey with that Node or slave.
For a DX80 network, the Gateway controls the site survey and the results display on the LCD. Running Site Survey on a
DX80 network does not affect the throughput of the DX80 network.
For a MulitHop network, the master device passes the site survey request to the intended Modbus slave device. The Site
Survey runs and the results display on the LCD. Running Site Survey on a MultiHop network stops all network traffic to
that device.

3.3 Modbus Registers for the Gateway Performance 1 Watt Radio


The DX80 Gateway (PE5) is a star-based architecture device that contains all the Modbus registers for the wireless
network within the Gateway. To access any input or output values within the entire wireless network, read the appropriate
Modbus register from Gateway.

There are 16 Modbus registers allocated for each device in the wireless network. The first 16 registers (116) are allocated
for the Gateway, the next 16 (1732) are allocated for Node 1, the next 16 (3348) are allocated for Node 2 and so forth.
There are no inputs or outputs on the DXM embedded Gateway but the Modbus registers are still allocated for them.

Although only seven Nodes are listed in the table, the Modbus register numbering continues for as many Nodes as are in
the network. For example, the register number for Node 10, I/O point 15 , is 175. Calculate the Modbus register number
for each device using the equation:

Register Number = I/O# + (Node# 16)

Table 1: Modbus Holding Registers

I/O Point Gateway Node 1 Node 2 Node 3 Node 4 Node 5 Node 6 Node 7

1 1 17 33 49 65 81 97 113

2 2 18 34 50 66 82 98 114

www.bannerengineering.com - Tel: 763.544.3164 11


DXM100-Bx Wireless Controller Instruction Manual

I/O Point Gateway Node 1 Node 2 Node 3 Node 4 Node 5 Node 6 Node 7

3 3 19 35 51 67 83 99 115

4 4 20 36 52 68 84 100 116

5 5 21 37 53 69 85 101 117

6 6 22 38 54 70 86 102 118

7 7 23 39 55 71 87 103 119

8 8 24 40 56 72 88 104 120

9 9 25 41 57 73 89 105 121

10 10 26 42 58 74 90 106 122

11 11 27 43 59 75 91 107 123

12 12 28 44 60 76 92 108 124

13 13 29 45 61 77 93 109 125

14 14 30 46 62 78 94 110 126

15 15 31 47 63 79 95 111 127

16 16 32 48 64 80 96 112 128

Example: DX80 Performance Gateway Modbus Register Table


Access all wireless network registers by reading Modbus slave ID 1.

DX80 Device Slave ID Modbus Registers

DXM Gateway radio 1 Modbus registers 18 are inputs, 916 are outputs

Node 1 - Modbus registers 1725 are inputs, 2632 are outputs

Node 2 - Modbus registers 3340 are inputs, 4148 are outputs

Node 3 - Modbus registers 4956 are inputs, 5764 are outputs

3.3.1 Alternative Modbus Register Organization


The Sure Cross DX80 Alternative Modbus Register Organization registers are used for reordering data registers to allow
host systems to efficiently access all inputs or outputs using a single Modbus command. The register groups include the
input/output registers, bit-packed registers, and analog registers. This feature is only available with the Performance
models using version 3 or newer of the LCD firmware code.

Name Modbus Register Address (Dec.)

Inputs and Outputs, in order by device 2201 through 4784

Discrete Bit Packed (Status, Discrete Inputs, Discrete Outputs) 6601 through 6753

Analog Inputs (1-8) and Analog Outputs (1-8) 6801 through 9098

Input Registers and Outputs Registers


Modbus registers 2201 through 2584 are used to organize all inputs together. In this format, users can sequentially read
all input registers using one Modbus message. Modbus registers 4401 through 4784 organize all outputs together to allow
users to sequentially write to all outputs registers using one Modbus message.

Inputs (22012584) Outputs (44014784)

Modbus Register Address (Dec) 16-bit Register Value Modbus Register Address (Dec) 16-bit Register Value

22012208 Gateway Inputs 1 through 8 44014408 Gateway Outputs 1 through 8

22092216 Node 1 Inputs 1 through 8 44094416 Node 1 Outputs 1 through 8

22172224 Node 2 Inputs 1 through 8 44174424 Node 2 Outputs 1 through 8

... ... ... ...

25772584 Node 47 Inputs 1 through 8 47774784 Node 47 Outputs 1 through 8

12 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

Refer to your device's datasheet for a list of the active inputs and outputs. Not all inputs or outputs listed in this table may
be active for your system.

Discrete Bit-Packed Registers


Discrete bit-packed registers include the discrete status registers, discrete inputs, and discrete outputs.

Bit packing involves using a single register, or range of contiguous registers, to represent I/O values.

When networks use similar Nodes to gather data using the same I/O registers for each Node, discrete data from multiple
Nodes can be bit packed into a single register on the Gateway. The bit-packed data is arranged by I/O point starting at
Modbus register 6601. For example, Discrete IN 1 for all the Nodes in the network is stored in three contiguous 16-bit
registers.

The most efficient way to read (or write) discrete data from a SureCross DX80 Gateway is by using these bit-packed
registers because users can read or write registers for all devices using one Modbus message. The following registers
contain discrete bit-packed I/O values for the Gateway and all Nodes. Values are stored first for the Gateway, then for
each Node in order of Node address.

Bit-Packed Device Status R egisters


Bit Position
Register Address 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
6601 Node 15 Node 14 Node 13 Node 12 Node 11 Node 10 Node 9 Node 8 Node 7 Node 6 Node 5 Node 4 Node 3 Node 2 Node 1 Gateway
6602 Node 31 Node 30 Node 29 Node 28 Node 27 Node 26 Node 25 Node 24 Node 23 Node 22 Node 21 Node 20 Node 19 Node 18 Node 17 Node 16
6603 Node 47 Node 46 Node 45 Node 44 Node 43 Node 42 Node 41 Node 40 Node 39 Node 38 Node 37 Node 36 Node 35 Node 34 Node 33 Node 32

Bit-Packed Discrete Input 1


Bit Position
Register Address 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
6611 Node 15 Node 14 Node 13 Node 12 Node 11 Node 10 Node 9 Node 8 Node 7 Node 6 Node 5 Node 4 Node 3 Node 2 Node 1 Gateway
6612 Node 31 Node 30 Node 29 Node 28 Node 27 Node 26 Node 25 Node 24 Node 23 Node 22 Node 21 Node 20 Node 19 Node 18 Node 17 Node 16
6613 Node 47 Node 46 Node 45 Node 44 Node 43 Node 42 Node 41 Node 40 Node 39 Node 38 Node 37 Node 36 Node 35 Node 34 Node 33 Node 32

Bit-Packed Discrete Output 1


Bit Position
Register Address 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
6691 Node 15 Node 14 Node 13 Node 12 Node 11 Node 10 Node 9 Node 8 Node 7 Node 6 Node 5 Node 4 Node 3 Node 2 Node 1 Gateway
6692 Node 31 Node 30 Node 29 Node 28 Node 27 Node 26 Node 25 Node 24 Node 23 Node 22 Node 21 Node 20 Node 19 Node 18 Node 17 Node 16
6693 Node 47 Node 46 Node 45 Node 44 Node 43 Node 42 Node 41 Node 40 Node 39 Node 38 Node 37 Node 36 Node 35 Node 34 Node 33 Node 32

Inputs Outputs

Modbus Register Description (Inputs) Modbus Register Description (Outputs)


Address (Decimal) Address (Decimal)

6601-6603 Status for all devices

6611-6613 Input 1 from all devices 66916693 Output 1 from all devices

6621-6623 Input 2 from all devices 67016703 Output 2 from all devices

6631-6633 Input 3 from all devices 67116713 Output 3 from all devices

6641-6643 Input 4 from all devices 67216723 Output 4 from all devices

6651-6653 Input 5 from all devices 67316733 Output 5 from all devices

6661-6663 Input 6 from all devices 67416743 Output 6 from all devices

6671-6673 Input 7 from all devices 67516753 Output 7 from all devices

6681-6683 Input 8 from all devices

Status registers (6601-6603) contain a bit-packed representation defining the devices that are operational in the
wireless system.

Input registers from all devices use Modbus registers 6611 through 6683 to organize the least significant bit into a
sequential array of registers. The first register contains the least significant bit from the input values for the Gateway
through Node 15. The second register contains the input values for Node 16 through Node 31, and the third register
contains the input values for Nodes 32 through 47.

For discrete inputs, only the least significant bit is used. For analog inputs, the least significant bit indicates if the analog
value is above or below the selected threshold value (when using the threshold parameter). For example, a least
significant bit of one (1) indicates the analog value is above the selected threshold value. A least significant bit of zero (0)
indicates the analog value is below the threshold value.

www.bannerengineering.com - Tel: 763.544.3164 13


DXM100-Bx Wireless Controller Instruction Manual

Output registers from all devices use Modbus registers 6691 through 6753 to organize the least significant bit into a
sequential array of registers. Output 8 (I/O point 16) cannot be written using the discrete format.

Analog 16-Bit Registers (Registers 6801 through 9098)


The most efficient way to read (or write) analog data from a Gateway is by using these 16-bit analog registers. Most
networks consist of similar Nodes reporting data using the same I/O registers for each Node. For this reason, the analog
data is arranged by I/O point using Modbus registers 6801 through 9098. For example, Input 1 for Gateway and all Nodes
is stored in the first 48 contiguous blocks of 16-bit analog registers, beginning with register 6801.

In this format, users can read a 16-bit holding register for all devices or write to a register for all devices using one
Modbus message. Using these registers is the most efficient way to read all status registers, read all analog inputs, or
write all analog outputs.

The following registers contain analog I/O values for the Gateway and all Nodes. Values are stored first for the Gateway,
then for each Node in order of Node address.

Inputs Outputs

Modbus Register Address Description (Inputs) Modbus Register Description (Outputs)


(Decimal) Address (Decimal)

6801 Input 1 for Gateway 8001 Output 1 for Gateway

6802 Input 1 for Node 1 8002 Output 1 for Node 1

6803 Input 1 for Node 2 8003 Output 1 for Node 2

... ... ... ...

6951 Input 2 for Gateway 8151 Output 2 for Gateway

6952 Input 2 for Node 1 8152 Output 2 for Node 1

6953 Input 2 for Node 2 8153 Output 2 for Node 2

... ... ... ...

7101 Input 3 for Gateway 8301 Output 3 for Gateway

7102 Input 3 for Node 1 8302 Output 3 for Node 1

7103 Input 3 for Node 2 8303 Output 3 for Node 2

... ... ... ...

7851 Input 8 (Status Register) for Gateway 9051 Output 8 for Gateway

7852 Input 8 (Status Register) for Node 1 9052 Output 8 for Node 1

7853 Input 8 (Status Register) for Node 2 9053 Output 8 for Node 2

... ... ... ...

For example, 6801 contains the input 1 value for the Gateway, 6802 contains the input 1 value for Node 1, and 6848
contains the input 1 value for Node 47.

3.4 Modbus Registers for the MultiHop 1 Watt Radio Board


The DX80 MultiHop master radio (HE5) is a tree-based architecture device that allows for repeater radios to extend the
wireless network. Each device in a MultiHop network is a Modbus device with a unique Modbus ID. Modbus registers in a
MultiHop network are contained within each individual radio device. To get Modbus register data from a MultiHop device,
configure the DXM Controller to access each device across the wireless network as an individual Modbus slave device.

Example: MultiHop Modbus Register Table


Example MultiHop Modbus registers with generic devices.

MulitHop Device Slave ID Modbus Registers

DXM Master radio 1 none

Slave device 11 Modbus register 116 are inputs, 501516 are outputs

Repeater device 12 Modbus register 116 are inputs, 501516 are outputs

Slave device 15 Modbus register 116 are inputs, 501516 are outputs

14 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

4 Processor Board
4.1 SAM4 Processor Board
A - Cellular radio connection
B - Force cloud push/Clear password
A C - Boot load jumpers
D
D - DIP switches
LED 1
E - Micro SD card

P2
E
LED 2

1
A
LED 3

LED 4

C
B

Cellular Radio Connection. Install the cellular modem onto the SAM4 board with the cellular modem's U.FL connector on
the left. The antenna cable will go between the cellular U.FL connector and the left I/O board U.FL connector. Only install/
remove a cellular modem when the power to the device is disconnected.
Force Cloud Push button. Press and hold this button for two seconds to send an immediate push message from the
device (if properly configured).
Clear Password. By default, the DXM Controller does not require a password to load a configuration file. If a password is
defined, the DXM Controller requires that you enter the password before uploading a configuration file. To change the
password, you must already know the current password. If you do not know the current password, clear the password
from the DXM Controller.

CAUTION: Clearing the password erases the current configuration and any program files, log files, or history files
currently on the DXM Controller.

Follow these steps to clear the password requirement from your DXM Controller.
1. Turn off the power.
2. Set DIP switch 4 to the ON position.
3. Press and hold button 'B'.
4. Apply power to the device.
5. After leaving the device powered on for a few seconds, turn off the power again.
6. Set DIP switch 4 to the OFF position.
7. Reload the configuration file before resuming normal operation.
The password is cleared from the system.

4.1.1 DIP Switch Configuration


Cycle power to the device after making any changes to the DIP switch settings.

DIP Switches
Settings
1 2 3 4

OFF *
Disable Ethernet Port
ON

OFF *
Disable LCD Display
ON

Not used OFF *

Bypass XML OFF *

www.bannerengineering.com - Tel: 763.544.3164 15


DXM100-Bx Wireless Controller Instruction Manual

DIP Switches
Settings
1 2 3 4

ON

Bypass XML
Turn to ON to have the XML file ignored at boot time. This is useful for ignoring a corrupt or questionable XML
configuration file. After the device is running, a new XML file can be loaded using the DXM configuration tool. The
factory default position is OFF.
Disable Ethernet Port
Set to ON to power down the Ethernet interface. The factory default position is OFF.
Disable LCD Display
Set to ON to disable the LCD. This DIP switched should be ON when the LCD display board is not connected. The
factory default position is OFF.

4.1.2 Button Operation


The SAM4 processor button has two functions:
Clearing the access password as explained above.
Pressing the button for 5 seconds forces a Push to the webserver. This assumes a proper configuration for the
webserver.

4.1.3 LED Operation


By default, the four LEDs indicate the following conditions:
LED 1 - Heartbeat, indicates the processor is running.
LED 2 - Indicates the cellular modem power cutoff is active. If the incoming power is less than 11.2 V, the cellular
modem is powered down.
LED 3 - XML configuration file was rejected.
LED 4 - ScriptBasic program failed to load.

4.2 Ethernet
Before applying power to the DXM100-Bx Wireless Controller, verify the Ethernet cable is connected. If the Ethernet cable
is not connected when the device powers up, the DXM100-Bx Wireless Controller will not recognize the connection.
The Ethernet connection supports the DXM Configuration Tool, Modbus/TCP, and EtherNet/IP. ScriptBasic also has access
to Ethernet for custom programming. Use the DXM Configuration Tool to configure the characteristics of the Ethernet
connection, fixed IP addresses, DHCP, etc. The LCD menu allows the user to change the IP Address.

4.3 USB
The USB port is used with the DXM Configuration Tool to program the DXM100-Bx Wireless Controller. The USB port is also
used as the console output for the processor and ScriptBasic.

4.4 Modbus Registers - Internal Local Registers (Modbus Slave 199)


The main storage elements for the DXM Controller are its Local Registers, which can store 4-byte values that result from
register mapping, action rules, or ScriptBasic commands.
Local Registers 1 through 850 are standard 32-bit signed registers.
Local Registers 851 through 900 are non-volatile registers that are limited to 100,000 write cycles.
Local Registers 1001 through 1900 are floating point format numbers. Each register address stores half of a
floating point number. For example, registers 1001 and 1002 store the first full 32-bit floating point number.
Local Registers 10001 through 19000 are system, read-only, registers that track DXM Controller data and
statistics.

4.4.1 Local Registers 1850 (Internal Processor Memory, 32-bit, Unsigned)


The local registers are the main global pool of registers. Local registers are used as basic storage registers and as the
common data exchange mechanism.

Modbus slave ID 0 is reserved for the processor.

16 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

External Modbus device registers can be read into the local registers or written from the local registers. The DXM
Controller, as a Modbus master device or a Modbus slave device, exchanges data using the local registers.

Modbus over Ethernet (Modbus/TCP) uses the local registers as the accessible register data.

4.4.2 Local Registers 851900 (Data Flash, Non-volatile, 32-bit, Unsigned)


The top 50 local registers are special non-volatile registers. The registers can store constants or calibration type data that
must be maintained when power is turned off.

This register data is stored in a data flash component that has a limited write capability of 100,000 cycles, so these
registers should not be used as common memory registers that change frequently.

4.4.3 Local Registers 10011900 (32-bit IEEE Floating Point)


These local registers are paired together to store a 32-bit IEEE floating point format number in big endian format.

Registers 1001 [31:16], 1002 [15:0] store the first floating point value; registers 1003, 1004 store the second floating
point number. There are a total of 500 floating point values; they are addressed as two 16-bit pieces to accommodate the
Modbus protocol.
Use these registers when reading/writing external devices that require Modbus registers in floating point format. Since
Modbus transactions are 16-bits, the protocol requires two registers to form a 32-bit floating point number.

4.4.4 Virtual Registers


The DXM Controller has a small pool of virtual registers that show internal variables of the main processor. Some register
values will be dependent upon the configuration settings of the DXM Controller.
Do not use Read Rules to move Virtual Local Registers data into Local Registers. Use the Action Rule > Register Copy
function to move Virtual Local Registers into Local Registers space (1-850).

Registers Definition

10001 GPS latitude direction (N, S, E, W) GPS Coordinate Data if the DXM is configured to read an external GPS unit.

10002 GPS latitude

10003 GPS longitude direction (N, S, E, W)

10004 GPS longitude

1001110012 Resync timer Engineering use

1001310014 Resync timer rollover Engineering use

1001510016 Reboot cause (Restart Codes above) Reboot Type

1001710018 Watchdog reset count Counter to track how many resets have been caused by the Watchdog

10021 IO Board Battery Voltage (mV) DXM Base I/O board battery / solar charger statistics.

10022 IO Board Battery Charging Current (mA) Refer to the DXM Instruction Manual for more information.

10023 IO Board Incoming Supply (mV)

10024 IO Board On board thermistor ( degrees C)

1002510026 Http Push SSL Acquires Statistical counts of connections, disconnections and forced disconnects when
the DXM Controller creates a connection using SSL/TLS (Encrypted
1002710028 Http Push SSL Releases connections)

1002910030 Http Push SSL Forced Releases

1003110032 Http Push Attempts Statistical counts of connections, disconnections and forced disconnects when
the DXM controller creates a connection using HTTP non-encrypted
1003310034 Http Push Successes

1003510036 Http Push Failures

1003710038 Http Push Last Status Last DXM Controller push status

1003910040 Cellular Strength, BER Cellular signal strength. Value range: 031

0 = 113 dBm or less


1 = 111 dBm
230 = 109 dBm through 53 dBm in 2 dBm steps
31 = 51 dBm or greater
99 = not known or not detectable; BER not used

10100 Number of read maps in default Read Map statistics

10101 Number of read map successes

www.bannerengineering.com - Tel: 763.544.3164 17


DXM100-Bx Wireless Controller Instruction Manual

Registers Definition

10102 Number of read map timeouts

10103 Number of read map errors

10104 Read map success streak

10105 Number of write map successes Write Map statistics

10106 Number of write map timeouts

10107 Number of write map errors

10108 Write map success streak

10109 Number of passthrough successes API message passing statistics

10110 Number of passthrough timeouts

10111 Number of passthrough errors

10112 Passthrough success streak

10113 Number of 43 buffer successes DX80 Gateway automatic messaging buffer statistics

10114 Number of 43 buffer timeouts

10115 Number of 43 buffer errors

10116 43 buffer success streak

11000 Read map success count Read/Write maps statistics

12000 Write map success count

13000 Read map timeout count

14000 Write map timeout count

15000 Read map error count

16000 Write map error count

17000 Read map success streak

18000 Write map success streak

19000 Read map is in default

4.4.5 Reset Codes


The reset codes are in virtual register 11015 and define the condition of the last restart operation.

Code Definition

0 Undefined

1 Unknown

2 General

3 Brownout

4 Watchdog

5 User

6 Software

7 Return from backup mode

18 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

5 I/O Base Board for the DXM100-B1 Models


5.1 DXM100-B1 I/O Base Board Connections

B 32 19 D
1 1 1
TB1 TB2 TB3

P2

TVS1

P1

P4
P3

mA
A OUT 2
E
P6
P7 P16

M L H V
A OUT 1

C4
L1

P5
P10
P8

P9

Y1
R77
R82

ON

J
C6

SW1

L ON

K
C10
D3
SW2 1
R118

F
DZ2
R120

C18
L2
R121 R122
C19
SW3

D4
FET9

D5
C95

C20
IC18

A C
LED2
LED1

TB4 TB5 TB9


1 1 1

1 18

1 No connection 12 CT. RS-232 CTS 23 N3. NMOS OUT 3

2 PW. 12 to 30 V dc or solar power in (+) 13 S-. Secondary RS-485 24 N2. NMOS OUT 2

3 GD. Ground 14 S+. Secondary RS-485 + 25 N1. NMOS OUT 1

4 B+. Battery in (< 15 V dc) 15 CL. CANL 26 GD. Ground

5 GD. Ground 16 CH. CANH 27 U4. Universal Input 4

6 M-. Primary RS-485 17 GD. GND 28 U3. Universal Input 3

7 M+. Primary RS-485 + 18 P3. Courtesy Power 5 V 29 GD. Ground

P1. Adjustable Courtesy Power (5 V or


8 GD. Ground 19 A2. Analog OUT 2 30
16 V)

9 TX. RS-232 Tx 20 A1. Analog OUT 1 31 U2. Universal Input 2

P2. Adjustable Courtesy Power (5 V


10 RX. RS-232 Rx 21 32 U1. Universal Input 1
or 16 V)

11 RT. RS-232 RTS 22 N4. NMOS OUT 4

Jumpers - Configures Analog Out 1


A Base board LED E J Modbus Slave ID DIP Switches
and 2 for mA or V

B A1. Cellular antenna F Radio Binding Button K Modbus Slave ID DIP Switches

C Radio LED G Programming header L SAM4 Processor Board Connection

D A2. ISM Antenna H ISM Radio Board Connection M Display Connection

5.1.1 DIP Switches for the I/O Board


The DXM100-Bx Wireless Controller I/O board DIP switches are set from the factory to Modbus Slave ID 200. For more
information, refer to Setting the Modbus Slave ID on the I/O Base Board.

www.bannerengineering.com - Tel: 763.544.3164 19


DXM100-Bx Wireless Controller Instruction Manual

5.1.2 I/O Board Jumpers


Hardware jumpers on the DXM I/O board allow the user to select alternative pin operations. Turn the power off to the
device before changing jumper positions.

Jumper Function Positions

E Analog output characteristics for Defines current (020 mA) or voltage (010 V) for analog output 1 and 2.
AO2 (pin 19) and AO1 (pin 20)
By default, current (020 mA) is selected using jumpers 1 and 2 and registers 4008 and 4028
contain a value of 2.
To select voltage (010 V) for output Aout1, set jumper 1 in the voltage position (V) and set
Modbus register 4008 on the I/O board (SID 200) to 3.

To select voltage (010 V) for output Aout2, set jumper 2 in the voltage position (V) and set
Modbus register 4028 on the I/O board (SID 200) to 3.

5.2 Applying Power to the DXM100-Bx Wireless Controller


Apply power to the DXM100-Bx Wireless Controller using either 12 to 30 V dc or a 12 V dc solar panel and 12 V sealed
lead acid battery operating together.

The DXM100 has three power input and three power output options:
Input Power:
12 to 30 V dc
12 to 30 V dc solar panel
12 V dc sealed lead acid battery with automatic charging
Courtesy Output Power Supplies:
One 5 V dc fixed
Two 5 V dc or 16 V dc (DXM100-B1 models) or Two 5 V to 24 V dc (DXM100-B2 models)
The DXM Controller continuously monitors the health of the power inputs. If a power input fault is detected, the DXM
Controller automatically switches over to battery with continuous uninterrupted operation.
If the incoming voltage drops below 11.2 V dc, the cellular modem does not turn on and will not turn on until the voltage is
above 11.8 V dc. A text file (CmVMon.txt) on the internal micro SD card saves the periodic sampling of the incoming
voltage. If cellular operation stops because of voltage, it is logged in this file.

Pin Description

Pin 1 No connection

Pin 2 12 to 30 V dc input (+) or solar panel connection (+)

Pins 3, 5, 8, 17, 26, 29 Main logic ground for the DXM100-Bx Wireless Controller

Pin 4 Solar or backup battery positive input. Battery voltage must be less than 15 V dc. Use only a sealed lead acid (SLA)
battery.

5.2.1 Using Courtesy Power or Switch Power


Pin 18 of the DXM100-Bx Wireless Controller is a constant power source that supplies 5 volts up to 500 mA.

Pins 21 (switch power 2) and 30 (switch power 1) are switched power outputs. Configure the switched power outputs using
Modbus registers. The output voltage can be selected and is controlled using a Modbus register on the I/O board (Modbus
slave ID 200). The voltage options are:
5 volts or 16 volts for DXM100-B1 models; or
5 to 24 V dc for DXM100-B2 models.

Turn the switched power on or off using the output register 505 for switch power 1 or 506 for switch power 2. For
continuous power, set the Default Output register to 1, then cycle the power.

Switch Power Enable Register Voltage Register Default Output Register Output Register

1 (pin 30) 2201 3601 3602 505


Write a 0 to turn OFF Write a 0 to select 5 V (default)
Write a 1 to turn ON (default) Write a 1 to select 16 V

20 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

Switch Power Enable Register Voltage Register Default Output Register Output Register

2 (pin 21) 2251 3621 3622 506


Write a 0 to turn OFF Write a 0 to select 5 V (default)
Write a 1 to turn ON (default) Write a 1 to select 16 V

Enable Register
Configuration registers that turn on the ability to use the switched power output.
Default setting = ON
Voltage Register
Configuration registers that define the output voltage to the switched power output.
Default setting = 5 V
Default Output Register
Configuration registers that turn on the switched power outputs for continuous power out.
Set register to 1 for continuous power. Cycle power if this register is changed.
Default setting = 0
Modbus Output Register
Turn on or turn off the voltage output. If both outputs 505 and 506 are turned on at the same time but are set to
different voltages, the output voltage is 5 V for DXM100-B1 models and set to the lower voltage setting for
DXM100-B2 models.

5.2.2 Associating a Switched Power Output to an Input


Switched power 1 and 2 (pins 30 and 21) can be associated to any Universal input to apply power a sensor, take a
reading, and then remove power from the sensor. This conserves power in battery-operated systems.
The switched power supply can be used in one of two different ways: supplying courtesy power to an output pin or
associated to an input. (Only one method can be active at a time.)
Use the following configuration parameters to define the courtesy power supplied to a switched power output pin.

Courtesy Power Output Configuration Parameters 1 Modbus Registers

Switched Power 1 Switched Power 2

Switched Power Enable 2201 2251

Voltage 3601 3621

Default Output 3602 3622

Output Register 505 506

Default Output
Set the register value to 1 for continuous power. The default setting is 0.
Cycle power if this register value is changed.
Switched Power Enable
Enables the switched power supply. Set to 1 to enable; set to 0 to disable.
This does not enable the supply output to the actual output pin. To enable the supply output to the output pin, set
Modbus register 505 or 506 to 1. Set to 0 when associating the switched power supply to an input.
Output Register
Write to the Output register to turn on or turn off the voltage output.
If both Output Registers 505 and 506 are turned on at the same time, but are set to different voltages, the output
voltage is 5 V for DXM100-B1 models and set to the lower voltage setting for DXM100-B2 models.

1 Only used when supply courtesy power to the output pin, not when associating switched power to an input.

www.bannerengineering.com - Tel: 763.544.3164 21


DXM100-Bx Wireless Controller Instruction Manual

Voltage
For the B1 and S1 models, set the Modbus register value to 0 for a switched power supply at 5 volts. Se the
Modbus register value to 1 for a switched power supply at 16 volts.
For the B2 and S2 models, set one of the following register values to select your switched power output voltage.
For 5 V, set the Modbus register to 204.
For 7 V, set the Modbus register to 125.
For 10 V, set the Modbus register to 69.
For 15 V, set the Modbus register to 32.
For 20 V, set the Modbus register to 12.
For 24 V, set the Modbus register to 3.

When associating a switched power supply to an input, set the Switch Power Output Enable register to off (0). Set
Modbus register 2201 for switched power 1 and Modbus register 2251 for switched power 2. This allows the input sampling
mechanism to control the output.
Use the following configuration parameters to define the switch power associated with an input.

Input Parameter Universal Input Configuration Parameter Modbus Registers

Universal Input 1 Universal Input 2 Universal Input 3 Universal Input 4

Input Enable 1001 1051 1101 1151

Sample Interval (high) 1002 1052 1102 1152

Sample Interval (low) 1003 1053 1103 1153

Switched Power Enable 1004 1054 1104 1154


Mask

Switched Power Warmup 1005 1055 1105 1155

Switched Power Voltage 1006 1056 1106 1156

Extended Input Read 1007 1057 1107 1157

Input Out-of-Sync Enable 1008 1058 1108 1158

Extended Input Read


The Extended Input Read is a bit field parameter that allows multiple inputs to be sampled with the same switch
power parameters.
If the bit field is set to 0x000F, the first four inputs are sampled after the switch power parameters are satisfied.
If the Extended Input Read parameter is set in the Universal input 1 configuration registers, set Universal inputs 2
through 4 Extended Input Read and Sample Interval parameters to zero.
Input Enable
Set to 1 to enable the input. Set to 0 to disable the input.
Out-of-Sync Enable
To enable the input to continue operating when the device is out of sync with the master radio, set to 1.
To disable the input when the device is not synchronized to the master radio, set to 0.
Sample Interval (high), Sample Interval (low)
The sample interval (rate) is a 32-bit value (requires two Modbus registers) that represents how often the I/O
board samples the input.
The register value is the number of time units. One time unit is equal to 0.01 seconds.
For example, a Modbus register value of 1000 represents a sample interval of 10 seconds (1000 0.010 seconds
= 10 seconds).
Switch Power Enable Mask
The Switch Power Enable Mask works with the warm-up and voltage parameters to define the switch power
output. The bit mask can select any number of switch powers.
0x0 - No switch power enabled
0x1 - Enable Switch Power 1
0x2 - Enable Switch Power 2
0x3 - Enable Switch Power 1 and Switch Power 2

22 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

Switch Power Voltage


The Switch Power Voltage parameter defines the output voltage of the switch power output.
This parameter applies only to inputs using switched power. If switch power is not used with an input, use the
Courtesty Power Voltage parameter to control the voltage.
See Voltage entry for Modbus register values used to select the output voltage.
Switch Power Warm-up
When an input controls power to external sensors, the Switch Power Warm-up parameter defines how long power
is applied to the external sensor before the input point is examined for changes.
The register value is the number of time units, and a time unit is 0.01 seconds. For a warm-up time of 1 second,
this parameter value is 100 (0.01 seconds 100 = 1 second).

Associate Universal Input 1 with Switch Power 1


To associate universal input 1 with switched power 1, follow these instructions. Set Input 1 to sample every 60 seconds,
with a warmup time of 10 seconds.
1. Verify Switched Power 1 Output Enable is off (0). Set Modbus Register 2201 = 0
2. Set the Sample Interval to 1 minute. Modbus Registers 1002 = 0, 1003= 6000 (0.01 seconds 6000 = 60
seconds).
3. Set the Switched Power Enable Mask to use Switch Power 1. Modbus Register 1004 = 1
4. Set the Switched Power Warm-up time to 10 seconds. Modbus Register 1005 = 1000 (0.01 seconds 1000 =
10 seconds).
5. Set the Switched Power Voltage to 16 volts. Modbus Register 1006 = 1.

5.2.3 Connecting a Battery to the DXM Controller


When attaching a battery to the DXM Controller as a backup battery or as a solar battery, verify the charging algorithm is
set properly. The factory default setting for the battery charging algorithm assumes you are using 12 to 30 V dc to
recharge the battery.
The charging algorithm is designed to work with a sealed lead acid (SLA) battery only.
When using 12 to 30 V dc, connect the 12 to 30 V dc + to pin 2 and connect the ground to pin 3.
When using main dc power with a back up battery (default configuration), connect the incoming main power pin 2
(+) and to pin 3 (-). Connect the 12 V sealed lead acid battery to pin 4 (+) and pin 5 (-). The incoming main power
must be 15 to 30 V dc to charge the battery.
When using a solar panel, connect the solar panel output to pin 2 and connect the ground to pin 3. Connect the 12
V dc SLA battery to pin 4 (+) and pin 5 (-). To change the charging algorithm, refer to Supplying Power from a
Solar Panel on page 23.

Modbus Slave ID Modbus Register Description

200 * 6071 Battery backup charging algorithm.


0 = Battery is recharged from a solar panel
1 = Battery is recharged from 12 to 30 V dc (default)

* The Modbus Slave ID for the base board is set at the factory and may be changed using the base board DIP switch
settings.

5.2.4 Supplying Power from a Solar Panel


To power the DXM100-Bx Wireless Controller from a 12 V dc solar panel, connect the solar panel to power pins 2(+) and
3(-). Connect a 12 V dc sealed lead acid (SLA) rechargeable battery to pins 4(+) and 5(-).
The factory default setting for the battery charging algorithm assumes you are using 12 to 30 V dc power to recharge the
battery. If the incoming power is from a solar panel, you must change the charging algorithm.

To change the charging algorithm from the menu system:


1. From the LCD menu, select Update > Power.
2. Use the up/down arrows to select "SOLAR" power.

To change the charging algorithm by writing to Modbus register 6071 on the I/O base board (Slave ID 200):
1. Write a 0 to select the solar power charging algorithm.

www.bannerengineering.com - Tel: 763.544.3164 23


DXM100-Bx Wireless Controller Instruction Manual

Modbus Slave ID Modbus Register Description

200 * 6071 Battery backup charging algorithm.


0 = Battery is recharged from a solar panel
1 = Battery is recharged from 12 to 30 V dc (default)

The following power operating characteristics are stored in Modbus registers.


Battery voltage
If no battery is present, the value in this register is less than 5 V. If the value in this register is greater than the
incoming voltage register, the battery is powering the system.
Battery charging current
The charging algorithm charges the battery when the incoming voltage register value is greater than the battery
voltage register value. This registers shows the charging current in milliamps.
Incoming supply voltage
The incoming power can be from a solar panel or from a power supply. The battery is charging when the incoming
voltage register value is greater than the battery voltage register value. The battery is powering the system when
the incoming voltage register value is less than the battery voltage register value.
On-board thermistor temperature
This register stores the on-board thermistor reading in tenths of degrees C, this is not a calibrated input: divide by
10 to calculate the temperature in degrees C. For calibrated temperature inputs, define one of the universal inputs
as a temperature input.

Modbus Slave ID Modbus Register Description

200 * 6081 Battery voltage (mV)

6082 Battery charging current (mA)

6083 Incoming supply voltage (mV) (solar or power supply)

6084 On-board thermistor temperature (C)

* The Slave ID for the base board is set at the factory. This may be changed using the base board DIP switch settings.

5.3 Working with Solar Power


A reliable solar system requires careful planning and monitoring to size the components correctly. The recommendations
provided are for the DXM Controller system as an autonomous system.
Adding extra components increases the power requirements and likely requires increasing the solar system components.
Depending upon the geographical location, the size of the solar panel and battery may vary.

5.3.1 Setting the DXM Controller for Solar Power


By default, the DXM Controller is set from the factory to charge a backup battery from a line power source. Use the LCD
menu on the front of the DXM Controller to change the charging algorithm to solar power.
Go to System > Power Select. Change the Power to Solar.

Power Select 08:25:45

Power: [DC]
Change Power Select
<Ent> Accept
<Back> Previous Menu

24 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

For DXM devices without an LCD, adjust the I/O board Modbus register 6071. Set the register to 0 to select battery
charging from a solar panel, and set to 1 to select battery charging from incoming 12 to 30 V dc supply.

Here are a few DXM configuration tips to help minimize the power consumption (may not apply to all models).
If Ethernet is not being used, save up to 25% of the consumed power by disabling Ethernet. Set DIP switch 1 to
the ON position on the processor board then reboot.
Instead of powering external devices all the time, take advantage of the switched power mechanisms to turn off
devices when possible.
Minimize the number of cellular transactions and the amount of data pushed across the cellular modem.

5.3.2 Solar Components


The components of a solar system include the battery and the solar panel.

Battery
The DXM solar controller is designed to use a 12 V lead acid battery. The characteristics of a solar system require the
battery to be of a certain type. There are basically two types of lead acid batteries:
SLI batteries (Starting Lights Ignition) designed for quick bursts of energy, like starting engines
Deep Cycle batteries - greater long-term energy delivery. This is the best choice for a solar battery.

Since a solar system charges and discharges daily, a deep cycle battery is the best choice. There are different versions of a
lead acid battery: wet cell (flooded), gel cell, and an AGM (absorbed glass mat).

Wet cell batteries are the original type of rechargeable battery and come in two styles, serviceable and maintenance free.
Wet cell batteries typically require special attention to ventilation as well as periodic maintenance but are the lowest cost.
The gel cell and AGM battery are sealed batteries that cost more but store very well and do not tend to sulfate or degrade
as easily as a wet cell. Gel or AGM batteries are the safest lead acid batteries you can use.
Battery Capacity

Battery capacity is a function of the ambient temperature and the rate Use this as a guide to the approximate state of
of discharge. Depending upon the specific battery, a battery operating charge and in determining when to apply
at 30 C can have as much as 40 percent less capacity than a battery conservation measures.
operating at 20 C. Choose enough battery capacity based on your
Average Voltage Readings Relative to Battery
geographical location.
Change
A larger capacity battery typically lasts longer for a given solar State of Charge (%) Open Circuit Voltage
application because lead-acid batteries do not like deep cycling
(discharging a large percentage of its capacity). Depending upon the 100 13.0 or higher
battery, a battery discharging only 30 percent of its capacity before 75 12.6
recharging will have approximately 1100 charge/discharge cycles. The
same battery discharging 50 percent of its capacity will have 50 12.1
approximately 500 charge/discharge cycles. Discharging 100 percent 25 11.66
leaves the battery with only 200 charge/discharge cycles.
0 11.4 or less
Batteries degrade over time based on discharge/charge cycles and
environmental conditions. Always monitor the battery system to obtain
the best performance of the solar powered system.

Solar Panel
Banner solar panels come in two common sizes for the DXM Controller: 5 Watt and 20 Watt. Both panels are designed to
work with the DXM Controller but provide different charging characteristics. Use the 5 watt panel for light duty operation
and use the 20 watt panel when you require greater charging capabilities.

Solar Panel Voltage Current Typical DXM Configurations

5 Watt 17 V 0.29 A DXM slave controller, ISM radio, I/O base board

20 Watt 21 V 1A DXM Controller with ISM radio and Cellular modem

Photovoltaic panels are very sensitive to shading. Unlike solar thermal panels, PV solar panels cannot tolerate shading
from a branch of a leafless tree or small amounts of snow in the corners of the panel. Because all cells are connected in a
series string, the weakest cell will bring down the other cells' power level.

Good quality solar panels will not degrade much from year to year, typically less than 1 percent .

Solar Panel Mounting

www.bannerengineering.com - Tel: 763.544.3164 25


DXM100-Bx Wireless Controller Instruction Manual

To capture the maximum amount of solar radiation throughout the year, mount a fixed solar panel to optimize the sun's
energy throughout the year. For the northern hemisphere, face the panel true south. For the southern hemisphere, face
the panel true north. If you are using a compass to orientate the panels, compensate for the difference between true north
and magnetic north. Magnetic declination varies across the globe.

A solar panel's average tilt from horizontal is at an angle equal to the latitude of the site location. For optimum
performance, adjust the tilt by plus 15 degrees in the winter or minus 15 degrees in the summer. For a fixed panel with a
consistent power requirement throughout the year, adjust the tilt angle to optimize for the winter months: latitude plus 15
degrees. Although in the summer months the angle may not be the most efficient, there are more hours of solar energy
available.

For sites with snow in the winter months, the increased angle helps to shed snow. A solar panel covered in snow produces
little or no power.

5.3.3 Recommended Solar Configurations


These solar panel and battery combinations assume direct sunlight for two to three hours a day. Solar insolation maps
provide approximate sun energy for various locations. The depth of battery discharge is assumed to be 50 percent.

Solar panel and battery combinations for a DXM Controller system

Solar Panel Battery Capacity2 Days of Autonomy DXM mA DXM Controller

5 watt 10 Ahr 10 days 25 mA DXM Slave Controller - ISM radio and I/O base board

20 watt 14 Ahr 10 days 30 mA DXM Controller with ISM radio

20 watt 20 Ahr 10 days 35 mA DXM Controller with ISM radio and Cellular Modem

5.3.4 Monitoring Solar Operation


The DXM solar controller provides Modbus registers that allow the user to monitor the state of the solar panel input
voltage, the battery voltage, the charging current, and the temperature in C. The DXM Controller can be configured to
monitor the health of the charging system as well as send an alert message when the battery is too low.
The charts show a typical charging cycle, with each vertical grid representing about eight hours. The chart shows three
days of charging.

Figure 1. Solar Panel Voltage (mV) -- Cloudy First Day

Figure 2. Battery Voltage (mV) - Cloudy First Day

2 Battery capacity (amp hour) is standard amp rating taken for 20 hours. Battery capacity should be monitored for reliable system power and may
need to be increased for cold weather locations.

26 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

5.4 Connecting the Communication Pins


The base board communications connections to the DXM100-B1 Wireless Controller are RS-485 (primary), RS-485
(secondary) or RS-232. The base board communications connections to the DXM100-B2 Wireless Controller are RS-485
(primary) and RS-485 (secondary).

RS-485. The primary RS-485 bus is a common bus shared with the ISM radio board (Modbus Slave ID 1) or optional
cellular board. The DXM100-Bx Wireless Controller is defined as the Modbus Master on this bus. Other internal Modbus
slaves include the local processor registers (Modbus Slave ID 199), the base I/O controller (Modbus Slave ID 200), and the
display board (Modbus Slave ID 201). When assigning Modbus Slave IDs to externally connected devices, only use IDs 2
through 198.

RS-232. The RS-232 bus is not currently defined for the DXM100-B1 models. There is no RS-232 for the DXM100-B2
models.

Pin Parameter Description

Pin 6 Primary RS-485


Running Modbus protocol at 19.2k baud, use this bus to connect to other Modbus Slave devices.
The DXM100-Bx Wireless Controller is a Modbus Master device on this RS-485 port.
Pin 7 Primary RS-485 +

Pin 9 RS-232 Tx
Serial RS-232 connection. This bus must use a ground connection between devices to operate
correctly. (DXM100-B1 models only; not available on the DXM100-B2 models)
Pin 10 RS-232 Rx

The DXM100-Bx Wireless Controller is a Modbus slave on this bus (see DXM100-B1 I/O Base
Pin 13 Secondary RS-485
Board Connections on page 19).

Pin 14 Secondary RS-485 +

Pin 15 CANL
DXM100-B1 models only. Not available on the DXM100-B2 models.
Pin 16 CANH +

5.4.1 Modbus RTU Master/Modbus RTU Slave


The DXM100-Bx Wireless Controller can be a Modbus RTU master device to other slave devices and can be a Modbus slave
device to another Modbus RTU master.
The DXM100-Bx Wireless Controller uses the primary RS-485 port as a Modbus RTU master to control external slave
devices. The secondary port is the Modbus RTU slave connection.
As a Modbus RTU master device, the DXM100-Bx Wireless Controller controls external slaves connected to the
primary RS-485 port, the local ISM radio, local I/O base board, and the local display board.
As a Modbus RTU slave device, the DXM100-Bx Wireless Controller local registers can be read from or written to by
another Modbus RTU master device.
Use the DXM Configuration Tool to define operational settings for both the Modbus RTU master port and the Modbus RTU
slave port.

5.5 Modbus Master Port and Slave Port


There are two RS-485 ports on the DXM Controller, a Modbus master RS-485 port and a Modbus slave RS-485 port.
The Modbus master RS-485 is controlled by the DXM Controller, which acts as the Modbus master. All wired devices
connected to the master RS-485 port must be slave devices.

The Modbus slave RS-485 port is controlled by another Modbus master device, not the DXM Controller. The slave port is
used by other devices that want to access the DXM Controller as a Modbus slave device. All local registers are available to
be read or written from this slave port. Set the Modbus Slave ID for the secondary RS-485 port using the LCD display
menu: System > DXM Slave ID.

5.5.1 Modbus Master and Slave Port Settings


The basic communications parameters for the RS-485 ports are set in the DXM Configuration Tool and are saved in the
XML configuration file. All basic settings are available under Settings > General screen of the DXM Configuration Tool.

Master port parameters include:


Baud rate and parity
Set the Communications Timeout parameter to cover the expected time for messages to be sent throughout the
wireless network. For the DXM Controller, the Communications Timeout parameter is the maximum amount of
time the DXM Controller should wait after a request is sent until the response message is received from the Modbus
slave device.

www.bannerengineering.com - Tel: 763.544.3164 27


DXM100-Bx Wireless Controller Instruction Manual

Maximum Polling Rate sets the minimum wait time from the end of a Modbus transaction to the beginning of the
next Modbus transaction.

The Modbus Slave port settings include:


Baud rate and parity (also set on this screen)
Set the Modbus Slave port ID using the DXM Controller LCD
Set the Wireless Modbus Backbone parameter when there is an ISM radio plugged into the SAM4 processor
board and the Modbus slave port is using the MultiHop radio as the slave port instead of the terminal block
connection.

5.5.2 Modbus Slave Port ID


Set the DXM Modbus slave port using the LCD menu system. On the LCD,
use the down arrow to highlight System. Enter the System menu by
Banner Eng 08:25:45
clicking Enter.
Registers
Push S 08:25:15
ENTER

ISM Radio
System
System Info BACK

To change the DXM Slave ID, highlight DXM Slave ID, then click Enter. System 08:25:45
ISM Radio
Ethernet
Provision Cell
DXM Slave ID: 255
ISM Type 08:25:45
Power: [dc / solar]
LCD Contrast: 28 ISM Type: MultiHop
Restart

Change Type
<Ent> Accept Type
<Back> Previous Menu ISM Radio 08:25:45
ISM Radio 08:25:45
Updated! A device
ISM Type: MultiHop restart is needed
ISM Modbus ID: 1 to take effect.
ISM ID 08:25:45
<Ent> Restart
ISM Modbus ID:
<Back> Previous Menu
>> 1

Change Modbus ID #
<Ent> Accept ID
<Back> Previous Menu

Use the up and down arrow buttons to change the DXM Slave ID.

Press Enter to accept the ID change.

After you change the DXM Slave ID, use the DXM Configuration Tool to cycle power to the device. After cycling power to
the device, the updated DXM Slave ID is listed under the System menu.

5.6 Inputs and Outputs


The I/O base board is a Modbus slave device (Slave ID 200) that communicates to the processor board using Modbus
commands. Use the DXM Configuration Tool to create a configuration using read/write maps that will access inputs or
outputs on the I/O board.

Communication with the I/O board runs at a maximum rate of 10 ms per transaction. The parameter setting for the bus
with the I/O board and the processor board are fixed. External Modbus communication runs at a maximum rate of 50 ms
per transaction. The parameter settings for the external RS-485 buses are controlled by the DXM Configuration Tool.

28 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

Refer to the Modbus Registers section for more descriptions of each Modbus register on the DXM100-Bx Wireless
Controller.

5.6.1 Universal Inputs


The universal inputs on the DXM100-Bx Wireless Controller can be programmed to accept several different types of inputs:
Discrete NPN/PNP
0 to 20 mA analog
0 to 10 V analog
10k temperature thermistor
Potentiometer sense
Bridge
NPN raw fast

Any input can be used as a synchronous counter by configuring the input as a discrete NPN/PNP input.

Use the DXM Configuration Tool tool to write to the appropriate Modbus registers in the I/O board to configure the input
type. The universal inputs are treated as analog inputs. When the universal inputs are defined as mA, V, or temperature,
use Modbus registers to configure the operational characteristics of the inputs. These parameters are temperature
conversion type, enable full scale, threshold and hysteresis. Refer to the DXM100 Controller Instruction Manual (p/n
190037) for the parameter definitions.

When a universal input is configured as an NPN or PNP input type, it can be enabled to be a synchronous counter. Enable
the counter function by setting Modbus register 'Enable Rising' or 'Enable Falling' to 1. See Modbus I/O Registers for the
DXM100-B1 I/O Base Board on page 31 for universal input register definitions.

Pin Universal Input Modbus Register Description

27 4 4 Program the universal inputs to accept input types NPN, PNP, 10k thermistor, 0 to 10 V, 0 to 20
mA, or potentiometer. The default setting is 8: NPN raw fast. To set the input type, write the
28 3 3 following values to the Input Type Modbus registers defined in Modbus I/O Registers for the
DXM100-B1 I/O Base Board on page 31.
31 2 2 0 = NPN
1 = PNP
2 = 0 to 20 mA
3 = 0 to 10 V dc
4 = 10k Thermistor
32 1 1
5 = Not used
6 = Not used
7 = Bridge
8 = NPN Raw Fast (default)

Thermistor Input
A thermistor input must use a 10k temperature thermistor between ground and the universal input. The
thermistor must be a 10k NTC (Banner model number BWA-THERMISTOR-002) or equivalent. Select the
temperature conversion of degrees C (default) or degrees F by writing Modbus registers defined in Modbus I/O
Registers for the DXM100-B1 I/O Base Board on page 31.
Potentiometer Input
A potentiometer input is created from three inputs: a voltage source (pin 30) that supplies 5 V to the
potentiometer and two inputs set to voltage inputs to read the voltage across the potentiometer. See the DXM
tech note for setting up a potentiometer.
Bridge Input
The bridge input is not implemented yet.
NPN vs NPN Raw Fast
The difference between NPN and NPN Raw Fast is the amount of settling time given to the input. Switch the input
type to NPN if the input is not detecting a transition.
Synchronous Counters
When an input is configured as a counter (inputs set to NPN/PNP), the input counts the input signal transitions.
The count value is stored into two 16-bit Modbus registers for a total count of 32-bits (unsigned). To program an
input to capture the edge transition counts, follow Example: Configure Input 1 as a Synchronous Counter on page
30.
Synchronous counter sample the inputs every 10 ms. The input logic does not detect rising or falling edges, but
instead samples the input every 10 ms to find level changes. The input signals must be high or low for more than
10 ms or the input will not detect transitions. Because most signals are not perfect, a realistic limit for the
synchronous counter would be 30 to 40 Hz.

www.bannerengineering.com - Tel: 763.544.3164 29


DXM100-Bx Wireless Controller Instruction Manual

Example: Configure Input 1 as a Synchronous Counter


1. Connect the DXM Controller to the PC.
2. Launch the DXM Configuration Tool software.
3. Connect to the DXM Controller by selecting the Device > Connection Settings menu option. You may connect using
either USB or Ethernet.
4. Select a COMM port from the drop-down list and click Connect.
5. Click on the Register View tab on the left part of the page.
6. Change the Source Register selection to I/O Board Registers.
7. In the Write Registers area, write Modbus register 4908 to 1 to enable counting on the rising edge of the input signal.
8. Read Modbus registers 4910 and 4911 to get the 32-bit value of the count.

Example: Change Universal Input 2 to a 0 to 10 V dc Input


1. Connect the DXM Controller to the PC.
2. Launch the DXM Configuration Tool software.
3. Connect to the DXM Controller by selecting the Device > Connection Settings menu option. You may connect using
either USB or Ethernet.
4. Select a COMM port from the drop-down list and click Connect.
5. Click on the Register View tab on the left part of the page.
6. Change the Source Register selection to I/O Board Registers.
7. Write a 3 to Modbus register 3326 on Modbus Slave ID 200 (I/O board).
8. Cycle power to the device.
9. Using the Register View tab, read register 3326 to verify it is set to 3.

Example: Change Analog Output 1 to a 0 to 10 V dc Output


1. Connect the DXM Controller to the PC.
2. Launch the DXM Configuration Tool software.
3. Connect to the DXM Controller by selecting the Device > Connection Settings menu option. You may connect using
either USB or Ethernet.
4. Select a COMM port from the drop-down list and click Connect.
5. Click on the Register View tab on the left part of the page.
6. Change the Source Register selection to I/O Board Registers.
7. Set jumper 1 on the I/O base board to the 0 to 10 V position. Refer to the base board image for the analog output
jumper position.
8. Write a 3 to Modbus register 4008 on Modbus Slave ID 200 (I/O board).
9. Cycle power to the device.
10. Using the Register View tab, read register 4008 to verify it is set to 3.

5.6.2 NMOS Outputs


Pin NMOS Discrete Modbus Register Description Wiring
Outputs

22 4 504
Output
23 3 503

24 2 502 Less than 1 A maximum current at 30 V dc


ON-State Saturation: Less than 0.7 V at 20 mA
ON Condition: Less than 0.7 V
OFF Condition: Open
35 1 501

5.6.3 Analog (DAC) Outputs


The DXM100-B1 and S1 analog outputs may be configured as either 0 to 20 mA outputs (default) or 0 to 10 V outputs.

To change the analog (DAC) output type:


1. Remove power to the device.
2. Remove the DXM cover.
3. Change the hardware jumper position (see the table for the pin number and DXM100-B1 I/O Base Board
Connections on page 19 for the pin locations).
4. Replace the DXM cover.
5. Restore power to the DXM.

30 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

6. Set the Output Type Select Modbus register (on the I/O board, Slave ID 200) to a value of 2 (default) to select 0 to
20 mA or a value of 3 to select 0 to 10 V. For analog output 1 write to Modbus register 4008, for analog output 2
write to Modbus register 4028 (see the table for the values).

DXM100-B1 and S1 Models

Pin Analog Modbus Description


Output Register

20 1 507 0 to 20 mA or 0 to 10 V dc output (I/O board jumper selectable)


Accuracy: 0.1% of full scale +0.01% per C
19 2 508 Resolution: 12-bit

Parameters for Analog Output 1 start at 4001 through 4008. Parameters for Analog Output 2 start at 4021 through 4028.

Parameter Registers for Analog Outputs (4xxxx)

OUT 1 OUT 2 Parameters

4001 4021 Maximum Analog Value

4002 4022 Minimum Analog Value

4003 4023 Enable Register Full Scale

4004 4024 Hold Last State Enable

4005 4025 Default Output State

4008 4028 Analog Output Type

Analog Output Type. The analog outputs may be configured as either 0 to 20 mA outputs (default) or 0 to 10 V outputs.
To change the analog output type change the hardware jumper position and write to the Modbus register that defines the
analog output type. For analog output 1, write to Modbus register 4008, for analog output 2 write to Modbus register
4028. Write a value of 2 (default) to select 0 to 20 mA; write a value of 3 to select 0 to 10 V.
Default Output Conditions. Default output conditions/triggers are the conditions that drive outputs to defined states.
Example default output conditions include when radios are out of sync, when a device cycles power, or during a host
communication timeout.
2952 Enable Default Communication Timeout. A communication timeout" refers to the communication
between any Modbus master host and the DXM baseboard. Set this register to 1 to enable the default condition
when the host has not communicated with the DXM baseboard for the period of time defined by the Communication
Default IO Timeout.
2953 Communication Default I/O Timeout (100 ms/Count). This parameter defines the host timeout period
in 100 millisecond increments. If a host does not communicate within this timeout period, the device outputs are
set to the default values.
2954 Enable Default on Power Up. Setting this parameter to 1 sends the device outputs to their default
condition when the DXM baseboard is powered up. Set to 0 to disable this feature.
Default Output State. The Default Output State parameter represents the default condition of the analog output. When
an error condition exists, the outputs are set to this 16-bit user-defined output state. To define the error conditions for
device outputs, refer to the MultiHop default output parameters 2950-2954.
Enable Register Full Scale. Set to 1 to enable a linear range from 0 to 65535 for specified input range. For a 4 to 20 mA
output, a value of 0 represents 4 mA and 65535 represents 20 mA. Set this parameter to 0 to store readings in unit-
specific data. For example, the register data representing a 15.53 mA reading is 15530. For units of current (0 to 20 mA
outputs), values are stored as A (micro Amps) and voltage values are stored as mV (millivolts).

Hold Last State Enable. Set the Hold Last State to 1 to set the output to its last known value before the error occurred.
Set this parameter to 0 to disable the Hold Last State and use the Default Output State setting during an error condition.

Maximum Analog Value. The Maximum Analog Value register stores the maximum allowed analog value. The specific
units of measure apply to the register value. For example, the register may contain 20000, for 20 mA, or for a voltage
output the register may contain 8000, for 8 volts.

Minimum Analog Value. The Minimum Analog Value register stores the minimum allowed analog value. The specific units
of measure apply to register value. For example, the register may contain 4000, for 4 mA, or for a voltage output the
register may contain 2000, for 2 volts.

5.6.4 Modbus I/O Registers for the DXM100-B1 I/O Base Board
The I/O base board stores the input and output values in Modbus holding registers. Since the I/O base board is defined as
a separate device, configure the DXM Controller to read or write the values on the I/O base board.

www.bannerengineering.com - Tel: 763.544.3164 31


DXM100-Bx Wireless Controller Instruction Manual

Base Board Input Connection

Modbus Register Range Description

1 065535 Universal input 1

2 065535 Universal input 2

3 065535 Universal input 3

4 065535 Universal input 4

Universal Input Register Ranges

Register Types Unit Minimum Value Maximum Value

Discrete input/output 0 1

Universal input 0 to 10 V mV 0 10000 *

Universal input 0 to 20 mA A 0 20000 *

Universal input temperature (40 C to +85 C) C or F, signed, in tenths of a degree 400 850

Universal potentiometer unsigned 0 65535

* Setting Enable Full Scale to 1 sets the ranges to a linear scale of 0 to 65535.

DXM100-B1 Controller Base Board Output Connection

Modbus Register Range Description

501 01 NMOS Output 1

502 01 NMOS Output 2

503 01 NMOS Output 3

504 01 NMOS Output 4

505 01 Switched Power 1 (5 V or 16 V)

506 01 Switched Power 2 (5 V or 16 V)

507 020000 Analog Output 1 default (0-20.000 mA)

010000 Analog Output 1 (0-10.000 V)

508 020000 Analog Output 2 default (0-20.000 mA)

010000 Analog Output 2 (0-10.000 V)

Modbus Configuration Registers for the I/O


Each input or output on the I/O base board has associated Modbus registers that configure its operation.

Universal Input Parameters Registers

Universal Inputs 1 2 3 4

Enable Full Scale Registers 3303 3323 3343 3363

Temperature C/F Registers 3304 3324 3344 3364

Input Type Registers 3306 3326 3346 3366

Threshold Registers 3308 3328 3348 3368

Hysteresis Registers 3309 3329 3349 3369

Enable Rising Registers 4908 4928 4948 4968

Enable Falling Registers 4909 4929 4949 4969

High Register for Counter Registers 4910 4930 4950 4970

Low Register for Counter Registers 4911 4931 4951 4971

32 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

Enable Full Scale


Set to 1 to enable a linear range from 0 to 65535 for specified input range. For a 4 to 20 mA input, a value of 0
represents 4 mA and 65535 represents 20 mA. Set this parameter to 0 to store input readings in unit-specific
data. For example, the register data representing a 15.53 mA reading is 15530. For units of current (0 to 20 mA
inputs), values are stored as A (micro Amps) and voltage values are stored as mV (millivolts).
Enable Rising/Falling
Use these registers to enable the universal input logic to count on a rising transition or a falling transition. Write a
one (1) to enable; write a zero (0) to disable.
High/Low Register for Counter
The low and high registers for the counter hold the 32-bit counter value. To erase the counter, write zeroes to
both registers. To preset a counter value, write that value to the appropriate register.
Hysteresis and Threshold
Threshold and hysteresis work together to establish the ON and OFF points of an analog input. The threshold
defines a trigger point or reporting threshold (ON point) for a sensor input. Setting a threshold establishes an ON
point. Hysteresis defines how far below the threshold the analog input is required to be before the input is
considered OFF. A typical hysteresis value is 10% to 20% of the units range.

ON point
In the example shown graphically, the input is considered on at
15 mA. To consider the input off at 13 mA, set the hysteresis to
Input Value

Threshold 2 mA. The input will be considered off when the value is 2 mA
Hysteresis
less than the threshold.

Input
OFF point

Time

Input Type
Program the universal inputs to accept input types NPN, PNP, 10k thermistor, 0 to 10 V, 0 to 20 mA, or
potentiometer. The default setting is 8: NPN raw fast. To set the input type, write the following values to the Input
Type Modbus registers.
0 = NPN
1 = PNP
2 = 0 to 20 mA
3 = 0 to 10 V dc
4 = 10k Thermistor
5 = Potentiometer Sense (DXM150 only)
6 = Not used
7 = Bridge
8 = NPN Raw Fast (default)
Temperature C/F
Set to 1 to represent temperature units in degrees Fahrenheit, and set to 0 (default) to represent temperature
units in degrees Celsius.

Modbus Configuration Registers for the Analog Output


The DXM100-B1 I/O base board has two analog outputs that are selectable as 0 to 20 mA (factory default) or 0 to 10 V. To
change the analog output characteristic, physical jumpers must be change on the I/O board and a parameter Modbus
register must be changed. For step by step instructions on changing the output characteristics see Analog (DAC) Outputs
on page 30.

Modbus Register Analog Output Description

4008 Analog Output 1 0 to 20 mA or 0 to 10 V dc output (I/O board jumper selectable)

4028 Analog Output 2 Accuracy: 0.1% of full scale +0.01% per C


Resolution: 12-bit
After changing the jumper position, write the appropriate value to the Modbus registers to define
your analog output to match the setting selected by the jumper.
2 = 0 to 20 mA output (default)
3 = 0 to 10 V output

www.bannerengineering.com - Tel: 763.544.3164 33


DXM100-Bx Wireless Controller Instruction Manual

Modbus Configuration Registers for Power


To monitor the input power characteristics of the DXM Controller, read the following power Modbus registers. The on-board
thermistor is not calibrated, but can be used as a non-precision temperature input.

Modbus Register Description

6071 Battery backup charging algorithm.


0 = Battery is recharged from a solar panel
1 = Battery is recharged from 12 to 30 V dc . (default)

6081 Battery voltage (mV)

6082 Battery charging current (mA)

6083 Incoming supply voltage (mV) (solar or power supply)

6084 On-board thermistor temperature (C)

5.7 Restoring Factory Default Settings


To reset to factory defaults, write to two Modbus registers in the I/O board. The default slave ID for the I/O board is 200.

To reset the DXM I/O board parameters:


1. Write a 1 to Modbus register 4152
2. Write a 10 to Modbus register 4151
To reset only the I/O board:
1. Write a 0 to Modbus register 4152
2. Write a 10 to Modbus register 4151

Modbus Register Values Description

4151 0255 Reset/restore trigger. This timer is based in 100 millisecond units. Once written, the timer starts to count down to
zero. After the timer expires, the restore factory defaults are applied if register 4152 = 1. If register 4152 is zero,
the I/O board is reset.

Default value: 0

1 = 100 milliseconds, 10 = 1 second.

4152 01 1 = Restores factory defaults for I/O parameters.


Default value: 0

5.8 Setting the Modbus Slave ID on the I/O Base Board


Only DXM100-S1 and -S1R2 Slave models require that the Modbus Slave ID to be adjusted on the I/O base board. The
DXM100-Bx Wireless Controller models use DIP switches J and K to set the Modbus Slave ID. This device can use a
Modbus register 6804 in the I/O board to access the full range of Modbus Slave IDs.
On the DXM100-Bx Wireless Controller models, use the DIP switches at location K to define the lower digit of the Modbus
Slave ID.

DIP Switch location J defines the course group of Modbus Slave IDs. DIP Switch 4 must be set to ON for DXM100-S1,
DXM100-S2, DXM100-S1R2, and DXM100-S2R2 models.

Location J DIP Switches


Settings
1 2 3 4

Modbus Slave ID set to 11 through 19 OFF OFF

Modbus Slave ID set to 20 through 29 ON OFF

Modbus Slave ID set to 30 through 39 OFF ON

Modbus Slave ID set to 40 through 49 ON ON

Not Used -

Modbus Slave Configuration (DX100-S1 and -S1R2 models only) 3 ON

3 Must be in the ON position for the -S1 and -S1R2 model)

34 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

Location J DIP Switches


Settings
1 2 3 4

Standard Communication Mode OFF

DIP Switches J DIP Switch K, Switches 1, 2, 3, 4 (0 is OFF, 1 is ON)

1 2 0,0,0,0 1,0,0,0 0,1,0,0 1,1,0,0 0,0,1,0 1,0,1,0 0,1,1,0 1,1,1,0 0,0,0,1 1,0,0,1

OFF OFF x4 11 12 13 14 15 16 17 18 19

ON OFF 20 21 22 23 24 25 26 27 28 29

OFF ON 30 31 32 33 34 35 36 37 38 39

ON ON 40 41 42 43 44 45 46 47 48 49

DXM100-Bx Wireless Controller ExampleTo set the DXM100-Bx Wireless Controller to a Modbus Slave ID of 34, set
the following:
Location J DIP switches set to 1=OFF, 2=ON
Location K DIP switches set to 1=OFF, 2=OFF, 3=ON, 4=OFF

The location J DIP switches set the upper Modbus Slave ID digit to 3 while the location K DIP switches set the lower digit to
4.

Setting the DXM I/O Board Modbus Slave ID using Modbus RegistersWrite to the I/O board's Modbus register
6804 to set the Modbus Slave ID to any valid Modbus Slave ID (1 through 245).
For the DXM100-Bx Wireless Controller model, all switches on DIP switch K should be in the OFF position to use the
Modbus register slave ID.

4 Uses value in Modbus register 6804.

www.bannerengineering.com - Tel: 763.544.3164 35


DXM100-Bx Wireless Controller Instruction Manual

6 I/O Base Board for the DXM100-B2 Models


6.1 DXM100-B2 and S2 I/O Base Board Connections

B 32 19 D
1 1 1
TB1 TB2 TB3

P2

TVS1

P1

P4
P3

P6
P7

M L H

C4
L1

P5
P10
P8

P9

Y1
R77
R82

ON

J
C6

SW1

L ON

SW2 1
K

L2

A C
LED2
LED1

TB4 TB5 TB9


1 1 1

1 18

1 No connection 12 D2B. DLatch 2B 23 N3. NMOS OUT 3

2 PW. 1230 V dc or solar power in (+) 13 S-. Secondary RS-485 24 N2. NMOS OUT 2

3 GD. Ground 14 S+. Secondary RS-485 + 25 N1. NMOS OUT 1

4 B+. Battery in (< 15 V dc) 15 P12. SDI-12 Courtesy Power 26 GD. Ground

5 GD. Ground 16 D12. SDI-12 Data 27 U4. Universal Input 4

6 M-. Primary RS-485 17 GD. GND 28 U3. Universal Input 3

7 M+. Primary RS-485 + 18 P3. Courtesy Power 5 V 29 GD. Ground

P1. Adjustable Courtesy Power (524


8 GD. Ground 19 A2. Analog OUT 2 (010 V) 30
V)

9 D1A. DLatch 1A 20 A1. Analog OUT 1 (010 V) 31 U2. Universal Input 2

P2. Adjustable Courtesy Power (524


10 D1B. DLatch 1B 21 32 U1. Universal Input 1
V)

11 D2A. DLatch 2A 22 N4. NMOS OUT 4

A Base board LED J Modbus Slave ID DIP Switches

B A1. Cellular antenna K Modbus Slave ID DIP Switches

C Radio LED G Programming header L SAM4 Processor Board Connection

D A2. ISM Antenna H ISM Radio Board Connection M Display Connection

6.1.1 DIP Switches for the I/O Board


The DXM100-Bx Wireless Controller I/O board DIP switches are set from the factory to Modbus Slave ID 200. For more
information, refer to Setting the Modbus Slave ID on the I/O Base Board.

36 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

6.2 Applying Power to the DXM100-Bx Wireless Controller


Apply power to the DXM100-Bx Wireless Controller using either 12 to 30 V dc or a 12 V dc solar panel and 12 V sealed
lead acid battery operating together.

The DXM100 has three power input and three power output options:
Input Power:
12 to 30 V dc
12 to 30 V dc solar panel
12 V dc sealed lead acid battery with automatic charging

Courtesy Output Power Supplies:


One 5 V dc fixed
Two 5 V dc or 16 V dc (DXM100-B1 models) or Two 5 V to 24 V dc (DXM100-B2 models)

The DXM Controller continuously monitors the health of the power inputs. If a power input fault is detected, the DXM
Controller automatically switches over to battery with continuous uninterrupted operation.

If the incoming voltage drops below 11.2 V dc, the cellular modem does not turn on and will not turn on until the voltage is
above 11.8 V dc. A text file (CmVMon.txt) on the internal micro SD card saves the periodic sampling of the incoming
voltage. If cellular operation stops because of voltage, it is logged in this file.

Pin Description

Pin 1 No connection

Pin 2 12 to 30 V dc input (+) or solar panel connection (+)

Pins 3, 5, 8, 17, 26, 29 Main logic ground for the DXM100-Bx Wireless Controller

Pin 4 Solar or backup battery positive input. Battery voltage must be less than 15 V dc. Use only a sealed lead acid (SLA)
battery.

6.2.1 Using Courtesy Power or Switch Power


Pin 18 of the DXM100-Bx Wireless Controller is a constant power source that supplies 5 volts up to 500 mA.
Pins 21 (switch power 2) and 30 (switch power 1) are switched power outputs. Configure the switched power outputs using
Modbus registers. The output voltage can be selected and is controlled using a Modbus register on the I/O board (Modbus
slave ID 200). The voltage options are:
5 volts or 16 volts for DXM100-B1 models; or
5 to 24 V dc for DXM100-B2 models.
Turn the switched power on or off using the output register 505 for switch power 1 or 506 for switch power 2. For
continuous power, set the Default Output register to 1, then cycle the power.

Switch Power Enable Register Voltage Register Default Output Register Output Register

1 (pin 30) 2201 3601 3602 505


Write a 0 to turn OFF Write a 0 to select 5 V (default)
Write a 1 to turn ON (default) Write a 1 to select 16 V

2 (pin 21) 2251 3621 3622 506


Write a 0 to turn OFF Write a 0 to select 5 V (default)
Write a 1 to turn ON (default) Write a 1 to select 16 V

Enable Register
Configuration registers that turn on the ability to use the switched power output.
Default setting = ON
Voltage Register
Configuration registers that define the output voltage to the switched power output.
Default setting = 5 V
Default Output Register
Configuration registers that turn on the switched power outputs for continuous power out.
Set register to 1 for continuous power. Cycle power if this register is changed.
Default setting = 0

www.bannerengineering.com - Tel: 763.544.3164 37


DXM100-Bx Wireless Controller Instruction Manual

Modbus Output Register


Turn on or turn off the voltage output. If both outputs 505 and 506 are turned on at the same time but are set to
different voltages, the output voltage is 5 V for DXM100-B1 models and set to the lower voltage setting for
DXM100-B2 models.

6.2.2 Associating a Switched Power Output to an Input


Switched power 1 and 2 (pins 30 and 21) can be associated to any Universal input to apply power a sensor, take a
reading, and then remove power from the sensor. This conserves power in battery-operated systems.

The switched power supply can be used in one of two different ways: supplying courtesy power to an output pin or
associated to an input. (Only one method can be active at a time.)
Use the following configuration parameters to define the courtesy power supplied to a switched power output pin.

Courtesy Power Output Configuration Parameters 5 Modbus Registers

Switched Power 1 Switched Power 2

Switched Power Enable 2201 2251

Voltage 3601 3621

Default Output 3602 3622

Output Register 505 506

Default Output
Set the register value to 1 for continuous power. The default setting is 0.
Cycle power if this register value is changed.
Switched Power Enable
Enables the switched power supply. Set to 1 to enable; set to 0 to disable.
This does not enable the supply output to the actual output pin. To enable the supply output to the output pin, set
Modbus register 505 or 506 to 1. Set to 0 when associating the switched power supply to an input.
Output Register
Write to the Output register to turn on or turn off the voltage output.
If both Output Registers 505 and 506 are turned on at the same time, but are set to different voltages, the output
voltage is 5 V for DXM100-B1 models and set to the lower voltage setting for DXM100-B2 models.
Voltage
For the B1 and S1 models, set the Modbus register value to 0 for a switched power supply at 5 volts. Se the
Modbus register value to 1 for a switched power supply at 16 volts.
For the B2 and S2 models, set one of the following register values to select your switched power output voltage.
For 5 V, set the Modbus register to 204.
For 7 V, set the Modbus register to 125.
For 10 V, set the Modbus register to 69.
For 15 V, set the Modbus register to 32.
For 20 V, set the Modbus register to 12.
For 24 V, set the Modbus register to 3.
When associating a switched power supply to an input, set the Switch Power Output Enable register to off (0). Set
Modbus register 2201 for switched power 1 and Modbus register 2251 for switched power 2. This allows the input sampling
mechanism to control the output.
Use the following configuration parameters to define the switch power associated with an input.

Input Parameter Universal Input Configuration Parameter Modbus Registers

Universal Input 1 Universal Input 2 Universal Input 3 Universal Input 4

Input Enable 1001 1051 1101 1151

Sample Interval (high) 1002 1052 1102 1152

Sample Interval (low) 1003 1053 1103 1153

Switched Power Enable 1004 1054 1104 1154


Mask

5 Only used when supply courtesy power to the output pin, not when associating switched power to an input.

38 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

Input Parameter Universal Input Configuration Parameter Modbus Registers

Universal Input 1 Universal Input 2 Universal Input 3 Universal Input 4

Switched Power Warmup 1005 1055 1105 1155

Switched Power Voltage 1006 1056 1106 1156

Extended Input Read 1007 1057 1107 1157

Input Out-of-Sync Enable 1008 1058 1108 1158

Extended Input Read


The Extended Input Read is a bit field parameter that allows multiple inputs to be sampled with the same switch
power parameters.
If the bit field is set to 0x000F, the first four inputs are sampled after the switch power parameters are satisfied.
If the Extended Input Read parameter is set in the Universal input 1 configuration registers, set Universal inputs 2
through 4 Extended Input Read and Sample Interval parameters to zero.
Input Enable
Set to 1 to enable the input. Set to 0 to disable the input.
Out-of-Sync Enable
To enable the input to continue operating when the device is out of sync with the master radio, set to 1.
To disable the input when the device is not synchronized to the master radio, set to 0.
Sample Interval (high), Sample Interval (low)
The sample interval (rate) is a 32-bit value (requires two Modbus registers) that represents how often the I/O
board samples the input.
The register value is the number of time units. One time unit is equal to 0.01 seconds.
For example, a Modbus register value of 1000 represents a sample interval of 10 seconds (1000 0.010 seconds
= 10 seconds).
Switch Power Enable Mask
The Switch Power Enable Mask works with the warm-up and voltage parameters to define the switch power
output. The bit mask can select any number of switch powers.
0x0 - No switch power enabled
0x1 - Enable Switch Power 1
0x2 - Enable Switch Power 2
0x3 - Enable Switch Power 1 and Switch Power 2
Switch Power Voltage
The Switch Power Voltage parameter defines the output voltage of the switch power output.
This parameter applies only to inputs using switched power. If switch power is not used with an input, use the
Courtesty Power Voltage parameter to control the voltage.
See Voltage entry for Modbus register values used to select the output voltage.
Switch Power Warm-up
When an input controls power to external sensors, the Switch Power Warm-up parameter defines how long power
is applied to the external sensor before the input point is examined for changes.
The register value is the number of time units, and a time unit is 0.01 seconds. For a warm-up time of 1 second,
this parameter value is 100 (0.01 seconds 100 = 1 second).

Associate Universal Input 1 with Switch Power 1


To associate universal input 1 with switched power 1, follow these instructions. Set Input 1 to sample every 60 seconds,
with a warmup time of 10 seconds.
1. Verify Switched Power 1 Output Enable is off (0). Set Modbus Register 2201 = 0
2. Set the Sample Interval to 1 minute. Modbus Registers 1002 = 0, 1003= 6000 (0.01 seconds 6000 = 60
seconds).
3. Set the Switched Power Enable Mask to use Switch Power 1. Modbus Register 1004 = 1
4. Set the Switched Power Warm-up time to 10 seconds. Modbus Register 1005 = 1000 (0.01 seconds 1000 =
10 seconds).
5. Set the Switched Power Voltage to 16 volts. Modbus Register 1006 = 1.

www.bannerengineering.com - Tel: 763.544.3164 39


DXM100-Bx Wireless Controller Instruction Manual

6.2.3 Connecting a Battery to the DXM Controller


When attaching a battery to the DXM Controller as a backup battery or as a solar battery, verify the charging algorithm is
set properly. The factory default setting for the battery charging algorithm assumes you are using 12 to 30 V dc to
recharge the battery.

The charging algorithm is designed to work with a sealed lead acid (SLA) battery only.
When using 12 to 30 V dc, connect the 12 to 30 V dc + to pin 2 and connect the ground to pin 3.
When using main dc power with a back up battery (default configuration), connect the incoming main power pin 2
(+) and to pin 3 (-). Connect the 12 V sealed lead acid battery to pin 4 (+) and pin 5 (-). The incoming main power
must be 15 to 30 V dc to charge the battery.
When using a solar panel, connect the solar panel output to pin 2 and connect the ground to pin 3. Connect the 12
V dc SLA battery to pin 4 (+) and pin 5 (-). To change the charging algorithm, refer to Supplying Power from a
Solar Panel on page 23.

Modbus Slave ID Modbus Register Description

200 * 6071 Battery backup charging algorithm.


0 = Battery is recharged from a solar panel
1 = Battery is recharged from 12 to 30 V dc (default)

* The Modbus Slave ID for the base board is set at the factory and may be changed using the base board DIP switch
settings.

6.2.4 Supplying Power from a Solar Panel


To power the DXM100-Bx Wireless Controller from a 12 V dc solar panel, connect the solar panel to power pins 2(+) and
3(-). Connect a 12 V dc sealed lead acid (SLA) rechargeable battery to pins 4(+) and 5(-).
The factory default setting for the battery charging algorithm assumes you are using 12 to 30 V dc power to recharge the
battery. If the incoming power is from a solar panel, you must change the charging algorithm.
To change the charging algorithm from the menu system:
1. From the LCD menu, select Update > Power.
2. Use the up/down arrows to select "SOLAR" power.
To change the charging algorithm by writing to Modbus register 6071 on the I/O base board (Slave ID 200):
1. Write a 0 to select the solar power charging algorithm.

Modbus Slave ID Modbus Register Description

200 * 6071 Battery backup charging algorithm.


0 = Battery is recharged from a solar panel
1 = Battery is recharged from 12 to 30 V dc (default)

The following power operating characteristics are stored in Modbus registers.


Battery voltage
If no battery is present, the value in this register is less than 5 V. If the value in this register is greater than the
incoming voltage register, the battery is powering the system.
Battery charging current
The charging algorithm charges the battery when the incoming voltage register value is greater than the battery
voltage register value. This registers shows the charging current in milliamps.
Incoming supply voltage
The incoming power can be from a solar panel or from a power supply. The battery is charging when the incoming
voltage register value is greater than the battery voltage register value. The battery is powering the system when
the incoming voltage register value is less than the battery voltage register value.
On-board thermistor temperature
This register stores the on-board thermistor reading in tenths of degrees C, this is not a calibrated input: divide by
10 to calculate the temperature in degrees C. For calibrated temperature inputs, define one of the universal inputs
as a temperature input.

Modbus Slave ID Modbus Register Description

200 * 6081 Battery voltage (mV)

40 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

Modbus Slave ID Modbus Register Description

6082 Battery charging current (mA)

6083 Incoming supply voltage (mV) (solar or power supply)

6084 On-board thermistor temperature (C)

* The Slave ID for the base board is set at the factory. This may be changed using the base board DIP switch settings.

6.3 Working with Solar Power


A reliable solar system requires careful planning and monitoring to size the components correctly. The recommendations
provided are for the DXM Controller system as an autonomous system.

Adding extra components increases the power requirements and likely requires increasing the solar system components.
Depending upon the geographical location, the size of the solar panel and battery may vary.

6.3.1 Setting the DXM Controller for Solar Power


By default, the DXM Controller is set from the factory to charge a backup battery from a line power source. Use the LCD
menu on the front of the DXM Controller to change the charging algorithm to solar power.

Go to System > Power Select. Change the Power to Solar.

Power Select 08:25:45

Power: [DC]
Change Power Select
<Ent> Accept
<Back> Previous Menu

For DXM devices without an LCD, adjust the I/O board Modbus register 6071. Set the register to 0 to select battery
charging from a solar panel, and set to 1 to select battery charging from incoming 12 to 30 V dc supply.
Here are a few DXM configuration tips to help minimize the power consumption (may not apply to all models).
If Ethernet is not being used, save up to 25% of the consumed power by disabling Ethernet. Set DIP switch 1 to
the ON position on the processor board then reboot.
Instead of powering external devices all the time, take advantage of the switched power mechanisms to turn off
devices when possible.
Minimize the number of cellular transactions and the amount of data pushed across the cellular modem.

6.3.2 Solar Components


The components of a solar system include the battery and the solar panel.

Battery
The DXM solar controller is designed to use a 12 V lead acid battery. The characteristics of a solar system require the
battery to be of a certain type. There are basically two types of lead acid batteries:
SLI batteries (Starting Lights Ignition) designed for quick bursts of energy, like starting engines
Deep Cycle batteries - greater long-term energy delivery. This is the best choice for a solar battery.

Since a solar system charges and discharges daily, a deep cycle battery is the best choice. There are different versions of a
lead acid battery: wet cell (flooded), gel cell, and an AGM (absorbed glass mat).

www.bannerengineering.com - Tel: 763.544.3164 41


DXM100-Bx Wireless Controller Instruction Manual

Wet cell batteries are the original type of rechargeable battery and come in two styles, serviceable and maintenance free.
Wet cell batteries typically require special attention to ventilation as well as periodic maintenance but are the lowest cost.
The gel cell and AGM battery are sealed batteries that cost more but store very well and do not tend to sulfate or degrade
as easily as a wet cell. Gel or AGM batteries are the safest lead acid batteries you can use.

Battery Capacity

Battery capacity is a function of the ambient temperature and the rate Use this as a guide to the approximate state of
of discharge. Depending upon the specific battery, a battery operating charge and in determining when to apply
at 30 C can have as much as 40 percent less capacity than a battery conservation measures.
operating at 20 C. Choose enough battery capacity based on your
Average Voltage Readings Relative to Battery
geographical location.
Change
A larger capacity battery typically lasts longer for a given solar State of Charge (%) Open Circuit Voltage
application because lead-acid batteries do not like deep cycling
(discharging a large percentage of its capacity). Depending upon the 100 13.0 or higher
battery, a battery discharging only 30 percent of its capacity before 75 12.6
recharging will have approximately 1100 charge/discharge cycles. The
same battery discharging 50 percent of its capacity will have 50 12.1
approximately 500 charge/discharge cycles. Discharging 100 percent 25 11.66
leaves the battery with only 200 charge/discharge cycles.
0 11.4 or less
Batteries degrade over time based on discharge/charge cycles and
environmental conditions. Always monitor the battery system to obtain
the best performance of the solar powered system.

Solar Panel
Banner solar panels come in two common sizes for the DXM Controller: 5 Watt and 20 Watt. Both panels are designed to
work with the DXM Controller but provide different charging characteristics. Use the 5 watt panel for light duty operation
and use the 20 watt panel when you require greater charging capabilities.

Solar Panel Voltage Current Typical DXM Configurations

5 Watt 17 V 0.29 A DXM slave controller, ISM radio, I/O base board

20 Watt 21 V 1A DXM Controller with ISM radio and Cellular modem

Photovoltaic panels are very sensitive to shading. Unlike solar thermal panels, PV solar panels cannot tolerate shading
from a branch of a leafless tree or small amounts of snow in the corners of the panel. Because all cells are connected in a
series string, the weakest cell will bring down the other cells' power level.
Good quality solar panels will not degrade much from year to year, typically less than 1 percent .
Solar Panel Mounting
To capture the maximum amount of solar radiation throughout the year, mount a fixed solar panel to optimize the sun's
energy throughout the year. For the northern hemisphere, face the panel true south. For the southern hemisphere, face
the panel true north. If you are using a compass to orientate the panels, compensate for the difference between true north
and magnetic north. Magnetic declination varies across the globe.
A solar panel's average tilt from horizontal is at an angle equal to the latitude of the site location. For optimum
performance, adjust the tilt by plus 15 degrees in the winter or minus 15 degrees in the summer. For a fixed panel with a
consistent power requirement throughout the year, adjust the tilt angle to optimize for the winter months: latitude plus 15
degrees. Although in the summer months the angle may not be the most efficient, there are more hours of solar energy
available.

For sites with snow in the winter months, the increased angle helps to shed snow. A solar panel covered in snow produces
little or no power.

6.3.3 Recommended Solar Configurations


These solar panel and battery combinations assume direct sunlight for two to three hours a day. Solar insolation maps
provide approximate sun energy for various locations. The depth of battery discharge is assumed to be 50 percent.

42 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

Solar panel and battery combinations for a DXM Controller system

Solar Panel Battery Capacity6 Days of Autonomy DXM mA DXM Controller

5 watt 10 Ahr 10 days 25 mA DXM Slave Controller - ISM radio and I/O base board

20 watt 14 Ahr 10 days 30 mA DXM Controller with ISM radio

20 watt 20 Ahr 10 days 35 mA DXM Controller with ISM radio and Cellular Modem

6.3.4 Monitoring Solar Operation


The DXM solar controller provides Modbus registers that allow the user to monitor the state of the solar panel input
voltage, the battery voltage, the charging current, and the temperature in C. The DXM Controller can be configured to
monitor the health of the charging system as well as send an alert message when the battery is too low.

The charts show a typical charging cycle, with each vertical grid representing about eight hours. The chart shows three
days of charging.

Figure 3. Solar Panel Voltage (mV) -- Cloudy First Day

Figure 4. Battery Voltage (mV) - Cloudy First Day

6.4 Connecting the Communication Pins


The base board communications connections to the DXM100-B1 Wireless Controller are RS-485 (primary), RS-485
(secondary) or RS-232. The base board communications connections to the DXM100-B2 Wireless Controller are RS-485
(primary) and RS-485 (secondary).
RS-485. The primary RS-485 bus is a common bus shared with the ISM radio board (Modbus Slave ID 1) or optional
cellular board. The DXM100-Bx Wireless Controller is defined as the Modbus Master on this bus. Other internal Modbus
slaves include the local processor registers (Modbus Slave ID 199), the base I/O controller (Modbus Slave ID 200), and the
display board (Modbus Slave ID 201). When assigning Modbus Slave IDs to externally connected devices, only use IDs 2
through 198.

RS-232. The RS-232 bus is not currently defined for the DXM100-B1 models. There is no RS-232 for the DXM100-B2
models.

Pin Parameter Description

Pin 6 Primary RS-485


Running Modbus protocol at 19.2k baud, use this bus to connect to other Modbus Slave devices.
The DXM100-Bx Wireless Controller is a Modbus Master device on this RS-485 port.
Pin 7 Primary RS-485 +

6 Battery capacity (amp hour) is standard amp rating taken for 20 hours. Battery capacity should be monitored for reliable system power and may
need to be increased for cold weather locations.

www.bannerengineering.com - Tel: 763.544.3164 43


DXM100-Bx Wireless Controller Instruction Manual

Pin Parameter Description

Pin 9 RS-232 Tx
Serial RS-232 connection. This bus must use a ground connection between devices to operate
correctly. (DXM100-B1 models only; not available on the DXM100-B2 models)
Pin 10 RS-232 Rx

The DXM100-Bx Wireless Controller is a Modbus slave on this bus (see DXM100-B1 I/O Base
Pin 13 Secondary RS-485
Board Connections on page 19).

Pin 14 Secondary RS-485 +

Pin 15 CANL
DXM100-B1 models only. Not available on the DXM100-B2 models.
Pin 16 CANH +

6.4.1 Modbus RTU Master/Modbus RTU Slave


The DXM100-Bx Wireless Controller can be a Modbus RTU master device to other slave devices and can be a Modbus slave
device to another Modbus RTU master.

The DXM100-Bx Wireless Controller uses the primary RS-485 port as a Modbus RTU master to control external slave
devices. The secondary port is the Modbus RTU slave connection.
As a Modbus RTU master device, the DXM100-Bx Wireless Controller controls external slaves connected to the
primary RS-485 port, the local ISM radio, local I/O base board, and the local display board.
As a Modbus RTU slave device, the DXM100-Bx Wireless Controller local registers can be read from or written to by
another Modbus RTU master device.

Use the DXM Configuration Tool to define operational settings for both the Modbus RTU master port and the Modbus RTU
slave port.

6.5 Modbus Master Port and Slave Port


There are two RS-485 ports on the DXM Controller, a Modbus master RS-485 port and a Modbus slave RS-485 port.
The Modbus master RS-485 is controlled by the DXM Controller, which acts as the Modbus master. All wired devices
connected to the master RS-485 port must be slave devices.
The Modbus slave RS-485 port is controlled by another Modbus master device, not the DXM Controller. The slave port is
used by other devices that want to access the DXM Controller as a Modbus slave device. All local registers are available to
be read or written from this slave port. Set the Modbus Slave ID for the secondary RS-485 port using the LCD display
menu: System > DXM Slave ID.

6.5.1 Modbus Master and Slave Port Settings


The basic communications parameters for the RS-485 ports are set in the DXM Configuration Tool and are saved in the
XML configuration file. All basic settings are available under Settings > General screen of the DXM Configuration Tool.
Master port parameters include:
Baud rate and parity
Set the Communications Timeout parameter to cover the expected time for messages to be sent throughout the
wireless network. For the DXM Controller, the Communications Timeout parameter is the maximum amount of
time the DXM Controller should wait after a request is sent until the response message is received from the Modbus
slave device.
Maximum Polling Rate sets the minimum wait time from the end of a Modbus transaction to the beginning of the
next Modbus transaction.

44 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

The Modbus Slave port settings include:


Baud rate and parity (also set on this screen)
Set the Modbus Slave port ID using the DXM Controller LCD
Set the Wireless Modbus Backbone parameter when there is an ISM radio plugged into the SAM4 processor
board and the Modbus slave port is using the MultiHop radio as the slave port instead of the terminal block
connection.

6.5.2 Modbus Slave Port ID


Set the DXM Modbus slave port using the LCD menu system. On the LCD,
use the down arrow to highlight System. Enter the System menu by
Banner Eng 08:25:45
clicking Enter.
Registers
Push S 08:25:15
ENTER

ISM Radio
System
System Info BACK

To change the DXM Slave ID, highlight DXM Slave ID, then click Enter. System 08:25:45
ISM Radio
Ethernet
Provision Cell
DXM Slave ID: 255
ISM Type 08:25:45
Power: [dc / solar]
LCD Contrast: 28 ISM Type: MultiHop
Restart

Change Type
<Ent> Accept Type
<Back> Previous Menu ISM Radio 08:25:45
ISM Radio 08:25:45
Updated! A device
ISM Type: MultiHop restart is needed
ISM Modbus ID: 1 to take effect.
ISM ID 08:25:45
<Ent> Restart
ISM Modbus ID:
<Back> Previous Menu
>> 1

Change Modbus ID #
<Ent> Accept ID
<Back> Previous Menu

Use the up and down arrow buttons to change the DXM Slave ID.

Press Enter to accept the ID change.

After you change the DXM Slave ID, use the DXM Configuration Tool to cycle power to the device. After cycling power to
the device, the updated DXM Slave ID is listed under the System menu.

6.6 Inputs and Outputs


The I/O base board is a Modbus slave device (Slave ID 200) that communicates to the processor board using Modbus
commands. Use the DXM Configuration Tool to create a configuration using read/write maps that will access inputs or
outputs on the I/O board.

Communication with the I/O board runs at a maximum rate of 10 ms per transaction. The parameter setting for the bus
with the I/O board and the processor board are fixed. External Modbus communication runs at a maximum rate of 50 ms
per transaction. The parameter settings for the external RS-485 buses are controlled by the DXM Configuration Tool.

Refer to the Modbus Registers section for more descriptions of each Modbus register on the DXM100-Bx Wireless
Controller.

www.bannerengineering.com - Tel: 763.544.3164 45


DXM100-Bx Wireless Controller Instruction Manual

6.6.1 Universal Inputs


The universal inputs on the DXM100-Bx Wireless Controller can be programmed to accept several different types of inputs:
Discrete NPN/PNP
0 to 20 mA analog
0 to 10 V analog
10k temperature thermistor
Potentiometer sense
Bridge
NPN raw fast

Any input can be used as a synchronous counter by configuring the input as a discrete NPN/PNP input.

Use the DXM Configuration Tool tool to write to the appropriate Modbus registers in the I/O board to configure the input
type. The universal inputs are treated as analog inputs. When the universal inputs are defined as mA, V, or temperature,
use Modbus registers to configure the operational characteristics of the inputs. These parameters are temperature
conversion type, enable full scale, threshold and hysteresis. Refer to the DXM100 Controller Instruction Manual (p/n
190037) for the parameter definitions.

When a universal input is configured as an NPN or PNP input type, it can be enabled to be a synchronous counter. Enable
the counter function by setting Modbus register 'Enable Rising' or 'Enable Falling' to 1. See Modbus I/O Registers for the
DXM100-B1 I/O Base Board on page 31 for universal input register definitions.

Pin Universal Input Modbus Register Description

27 4 4 Program the universal inputs to accept input types NPN, PNP, 10k thermistor, 0 to 10 V, 0 to 20
mA, or potentiometer. The default setting is 8: NPN raw fast. To set the input type, write the
28 3 3 following values to the Input Type Modbus registers defined in Modbus I/O Registers for the
DXM100-B1 I/O Base Board on page 31.
31 2 2 0 = NPN
1 = PNP
2 = 0 to 20 mA
3 = 0 to 10 V dc
4 = 10k Thermistor
32 1 1
5 = Not used
6 = Not used
7 = Bridge
8 = NPN Raw Fast (default)

Thermistor Input
A thermistor input must use a 10k temperature thermistor between ground and the universal input. The
thermistor must be a 10k NTC (Banner model number BWA-THERMISTOR-002) or equivalent. Select the
temperature conversion of degrees C (default) or degrees F by writing Modbus registers defined in Modbus I/O
Registers for the DXM100-B1 I/O Base Board on page 31.
Potentiometer Input
A potentiometer input is created from three inputs: a voltage source (pin 30) that supplies 5 V to the
potentiometer and two inputs set to voltage inputs to read the voltage across the potentiometer. See the DXM
tech note for setting up a potentiometer.
Bridge Input
The bridge input is not implemented yet.
NPN vs NPN Raw Fast
The difference between NPN and NPN Raw Fast is the amount of settling time given to the input. Switch the input
type to NPN if the input is not detecting a transition.
Synchronous Counters
When an input is configured as a counter (inputs set to NPN/PNP), the input counts the input signal transitions.
The count value is stored into two 16-bit Modbus registers for a total count of 32-bits (unsigned). To program an
input to capture the edge transition counts, follow Example: Configure Input 1 as a Synchronous Counter on page
30.
Synchronous counter sample the inputs every 10 ms. The input logic does not detect rising or falling edges, but
instead samples the input every 10 ms to find level changes. The input signals must be high or low for more than
10 ms or the input will not detect transitions. Because most signals are not perfect, a realistic limit for the
synchronous counter would be 30 to 40 Hz.

Example: Configure Input 1 as a Synchronous Counter


1. Connect the DXM Controller to the PC.
2. Launch the DXM Configuration Tool software.
3. Connect to the DXM Controller by selecting the Device > Connection Settings menu option. You may connect using
either USB or Ethernet.

46 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

4. Select a COMM port from the drop-down list and click Connect.
5. Click on the Register View tab on the left part of the page.
6. Change the Source Register selection to I/O Board Registers.
7. In the Write Registers area, write Modbus register 4908 to 1 to enable counting on the rising edge of the input signal.
8. Read Modbus registers 4910 and 4911 to get the 32-bit value of the count.

Example: Change Universal Input 2 to a 0 to 10 V dc Input


1. Connect the DXM Controller to the PC.
2. Launch the DXM Configuration Tool software.
3. Connect to the DXM Controller by selecting the Device > Connection Settings menu option. You may connect using
either USB or Ethernet.
4. Select a COMM port from the drop-down list and click Connect.
5. Click on the Register View tab on the left part of the page.
6. Change the Source Register selection to I/O Board Registers.
7. Write a 3 to Modbus register 3326 on Modbus Slave ID 200 (I/O board).
8. Cycle power to the device.
9. Using the Register View tab, read register 3326 to verify it is set to 3.

Example: Change Analog Output 1 to a 0 to 10 V dc Output


1. Connect the DXM Controller to the PC.
2. Launch the DXM Configuration Tool software.
3. Connect to the DXM Controller by selecting the Device > Connection Settings menu option. You may connect using
either USB or Ethernet.
4. Select a COMM port from the drop-down list and click Connect.
5. Click on the Register View tab on the left part of the page.
6. Change the Source Register selection to I/O Board Registers.
7. Set jumper 1 on the I/O base board to the 0 to 10 V position. Refer to the base board image for the analog output
jumper position.
8. Write a 3 to Modbus register 4008 on Modbus Slave ID 200 (I/O board).
9. Cycle power to the device.
10. Using the Register View tab, read register 4008 to verify it is set to 3.

6.6.2 NMOS Outputs


Pin NMOS Discrete Modbus Register Description Wiring
Outputs

22 4 504
Output
23 3 503

24 2 502 Less than 1 A maximum current at 30 V dc


ON-State Saturation: Less than 0.7 V at 20 mA
ON Condition: Less than 0.7 V
OFF Condition: Open
35 1 501

6.6.3 Analog (DAC) Outputs


The DXM100-B2 and S2 analog outputs are 0 to 10 V dc outputs and cannot be changed.

DXM100-B2 and S2 Models

Pin Analog Modbus Description


Output Register

20 1 509 0 to 10 V dc output
Accuracy: 0.1% of full scale +0.01% per C
19 2 510 Resolution: 12-bit

Parameters for Analog Output 1 start at 4001 through 4008. Parameters for Analog Output 2 start at 4021 through 4028.

www.bannerengineering.com - Tel: 763.544.3164 47


DXM100-Bx Wireless Controller Instruction Manual

Parameter Registers for Analog Outputs (4xxxx)

OUT 1 OUT 2 Parameters

4001 4021 Maximum Analog Value

4002 4022 Minimum Analog Value

4003 4023 Enable Register Full Scale

4004 4024 Hold Last State Enable

4005 4025 Default Output State

Default Output Conditions. Default output conditions/triggers are the conditions that drive outputs to defined states.
Example default output conditions include when radios are out of sync, when a device cycles power, or during a host
communication timeout.
2952 Enable Default Communication Timeout. A communication timeout" refers to the communication
between any Modbus master host and the DXM baseboard. Set this register to 1 to enable the default condition
when the host has not communicated with the DXM baseboard for the period of time defined by the Communication
Default IO Timeout.
2953 Communication Default I/O Timeout (100 ms/Count). This parameter defines the host timeout period
in 100 millisecond increments. If a host does not communicate within this timeout period, the device outputs are
set to the default values.
2954 Enable Default on Power Up. Setting this parameter to 1 sends the device outputs to their default
condition when the DXM baseboard is powered up. Set to 0 to disable this feature.

Default Output State. The Default Output State parameter represents the default condition of the analog output. When
an error condition exists, the outputs are set to this 16-bit user-defined output state. To define the error conditions for
device outputs, refer to the MultiHop default output parameters 2950-2954.
Enable Register Full Scale. Set to 1 to enable a linear range from 0 to 65535 for specified input range. For a 4 to 20 mA
output, a value of 0 represents 4 mA and 65535 represents 20 mA. Set this parameter to 0 to store readings in unit-
specific data. For example, the register data representing a 15.53 mA reading is 15530. For units of current (0 to 20 mA
outputs), values are stored as A (micro Amps) and voltage values are stored as mV (millivolts).
Hold Last State Enable. Set the Hold Last State to 1 to set the output to its last known value before the error occurred.
Set this parameter to 0 to disable the Hold Last State and use the Default Output State setting during an error condition.
Maximum Analog Value. The Maximum Analog Value register stores the maximum allowed analog value. The specific
units of measure apply to the register value. For example, the register may contain 20000, for 20 mA, or for a voltage
output the register may contain 8000, for 8 volts.
Minimum Analog Value. The Minimum Analog Value register stores the minimum allowed analog value. The specific units
of measure apply to register value. For example, the register may contain 4000, for 4 mA, or for a voltage output the
register may contain 2000, for 2 volts.

6.6.4 DC Latching Outputs


Pin DC Latching Outputs Modbus Register Description Wiring

9 D1A
507 Write a 1 to the output register to activate the DC
10 D1B
DA 2-wire
Latching output from A to B.
self-latching
11 D2A Write a 0 to the output register to deactivate the
508 DC Latching output form B to A. DB solenoid
12 D2B

6.6.5 SDI-12 Interface

The SDI-12 interface on the DXM100-B2 Wireless Controllers can support


up to five devices with twelve 32-bit register values each. The DXM100- serial D12
B2 SDI-12 interface can be configured to increase the number of registers
per device address for devices with large register sets. The factory default SDI-12 DXM100-B2
power P12 Controller
enables one SDI-12 device using device address 1 with up to nine device
registers with a SDI-12 command of "M!".
ground GND
The DXM100-B2 controller is configured by writing non-volatile Modbus
registers with configuration parameters. Read or write the device
configuration parameters using standard Modbus commands.

48 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

Basic SDI-12 Interface Parameters


Up to five devices/commands can be accessed using the SDI-12 interface. There are three parameters for each device/
command: Enable, Device Address, Device Command. For more information, refer to the SDI-12 Technical Notes.

Enable. Instructs the DXM Controller device to activate or deactivate the SDI-12 device. Write a 1 to enable, and write a 0
to disable. The factory default for device 1 is enabled; devices 2 through 5 are disabled.

Device Address. Each SDI-12 device must have a unique device address. This parameter is the ASCII code for the device
address. Valid device addresses are 09 and az that map to ASCII codes 4857 and 97122, respectively. The factory
default addresses are:
SDI-12 Device 0 uses ASCII code 48
SDI-12 Device 1 uses ASCII code 49
SDI-12 Device 2 uses ASCII code 50
SDI-12 Device 3 uses ASCII code 51
SDI-12 Device 4 uses ASCII code 52

Device Command The SDI-12 interface supports "M!" or "C!" commands. Use the Device Command parameter to define
which command to use for this device. The factory default is "M!" commands for all devices (value of 10 in the Modbus
register).

Supported M! Commands Supported C! Commands

SDI-12 Command Register Value SDI-12 Command Register Value

xM! 0 or 10 xC! 1 or 20

xM1! 11 xC1! 21

xM2! 12 xC2! 22

xM3! 13 xC3! 23

xM4! 14 xC4! 24

xM5! 15 xC5! 25

xM6! 16 xC6! 26

xM7! 17 xC7! 27

xM8! 18 xC8! 28

xM9! 19 xC9! 29

The Modbus configuration registers are listed. All registers are defined as Modbus holding registers. The factory default
values are shown in parentheses. All values are in decimal, unless noted otherwise.

Registers (Default Value)


Device/CMD Configuration
Enable Device Address Device Command

SDI-12 Device/CMD 1 1751 (1) 11001 (48) 7 11002 (10)

SDI-12 Device/CMD 2 1701 (0) 11201 (49) 11202 (10)

SDI-12 Device/CMD 3 1651 (0) 11401 (50) 11402 (10)

SDI-12 Device/CMD 4 1601 (0) 11601 (51) 11602 (10)

SDI-12 Device/CMD 5 1551 (0) 11801 (52) 11802 (10)

SDI-12 Device Result Registers


The result registers store all information received from the SDI-12 devices.

The registers are 16-bit registers and require two registers to store a 32-bit value. The factory default configuration
defines the result registers as 32-bit registers, floating point format, and the first nine result registers are enabled for use.
A host system reads the SDI-12 device data from these registers.

Result Registers Register 1 Register 2 Register 3 Register 4 Register 5 Register 6

SDI-12 Device/CMD 1 Result Upper 11101 11103 11105 11107 11109 11111

7 The default device addresses 48 through 52 are in ASCII.

www.bannerengineering.com - Tel: 763.544.3164 49


DXM100-Bx Wireless Controller Instruction Manual

Result Registers Register 1 Register 2 Register 3 Register 4 Register 5 Register 6

SDI-12 Device/CMD 1 Result Lower 11102 11104 11106 11108 11110 11112

SDI-12 Device/CMD 2 Result Upper 11301 11303 11305 11307 11309 11311

SDI-12 Device/CMD 2 Result Lower 11302 11304 11306 11308 11310 11312

SDI-12 Device/CMD 3 Result Upper 11501 11503 11505 11507 11509 11511

SDI-12 Device/CMD 3 Result Lower 11502 11504 11506 11508 11510 11512

SDI-12 Device/CMD 4 Result Upper 11701 11703 11705 11707 11709 11711

SDI-12 Device/CMD 4 Result Lower 11702 11704 11706 11708 11710 11712

SDI-12 Device/CMD 5 Result Upper 11901 11903 11905 11907 11909 11911

SDI-12 Device/CMD 5 Result Lower 11902 11904 11906 11908 11910 11912

Result Registers Register 7 Register 8 Register 9 Register 10 Register 11 Register 12

SDI-12 Device/CMD 1 Result Upper 11113 11115 11117 11119 11121 11123

SDI-12 Device/CMD 1 Result Lower 11114 11116 11118 11120 11122 11124

SDI-12 Device/CMD 2 Result Upper 11313 11315 11317 11319 11321 11323

SDI-12 Device/CMD 2 Result Lower 11314 11316 11318 11320 11322 11324

SDI-12 Device/CMD 3 Result Upper 11513 11515 11517 11519 11521 11523

SDI-12 Device/CMD 3 Result Lower 11514 11516 11518 11520 11522 11524

SDI-12 Device/CMD 4 Result Upper 11713 11715 11717 11719 11721 11723

SDI-12 Device/CMD 4 Result Lower 11714 11716 11718 11720 11722 11724

SDI-12 Device/CMD 5 Result Upper 11913 11915 11917 11919 11921 11923

SDI-12 Device/CMD 5 Result Lower 11914 11916 11918 11920 11922 11924

SDI-12 Device Settings


The following are generic sampling, power and warmup parameters that should work for all SDI-12 devices. See the tested
device table below. In most cases, parameters will not need to be adjusted but if needed there are three common SDI-12
device parameters that control the communications and power of the SDI-12 device. Contact Banner Engineering Corp
support for more guidance.
Sample Rate. Formed using two 16-bit parameters, a HI word and a LOW word. The sample rate is how often the
SDI-12 device is powered up, then interrogated for data. The value in the registers is the number of 0.010 second
counts. For example, the default value is 22,500, which calculates to a sample rate of 22500 0.010 seconds.
Adjusting this value affects the battery life.
Warmup time. Amount of time to wait, in 0.010 second increments, from powering on the device to the time to
send communications to the device. The default value is 50, or 50 0.010 seconds. Adjusting this value affects the
battery life.
Voltage. The default voltage setting is 6 volts or a register value of 168. Adjusting this value affects the battery
life.

Registers (Default Value)

Switch
Device Device Sample Sample Warmup
Device / Cmd Configuration Enable Power Voltage
Address Command Hi Low Time
Enable

1753
SDI-12 Device/CMD 1 1751 (1) 11001 (48) 8 1754 (1) 11002 (10) 1752 (0) 1755 (50) 1756 (148)
(22500)

1703
SDI-12 Device/CMD 2 1701 (0) 11201 (49) 1704 (0) 11202 (10) 1702 (0) 1705 (50) 1706 (148)
(22500)

1653
SDI-12 Device/CMD 3 1651 (0) 11401 (50) 1654 (0) 11402 (10) 1652 (0) 1655 (50) 1656 (148)
(22500)

1603
SDI-12 Device/CMD 4 1601 (0) 11601 (51) 1604 (0) 11602 (10) 1602 (0) 1605 (50) 1606 (148)
(22500)

1553
SDI-12 Device/CMD 5 1551 (0) 11801 (52) 1554 (0) 11802 (10) 1552 (0) 1555 (50) 1556 (148)
(22500)

8 The default device addresses 48 through 52 are in ASCII.

50 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

These SDI-12 probes have been tested and are functional with the factory default settings.

MFG Models Technical Note

Acclima SEN-SDI (TDT SDI-12 Soil Moisture Sensor) SDI-12 and the Acclima TDT SDI-12 Soil Moisture Probe

Adcon Telemetry HydraProbeII

AquaCheck Sub-surface Probe SDI-12 and the AquaCheck Sub-Surface Soil Moisture Probe

SDI-12 and the Decagon 5TE Soil Moisture Probe

Decagon MPS-2, MPS-6, 5TE, TS1, T8 SDI-12 and the Decagon GS3 Soil Moisture Probe

SDI-12 and the Decagon MPS-2 Soil Moisture Probe

HSTI HydraScout SDI-12 and the HydraScout HSTI Probe

Sentek EnviroSCAN SDI-12 and the Sentek EnviroScan Soil Moisture Probe

6.6.6 Modbus I/O Registers for the DXM100-B2 I/O Base Board
The I/O base board stores the input and output values in Modbus holding registers. Since the I/O base board is defined as
a separate device, configure the DXM Controller to read or write the values on the I/O base board.

Base Board Input Connection

Modbus Register Range Description

1 065535 Universal input 1

2 065535 Universal input 2

3 065535 Universal input 3

4 065535 Universal input 4

Universal Input Register Ranges

Register Types Unit Minimum Value Maximum Value

Discrete input/output 0 1

Universal input 0 to 10 V mV 0 10000 *

Universal input 0 to 20 mA A 0 20000 *

Universal input temperature (40 C to +85 C) C or F, signed, in tenths of a degree 400 850

Universal potentiometer unsigned 0 65535

* Setting Enable Full Scale to 1 sets the ranges to a linear scale of 0 to 65535.

DXM100-B2 Controller Base Board Output Connection

Modbus Register Range Description

501 01 NMOS Output 1

502 01 NMOS Output 2

503 01 NMOS Output 3

504 01 NMOS Output 4

505 01 Switched Power 1 (5 V to 24 V)

506 01 Switched Power 2 (5 V to 24 V)

507 01 DC Latching Output 1

508 01 DC Latching Output 2

509 010000 Analog Output 1 (0-10.000 V)

510 010000 Analog Output 2 (0-10.000 V)

Modbus Configuration Registers for the I/O


Each input or output on the I/O base board has associated Modbus registers that configure its operation.

www.bannerengineering.com - Tel: 763.544.3164 51


DXM100-Bx Wireless Controller Instruction Manual

Universal Input Parameters Registers

Universal Inputs 1 2 3 4

Enable Full Scale Registers 3303 3323 3343 3363

Temperature C/F Registers 3304 3324 3344 3364

Input Type Registers 3306 3326 3346 3366

Threshold Registers 3308 3328 3348 3368

Hysteresis Registers 3309 3329 3349 3369

Enable Rising Registers 4908 4928 4948 4968

Enable Falling Registers 4909 4929 4949 4969

High Register for Counter Registers 4910 4930 4950 4970

Low Register for Counter Registers 4911 4931 4951 4971

Enable Full Scale


Set to 1 to enable a linear range from 0 to 65535 for specified input range. For a 4 to 20 mA input, a value of 0
represents 4 mA and 65535 represents 20 mA. Set this parameter to 0 to store input readings in unit-specific
data. For example, the register data representing a 15.53 mA reading is 15530. For units of current (0 to 20 mA
inputs), values are stored as A (micro Amps) and voltage values are stored as mV (millivolts).
Enable Rising/Falling
Use these registers to enable the universal input logic to count on a rising transition or a falling transition. Write a
one (1) to enable; write a zero (0) to disable.
High/Low Register for Counter
The low and high registers for the counter hold the 32-bit counter value. To erase the counter, write zeroes to
both registers. To preset a counter value, write that value to the appropriate register.
Hysteresis and Threshold
Threshold and hysteresis work together to establish the ON and OFF points of an analog input. The threshold
defines a trigger point or reporting threshold (ON point) for a sensor input. Setting a threshold establishes an ON
point. Hysteresis defines how far below the threshold the analog input is required to be before the input is
considered OFF. A typical hysteresis value is 10% to 20% of the units range.

ON point
In the example shown graphically, the input is considered on at
15 mA. To consider the input off at 13 mA, set the hysteresis to
Input Value

Threshold 2 mA. The input will be considered off when the value is 2 mA
Hysteresis
less than the threshold.

Input
OFF point

Time

Input Type
Program the universal inputs to accept input types NPN, PNP, 10k thermistor, 0 to 10 V, 0 to 20 mA, or
potentiometer. The default setting is 8: NPN raw fast. To set the input type, write the following values to the Input
Type Modbus registers.
0 = NPN
1 = PNP
2 = 0 to 20 mA
3 = 0 to 10 V dc
4 = 10k Thermistor
5 = Potentiometer Sense (DXM150 only)
6 = Not used
7 = Bridge
8 = NPN Raw Fast (default)
Temperature C/F
Set to 1 to represent temperature units in degrees Fahrenheit, and set to 0 (default) to represent temperature
units in degrees Celsius.

52 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

Modbus Configuration Registers for Power


To monitor the input power characteristics of the DXM Controller, read the following power Modbus registers. The on-board
thermistor is not calibrated, but can be used as a non-precision temperature input.

Modbus Register Description

6071 Battery backup charging algorithm.


0 = Battery is recharged from a solar panel
1 = Battery is recharged from 12 to 30 V dc . (default)

6081 Battery voltage (mV)

6082 Battery charging current (mA)

6083 Incoming supply voltage (mV) (solar or power supply)

6084 On-board thermistor temperature (C)

6.7 Restoring Factory Default Settings


To reset to factory defaults, write to two Modbus registers in the I/O board. The default slave ID for the I/O board is 200.

To reset the DXM I/O board parameters:


1. Write a 1 to Modbus register 4152
2. Write a 10 to Modbus register 4151
To reset only the I/O board:
1. Write a 0 to Modbus register 4152
2. Write a 10 to Modbus register 4151

Modbus Register Values Description

4151 0255 Reset/restore trigger. This timer is based in 100 millisecond units. Once written, the timer starts to count down to
zero. After the timer expires, the restore factory defaults are applied if register 4152 = 1. If register 4152 is zero,
the I/O board is reset.

Default value: 0

1 = 100 milliseconds, 10 = 1 second.

4152 01 1 = Restores factory defaults for I/O parameters.


Default value: 0

6.8 Setting the Modbus Slave ID on the I/O Base Board


Only DXM100-S1 and -S1R2 Slave models require that the Modbus Slave ID to be adjusted on the I/O base board. The
DXM100-Bx Wireless Controller models use DIP switches J and K to set the Modbus Slave ID. This device can use a
Modbus register 6804 in the I/O board to access the full range of Modbus Slave IDs.
On the DXM100-Bx Wireless Controller models, use the DIP switches at location K to define the lower digit of the Modbus
Slave ID.

DIP Switch location J defines the course group of Modbus Slave IDs. DIP Switch 4 must be set to ON for DXM100-S1,
DXM100-S2, DXM100-S1R2, and DXM100-S2R2 models.

Location J DIP Switches


Settings
1 2 3 4

Modbus Slave ID set to 11 through 19 OFF OFF

Modbus Slave ID set to 20 through 29 ON OFF

Modbus Slave ID set to 30 through 39 OFF ON

Modbus Slave ID set to 40 through 49 ON ON

Not Used -

Modbus Slave Configuration (DX100-S1 and -S1R2 models only) 9 ON

9 Must be in the ON position for the -S1 and -S1R2 model)

www.bannerengineering.com - Tel: 763.544.3164 53


DXM100-Bx Wireless Controller Instruction Manual

Location J DIP Switches


Settings
1 2 3 4

Standard Communication Mode OFF

DIP Switches J DIP Switch K, Switches 1, 2, 3, 4 (0 is OFF, 1 is ON)

1 2 0,0,0,0 1,0,0,0 0,1,0,0 1,1,0,0 0,0,1,0 1,0,1,0 0,1,1,0 1,1,1,0 0,0,0,1 1,0,0,1

OFF OFF x 10 11 12 13 14 15 16 17 18 19

ON OFF 20 21 22 23 24 25 26 27 28 29

OFF ON 30 31 32 33 34 35 36 37 38 39

ON ON 40 41 42 43 44 45 46 47 48 49

DXM100-Bx Wireless Controller ExampleTo set the DXM100-Bx Wireless Controller to a Modbus Slave ID of 34, set
the following:
Location J DIP switches set to 1=OFF, 2=ON
Location K DIP switches set to 1=OFF, 2=OFF, 3=ON, 4=OFF

The location J DIP switches set the upper Modbus Slave ID digit to 3 while the location K DIP switches set the lower digit to
4.

Setting the DXM I/O Board Modbus Slave ID using Modbus RegistersWrite to the I/O board's Modbus register
6804 to set the Modbus Slave ID to any valid Modbus Slave ID (1 through 245).
For the DXM100-Bx Wireless Controller model, all switches on DIP switch K should be in the OFF position to use the
Modbus register slave ID.

10 Uses value in Modbus register 6804.

54 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

7 Cellular CDMA
7.1 Cellular Modem Board
The optional cellular modem is installed on the SAM4 processor
board on the two 12-pin sockets. The U.FL connector should be to
the left, with the antenna cable going to the left antenna U.FL
connector.

7.2 Cellular Power Requirements


If the incoming voltage drops below 11.2 V dc, the cellular modem does not turn on and will not turn on until the voltage is
above 11.8 V dc. A text file (CmVMon.txt) on the internal micro SD card saves the periodic sampling of the incoming
voltage. If cellular operation stops because of voltage, it is logged in this file.
There are four LED indicators that give the run/fault status for the DXM Controller. To view the processor board, open the
housing top cover. Refer to SAM4 Processor Board on page 15 for LED locations. The four processor board LEDs indicate
the following conditions:
LED 1Heartbeat; indicates the processor is running.
LED 2Indicates the cellular modem power cutoff is active. If the incoming power is less than 11.2 V, the cellular
modem is powered down.
LED 3XML configuration file was rejected.
LED 4ScriptBasic program failed to load.

7.3 DXM Cellular Modem


The DXM cellular modem provides a remote network connectivity solution for the DXM Controller.
To use the cellular modem, first configure the DXM Controller to use the cellular network as the external network
connection. Verify the cellular modem is installed and the correct antenna is connected to the cellular antenna port.

7.3.1 Configure the DXM Controller for a Cellular Modem


Use the DXM Configuration Tool to create a configuration using a cellular connection. Under Settings > Cloud Services,
define the Network Interface as Cell to have all push data, SMS messages, or email alerts to be sent using the cellular
modem. The Cloud Push settings and the Webserver settings are required if the DXM Controller is sending data to a
webserver.

www.bannerengineering.com - Tel: 763.544.3164 55


DXM100-Bx Wireless Controller Instruction Manual

When the DXM Controller is configured to use the cellular modem, the information on the cellular modem is found on the
LCD menu under System Info > Cell. The menu does not display values until a transaction with the wireless cell tower is
complete. If there are no webserver parameters defined, the user must force a push to retrieve the data from the cellular
network. On the LCD menu, select Push > Trigger Data Push.
FW
Firewall IP address setting for VPN connection. The user enters the IP address of the host system on the other end
of the VPN connection.
Mask
IP mask associated to the firewall IP address.
MEID
Mobile Equipment Identifiera unique number for each cellular modem; this is the number the wireless carrier
uses to attach a wireless plan.
MDN
Mobile Device Numberphone number.
Signal
Signal Strength between the cellular modem and the wireless network tower; this value ranges between 51 and
112 dBm. The more positive number is better, 51 is better than 81.
Version
Firmware version of the cellular modem; this can only be updated at the factory.

7.3.2 Cellular Activation Quick Start Guide


Sensonix CDMA cellular modems (based on the Telit CE910-DUAL) are ready to be activated when they leave the factory.
Successful activation of every device on the cellular network requires two basic steps:
1. Attaching a data plan to the particular device
2. Completing Over-the-Air Service Provisioning (OTASP)

To attach a cellular data plan:


1. Select a data plan with a carrier that uses the Verizon network, working with Verizon directly or using an MVNO
such as M2MAir or KORE Telematics.
2. Set up an account with the selected carrier.
3. When working with cellular devices you may be required to log into a web portal provided by the carrier and follow
their instructions for device activation.
4. It is very important to make sure the carrier knows that the data plan is being attached to the device known as
SENSX001.
5. Remove the DXM100 housing cover to see the cellular modem. Use the MEID printed on the Telit CE910-DUAL
cellular modem to uniquely identify the device. The carrier requires this number to attach a monthly data plan.

To complete the Over-the-Air Provisioning (OTASP):

56 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

1. Once the contract is attached, the DXM Controller must provision the service using OTASP (Over-the-Air Service
Provisioning).
2. Make sure the cellular module is plugged into the DXM Controller and has its antenna properly connected.
3. On the DXM Controller LCD display select menu: System and then Provision Cell.
4. Click Enter on the Provision Cell menu.
5. The next screen will ask if you want to provision the cellular device, click Enter.
6. It will take approximately 60 seconds and will indicate when it has completed.
7. The cellular modem is ready for use.

7.3.3 DXM Cellular VPN Setup


A software VPN tunnel can be created between a DXM Controller using a cellular modem to a host PC using a private IP or
static wireless cellular plan. The instructions below outline the DXM Controller set up required to become aware of the VPN
connection. The cellular plan provider will have separate instructions for setting up the VPN on the PC side.

1. Establish VPN tunnel on your computer. Instructions should be provided from your VPN provider.
2. From within the DXM Configuration Tool, go to Settings > Network > Cellular Firewall Settings..
3. Fill in the Firewall IP address and Firewall netmask provided by your VPN provider. For M2Mair this was
included in the Routes.cmd file. It opens the device to traffic from 172.16.1.[0-255].
4. Go to Settings > Cloud Services > Network Interface.
5. Select Cell from the drop-down list and select the Enable VPN checkbox.
6. With your VPN tunnel open, select Device > Connection Settings.
7. Select TCP/IP, enter your VPN IP address, check VPN, and click Connect.

7.4 Accessing the DXM Using SMS


The DXM Controller with a cellular modem can be remotely accessed using SMS messages. Simple text messages can:
Force a push to the cloud
Reboot the controller
Read/write local registers
The incoming firewall provides security; only defined phone numbers are permitted to access the controller. Use the DXM
Configuration Tool to configure the SMS commanding feature. This feature requires firmware version 3.51 or later.
SMS command messages sent from approved phone numbers to the DXM Controller cause the DXM to respond. See the
examples below for SMS responses. Responses may take 20 seconds or more, depending upon the network.
A DXM Controller requires a few minutes after powering up before it can accept SMS messages. Initial cellular connection
times vary based on the wireless network. A SMS message sent to the controller while a push session is active delays any
response or the SMS message may be dropped based on the length of the push session.

7.4.1 HTTP Push


Push triggers a http push to a webserver. The DXM Controller accepts the message, executes the action, and sends an
acknowledgment text message back to the user.
Example: Texting push forces defined local registers to be sent to a webserver

push <send>

DXM Controller acknowledgment text message: Register push requested

7.4.2 Reboot
Reboot triggers the DXM Controller to reboot. The processor reloads the XML configuration file and zeroes all local register
data. This does not affect the other components of the DXM Controller (ISM radio, I/O board, cellular modem). The DXM
Controller accepts the message, executes the action, and sends an acknowledgment text message back to the user.

Example: Texting reboot forces the processor to reboot.

reboot <send>

DXM Controller acknowledgment text message: rebooting

7.4.3 Get Register


grN gets register number N (DXM Local Register) and sends a text with the value back to the user. The response text
message shows the value in floating point format regardless of register number.

Example: Text gr1 to retrieve the value for register 1.

www.bannerengineering.com - Tel: 763.544.3164 57


DXM100-Bx Wireless Controller Instruction Manual

gr1 <send>

DXM Controller acknowledgment text message: Register 1 is 0

7.4.4 Set Register


srN,X sets a register value, where N is the register number and X is the value. The DXM Controller responds with a SMS
message indicating the register was set.

Example: Texting sr1,10 sets register 1 to value of 10

sr1,10 <send>

DXM Controller acknowledgment text message: Register 1 has been set to 10

7.4.5 Configuring the DXM Controller for SMS Controlling


Configure the DXM Controller for SMS messaging capability using the DXM Configuration Tool.

1. On the Settings > Cloud Services screen, set the network interface to Cell.
2. On the Settings > Network screen, enter the phone numbers that are allowed access to the DXM Controller.
3. Save the configuration file (File > Save.
4. Load the XML file to the DXM Controller.
5. After the device has been running for a few minutes, the cellular network should be operational. The phone number
(MDN) is visible on the DXM LCD menu (System Info > Cell).
6. Send a text message to the DXM Controller from an approved phone number.

58 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

8 LCD and Menu System


The LCD has four user-defined LED indicators, four control buttons, and an LCD display. The four buttons control the menu
system on the LCD menu.

The top-level menu always displays the time in a 24-hour format.


The up and down arrows scroll through display items.
Banner Eng 08:25:45
The enter button selects the highlighted items on the display
Registers
Push S 08:25:15
ENTER
The back button returns to a previous menu option.

ISM Radio The left display column shows an arrow at the beginning of the line if
System the menu has submenus. The right column shows a vertical line with an
System Info BACK arrow at the bottom if the user can scroll down to see more menu
items.

8.1 Registers
The Registers submenu displays the processor's local registers that can be configured using the DXM Configuration Tool.

To configure these local registers, launch the DXM Configuration


Tool. Go to Local Registers and expand the view for a local register
by clicking on the down arrow next to the register number. In the Registers 08:25:45
LCD Permissions field, select None, Read, Write, or Read/Write.
-> 1 on/off:DoorAlarm5
-> 0 on/off: Door Switch5
2.13 mA: Tank Level
16.60 V: Solar Voltage In
450 mA: Solar Current In
13.28 V: Battery Voltage In

Read allows the register to be displayed, and Write or Read/Write allows the register value to be changed using the LCD.
The Units and Scaling parameters are optional and affect the LCD.

8.2 Push
The Push menu displays information about the last data sent to the Webserver.

The user can force an immediate push to the webserver using Trigger
Push. If a current push is in process it may take several minutes to
complete over cellular.
The Trigger Push submenu forces an immediate push to the web Push 08:25:45
server.
Trigger Data Push
The status and time fields indicate success or failure of the last Status : Success
attempted push and time of the last attempted push. Time : 09:25:15

www.bannerengineering.com - Tel: 763.544.3164 59


DXM100-Bx Wireless Controller Instruction Manual

8.3 ISM Radio


The ISM Radio menu allows the user to view the Modbus ID of the internal ISM radio, invoke binding, or run a site
survey. To change the ISM Radio Modbus ID refer to the System menu.

The top level menu includes a read-only ISM Radio menu selection. This
menu is displays the type of radio in the DXM Controller (MultiHop or DX80
Star) and the Modbus ID of the radio.
ISM Radio 08:25:45
This menu only allows the user to view this data. Binding or Site Survey with
the internal radio is also run from this menu selection. This top-level ISM
MultiHop ID: 4
-> Binding
Radio menu is different from the System > ISM Radio submenu.
-> Site Survey

Binding All ISM radio devices must be bound to the internal Gateway/master device before the DXM Controller can
access the wireless devices. The first submenu under binding allows the user to set the wireless address of the device to
bind with. This is required to bind with wireless devices that do not have rotary dials (for example: M-GAGEs, Ultrasonic
sensors, and Q45 devices).

To bind:
1. Enter the Binding menu. Binding 08:25:45
2. For devices without rotary dials, select the wireless device number.
Bind to > 1
3. Enter binding mode. The gateway/master radio enters binding mode.
4. Triple-click the wireless Node/slave device to put it into binding
mode. The LEDs indicate when binding on the wireless device is Change Device #
completed. <Ent> Start Binding
For more information of the binding of a particular device review the <Back> End Binding
individual datasheet.

Site Survey After creating a wireless network using the binding process, run a site survey on each device to see the link
quality.
1. Enter the Site Survey menu.
2. Select the Node or Slave ID for the end device.
3. Click Enter to run a site survey.

Site Survey 08:25:45


Node / Slave ID
> 1
Site Survey 08:25:45
Change Device #
<Ent> Run Site Survey Please Wait
<Back> Previous Menu Site Survey 08:25:45
Device #

Grn : 45 Ylw : 15
Red: 15 Miss: 25

<Back> Previous Menu

The Site Survey results display as green, yellow, red, and missed packets. Green indicates the highest signal strength,
then yellow, and red. MIssed packets failed to be received. The DX80 system can run a site survey analysis while the
network is operational. A MultiHop device runs with its parent device and does not allow other traffic when a site survey is
running.

60 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

8.4 System
Use the System menu to set DXM Controller system parameters.

System 08:25:45
ISM Radio
Ethernet
Provision Cell
DXM Slave ID: 255
Power: [dc / solar]
LCD Contrast: 28
Restart

8.4.1 ISM Radio


The internal ISM radio of the DXM Controller is set at the factory to be Modbus device address 1 (Modbus ID 1).

For some applications, you may need to change this ID. The best way to adjust the Modbus device address is by using the
LCD menu system of the DXM Controller. Any other method may cause issues with the DXM Controller not knowing which
Modbus device address is assigned to the radio, which causes issues with running Binding or Site Survey from the LCD
menu.
To setting the Modbus ID on the internal radio, select the System > ISM Radio menu. There are two options: Modbus
ID and Advanced Options.
Modbus IDSet the ISM Modbus ID to any number (1 through 247) not being used by the DXM system. Processor Local
Registers allocate ID 199, the I/O board is set to ID 200, and the display board is set to ID 201. With a DX80 Star
Gateway device, it's easy to choose a new ID. With a MultiHop network, remember that the master MultiHop radio
allocates a range of Modbus IDs for wireless devices, typically 11 through 110.
When setting the new ISM Modbus ID, the system changes the Modbus ID on the internal radio and changes the reference
to it on the DXM Controller. The reference Modbus ID is what the DXM Controller uses to access the internal radio when
running Binding or Site Survey.
Advanced Options The Advanced Options menu is typically not used unless the Modbus ID is changed without the DXM
Controller being involved, such as when you write directly to the radio Modbus registers.
If the internal Modbus ID of the radio was changed, but not recorded, use Auto Detect Radio to determine the radio ID.
The auto detect routine broadcasts discovery messages and waits for a response. If devices are connected to the external
RS-485 ports, they may need to be disconnected for this process to work properly.
Reference Type selects the radio type between DX80 Star architecture radios and a MultiHop radio. The DXM Controller
uses this reference to determine how to communicate to the internal radio. If set incorrectly, the DXM Controller may not
be able to run Site Survey from the LCD menu. Unless you are changing or adding the internal radio device there should
no reason to change the radio type.
The Reference Modbus ID defines the Modbus ID the DXM Controller uses when communicating with the internal radio.
If this is set incorrectly the DXM Controller will not be able to run Binding or Site Survey through the LCD menu.

8.4.2 Ethernet
Use the System > Ethernet menu to set the IP Address, Gateway Address, and Subnet mask of the DXM Controller's
Ethernet interface. You may change these settings either from the LCD menu (System > Ethernet) or from the XML
configuration file created by the DXM Configuration Tool.

The network address settings from the LCD menu have the highest priority and override settings in the XML configuration
file. To use the parameter settings from the XML configuration file or use DHCP, execute the Reset under System >
Ethernet or use the LCD display to set the IP Address, Gateway Address, and Subnet Mask to 255.255.255.255. Reboot
the DXM Controller after changing the Ethernet parameters.

The Ethernet cable should be attached before powering up the DXM Controller.

8.4.3 Provision Cell


If the DXM Controller has a cellular modem installed, the modem must be provisioned on the network. This menu will
provision the cellular modem on the network. For step by step directions, see DXM Cellular Modem on page 55.

www.bannerengineering.com - Tel: 763.544.3164 61


DXM100-Bx Wireless Controller Instruction Manual

8.4.4 DXM Slave ID


Use the secondary Modbus RS-485 port when the DXM Controller is connected to a Modbus RTU network as a Modbus
slave device. Set the Modbus ID for the secondary RS-485 port using the LCD display menu System > DXM Slave ID.

8.4.5 Power DC/Solar


The DC/Solar parameter selects the charging algorithm for batteries attached to the DXM Controller. The factory default
setting is DC.

Set the charging algorithm to Solar when the main power source is a solar panel and batteries. Set the battery charging
algorithm to DC when the main power source is line powered 1030 V dc and the attached batteries are used as backup
batteries. This setting can also be set by writing Modbus register 6071 of the I/O board. See Supplying Power from a Solar
Panel on page 23.

8.4.6 LCD Contrast


Use the LCD Contrast option to adjust the LCD contrast. Adjust the starting number lower to decrease the display contrast.
The factory default is 28. Do not set a number less than 14 or the display may not be bright enough to see to change
back.

8.4.7 Restart
Use Restart to force the main processor to restart. This does not affect the other boards in the system, I/O board, ISM
radio board, or Cellular modem.

8.5 System Info


Various DXM system settings are shown in this menu. The Push, Ethernet, and Cell parameters are helpful for debugging
network connections. This menu is a read only menu.

Cell
Shows the cellular MEID number (Mobil Equipment Identifier), MDN
(Mobil Device Number), version, signal, firewall setting, and firewall System Info 08:25:45
mask. Some of these parameters are not visible until the cellular
Controller
network is accessed. ISM Radio
Controller Push
Ethernet
Displays the date, build, model, and serial number. Cell
I/O Board
Ethernet LCD Board
Displays the IP address, MAC address, DHCP, Gateway address, and
DNS settings.
I/O Board
Displays the serial number, model, date, firmware part numbers, and
version numbers.
ISM Radio
Displays the serial number, model, date, firmware part numbers, and
version numbers.
LCD Board
Displays the serial number, model, date, firmware part numbers, and
version numbers.
Push
Shows the current parameters loaded from the XML configuration that
applies to pushing data to a webserver, including method (Ethernet or
cellular), interval, URL, page, HTTPS, and site ID.

62 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

8.6 Using the Display LEDs


Turn on the DXM Controller LEDs by writing to the LEDs' Modbus registers.

The DXM display uses Modbus slave ID 201 and has four individual
Display Modbus Display LED
registers for each of the four LEDs on the display. Register
Turn on an LED by writing a 1 value to the register. Turn off the LED by 1102: bit 0 LED 1 (Green)
writing a 0 to the register.
1103: bit 0 LED 2 (Red)
Do not write to any other Modbus registers. They are used by the LCD
1104: bit 0 LED 3 (Yellow)
display for menu data.
1105: bit 0 LED 4 (Red)

DXM Controller Display Example


This example shows setting up the DXM Controller using the DXM Configuration Tool to read four universal inputs and
write the state values to the display LEDs.
1. Using the DXM Configuration Tool, go to the Local Registers > Local Register Configuration screen.
2. Define the local registers by assigning names to the first four registers and setting the LCD permissions parameter
to read/write. The LCD permissions show the register contents on the LCD menu under the REGISTER menu. You
can also set the value from the LCD menu.

3. Create a Read Rule to read the four universal inputs from the I/O board (Modbus slave 200) and write the values in
local registers 1 through 4.

4. Create a Write Rule to write the four local register values to the DXM display registers 1102 through 1105 (Modbus
Slave 201). Define the Write Rule to only write the display registers when the inputs change.

www.bannerengineering.com - Tel: 763.544.3164 63


DXM100-Bx Wireless Controller Instruction Manual

5. Save the XML configuration from the File > Save As menu.
6. Connect to the DXM Controller using a USB cable and select Device > Connection Settings from the menu bar.
7. Upload the XML configuration file to the DXM Controller by selecting Device > Upload Configuration to Device
from the menu bar.

After a configuration file is uploaded, the DXM Controller reboots. The new configuration is now running.
Turning on any one of the universal inputs 1 through 4 on the I/O base board of the DXM Controller now turns on an LED
on the display.

On the DXM Controller's LCD menu, the arrow on the left side of the register line indicates this local register can be written
to. Try changing the configuration to delete the Read Rule then turn on/off the LEDs by changing the register value
through the LCD display.

8.7 Modbus Registers for the LCD Board (Modbus Slave ID 201)
Control the four user-defined LEDs using the display board's Modbus registers. Using write maps or ScriptBasic, write the
Modbus registers shown below with 0 (off) or 1 (on). The LCD display is Modbus Slave 201.

Modbus Register I/O Connection Modbus Register I/O Connection

1102 : bit 0 LED 1 1104 : bit 0 LED 3

1103 : bit 0 LED 2 1105 : bit 0 LED 4

64 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

9 Working with Modbus Devices


9.1 Overview
The DXM Controller has two physical RS-485 connections using Modbus RTU protocol.

The master Modbus RS-485 port is for the DXM Controller to act as a Modbus master device to control internal and
external Modbus slave devices.

The Modbus master RS-485 port is labeled M+ and M- on the DXM Controller. The Modbus slave port is used when another
Modbus master device wants to communicate with the DXM Controller when the DXM Controller is a Modbus slave device.

The Modbus slave RS-485 port is labeled S+ and S1 on the DXM Controller.

Ethernet
Processor Modbus
Control/Data
Modbus RS-485
(slave port)
Modbus RS-485
(master port)

External
Modbus
Local GW/MH Display I/O Base Slaves (2-10)
Registers Radio

Modbus Modbus Modbus Modbus


SID 199 SID 1 SID 201 SID 200

The DXM Controller has dual Modbus roles: a Modbus slave device and a Modbus master device. These run as separate
processes.
The Modbus slave port can only access the DXM Controller local registers. To operate as a Modbus slave device, the DXM
Controller needs to be assigned a unique Modbus slave ID as it pertains to the host Modbus network. This slave ID is
separate from the internal Modbus slave IDs the DXM Controller uses for its own Modbus network. The DXM Modbus slave
ID is defined through the LCD menu. Other Modbus slave port parameters are defined by using the DXM Configuration
Tool.
The DXM Controller operates the Modbus master port. Each device on the master port must be assigned a unique slave ID.
There are slave IDs that are reserved for internal devices in the DXM Controller.

DXM Internal Modbus Slave IDs (factory default)

Modbus Slave ID Device

1 Gateway (PE5) or MultiHop (HE5) ISM RadioMultiHop wireless devices connected to the internal MultiHop radio should
be assigned Modbus Slave addresses starting at 11.

199 Local RegistersInternal storage registers of the DXM Controller

200 I/O Base BoardAll data and parameters for each input or output of the DXM Controller.

201 LCD DisplayThe user has access to the LED indicators on the DXM Controller.

9.2 Assigning Modbus Slave IDs


Assign the DXM Modbus Slave ID only if a Modbus master device is reading or writing the DXM Controller Local Register
data through the Modbus RS-485 slave port (S+, S-).

Set the DXM Slave ID from the LCD menu under System > DXM Slave ID. The DXM Controller can have any unique slave
ID between 1 and 246, depending upon the host Modbus network. Other RS-485 slave port parameters are set in the DXM
Configuration Tool under the Settings > General tab.

DXM Master ConfigurationWhen the DXM Controller operates as a Modbus master device, use the DXM Configuration
Tool to configure read or write operations of the DXM Modbus network. The DXM Controller communicates with all internal
and external peripheral devices using the external Modbus bus RS-485 (M+, M-)

www.bannerengineering.com - Tel: 763.544.3164 65


DXM100-Bx Wireless Controller Instruction Manual

There are four internal Modbus slave devices that are configured from the factory with slave IDs. Assign slave IDs of 2
through 10 to Modbus slave devices that are physically wired to the DXM Controller. Assign slave IDs or 11 through 60 to
wireless slaves within the MultiHop network.

Do not assign a slave ID of greater than 10 to Modbus slave devices that are physically wired using the RS-485 port if
there is an internal MultiHop ISM radio in the DXM Controller. The MultiHop ISM radio attempts to send any Modbus data
intended for slaves 1160 across the radio network, which conflicts with wired slave devices if the slave IDs overlap. The
MultiHop master radio can be changed from the factory default of 1160 Modbus slave IDs if more hardwired slaves are
required.

9.3 Modbus Operation


All Modbus transactions are managed by a central Modbus engine. If there are Modbus messages intended for a Modbus
slave that doesn't exist, the Modbus engine waits for a response until the timeout period is expired. This slows down the
Modbus polling loop for read and write operations. For this reason, verify all Modbus read and write operations are
intended for Modbus slave devices that are in the network.

If a Modbus slave is not in the network, either a wired or wireless device, the operation of the LCD menu system can be
compromised. Operations like Binding, Site Survey, or accessing the ISM menu may be slower. This is because all internal
devices of the DXM Controller are also Modbus slaves, ISM radio, I/O base board, LCD, and internal Local registers.

9.4 Wireless and Wired Devices


Wireless DX80 GatewayThe DX80 Gateway architecture is a star architecture in which all Nodes in the system send
their data back to the Gateway. The host can access the entire network data from the Gateway, which is Modbus slave ID
1. Because the DXM Controller will not be sending any Modbus messages across the wireless link, the timeout parameter
can be set low (less than 1 second) and the device is treated like a directly connected device.
MultiHop MasterThe MultiHop master radio forms a wireless tree network using repeaters and slave devices. Each
device in a MultiHop network must be assigned a unique Modbus Slave ID and is accessed as a separate device.
For the DXM Controller to talk with a MultiHop device in the wireless network, the master MultiHop device interrogates
every message on the RS-485 bus. If they are within the wireless devices range (slave IDs 11 though 60), the message is
sent across the wireless network. To change this range, the user must adjust the offset and range setting in the MultiHop
master radio (Modbus Slave ID 1). Modbus register 6502 holds the Modbus offset, default 11. Modbus register 6503 holds
the number of Modbus slaves allowed (maximum of 100).

Modbus Slave ID Description

1 Allocated for the internal ISM radio device, either a DX80 Gateway or MultiHop Master

210 Slave addresses available for direct connected Modbus slave devices to the master RS485 port (M+ , M-)

1160 Allocated for wireless MultiHop radio network devices. If there is not an internal MultiHop in the DXM Controller, these slave
addresses are available to use for directly connected devices.

61198 Available to user for direct connected Modbus slave devices or the expansion of the wireless network slave IDs to go past 50
wireless devices.

199 Allocated for internal Local Register

200 Allocated for the I/O base board, will be different for special DXM slave only models.

201 Allocated for the LCD display board, the user can read/write LEDs.

9.5 Modbus Timeouts


A Modbus timeout is the amount of time a Modbus slave is given to return an acknowledgement of a message sent by the
Modbus master. If the Modbus master waits for the timeout period and no response is seen, the Modbus master considers
it a lost message and continues on to the next operation.

The timeout parameter is simple to set for Modbus devices directly connected to the DXM controller, if there are no
MultiHop wireless devices. If a MultiHop network a part of the DXM Controller, special considerations need to be made to
set the timeout parameter.

Wireless communications are inherently lossy networks, and controllers operating these networks must be configured to
allow for enough time for hardware transmission retries. Set the Communications Timeout parameter to cover the
expected time for messages to be sent throughout the wireless network. For the DXM Controller, the Communications
Timeout parameter is the maximum amount of time the DXM Controller should wait after a request is sent until the
response message is received from the Modbus slave device. Use the DXM Configuration Tool to set the timeout parameter
on the Settings > General screen.

66 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

The default setting for the timeout parameter is 5 seconds.

9.5.1 MultiHop Networks vs DX80 Star Networks


The DX80 star Gateway collects all the data from the Nodes, which allows the host system to directly read the data from
the Gateway without sending messages across the wireless network. This allows for DX80 Gateway to be treated like any
other wired Modbus device.

In a MultiHop network, the data resides at each device, forcing the controller to send messages across the wireless
network to access the data. For this reason, carefully consider the value of the wireless timeout parameter.

9.5.2 MultiHop Radios Powered by Battery


Battery-powered MultiHop radios are configured to run efficiently to maximize battery life. By optimizing battery life, the
allowed communications window for receive messages is slow (once per 1.3 seconds) and sending message rates are
standard (once per 0.04 seconds).

A MultiHop device is set from the factory with the retry parameter set to 8. This means that under worst-case conditions, a
message is sent from the DXM Controller to an end device a total of nine times (one initial message and eight retry
messages. The end device sends the acknowledgment message back to the DXM Controller a maximum of nine times (one
initial message and eight retries). A single Modbus transaction may send up to two messages + 16 retry messages before
the transaction is complete. In addition, the radios randomly wait 01 time period before retransmitting a retry message.
So to allow for the random wait time, add one extra time period for each in-between time of retries.

For a Master radio to a slave radio (no repeaters):


Master to Slave Send time = (9 1.3 sec) + (8 retry wait 1.3 sec) = 22 seconds
Slave to Master Send time = (9 0.04 sec) + (8 retry wait 0.04 sec) = 1 second
Total Send/Receive time = 23 seconds
Minimum Timeout period = 23 seconds
This calculates the maximum timeout value for a wireless transaction. If the link quality of the network is poor, the
maximum transfer times may happen. Set the timeout parameter to accommodate the maximum number of retries that
may happen in your application.
When MultiHop repeaters are added into the wireless network, each additional level of hierarchical network increases the
required timeout period. Since MultiHop repeaters are running at the highest communications rate, the overall affect is not
as great.
Master to Repeater Send time = (9 0.04 sec) + (8 retry wait 0.04 sec) = 1 second
Repeater to Master Send time = (9 0.04 sec) + (8 retry wait 0.04 sec) = 1 second
Additional Timeout period for a repeater = 2 seconds
Using the timeout calculation above of 23 seconds, if a repeater is added to the network the timeout should be set to 25
seconds. For each additional MultiHop repeater device creating another level of network hierarchy, add an additional two
seconds to the timeout period.

9.5.3 MultiHop Radios Powered by 10-30 V DC


Line-powered (1030 V dc) MultiHop devices operate at the maximum communication rate, resulting in a much lower
timeout parameter setting. For each repeater added to the network, increase the timeout parameter 2 seconds.
For a Master radio to a 1030 V dc powered slave radio (no repeaters):
Master to Slave Send time = (9 0.04 sec) + (8 retry wait 0.04 sec) = 1 second
Slave to Master Send time = (9 * 0.04 sec) + (8 retry wait 0.04 sec) = 1 second
Total Send/Receive time = 2 seconds
Minimum Timeout period = 2 seconds

9.5.4 Adjusting the Receive Slots and Retry Count Parameters


The number of receive slots governs how often a MultiHop device can communicate on the wireless network.

Battery-powered devices typically have DIP switches that allow the user to set the number of receive slots. (This will
directly affect the battery life of the device.) Adjusting the receive slots changes how often a message can be received. In
the battery power example (default factory settings) the receive slots are 1.3 seconds (receive slots = 4). With the receive
slots set to 32, how often a message can be received goes from 1.3 seconds down to 0.16 seconds.

An argument can be made to allow the application accessing the wireless network, in this case the DXM Controller, to
control the retry mechanism. The number of retries can be adjusted in the MultiHop devices by writing Modbus register
6012 to the number of retires desired. The factory default setting is eight.

www.bannerengineering.com - Tel: 763.544.3164 67


DXM100-Bx Wireless Controller Instruction Manual

9.5.5 DX80 Star Architecture Network Timeouts


In the DX80 network, all Node data is automatically collected at the Gateway to be read. The DXM Controller does not use
the wireless network to access the data, which allows for much faster messaging and much lower timeout values.

For a DXM Controller with an internal DX80 Gateway, set the timeout value 0.5 seconds. If other Modbus slave devices are
connected to the RS-485 lines, the timeout parameter will govern all communication transactions and must be set to
accommodate all devices on the bus.

68 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

10 Configuration Instructions
10.1 Scheduler
Use the Scheduler screen to create a calendar schedule for local register changes, including defining the days of the
week, start time, stop time, and register values. Schedules are stored in the XML configuration file, which is loaded to the
DXM Controller. Reboot the DXM Controller to activate a new schedule.

10.1.1 Creating a Weekly Schedule


Use the Weekly Events screen to define weekly events.

To create a new rule:


1. Click Add New Rule.
2. Click on the arrow to the left of the new rule to expand the parameters into view.
3. Enter the local register.
4. Select the days of the week this rule applies to.
5. Use the drop-down list to select the type of Start At time: a specific time or a relative time.
6. Enter the starting time.
7. Enter the starting value for the local register.
8. Enter the end time and end value for the local register.
Register updates can be changed up to two times per day for each rule. Each rule can be set for any number of days in the
week by clicking the buttons M, T, W, Th, F, S, or Su.
If two register changes are defined for a day, define the start time to be before the end time. Select End Value to enable
the second event in a 24 hour period. To span across two days (crossing the midnight boundary), set the start value in the
first day, without selecting End Value. Use the next day to create the final register state.
Start and end times can be specified relative to sunrise and sunset, or set to a specific time within a 24 hour period. When
using sunrise or sunset times, set the GPS coordinates on the device so it can calculate sunrise and sunset.

10.1.2 Defining One-Time Events


Define one-time events to update registers at any time within a calendar year. Similar to Weekly events, the times can be
specific or relative to sunrise or sunset. Define one-time events using the one-time events screen.

To create a one-time event rule:

www.bannerengineering.com - Tel: 763.544.3164 69


DXM100-Bx Wireless Controller Instruction Manual

1. Click on Add One Time Event.


2. Name your one-time event by clicking on the name link and entering a name.
3. Click on the arrow to expand the parameters into view.
4. Enter the local register.
5. Enter the starting time, date, and starting value for the local register.
6. Enter the ending time, date, and ending value for the local register.

10.1.3 Creating a Holiday Schedule


Use the Create Holidays screen to create exception conditions that alter the standard scheduled register changes.

To create a holiday:
1. Click on Add New Rule.
2. Name your new holiday by clicking on the name link and entering a name.
3. Select the start date and time for the new holiday.
4. Select the stop date and time for the new holiday.

10.1.4 Cycling Power During Schedules


If power is cycled to the DXM Controller in the middle of a schedule, the DXM Controller looks at all events scheduled that
day and processes the last event before the current time.

10.2 Authentication Setup


The DXM Controller has three different areas that can be configured to require a login and password authentication.
Webserver/ Cloud Services Authentication
Mail Server Authentication
DXM Configuration Authentication
The webserver and mail server authentication depends upon the service provider.

10.2.1 Cloud and Webserver Services Authentication


The DXM Controller can be configured to send login and password credentials for every HTTP packet sent to the webserver.
This provides another layer of security for the webserver data.

Setup requires both the webserver and the DXM Controller to be given the same credentials for the login and password.
The webserver authentication username and password are not stored in the XML configuration file and must be stored in
the DXM Controller.

Define the login and password using the Settings > Cloud Services screen
of the DXM Configuration Tool, in the Webserver Authentication section
of the screen.

The first time you select Require Authentication, a pop-up box appears
with additional instructions. Since the data is not stored in the XML
configuration file, it is hidden from view of the DXM Configuration Tool.

70 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

After enter the username and password, click on Send Authentication to transmit the data directly to the DXM
Controller's non-volatile memory. The controller must be connected to the PC for this operation to succeed. If successful, a
pop-up window appears, asking to reboot the device. Select Yes to reboot the device.

Set up the webserver with a username and password to accept the DXM
Controller messages. Otherwise, the webserver ignores all messages.

When using the Sensonix website's dashboard, set the authentication by


clicking the edit button next to the appropriate site name. Enter the
Username and Password, then click Save to save your changes.

10.2.2 Mail Server Authentication


Complete the mail server settings to have the DXM Controller send email alert messages or to email the log files.

The SMTP password is stored in the DXM Controller, not the XML configuration file. Use the Settings > Mail and
Messaging screen to complete this configuration.

After selecting Enable SMTP Authentication for the first time, a pop-up box appears with additional instructions to
complete the mail server authentication process.
After entering the user name and password, click on Send SMTP Password to save the user name and password to the
DXM Controller. The DXM Controller must be connected to the PC to complete this operation. If successful, a pop-up
window appears, asking to reboot the device. Select Yes to reboot the device.

10.2.3 DXM Controller Configuration Authentication


The DXM Controller can be programmed to allow changes to the configuration files only with proper authentication by
setting up a password on the Settings > Administration screen in the DXM Configuration Tool.
With the DXM Controller connected to the PC, click Get Device Status. The DXM Controller status displays next to the
button.

www.bannerengineering.com - Tel: 763.544.3164 71


DXM100-Bx Wireless Controller Instruction Manual

Use the DXM Configuration Tool to:


Set the Admin Password
Change the Admin Password
Remove the Admin Password
To change or remove an admin password, the current password must be supplied. The DXM Controller must be connected
to the PC to change the administration password.
The DXM Controller can be unlocked without knowing the administration password, but doing this erases the configuration
program, logging files, and any ScriptBasic program on the device.
To unlock the hardware without knowing the administration password:
1. Turn off the power to the DXM Controller.
2. Open the controller top to access the button and DIP switches of the SAM4 processor board.
3. Turn on DIP switch 4 (next to the SD card holder).
4. Press and hold the reset button (next to the USB jack) while applying power to the DXM Controller.
5. Release the reset button.
6. After five seconds, turn off the power.
7. Turn off DIP Switch 4.
8. Install the DXM cover and apply power.
The device no longer has an administration password set.

10.3 Register Flow and Configuration


The DXM Controller register data flow goes through the Local Registers, which are data storage elements that reside within
the processor. Using the DXM Configuration Tool, the controller can be programmed to move register data from the Local
Register pool to remote devices, the internal radio, the I/O base, or the display.

72 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

Processor

Local
Ethernet/USB/Cellular Registers Remote Devices

Display I/O Base Internal


Radio

10.3.1 Basic Approach to Configuration


When programming an application in the DXM Controller, the first step is to plan the overall data structure of the Local
Registers.
The Local Registers are the main storage elements in the DXM Controller. Everything goes into or out of the Local
Registers. Start by naming the Local Registers in the application as this helps to provide the beginning structure of the
application.
After you have a basic idea what data values to store, configure the read/write rules to move the data. The Read/Write
rules are simple rules that move data between devices and the Local Registers.
Most applications require the ability to manipulate the Local Register data, not just move data around. Use the Action rules
to make decisions or transform the data after the data is in the Local Registers. Action rules can apply many different
functions to the Local Register data, including conditional statements, math operations, copy operations, or trending.
To perform scheduled events in Local Registers, look under the Scheduler tab in the DXM Configuration Tool. These rules
provide the ability to create register events by days of the week. The scheduler can also create events based on sunrise or
sunset.

10.3.2 Troubleshooting a Configuration


The built-in Register View utility is found in the DXM Configuration Tool on the Register View screen.
When a configuration is running on the DXM Controller, this utility can read or write Local Registers to help understand
application operation. The utility can also access data from remote devices, making it easier to troubleshoot a
configuration.
Local Registers can also be configured to show register data on the LCD menu to view Local Register data without having
the controller connected to a PC. On the Local Registers tab, set the read permissions on each register to be display on
the LCD.

10.3.3 Saving and Loading Configuration Files


The DXM Configuration Tool saves its configuration information in a XML file. Use the File menu to Save or Load
configuration files.

Save the configuration file before attempting to upload the configuration to the DXM Controller. The DXM Configuration
Tool uploads the configuration file saved on the PC to the DXM Controller; it will not send the configuration loaded in the
tool.

10.3.4 Uploading or Downloading Configuration Files


The DXM Controller requires a XML configuration file to become operational. To upload or download configuration files,
connect a computer to the DXM Controller using the USB port or Ethernet port. Then use the Upload Configuration to
Device or Download Configuration from Device under the Device menu.

www.bannerengineering.com - Tel: 763.544.3164 73


DXM100-Bx Wireless Controller Instruction Manual

10.4 Setting Up EtherNet/IP


The DXM Controller is defined from the factory to send/receive register data from the Gateway and the first 16 Nodes with
an EtherNet/IP11 host. To expand the number devices going to Ethernet/IP the user must change the Maximum Node
count parameter in the DX80 Gateway from 16 to 32. Use the DX80 Configuration Tool to set this parameter.

This allows the user to maximize the use of the EtherNet/IP buffer to 28 devices. To expand the number of devices further,
customize the data collection for EtherNet/IP using the DXM Configuration Tool and only selecting the needed registers. A
maximum of 228 registers can be read or written with Ethernet/IP.

EDS (Electronic Data Sheet) files allow users of the EtherNet/IP protocol to easily add a Banner DXM device. Download the
EDS files from the Banner website.

10.4.1 Configuring the Host PLC


On the host PLC, install the DXM Controller using an EDS file or by using the following parameters:
Assembly1: Originator to DXM = Instance 112, 456 bytes (228 words)
Assembly2: DXM to Originator = Instance 100, 456 bytes (228 words)

The Originator is the host PLC system, and the DXM is the DXM Controller. The host system sees the DXM Controller as a
generic device with the product name of Banner DXM (ProdType: 43 - Generic Device, ProdName: Banner DXM).

10.4.2 Configuring the DXM Controller


Use the DXM Configuration Tool to define each local register to be Originator -> DXM or as a DXM -> Originator.
Define a DXM local register as Originator -> DXM when the host PLC (Originator) will send data to the DXM
Controller local register (DXM).
Define a DXM local register as DXM -> Originator when that register data will be sent from the DXM Controller
(DXM) to the host PLC (Originator).
Data from an EIP controller in assembly instance 112 is data destined for the DXM Controller local registers. The first two
bytes of the assembly instance are stored in the first local register defined as an Originator -> DXM register. The next
two bytes of the assembly instance are stored in the next local register defined as an Originator -> DXM register. For
example, if DXM local registers 5, 12, 13, and 15 are configured as Originator -> DXM, the first eight bytes (four words)
of data from the assembly instance are stored into these registers in order (5, 12, 13, and 15). The system ignores the
rest of the bytes in the assembly instance.
Data from the DXM Controller local registers is sent to the EIP controller using assembly instance 100. Each local register
in the DXM Controller defined as DXM -> Originator is collected in numerical order and placed into the data buffer
destined for assembly instance 100. DXM local registers are capable of 32-bits, but only the lower 2-bytes for each local
register are transferred. For example, if DXM registers 1, 10, 20, and 21 are defined as DXM -> Originator registers, the
assembly instance 100 will have the first eight bytes of data coming from the DXM local registers 1, 10, 20, and 21. The
rest of the data is in assembly instance 100 is zero.

10.5 Setting up Email and Text Messaging


The DXM Controller can be configured to send email or SMS messages based on threshold conditions. Internal log files
may be sent using email
Cellular-connected systems can use email or SMS. Ethernet-connected systems may only use email, but can send email to
cellular phones as a SMS message depending upon the network carrier. To send email to a Verizon phone, use the phone
number followed by @vtext.com, for example, 1234567890@vtext.com.

Following these instructions using the DXM Configuration Tool to program the controller for email and/or SMS.
1. Set the time on the DXM Controller.
2. Define the Network Interface settings by selecting either Ethernet or Cell on the Cloud Services screen.
3. If you selected Ethernet, configure your Ethernet connection by setting the IP settings on the Network screen.
4. Set the email and message parameters on the Mail and Messaging screen.
5. To send alert messages, define the threshold rule to use email and/or SMS.
6. To send log files, define the log file parameters.

10.5.1 Define the Network Interface Settings


On the Cloud Services screen, define the network connection settings by selecting Ethernet or Cell from the Network
Interface drop-down list. This determines how the DXM Controller sends data.

11 EttherNet/IP is a trademark of Rockwell Automation.

74 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

When selecting Ethernet, provide the network parameters on the Network screen. If you don't require pushing data to a
web server, set the Cloud Push interval to zero.

10.5.2 Configure your Ethernet Connection


To send email based on a threshold rule or to email log files, first define the network and email servers. In the DXM
Configuration Tool, go to Settings > Network.
1. To define the Ethernet IP address, give the DXM Controller a static IP address. In most cases you may select the
device to use DHCP and have the IP address automatically assigned.
2. DNS settings are not typically required. The DXM Controller uses a public service to resolve Domain names, but if
the network connection does not have Internet access, the DNS settings may be required.

www.bannerengineering.com - Tel: 763.544.3164 75


DXM100-Bx Wireless Controller Instruction Manual

10.5.3 Configure your Cellular Connection


A cellular connection does not require any configuration other than being selected as the network connection under the
Cloud Services screen.

10.5.4 Set the Email and Messaging Parameters


From the Settings > Mail and Messaging screen, enter the SMPT definition, login, and password for a mail server. You
must supply the SMTP Server, Server Port, and login credentials to send email. When only sending SMS messages over
cellular, the SMTP Server is not required. The default SMTP port is 25 but may need to be adjusted for Ethernet-based
networks. Note that many facilities block port 25. Port 587 is another common SMTP submission port.

The SMTP password is not stored in the XML configuration file, but on the DXM Controller. After the password is entered,
click on Send SMTP Password to send it to the DXM Controller. The password is stored in non-volatile memory, so reboot
the DXM Controller to recognize the new password.

At the bottom of the screen, define the recipient to receive emails and enter the phone numbers for SMS messages. These
recipients for email or SMS messages can be selected in the threshold definition for sending alert messages.

10.5.5 Define Threshold Rules for Email


To define a threshold, go to Action Rules > Thresholds. Depending upon which recipients are defined, select the
appropriate email or SMS checkbox for the threshold rule (under Email/SMS on state transition). When the threshold
rules goes active or inactive, an email is generated.

76 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

10.5.6 Define Log File Parameters for Emailing Log Files


The DXM Controller can email log files generated on the device.
Before emailing log files, set the Mail and Messaging parameters to provide the login credentials. When using Ethernet,
verify the IP address settings are defined on the Network screen. Set the DXM Controller time, under Settings >
General, so that all data is properly time stamped.
Select the registers to log on the Local Registers > Register Configuration screen. Define the setup of the log file
using the Settings > Logging screen. Typical settings are shown.
1. Enable the log and timestamp with every entry.
2. Enter the filename, log rate, and the maximum file size to send via email (5 to 10k is an efficient size for a cellular
connection).
3. Define the email address.

4. Define the local register data put into the log file using the Local Registers > Local Register Configuration
screen, under the Logging and Protocol Conversion section. From the SD Card Logging drop-down list, select
the log file to write to. Log files are written in CSV format.
5. Use the DXM Configuration Tool to read back the log files. Under Settings > Logging, click Refresh List,
highlight the file to download, then click Save Selected.

10.6 Ethernet and Cellular Push Retries


The DXM Controller can be configured to send register data packets to a webserver. When the Ethernet or cell
communications path is not operating, the DXM Controller retries the send procedure. The communications retry process is
outlined below for each configuration.

www.bannerengineering.com - Tel: 763.544.3164 77


DXM100-Bx Wireless Controller Instruction Manual

Regardless of the communications connection (Ethernet or cellular), a failed attempt results in the register data packet
being saved on the local micro SD card12. The number of retries will depend upon the network connection type.

When there is bad cellular signal strength or there is no Ethernet connection, the transmission attempts are not counted as
failed attempts to send data. Only when there is a good network connection and there are 10 failed attempts will the
controller archive the data on the SD card. Data archived on the SD card must be manually retrieved.

10.6.1 Ethernet Push Retries


With an Ethernet-based network connection, the DXM Controller retries a message five times. The five retry attempts
immediately follow each other. After all attempts are exhausted, the register data packet is saved on the micro SD card.

At the next scheduled time, the DXM Controller attempts to send the saved packet as well as the newly created register
data packet. If it cannot send the new register data packet, the new register data packet is appended to the saved file on
the micro SD card to be sent later. After 10 rounds of retries, the data set is archived on the micro SD card under folder
_sxi. No additional attempts to resend the data are made; the data file must be manually retrieved.

Using SSL on Ethernet will have no retries, but will save each failed attempt to the micro SD card until 10 failed rounds. At
this time, the register data packet is archived.

10.6.2 Cellular Push Retries


In a cellular-connected system there are no retries. Failed transmissions are saved on the micro SD card.

After 10 successive failed attempts, the data is archived in the _sxi folder. Send attempts with a low signal quality are not
counted against the 10 count limit. For example, if the cellular antenna is disconnected for period that the DXM controller
would have sent 20 messages under normal circumstances, all 20 messages would be saved and will be retried when the
antenna is reconnected. If the signal quality was good, but the cellular network was not responding, the DXM Controller
archives the register data packets after 10 failed attempts.

10.6.3 Event/Action Rule or Log File Push Retries


Event-based pushes caused by Action rules and locally stored log files sent using email follow the same process when
failures occur, based on the network connection. The failed Event-based messages are resent with the next cyclical
schedule or the next event message that triggers a push message.

10.6.4 Email and Text Message Push Retries


There are no retries for emails or SMS messages that fail to be sent from the DXM Controller.

10.7 DXM Modbus Registers


The DXM100-Bx Wireless Controller may have up to four internal Modbus slave devices:

DXM Internal Modbus Slave IDs (factory default)

Modbus Slave ID Device

1 Gateway (PE5) or MultiHop (HE5) ISM RadioMultiHop wireless devices connected to the internal MultiHop radio should
be assigned Modbus Slave addresses starting at 11.

199 Local RegistersInternal storage registers of the DXM Controller

200 I/O Base BoardAll data and parameters for each input or output of the DXM Controller.

201 LCD DisplayThe user has access to the LED indicators on the DXM Controller.

All Modbus registers are defined as 16-bit Modbus Holding Registers. When connecting external Modbus slave devices, only
use Modbus slave IDs 2 through 198. The local registers, the I/O base, and the LCD slave IDs are fixed, but the internal
radio slave ID can be changed if needed.

12 Enable HTTP logging to save data on the SD card; this is the factory default. See SETTINGS -> LOGGING in the DXM Configuration Tool.

78 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

11 File System and Archive Process


The DXM file system consists of two physical components: the serial EEPROM that stores non-volatile configuration
information and a removable micro SD card that stores file backup data and user created files.

11.1 EEPROM Files


The serial EEPROM stores basic data that is required to be non-volatile, including network configuration data, IP address,
MAC address, network masks, firewall settings, and authentication information. The controller XML configuration file
created by the DXM Configuration Tool is stored in EEPROM. The small section of non-volatile local registers is also stored
in EEPROM.

11.2 Micro SD Card Files


The micro SD card contains most files at the root level. The archive directory contains files kept by the system for history
backup. Archive files are stored in the directory _sxi and are only accessible by removing the SD card.
Data Log Files
HTTP Push Files
User created ScriptBasic file
ScriptBasic program file
CmVMon file
_sxi Archive directory
Archive Directory
Only two types of files are moved into the archive directory: data log files and HTTP log files. Data log files are
date/time stamped and placed into the archive directory when the size limit is reached. HTTP log files are date/
time stamped then placed into the archive directory when they are successfully sent to the webserver or host
system. If the HTTP log files were not successfully sent after the retries have been exhausted, the files are placed
into a root directory called sav.
Data Log files
Users may create up to four data log files using the DXM Configuration Tool. The log files are stored in the root
directory on the SD card. When the file size limit is reached, the filename is changed to include the date and time
and the file is moved into the archive directory _sxi. If a finished log file is to be e-mailed, it will be done at this
time and then moved into the archive directory. Archived log files are deleted based on the Clear Logs parameter.
HTTP Push File
If the DXM Controller is configured to send data to a webserver or host system, the device creates an HTTP.LOG
file on the SD card. The HTTP log is created only if the Logging Interval is non-zero and the HTTP enable log is set.
An entry is placed in the HTTP log file at the Logging Interval specified by the user. At the Push Interval time, the
HTTP log file is sent to the webserver or host system. If the transmission is successful, the HTTP log file is time
stamped and placed into the archive directory (_sxi). If the transmission fails, the file remains in the root
directory and subsequent Logging Intervals are appended to the file and are sent at the next Push Interval. For
more information on the communications retry mechanism, refer to the technicel note on system retries. (DXM
Ethernet and Cellular Push Retries.docx).
ScriptBasic Created Files
Users may use ScriptBasic to create files on the SD card by using the FILEOUT function. The filenames are fixed
and up to five files can be created in the root directory.
ScriptBasic Program File
The main ScriptBasic program that runs at boot time is stored on the SD card in the root directory.
System Voltage Monitor File
The CmVMon.txt file (Cellular milli-Volt Monitor) is created by the system and is used to track power events.
Every power-up cycle is date/time stamped with the voltage read from the I/O board. The value 24487 is equal to
24.487 volts. If the voltage drops below 11.2 V, another entry is put in the log file indicating the cellular modem
will shut down.

CM 2015-09-22 18:52:43 VMon Power entered normal range 24487

CM 2015-10-13 20:49:47 VMon Power entered normal range 24004

CM 2015-10-16 15:00:20 VMon Power entered normal range 24014

CM 2015-10-19 19:12:26 VMon Power entered normal range 12845

www.bannerengineering.com - Tel: 763.544.3164 79


DXM100-Bx Wireless Controller Instruction Manual

12 DXM100 Dimensions

59.5 mm
[2.34]

104 mm 35 mm 20.4 mm
[4.09] [1.38] [0.8]

86 mm
[3.39]
94.6 mm
[3.72]

All measurements are listed in millimeters, unless noted otherwise.

80 www.bannerengineering.com - Tel: 763.544.3164


DXM100-Bx Wireless Controller Instruction Manual

13 Contact Us
Corporate Headquarters

Address: Phone: +1 763 544 3164


Banner Engineering Corporate Website: www.bannerengineering.com
9714 Tenth Avenue North
Minneapolis, Minnesota 55441, USA

Europe

Address: Phone: +32 (0)2 456 0780


Banner Engineering EMEA Website: www.bannerengineering.com/eu
Park Lane Culliganlaan 2F Email: mail@bannerengineering.com
Diegem B-1831, Belgium

Turkey

Address: Phone: +90 216 688 8282


Banner Engineering Turkey Website: www.bannerengineering.com.tr
Barbaros Mah. Uphill Court Towers A Blok D:49 Email: turkey@bannerengineering.com.tr
34746 Bat Ataehir Istanbul Trkiye

India

Address: Phone: +91 (0) 206 640 5624


Banner Engineering India Pune Head Quarters Website: www.bannerengineering.co.in
Office No. 1001, 10th Floor Sai Capital, Opp. ICC Senapati Bapat Road Email: salesindia@bannerengineering.com
Pune 411016, India

Mexico

Address: Phone: +52 81 8363 2714 or 01 800 BANNERE (toll free)


Banner Engineering de Mexico Monterrey Head Office Website: www.bannerengineering.com.mx
Edificio VAO Av. David Alfaro Siqueiros No.103 Col. Valle Oriente C.P.66269 Email: mexico@bannerengineering.com
San Pedro Garza Garcia, Nuevo Leon, Mexico

Brazil

Address: Phone: +1 763 544 3164


Banner do Brasil Website: www.bannerengineering.com.br
Rua Baro de Teff n 1000, sala 54 Email: brasil@bannerengineering.com
Campos Elseos, Jundia - SP, CEP.: 13208-761, Brasil

China

Address: Phone: +86 212 422 6888


Banner Engineering Shanghai Rep Office Website: www.bannerengineering.com.cn
Xinlian Scientific Research Building Level 12, Building 2 Email: sensors@bannerengineering.com.cn
1535 Hongmei Road, Shanghai 200233, China

Japan

Address: Phone: +81 (0)6 6309 0411


Banner Engineering Japan Website: www.bannerengineering.co.jp
Cent-Urban Building 305 3-23-15 Nishi-Nakajima Yodogawa-Ku Email: mail@bannerengineering.co.jp
Osaka 532-0011, Japan

Taiwan

Address: Phone: +886 (0)2 8751 9966


Banner Engineering Taiwan Website: www.bannerengineering.com.tw
8F-2, No. 308 Section 1, Neihu Road Email: info@bannerengineering.com.tw
Taipei 114, Taiwan

www.bannerengineering.com - Tel: 763.544.3164 81


DXM100-Bx Wireless Controller Instruction Manual

14 Warnings
Install and properly ground a qualified surge suppressor when installing a remote antenna system. Remote antenna configurations installed without surge
suppressors invalidate the manufacturer's warranty. Keep the ground wire as short as possible and make all ground connections to a single-point ground system to ensure no
ground loops are created. No surge suppressor can absorb all lightning strikes; do not touch the Sure Cross device or any equipment connected to the Sure Cross device
during a thunderstorm.
Exporting Sure Cross Radios. It is our intent to fully comply with all national and regional regulations regarding radio frequency emissions. Customers who want to
re-export this product to a country other than that to which it was sold must ensure the device is approved in the destination country. A list of approved
countries appears in the Radio Certifications section of the product manual. The Sure Cross wireless products were certified for use in these countries using the antenna that
ships with the product. When using other antennas, verify you are not exceeding the transmit power levels allowed by local governing agencies. Consult with Banner
Engineering Corp. if the destination country is not on this list.

14.1 Banner Engineering Corp. Limited Warranty


Banner Engineering Corp. warrants its products to be free from defects in material and workmanship for one year following the date of shipment. Banner Engineering Corp.
will repair or replace, free of charge, any product of its manufacture which, at the time it is returned to the factory, is found to have been defective during the warranty
period. This warranty does not cover damage or liability for misuse, abuse, or the improper application or installation of the Banner product.
THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED (INCLUDING, WITHOUT LIMITATION,
ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE), AND WHETHER ARISING UNDER COURSE OF PERFORMANCE, COURSE
OF DEALING OR TRADE USAGE.
This Warranty is exclusive and limited to repair or, at the discretion of Banner Engineering Corp., replacement. IN NO EVENT SHALL BANNER ENGINEERING CORP. BE
LIABLE TO BUYER OR ANY OTHER PERSON OR ENTITY FOR ANY EXTRA COSTS, EXPENSES, LOSSES, LOSS OF PROFITS, OR ANY INCIDENTAL,
CONSEQUENTIAL OR SPECIAL DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY TO USE THE PRODUCT, WHETHER
ARISING IN CONTRACT OR WARRANTY, STATUTE, TORT, STRICT LIABILITY, NEGLIGENCE, OR OTHERWISE.
Banner Engineering Corp. reserves the right to change, modify or improve the design of the product without assuming any obligations or liabilities relating to any product
previously manufactured by Banner Engineering Corp. Any misuse, abuse, or improper application or installation of this product or use of the product for personal protection
applications when the product is identified as not intended for such purposes will void the product warranty. Any modifications to this product without prior express approval
by Banner Engineering Corp will void the product warranties. All specifications published in this document are subject to change; Banner reserves the right to modify product
specifications or update documentation at any time. Specifications and product information in English supersede that which is provided in any other language. For the most
recent version of any documentation, refer to: www.bannerengineering.com.

82 www.bannerengineering.com - Tel: 763.544.3164

You might also like