General AC Drive: 3-Phase 200 240V 0.4 22kW (0.5 30HP) 3-Phase 380 480V 0.4 22kW (0.5 30HP)

Download as pdf or txt
Download as pdf or txt
You are on page 1of 52

LSLV

General AC Drive G100


3-phase 200~240V 0.4~22kW (0.5~30HP)
3-phase 380~480V 0.4~22kW (0.5~30HP)
Contents
04 Features
10 Model & Type
11 Specifications
13 Wiring
14 Power Terminal
15 Control Terminal
16 Keypad Functions
22 Parameter Group
46 Peripheral Devices
47 Drive Watt Loss Data
48 Dimensions

General Drive

G100
02 | LSIS Co., Ltd.
General AC Drive G100

Great Reliability
• Meets UL 61800-5-1
• Military (MIL 217Plus) design based
methodology
The G100 is the • Enhanced materials and
manufacturing processes
solution for general
drives applications because Great Performance
of its high performance • Enhanced motor control-sensorless  
& V/F performance
sensorless operation, • User-friendly-easy tuning
sensorless control
premium quality and • Suitable for most applications

high reliability.
User Friendly
• Easy to install, use and maintain
• Various options

LSIS Co., Ltd. | 03


Features

G100 is designed to meet global standards through


upgraded design, materials and manufacturing improving
its endurance for harsh environments.  

UL 61800-5-1*1) Design
Great Satisfied the new UL certification
*1) After February 2020 all of system, product have to satisfy new UL certification
Reliability
Robust Design
Construction of the air flow design minimizes exposure of critical components
(IGBT, PCB, etc.) from outside contaminants.

Built-in EMC Filter


Embedded C3 EMC filter to meet EN618000-3 standards and provide noise reduction

04 | LSIS Co., Ltd.


General AC Drive G100

Fan Lifecycle Display fan replacement warning message with digital output or keypad
Diagnosis
Drive
Run Signal
Time (s)

FAN
Usage Rate

PRT- 87

Time (s)

FAN
Warning
Standard fan run-time is 50,000 hours, and the fan replacement level(PRT-87)
should be set according to the environment

MIL217Plus based • Reliability design basis tool (PSA, Fr-FMEA, FTA, RBD, PBS)
• Improved circuit robustness through strict quality margins
Design
Category G100
240,455 hrs(27 yrs)
Estimated Life Cycle
(Accelerated life test result : 295,951 hrs)
Reliablity Test Method MTTF
MIL-HDBK-217F
Standard
RIAC HDBK 217Plus
Ambient Temperature 30°C (86°F)

Material Design • Enhanced thermal resistance and intensity through upgraded materials
• Increased thickness to prevent damage

LSIS Co., Ltd. | 05


Features

Heavy Duty
Hoist Conveyor Compressor

Normal Duty
Pump Fan

The G100 has an advanced sensorless vector mode along


with a highly adaptable V/F mode making
it one of the most versatile drives on the market.

Application Adaptability
Great Dual ratings enable use in most applications

Performance V/F Accelerate and Decelerate Function


Applied ATB & Flux braking function

06 | LSIS Co., Ltd.


General AC Drive G100

Sensorless • Low speed/High torque


Performance • Tight speed regulation +/- 1%
• 0.5Hz 200% peak torque

Torque (%)
200%
0.5Hz
150%
1Hz
3Hz 100%
5Hz
10Hz 50%

20Hz 0%

-50%
30Hz
40Hz
50Hz -100%

-150%
55Hz
60Hz
-200%
0 200 400 600 800 1000 1200 1400 1600 1800 2000
Operating Speed (RPM)

KEB (Kinetic • KEB for a stable system stop in case of power loss or failure.
Energy Buffering) • Select KEB operation function for different speeds and purposes

Flying Start Select optimal flying start operation for different applications

Power Failure
Frequenccy
(Hz) Motor Rotation Speed

Normal Free-run SS Block Time Speed Search Acceleration Normal


Operation Operation

Time (s)

Operation
Command ON ON

LSIS Co., Ltd. | 07


Features

❶ ❺

G100 is convenient to install, control,


perform maintenance and many other functions.

❶ Built-in Potentiometer ❷ Smart Copier


Easy operation with built-in potentiometer Copy parameter (Read/Write) and download
User- firmware without supplying power to drive
❷ Remote Keypad
friendly Copy parameter (Read/Write)
Design using remote keypads

08 | LSIS Co., Ltd.


General AC Drive G100

❷ Fieldbus Options
❺ DIN rail Mount (Below 4kW)
Provides various communication options
Install using DIN rails (Side-by-side)
with simple mounting structure
• Dual Port EtherNet/IP
• Profibus-DP
• CANopen

❻ Fan Replacement
Ethernet 2 port support
Simple cooling fan replacement procedure

❷ PC Tools (DriveView 9)
New version of PC tool

❷❼ Easy Modbus Communication


Connection
2 type of connection of Modbus communication
• RJ45 Port • I/O (S+, S-)
❼ I/O Terminal (5mm)
❸ QR Code Easy wiring with 5mm I/O pitch
View manuals and various
information from the QR code 5mm
printed on the front cover.

❽ Operation Group
❹ Built-in 2 Relay • Access commonly used parameters in
Cost efficient and easy to compose system the operation group
with two embedded relays. • Identical Parameter group structure for
all 100 series

❽ 100 Series Parameter Group


Configuration Applied

LSIS Co., Ltd. | 09


LSLV
General
Drive G100 Model & Type

Motor rating 3-Phase 200V 3-Phase 400V

0.4 kW LSLV0004G100-2EONN LSLV0004G100-4EO(F)N

0.75 kW LSLV0008G100-2EONN LSLV0008G100-4EO(F)N

1.5 kW LSLV0015G100-2EONN LSLV0015G100-4EO(F)N

2.2 kW LSLV0022G100-2EONN LSLV0022G100-4EO(F)N

4.0 kW LSLV0040G100-2EONN LSLV0040G100-4EO(F)N

5.5 kW LSLV0055G100-2EONN LSLV0055G100-4EO(F)N

7.5 kW LSLV0075G100-2EONN LSLV0075G100-4EO(F)N

11 kW

15 kW

18.5 kW

22 kW

※ (F): Built-in EMC or Non-EMC type


※ 200V/400V 11~22kW TBA

LSLV 055
0008 055
G100 -- 4 E O F N

LS Low Voltage Reactor


Series Name
Drive Series N : Non-reactor

Motor Rating(kW) Input Voltage EMC Filter


0004:0.4kW~0220:22kW 2 : 3-phase 200~240[V] F : Built-in EMC
4 : 3-phase 380~480[V] N : Non-EMC

Keypad UL Type
E : LED Keypad O : UL Open

10 | LSIS Co., Ltd.


Specifications General Drive

3-Phase 200V Class (0.4~7.5kW)


 G100-2 0004 0008 0015 0022 0040 0055 0075
(HP) 0.5 1.0 2.0 3.0 5.4 7.5 10
Heavy Duty (HD)
Motor (kW) 0.4 0.75 1.5 2.2 4.0 5.5 7.5
Rating (HP) 1.0 2.0 3.0 5.4 7.5 10 15
Normal Duty (ND)
(kW) 0.75 1.5 2.2 4.0 5.5 7.5 11
Heavy Duty (HD) 1.0 1.9 3.0 4.2 6.5 9.1 12.2
Capacity [kVA]
Normal Duty (ND) 1.2 2.3 3.8 4.6 6.9 11.4 15.2

Rated Current Heavy Duty (HD) 2.5 5.0 8.0 11.0 17.0 24.0 32.0
(3-Phase Input) [A] Normal Duty (ND) 3.1 6.0 9.6 12.0 18.0 30.0 40.0
Output
Rating Heavy Duty (HD) 1.5 2.8 4.6 6.1 9.3 12.8 17.4
Rated Current
(1-Phase Input) [A] Normal Duty (ND) 2.0 3.6 5.9 6.7 9.8 16.3 22.0
Frequency [Hz] 0~400Hz (IM sensorless: 0~120Hz)
Voltage [V] 3-Phase 200~240V
Voltage [V] 3-Phase 200~240VAC (-15%~+10%)

Input Frequency [Hz] 50~60Hz (±5%)


Rating Heavy Duty (HD) 2.2 4.9 8.4 11.8 18.5 25.8 34.9
Rated Current [A]
Normal Duty (ND) 3.0 6.3 10.8 13.1 19.4 32.7 44.2
Weight [kg] 1.04 1.06 1.36 1.4 1.89 3.08 3.21

3-Phase 400V Class (0.4~7.5kW)


 G100-4 0004 0008 0015 0022 0040 0055 0075
(HP) 0.5 1.0 2.0 3.0 5.4 7.5 10
Heavy Duty (HD)
Motor (kW) 0.4 0.75 1.5 2.2 4.0 5.5 7.5
Rating (HP) 1.0 2.0 3.0 5.4 7.5 10 15
Normal Duty (ND)
(kW) 0.75 1.5 2.2 4.0 5.5 7.5 11
Heavy Duty (HD) 1.0 1.9 3.0 4.2 6.5 9.1 12.2
Capacity [kVA]
Normal Duty (ND) 1.5 2.4 3.9 5.3 7.6 12.2 17.5

Rated Current Heavy Duty (HD) 1.3 2.5 4.0 5.5 9.0 12.0 16.0
(3-Phase Input) [A] Normal Duty (ND) 2.0 3.1 5.1 6.9 10.0 16.0 23.0
Output
Rating Heavy Duty (HD) 0.7 1.4 2.1 2.8 4.9 6.4 8.7
Rated Current
(1-Phase Input) [A] Normal Duty (ND) 1.3 1.9 2.8 3.6 5.4 8.7 12.6
Frequency [Hz] 0~400Hz (IM sensorless: 0~120Hz)
Voltage [V] 3-Phase 380~480V
Voltage [V] 3-Phase 380~480VAC (-15%~+10%)

Input Frequency [Hz] 50~60Hz (±5%)


Rating Heavy Duty (HD) 1.1 2.4 4.2 5.9 9.8 12.9 17.5
Rated Current [A]
Normal Duty (ND) 2.0 3.3 5.5 7.5 10.8 17.5 25.4
Weight [kg] 1.02 (1.04) 1.06 (1.08) 1.4 (1.44) 1.42 (1.46) 1.92 (1.98) 3.08 (3.24) 3.12 (3.28)
• Maximum applicable capacity is indicated in case of using a 4-pole standard motor
• For the rated capacity, 200 and 400V class input capacities are based on 220 and 440V, respectively.
• The rated output current is limited based on the carrier frequency set at Cn.04.
• The output voltage becomes 20-40 % lower during no-load operations to protect the inverter from the impact of the motor closing and opening (0.4-4.0 kW models only).

LSIS. Co., Ltd. | 11


LSLV
General
Drive G100 Specifications

Control
Control Method V/F, Slip Compensation, Sensorless Vector

Digital command: 0.01Hz


Frequency Setting Resolution
Analog command: 0.06Hz(maximum frequency: 60 Hz)

Frequency Accuracy 1% of the maximum output frequency


V/F Pattern Linear, squared, user V/F
Overload Capacity HD: 150% 1 minute, ND: 120% 1minute
Torque Boost Manual/Automatic torque boost

Operation
Operation Mode Select key pad, terminal strip, or communication operation

Analog: -10~10[V], 0~10[V], 4~20[mA]


Frequency Setting
Digital: Keypad
PID control, 3-wire operation, Frequency limit, Second function, Anti-forward and reverse direction
rotation, Commercial transition, Speed search, Power braking, Leakage reduction, Up-down operation,
Operation Function
DC braking, Frequency jump, Slip compensation, Automatic restart, Automatic tuning, Energy buffering,
Flux braking, Fire mode
NPN (Sink) / PNP (Source) Selectable

Multi-Function Terminal Function: Forward run, Reverse run, Reset, External trip, Emergency stop, Jog operation, Multi-step frequency-
(5 Points) high, middle, low, Multi-step acceleration/ deceleration-high, middle, low, DC braking at stop, 2nd motor select,
Input
Frequency up/down, 3-wire operation, Change into normal operation during PID operation, Change into main body
operation during option operation, Analog command frequency fixing, Acceleration/deceleration stop etc. Selectable
Analog Input V1: -10~10V, I2 4~20mA
Multi-function Relay Terminal Fault output and drive operation status output (N.O., N.C.) less than AC 250V 1A, less than DC 30V 1A
Output
Analog Output 0~12Vdc: Frequency, Output current, Output voltage, DC stage voltage etc. selectable

Protective Function
Over current trip, external signal trip, ARM short Over voltage trip, temperature sensor trip, inverter
current fault trip, over heat trip, input imaging trip, over heat, option trip, output image trip, inverter
ground trip, motor over heat trip, I/O board link trip, overload trip, fan trip, pre-PID operation failure
Trip
no motor trip, parameter writing trip, emergency external brake trip, low voltage trip during operation,
stop trip, command loss trip, external memory error, low voltage trip, analog input error, motor overload
CPU watchdog trip, motor light load trip trip, over torque trip, under torque trip
Command loss trip warning, overload warning, light load warning, inverter overload warning,
Alarm fan operation warning, braking resistance braking rate warning, rotor time constant tuning error,
inverter pre-overheat warning, over torque warning, under torque warning
HD below 15ms (ND below 8ms): Continuous operation (To be within rated input voltage, rated output)
Momentary Power Loss
HD above 15ms (ND above 8ms): Automatic restart operation enable

Environment
Cooling Type Forced fan cooling structure
Protection Degree IP20/UL Open (Default), UL Enclosed type 1 (Option)
Ambient temperature under the condition of no ice or frost.
Ambient Temperature HD: -10~50℃(14~122°F) / ND: -10~40℃(14~104°F)
[However, recommended to use load below 80% when using at 50°C under light load]
Humidity Relative humidity below 95% RH (no dew formation)
Storage Temperature -20~65℃(-4~149°F)
Location No corrosive gas, flammable gas, oil mist and dust etc. indoors (Pollution degree 2 environment)

Below 1,000m (From 1000 to 4000m, the rated input voltage and rated output current
Altitude, Vibration
of the drive must be derated by 1% for every 100m.), below 9.8m/sec2 (1G)

Pressure 70~106kPa

12 | LSIS Co., Ltd.


Wiring General Drive

Multi-function input
(Default)
SW2 S+ RS485
FX P1
SW1
ON OFF S-
RX P2 NPN PNP

BX Switch Description
P3 Analog output
SW1 NPN/PNP mode selection switch AO
(Default: Frequency)
SW2 Terminating resistor selection switch
RST P4

P24 24V Power


Spd-L P5

CM

C1

A1
Relay output 1
(Default: Trip)

Analog input B1
VR

V1

CM
C2

I2 Relay output 2
(Default: Run)
A2

LSIS. Co., Ltd. | 13


LSLV
General
Drive G100 Power Terminal

0.4 / 0.75kW 1.5 / 2.2kW 4kW

5.5 / 7.5kW

Terminal Labels Name Description


Ground terminal Connect earth grounding.
R(L1)/S(L2)/T(L3) AC power input terminal Mains supply AC power connections.
B1/B2 Brake resistor terminals Brake resistor wiring connection.
U/V/W Motor output terminals 3-phase induction motor wiring connections.

Capacity (kW) Terminal Screw Size Rated Screw Torque (Kgf.cm/Nm)


0.4
R / S / T, U / V / W : M3 R / S / T, U / V / W : 5.1 / 0.5
0.75
1.5
3-Phase R / S / T, U / V / W : M4 R / S / T, U / V / W : 12.1 / 1.2
2.2
200V Class
4 R/S/T, U/V/W : M4 R / S / T, U / V / W : 18.4 / 1.8
5.5 R / S / T : 24.0 / 2.4
R / S / T, U / V / W : M4
7.5 U / V / W : 15.0 / 1.5

0.4
0.75
R / S / T, U / V / W : M3.5 R / S / T, U / V / W : 10.3 / 1.0
1.5
3-Phase
2.2
400V Class
4 R / S / T, U / V / W : M4 R / S / T, U / V / W : 18.4 / 1.8
5.5 R / S / T : 14.3 / 1.4
R / S / T, U / V / W : M4
7.5 U / V / W : 18.4 / 1.8
• Only use the specified torque on the screw heads otherwise damage could occur. Loose screws can cause overheating and damage.
• Use copper wires with 600V, 75°C specification.

14 | LSIS Co., Ltd.


Control Terminal General Drive

SW2
SW1
24 P1 P2 P3 P4 P5 CM

A1 B1 C1 A2 C2 VR V1 I2 AO CM S+ S-

Terminals Terminal Screw Size Screw Torque (Kgf.cm/Nm)


P1~P5 / CM / VR / V1 / I2 / AO / 24 / S+ / S- M2 2.2~2.5/0.22~0.25
A1 / B1 / C1, A2 / C2 M2.6 4.0/0.4
• Only use the specified torque on the screw heads otherwise damage could occur.
Loose screws can cause overheating and damage.

Terminal
Category Name Description
Labels
Configurable for multi-function input terminals.
Factory default terminals and setup are as follows.
• P1: Fx
P1~P5 Multi-function
Multi-function • P2: Rx
Input 1-5
Terminal • P3: BX
Configuration • P4: RST
• P5: Speed-L
Sequence common
CM Common terminal for analog terminal inputs and outputs.
terminal
Used to setup or modify a frequency reference via analog voltage or current input.
Potentiometer • Maximum voltage output: 12 V
VR frequency reference
• Maximum current output: 100mA
input
• Potentiometer: 1/5 kΩ
Voltage input for Used to setup or modify a frequency reference via analog voltage input terminal.
Analog Input V1 frequency reference • Unipolar: 0–10V (12V Max.)
input • Bipolar: -10–10V (±12V Max.)
Used to setup or modify a frequency reference via current input terminal.
Current input for • Input current: 4-20 mA
I2 frequency reference
• Maximum Input current: 24mA
input terminal
• Input resistance: 249 Ω
Used to send inverter output information to external devices: Output frequency,
output current, output voltage, or a DC voltage.
Voltage output
AO • Output voltage: 0–10 V
terminal
• Maximum output voltage/Current: 12 V, 10 mA
• Factory default output: Frequency
24 External 24V power source Maximum current output: 100mA

Analog Output Sends out alarm signals when the inverter’s safety features are activated
(AC 250V 1A, DC 30V 1A).
A1/C1/B1 Fault signal output 1
• Fault condition: A1 and C1 contacts are connected (B1 and C1 open connection)
• Normal operation: B1 and C1 contacts are connected (A1 and C1 open connection)
Sends out alarm signals when the inverter’s safety features are activated
(AC 250V 1A, DC 30V 1A).
A2/C2 Fault signal output 2
• Fault condition: A2 and C2 contacts are open connection
• Normal operation: A2 and C2 contacts are connected

RS-485
S+ / S- RS-485 signal line Used to send or receive RS-485 signals.
Communication

LSIS. Co., Ltd. | 15


LSLV
General
Drive G100 Keypad Functions

❷ ❹

❸ ❺

No. Name Function

➊ 7-Segment Display Displays current operational status and parameter information.

LED flashes during parameter configuration and when the ESC key operates as the
➋ SET Indicator
multi-function key.

➌ RUN Indicator LED turns on (Steady) during an operation, and flashes during acceleration or deceleration.

➍ FWD Indicator LED turns on (Steady) during forward operation.

➎ REV Indicator LED turns on (Steady) during reverse operation.

Key Name Function

[RUN] Key Used to run the inverter (Inputs a RUN command).

STOP: Stops the inverter.


[STOP/RESET] Key
RESET: Resets the inverter if a fault or failure occurs.

[▲] Key, [▼] Key Switches between codes, or increases or decreases parameter values.

Moves between groups or moves to the digit on the left when setting the parameter.
[MODE / SHIFT] Key Press the MODE/SHIFT key once again on the maximum number of digits to move to the
minimum number of digits.

Switches from the selected state of parameter to the input state.


[ENTER] Key Edits parameter and apply change.
Accesses the operation information screen during failure on the failure screen.

[ESC] ESC to the initial display.

[VOLUME] Used to set the operation frequency.

16 | LSIS Co., Ltd.


General Drive

Group Keypad Display Description

Operation - Configures basic parameters for inverter operation.

Configures parameters for basic operations.


Drive These include jog operation, motor capacity evaluation, torque boost, and other keypad related
parameters.

Configures basic operation parameters.


Basic
These parameters include motor parameters and multi-step frequency parameters.

Advanced Configures acceleration or deceleration patterns, frequency limits, etc.

Control Configures sensorless vector-related features.

Configures input terminal-related features, including digital multi-functional inputs and


Input Terminal
analog inputs.

Output Terminal Configures output terminal-related features such as relays and analog outputs.

Communication Configures communication features for RS-485 or other communication options.

Application Configures functions related to PID control.

Protection Configures motor and inverter protection features

Motor 2 Configures secondary motor related features.


(Secondary The secondary motor (M2) group appears on the keypad only when one of the multi-function
Motor) input terminals (In.65–In.69) has been set to 26 (Secondary motor).

LSIS. Co., Ltd. | 17


LSLV
General
G100 Keypad Functions
ENT

Drive
ENT

0QFSBUJPO

Group & Code selection


Step Instruction Keypad Display

Move to the group you want using the [MODE] keys.


1 Press the [MODE] key for longer than 1 second to
move in the opposite direction.

Move up and down through the codes using the


0QFSBUJPO

2 [▲] and [▼] keys until you locate the code that you 0VUQVUDVSSFOU
require.
ENT

0VUQVUGSFRVFODZ

3 Press the [ENT] key to save the change. -


When moving up and down through the codes using the [▲] and [▼] keys in each group, there are cases where the code number does not increase or decrease.
This is because the number was left blank in the inverter program by expecting additional features or the program was set up to not display the unused features.

Navigating Directly to Different Codes


The following example details navigating to code dr. 95, from the initial code in the drive group (dr. 0).
This example applies to all groups whenever you would like to navigate to a specific code number.
Step Instruction Keypad Display

1 Ensure that you are currently at the first code of the drive group (dr.0).

Press the [ENT] key.


2
Number "9" will flash.

3 Press the [▼] key and change the ones' place of the code "95" to "5."

Press the [MODE] to move to the tens' place.


4 The cursor will move to the left and "05" will be displayed.
At this time, the number "0" will be flashing.

Press the [▲] key to change the tens' place number from "0" to "9,"
5
so the designated code is "95."
Press the [ENT] key.
6
Code dr.95 is displayed.

18 | LSIS Co., Ltd.


General Drive

Fault Trips
Protection functions for output current and input voltage
Keypad Display Name Type Description
Displayed when the motor overload trip is activated and the actual load level
Over Load Latch exceeds the set level.
Operates when Pr.20 is set to a value other than 0.
Displayed when the motor underload trip is activated and the actual load level is
Under Load Latch less than the set level.
Operates when Pr.27 is set to a value other than 0.

Over Current 1 Latch Displayed when inverter output current exceeds 200% of the rated current.

Over Voltage Latch Displayed when internal DC circuit voltage exceeds the specified value.

Low Voltage Level Displayed when internal DC circuit voltage is less than the specified value.

Displayed when internal DC circuit voltage is less than the specified value during
Low Voltage 2 Latch inverter operation.
Operates when Pr.82 is set to 1.

Displayed when a ground fault trip occurs on the output side of the inverter and
Ground Trip* Latch causes the current to exceed the specified value.
The specified value varies depending on inverter capacity.
Displayed based on inverse time-limit thermal characteristics to prevent motor
E-Thermal Latch overheating.
Operates when Pr.40 is set to a value other than 0.
Displayed when a 3-phase inverter output has one or more phases in an open
Out Phase
Latch circuit condition.
Open
Operates when bit 1 of Pr.05 is set to 1.
Displayed when a 3-phase inverter input has one or more phases in an open circuit
In Phase Open Latch condition.
Operates only when bit 2 of Pr.05 is set to 1.
Displayed when the inverter has been protected from overload and resultant
overheating, based on inverse time-limit thermal characteristics.
Inverter OLT Latch Allowable overload rates for the inverter are 150% for 1 min and 200% for 4 sec.
Protection is based on inverter rated capacity, and may vary depending on the
device’s capacity.

Displayed when the motor is not connected during inverter operation.


No Motor Trip Latch
Operates when Pr.31 is set to 1.

Relay Open Occurs when the DC voltage relay is not operating when power the is input.
Latch
Trip The Pr-90 code must be set to 1 to operate.

Over Torque Occurs when the output current is higher than the level set in Ou-68.
Latch
Trip 1 Operates when OU-67 is set to 3, 4.

Over Torque Occurs when the output current is higher than the level set in OU-71.
Latch
Trip 2 Operates when OU-70 is set to 3, 4.

Under Torque Occurs when the output current is lower than the level set in OU-68.
Latch
Trip 1 Operates when OU-67 is set to 7, 8.

Under Torque Occurs when the output current is lower than the level set in OU-71.
Latch
Trip 2 Operates when OU-70 is set to 7, 8.

* Ground Trip (GFT) feature is not provided in the products under 4.0 kW. Over current trip (OCT) or over voltage trip (OVT) may occur during low resistance grounding.

LSIS. Co., Ltd. | 19


LSLV
General
Drive G100 Keypad Functions

Fault Trips
Protection functions using abnormal internal circuit conditions and external signals
Keypad Display Name Type Description

Displayed when the temperature of the inverter heat sink exceeds the
Over Heat Latch
specified value.

Displayed when the DC circuit in the inverter detects a specified level of excessive,
Over Current 2 Latch
short circuit current.

Displayed when an external fault signal is provided by the multi-function terminal.


External Trip Latch Set one of the multi-function input terminals at In.65-69 to 4 (External trip) to
enable external trip.
Displayed when the inverter output is blocked by a signal provided from the
BX Level multi-function terminal. Set one of the multi-function input terminals at In.
65-69 to 5 (BX) to enable input block function.
Displayed when an error is detected in the memory (EEPRom), analog-digital
converter output (ADC Off Set), or CPU watchdog (Watch Dog-1, Watch Dog-2).
H/W-Diag Fatal
• EEP Err: An error in reading/Writing parameters due to keypad or memory (EEPRom) fault.
• ADC Off Set: An error in the current sensing circuit (U/V/W terminal, current sensor, etc.).

Displayed when an error is detected in the temperature sensor of the insulated


NTC Open Latch
Gate Bipolar Transistor (IGBT).

Displayed when an error is detected in the cooling fan.


Fan Trip Latch
Set Pr.79 to 0 to activate fan trip (for models below 22kW capacity).

Displayed when pre-PID is operating with functions set at AP.34–AP.36. A fault trip
Pre-PID Fail Latch occurs when a controlled variable (PID feedback) is measured below the set value
and the low feedback continues, as it is treated as a load fault.

Operates when the external brake signal is provided by the multi-function terminal.
Ext-Brake Latch Occurs when the inverter output starting current remains below the set value at
Ad.41. Set either OU.31 or OU.32 to 35 (BR Control).

When the user has set Pr-78 to 2: Free-Run or 3: Dec, pre-overheating warning
Overheat
Latch trip of inverter occurs if the inverter temperature exceeds the temperature set
Pre Alarm
by the user in Pr-77.

Protection functions for communication options


Keypad Display Name Type Description

Displayed when a frequency or operation command error is detected during inverter


Lost
Level operation by controllers other than the keypad (e.g., using a terminal block and a
Command
communication mode). Operates when Pr.12 is set to a value other than 0.

Displayed when the I/O board or external communication card is not connected to
the inverter or there is a bad connection.
IO Board Trip Latch

Displayed when the error code continues for more than 5 sec.
(‘Errc’ -> ’-rrc’ -> ‘E-rc’ -> ’Er-c’ -> ‘Err-‘ -> ’- -rc’ -> ‘Er- -‘ -> ’- - - -‘ -> ’Errc’ -> …)

Displayed when a communication error is detected between the inverter and the
Option Trip -1 Latch
communication board. Occurs when the communication option card is installed.

20 | LSIS Co., Ltd.


General Drive

Warning Messages
Keypad Display Name Description
Displayed when the motor is overloaded. Operates when Pr.17 is set to 1. To operate, select 5.
Over Load Set the digital output terminal or relay (OU.31 or OU.33) to 5 (Over load) to receive overload warning
output signals.
Displayed when the motor is underloaded. Operates when Pr.25 is set to 1.
Under Load Set the digital output terminal or relay (OU.31 or OU.33) to 7 (Under load) to receive underload
warning output signals.
Displayed when the overload time equivalent to 60 % of the inverter overheat protection (inverter IOLT)
level, is accumulated.
INV Over Load
Set the digital output terminal or relay (OU.31 or OU.33) to 6 (IOL) to receive inverter overload warning
output signals.

Lost command warning alarm occurs even with Pr.12 set to 0. The warning alarm occurs based on the
condition set at Pr.13- 15. Set the digital output terminal or relay (OU.31 or OU.33) to 13
Lost Command
(Lost command) to receive lost command warning output signals.
If the communication settings and status are not suitable for P2P, a lost command alarm occurs.

An alarm occurs when the value set at PRT-86 is less than the value set at PRT-87.
Fan Exchange To receive fan exchange output signals, set the digital output terminal or relay (OUT-31 or OUT-33) to 38
(Fan exchange).

Displayed when an error is detected from the cooling fan while Pr.79 is set to 1.
Fan Warning Set the digital output terminal or relay (OU.31 or OU.33) to 8 (Fan warning) to receive fan warning
output signals.

DB Warn %ED Displayed when the DB resistor usage rate exceeds the set value. Set the detection level at Pr.66.

Operates when dr.9 is set to 4. The warning alarm occurs when the motor’s rotor time constant (Tr) is
Retry Tr Tune
either too low or too high.

Overheat Pre When the user has set Pr-78 to 1: Warning, pre-overheating warning of inverter occurs if the inverter
Alarm temperature exceeds the temperature set by the user in Pr-77.

LSIS. Co., Ltd. | 21


LSLV
General
Drive G100 Operation Group

Code Comm. Address Name Keypad Display Setting Range Initial Value Property* V/F SL
- 0h1D00 Target frequency 0.00 0-Maximum frequency(Hz) 0.00 O O O
- 0h1D01 Acceleration time ACC 0.0–600.0(s) 5.0 O O O
- 0h1D02 Deceleration time dEC 0.0–600.0(s) 10.0 O O O
0 Keypad
1 Fx / Rx-1
- 0h1D03 Command source drv 2 Fx / Rx-2 1: Fx / Rx-1 X O O
3 Int 485
4 Fieldbus 1)
0 Keypad-1
1 Keypad-2
2 V1
Frequency reference
- 0h1D04 Frq 4 V0 (Built-in volume) 0: Keypad-1 X O O
source
5 I2
6 Int 485
8 Fiedbus 1)
Multi-step speed
- 0h1D05 St1 0.00-Maximum frequency (Hz) 10.00 O O O
frequency 1
Multi-step speed
- 0h1D06 St2 0.00-Maximum frequency (Hz) 20.00 O O O
frequency 2
Multi-step speed
- 0h1D07 St3 0.00-Maximum frequency (Hz) 30.00 O O O
frequency 3
- 0h1D08 Output current CUr - - O O
Motor revolutions
- 0h1D09 Rpm - O O
per minute
- 0h1D0A Inverter DC voltage dCL - - - O O
- 0h1D0B Inverter output voltage vOL - O O
- 0h1D0C Out of order signal nOn - O O

Select rotation F Forward direction operation


- 0h1D0D drC F O O O
direction r Reverse run
• SL: Sensorless vector control (dr.09), Property: Write-enabled during operation
1) Table of options are provided separately in the option manual.

22 | LSIS Co., Ltd.


Drive Group (PAR → dr) General Drive

Code Comm. Address Name Setting Range Initial Value Property* V/F SL
dr-00 - Jump code 1–99 9 O O O
0 V / F
dr-09 0h1109 Control mode 2 Slip compen 0: V / F X O O
4 IM sensorless
dr-11 0h110B Jog frequency 0.00, Start frequency-Maximum frequency(Hz) 10.00 O O O
dr-12 0h110C Jog run acceleration time 0.0–600.0(s) 20.0 O O O
dr-13 0h110D Jog run deceleration time 0.0–600.0(s) 30.0 O O O

0: 0.2kW
1: 0.4kW
2: 0.75kW
3: 1.1kW
4: 1.5kW
5: 2.2kW Varies by
dr-14 0h110E Motor capacity X O O
6: 3.0kW motor capacity
7: 3.7kW
8: 4.0kW
9: 5.5kW
10: 7.5kW
11:11.0kW

0 Manual
dr-15 0h110F Torque boost mode 0: Manual X O X
1 Auto
dr-16 0h1110 Forward torque boost 0.0–15.0(%) 2.0 X O X
dr-17 0h1111 Reverse torque boost 0.0–15.0(%) 2.0 X O X
30.00-400.00(Hz) [V / F, Slip compen]
dr-18 0h1112 Base frequency 60.00 X O O
40.00-120.00(Hz) [IM sensorless]
dr-19 0h1113 Start frequency 0.01-10.00(Hz) 0.50 X O O
40.00-400.00(Hz) [V / F, Slip compen]
dr-20 0h1114 Maximum frequency 60.00 X O O
40.00-120.00(Hz) [IM sensorless]
dr-26 2) 0h111A Auto torque boost filter gain 1~1000 2 O O X
dr-27 2) 0h111B Auto torque boost motoring gain 0.0–300.0[%] 50.0 O O X
dr-28 2) 0h111C Auto torque boost regeneration gain 0.0–300.0[%] 50.0 O O X
Select ranges inverter displays
at power input
0 Operation frequency
1 Acceleration time
2 Deceleration time
3 Command source
4 Frequency reference source
5 Multi-step speed frequency 1
dr-80 0h1150 Select ranges at power input 0: Operation frequency O O O
6 Multi-step speed frequency 2
7 Multi-step speed frequency 3
8 Output current
9 Motor RPM
10 Inverter DC voltage
11 User select signal (dr.81)
12 Currently out of order
13 Select run direction
• SL: Sensorless vector control (dr.09), Property: Write-enabled during operation
2) Appears when Dr15 is 1 (automatic torque boost).

LSIS. Co., Ltd. | 23


LSLV
General
Drive G100 Drive Group (PAR → dr)

Code Comm. Address Name Setting Range Initial Value Property* V/F SL
14 Output current 2

Select ranges at 15 Motor RPM 2


dr-80 0h1150 0: Operation frequency - - -
power input 16 Inverter DC voltage 2
17 User select signal 2(dr.81)

Monitors user selected code

dr-81 0h1151 Select monitor code 0 Output voltage(V) 0: Output voltage O O O


1 Output power(kW)
2 Torque(kgf ‧ m)

Display changed 0 View all


dr-89 0h03E3 0: View All O O O
parameter display 1 View changed
0 None
1 Smartdownload
dr-91 0h115B Smart copy 3 Smartupload 0: None X O O
4 Remoteupload
5 Remotedownload
0 None
dr-92 0h115C Parameter save 0: None X O O
1 Parameter save
0 No
1 All grp
2 dr grp
3 bA grp
4 Ad grp
5 Cn grp
6 In grp
dr-93 0h115D Parameter initialization 0: No X O O
7 OU grp
8 CM grp
9 AP grp
11 AO grp
12 Pr grp
13 M2 grp
14 run grp
dr-94 0h115E Password registration 0~9999 O O O
dr-95 0h115F Parameter lock settings 0~9999 O O O
dr-97 0h1161 Software version - O O
dr-98 0h1162 Display I / O board version - O O
• SL: Sensorless vector control (dr.09), Property: Write-enabled during operation

24 | LSIS Co., Ltd.


Basic Function Group (PAR → bA) General Drive

Code Comm. Address Name Setting Range Initial Value Property* V/F SL
bA-00 - Jump code 1~99 20 O O O
0 None
1 V1
bA-01 0h1201 Auxiliary reference source 0: None X O O
3 V0
4 I2
0 M+(G*A)
1 Mx (G*A)
2 M / (G*A)

Auxiliary command 3 M+[M*(G*A)]


bA-02 3) 0h1202 0: M+(GA) X O O
calculation type 4 M+G*2(A-50%)
5 Mx[G*2(A-50%)
6 M / [G*2(A-50%)]
7 M+M*G*2(A-50%)
bA-03 3) 0h1203 Auxiliary frequency reference gain -200.0~200.0(%) 100.0 O O O
0 Keypad
1 Fx / Rx-1
bA-04 0h1204 2nd command source 2 Fx / Rx-2 1: Fx / Rx-1 X O O
3 Int 485
4 FieldBus 4)
0 Keypad-1
1 Keypad-2
2 V1
bA-05 0h1205 2nd frequency source 4 V0 0: Keypad-1 O O O
5 I2
6 Int 485
8 FieldBus 4)
0 Linear
1 Square
bA-07 0h1207 V / F pattern 0: Linear X O X
2 User V / F
3 Square 2
0 Max freq
bA-08 0h1208 Acc / Dec reference 0: Max freq X O O
1 Delta freq
0 0.01 sec
bA-09 0h1209 Time scale setting 1 0.1 sec 1: 0.1 sec X O O
2 1 sec
0 60Hz
bA-10 0h120A input power frequency 0: 60Hz X O O
1 50Hz
bA-11 0h120B Number of motor poles 2~48 X O O
bA-12 0h120C Rated slip speed 0~3000(Rpm) Dependent X O O
bA-13 0h120D Motor rated current 1.0~1000.0(A) on motor setting X O O
bA-14 0h120E Motor noload current 0.0~1000.0(A) X O O
bA-15 0h120F Motor rated voltage 0, 100~480(V) 0 X O O
• In the following table, data shaded in blue will be displayed when the related code has been selected.
• SL: Sensorless vector control (dr.09), Property: Write-enabled during operation
3) Displayed if bA.01 is not set to 0 (None).
4) Table of options are provided separately in the option manual.

LSIS. Co., Ltd. | 25


LSLV
General
Drive G100 Basic Function Group (PAR → bA)

Code Comm. Address Name Setting Range Initial Value Property* V/F SL
bA-16 0h1210 Motor efficiency 64~100(%) Dependent on motor setting X O O
bA-17 0h1211 Load inertia rate 0~8 0 X O O
bA-18 0h1212 Trim power display 70~130(%) 100% O O O
bA-19 0h1213 Input power voltage 170~480V 220 / 380V O O O
0 None
1 All(Rotation type)
bA-20 - Auto tuning 2 All(Static type) 0: None X X O
3 Rs+Lsigma(Rotation type)
6 Tr(Static type)
bA-21 - Stator resistance X X O
Dependent
bA-22 - Leakage inductance Dependent on motor setting X X O
on motor setting
bA-23 - Stator inductance X X O
bA-24 5) - Rotor time constant 25~5000(ms) - X X O
bA-41 6) 0h1229 User frequency 1 0.00-Maximum frequency(Hz) 15.00 X O X
bA-42 6) 0h122A User voltage 1 0-100(%) 25 X O X
bA-43 6) 0h122B User frequency 2 0.00-Maximum frequency(Hz) 30.00 X O X
bA-44 6) 0h122C User voltage 2 0-100(%) 50 X O X
bA-45 6) 0h122D User frequency 3 0.00-Maximum frequency(Hz) 45.00 X O X
bA-46 6) 0h122E User voltage 3 0-100(%) 75 X O X
bA-47 6) 0h122F User frequency 4 0.00-Maximum frequency(Hz) Maximum frequency X O X
bA-48 6) 0h1230 User voltage 4 0-100(%) 100 X O X
bA-53 7) 0h1235 Multi-step speed frequency 4 0.00-Maximum frequency(Hz) 40.00 O O O
bA-54 7) 0h1236 Multi-step speed frequency 5 0.00-Maximum frequency(Hz) 50.00 O O O
bA-55 7) 0h1237 Multi-step speed frequency 6 0.00-Maximum frequency(Hz) Maximum frequency O O O
bA-56 7) 0h1238 Multi-step speed frequency 7 0.00-Maximum frequency(Hz) Maximum frequency O O O
bA-70 0h1246 Multi-step acceleration time 1 0.0–600.0(s) 20.0 O O O
bA-71 0h1247 Multi-step deceleration time 1 0.0–600.0(s) 20.0 O O O
bA-72 8) 0h1248 Multi-step acceleration time 2 0.0–600.0(s) 30.0 O O O
bA-73 8) 0h1249 Multi-step deceleration time 2 0.0–600.0(s) 30.0 O O O
bA-74 8) 0h124A Multi-step acceleration time 3 0.0–600.0(s) 40.0 O O O
bA-75 8) 0h124B Multi-step deceleration time 3 0.0–600.0(s) 40.0 O O O
bA-76 8) 0h124C Multi-step acceleration time 4 0.0~600.0(s) 50.0 O O O
bA-77 8) 0h124D Multi-step deceleration time 4 0.0~600.0(s) 50.0 O O O
bA-78 8) 0h124E Multi-step acceleration time 5 0.0~600.0(s) 40.0 O O O
bA-79 8) 0h124F Multi-step deceleration time 5 0.0~600.0(s) 40.0 O O O
bA-80 8) 0h1250 Multi-step acceleration time 6 0.0~600.0(s) 30.0 O O O
bA-81 8) 0h1251 Multi-step deceleration time 6 0.0~600.0(s) 30.0 O O O
bA-82 8) 0h1252 Multi-step acceleration time 7 0.0~600.0(s) 20.0 O O O
bA-83 8) 0h1253 Multi-step deceleration time 7 0.0~600.0(s) 20.0 O O O
• In the following table, data shaded in blue will be displayed when the related code has been selected.
• SL: Sensorless vector control (dr.09), Property: Write-enabled during operation
5) Displayed when dr.09 is set to 4(IM sensorless).
6) Displayed if either bA.07 or M2.25 is set to 2 (User V / F).
7) Displayed if one of In.65-71 is set to speed–L / M / H.
8) Displayed one of In.65-71 is set to Xcel–L / M / H.

26 | LSIS Co., Ltd.


Expanded Function Group (PAR → Ad) General Drive

Code Comm. Address Name Setting Range Initial Value Property* V/F SL
Ad-00 - Jump code 1~99 24 O O O
Ad-01 0h1301 Acceleration pattern 0 Linear X O O
0: Linear
Ad-02 0h1302 Deceleration pattern 1 S-curve X O O
Ad-03 9) 0h1303 S-curve acceleration start point gradient 1~100(%) 40 X O O
Ad-04 9) 0h 1304 S-curve acceleration end point gradient 1~100(%) 40 X O O
Ad-05 10) 0h1305 S-curve deceleration start point gradient 1~100(%) 40 X O O
Ad-06 10) 0h1306 S-curve deceleration end point gradient 1~100(%) 40 X O O
0 Acc
Ad-07 0h1307 Start mode 0: Acc X O O
1 Dc-start
0 Dec
1 Dc-brake
Ad-08 0h1308 Stop mode 0: Dec X O O
2 Free-run
4 Power braking
0 None
Ad-09 0h1309 Run prevention options 1 Forward prev 0: None X O O
2 Reverse prev
0 No
Ad-10 0h130A Starting with power on 0: No O O O
1 Yes
Ad-12 11) 0h130C Start DC braking time 0.00~60.00(s) 0.00 X O X
Ad-13 0h130D Amount of applied DC 0-inverter rated current(%) 50 X O X
Ad-14 12) 0h130E Output blocking time before DC braking 0.00–60.00(s) 0.10 X O O
Ad-15 12) 0h130F DC braking time 0.00–60.00(s) 1.00 X O O
Ad-16 12) 0h1310 DC braking rate 0 - inverter rated current / motor rated current x 100 (%) 50 X O O
Ad-17 12) 0h1311 DC braking frequency Start frequency-60Hz 5.00 X O O
Ad-20 0h1314 Dwell frequency on acceleration Start frequency-maximum frequency(Hz) 5.00 X O O
Ad-21 0h1315 Dwell operation time on acceleration 0.0–60.0(s) 0.0 X O O
Ad-22 0h1316 Dwell frequency during deceleration Start frequency-maximum frequency(Hz) 5.00 X O O
Ad-23 0h1317 Operation time during deceleration 0.0–60.0(s) 0.0 X O O
0 No
Ad-24 0h1318 Frequency limit 0: No X O O
1 Yes
Ad-25 13) 0h1319 Frequency lower limit value 0.00-Upper limit frequency(Hz) 0.50 O O O
Ad-26 13) 0h131A Frequency upper limit value Lower limit frequency-maximum frequency(Hz) Maximum frequency X O O
0 No
Ad-27 0h131B Frequency jump 0: No X O O
1 Yes
Ad-28 14) 0h131C Jump frequency lower limit 1 0.00-Jump frequency upper limit1(Hz) 10.00 O O O
Ad-29 14) 0h131D Jump frequency upper limit 1 Jump frequency lower limit1-maximum frequency(Hz) 15.00 O O O
Ad-30 14) 0h131E Jump frequency lower limit 2 00-Jump frequency upper limit2(Hz) 20.00 O O O
Ad-31 14) 0h131F Jump frequency upper limit 2 Jump frequency lower limit2-maximum frequency(Hz) 25.00 O O O
• In the following table, data shaded in blue will be displayed when the related code has been selected.
• SL: Sensorless vector control (dr.09), Property: Write-enabled during operation
9) Displayed when Ad. 01 is set to 1 (S-curve).
10) Displayed when the Ad. 02 code is set to 1 (S-curve).
11) Displayed when Ad. 07 is set to 1 (DC-start).
12) Displayed when Ad. 08 is set to 1 (DC-brake).
13) Displayed when the Ad.24 code is set to 1 (Yes).
14) Displayed when the Ad.27 code is set to 1 (Yes).

LSIS. Co., Ltd. | 27


LSLV
General
Drive G100 Expanded Function Group (PAR → Ad)

Code Comm. Address Name Setting Range Initial Value Property* V/F SL
Ad-32 14) 0h1320 Jump frequency lower limit 3 0.00-Jump frequency upper limit3(Hz) 30.00 O O O
Ad-33 14) 0h1321 Jump frequency upper limit 3 Jump frequency lower limit3-maximum frequency(Hz) 35.00 O O O
Ad-41 15) 0h1329 Brake release current 0.0-180.0(%) 50.0 O O O
Ad-42 15) 0h132A Brake release delay time 0.00–10.00(s) 1.00 X O O
Ad-44 15) 0h132C Brake release forward frequency 0.00-Maximum frequency(Hz) 1.00 X O O
Ad-45 15) 0h132D Brake release reverse frequency 0.00-Maximum frequency(Hz) 1.00 X O O
Ad-46 15) 0h132E Brake engage delay time 0.00–10.00(s) 1.00 X O O
Ad-47 15) 0h132F Brake engage frequency 0.00-Maximum frequency(Hz) 2.00 X O O
0 None
Ad-50 0h1332 Energy saving operation 1 Manual 0: None X O X
2 Auto
Ad-51 16) 0h1333 Energy saving amount 0–30(%) 0 O O X
Ad-60 0h133C Acc / Dec time transition frequency 0.00-Maximum frequency(Hz) 0.00 X O O
Ad-61 0h133D Rotation count speed gain 0.1–6000.0[%] 100.0 O O O
0 x1
1 x 0.1
Ad-62 0h133E Rotation count speed scale 2 x 0.01 0: x 1 O O O
3 x 0.001
4 x 0.0001
0 Rpm
Ad-63 0h133F Rotation count speed unit 0: rpm O O O
1 mpm
0 During run
Ad-64 0h1340 Cooling fan control 1 Always on 0: During run O O O
2 Temp control

Up / Down operation 0 No
Ad-65 0h1341 0: No O O O
frequency save 1 Yes
0 None

Output contact on /  1 V1


Ad-66 0h1342 0: None X O O
Off control options 3 V0
4 I2
Ad-67 0h1343 Output contact on level Output contact off level–100.00 % 90.00 X O O
Ad-68 0h1344 Output contact off level -100.00-output contact on level (%) 10.00 X O O
0 Always enable
Ad-70 0h1346 Safe operation selection 0: Always enable X O O
1 DI Dependent
0 Free-run
Ad-71 17) 0h1347 Safe operation stop options 1 Q-Stop 0: Free-run X O O
2 Q-Stop resume
Ad-72 17) 0h1348 Safe operation deceleration time 0.0~600.0(s) 5.0 O O O
• In the following table, data shaded in blue will be displayed when the related code has been selected.
• SL: Sensorless vector control (dr.09), Property: Write-enabled during operation
14) Displayed when the Ad.27 code is set to 1 (Yes).
15) Displayed if either OU.31 or OU.33 is set to 35 (BR Control).
16) Displayed if Ad.50 is not set to 0 (None).
17) Displayed when Ad.70 is set to 1 (DI Dependent).

28 | LSIS Co., Ltd.


General Drive

Code Comm. Address Name Setting Range Initial Value Property* V/F SL

Selection of regeneration 0 No
Ad-74 0h134A 0: No X O O
evasion function for press 1 Yes

Voltage level of regeneration 200V : 300–400V 350


Ad-75 0h134B X O O
evasion motion for press 400V : 600–800V 700
Compensation frequency limit of
Ad-76 18) 0h134C 0.00–10.00 Hz 1.00 X O O
regeneration evasion for press
Ad-77 18) 0h134D Regeneration evasion for press P gain 0.0–100.0% 50.0 O O O
Ad-78 18) 0h134E Regeneration evasion for press I gain 20–30000(ms) 500 O O O
200V: Min 19)–400[V] 390[V]
Ad-79 0h134F DB Unit turn on voltage level X O O
400V: Min 19)–800[V] 780[V]
0 None
Ad-80 0h1350 Fire Mode selection 1 Fire mode 0: None X O O
2 Fire mode test
Ad-81 20) 0h1351 Fire mode operation frequency Start frequency-maximum frequency [Hz] 60.00 X O O
0 Forward
Ad-82 20) 0h1352  Fire mode run direction 0: Forward X O O
1 Reverse
Ad-83 20) Fire mode operation count Not configurable - - - -
• In the following table, data shaded in blue will be displayed when the related code has been selected.
• SL: Sensorless vector control (dr.09), Property: Write-enabled during operation
18) Displayed when the Ad.74 code is set to 1 (Yes).
19) Voltage type which DC converted the bA.19 AC input voltage: +20V (200Vtype), +40V (400V type). 200V type is limited to 350V and 400V type is limited to 600V.
20) Displayed if Ad.80 is not set to 0 (None).

LSIS. Co., Ltd. | 29


LSLV
General
Drive G100 Control Function Group (PAR → Cn)

Code Comm. Address Name Setting Range Initial Value Property* V/F SL
Cn-00 - Jump code 1~99 4 O O O
V / F: 1.0~15.0(kHz)
Heavy duty 3.0
IM: 2.0~15.0(kHz)
Cn-04 21) 0h1404 Carrier frequency X O O
V / F: 1.0~ 5.0(kHz)
Normal duty 2.0
IM: 2.0~5.0(kHz )
Cn-05 0h1405 Switching mode 0 Normal PWM 0: Normal PWM X O O
Cn-09 0h1409 Initial excitation time 0.00~60.00(s) 1.00 X X O
Cn-10 0h140A Initial excitation amount 100.0~300.0(%) 100.0 X X O
Cn-11 0h140B Continued operation duration 0.00~60.00(s) 0.00 X X O

Low - speed torque


Cn-21 0h1415 50~300(%) Varies by motor capacity X X O
compensation gain

Output torque
Cn-22 0h1416 50~300(%) Varies by motor capacity X X O
compensation gain

Speed deviation sub


Cn-23 0h1417 50~300(%) Varies by motor capacity X X O
compensation gain

Speed deviation main


Cn-24 0h1418 50~300(%) Varies by motor capacity X X O
compensation gain

No-load speed deviation


Cn-29 0h141D 0.50~2.00 1.06 O X O
compensation gain

Speed controller
Cn-30 0h141E 2.0~10.0 4.0 O X O
adjustment gain

0 Keypad-1
1 Keypad-2
2 V1
Cn-53 0h1435 Torque limit setting 4 V0 0: Keypad-1 X X O
5 I2
6 Int 485
8 FieldBus
Cn-54 22) 0h1436 Positive-direction reverse torque limit 0.0~200.0(%) 180 O X O
Cn-55 22) 0h1437 Positive-direction regeneration torque limit 0.0~200.0(%) 180 O X O
Cn-56 22) 0h1438 Negative-direction regeneration torque limit 0.0~200.0(%) 180 O X O
Cn-57 22) 0h1439 Negative-direction reverse torque limit 0.0~200.0(%) 180 O X O
0 Flying start-1 23)
Cn-70 0h 1446 Speed search mode selection 0: Flying start-1 X O O
1 Flying start-2
bit 0000–1111
0001 Selects the speed search function at acceleration.
Speed search operation
Cn-71 0h1447 0010 Initialization after a fault trip 0000 24) X O O
selection
0100 Restart after instantaneous power interruption
1000 Starting with power-on
• In the following table, data shaded in blue will be displayed when the related code has been selected.
• SL: Sensorless vector control (dr.09), Property: Write-enabled during operation
21) It is for 5.5~7.5kW.
22) Displayed when dr.09 is set to 4 (IM Sensorless). This will change the initial value of the parameter at Ad.74 (Torque limit) to 150%.
23) Will not be displayed if dr.09 is set to 4 (IM Sensorless).

24) The initial value 0000 will be displayed on the keypad as .

30 | LSIS Co., Ltd.


General Drive

Code Comm. Address Name Setting Range Initial Value Property* V/F SL
Cn-72 25) 0h1448 Speed search reference current 80~200(%) 150 O O O
Flying start-1: 100
Cn-73 26) 0h1449 Speed search proportional gain 0~9999 O O O
Flying start-2: 600 27)
Flying start-1: 200
Cn-74 26) 0h144A Speed search integral gain 0~9999 O O O
Flying start-2: 1000
Cn-75 26) 0h144B Output block time before speed search 0.0~60.0(s) 1.0 X O O
Cn-76 26) 0h144C Speed search estimator gain 50~150(%) 100 O O O
0 No

Cn-77 0h144D Energy buffering selection 1 KEB-1 0: No X O O

2 KEB-2
Cn-78 28) 0h144E Energy buffering start level 110.0~200.0(%) 125.0 X O O
Cn-79 28) 0h144F Energy buffering stop level Cn78~210.0(%) 130.0 X O O
Cn-80 28) 0h1450 Energy buffering P gain 0~20000 1000 O O O
Cn-81 28) 0h1451 Energy buffering I gain 1~20000 500 O O O
Cn-82 28) 0h1452 Energy buffering slip gain 0~2000.0% 30.0 O O O
Cn-83 28) 0h1453 Energy buffering acceleration time 0.0~600.0(s) 10.0 O O O
• In the following table, data shaded in blue will be displayed when the related code has been selected.
• SL: Sensorless vector control (dr.09), Property: Write-enabled during operation
25) Displayed when any of the Cn.71 code bits are set to 1 and Cn70 is set to 0 (Flying start-1).
26) Displayed when any of the Cn.71 code bits are set to 1.
27) The initial value is 1200 when the motor-rated capacity is less than 7.5 kW
28) Displayed when Cn.77 is not set to 0 (No).

LSIS. Co., Ltd. | 31


LSLV
General
Drive G100 Input Terminal Block Function Group (PAR → In)

Code Comm. Address Name Setting Range Initial Value Property* V/F SL
In-00 - Jump code 1~99 65 O O O
In-01 0h1501 Frequency for maximum analog input Start frequency-maximum frequency(Hz) Maximum frequency O O O
In-02 0h1502 Torque at maximum analog input 0.0~200.0(%) 100.0 O X X
In-05 0h1505 V1 input voltage display -12.00~12.00(V) 0.00 - O O
0 Unipolar
In-06 0h1506 V1 input polarity selection 0: Unipolar X O O
1 Bipolar
In-07 0h1507 Time constant of V1 input filter 0~10000(ms) 100 O O O
In-08 0h1508 V1 Minimum input voltage 0.00~10.00(V) 0.00 O O O
In-09 0h1509 V1 output at Minimum voltage(%) 0.00~100.00(%) 0.00 O O O
In-10 0h150A V1 Maximum input voltage 0.00~12.00(V) 10.00 O O O
In-11 0h150B V1 output at Maximum voltage(%) 0.00~100.00(%) 100.00 O O O
In-12 29) 0h150C V1 Minimum input voltage -10.00~ 0.00(V) 0.00 O O O
In-13 29) 0h150D V1 output at Minimum voltage(%) -100.00~0.00(%) 0.00 O O O
In-14 29) 0h150E V1 Maximum input voltage -12.00~ 0.00(V) -10.00 O O O
In-15 29) 0h150F V1 output at Maximum voltage(%) -100.00~0.00(%) -100.00 O O O
Changing rotation 0 No
In-16 0h1510 0: No O O O
direction of V1 1 Yes
In-17 0h1511 V1 quantization level 0.00 30), 0.04~10.00(%) 0.04 X O O
In-35 0h1523 V0 input voltage display 0.00~5.00(V) 0.00 - O O
In-37 0h1525 Time constant of V0 input filter 0~10000(ms) 100 O O O
In-38 0h1526 V0 Minimum input voltage 0.00~5.00(V) 0.00 O X O
In-39 0h1527 V0 output at minimum voltage(%) 0.00~100.00(%) 0.00 O O O
In-40 0h1528 V0 Maximum input voltage 0.00~5.00(V) 5.00 O X O
In-41 0h1529 V0 output at maximum voltage(%) 0.00~100.00(%) 100.00 O O O
Changing rotation 0 No
In-46 0h152E 0: No O O O
direction of V0 1 Yes
In-47 0h152F V0 quantization level 0.00 30), 0.04~ 10.00(%) 0.04 O O O
In-50 0h1532 I2 input voltage display 0~24(mA) 0.00 - O O
In-52 0h1534 I2 input filter time constant 0~10000(ms) 100 O O O
In-53 0h1535 I2 minimum input current 0.00~20.00(mA) 4.00 O O O
In-54 0h1536 I2 output at minimum current(%) 0.00~100.00(%) 0.00 O O O
In-55 0h1537 I2 maximum input current 0.00~24.00(mA) 20.00 O O O
In-56 0h1538 I2 output at maximum current(%) 0.00~100.00(%) 100.00 O O O
0 No
In-61 0h153D Changing rotation direction of I2 0: No O O O
1 Yes
In-62 0h153E I2 quantization level 0.00 29),0.04~10.00(%) 0.04 O O O
0 None
In-65 0h1541 P1 terminal function setting 1: Fx X O O
1 Fx
2 Rx
In-66 0h1542 P2 terminal function setting 2: Rx X O O
3 RST
4 External trip
In-67 0h1543 P3 terminal function setting 5: BX X O O
5 BX
6 JOG
In-68 0h1544 P4 terminal function setting 3: RST X O O
7 Speed-L
8 Speed-M
In-69 0h1545 P5 terminal function setting 7: Sp-L X O O
9 Speed-H
• In the following table, data shaded in blue will be displayed when the related code has been selected.
• SL: Sensorless vector control (dr.09), Property: Write-enabled during operation
29) Displayed when In.06 is set to 1 (Bipolar).
30) Quantizing is not used when set to 0.

32 | LSIS Co., Ltd.


General Drive

Code Comm. Address Name Setting Range Initial Value Property* V/F SL
11 XCEL-L
12 XCEL-M
13 RUN enable
14 3-Wire
15 2nd source
16 Exchange
17 Up
18 Down
20 U / D Clear
21 Analog hold
22 I-Term clear
23 PID Openloop
- - - 24 P Gain2 - - - -
25 XCEL stop
26 2nd motor
27 U / D Enable
33 Baseblock
34 Pre excite
38 Timer in
40 dis Aux ref
46 FWD JOG
47 REV JOG
49 XCEL-H
51 Fire mode
52 KEB-1 Select
P5 – P1
Multi-function input terminal
In-84 0h1554 0 Disable(Off) 1 1111 31) O O O
on filter selection
1 Enable(On)
In-85 0h1555 Multi-function input terminal on filter 0~10000(ms) 10 O O O
In-86 0h1556 Multi-function input terminal off filter 0~10000(ms) 3 O O O
P5 – P1
Multi-function input
In-87 0h1557 0 A contact (NO) 0 0000 32) X O O
terminal selection
1 B contact (NC)
Selects the NO / NC operation 0 NO
In-88 0h1558 0 X O O
command 1 NO/NC
In-89 0h1559 Multi-step command delay time 1-5000(ms) 1 X O O
P5 – P1
Multi-function input
In-90 0h155A 0 release(Off) 0 0000 - O O
terminal status
1 Connection (On)
Bit 0~1
In-99 0h1563 SW1(NPN/PNP), status 0 NPN 0 - O O
1 PNP
• SL: Sensorless vector control (dr.09), Property: Write-enabled during operation

31) The initial value 11111 will be displayed on the keypad as .

32) The initial value 0000 will be displayed on the keypad as .

LSIS. Co., Ltd. | 33


LSLV
General
Drive G100 Output Terminal Block Function Group (PAR → OU)

Code Comm.Address Name Setting Range Initial Value Property* V/F SL


OU-00 - Jump code 1~99 30 O O O
0 Frequency
1 Output current
2 Output voltage
3 DCLink voltage
4 Torque
5 Output power
6 Idse
OU-01 0h1601 Analog output 1 item 7 Iqse 0: Frequency O O O
8 Target freq
9 Ramp freq
10 Speed fdb
12 PID ref value
13 PID fdb value
14 PID output
15 Constant
OU-02 0h1602 Analog output 1 gain -1000.0~1000.0(%) 100.0 O O O
OU-03 0h1603 Analog output 1 bias -100~100(%) 0 O O O
OU-04 0h1604 Analog output 1 filter 0~10000(ms) 5 O O O
OU-05 0h1606 Analog constant output 1 0.0~100.0(%) 0.0 O O O
OU-06 0h1606 Analog output 1 monitor 0.0~1000.0(%) 0.0 - O O
bit 000~111
1 Low voltage
OU-30 0h161E Fault output item 010 33) O O O
2 Any faults other than low voltage
3 Final failure of automatic restart
0 None
1 FDT-1
2 FDT-2
3 FDT-3
4 FDT-4
5 Over load
6 IOL
7 Under load
OU-31 0h161F Multi-function relay 1 item 29: Trip O O O
8 Fan warning
9 Stall
10 Over voltage
11 Low voltage
12 Over heat
13 Lost command
14 Run
15 Stop
• SL: Sensorless vector control (dr.09), Property: Write-enabled during operation

33) The initial value 0000 will be displayed on the keypad as .

34 | LSIS Co., Ltd.


General Drive

Code Comm.Address Name Setting Range Initial Value Property* V/F SL


16 Steady
17 Inverter line
18 Comm line
19 Speed search
21 Regeneration
22 Ready
23 Zero speed
28 Timer out
29 Trip
31 DB Warn%ED
OU-31 0h161F Multi-function relay 1 item 29: Trip O O O
34 On / Off control
35 BR control
36 Reserved
37 FAN exchange
38 Fire mode
40 KEB operating
41 Pre overheat
42 Minor fault
43 Torque detect 1
44 Torque detect 2
0 None
1 FDT-1
2 FDT-2
3 FDT-3
4 FDT-4
5 Over load
6 IOL
7 Under load
8 Fan warning
9 Stall
10 Over voltage
OU-33 0h1621 Multi-function relay 2 item 11 Low voltage 14: Run O O O
12 Over heat
13 Lost command
14 Run
15 Stop
16 Steady
17 Inverter line
18 Comm line
19 Speed search
21 Regeneration
22 Ready
23 Zero speed
• SL: Sensorless vector control (dr.09), Property: Write-enabled during operation

LSIS. Co., Ltd. | 35


LSLV
General
Drive G100 Output Terminal Block Function Group (PAR → OU)

Code Comm.Address Name Setting Range Initial Value Property* V/F SL


28 Timer out
29 Trip
31 DB Warn%ED
34 On / Off control
35 BR Control
36 Reserved
OU-33 0h1621 Multi-function relay 2 item 37 FAN Exchange 14: Run O O O
38 Fire mode
40 KEB Operating
41 Pre overheat
42 Minor fault
43 Torque detect 1
44 Torque detect 2
OU-41 0h1629 Multi-function output monitor - 00 - - -
OU-50 0h1632 Multi-function output on delay 0.00~100.00(s) 0.00 O O O
OU-51 0h1633 Multi-function output off delay 0.00~100.00(s) 0.00 O O O
Relay2, Relay1
Multi-function output
OU-52 0h1634 0 A contact (NO) 00 34) X O O
contact selection
1 B contact (NC)
OU-53 0h1635 Fault output on delay 0.00~100.00(s) 0.00 O O O
OU-54 0h1636 Fault output off delay 0.00~100.00(s) 0.00 O O O
OU-55 0h1637 Timer on delay 0.00~100.00(s) 0.00 O O O
OU-56 0h1638 Timer off delay 0.00~100.00(s) 0.00 O O O
OU-57 0h1639 Detection frequency 0.00-Maximum frequency(Hz) 30.00 O O O
OU-58 0h163A Detection frequency band 0.00-Maximum frequency(Hz) 10.00 O O O
0 None
1 OT cmdspd warn
2 OT warning
3 OT cmdspdtrip
OU-67 35) 0h1643 Torque detection 1 setting 4 OT trip 0 X O O
5 UT cmdspd warn
6 UT warning
7 UT cmdspd trip
8 UT trip
OU-68 0h1644 Torque detection 1 level 0~200.0 (%) 100 X O O
OU-69 0h1645 Torque detection 1 delay time 0.0~10.0 (s) 0.1 X O O
0 None
1 OT cmdspd warn
2 OT warning
3 OT cmdspdtrip
OU-70 36) 0h1646 Torque detection 1 setting 4 OT trip 0 X O O
5 UT cmdspd warn
6 UT warning
7 UT cmdspd trip
8 UT trip
OU-71 0h1647 Torque detection 2 level 0~200.0 (%) 100 X O O
OU-72 0h1648 Torque detection 2 delay time 0.0~10.0 (s) 0.1 X O O
• SL: Sensorless vector control (dr.09), Property: Write-enabled during operation

34) The initial value 0000 will be displayed on the keypad as .


35) Displayed when OU.31,33 is set to 43 (Prt Trq Det1).
36) Displayed when OU.31,33 is set to 44 (Prt Trq Det2).

36 | LSIS Co., Ltd.


Communication Function Group (PAR → CM) General Drive

Code Comm.Address Name Setting Range Initial Value Property* V/F SL


CM-00 - Jump code 1~99 20 O O O
CM-01 0h1701 Built-in communication inverter ID 1~250 1 O O O

Built-in communication 0 Modbus RTU


CM-02 0h1702 0: Modbus RTU O O O
protocol 2 LS Inv 485
0 1200 bps
1 2400 bps
2 4800 bps

Built-in communication 3 9600 bps


CM-03 0h1703 3: 9600 bps O O O
speed 4 19200 bps
5 38400 bps
6 56 Kbps
7 115 Kbps 37)
0 D8 / PN / S1

Built-in communication 1 D8 / PN / S2


CM-04 0h1704 0: D8 / PN / S1 O O O
frame setting 2 D8 / PE / S1
3 D8 / PO / S1
CM-05 0h1705 Transmission delay after reception 0~1000(ms) 5ms O O O
CM-06 38) 0h1706 Communication option S/W version - 0.00 O O O
CM-07 38) 0h1707 Communication option inverter ID 0~255 1 O O O
CM-08 38) 0h1708 Field bus communication speed - 12Mbps - O O
CM-09 38) 0h1709 Communication option LED status - - O O O
CM-30 0h171E Number of output parameters 0~8 3 O O O
CM-31 0h171F Output communication address 1 0000~FFFF Hex 000A O O O
CM-32 0h1720 Output communication address 2 0000~FFFF Hex 000E O O O
CM-33 0h1721 Output communication address 3 0000~FFFF Hex 000F O O O
CM-34 0h1722 Output communication address 4 0000~FFFF Hex 0000 O O O
CM-35 0h1723 Output communication address 5 0000~FFFF Hex 0000 O O O
CM-36 0h1724 Output communication address 6 0000~FFFF Hex 0000 O O O
CM-37 0h1725 Output communication address 7 0000~FFFF Hex 0000 O O O
CM-38 0h1726 Output communication address 8 0000~FFFF Hex 0000 O O O
CM-50 0h1732 Number of input parameters 0~8 2 O O O
CM-51 0h1733 Input communication address 1 0000~FFFF Hex 0005 X O O
CM-52 0h1734 Input communication address 2 0000~FFFF Hex 0006 X O O
CM-53 0h1735 Input communication address 3 0000~FFFF Hex 0000 X O O
CM-54 0h1736 Input communication address 4 0000~FFFF Hex 0000 X O O
CM-55 0h1737 Input communication address 5 0000~FFFF Hex 0000 X O O
CM-56 0h1738 Input communication address 6 0000~FFFF Hex 0000 X O O
CM-57 0h1739 Input communication address 7 0000~FFFF Hex 0000 X O O
CM-58 0h173A Input communication address 8 0000~FFFF Hex 0000 X O O
0 No
CM-68 0h1744 Field bus data swap 0 X O O
1 Yes
CM-70 0h1746 Communication multi-function input 1 0 None 0: None O O O
• In the following table, data shaded in blue will be displayed when the related code has been selected.
• SL: Sensorless vector control (dr.09), Property: Write-enabled during operation
37) 115200bps
38) Displayed only when a communication option card is installed.

LSIS. Co., Ltd. | 37


LSLV
General
Drive G100 Communication Function Group (PAR → CM)

Code Comm.Address Name Setting Range Initial Value Property* V/F SL


CM-71 0h1747 Communication multi-function input 2 1 Fx 0: None O O O
CM-72 0h1748 Communication multi-function input 3 2 Rx 0: None O O O
CM-73 0h1749 Communication multi-function input 4 3 RST 0: None O O O
CM-74 0h174A Communication multi-function input 5 4 External trip 0: None O O O
CM-75 0h174B Communication multi-function input 6 5 BX 0: None O O O
CM-76 0h174C Communication multi-function input 7 6 JOG 0: None O O O
7 Speed-L
8 Speed-M
9 Speed-H
11 XCEL-L
12 XCEL-M
13 Run enable
14 3-wire
15 2nd source
16 Exchange
17 Up
18 Down
20 U / D clear
21 Analog hold

Communication 22 I-term clear


CM-77 0h174D 0: None O O O
multi-function input 8 23 PID openloop
24 P gain2
25 XCEL stop
26 2nd motor
27 U / D enable
33 Baseblock
34 Pre excite
38 Timer in
40 Dis Aux ref
46 FWD JOG
47 REV JOG
49 XCEL-H
51 Fire mode
52 KEB-1 select
CM-86 0h1756 Communication multi-function input monitoring - 0 X O O

Selection of data frame 0 Int485


CM-90 0h175A 0 O O O
communication monitor 1 Keypad
CM-91 0h175B Rev data frame count 0~65535 - X O O
CM-92 0h175C Err data frame count 0~65535 - X O O
CM-93 0h175D NAK data frame count 0~65535 - X O O
0 No
CM-94 39) - Communication data upload 0: No X O O
1 Yes
• In the following table, data shaded in blue will be displayed when the related code has been selected.
• SL: Sensorless vector control (dr.09), Property: Write-enabled during operation
39) Displayed only when a communication option card is installed.

38 | LSIS Co., Ltd.


Application Function Group (PAR → AP) General Drive

Code Comm.Address Name Setting Range Initial Value Property* V/F SL


AP-00 - Jump code 1~99 20 O O O
0 None
Application function
AP-01 0h1801 1 - 0: None X O O
selection
2 Proc PID
AP-16 40) 0h1810 PID output monitor (%) 0.00 - O O
AP-17 40) 0h1811 PID reference monitor (%) 50.00 - O O
AP-18 40) 0h1812 PID feedback monitor (%) 0.00 - O O
AP-19 40) 0h1813 PID reference setting -100.00~100.00(%) 50.00 O O O
0 Keypad
1 V1
3 V0
AP-20 40) 0h1814 PID reference source 0: Keypad X O O
4 I2
5 Int 485
6 Fieldbus
0 V1
2 V0
AP-21 40) 0h1815 PID feedback source 3 I2 0: V1 X O O
4 Int 485
6 Fieldbus
AP-22 40) 0h1816 PID controller proportional gain 0.0~1000.0(%) 50.0 O O O
AP-23 40) 0h1817 PID controller integral time 0.0~200.0(s) 10.0 O O O
AP-24 40) 0h1818 PID controller differentiation time 0~1000(ms) 0 O O O
AP-25 40) 0h1819 PID controller feed-forward compensation gain 0.0~1000.0(%) 0.0 O O O
AP-26 40) 0h181A Proportional gain scale 0.0~100.0(%) 100.0 X O O
AP-27 40) 0h181B PID output filter 0~10000(ms) 0 O O O
0 Process PID
AP-28 40) 0h181C PID Mode 0 X O O
1 Normal PID
AP-29 40) 0h181D PID upper limit frequency PID lower limit frequency-300.00(Hz) 60.00 O O O
AP-30 40) 0h181E PID lower limit frequency -300.00-PID upper limit frequency(Hz) -60.00 O O O
AP-32 40) 0h1820 PID output scale 0.1~1000.0(%) 100.0 X O O
0 No
AP-33 40) 0h181F PID output inverse 0: No X O O
1 Yes
AP-34 40) 0h1822 PID controller motion frequency 0.00-Maximum frequency(Hz) 0.00 X O O
AP-35 40) 0h1823 PID controller motion level 0.0~100.0(%) 0.0 X O O
AP-36 40) 0h1824 PID controller motion delay time 0~9999(s) 600 O O O
AP-37 40) 0h1825 PID sleep mode delay time 0.0~999.9(s) 60.0 O O O
AP-38 40) 0h1826 PID sleep mode frequency 0.00-Maximum frequency(Hz) 0.00 O O O
AP-39 40) 0h1827 PID wake-up level 0~100(%) 35 O O O
0 Below level
AP-40 40) 0h1828 PID wake-up mode setting 1 Above level 0: Below level O O O
2 Beyond level
• In the following table, data shaded in blue will be displayed when the related code has been selected.
• SL: Sensorless vector control (dr.09), Property: Write-enabled during operation
40) Displayed when AP.01 is set to 2 (Proc PID).

LSIS. Co., Ltd. | 39


LSLV
General
Drive G100 Application Function Group (PAR → AP)

Code Comm.Address Name Setting Range Initial Value Property* V/F SL


0 %
1 Bar
2 mBar
3 Pa
4 kPa
5 Hz
AP-42 40) 0h182A PID controller unit selection 6 Rpm 0: % O O O
7 V
8 I
9 kW
10 HP
11 ℃
12 ℉
AP-43 40) 0h182B PID unit gain 0.00~300.00(%) 100.00 O O O
0 x100
1 x10
AP-44 40) 0h182C PID unit scale 2 x1 2: x 1 O O O
3 x 0.1
4 x 0.01
AP-45 40) 0h182D PID 2nd proportional gain 0.0~1000.0(%) 100.0 X O O
• In the following table, data shaded in blue will be displayed when the related code has been selected.
• SL: Sensorless vector control (dr.09), Property: Write-enabled during operation
40) Displayed when AP.01 is set to 2 (Proc PID).

40 | LSIS Co., Ltd.


Protection Function Group (PAR → Pr) General Drive

Code Comm.Address Name Setting Range Initial Value Property* V/F SL


Pr-00 - Jump code 1~99 40 O O O
0 Normal duty
Pr-04 0h1B04 Load level setting 1: Heavy duty X O O
1 Heavy duty
bit 00~11
Input / Output open-phase
Pr-05 0h1B05 01 Output open phase 00 41) X O O
protection
10 Input open phase
Pr-06 0h1B06 Input voltage range during open-phase 1~100(V) 15 X O O
Pr-07 0h1B07 Deceleration time at fault trip 0.0~600.0(s) 3.0 O O O

Selection of startup 0 No
Pr-08 0h1B08 0: No O O O
on trip reset 1 Yes
Pr-09 0h1B09 Number of automatic restarts 0~10 0 O O O
Pr-10 42) 0h1B0A Automatic restart delay time 0.0~60.0(s) 1.0 O O O
0 None
1 Free-run

Motion at speed 2 Dec


Pr-12 0h1B0C 0: None O O O
command loss 3 Hold input
4 Hold output
5 Lost preset
Pr-13 43) 0h1B0D Time to determine speed command loss 0.1~120(s) 1.0 O O O
Pr-14 43) 0h1B0E Operation frequency at speed command loss 0, Start frequency-maximum frequency(Hz) 0.00 O O O

Analog input loss 0 Half of x1


Pr-15 43) 0h1B0F 0: Half of x1 O O O
decision level 1 Below x1
0 No
Pr-17 0h1B11 Overload warning selection 0: No O O O
1 Yes
Pr-18 0h1B12 Overload warning level 30~180(%) 150 O O O
Pr-19 0h1B13 Overload warning time 0.0~30.0(s) 10.0 O O O
0 None
Pr-20 0h1B14 Motion at overload fault 1 Free-run 1: Free-run O O O
2 Dec
Pr-21 0h1B15 Overload fault level 30~200(%) 180 O O O
Pr-22 0h1B16 Overload fault time 0.0~60.0(s) 60.0 O O O
0 No
Pr-25 0h1B19 Under load warning selection 0: No O O O
1 Yes
Pr-26 0h1B1A Under load warning time 0.0~600.0(s) 10.0 O O O
0 None
Pr-27 0h1B1B Under load fault selection 1 Free-run 0: None O O O
2 Dec
Pr-28 0h1B1C Under load fault time 0.0~600.0(s) 30.0 O O O
Pr-29 0h1B1D Under load lower limit level 10~100(%) 30 O O O
• In the following table, data shaded in blue will be displayed when the related code has been selected.
• SL: Sensorless vector control (dr.09), Property: Write-enabled during operation

41) The initial value 0000 will be displayed on the keypad as .


42) Displayed when Pr.09 is set higher than 0.
43) Displayed when Pr.12 is not set to 0 (NONE).

LSIS. Co., Ltd. | 41


LSLV
General
Drive G100 Protection Function Group (PAR → Pr)

Code Comm.Address Name Setting Range Initial Value Property* V/F SL


Pr-30 0h1B1E Under load upper limit level 10~100(%) 30 O O O
0 None
Pr-31 0h1B1F No motor motion at detection 0: None O O O
1 Free-run
Pr-32 0h1B20 No motor detection current level 1~100(%) 5 O O O
Pr-33 0h1B21 No motor detection time 0.1~10.0(s) 3.0 O O O
0 None
Electronic thermal fault
Pr-40 0h1B28 1 Free-run 0: None O O O
selection
2 Dec
0 Self-cool
Pr-41 0h1B29 Motor cooling fan type 0: Self-cool O O O
1 Forced-cool
Pr-42 0h1B2A Electronic thermal 1 minute rating 120~200(%) 150 O O O
Pr-43 0h1B2B Electronic thermal continuous rating 50~150(%) 120 O O O
0 Free-run
Pr-45 0h1B2D BX trip mode 0 X O O
1 Dec
bit 0000~1111
0001 Accelerating
Stall prevention motion
Pr-50 0h1B32 0010 At constant speed 0000 X O X
and flux braking
0100 Decelerating
1000 Fluxbraking
Pr-51 0h1B33 Stall frequency 1 Start frequency-stall frequency2(Hz) 60.00 O O X
Pr-52 0h1B34 Stall level 1 30~250(%) 180 X O X
Pr-53 0h1B35 Stall frequency 2 Start frequency1-stall frequency2(Hz) 60.00 O O X
Pr-54 0h1B36 Stall level 2 30~250(%) 180 X O X
Pr-55 0h1B37 Stall frequency 3 Start frequency2-stall frequency4(Hz) 60.00 O O X
Pr-56 0h1B38 Stall level 3 30~250(%) 180 X O X
Pr-57 0h1B39 Stall frequency 4 Stall frequency3-maximum frequency(Hz) 60.00 O O X
Pr-58 0h1B3A Stall level 4 30~250(%) 180 X O X
Pr-59 0h1B3B Flux braking gain value 0~150[%] 0 O O O
Pr-66 0h1B42 DB resistor warning level 0~30(%) 10 O O O
Pr-77 0h1B4D Pre-overheat warning temperature 90-110 90 O O O
0 None

Pre-overheat warning 1 Warning


Pr-78 0h1B4E 0 O O O
operation selection 2 Freerun
3 Dec
0 Trip
Pr-79 0h1B4F Cooling fan fault selection 1: Warning O O O
1 Warning
0 None
Motion selection at
Pr-80 0h1B50 1 Free-run 1: Free-run O O O
option trip
2 Dec
Pr-81 0h1B51 Low voltage fault decision delay time 0.0~60.0(s) 0.0 X O O
0 No
Pr-82 0h1B52 LV2 Selection 0 X O O
1 Yes
Pr-86 0h1B56 Accumulated percent of fan usage 0.0~100.0[%] 0.0 - O O
Pr-87 0h1B57 Fan exchange warning level 0.0~100.0[%] 90.0 O O O
• SL: Sensorless vector control (dr.09), Property: Write-enabled during operation

42 | LSIS Co., Ltd.


General Drive

Code Comm.Address Name Setting Range Initial Value Property* V/F SL


0 No
Pr-88 0h1B58 Fan reset time 0 X O O
1 Yes
Bit 00~01
Pr-89 0h1B59 Fan status 00 - 0 - O O
01 Fan exchange
Pr-90 0h1B5A Relay open trip selection - - X O O
Pr-91 0h1B5B Fault history 1 - - - O O
Pr-92 0h1B5C Fault history 2 - - - O O
Pr-93 0h1B5D Fault history 3 - - - O O
Pr-94 0h1B5E Fault history 4 - - - O O
Pr-95 0h1B5F Fault history 5 - - - O O
0 No
Pr-96 0h1B60 Fault history deletion 0: No O O O
1 Yes
• SL: Sensorless vector control (dr.09), Property: Write-enabled during operation

LSIS. Co., Ltd. | 43


LSLV
General
Drive G100 2nd Motor Function Group (PAR → M2)

Code Comm.Address Name Setting Range Initial Value Property* V/F SL


M2-00 - Jump code 1~99 14 O O O
M2-04 0h1C04 Acceleration time 0.0~600.0(s) 20.0 O O O
M2-05 0h1C05 Deceleration time 0.0~600.0(s) 30.0 O O O
0 0.2 kW
1 0.4 kW
2 0.75 kW
3 1.1 kW
4 1.5 kW
5 2.2 kW
M2-06 0h1C06 Motor capacity - X O O
6 3.0 kW
7 3.7 kW
8 4.0 kW
9 5.5 kW
10 7.5 kW
11 11.0kW
M2-07 0h1C07 Base frequency 30.00~400.00(Hz) 60.00 X O O
0 V / F
M2-08 0h1C08 Control mode 2 Slip compen 0: V / F X O O
4 IM sensorless
M2-10 0h1C0A Number of motor poles 2~48 X O O
M2-11 0h1C0B Rated slip speed 0~3000(Rpm) X O O
M2-12 0h1C0C Motor rated current 1.0~1000.0(A) X O O
M2-13 0h1C0D Motor noload current 0.5~1000.0(A) X O O
M2-14 0h1C0E Motor rated voltage 170~480(V) X O O
Dependent on motor
M2-15 0h1C0F Motor efficiency 64~100(%) X O O
setting
M2-16 0h1C10 Load inertia rate 0~8 X O O
M2-17 - Stator resistance X O O
M2-18 - Leakage inductance Dependent on motor setting X O O
M2-19 - Stator inductance X O O
M2-20 44) - Rotor time constant 25~5000(ms) X O O
0 Linear

M2-25 0h1C19 V / F pattern 1 Square 0: Linear X O O

2 User V / F

M2-26 0h1C1A Forward torque boost 0.0~15.0(%) X O O


2.0
M2-27 0h1C1B Reverse torque boost 0.0~15.0(%) X O O

M2-28 0h1C1C Stall prevention level 30~150(%) 150 X O O

M2-29 0h1C1D Electronic thermal 1 minute rating 100~200(%) 150 X O O

M2-30 0h1C1E Electronic thermal continuous rating 50–Electronic thermal 1 minute rating 100 X O O

M2-31 0h1C1F Low-speed torque compensation gain 50~300(%) Varies by motor capacity X X O

• In the following table, data shaded in blue will be displayed when the related code has been selected.
• The 2nd Motor function group will be displayed if any of In.65-71 is set to 26 (2nd motor).
• SL: Sensorless vector control (dr.09), Property: Write-enabled during operation
44) Displayed when M2.08 is set to 4(IM Sensorless).

44 | LSIS Co., Ltd.


Peripheral Devices General Drive

Code Comm.Address Name Setting Range Initial Value Property* V/F SL


M2-32 0h1C20 Output torque compensation gain 50~300(%) Varies by motor capacity X X O

M2-33 0h1C21 Speed deviation sub compensation gain 50~300(%) Varies by motor capacity X X O

M2-34 0h1C12 Speed deviation main compensation gain 50~300(%) Varies by motor capacity X X O

M2-40 0h1C28 Rotation count speed gain 0.1~6000.0[%] 100.0 O O O

0 x1

1 x 0.1

M2-41 0h1C29 Rotation count speed scale 2 x 0.01 0: x 1 O O O

3 x 0.001

4 x 0.0001

0 Rpm
M2-42 0h1C2A Rotation count speed unit 0: rpm O O O
1 mpm

• The 2nd Motor function group will be displayed if any of In.65-71 is set to 26 (2nd motor).
• SL: Sensorless vector control (dr.09), Property: Write-enabled during operation

LSIS. Co., Ltd. | 45


LSLV
General
Drive G100 Peripheral Devices

Braking Resistor Specification


Capacity(kW) Resistance(Ω) Rated Capacity(W)
0.4 300 100
0.75 150 150
1.5 60 300
3-Phase 2.2 50 400
200V Class 3.7 33 600
4 33 600
5.5 20 800
7.5 15 1200
0.4 1200 100
0.75 600 150
1.5 300 300
3-Phase 2.2 200 400
400V Class 3.7 130 600
4 130 600
5.5 85 1000
7.5 60 1200
* The standard for braking torque is 150% and the working rate (%ED) is 5%. If the working rate is 10%, the rated capacity for braking resistance must be calculated at twice the standard.

Compatible Circuit Breaker, Leakage Breaker and Magnetic Contactor Models (Manufactured by LSIS)
Circuit Breaker Leakage Breaker Magnetic Contactor
Capacity(kW)
Model Current(A) Specific Model Name Model Current(A) Model Current(A)
0.4 5 MC-6a 9
0.75 15 UTE100·H·FTU·15·3P·UL 10 MC-9a, MC-9b 11
3-Phase 1.5 UTE100H EBS33c 15 MC-18a, MC-18b 18
200V 2.2 20 UTE100·H·FTU·20·3P·UL 20 MC-22b 22
Class 4.0 30 UTE100·H·FTU·30·3P·UL 30 MC-32a 32
5.5 50 UTS150·H·FTU·50·3P·UL EBS53c 50 MC-50a 55
UTS150H
7.5 60 UTS150·H·FTU·60·3P·UL EBS63c 60 MC-65a 65
0.4 MC-6a
5 7
0.75 MC-6a
15 UTE100·E·FTU·15·3P·UL
3-Phase 1.5 MC-9a, MC-9b 9
10
400V 2.2 UTE100E EBS33c MC-12a, MC-12b 12
Class 4.0 20 UTE100·E·FTU·20·3P·UL 20 MC-18a, MC-18b 18
5.5 MC-22b 22
30 UTE100·E·FTU·30·3P·UL 30
7.5 MC-32a 32

Fuse and Reactor Specifications


AC Input Fuse AC Reactor
Capacity (kW)
Model Current (A) Voltage (V) Inductance (mH) Current (A)
0.4
DFJ-10 1) 10 1.20 10
0.75
3-Phase 1.5 DFJ-15 15 0.88 14
200V 2.2 DFJ-20 20 0.56 20
Class 4.0 DFJ-30 30 0.39 30
5.5 DFJ-50 50 0.30 34
7.5 DFJ-60 60 0.22 45
600
0.4
4.81 4.8
0.75 DFJ-10 10
3-Phase 1.5 3.23 7.5
400V
2.2 DFJ-15 15 2.34 10
Class
4.0 DFJ-20 20 1.22 15
5.5 DFJ-30 30 1.12 19
7.5 DFJ-35 35 0.78 27
Note1) DFJ is class J / 600V level model name of the bussmann company.

Caution Use class CC, G, J, L, R or T UL listed Input fuse and UL listed breaker only. See the table above for the voltage and current rating of the fuse and the breaker.

46 | LSIS Co., Ltd.


Drive Watt Loss Data General Drive

HD ND
Rated
Voltage Model Number Power Rated Heat Rated Heat
Total Internal Total Internal
(kW) Output Losses Output Losses
Losses(W) Losses(W) Losses(W) Losses(W)
Current(A) (Kacl) Current(A) (Kacl)

220 LSLV0004G100-2 0.4 2.5 19 16.8 2 3.1 24 16.8 7


220 LSLV0008G100-2 0.75 5.0 34 16.8 14 6.0 37 16.8 17
220 LSLV0015G100-2 1.5 8.0 50 17.4 28 9.6 59 17.4 35
220 LSLV0022G100-2 2.2 11.0 80 17.4 54 12.0 89 17.4 62
220 LSLV0037G100-2 4.0 17.0 127 17.7 94 18.0 160 17.7 122
220 LSLV0055G100-2 5.5 24.0 173 18.7 132 30.0 267 18.7 214
220 LSLV0075G100-2 7.5 32.0 247 18.7 197 40.0 398 18.7 326
440 LSLV0004G100-4 0.4 1.3 21 17.4 3 2.0 22 17.4 4
440 LSLV0008G100-4 0.75 2.5 25 17.4 7 3.1 31 17.4 12
440 LSLV0015G100-4 1.5 4.0 40 17.7 19 5.1 47 17.7 25
440 LSLV0022G100-4 2.2 5.5 54 17.7 31 6.9 57 17.7 33
440 LSLV0037G100-4 4.0 9.0 93 18.7 64 10.0 125 18.7 91
440 LSLV0055G100-4 5.5 12.0 170 19.7 129 16.0 153 19.7 115
440 LSLV0075G100-4 7.5 16.0 194 19.7 149 23.0 225 19.7 177

Total losses
Capacity(kW) x (1-Efficiency/100) x 1000 = W
ex) 0.4kW x (1- 95.3/100) x 1000 = 18.8W
Total losses = Internal loss + External loss

Internal losses
Based on design standard such as SMPS Rated Capacity, Fan and so forth

External(Heat) losses
1wh = 3,600J,1kcal = 4,186 J
Efficiency= Output/(Output+Loss)*100=Output/Input*100
Loss*0.9=Heat Loss
-> Other Loss 0.1
Σ(The number of installed drive at each capacity*Heat) = Total amount of Heat

LSIS. Co., Ltd. | 47


LSLV
General
Drive G100 Dimensions

0.4~0.75kW (0004G100-2, 0008G100-2, 0004G100-4, 0008G100-4) Units: mm(Inches)

∅4 86.4 (3.40)

5 (0.20)
.5 ( 76.2 (3.00) 139.7 (5.50)
0.1
8)

164.2 (6.46)
154 (6.06)

153.8 (6.06)

101.5 (4.00)
4.5 (0.18)
131.5 (5.18)

1.5~2.2kW (0015G100-2, 0022G100-2, 0015G100-4, 0022G100-4) Units: mm(Inches)

∅4 101.2 (3.98)
5 (0.20)

.5 ( 158.7 (6.25)
0.1 90 (3.54)
8)
177.2 (6.98)
167 (6.57)

166.9 (6.57)

114.5 (4.51)

4.5 (0.18)
151.1 (5.95)

48 | LSIS Co., Ltd.


General Drive

4.0kW (0040G100-2, 0040G100-4) Units: mm(Inches)

158.8 (6.25)
∅ 135 (5.31)
4.5
(0. 125 (4.92)
18
)

182.8 (7.20)
193 (7.60)
183 (7.20)

130.4 (5.13)
4.5 (0.18) 150.5 (5.93)

5.5~7.5kW (0055G100-2, 0075G100-2, 0055G100-4, 0075G100-4) Units: mm(Inches)

)
.18
180.3 (7.10) (0
6.5 (0.23)

162 (6.38) 4.5 152.2 (5.99)



9(
0.3
12.1 (0.48)

5)
240.3 (9.46)

219.8 (8.65)
223 (8.78)

4.5 (0.18)
144 (5.67)
170 (6.69)

LSIS. Co., Ltd. | 49


Global LSIS is engaged in business all over the world.
LSIS global network includes 7 overseas corporations,
Network 12 overseas branches, and 224 clients in 77 countries.

▶R&D ▶Factory

R&D Campus Power Device R&D Center Automation R&D Center PT&T (Testing laboratory) Cheongju Factory (Korea)
Focuses on gaining competitive Leading technology in electric Serves as the main research Internationally-renowned testing Electric products, mold TR,
advantages through development industry and continuously institute for LSIS center that has formed partner- MV/LV switchgear, HV GIS
of next generation platforms developing future-growth ships with the UL, CE, KEMA
dynamic engines and CESI
Head office
Domestic business establishment
Anyang Overseas manufacturing plant
R&D center
Head office Cheonan factory Overseas sales corporation
Cheonan Automation소R&D center
Overseas branch
Cheongju factory 1
Cheongju factory 2 Global service center
Cheongju Power device R&D center
PT&T(Power Testing & Technology Institute) Global R&D center
Presence internationally : 77 countries

Busan
Busan factory

Cheonan Factory (Korea) Busan Factory (Korea) Wuxi Factory (China) Dalian Factory (China) Hanoi Factory (Vietnam)
PLC, AC drive, HMI, DCS, HV TR, HVDC, FACTS Electric products MV/LV switchgear, MV contactor MV/LV switchgear, Mold TR
PV module
■Head Quarter • LSIS Beijing Office (China)
LS Yongsan Tower, 92, Hangang-daero, Yongsan-gu, Seoul, 04386, Korea Tel: 86-10-5761-3127 Fax: 86-10-5761-3128 E-Mail: sson@lsis.com
Tel : 82-2-2034-4286 Fax : 82-2-2034-4648 E-mail : mswoo@lsis.com • LSIS Guangzhou Office (China)
Tel: 86-20-8326-6784 Fax: 86-20-8326-6287 E-Mail: sojhtroh@lsis.com
■Overseas Subsidiaries
• LSIS Qingdao Office (China)
• LSIS(Shanghai) Co., Ltd. /CHINA
Tel: 86-532-8501-6058 Fax: 86-532-8501-6057 E-Mail: sson@lsis.com
Tel : 86-21-5237-9977(609) Fax : 86-21-5237-7189
• LSIS Chengdu Office (China)
• LSIS(Dalian) Co., Ltd. (Dalian, China)
Tel: 86-28-8670-3200 Fax: 86-28-8670-3203 E-Mail: yangcf@lsis.com
Tel: 86-411-8730-7510 Fax: 86-411-8730-7560 E-Mail: jiheo@lsis.com
• LSIS ShenYang Office (China)
• LSIS(Wuxi) Co., Ltd. (Wuxi, China)
Tel:86-24-2321-9050 Fax: 86-24-8386-7210 E-Mail: yangcf@lsis.com
Tel: 86-510-8534-6666-8005 Fax: 86-510-8534-4078 E-Mail: sunhwank@lsis.com
• LSIS Jinan Office (China)
• LS VINA Industrial Systems Co., Ltd. (Hanoi, Vietnam)
Tel: 86-531-8699-7826 Fax: 86-531-8697-7628 E-Mail: yangcf@lsis.com
Tel: 84-24-3882-0222 Fax: 84-24-3882-0220 E-Mail: jhchoi4@lsis.com
• LSIS Co., Ltd. Tokyo Office (Japan)
• LSIS Middle East FZE (Dubai, U.A.E.)
Tel: 81-3-6268-8241 Fax: 81-3-6268-8240 E-Mail: jschuna@lsis.com
Tel: 971-4-886-5360 Fax: 971-4-886-5361 E-Mail: hschoib@lsis.com
• LSIS Co., Ltd. Rep. Office (Vietnam)
• LSIS Europe B.V. (Amsterdam, Netherlands)
Tel: 84-28-3823-7890 E-Mail: sjbaik@lsis.com
Tel: 31-20-654-1420 Fax: 31-20-654-1429 E-Mail: htha@lsis.com
• LSIS Moscow Office (Russia)
• LSIS Japan Co., Ltd. (Tokyo, Japan)
Tel: 7-499-682-6130 E-Mail: jdpark1@lsis.com
Tel: 81-3-6268-8241 Fax: 81-3-6268-8240 E-Mail: jschuna@lsis.com
• LSIS Jakarta Office (Indonesia)
• LSIS USA Inc. (Chicago, U.S.A.)
Tel: 62-21-2933-7614 E-Mail: dioh@lsis.com
Tel: 1-800-891-2941 Fax: 1-847-383-6543 E-Mail: sales.us@lsis.com
• LSIS Bangkok Office (Thailand)
■Overseas Branches Tel: 66-90-950-9683 E-Mail: sjleet@lsis.com
• LSIS Shanghai Office (China)
Tel: 86-21-5237-9977(609) Fax: 86-21-5237-7189 E-Mail: ygeo@lsis.com

2019. 07 2019. 07 LSIS Co., Ltd. All Rights Reserved. / (01) 2019. 07 HumanPower

You might also like