General AC Drive: 3-Phase 200 240V 0.4 22kW (0.5 30HP) 3-Phase 380 480V 0.4 22kW (0.5 30HP)
General AC Drive: 3-Phase 200 240V 0.4 22kW (0.5 30HP) 3-Phase 380 480V 0.4 22kW (0.5 30HP)
General AC Drive: 3-Phase 200 240V 0.4 22kW (0.5 30HP) 3-Phase 380 480V 0.4 22kW (0.5 30HP)
General Drive
G100
02 | LSIS Co., Ltd.
General AC Drive G100
Great Reliability
• Meets UL 61800-5-1
• Military (MIL 217Plus) design based
methodology
The G100 is the • Enhanced materials and
manufacturing processes
solution for general
drives applications because Great Performance
of its high performance • Enhanced motor control-sensorless
& V/F performance
sensorless operation, • User-friendly-easy tuning
sensorless control
premium quality and • Suitable for most applications
high reliability.
User Friendly
• Easy to install, use and maintain
• Various options
UL 61800-5-1*1) Design
Great Satisfied the new UL certification
*1) After February 2020 all of system, product have to satisfy new UL certification
Reliability
Robust Design
Construction of the air flow design minimizes exposure of critical components
(IGBT, PCB, etc.) from outside contaminants.
Fan Lifecycle Display fan replacement warning message with digital output or keypad
Diagnosis
Drive
Run Signal
Time (s)
FAN
Usage Rate
PRT- 87
Time (s)
FAN
Warning
Standard fan run-time is 50,000 hours, and the fan replacement level(PRT-87)
should be set according to the environment
MIL217Plus based • Reliability design basis tool (PSA, Fr-FMEA, FTA, RBD, PBS)
• Improved circuit robustness through strict quality margins
Design
Category G100
240,455 hrs(27 yrs)
Estimated Life Cycle
(Accelerated life test result : 295,951 hrs)
Reliablity Test Method MTTF
MIL-HDBK-217F
Standard
RIAC HDBK 217Plus
Ambient Temperature 30°C (86°F)
Material Design • Enhanced thermal resistance and intensity through upgraded materials
• Increased thickness to prevent damage
Heavy Duty
Hoist Conveyor Compressor
Normal Duty
Pump Fan
Application Adaptability
Great Dual ratings enable use in most applications
Torque (%)
200%
0.5Hz
150%
1Hz
3Hz 100%
5Hz
10Hz 50%
20Hz 0%
-50%
30Hz
40Hz
50Hz -100%
-150%
55Hz
60Hz
-200%
0 200 400 600 800 1000 1200 1400 1600 1800 2000
Operating Speed (RPM)
KEB (Kinetic • KEB for a stable system stop in case of power loss or failure.
Energy Buffering) • Select KEB operation function for different speeds and purposes
Flying Start Select optimal flying start operation for different applications
Power Failure
Frequenccy
(Hz) Motor Rotation Speed
Time (s)
Operation
Command ON ON
❶ ❺
❷ Fieldbus Options
❺ DIN rail Mount (Below 4kW)
Provides various communication options
Install using DIN rails (Side-by-side)
with simple mounting structure
• Dual Port EtherNet/IP
• Profibus-DP
• CANopen
❻ Fan Replacement
Ethernet 2 port support
Simple cooling fan replacement procedure
❷ PC Tools (DriveView 9)
New version of PC tool
❽ Operation Group
❹ Built-in 2 Relay • Access commonly used parameters in
Cost efficient and easy to compose system the operation group
with two embedded relays. • Identical Parameter group structure for
all 100 series
11 kW
15 kW
18.5 kW
22 kW
LSLV 055
0008 055
G100 -- 4 E O F N
Keypad UL Type
E : LED Keypad O : UL Open
Rated Current Heavy Duty (HD) 2.5 5.0 8.0 11.0 17.0 24.0 32.0
(3-Phase Input) [A] Normal Duty (ND) 3.1 6.0 9.6 12.0 18.0 30.0 40.0
Output
Rating Heavy Duty (HD) 1.5 2.8 4.6 6.1 9.3 12.8 17.4
Rated Current
(1-Phase Input) [A] Normal Duty (ND) 2.0 3.6 5.9 6.7 9.8 16.3 22.0
Frequency [Hz] 0~400Hz (IM sensorless: 0~120Hz)
Voltage [V] 3-Phase 200~240V
Voltage [V] 3-Phase 200~240VAC (-15%~+10%)
Rated Current Heavy Duty (HD) 1.3 2.5 4.0 5.5 9.0 12.0 16.0
(3-Phase Input) [A] Normal Duty (ND) 2.0 3.1 5.1 6.9 10.0 16.0 23.0
Output
Rating Heavy Duty (HD) 0.7 1.4 2.1 2.8 4.9 6.4 8.7
Rated Current
(1-Phase Input) [A] Normal Duty (ND) 1.3 1.9 2.8 3.6 5.4 8.7 12.6
Frequency [Hz] 0~400Hz (IM sensorless: 0~120Hz)
Voltage [V] 3-Phase 380~480V
Voltage [V] 3-Phase 380~480VAC (-15%~+10%)
Control
Control Method V/F, Slip Compensation, Sensorless Vector
Operation
Operation Mode Select key pad, terminal strip, or communication operation
Multi-Function Terminal Function: Forward run, Reverse run, Reset, External trip, Emergency stop, Jog operation, Multi-step frequency-
(5 Points) high, middle, low, Multi-step acceleration/ deceleration-high, middle, low, DC braking at stop, 2nd motor select,
Input
Frequency up/down, 3-wire operation, Change into normal operation during PID operation, Change into main body
operation during option operation, Analog command frequency fixing, Acceleration/deceleration stop etc. Selectable
Analog Input V1: -10~10V, I2 4~20mA
Multi-function Relay Terminal Fault output and drive operation status output (N.O., N.C.) less than AC 250V 1A, less than DC 30V 1A
Output
Analog Output 0~12Vdc: Frequency, Output current, Output voltage, DC stage voltage etc. selectable
Protective Function
Over current trip, external signal trip, ARM short Over voltage trip, temperature sensor trip, inverter
current fault trip, over heat trip, input imaging trip, over heat, option trip, output image trip, inverter
ground trip, motor over heat trip, I/O board link trip, overload trip, fan trip, pre-PID operation failure
Trip
no motor trip, parameter writing trip, emergency external brake trip, low voltage trip during operation,
stop trip, command loss trip, external memory error, low voltage trip, analog input error, motor overload
CPU watchdog trip, motor light load trip trip, over torque trip, under torque trip
Command loss trip warning, overload warning, light load warning, inverter overload warning,
Alarm fan operation warning, braking resistance braking rate warning, rotor time constant tuning error,
inverter pre-overheat warning, over torque warning, under torque warning
HD below 15ms (ND below 8ms): Continuous operation (To be within rated input voltage, rated output)
Momentary Power Loss
HD above 15ms (ND above 8ms): Automatic restart operation enable
Environment
Cooling Type Forced fan cooling structure
Protection Degree IP20/UL Open (Default), UL Enclosed type 1 (Option)
Ambient temperature under the condition of no ice or frost.
Ambient Temperature HD: -10~50℃(14~122°F) / ND: -10~40℃(14~104°F)
[However, recommended to use load below 80% when using at 50°C under light load]
Humidity Relative humidity below 95% RH (no dew formation)
Storage Temperature -20~65℃(-4~149°F)
Location No corrosive gas, flammable gas, oil mist and dust etc. indoors (Pollution degree 2 environment)
Below 1,000m (From 1000 to 4000m, the rated input voltage and rated output current
Altitude, Vibration
of the drive must be derated by 1% for every 100m.), below 9.8m/sec2 (1G)
Pressure 70~106kPa
Multi-function input
(Default)
SW2 S+ RS485
FX P1
SW1
ON OFF S-
RX P2 NPN PNP
BX Switch Description
P3 Analog output
SW1 NPN/PNP mode selection switch AO
(Default: Frequency)
SW2 Terminating resistor selection switch
RST P4
CM
C1
A1
Relay output 1
(Default: Trip)
Analog input B1
VR
V1
CM
C2
I2 Relay output 2
(Default: Run)
A2
5.5 / 7.5kW
0.4
0.75
R / S / T, U / V / W : M3.5 R / S / T, U / V / W : 10.3 / 1.0
1.5
3-Phase
2.2
400V Class
4 R / S / T, U / V / W : M4 R / S / T, U / V / W : 18.4 / 1.8
5.5 R / S / T : 14.3 / 1.4
R / S / T, U / V / W : M4
7.5 U / V / W : 18.4 / 1.8
• Only use the specified torque on the screw heads otherwise damage could occur. Loose screws can cause overheating and damage.
• Use copper wires with 600V, 75°C specification.
SW2
SW1
24 P1 P2 P3 P4 P5 CM
A1 B1 C1 A2 C2 VR V1 I2 AO CM S+ S-
Terminal
Category Name Description
Labels
Configurable for multi-function input terminals.
Factory default terminals and setup are as follows.
• P1: Fx
P1~P5 Multi-function
Multi-function • P2: Rx
Input 1-5
Terminal • P3: BX
Configuration • P4: RST
• P5: Speed-L
Sequence common
CM Common terminal for analog terminal inputs and outputs.
terminal
Used to setup or modify a frequency reference via analog voltage or current input.
Potentiometer • Maximum voltage output: 12 V
VR frequency reference
• Maximum current output: 100mA
input
• Potentiometer: 1/5 kΩ
Voltage input for Used to setup or modify a frequency reference via analog voltage input terminal.
Analog Input V1 frequency reference • Unipolar: 0–10V (12V Max.)
input • Bipolar: -10–10V (±12V Max.)
Used to setup or modify a frequency reference via current input terminal.
Current input for • Input current: 4-20 mA
I2 frequency reference
• Maximum Input current: 24mA
input terminal
• Input resistance: 249 Ω
Used to send inverter output information to external devices: Output frequency,
output current, output voltage, or a DC voltage.
Voltage output
AO • Output voltage: 0–10 V
terminal
• Maximum output voltage/Current: 12 V, 10 mA
• Factory default output: Frequency
24 External 24V power source Maximum current output: 100mA
Analog Output Sends out alarm signals when the inverter’s safety features are activated
(AC 250V 1A, DC 30V 1A).
A1/C1/B1 Fault signal output 1
• Fault condition: A1 and C1 contacts are connected (B1 and C1 open connection)
• Normal operation: B1 and C1 contacts are connected (A1 and C1 open connection)
Sends out alarm signals when the inverter’s safety features are activated
(AC 250V 1A, DC 30V 1A).
A2/C2 Fault signal output 2
• Fault condition: A2 and C2 contacts are open connection
• Normal operation: A2 and C2 contacts are connected
RS-485
S+ / S- RS-485 signal line Used to send or receive RS-485 signals.
Communication
❷ ❹
❸ ❺
LED flashes during parameter configuration and when the ESC key operates as the
➋ SET Indicator
multi-function key.
➌ RUN Indicator LED turns on (Steady) during an operation, and flashes during acceleration or deceleration.
[▲] Key, [▼] Key Switches between codes, or increases or decreases parameter values.
Moves between groups or moves to the digit on the left when setting the parameter.
[MODE / SHIFT] Key Press the MODE/SHIFT key once again on the maximum number of digits to move to the
minimum number of digits.
Output Terminal Configures output terminal-related features such as relays and analog outputs.
Drive
ENT
0QFSBUJPO
2 [▲] and [▼] keys until you locate the code that you 0VUQVUDVSSFOU
require.
ENT
0VUQVUGSFRVFODZ
1 Ensure that you are currently at the first code of the drive group (dr.0).
3 Press the [▼] key and change the ones' place of the code "95" to "5."
Press the [▲] key to change the tens' place number from "0" to "9,"
5
so the designated code is "95."
Press the [ENT] key.
6
Code dr.95 is displayed.
Fault Trips
Protection functions for output current and input voltage
Keypad Display Name Type Description
Displayed when the motor overload trip is activated and the actual load level
Over Load Latch exceeds the set level.
Operates when Pr.20 is set to a value other than 0.
Displayed when the motor underload trip is activated and the actual load level is
Under Load Latch less than the set level.
Operates when Pr.27 is set to a value other than 0.
Over Current 1 Latch Displayed when inverter output current exceeds 200% of the rated current.
Over Voltage Latch Displayed when internal DC circuit voltage exceeds the specified value.
Low Voltage Level Displayed when internal DC circuit voltage is less than the specified value.
Displayed when internal DC circuit voltage is less than the specified value during
Low Voltage 2 Latch inverter operation.
Operates when Pr.82 is set to 1.
Displayed when a ground fault trip occurs on the output side of the inverter and
Ground Trip* Latch causes the current to exceed the specified value.
The specified value varies depending on inverter capacity.
Displayed based on inverse time-limit thermal characteristics to prevent motor
E-Thermal Latch overheating.
Operates when Pr.40 is set to a value other than 0.
Displayed when a 3-phase inverter output has one or more phases in an open
Out Phase
Latch circuit condition.
Open
Operates when bit 1 of Pr.05 is set to 1.
Displayed when a 3-phase inverter input has one or more phases in an open circuit
In Phase Open Latch condition.
Operates only when bit 2 of Pr.05 is set to 1.
Displayed when the inverter has been protected from overload and resultant
overheating, based on inverse time-limit thermal characteristics.
Inverter OLT Latch Allowable overload rates for the inverter are 150% for 1 min and 200% for 4 sec.
Protection is based on inverter rated capacity, and may vary depending on the
device’s capacity.
Relay Open Occurs when the DC voltage relay is not operating when power the is input.
Latch
Trip The Pr-90 code must be set to 1 to operate.
Over Torque Occurs when the output current is higher than the level set in Ou-68.
Latch
Trip 1 Operates when OU-67 is set to 3, 4.
Over Torque Occurs when the output current is higher than the level set in OU-71.
Latch
Trip 2 Operates when OU-70 is set to 3, 4.
Under Torque Occurs when the output current is lower than the level set in OU-68.
Latch
Trip 1 Operates when OU-67 is set to 7, 8.
Under Torque Occurs when the output current is lower than the level set in OU-71.
Latch
Trip 2 Operates when OU-70 is set to 7, 8.
* Ground Trip (GFT) feature is not provided in the products under 4.0 kW. Over current trip (OCT) or over voltage trip (OVT) may occur during low resistance grounding.
Fault Trips
Protection functions using abnormal internal circuit conditions and external signals
Keypad Display Name Type Description
Displayed when the temperature of the inverter heat sink exceeds the
Over Heat Latch
specified value.
Displayed when the DC circuit in the inverter detects a specified level of excessive,
Over Current 2 Latch
short circuit current.
Displayed when pre-PID is operating with functions set at AP.34–AP.36. A fault trip
Pre-PID Fail Latch occurs when a controlled variable (PID feedback) is measured below the set value
and the low feedback continues, as it is treated as a load fault.
Operates when the external brake signal is provided by the multi-function terminal.
Ext-Brake Latch Occurs when the inverter output starting current remains below the set value at
Ad.41. Set either OU.31 or OU.32 to 35 (BR Control).
When the user has set Pr-78 to 2: Free-Run or 3: Dec, pre-overheating warning
Overheat
Latch trip of inverter occurs if the inverter temperature exceeds the temperature set
Pre Alarm
by the user in Pr-77.
Displayed when the I/O board or external communication card is not connected to
the inverter or there is a bad connection.
IO Board Trip Latch
Displayed when the error code continues for more than 5 sec.
(‘Errc’ -> ’-rrc’ -> ‘E-rc’ -> ’Er-c’ -> ‘Err-‘ -> ’- -rc’ -> ‘Er- -‘ -> ’- - - -‘ -> ’Errc’ -> …)
Displayed when a communication error is detected between the inverter and the
Option Trip -1 Latch
communication board. Occurs when the communication option card is installed.
Warning Messages
Keypad Display Name Description
Displayed when the motor is overloaded. Operates when Pr.17 is set to 1. To operate, select 5.
Over Load Set the digital output terminal or relay (OU.31 or OU.33) to 5 (Over load) to receive overload warning
output signals.
Displayed when the motor is underloaded. Operates when Pr.25 is set to 1.
Under Load Set the digital output terminal or relay (OU.31 or OU.33) to 7 (Under load) to receive underload
warning output signals.
Displayed when the overload time equivalent to 60 % of the inverter overheat protection (inverter IOLT)
level, is accumulated.
INV Over Load
Set the digital output terminal or relay (OU.31 or OU.33) to 6 (IOL) to receive inverter overload warning
output signals.
Lost command warning alarm occurs even with Pr.12 set to 0. The warning alarm occurs based on the
condition set at Pr.13- 15. Set the digital output terminal or relay (OU.31 or OU.33) to 13
Lost Command
(Lost command) to receive lost command warning output signals.
If the communication settings and status are not suitable for P2P, a lost command alarm occurs.
An alarm occurs when the value set at PRT-86 is less than the value set at PRT-87.
Fan Exchange To receive fan exchange output signals, set the digital output terminal or relay (OUT-31 or OUT-33) to 38
(Fan exchange).
Displayed when an error is detected from the cooling fan while Pr.79 is set to 1.
Fan Warning Set the digital output terminal or relay (OU.31 or OU.33) to 8 (Fan warning) to receive fan warning
output signals.
DB Warn %ED Displayed when the DB resistor usage rate exceeds the set value. Set the detection level at Pr.66.
Operates when dr.9 is set to 4. The warning alarm occurs when the motor’s rotor time constant (Tr) is
Retry Tr Tune
either too low or too high.
Overheat Pre When the user has set Pr-78 to 1: Warning, pre-overheating warning of inverter occurs if the inverter
Alarm temperature exceeds the temperature set by the user in Pr-77.
Code Comm. Address Name Keypad Display Setting Range Initial Value Property* V/F SL
- 0h1D00 Target frequency 0.00 0-Maximum frequency(Hz) 0.00 O O O
- 0h1D01 Acceleration time ACC 0.0–600.0(s) 5.0 O O O
- 0h1D02 Deceleration time dEC 0.0–600.0(s) 10.0 O O O
0 Keypad
1 Fx / Rx-1
- 0h1D03 Command source drv 2 Fx / Rx-2 1: Fx / Rx-1 X O O
3 Int 485
4 Fieldbus 1)
0 Keypad-1
1 Keypad-2
2 V1
Frequency reference
- 0h1D04 Frq 4 V0 (Built-in volume) 0: Keypad-1 X O O
source
5 I2
6 Int 485
8 Fiedbus 1)
Multi-step speed
- 0h1D05 St1 0.00-Maximum frequency (Hz) 10.00 O O O
frequency 1
Multi-step speed
- 0h1D06 St2 0.00-Maximum frequency (Hz) 20.00 O O O
frequency 2
Multi-step speed
- 0h1D07 St3 0.00-Maximum frequency (Hz) 30.00 O O O
frequency 3
- 0h1D08 Output current CUr - - O O
Motor revolutions
- 0h1D09 Rpm - O O
per minute
- 0h1D0A Inverter DC voltage dCL - - - O O
- 0h1D0B Inverter output voltage vOL - O O
- 0h1D0C Out of order signal nOn - O O
Code Comm. Address Name Setting Range Initial Value Property* V/F SL
dr-00 - Jump code 1–99 9 O O O
0 V / F
dr-09 0h1109 Control mode 2 Slip compen 0: V / F X O O
4 IM sensorless
dr-11 0h110B Jog frequency 0.00, Start frequency-Maximum frequency(Hz) 10.00 O O O
dr-12 0h110C Jog run acceleration time 0.0–600.0(s) 20.0 O O O
dr-13 0h110D Jog run deceleration time 0.0–600.0(s) 30.0 O O O
0: 0.2kW
1: 0.4kW
2: 0.75kW
3: 1.1kW
4: 1.5kW
5: 2.2kW Varies by
dr-14 0h110E Motor capacity X O O
6: 3.0kW motor capacity
7: 3.7kW
8: 4.0kW
9: 5.5kW
10: 7.5kW
11:11.0kW
0 Manual
dr-15 0h110F Torque boost mode 0: Manual X O X
1 Auto
dr-16 0h1110 Forward torque boost 0.0–15.0(%) 2.0 X O X
dr-17 0h1111 Reverse torque boost 0.0–15.0(%) 2.0 X O X
30.00-400.00(Hz) [V / F, Slip compen]
dr-18 0h1112 Base frequency 60.00 X O O
40.00-120.00(Hz) [IM sensorless]
dr-19 0h1113 Start frequency 0.01-10.00(Hz) 0.50 X O O
40.00-400.00(Hz) [V / F, Slip compen]
dr-20 0h1114 Maximum frequency 60.00 X O O
40.00-120.00(Hz) [IM sensorless]
dr-26 2) 0h111A Auto torque boost filter gain 1~1000 2 O O X
dr-27 2) 0h111B Auto torque boost motoring gain 0.0–300.0[%] 50.0 O O X
dr-28 2) 0h111C Auto torque boost regeneration gain 0.0–300.0[%] 50.0 O O X
Select ranges inverter displays
at power input
0 Operation frequency
1 Acceleration time
2 Deceleration time
3 Command source
4 Frequency reference source
5 Multi-step speed frequency 1
dr-80 0h1150 Select ranges at power input 0: Operation frequency O O O
6 Multi-step speed frequency 2
7 Multi-step speed frequency 3
8 Output current
9 Motor RPM
10 Inverter DC voltage
11 User select signal (dr.81)
12 Currently out of order
13 Select run direction
• SL: Sensorless vector control (dr.09), Property: Write-enabled during operation
2) Appears when Dr15 is 1 (automatic torque boost).
Code Comm. Address Name Setting Range Initial Value Property* V/F SL
14 Output current 2
Code Comm. Address Name Setting Range Initial Value Property* V/F SL
bA-00 - Jump code 1~99 20 O O O
0 None
1 V1
bA-01 0h1201 Auxiliary reference source 0: None X O O
3 V0
4 I2
0 M+(G*A)
1 Mx (G*A)
2 M / (G*A)
Code Comm. Address Name Setting Range Initial Value Property* V/F SL
bA-16 0h1210 Motor efficiency 64~100(%) Dependent on motor setting X O O
bA-17 0h1211 Load inertia rate 0~8 0 X O O
bA-18 0h1212 Trim power display 70~130(%) 100% O O O
bA-19 0h1213 Input power voltage 170~480V 220 / 380V O O O
0 None
1 All(Rotation type)
bA-20 - Auto tuning 2 All(Static type) 0: None X X O
3 Rs+Lsigma(Rotation type)
6 Tr(Static type)
bA-21 - Stator resistance X X O
Dependent
bA-22 - Leakage inductance Dependent on motor setting X X O
on motor setting
bA-23 - Stator inductance X X O
bA-24 5) - Rotor time constant 25~5000(ms) - X X O
bA-41 6) 0h1229 User frequency 1 0.00-Maximum frequency(Hz) 15.00 X O X
bA-42 6) 0h122A User voltage 1 0-100(%) 25 X O X
bA-43 6) 0h122B User frequency 2 0.00-Maximum frequency(Hz) 30.00 X O X
bA-44 6) 0h122C User voltage 2 0-100(%) 50 X O X
bA-45 6) 0h122D User frequency 3 0.00-Maximum frequency(Hz) 45.00 X O X
bA-46 6) 0h122E User voltage 3 0-100(%) 75 X O X
bA-47 6) 0h122F User frequency 4 0.00-Maximum frequency(Hz) Maximum frequency X O X
bA-48 6) 0h1230 User voltage 4 0-100(%) 100 X O X
bA-53 7) 0h1235 Multi-step speed frequency 4 0.00-Maximum frequency(Hz) 40.00 O O O
bA-54 7) 0h1236 Multi-step speed frequency 5 0.00-Maximum frequency(Hz) 50.00 O O O
bA-55 7) 0h1237 Multi-step speed frequency 6 0.00-Maximum frequency(Hz) Maximum frequency O O O
bA-56 7) 0h1238 Multi-step speed frequency 7 0.00-Maximum frequency(Hz) Maximum frequency O O O
bA-70 0h1246 Multi-step acceleration time 1 0.0–600.0(s) 20.0 O O O
bA-71 0h1247 Multi-step deceleration time 1 0.0–600.0(s) 20.0 O O O
bA-72 8) 0h1248 Multi-step acceleration time 2 0.0–600.0(s) 30.0 O O O
bA-73 8) 0h1249 Multi-step deceleration time 2 0.0–600.0(s) 30.0 O O O
bA-74 8) 0h124A Multi-step acceleration time 3 0.0–600.0(s) 40.0 O O O
bA-75 8) 0h124B Multi-step deceleration time 3 0.0–600.0(s) 40.0 O O O
bA-76 8) 0h124C Multi-step acceleration time 4 0.0~600.0(s) 50.0 O O O
bA-77 8) 0h124D Multi-step deceleration time 4 0.0~600.0(s) 50.0 O O O
bA-78 8) 0h124E Multi-step acceleration time 5 0.0~600.0(s) 40.0 O O O
bA-79 8) 0h124F Multi-step deceleration time 5 0.0~600.0(s) 40.0 O O O
bA-80 8) 0h1250 Multi-step acceleration time 6 0.0~600.0(s) 30.0 O O O
bA-81 8) 0h1251 Multi-step deceleration time 6 0.0~600.0(s) 30.0 O O O
bA-82 8) 0h1252 Multi-step acceleration time 7 0.0~600.0(s) 20.0 O O O
bA-83 8) 0h1253 Multi-step deceleration time 7 0.0~600.0(s) 20.0 O O O
• In the following table, data shaded in blue will be displayed when the related code has been selected.
• SL: Sensorless vector control (dr.09), Property: Write-enabled during operation
5) Displayed when dr.09 is set to 4(IM sensorless).
6) Displayed if either bA.07 or M2.25 is set to 2 (User V / F).
7) Displayed if one of In.65-71 is set to speed–L / M / H.
8) Displayed one of In.65-71 is set to Xcel–L / M / H.
Code Comm. Address Name Setting Range Initial Value Property* V/F SL
Ad-00 - Jump code 1~99 24 O O O
Ad-01 0h1301 Acceleration pattern 0 Linear X O O
0: Linear
Ad-02 0h1302 Deceleration pattern 1 S-curve X O O
Ad-03 9) 0h1303 S-curve acceleration start point gradient 1~100(%) 40 X O O
Ad-04 9) 0h 1304 S-curve acceleration end point gradient 1~100(%) 40 X O O
Ad-05 10) 0h1305 S-curve deceleration start point gradient 1~100(%) 40 X O O
Ad-06 10) 0h1306 S-curve deceleration end point gradient 1~100(%) 40 X O O
0 Acc
Ad-07 0h1307 Start mode 0: Acc X O O
1 Dc-start
0 Dec
1 Dc-brake
Ad-08 0h1308 Stop mode 0: Dec X O O
2 Free-run
4 Power braking
0 None
Ad-09 0h1309 Run prevention options 1 Forward prev 0: None X O O
2 Reverse prev
0 No
Ad-10 0h130A Starting with power on 0: No O O O
1 Yes
Ad-12 11) 0h130C Start DC braking time 0.00~60.00(s) 0.00 X O X
Ad-13 0h130D Amount of applied DC 0-inverter rated current(%) 50 X O X
Ad-14 12) 0h130E Output blocking time before DC braking 0.00–60.00(s) 0.10 X O O
Ad-15 12) 0h130F DC braking time 0.00–60.00(s) 1.00 X O O
Ad-16 12) 0h1310 DC braking rate 0 - inverter rated current / motor rated current x 100 (%) 50 X O O
Ad-17 12) 0h1311 DC braking frequency Start frequency-60Hz 5.00 X O O
Ad-20 0h1314 Dwell frequency on acceleration Start frequency-maximum frequency(Hz) 5.00 X O O
Ad-21 0h1315 Dwell operation time on acceleration 0.0–60.0(s) 0.0 X O O
Ad-22 0h1316 Dwell frequency during deceleration Start frequency-maximum frequency(Hz) 5.00 X O O
Ad-23 0h1317 Operation time during deceleration 0.0–60.0(s) 0.0 X O O
0 No
Ad-24 0h1318 Frequency limit 0: No X O O
1 Yes
Ad-25 13) 0h1319 Frequency lower limit value 0.00-Upper limit frequency(Hz) 0.50 O O O
Ad-26 13) 0h131A Frequency upper limit value Lower limit frequency-maximum frequency(Hz) Maximum frequency X O O
0 No
Ad-27 0h131B Frequency jump 0: No X O O
1 Yes
Ad-28 14) 0h131C Jump frequency lower limit 1 0.00-Jump frequency upper limit1(Hz) 10.00 O O O
Ad-29 14) 0h131D Jump frequency upper limit 1 Jump frequency lower limit1-maximum frequency(Hz) 15.00 O O O
Ad-30 14) 0h131E Jump frequency lower limit 2 00-Jump frequency upper limit2(Hz) 20.00 O O O
Ad-31 14) 0h131F Jump frequency upper limit 2 Jump frequency lower limit2-maximum frequency(Hz) 25.00 O O O
• In the following table, data shaded in blue will be displayed when the related code has been selected.
• SL: Sensorless vector control (dr.09), Property: Write-enabled during operation
9) Displayed when Ad. 01 is set to 1 (S-curve).
10) Displayed when the Ad. 02 code is set to 1 (S-curve).
11) Displayed when Ad. 07 is set to 1 (DC-start).
12) Displayed when Ad. 08 is set to 1 (DC-brake).
13) Displayed when the Ad.24 code is set to 1 (Yes).
14) Displayed when the Ad.27 code is set to 1 (Yes).
Code Comm. Address Name Setting Range Initial Value Property* V/F SL
Ad-32 14) 0h1320 Jump frequency lower limit 3 0.00-Jump frequency upper limit3(Hz) 30.00 O O O
Ad-33 14) 0h1321 Jump frequency upper limit 3 Jump frequency lower limit3-maximum frequency(Hz) 35.00 O O O
Ad-41 15) 0h1329 Brake release current 0.0-180.0(%) 50.0 O O O
Ad-42 15) 0h132A Brake release delay time 0.00–10.00(s) 1.00 X O O
Ad-44 15) 0h132C Brake release forward frequency 0.00-Maximum frequency(Hz) 1.00 X O O
Ad-45 15) 0h132D Brake release reverse frequency 0.00-Maximum frequency(Hz) 1.00 X O O
Ad-46 15) 0h132E Brake engage delay time 0.00–10.00(s) 1.00 X O O
Ad-47 15) 0h132F Brake engage frequency 0.00-Maximum frequency(Hz) 2.00 X O O
0 None
Ad-50 0h1332 Energy saving operation 1 Manual 0: None X O X
2 Auto
Ad-51 16) 0h1333 Energy saving amount 0–30(%) 0 O O X
Ad-60 0h133C Acc / Dec time transition frequency 0.00-Maximum frequency(Hz) 0.00 X O O
Ad-61 0h133D Rotation count speed gain 0.1–6000.0[%] 100.0 O O O
0 x1
1 x 0.1
Ad-62 0h133E Rotation count speed scale 2 x 0.01 0: x 1 O O O
3 x 0.001
4 x 0.0001
0 Rpm
Ad-63 0h133F Rotation count speed unit 0: rpm O O O
1 mpm
0 During run
Ad-64 0h1340 Cooling fan control 1 Always on 0: During run O O O
2 Temp control
Up / Down operation 0 No
Ad-65 0h1341 0: No O O O
frequency save 1 Yes
0 None
Code Comm. Address Name Setting Range Initial Value Property* V/F SL
Selection of regeneration 0 No
Ad-74 0h134A 0: No X O O
evasion function for press 1 Yes
Code Comm. Address Name Setting Range Initial Value Property* V/F SL
Cn-00 - Jump code 1~99 4 O O O
V / F: 1.0~15.0(kHz)
Heavy duty 3.0
IM: 2.0~15.0(kHz)
Cn-04 21) 0h1404 Carrier frequency X O O
V / F: 1.0~ 5.0(kHz)
Normal duty 2.0
IM: 2.0~5.0(kHz )
Cn-05 0h1405 Switching mode 0 Normal PWM 0: Normal PWM X O O
Cn-09 0h1409 Initial excitation time 0.00~60.00(s) 1.00 X X O
Cn-10 0h140A Initial excitation amount 100.0~300.0(%) 100.0 X X O
Cn-11 0h140B Continued operation duration 0.00~60.00(s) 0.00 X X O
Output torque
Cn-22 0h1416 50~300(%) Varies by motor capacity X X O
compensation gain
Speed controller
Cn-30 0h141E 2.0~10.0 4.0 O X O
adjustment gain
0 Keypad-1
1 Keypad-2
2 V1
Cn-53 0h1435 Torque limit setting 4 V0 0: Keypad-1 X X O
5 I2
6 Int 485
8 FieldBus
Cn-54 22) 0h1436 Positive-direction reverse torque limit 0.0~200.0(%) 180 O X O
Cn-55 22) 0h1437 Positive-direction regeneration torque limit 0.0~200.0(%) 180 O X O
Cn-56 22) 0h1438 Negative-direction regeneration torque limit 0.0~200.0(%) 180 O X O
Cn-57 22) 0h1439 Negative-direction reverse torque limit 0.0~200.0(%) 180 O X O
0 Flying start-1 23)
Cn-70 0h 1446 Speed search mode selection 0: Flying start-1 X O O
1 Flying start-2
bit 0000–1111
0001 Selects the speed search function at acceleration.
Speed search operation
Cn-71 0h1447 0010 Initialization after a fault trip 0000 24) X O O
selection
0100 Restart after instantaneous power interruption
1000 Starting with power-on
• In the following table, data shaded in blue will be displayed when the related code has been selected.
• SL: Sensorless vector control (dr.09), Property: Write-enabled during operation
21) It is for 5.5~7.5kW.
22) Displayed when dr.09 is set to 4 (IM Sensorless). This will change the initial value of the parameter at Ad.74 (Torque limit) to 150%.
23) Will not be displayed if dr.09 is set to 4 (IM Sensorless).
Code Comm. Address Name Setting Range Initial Value Property* V/F SL
Cn-72 25) 0h1448 Speed search reference current 80~200(%) 150 O O O
Flying start-1: 100
Cn-73 26) 0h1449 Speed search proportional gain 0~9999 O O O
Flying start-2: 600 27)
Flying start-1: 200
Cn-74 26) 0h144A Speed search integral gain 0~9999 O O O
Flying start-2: 1000
Cn-75 26) 0h144B Output block time before speed search 0.0~60.0(s) 1.0 X O O
Cn-76 26) 0h144C Speed search estimator gain 50~150(%) 100 O O O
0 No
2 KEB-2
Cn-78 28) 0h144E Energy buffering start level 110.0~200.0(%) 125.0 X O O
Cn-79 28) 0h144F Energy buffering stop level Cn78~210.0(%) 130.0 X O O
Cn-80 28) 0h1450 Energy buffering P gain 0~20000 1000 O O O
Cn-81 28) 0h1451 Energy buffering I gain 1~20000 500 O O O
Cn-82 28) 0h1452 Energy buffering slip gain 0~2000.0% 30.0 O O O
Cn-83 28) 0h1453 Energy buffering acceleration time 0.0~600.0(s) 10.0 O O O
• In the following table, data shaded in blue will be displayed when the related code has been selected.
• SL: Sensorless vector control (dr.09), Property: Write-enabled during operation
25) Displayed when any of the Cn.71 code bits are set to 1 and Cn70 is set to 0 (Flying start-1).
26) Displayed when any of the Cn.71 code bits are set to 1.
27) The initial value is 1200 when the motor-rated capacity is less than 7.5 kW
28) Displayed when Cn.77 is not set to 0 (No).
Code Comm. Address Name Setting Range Initial Value Property* V/F SL
In-00 - Jump code 1~99 65 O O O
In-01 0h1501 Frequency for maximum analog input Start frequency-maximum frequency(Hz) Maximum frequency O O O
In-02 0h1502 Torque at maximum analog input 0.0~200.0(%) 100.0 O X X
In-05 0h1505 V1 input voltage display -12.00~12.00(V) 0.00 - O O
0 Unipolar
In-06 0h1506 V1 input polarity selection 0: Unipolar X O O
1 Bipolar
In-07 0h1507 Time constant of V1 input filter 0~10000(ms) 100 O O O
In-08 0h1508 V1 Minimum input voltage 0.00~10.00(V) 0.00 O O O
In-09 0h1509 V1 output at Minimum voltage(%) 0.00~100.00(%) 0.00 O O O
In-10 0h150A V1 Maximum input voltage 0.00~12.00(V) 10.00 O O O
In-11 0h150B V1 output at Maximum voltage(%) 0.00~100.00(%) 100.00 O O O
In-12 29) 0h150C V1 Minimum input voltage -10.00~ 0.00(V) 0.00 O O O
In-13 29) 0h150D V1 output at Minimum voltage(%) -100.00~0.00(%) 0.00 O O O
In-14 29) 0h150E V1 Maximum input voltage -12.00~ 0.00(V) -10.00 O O O
In-15 29) 0h150F V1 output at Maximum voltage(%) -100.00~0.00(%) -100.00 O O O
Changing rotation 0 No
In-16 0h1510 0: No O O O
direction of V1 1 Yes
In-17 0h1511 V1 quantization level 0.00 30), 0.04~10.00(%) 0.04 X O O
In-35 0h1523 V0 input voltage display 0.00~5.00(V) 0.00 - O O
In-37 0h1525 Time constant of V0 input filter 0~10000(ms) 100 O O O
In-38 0h1526 V0 Minimum input voltage 0.00~5.00(V) 0.00 O X O
In-39 0h1527 V0 output at minimum voltage(%) 0.00~100.00(%) 0.00 O O O
In-40 0h1528 V0 Maximum input voltage 0.00~5.00(V) 5.00 O X O
In-41 0h1529 V0 output at maximum voltage(%) 0.00~100.00(%) 100.00 O O O
Changing rotation 0 No
In-46 0h152E 0: No O O O
direction of V0 1 Yes
In-47 0h152F V0 quantization level 0.00 30), 0.04~ 10.00(%) 0.04 O O O
In-50 0h1532 I2 input voltage display 0~24(mA) 0.00 - O O
In-52 0h1534 I2 input filter time constant 0~10000(ms) 100 O O O
In-53 0h1535 I2 minimum input current 0.00~20.00(mA) 4.00 O O O
In-54 0h1536 I2 output at minimum current(%) 0.00~100.00(%) 0.00 O O O
In-55 0h1537 I2 maximum input current 0.00~24.00(mA) 20.00 O O O
In-56 0h1538 I2 output at maximum current(%) 0.00~100.00(%) 100.00 O O O
0 No
In-61 0h153D Changing rotation direction of I2 0: No O O O
1 Yes
In-62 0h153E I2 quantization level 0.00 29),0.04~10.00(%) 0.04 O O O
0 None
In-65 0h1541 P1 terminal function setting 1: Fx X O O
1 Fx
2 Rx
In-66 0h1542 P2 terminal function setting 2: Rx X O O
3 RST
4 External trip
In-67 0h1543 P3 terminal function setting 5: BX X O O
5 BX
6 JOG
In-68 0h1544 P4 terminal function setting 3: RST X O O
7 Speed-L
8 Speed-M
In-69 0h1545 P5 terminal function setting 7: Sp-L X O O
9 Speed-H
• In the following table, data shaded in blue will be displayed when the related code has been selected.
• SL: Sensorless vector control (dr.09), Property: Write-enabled during operation
29) Displayed when In.06 is set to 1 (Bipolar).
30) Quantizing is not used when set to 0.
Code Comm. Address Name Setting Range Initial Value Property* V/F SL
11 XCEL-L
12 XCEL-M
13 RUN enable
14 3-Wire
15 2nd source
16 Exchange
17 Up
18 Down
20 U / D Clear
21 Analog hold
22 I-Term clear
23 PID Openloop
- - - 24 P Gain2 - - - -
25 XCEL stop
26 2nd motor
27 U / D Enable
33 Baseblock
34 Pre excite
38 Timer in
40 dis Aux ref
46 FWD JOG
47 REV JOG
49 XCEL-H
51 Fire mode
52 KEB-1 Select
P5 – P1
Multi-function input terminal
In-84 0h1554 0 Disable(Off) 1 1111 31) O O O
on filter selection
1 Enable(On)
In-85 0h1555 Multi-function input terminal on filter 0~10000(ms) 10 O O O
In-86 0h1556 Multi-function input terminal off filter 0~10000(ms) 3 O O O
P5 – P1
Multi-function input
In-87 0h1557 0 A contact (NO) 0 0000 32) X O O
terminal selection
1 B contact (NC)
Selects the NO / NC operation 0 NO
In-88 0h1558 0 X O O
command 1 NO/NC
In-89 0h1559 Multi-step command delay time 1-5000(ms) 1 X O O
P5 – P1
Multi-function input
In-90 0h155A 0 release(Off) 0 0000 - O O
terminal status
1 Connection (On)
Bit 0~1
In-99 0h1563 SW1(NPN/PNP), status 0 NPN 0 - O O
1 PNP
• SL: Sensorless vector control (dr.09), Property: Write-enabled during operation
Selection of startup 0 No
Pr-08 0h1B08 0: No O O O
on trip reset 1 Yes
Pr-09 0h1B09 Number of automatic restarts 0~10 0 O O O
Pr-10 42) 0h1B0A Automatic restart delay time 0.0~60.0(s) 1.0 O O O
0 None
1 Free-run
2 User V / F
M2-30 0h1C1E Electronic thermal continuous rating 50–Electronic thermal 1 minute rating 100 X O O
M2-31 0h1C1F Low-speed torque compensation gain 50~300(%) Varies by motor capacity X X O
• In the following table, data shaded in blue will be displayed when the related code has been selected.
• The 2nd Motor function group will be displayed if any of In.65-71 is set to 26 (2nd motor).
• SL: Sensorless vector control (dr.09), Property: Write-enabled during operation
44) Displayed when M2.08 is set to 4(IM Sensorless).
M2-33 0h1C21 Speed deviation sub compensation gain 50~300(%) Varies by motor capacity X X O
M2-34 0h1C12 Speed deviation main compensation gain 50~300(%) Varies by motor capacity X X O
0 x1
1 x 0.1
3 x 0.001
4 x 0.0001
0 Rpm
M2-42 0h1C2A Rotation count speed unit 0: rpm O O O
1 mpm
• The 2nd Motor function group will be displayed if any of In.65-71 is set to 26 (2nd motor).
• SL: Sensorless vector control (dr.09), Property: Write-enabled during operation
Compatible Circuit Breaker, Leakage Breaker and Magnetic Contactor Models (Manufactured by LSIS)
Circuit Breaker Leakage Breaker Magnetic Contactor
Capacity(kW)
Model Current(A) Specific Model Name Model Current(A) Model Current(A)
0.4 5 MC-6a 9
0.75 15 UTE100·H·FTU·15·3P·UL 10 MC-9a, MC-9b 11
3-Phase 1.5 UTE100H EBS33c 15 MC-18a, MC-18b 18
200V 2.2 20 UTE100·H·FTU·20·3P·UL 20 MC-22b 22
Class 4.0 30 UTE100·H·FTU·30·3P·UL 30 MC-32a 32
5.5 50 UTS150·H·FTU·50·3P·UL EBS53c 50 MC-50a 55
UTS150H
7.5 60 UTS150·H·FTU·60·3P·UL EBS63c 60 MC-65a 65
0.4 MC-6a
5 7
0.75 MC-6a
15 UTE100·E·FTU·15·3P·UL
3-Phase 1.5 MC-9a, MC-9b 9
10
400V 2.2 UTE100E EBS33c MC-12a, MC-12b 12
Class 4.0 20 UTE100·E·FTU·20·3P·UL 20 MC-18a, MC-18b 18
5.5 MC-22b 22
30 UTE100·E·FTU·30·3P·UL 30
7.5 MC-32a 32
Caution Use class CC, G, J, L, R or T UL listed Input fuse and UL listed breaker only. See the table above for the voltage and current rating of the fuse and the breaker.
HD ND
Rated
Voltage Model Number Power Rated Heat Rated Heat
Total Internal Total Internal
(kW) Output Losses Output Losses
Losses(W) Losses(W) Losses(W) Losses(W)
Current(A) (Kacl) Current(A) (Kacl)
Total losses
Capacity(kW) x (1-Efficiency/100) x 1000 = W
ex) 0.4kW x (1- 95.3/100) x 1000 = 18.8W
Total losses = Internal loss + External loss
Internal losses
Based on design standard such as SMPS Rated Capacity, Fan and so forth
External(Heat) losses
1wh = 3,600J,1kcal = 4,186 J
Efficiency= Output/(Output+Loss)*100=Output/Input*100
Loss*0.9=Heat Loss
-> Other Loss 0.1
Σ(The number of installed drive at each capacity*Heat) = Total amount of Heat
∅4 86.4 (3.40)
5 (0.20)
.5 ( 76.2 (3.00) 139.7 (5.50)
0.1
8)
164.2 (6.46)
154 (6.06)
153.8 (6.06)
101.5 (4.00)
4.5 (0.18)
131.5 (5.18)
∅4 101.2 (3.98)
5 (0.20)
.5 ( 158.7 (6.25)
0.1 90 (3.54)
8)
177.2 (6.98)
167 (6.57)
166.9 (6.57)
114.5 (4.51)
4.5 (0.18)
151.1 (5.95)
158.8 (6.25)
∅ 135 (5.31)
4.5
(0. 125 (4.92)
18
)
182.8 (7.20)
193 (7.60)
183 (7.20)
130.4 (5.13)
4.5 (0.18) 150.5 (5.93)
)
.18
180.3 (7.10) (0
6.5 (0.23)
∅
9(
0.3
12.1 (0.48)
5)
240.3 (9.46)
219.8 (8.65)
223 (8.78)
4.5 (0.18)
144 (5.67)
170 (6.69)
▶R&D ▶Factory
R&D Campus Power Device R&D Center Automation R&D Center PT&T (Testing laboratory) Cheongju Factory (Korea)
Focuses on gaining competitive Leading technology in electric Serves as the main research Internationally-renowned testing Electric products, mold TR,
advantages through development industry and continuously institute for LSIS center that has formed partner- MV/LV switchgear, HV GIS
of next generation platforms developing future-growth ships with the UL, CE, KEMA
dynamic engines and CESI
Head office
Domestic business establishment
Anyang Overseas manufacturing plant
R&D center
Head office Cheonan factory Overseas sales corporation
Cheonan Automation소R&D center
Overseas branch
Cheongju factory 1
Cheongju factory 2 Global service center
Cheongju Power device R&D center
PT&T(Power Testing & Technology Institute) Global R&D center
Presence internationally : 77 countries
Busan
Busan factory
Cheonan Factory (Korea) Busan Factory (Korea) Wuxi Factory (China) Dalian Factory (China) Hanoi Factory (Vietnam)
PLC, AC drive, HMI, DCS, HV TR, HVDC, FACTS Electric products MV/LV switchgear, MV contactor MV/LV switchgear, Mold TR
PV module
■Head Quarter • LSIS Beijing Office (China)
LS Yongsan Tower, 92, Hangang-daero, Yongsan-gu, Seoul, 04386, Korea Tel: 86-10-5761-3127 Fax: 86-10-5761-3128 E-Mail: sson@lsis.com
Tel : 82-2-2034-4286 Fax : 82-2-2034-4648 E-mail : mswoo@lsis.com • LSIS Guangzhou Office (China)
Tel: 86-20-8326-6784 Fax: 86-20-8326-6287 E-Mail: sojhtroh@lsis.com
■Overseas Subsidiaries
• LSIS Qingdao Office (China)
• LSIS(Shanghai) Co., Ltd. /CHINA
Tel: 86-532-8501-6058 Fax: 86-532-8501-6057 E-Mail: sson@lsis.com
Tel : 86-21-5237-9977(609) Fax : 86-21-5237-7189
• LSIS Chengdu Office (China)
• LSIS(Dalian) Co., Ltd. (Dalian, China)
Tel: 86-28-8670-3200 Fax: 86-28-8670-3203 E-Mail: yangcf@lsis.com
Tel: 86-411-8730-7510 Fax: 86-411-8730-7560 E-Mail: jiheo@lsis.com
• LSIS ShenYang Office (China)
• LSIS(Wuxi) Co., Ltd. (Wuxi, China)
Tel:86-24-2321-9050 Fax: 86-24-8386-7210 E-Mail: yangcf@lsis.com
Tel: 86-510-8534-6666-8005 Fax: 86-510-8534-4078 E-Mail: sunhwank@lsis.com
• LSIS Jinan Office (China)
• LS VINA Industrial Systems Co., Ltd. (Hanoi, Vietnam)
Tel: 86-531-8699-7826 Fax: 86-531-8697-7628 E-Mail: yangcf@lsis.com
Tel: 84-24-3882-0222 Fax: 84-24-3882-0220 E-Mail: jhchoi4@lsis.com
• LSIS Co., Ltd. Tokyo Office (Japan)
• LSIS Middle East FZE (Dubai, U.A.E.)
Tel: 81-3-6268-8241 Fax: 81-3-6268-8240 E-Mail: jschuna@lsis.com
Tel: 971-4-886-5360 Fax: 971-4-886-5361 E-Mail: hschoib@lsis.com
• LSIS Co., Ltd. Rep. Office (Vietnam)
• LSIS Europe B.V. (Amsterdam, Netherlands)
Tel: 84-28-3823-7890 E-Mail: sjbaik@lsis.com
Tel: 31-20-654-1420 Fax: 31-20-654-1429 E-Mail: htha@lsis.com
• LSIS Moscow Office (Russia)
• LSIS Japan Co., Ltd. (Tokyo, Japan)
Tel: 7-499-682-6130 E-Mail: jdpark1@lsis.com
Tel: 81-3-6268-8241 Fax: 81-3-6268-8240 E-Mail: jschuna@lsis.com
• LSIS Jakarta Office (Indonesia)
• LSIS USA Inc. (Chicago, U.S.A.)
Tel: 62-21-2933-7614 E-Mail: dioh@lsis.com
Tel: 1-800-891-2941 Fax: 1-847-383-6543 E-Mail: sales.us@lsis.com
• LSIS Bangkok Office (Thailand)
■Overseas Branches Tel: 66-90-950-9683 E-Mail: sjleet@lsis.com
• LSIS Shanghai Office (China)
Tel: 86-21-5237-9977(609) Fax: 86-21-5237-7189 E-Mail: ygeo@lsis.com