Transmission Line Protection
Transmission Line Protection
Transmission Line Protection
1
Fault Characteristics
• Transient Faults
Most common on Overhead transmission lines
Approximately 80 - 85% share
Lightning strikes are the most common cause
Other causes are falling trees, swinging lines etc.
By nature transient faults disappear in a short interval
• Persistent Faults
Mostly caused by a broken conductor fallen on to the tower or
ground
Can also be caused by a tree falling on to the line
Must be located and attended to, before normal service can be
resumed
2
Faults on Double Circuit Lines
Simultaneous Faults and Interline Faults
On parallel lines simultaneous faults and
interline faults can happen.
A non switched distance relay will be C A
discriminative in identifying the correct fault
A B
loop, when the protection is measuring two
different fault types at the same time. B C
AN
~ ~
CN
3
Measuring Principles
4
Application of Distance Protection
5
Distance Protection – Basic Principle
UM
ZF
IF UF=0
B
A
Distance
Relay
ZF=UM/ IF
V = I Z1 + I0 ( Z0 - Z1 ) [ 3I0 = IN ]
IN
V = I Z1 + ( Z0 - Z1 )
3
Z0 - Z1
V = IZ1 + IN( )
3
Z0 - Z1
Z0 - Z1 Z = Z1 ( 1 + ( ))
Z = Z1 + ( ) 3Z1
3
7
Ground Fault Measurement
8
Measuring Loop - Ground Faults
Zs IA RL XL
VA
IN RN XN
The measured Impedance is a function of
positive and zero sequence impedance
9
Measuring Loop – Phase - Phase Faults
Zs IA RL XL
VA-VB
IB RL XL
Zs IA RL XL
VA IB
VB IC
VC
12
Fault Resistance
Phase faults
Constitutes only the Arc Resistance C A
B B
Ground faults
A C
Constitutes of Arc and Tower Footing Resistance
Warrington´s Formula
L = Length of arc in meters
28707 x L Tower Footing
Rarc = 1.4 I= Fault current in Amps Resistance
I
13
Polarization Methods
Self Polarization
The same phase voltage is used for polarization
When a fault occurs close to the relay location, the voltage can drop
to a value where the directional measurement cannot be performed
Cross Polarization
Use other healthy phase voltages for polarization
Memory Polarization
At three phase fault close to the station all phase voltages are low
and cross polarization is not of any use. Instead a memory voltage
is used to secure correct measurement.
Cross Polarization
VCA
VC
VBC
VA
VB
VAB
15
Distance Protection Characteristics
Mho Characteristics
16
Distance Protection Characteristics
17
Distance Protection Characteristics
Quadrilateral Characteristics
18
Impedance Setting Criteria
ZL = R + jX
21 21
• While setting the distance protection relay, the line impedance
may have to be converted to secondary values by multiplying
with the Impedance ratio.
CTR
Zratio =
VTR
VTsec CTprim VTsec CTprim x
Zratio= x Zsec = x Zprim
VTprim CTsec VTprim CT sec
19
Zones Setting Criteria
Zone 2 Zone 3F
Zone 3R Zone 1
Zone 3R
Zone 2 Zone 1
Zone 3R Zone 2
Zone 1
Zone 3 Zone 3R
Zone 2 Zone 1
20
Zones Setting Criteria
A B C
Zone 4
Zone 1
Zone 2
Zone 3
21
Load Encroachment
When setting the zones for long lines or setting the over reaching zones, it
can happen that the characteristic may encroach into the Load region.
This will result in unwanted operation of the zones.
A novel approach is to have a Load Encroachment blinding characteristic.
22
Load Encroachment
Carrier Communication
Schemes
Permissive
Permissive Over
Under reach
reach Schemes
Schemes
25
Permissive Under Reach
S/Stn 1 S/Stn 2
Zone 2
Time Carrier
Zone 2
Aided
Time Delayed Trip
Trip
Distance
Zone 1 (No Operation) Zone 2
Zone 1 Distance
S/Stn 1 S/Stn 2
Zone 2
Time Carrier
Zone 2
Aided
Time Delayed Trip
Trip
Distance
Zone 1 (No Operation) Zone 2
Zone 2 Instantaneous
Zone 1
Distance
S/Stn 1 S/Stn 2
Zone 2
Time Carrier
Aided
Trip
Distance
Zone 1 (No Operation) Zone 2
S/Stn 1 S/Stn 2
Zone 2
Time Carrier
Aided
Trip
Distance
Zone 1 (No Operation) Zone 2
Zone 1 Distance
Zone 4 - Blocking
(No Operation)
Time
30
Weak End Infeed
Weak infeed is a condition that can occur during a fault on a transmission
line, either when the circuit breaker is open, so there is no current infeed
from that line end, or when the current infeed is low due to weak
generation behind the bus.
A B
W
S
CR CS (echo)
Z< Z<
CS CR
32
Double End Infeed
I1 I Load I2
V1 RF VF V2
VF = RF ( I1 + I2 )
RF ( I1 + I2 )
RF1 =
I1
33
Double end Infeed
Resistive Fault VA
IA IB
+ +
EA Rf EB
- -
VA = k ⋅ ZL ⋅ IA + (IA + IB ) ⋅ R f
VA IA + IB
ZA = = k ⋅ ZL + ⋅Rf
IA IA
The influence of the fault resistance on impedance measurement
depends on the fault current infeed from the remote end.
34
Double end Infeed
Resistive Fault
IA + IB
⋅ Rf
Rf IA
IA + IB
ZA = k ⋅ ZL + ⋅Rf
IA k ⋅ ZL
Resistive Fault
The apparent fault resistance seen by
the relay can get a phase shift,
depending on the load conditions Rf
before the fault, which can result in
Overreach.
IA + IB
⋅ Rf
IA
I +I k ⋅ ZL
ZA = k ⋅ ZL + A B ⋅ R f
IA
There is a risk that zone 1 will trip for faults outside its reach.
36
Remote Infeeds
Station A Station B
If1 If2
ZL
Vm If1+If2+If3
ZF
F
21 If3
39
Switch On To Fault (SOTF)
40
Switch On To Fault (SOTF)
41
Switch On To Fault (SOTF)
43
Power Swing Detection & Blocking
Power Swing Outer
boundary
Transit
time
44
Power Swing Blocking
45
Power Swing Blocking
46
Stub Protection
When the line disconnector is open in a Breaker and Half system, the
distance protection relay can’t measure proper impedance. Not to risk
incorrect operation, the distance protection must be blocked and a Stub
protection is released.
The Stub protection is a simple over current relay with a controlled release.
Bus A Bus B
Line Disconnector
Open
&
I > Stub Protection Trip
21
47
Series Compensated Transmission Lines
• Used to increase load capacity
A XC =40% B
XL =100%
48
Series Compensated Transmission Lines
A´
R
40%
gap not flashed
A
50
Use of traveling waves for protection
• Advantages
• Fast detection
• Not affected by CT saturation
• Less affected by series capacitors
52
Home