SINGER VALVE

FULL PRODUCT GUIDE - WATERWORKS

Real Solutions for Real Applications


SINGERVALVE.COM
SINGER VALVE PRODUCT CATALOGUE TABLE OF CONTENTS

About Singer Valve – Water Loss Specialists................................................................................................................ 4


Corporate Social Responsibility.................................................................................................................................... 5
Discover the Singer Valve Difference............................................................................................................................ 6
Regulatory Approvals ................................................................................................................................................. 7
Limited Warranty ................................................................................................................................................. 8

MAIN VALVES
106 / S106-PG Single Chamber, Hydraulically Operated Valve...............................................................12
206 / S206-PG Single Chamber, Hydraulically Operated Valve...............................................................20
106 / S106-PT / PTC Double Chamber, Hydraulically Operated Valve............................................................28
206 / S206-PT / PTC Double Chamber, Hydraulically Operated Valve............................................................36
106 / S106-PGM Integral Back-Up, Dual Diaphragm, Automatic Control Valve.......................................44
206 / S206-PGM Integral Back-Up, Dual Diaphragm, Automatic Control Valve.......................................53

MAIN VALVES – OPTIONS


106 / 206-GE Grooved Ends......................................................................................................................62
106 / S106-PG Stainless Steel, Single Chamber, Hydraulically Operated Valve....................................65
106 / 206-IDC Internal Drop Check............................................................................................................ 70
106 / 206-NYM No Yellow Metal................................................................................................................... 71
106 / 206-RW Reclaimed Water Valve ......................................................................................................72
X107 Position Indicator................................................................................................................72
X156 Linear Inductive Valve Position Transmitter....................................................................74
OX Oxy-Nitride Stem.................................................................................................................75
X129 Limit Switch Indicator......................................................................................................... 76
106-AC Anti-Cavitation Control Valve............................................................................................. 78

PRESSURE REDUCING
106 / 206-PR-SM Pressure Reducing Control with Integral Backup...........................................................90
106 / 206-PFC Pressure Flow Control (Modulation) Valve.......................................................................93
106 / 206-PR Pressure Reducing Valve.................................................................................................... 96
106 / 206-PR-48 Pressure Reducing Valve with Low Flow By-Pass............................................................99
106 / 206-PR-C Pressure Reducing and Check Valve...............................................................................102
106 / 206-PR-R Pressure Reducing and Pressure Sustaining Valve.......................................................105
106 / 206-PR-S Pressure Reducing Valve with Downstream Surge Protection....................................108
106 / 206-PR-SC Pressure Reducing Valve with Solenoid Shut Off..........................................................111
106 / 206-2PR-630 Pressure Management Valve...........................................................................................114

RELIEF / SUSTAINING / SURGE


106 / 206-RPS Pressure Relief Valve........................................................................................................118
106 / 206-RPS Pressure Sustaining Valve................................................................................................121
106 / 206-RPS-D Pressure Differential Sustaining Valve ..........................................................................124
106 / 206-RPS-L&H Surge Anticipating Relief Valve........................................................................................127
106 / 206-RPS-RR Surge Anticipating on Rate of Rise of Pressure Relief Valve.......................................130
A106-DL Spring Dynamic Lifter® Spring Pressure Relief.........................................................................133
A106-DL-Air /
A106-DL-ET Dynamic Lifter Air Operated Pressure Relief Valve......................................................136
Please refer to singervalve.com for up-to-date information

2016.1 1
PRODUCT CATALOGUE | TABLE OF CONTENTS

PUMP CONTROL
106 / 206-PG-BPC In-line Booster Pump Control Valve (Single Chamber)................................................142
106 / 206-BPC In-line Booster Pump Control Valve (Double Chamber)..............................................145
106 / 206-DW Bypass Deep Well Pump Control Valve (Double Chamber).........................................148
106 / 206-HC Hydraulic Check Valve......................................................................................................151

LEVEL CONTROL
106 / 206-A-Type 1 Two-Way Flow Altitude Control Valve.............................................................................156
106 / 206-A-Type 2 One-Way Flow Altitude Control Valve.............................................................................159
106 / 206-A-Type 3 Two-Way Flow Altitude Control Valve with Differential Control..................................162
106 / 206-A-Type 4 One-Way Flow Altitude Control Valve with Differential Control..................................165
106 / 206-F-Type 4 Modulating Float Valve.....................................................................................................168
106 / 206-F-Type 5 Non-Modulating Float Valve............................................................................................171

FLOW CONTROL
106 / 206-RF Flow Limiting Control Valve.............................................................................................176
106 / 206-EF-8837BX Excess Flow (Burst Control)..............................................................................................179

ELECTRONIC CONTROL
106 / 206-SC Solenoid Control Valve.....................................................................................................184
106 / 206-2SC-PCO Dual Solenoid Control for Positioning and SCADA Controls.......................................187
106 / 206-2PR-SC-BT Dual Adjustable Set Point Pressure Reducing Valve using Solenoid Control............190
106-SPI-MV Single Point Insertion Flow Metering Valve...................................................................192
106 / 206-2SC-MV Electronic Flow Control and Metering Valve..................................................................194
SCP-TP Single-Process Control Panel Series...............................................................................197
LCP-TP Level Control Panel...........................................................................................................198
MCP-TP Multi Process Control Panel Series.................................................................................199
SAP SAP Panel for Model RPS-L&H-ET; Surge Anticipator Panel........................................201
SPC Singer Pump Control Panel..............................................................................................203
420-DC / 420-AC Automated Pilot Control..................................................................................................205

PILOTS & ACCESSORIES


160 Pressure Reducing Pilot (Normally Open).....................................................................208
160-RF Rate of Flow Pilot (Normally Open)................................................................................209
81-RP Pressure Relief Pilot (Normally Closed)..........................................................................210
83-RP High Pressure Relief Pilot (Normally Closed).................................................................211
81-RPD Differential Pressure Relief Pilot (Normally Closed).....................................................212
301-4 Altitude Pilot Valve............................................................................................................213

2 2016.1
PRODUCT CATALOGUE | TABLE OF CONTENTS

R-400 Modulating Float Pilot .....................................................................................................214


34 Modulating Float Pilot with Vertical Rod........................................................................215
35 SST Modulating Float Pilot...............................................................................................216
39 Non-Modulating Float Pilot with Vertical Rod...............................................................217
43 Rotary Float Pilot (On / Off) with Vertical Rod...............................................................218
106-RD Differential Relief Pilot (Normally Closed).....................................................................220
625-RPD Differential Pilot (Normally Closed)................................................................................221
82-PR Pilot (Normally Open).......................................................................................................222
Model 167 Proportional pilot..............................................................................................................223
Model J0223A Building Trades Reducing Pilot........................................................................................224
SST / Braided Hose Stainless Steel Hose / Stainless Steel Braided Hose....................................................225
Model 26 Operating Speed Control.................................................................................................226
Fixed Restriction .............................................................................................................................................227
852-B Needle Valve Speed Control............................................................................................228
Micrometer Needle Valves...............................................................................................228
Micrometer Flow Control Valves.....................................................................................228
10 & 12 Pilot Check Valves.............................................................................................................228
J0098B / J0097B Strainers.............................................................................................................................229
J1521G / J1521M Arion Strainers...................................................................................................................230

TECHNICAL & SIZING


106 / 206 .............................................................................................................................................232
Cv And Kv Factor & the Straight Line.......................................................................................................................232
Drooping Portion of The Curves...............................................................................................................................233
When Actual Flow Is Less Than The Value Shown By The Graph.........................................................................233
Operating Ranges .............................................................................................................................................233
106 Series Flow vs. Pressure Drop Curve – Globe Body, Flat Diaphragm...........................................................234
106 Series Flow vs. Pressure Drop Curve – Globe Body, Rolling Diaphragm......................................................235
106 Series Flow vs. Pressure Drop Curve – Angle Body, Flat & Rolling Diaphragm...........................................236
206 Series Flow vs. Pressure Drop Curve – Globe & Angle, Flat & Rolling Diaphragm.....................................237
Dynamic Lifter – Sizing Graph Curve........................................................................................................................238
Series 106-AC – Anti-Cavitation Valve Curve...........................................................................................................239
Cavitation Chart (Inlet vs. Downstream Pressure)..................................................................................................240
Flange Dimensions – Ductile Iron Valves.................................................................................................................241

ENGINEERING NOTES ............................................................................................................................................ 242

HOW TO ORDER
Ordering Instructions .............................................................................................................................................243
Control Valve & Accessories Order Form.................................................................................................................244
SPI-MV Order Form .............................................................................................................................................245
420-DC / 420-AC Order Form ....................................................................................................................................246


Product names, logos, brands, and other trademarks featured or referred to within the
Singer Valve Product Catalogue are the property of their respective trademark holders.

2016.1 3
ABOUT SINGER VALVE | WATER LOSS SPECIALISTS

WATER IS ESSENTIAL FOR LIFE.


According to the International Water Association’s 2010 World Water Congress, 60 per cent of the
world’s population within the next generation will live in cities or urban areas, requiring massive
water and energy services and infrastructure. Water loss in potable water distribution systems
is also a significant issue. In the United States, for example, the associated cost of lost water is
estimated at $15 billion (US) per year. System losses are influenced by a variety of factors including
transmission line material and the age of the piping infrastructure with resulting water losses
between 15 to 70 per cent being quite common worldwide. Another key challenge is sanitation
and waste water management in developed and developing countries.
Because water is essential for life, water conservation, water loss management and waste water
management are absolutely critical to help quench the world’s demand for water.
Singer Valve is committed to conserving water. Since 1957, our pilot operated diaphragm control
valves have been installed on virtually every continent around the world. Whether it is water loss
management in Southeast Asia, water conservation concerns in Saudi Arabia or urban distribution
demands in the United States, we provide water loss management solutions to governments,
cities, companies and contractors around the world.
Many of the innovative products we offer are ones that have been born out of our inherent
desire to solve unique water loss challenges. Presented with a problem, our team of electronic,
instrumentation and control valve specialists are relentless in their research and design until they
know a solution works.
Some of our innovative water loss management valves include:
Model 106 / 206-PR – Standard Pilot Operated Pressure Reducing Valve (refer to page 98)
• One adjustable set-point
• Ideal for most pressure ranges
• Virtually stable low flow
Model 420-DC / 420-AC – SCADA Operated Control Valve (refer to page 206)
• Allows remote adjustment of pilot
• Fail safe operation
• Predictable, repeatable accuracy

Model 2PR-630 – Pressure Management Valve (refer to page 93)


• Substantially reduces water loss
• Decreases downstream pipe bursts and associated repair costs
•  A simple package that saves water loss and money

Model 2PR-SC-BT – Dual Adjustable Set-Point Pressure Reducing Valve


(refer to singervalve.com)
•  Two adjustable set-points for high and low pressure
•  Time-based selection via latching solenoid and timer

Model PR-8761A – Extremely Low Supply Pressure Reducing Valve


(refer to singervalve.com)
• M  aintains virtually constant downstream pressure regardless of fluctuations in supply
pressure or flow
•  High capacity pilot provides optimum modulation as required
•  Hydraulically operated – no electrical requirements

4 2016.1
CORPORATE SOCIAL RESPONSIBILITY

OUR VISION
To be the preferred provider of the most innovative, reliable water control solutions in the world.

OUR MISSION
We are innovative designers and manufacturers of high quality differentiated control valves with
excellent technical support and service to our customers.

OUR COMMITMENT TO THE ENVIRONMENT


At Singer Valve, we care about the environment. After all, we’re in the water conservation business,
assisting water utilities worldwide to reduce water loss and leakage. But, our concern goes beyond
our products and solutions. We are committed to implementing sustainable manufacturing
processes and environmentally-friendly office practices on a daily basis. Why? Just as every drop
of water counts toward conservation, the way we handle every piece of paper, every ounce of
metal and every litre of oil counts toward preserving and protecting the environment. For us, being
green means staying green.
Our efforts include:
• recycling target materials
• a separating, recovering process of waste fluids
• reducing, reusing and recycling programs

ABOUT OUR CATALOGUE


This catalogue is printed on paper certified by the Forest Stewardship Council® (FSC®).
FSC® is an independent, non-governmental, not-for-profit organization established in 1993 to
promote the responsible management of the world’s forest.

2016.1 5
DISCOVER THE SINGER VALVE DIFFERENCE

Removable, separate stem


cap reduces bent stems,
reducing inspection and
assembly time

Our AISI 316 Stainless steel external fasteners


Lifting eye bolts on Stainless Steel
rolling diaphragm prevent rust, reducing maintenance
spring is corrosion
models allows easy, resistant
safe removal of Smaller, lighter cover
inner ww assembly improves worker safety,
reduces maintenance

EPDM elastomer
diaphragm is
chlorine and Bonnet removes easily thanks
chloramine to locating-pin technology
resistant

Stainless steel
anti-vibration fasteners
Fusion create a dependable
bonded maintenance-free seat
coating inside
and outside
for improved
flow and
resistance to
wear Extra threaded
taps on main
valve allow
for easy re-
orientation of
pilot system

Accessible oversized
wrench flat means easy
Our AISI 316 Stainless
disassembly of inner Our AISI 316 Stainless
Steel stem is corrosion
valve Steel seat ring is
resistant
guaranteed for life

*Rolling diaphragm design offers


unequalled low flow stability

Valve Sizes: 1/2" to 40” / 15 mm to 1000 mm


Flows from: 0.5 to 55,470 USGPM / 0.03 to 3,500 L/s
*Not available in all size/model combinations. Consult with Singer Valve.
All 3D graphics done by:

6 2016.1
REGULATORY APPROVALS

Singer Valve is proud to hold a wide range of regulatory approvals to meet the requirements of
your application.
Not all regulatory requirements are available in all sizes and model combinations. Singer Valve will
provide approval details upon request.
Regulatory requirements must be specified at time of order for correct processing and labelling.
Processing fees may apply.
Singer Valve castings are based on ANSI Class 150 or 300 standards and drilled as per ANSI B16.42
or threaded NPT. Class 150 are machined flat faced while class 300 are machined raised face.
ANSI standard dimension are presented in this catalogue in US Units (inches) and Metric Units
(millimeters). Also available are ANSI flanges drilled to ISO 7005-2 / BS4504 PN10, PN16, PN25, PN40,
or threaded BSPT. ISO standard dimensions are presented in this catalogue in US Units (inches) and
Metric Units (millimeters). Australian Standard AS4087 machined to Class 16 or Class 35.

FM
APPROVED

U
® L
C US

2016.1 7
SINGER VALVE INC. | LIMITED WARRANTY

This limited warranty replaces and supersedes all other warranties previously given. All products
(the “Products”) manufactured by Singer Valve Inc. (“Singer”) are warranted for THREE YEARS (the
“Warranty Period”) from date of purchase (as confirmed by invoice) against manufacturing defects
in material and workmanship which develop in the service for which the Products are designed,
provided the Products were installed and used in accordance with all applicable instructions and
limitations issued by Singer. Singer will, at its sole discretion, repair or replace defective material,
free of charge, if returned to Singer’s factory, transportation charges prepaid, provided that, after
Singer’s inspection and review, the material is found to have been defective at time of shipment to
the Purchaser. Singer is not under any circumstances liable in any respect for any defective Products
beyond the Warranty Period.
This warranty is conditional upon the Purchaser giving Singer immediate written notice of discovery of
the defect.
Repairs or parts replaced under this warranty are warranted only throughout the remainder of the
Warranty Period.
This warranty is in the nature of liquidated damages to which the Purchaser might otherwise be
entitled at law or in equity. The Purchaser hereby agrees that, in lieu of any action for fundamental
breach of contract or breach of a fundamental term of a contract, it will rely solely on this warranty.
This warranty does not apply to any Product modified or changed in design or function after shipment
to the Purchaser, nor to components which are subject to the warranty conditions of another
manufacturer. Electronic components used by Singer, manufactured by others, are warranted by their
manufacturer for ONE YEAR from date of purchase.
Singer is not under any circumstances, including without limitation, any default, negligence or breach
of whatsoever nature by Singer, liable, whether during the Warranty Period or after the Warranty
Period, for any claims for labour, installation costs, damages or other special or consequential
damages including, but not limited to, loss of revenue or profits, or any other expenses incurred by
reason of any Products found to be defective. Singer is not liable for any incidental or consequential
loss, damages or expenses (including loss of use) caused by any defects in the Product, by repair of
it or arising directly or indirectly from its use. Singer is not liable for any damage or charge for labour
or expense in making unauthorized repairs or adjustments to any Product. Singer is not liable for any
damage or charges sustained in the adaptation or use of its engineering data and services.
This warranty does not apply if the Product has been altered or repaired by others. Singer will make
no allowances or credit for such repairs or alterations unless first authorized in writing by Singer.
No representative of Singer has authority to change any of the foregoing terms or to assume on
behalf of Singer any additional liability or responsibility in connection with any Product.
THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES, CONDITIONS
AND REPRESENTATIONS, WHETHER EXPRESS OR IMPLIED, ORAL OR
WRITTEN, STATUTORY OR OTHERWISE, INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTIES
OR CONDITIONS OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OR DURABILITY. ALL
OTHER WARRANTIES, CONDITIONS AND REPRESENTATIONS ARE HEREBY CANCELLED.

8 2016.1
INTERESTED IN AN INDUSTRY OTHER THAN WATERWORKS?

CHECK OUT OTHER PRODUCT CATALOGUES AND BROCHURES, AVAILABLE THROUGH


YOUR SINGER VALVE SALES REPRESENTATIVE.

FIRE PROTECTION CATALOGUE

INDUSTRIAL CONDENSED CATALOGUE

2016.1 9
METRO H20

EXPERIENCE SINGER VALVES IN ACTION. EXPLORE OUR INTERACTIVE APP.

Discover MetroH20 on our website: SINGERVALVE.COM

- Interactive software player


- Take a closer look at water systems
- See how valves work in applications
- A great tool for engineers
- Available for download
Everything you’ve ever wanted in an automatic control valve. At Singer Valve,
we design and manufacture control valves that can handle extreme pressure,
sense the slightest danger or call for back-up in emergencies.

Our innovative, patented technology translates into proven solutions for


real life applications such as water loss, high pressure drops and inaccurate
pressure management. Plagued with cavitation noise and damage? Our
double cage anti-cavitation control valve solves both. For precise pressure
management, our single rolling diaphragm PR valve is the answer.

Main Valves
MAIN VALVES

MODELS 106-PG / S106-PG SINGLE CHAMBER,


HYDRAULICALLY OPERATED VALVE

KEY FEATURES
• Anti-cavitation option is ideal for high pressure drop situations
• Available in globe and angle style

PRODUCT OVERVIEW
The 106-PG series control valve is designed to suit a large variety of
applications such as pressure, flow or level control. This hydraulically
operated valve introduces or releases water from the control chamber
above the diaphragm to effectively maintain accurate water control
Refer to Main Valve Options on page 62 and Pilots & Accessories on
page 207 to further customize the valve to suit specific applications.

PRODUCT LINE DRAWING ALTERNATIVE MODELS


1. Removable Stem Cap
2. ASTM A536 Ductile Iron Construction
3. Diaphragm EPDM
4. EPDM Resilient Disc
5. AISI 316 Stainless Steel Seat
6. AISI 316 Stainless Steel Stem A106-PG Angle 106-PG Threaded
7. NSF 61 Fusion Bonded Epoxy Coating

1
SELECTION
2 Automatic control valves operate by introducing
or exhausting water from above the diaphragm at
controlled rates. A pressure differential is required
3 and is either inlet to outlet or inlet to atmosphere,
depending on the application. Valves are sized to
4
provide an appropriate pressure drop for each
5 application. Most valves require a minimum of 10
psi / 0.7 bar pressure drop to operate. This applies
mostly to valves that have the bonnet vented to
6
downstream. With minimum of 5 psi / 0.35 bar
downstream pressure, many valves can be made to
open fully by venting the bonnet to atmosphere.
Singer control valves are designed for use with clean
potable water. Applications for other media are
possible. Consult with Singer Valve.

12 2016.1
MODELS 106-PG / S106-PG
SINGLE CHAMBER, HYDRAULICALLY OPERATED VALVE

VALVE SIZES & MATERIALS


Valve Styles
Ductile Stainless Steel
Available Sizes Threaded Flanged Threaded Flanged
Globe 1 in to 3 in (25-80 mm) 1-1/2 in to 36 in (40-900 mm) 1/2 in to 2 in (15-50 mm) 1-1/2 in to 6 in (40-150 mm)
2 in to 12 in, 16 in
Angle 1 in to 3 in (25-80 mm) N/A N/A
(50-300 mm, 400 mm)

Valve Components
Ductile Stainless Steel
Standard Optional Standard Optional
1. Valve Body, Cover 65-45-12 Ductile Iron - 316 Stainless Steel -
2. Seat Ring 316 Stainless Steel - 316 Stainless Steel -
3. Disc Retainer B16 Brass / B62 Bronze / A536 Ductile Iron 316 Stainless Steel 316 Stainless Steel -
4. Stem 316 Stainless Steel - 316 Stainless Steel -
5. Stem Nut B16 Brass 316 Stainless Steel 316 Stainless Steel -
6. Spring 316 Stainless Steel - 316 Stainless Steel -
7. Guide Bushings B16 Brass or SAE 660 Bronze 316 Stainless Steel 316 Stainless Steel -
8. Diaphragm EPDM Buna-N / Viton (limited sizes) EPDM Buna-N / Viton (limited sizes)
9. Resilient Disc EPDM Buna-N / Viton (limited sizes) EPDM Buna-N / Viton (limited sizes)
NSF61 Approved Fusion Bonded Epoxy
10. Coating Consult factory - -
Thickness 10-14 mils (250 – 350 microns)
11. Fasteners 18-8 Stainless Steel 316 Stainless Steel 18-8 Stainless Steel 316 Stainless Steel

Careful consideration of the possibility of cavitation


must be given. Anti-cavitation trim is available to
PILOTS & ACCESSORIES, REFER TO PG. 207
control the cavitation, reduce noise and prevent MATERIALS OF CONSTRUCTION
damage. Refer to 106-AC (page 78) or consult with Individual components can be upgraded from ductile
Singer Valve. iron, bronze and brass to stainless steel, for most
The 106-PG single chambered valve is the basic sizes. Consult with Singer Valve.
valve used in practically every model bearing the 106
description. The pilot systems are designed to meet
the functional and performance requirements of MODEL PGM
specific applications. Sizing is ultimately determined Provides a fully operational back-up system in the
by the specific application. event of a diaphragm or pilot failure. See page 46.

AVAILABLE OPTIONS ANTI-CAVITATION TRIM


Further customize the valve by adding any of the Model 106-AC allows very high pressure drops in one
available options below. valve, while retaining the standard 106 valve features.
See page 78.
MAIN VALVE OPTIONS, REFER TO PAGE 62
Position Indicators (Available for install at Singer ORDERING INSTRUCTIONS
Valve or as a field modification) Refer to page 244 for the order form and ordering
• Model X107 stem mounted position indicators instructions.
• Model X129 limit switch assembly with Single Pole
Double Throw limit switch (Double Pole Double
Throw optional)
• Model X156 position transmitter (4 to 20 mA)
Oxy-Nitride Stem Grooved Ends
Internal Drop Check Reclaim Water
External Spring Lift

2016.1 13
MODELS 106-PG / S106-PG
SINGLE CHAMBER, HYDRAULICALLY OPERATED VALVE

ANSI VALVE DATA (US UNITS)


Size DWG Standard Flat Diaphragm System
Inches REF ANSI 1/2 in 3/4 in 1 in 1-1/4 in 1-1/2 in 2 in 2-1/2 in 3 in 4 in 6 in 8 in
Globe Dimensions All figures shown in inches unless otherwise stated
Lay Length A FNPT 6.75 6.75 6.75 9.38 11.00 13.50 - - -
Centerline to Bottom D FNPT 2.50 2.50 2.50 2.75 3.38 3.68 - - -
Lay Length A 150F - - 8.50 9.38 11.00 12.00 15.00 20.00 25.38
Centerline to Bottom D 150F - - 2.75 3.00 3.50 3.75 4.60 5.60 7.63
Lay Length A 300F - - 9.00 10.00 11.63 13.25 15.63 21.00 26.38
Centerline to Bottom D 300F - - 3.25 3.25 3.75 4.13 5.09 6.34 7.88
Angle Dimensions
Center Inlet to Discharge B FNPT 3.38 3.38 3.38 4.69 5.50 6.63 - - -
Center Discharge to Inlet F FNPT 3.00 3.00 3.00 3.25 4.00 4.63 - - -
Center Inlet to Discharge B 150F - - - 4.75 5.50 6.06 7.50 10.00 12.75
Center Discharge to Inlet F 150F - - - 3.25 4.00 4.06 5.00 6.00 8.00
Center Inlet to Discharge B 300F - - - 5.00 5.88 6.43 7.88 10.50 13.25
Available in Stainless Steel only. See page 65.

Available in Stainless Steel only. See page 65.

Center Discharge to Inlet F 300F - - - 3.50 4.31 4.43 5.31 6.50 8.50
Common Dimensions (Globe & Angle)
Width C 4.88 4.88 6.13 6.50 8.19 9.25 10.88 16.75 21.63
Height (To Stem Cap)
E 4.38 4.38 4.38 4.75 7.50 8.00 9.15 11.75 14.91
Globe
Height (To Stem Cap) Angle E 4.38 4.38 4.38 4.75 7.50 8.00 9.15 11.75 14.91
Body Port Tapping FNPT 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 1/2
Stem Cap Plug MNPT 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Cover Port Tapping FNPT 3/8 3/8 3/8 3/8 3/8 3/8 3/8 1/2 1/2
Valve Stroke 1/2 1/2 1/2 9/16 15/16 1-1/8 1-7/16 1-11/16 2-7/8
Displaced Bonnet Volume (Gallons) 0.007 0.007 0.007 0.02 0.1 0.1 0.2 0.6 1.7
Approximate Shipping Weight (Lbs) 20 20 20 40 65 100 175 400 650
Flow Capacities (USGPM) Globe & Angle
Cv - Globe 28 30 32 55 80 110 200 460 800
Cv - Angle 24 24 26 63 90 135 230 535 950
Continuous (Globe) 49 93 125 210 300 460 800 1800 3100
Intermittent (Globe) 61 120 160 260 375 575 1000 2250 3875
Momentary (Globe) 110 170 250 470 670 1030 1800 4000 7000
Maximum Pressure Ratings (Ductile Only)
PSI1 FNPT 400 400 400 400 400 400 - - -
PSI 150F - - 250 250 250 250 250 250 250
PSI1 300F - - 400 400 400 400 400 400 400
Maximum Temperature
Fahrenheit 180º 180º 180º 180º 180º 180º 180º 180º 180º
1
Valves rated and stamped 400 psi as standard. Valves rated and stamped 600 psi on request.

See pilot system information, page 207.


For additional Engineering notes, see page 242.

14 2016.1
MODELS 106-PG / S106-PG
SINGLE CHAMBER, HYDRAULICALLY OPERATED VALVE

ANSI VALVE DATA (US UNITS)


Size DWG Standard Rolling Diaphragm System
Inches REF ANSI 6 in 8 in 10 in 12 in 14 in 16 in 20 in 24 in 36 in
Globe Dimensions All figures shown in inches unless otherwise stated.
Lay Length A FNPT - - - - - - - - -
Centerline to Bottom D FNPT - - - - - - - - -
Lay Length A 150F 20.00 25.38 29.75 34.00 31.00 41.38 52.00 61.50 76.00
Centerline to Bottom D 150F 5.60 7.63 8.56 9.50 10.50 11.75 14.43 17.13 23.50
Lay Length A 300F 21.00 26.38 31.12 35.50 32.50 43.50 53.62 63.25 78.00
Centerline to Bottom D 300F 6.34 7.88 9.31 10.25 11.50 12.75 15.75 19.65 25.50
Angle Dimensions
Center Inlet to Discharge B FNPT - - - - - - - - -
Center Discharge to Inlet F FNPT - - - - - - - - -
Center Inlet to Discharge B 150F - - 11.50 13.75 - 18.00 - - -
Center Discharge to Inlet F 150F - - 12.50 12.50 - 15.69 - - -
Center Inlet to Discharge B 300F - - 12.19 14.50 - 18.81 - - -
Center Discharge to Inlet F 300F - - 13.19 13.25 - 16.50 - - -
Common Dimensions (Globe & Angle)
Width C 12.75 16.09 22.13 26 26 32 35 49.68 64.5
Height (To Stem Cap) Globe E 15.43 20.19 23.31 26.75 26.8 31.4 35.5 45.75 61
Height (To Stem Cap) Angle E - - 20 23.75 - 28.5 - - -
Body Port Tapping FNPT 3/8 1/2 3/4 3/4 3/4 3/4 3/4 3/4 1
Stem Cap Plug MNPT 3/8 3/8 3/4 3/4 3/4 3/4 3/4 3/4 1
Cover Port Tapping FNPT 1/2 1/2 3/4 3/4 3/4 3/4 3/4 3/4 1
Valve Stroke 1-11/16 2-7/8 3-1/4 3-3/4 3-3/4 4-3/4 5-9/16 6 9
Displaced Bonnet Volume (Gallons) 0.50 1.00 1.50 2.30 2.30 6.75 9.00 14.75 43.00
Approximate Shipping Weight (Lbs) 350 650 900 1300 1400 2300 3450 5000 13500
Flow Capacities (USGPM) Globe & Angle
Cv - Globe 460 800 1300 2100 2575 3300 5100 7600 16340
Cv - Angle - - 1400 2450 - 4000 - - -
Continuous (Globe) 1800 3100 4900 7000 8500 11000 17500 25000 55470
Intermittent (Globe) 2250 3875 6100 8800 11500 14250 21700 31200 69338
Momentary (Globe) 4000 7000 11000 16000 19000 25000 39000 56200 124700
Maximum Pressure Ratings (Ductile Only)
PSI1 FNPT - - - - - - - - -
PSI 150F 250 250 250 250 250 250 250 250 250
PSI1 300F 400 400 400 400 400 400 400 400 400
Maximum Temperature
Fahrenheit 180º 180º 180º 180º 180º 180º 180º 180º 180º
Valves rated and stamped 400 psi as standard. Valves rated and stamped 600 psi on request.
1

Globe Style Angle Style


Rolling Diaphragm Rolling Diaphragm

'E'
'E' 'E' 'E' Flow
'E' 'E'
'E' Flange Flow
'E' 'E' 'C' Diameter
'F' 'C' 'C' 'D' Dim
'F' 'D' 'F' 'F'
'F' 'F' 'D' 'D' Flange Feet
'B' 'A' 'B' for Safety and Standard Opposite
Convenience
'B' 'B' 'A' 'A' 'B' 'B'
See pilot system information, page 207.
For additional Engineering notes, see page 242.

2016.1 15
MODELS 106-PG / S106-PG
SINGLE CHAMBER, HYDRAULICALLY OPERATED VALVE

ANSI VALVE DATA (METRIC UNITS)


Size DWG Stnd Flat Diaphragm System
mm REF ANSI 15 mm 20 mm 25 mm 32 mm 40 mm 50 mm 65 mm 80 mm 100 mm 150 mm 200 mm
Globe Dimensions All figures show in mm unless otherwise stated
Lay Length A FNPT 171 171 171 238 279 343 - - -
Centerline to Bottom D FNPT 64 64 64 70 86 93 - - -
Lay Length A 150F - - 216 238 279 305 381 508 645
Centerline to Bottom D 150F - - 70 76 89 95 117 142 200
Lay Length A 300F - - 229 254 295 337 397 533 670
Centerline to Bottom D 300F - - 83 83 95 105 129 161 200
Angle Dimensions
Center Inlet to Discharge B FNPT 86 86 86 119 140 168 - - -
Center Discharge to Inlet F FNPT 76 76 76 83 102 118 - - -
Center Inlet to Discharge B 150F - - - 121 140 154 191 254 324
Center Discharge to Inlet F 150F - - - 83 102 103 127 152 203
Center Inlet to Discharge B 300F - - - 127 149 163 200 267 337
Center Discharge to Inlet F 300F - - - 89 109 113 135 165 216
Available in Stainless Steel only. See page 65.

Available in Stainless Steel only. See page 65.

Common Dimensions (Globe & Angle)


Width C 124 124 156 165 208 235 276 425 549
Height (to stem cap)
E 111 111 111 121 191 203 232 298 379
Globe
Height (to stem cap)
E 111 111 111 121 191 203 232 298 379
Angle
Body Port Tapping FNPT in 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 1/2
Stem Cap Plug MNPT in 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Cover Port Tapping FNPT in 3/8 3/8 3/8 3/8 3/8 3/8 3/8 1/2 1/2
Valve Stroke mm 13 13 13 14 25 29 37 43 73
Displaced Bonnet Volume (Litres) 0.03 0.03 0.03 0.1 0.3 0.3 0.8 2.1 6.3
Approximate Shipping Weight (Kilograms) 9 9 9 18 29 45 79 181 295
Flow Capacities (L/s) Globe & Angle
Kv - Globe 6.6 7.1 7.6 13 19 26 47 110 190
Kv - Angle 5.7 5.7 6.2 15 21 32 55 127 225
Continuous (Globe) 3 6 8 13 19 29 50 114 196
Intermittent (Globe) 4 8 10 16 24 36 63 142 244
Momentary (Globe) 7 11 16 30 42 65 114 252 442
Maximum Pressure Ratings (Ductile Only)
Bar1 FNPT 27.6 27.6 27.6 27.6 27.6 27.6 - - -
Bar 150F - - 17 17 17 17 17 17 17
Bar1 300F - - 27.6 27.6 27.6 27.6 27.6 27.6 27.6
Maximum Temperature
Celcius 82º 82º 82º 82º 82º 82º 82º 82º 82º
Valves rated and stamped 27.6 bar as standard. Valves rated and stamped 41 bar on request
1

See pilot system information, page 207.


For additional Engineering notes, see page 242.

16 2016.1
MODELS 106-PG / S106-PG
SINGLE CHAMBER, HYDRAULICALLY OPERATED VALVE

ANSI VALVE DATA (METRIC UNITS)


Size DWG Standard Rolling Diaphragm System
mm REF ANSI 150 mm 200 mm 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm 900 mm
Globe Dimensions All figures shown in mm unless otherwise stated.
Lay Length A FNPT - - - - - - - - -
Centerline to Bottom D FNPT - - - - - - - - -
Lay Length A 150F 508 645 756 864 787 1051 1321 1562 1930
Centerline to Bottom D 150F 142 200 217 241 267 298 367 435 597
Lay Length A 300F 533 670 790 902 826 1105 1362 1607 1981
Centerline to Bottom D 300F 161 200 236 260 292 324 400 499 648
Angle Dimensions
Center Inlet to Discharge B FNPT - - - - - - - - -
Center Discharge to Inlet F FNPT - - - - - - - - -
Center Inlet to Discharge B 150F - - 292 349 - 457 - - -
Center Discharge to Inlet F 150F - - 318 318 - 399 - - -
Center Inlet to Discharge B 300F - - 310 368 - 478 - - -
Center Discharge to Inlet F 300F - - 335 337 - 419 - - -
Common Dimensions (Globe & Angle)
Width C 324 409 562 660 660 813 889 1262 1623
Height (To Stem Cap) Globe E 392 513 592 679 681 798 902 1162 1550
Height (To Stem Cap) Angle E - - 508 603 - 724 - - -
Body Port Tapping FNPT Inches 3/8 1/2 3/4 3/4 3/4 3/4 3/4 3/4 1
Stem Cap Plug MNPT Inches 3/8 3/8 3/4 3/4 3/4 3/4 3/4 3/4 1
Cover Port Tapping FNPT Inches 1/2 1/2 3/4 3/4 3/4 3/4 3/4 3/4 1
Valve Stroke mm 43 73 83 95 95 120 141 150 229
Displaced Bonnet Volume (Litres) 2 4 6 9 9 26 34 56 163
Approximate Shipping Weight (Kilograms) 160 250 480 590 635 1043 1565 2268 6124
Flow Capacities (L/s) Globe & Angle
Kv - Globe 110 190 310 500 610 780 1210 1800 3875
Kv - Angle - - 332 581 - 948 - - -
Continuous (Globe) 114 196 309 442 536 694 1104 1577 3500
Intermittent (Globe) 142 244 385 555 726 899 1370 1968 4375
Momentary (Globe) 252 442 694 1009 1199 1577 2460 3546 7867
Maximum Pressure Ratings (Ductile Only)
Bar1 FNPT - - - - - - - - -
Bar 150F 17 17 17 17 17 17 17 17 17
Bar1 300F 27.6 27.6 27.6 27.6 27.6 27.6 27.6 27.6 27.6
Maximum Temperature
Celcius 82º 82º 82º 82º 82º 82º 82º 82º 82º
Valves rated and stamped 27.6 bar as standard. Valves rated and stamped 41 bar on request
1

Globe Style Angle Style


Rolling Diaphragm Rolling Diaphragm

'E'
'E' 'E' 'E' Flow
'E' 'E'
'E' Flange Flow
'E' 'E' 'C' Diameter
'F' 'C' 'C' 'D' Dim
'F' 'D' 'F' 'F'
'F' 'F' 'D' 'D' Flange Feet
'B' 'A' 'B' for Safety and Standard Opposite
Convenience
'B' 'B' 'A' 'A' 'B' 'B'
See pilot system information, page 207.
For additional Engineering notes, see page 242.

2016.1 17
MODELS 106-PG / 206-PG
SINGLE CHAMBER, HYDRAULICALLY OPERATED VALVE

Size DWG Stnd Flat Diaphragm System


mm REF ISO 15 mm 20 mm 25 mm 32 mm 40 mm 50 mm 65 mm 80 mm 100 mm 150 mm 200 mm
Globe Dimensions All figures show in mm unless otherwise stated
Lay Length A BSPT 171 171 171 238 279 343 - - -
Centerline to Bottom D BSPT 64 64 64 70 86 93 - - -
Lay Length A PN10 / PN16 - - 229 238 279 318 381 508 645
Centerline to Bottom D PN10 / PN16 - - 83 76 89 100 117 142 200
Lay Length A PN25 / PN40 - - 229 238 279 318 397 533 670
Centerline to Bottom D PN25 / PN40 - - 83 76 89 100 129 161 200
Angle Dimensions
Center Inlet to Discharge B BSPT 86 86 86 119 140 168 - - -
Center Discharge to Inlet F BSPT 76 76 76 83 102 118 - - -
Center Inlet to Discharge B PN10 / PN16 - - - 121 140 163 191 254 324
Center Discharge to Inlet F PN10 / PN16 - - - 83 102 113 127 152 203
Center Inlet to Discharge B PN25 / PN40 - - - 121 140 163 200 267 337
Available in Stainless Steel only. See page 65.

Available in Stainless Steel only. See page 65.

Center Discharge to Inlet F PN25 / PN40 - - - 83 102 113 135 165 216
Common Dimensions (Globe & Angle)
Width C 124 124 156 165 208 235 276 425 549
Height (To Stem Cap) Globe E 111 111 111 121 191 203 232 298 379
Height (To Stem Cap) Angle E 111 111 111 121 191 203 232 298 379
Body Port Tapping FNPT Inches 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 1/2
Stem Cap Plug MNPT Inches 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Cover Port Tapping FNPT Inches 3/8 3/8 3/8 3/8 3/8 3/8 3/8 1/2 1/2
Valve Stroke mm 13 13 13 14 25 29 37 43 73
Displaced Bonnet Volume (Litres) 0.03 0.03 0.03 0.1 0.3 0.3 0.8 2.1 6.3
Approximate Shipping Weight (Kilograms) 9 9 9 18 29 45 79 181 295
Flow Capacities (L/s) Globe & Angle
Kv - Globe 6.6 7.1 7.6 13 19 26 47 110 190
Kv - Angle 5.7 5.7 6.2 15 21 32 55 123 225
Continuous (Globe) 3 6 8 13 19 29 50 114 196
Intermittent (Globe) 4 8 10 16 24 36 63 142 244
Momentary (Globe) 7 11 16 30 42 65 114 252 442
Maximum Pressure Ratings (Ductile Only)
Bar1 BSPT 27.6 27.6 27.6 27.6 27.6 27.6 - - -
Bar PN16 - - 16 16 16 16 16 16 16
Bar1 PN25 - - 25 25 25 25 25 25 25
Maximum Temperature
Celcius 82º 82º 82º 82º 82º 82º 82º 82º 82º
1
Valves rated and stamped 27.6 bar as standard. Valves rated and stamped 41 bar on request

See pilot system information, page 207.


For additional Engineering notes, see page 242.

18 2016.1
MODELS 106-PG / S106-PG
SINGLE CHAMBER, HYDRAULICALLY OPERATED VALVE

ISO VALVE DATA (METRIC UNITS)


Size DWG Standard Rolling Diaphragm System
MM REF ISO 150 mm 200 mm 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm 900 mm
Globe Dimensions All figures shown in mm unless otherwise stated
Lay Length A BSPT - - - - - - - - -
Centerline to Bottom D BSPT - - - - - - - -
Lay Length A PN10 / PN16 508 645 756 864 787 1051 1321 1562 1930
Centerline to Bottom D PN10 / PN16 142 200 217 241 267 298 367 435 597
Lay Length A PN25 / PN40 533 670 790 864 826 1105 1362 1607 1981
Centerline to Bottom D PN25 / PN40 161 200 243 241 292 324 400 499 648
Angle Dimensions
Center Inlet to Discharge B BSPT - - - - - - - - -
Center Discharge to Inlet F BSPT - - - - - - - - -
Center Inlet to Discharge B PN10 / PN16 - - 292 349 - 457 - - -
Center Discharge to Inlet F PN10 / PN16 - - 318 318 - 399 - - -
Center Inlet to Discharge B PN25 / PN40 - - 310 349 - 478 - - -
Center Discharge to Inlet F PN25 / PN40 - - 335 318 - 419 - - -
Common Dimensions (Globe & Angle)
Width C 324 409 562 660 660 813 889 1262 1422
Height (To Stem Cap)
E 346 455 592 679 681 798 902 1162 1550
Globe
Height (To Stem Cap)
E - - 508 603 - 724 - - -
Angle
Body Port Tapping FNPT Inches 3/8 1/2 3/4 3/4 3/4 3/4 3/4 3/4 1
Stem Cap Plug MNPT Inches 3/8 3/8 3/4 3/4 3/4 3/4 3/4 3/4 1
Cover Port Tapping FNPT Inches 1/2 1/2 3/4 3/4 3/4 3/4 3/4 3/4 1
Valve Stroke mm 43 73 83 95 95 120 141 150 229
Displaced Bonnet Volume (Litres) 2 4 6 9 9 26 34 56 163
Approximate Shipping Weight (Kilograms) 160 250 480 590 635 1043 1565 2268 6124
Flow Capacities (L/s) Globe & Angle
Kv - Globe 110 190 310 500 610 780 1210 1800 3875
Kv - Angle - - 332 581 - 948 - - -
Continuous (Globe) 114 196 309 442 536 694 1104 1577 3500
Intermittent (Globe) 142 244 385 555 726 899 1370 1968 4375
Momentary (Globe) 252 442 694 1009 1199 1577 2460 3546 7867
Maximum Pressure Ratings (Ductile Only)
Bar BSPT - - - - - - - - -
Bar PN16 16 16 16 16 16 16 16 16 16
Bar PN25 25 25 25 25 25 25 25 25 25
Maximum Temperature
Celcius 82º 82º 82º 82º 82º 82º 82º 82º 82º

See pilot system information, page 207.


For additional Engineering notes, see page 242.

2016.1 19
MAIN VALVES

MODEL 206-PG / S206-PG


SINGLE CHAMBER, HYDRAULICALLY OPERATED VALVE

KEY FEATURES
• Available in globe and angle style

PRODUCT OVERVIEW
The 206-PG series control valve is the preferred choice for pressure
reducing valves, flow control valves, relief valves and applications
with lower to medium flows. This hydraulically operated valve
introduces or releases water from the control chamber above the
diaphragm to effectively maintain water control.
Further adapt the valve to provide control for a wide range of
functions by selecting from Singer Valve’s wide range of pilot
and accessories options. Customize for functions like controlling
pressure, flow or level or in almost limitless combinations to suit
specific applications.

PRODUCT LINE DRAWING ALTERNATIVE MODELS


1. Removable Stem Cap
2. ASTM A536 Ductile Iron Construction
3. Diaphragm Buna-N or EPDM
4. Buna-N or EPDM Resilient Disc
5. AISI 316 Stainless Steel Seat
6. AISI 316 Stainless Steel Stem
7. NSF 61 Fusion Bonded Epoxy Coating
A206-PG Angle

1
SELECTION
2 Automatic control valves operate by introducing
or exhausting water from above the diaphragm at
3 controlled rates. A pressure differential is required
4 and is either inlet to outlet or inlet to atmosphere,
depending on the application. Valves are sized to
5 provide an appropriate pressure drop for each
application. Most valves require a minimum of 10 psi /
6 0.7 bar pressure drop to operate. This applies mostly
to valves that have the bonnet vented to downstream.
7 With minimum of 5 psi / 0.35 bar downstream
pressure, many valves can be made to open fully by
venting the bonnet to atmosphere.
Singer Valve control valves are designed for use with
clean potable water. Applications for other media are
possible. Consult with Singer Valve.

20 2018.2
MODEL 206-PG / S206-PG
SINGLE CHAMBER, HYDRAULICALLY OPERATED VALVE

VALVE SIZES & MATERIALS


Valve Materials
Standard Optional
Available Sizes Flanged -
Globe 3 in to 48 in (80-1200 mm) -
Angle 4 in to 8 in (100-200 mm) -
Valve Components
1.Valve Body, Cover 65-45-12 Ductile Iron -
2. Seat Ring 316 Stainless Steel -
3. Disc Retainer B16 Brass / B62 Bronze / A536 Ductile Iron 316 Stainless Steel
4. Stem 316 Stainless Steel -
5. Stem Nut B16 Brass 316 Stainless Steel
6. Spring 316 Stainless Steel -
7. Guide Bushings B16 Brass or SAE 660 Bronze 316 Stainless Steel
8. Diaphragm EPDM Buna-N / Viton (limited sizes)
9. Resilient Disc EPDM Buna-N / Viton (limited sizes)
10. Coating NSF61 Approved Fusion Bonded Epoxy - Thickness 10-14 mils (250-300 microns) Consult factory
11. Fasteners AISI 18-8 Stainless Steel AISI 316 Stainless Steel

Careful consideration of the possibility of cavitation


must be given. Anti-cavitation trim is available to
PILOTS & ACCESSORIES, REFER TO PG. 207
control the cavitation, reduce noise and prevent
damage. Refer to 106-AC (page 80) or consult with MATERIALS OF CONSTRUCTION
Singer Valve.
Individual components can be upgraded from ductile
The Singer Model 206-PG single chambered valve is iron, bronze and brass to stainless steel, for most
the basic valve used in practically every model bearing sizes. Consult with Singer Valve.
the 206 description. The pilot systems are designed to
meet the functional and performance requirements
of specific applications. Sizing is ultimately MODEL PGM
determined by the specific application. Provides a fully operational back-up system in the
event of a diaphragm or pilot failure. See page 46.
AVAILABLE OPTIONS
Further customize the valve by adding any of the ORDERING INSTRUCTIONS
available options below. Refer to page 244 for the order form and ordering
instructions.
MAIN VALVE OPTIONS, REFER TO PAGE 62
Position Indicators (Available for install at Singer ENGINEERING NOTES, REFER TO PAGE 242
Valve or as a field modification)
• Model X107 stem mounted position indicators
• Model X129 limit switch assembly with Single Pole
Double Throw limit switch (Double Pole Double
Throw optional)
• Model X156 position transmitter (4 to 20 mA)
Oxy-Nitride Stem Grooved Ends
Internal Drop Check Reclaimed Water
External Spring Lift

2018.2 21
MODEL 206-PG / S206-PG
SINGLE CHAMBER, HYDRAULICALLY OPERATED VALVE

ANSI VALVE DATA (US UNITS)


Size DWG Standard Flat Diaphragm System
Inches REF ANSI 3 in 4 in 6 in 8 in 10 in
Globe Dimensions All figures show in inches unless otherwise stated
Lay Length A NPT - - - - -
Centerline to Bottom D NPT - - - - -
Lay Length A 150F 12.00 15.00 20.13 25.00 24.50
Centerline to Bottom D 150F 4.00 4.60 5.62 6.75 8.56
Lay Length A 300F - 15.63 21.00 26.00 25.88
Centerline to Bottom D 300F - 5.00 6.34 7.50 9.31
Angle Dimensions
Center Inlet to Discharge B NPT - - - - -
Center Discharge to Inlet F NPT - - - - -
Center Inlet to Discharge B 150F - 7.56 10.19 12.50 -
Center Discharge to Inlet F 150F - 5.94 6.19 9.00 -
Center Inlet to Discharge B 300F - 7.88 10.63 13.00 -
Center Discharge to Inlet F 300F - 6.25 6.81 9.50 -
Common Dimensions (Globe & Angle)
Width C 8.19 10.00 12.50 16.00 20.00
Height (To Stem Cap) Globe E 7.50 9.62 10.50 14.13 18.63
Height (To Stem Cap) Angle E - 7.75 8.82 11.30 -
Body Port Tapping FNPT 3/8 3/8 3/8 3/8 1/2
Stem Cap Plug MNPT 3/8 3/8 3/8 3/8 3/8
Cover Port Tapping FNPT 3/8 3/8 3/8 1/2 1/2
Valve Stroke 9/16 1-1/8 1-7/16 1-11/16 2-7/8
Displaced Bonnet Volume (Gallons) 0.02 0.1 0.2 0.6 2
Approximate Shipping Weight (Lbs) 75 100 250 500 650
Flow Capacities (USGPM) Globe & Angle
Cv - Globe 60 150 250 505 985
Cv - Angle - 150 250 560 -
Continuous (Globe) 300 580 1025 2300 4100
Intermittent (Globe) 373 690 1190 2700 4670
Momentary (Globe) 564 1236 2160 4800 8400
Maximum Pressure Ratings
PSI1 FNPT - - - - -
PSI 150F 250 250 250 250 250
PSI1 300F 400 400 400 400 400
Maximum Temperature
Fahrenheit 180º 180º 180º 180º 180º
1
Valves rated and stamped 400 psi as standard. Valves rated and stamped 600 psi on request.

Globe Style
Flat Diaphragm 'E'
Flow
'E' 'E'
'E'
'E' Flange
Flow
'C' Diameter
'F' 'C'
'D' 'F' 'D' 'D' Dim
'D'
Flange Feet'A'
'A' 'A' 'B' 'B' for Safety and Standard Opposite
Convenience

See pilot system information, page 207.


For additional Engineering notes, see page 242.

22 2016.1
MODEL 206-PG / S206-PG
SINGLE CHAMBER, HYDRAULICALLY OPERATED VALVE

ANSI VALVE DATA (US UNITS)


S ize D WG S t a nda r R o lling D ia phra gm S ys t e m
Inc he s R EF A N SI 2 4 in x 2 0
12 in 16 in 18 in 2 0 in2 4 in x 16 in 3 0 in 3 6 in 4 8 in
in
G lo be D im e ns io ns A ll f igure s s ho wn in inc he s unle s s o t he rwis e s t a t e d.
Lay Length A NP T - - - - - - - - -
Centerline to B o tto m D NP T - - - - - - - - -
Lay Length A 150F 27.50 36.00 42.00 45.00 50.50 61.50 69.93 69.93 79.75
Centerline to B o tto m D 150F 9.50 11.75 12.50 13.75 16.50 17.13 20.68 23.75 30.75
Lay Length A 300F 29.00 37.63 43.63 46.63 52.25 63.25 - - -
Centerline to B o tto m D 300F 10.25 12.75 14.00 15.25 18.00 19.65 - - -
A ngle D im e ns io ns

Center Inlet to Discharge B NP T - - - - - - - - -


Center Discharge to Inlet F NP T - - - - - - - - -
Center Inlet to Discharge B 150F - - - - - - - - -
Center Discharge to Inlet F 150F - - - - - - - - -
Center Inlet to Discharge B 300F - - - - - - - - -
Center Discharge to Inlet F 300F - - - - - - - - -
C o m m o n D im e ns io ns ( G lo be & A ngle )
Width C 22.13 26.00 30.31 31.50 36.00 36.00 49.75 49.75 64.50
Height (To Stem Cap) Glo be E 23.31 26.75 31.38 31.38 31.38 34.46 45.75 45.75 61.00
Height (To Stem Cap) A ngle E - - - - - - - - -
B o dy P o rt Tapping FNP T 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 1
Stem Cap P lug M NP T 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 1
Co ver P o rt Tapping FNP T 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 1
Valve Stro ke 3-1/4 3-3/4 4-3/4 4-3/4 4-3/4 5-9/16 6 6 9
Displaced B o nnet Vo lume (Gallo ns) 1.5 2.3 6.8 6.8 6.8 9.0 14.8 14.8 43.0
A ppro ximate Shipping Weight (Lbs) 900 1400 2400 2600 2800 4500 6200 7000 18000
F lo w C a pa c it ie s ( US G P M ) G lo be & A ngle
C v - Glo be 1550 2200 3300 3400 3500 5100 7800 8000 16340
C v - A ngle - - - - - - - - -
Co ntinuo us (Glo be) 6400 9230 16500 16500 16500 21700 33650 33800 55470
Intermittent (Glo be) 7320 10470 20915 20915 20915 26000 37490 37640 69338
M o mentary (Glo be) 13200 19200 30000 30050 30100 39000 67490 67640 124700
M a xim um P re s s ure R a t ings

P SI1 FNP T - - - - - - - - -
P SI 150F 250 250 250 250 250 250 250 250 250
P SI1 300F 400 400 400 400 400 400 400 400 400
M aximum T emp er at ur e
Fahrenheit 180º 180º 180º 180º 180º 180º 180º 180º 180º
1Valves rated and stamped 400 psi as standard. Valves rated and stamped 600 psi on request.

Angle Style Globe Style


Rolling Diaphragm Rolling Diaphragm

'E'
Flow
'E' 'E'
'E'
'E' 'E' Flange
Flow
'C' Diameter
'F' 'C'
'F' 'D' 'D' 'D' Dim
'D' 'F'
'A' 'B' Flange Feet
'A' 'B' 'B'
'A' for Safety and Standard Opposite
Convenience

See pilot system information, page 207.


For additional Engineering notes, see page 242.

2016.1 23
MODEL 206-PG / S206-PG
SINGLE CHAMBER, HYDRAULICALLY OPERATED VALVE

ANSI VALVE DATA (METRIC UNITS)


Size DWG Standard Flat Diaphragm System
mm REF ANSI 80 mm 100 mm 150 mm 200 mm 250 mm
Globe Dimensions All figures show in mm unless otherwise stated
Lay Length A FNPT - - - - -
Centerline to Bottom D FNPT - - - - -
Lay Length A 150F 305 381 511 635 622
Centerline to Bottom D 150F 102 117 143 171 217
Lay Length A 300F - 397 533 660 657
Centerline to Bottom D 300F - 127 161 191 236
Angle Dimensions
Center Inlet to Discharge B FNPT - - - - -
Center Discharge to Inlet F FNPT - - - - -
Center Inlet to Discharge B 150F - 192 259 318 -
Center Discharge to Inlet F 150F - 151 157 229 -
Center Inlet to Discharge B 300F - 200 270 330 -
Center Discharge to Inlet F 300F - 159 173 241 -
Common Dimensions (Globe & Angle)
Width C 208 254 318 406 508
Height (To Stem Cap) Globe E 191 244 267 359 473
Height (To Stem Cap) Angle E - 197 224 287 -
Body Port Tapping FNPT Inches 3/8 3/8 3/8 3/8 1/2
Stem Cap Plug MNPT Inches 3/8 3/8 3/8 3/8 3/8
Cover Port Tapping FNPT Inches 3/8 3/8 3/8 1/2 1/2
Valve Stroke mm 14 29 37 43 73
Displaced Bonnet Volume (Litres) 0.1 0.3 0.8 2 6
Approximate Shipping Weight (Kilograms) 34 45 113 227 295
Flow Capacities (L/s) Globe & Angle
Kv - Globe 14 36 60 120 230
Kv - Angle - 36 60 133 -
Continuous (Globe) 19 37 65 145 259
Intermittent (Globe) 24 44 75 170 295
Momentary (Globe) 36 78 136 303 530
Maximum Pressure Ratings
Bar FNPT - - - - -
Bar 150F 17 17 17 17 17
Bar1 300F 27.6 27.6 27.6 27.6 27.6
Maximum Temperature
Celcius 82º 82º 82º 82º 82º
1
Valves rated and stamped 27.6 bar as standard. Valves rated and stamped 41 bar on request

Globe Style
Flat Diaphragm 'E'
Flow
'E' 'E'
'E'
'E' Flange
Flow
'C' Diameter
'F' 'C'
'D' 'F' 'D' 'D' Dim
'D'
Flange Feet'A'
'A' 'A' 'B' 'B' for Safety and Standard Opposite
Convenience

See pilot system information, page 207.


For additional Engineering notes, see page 242.

24 2016.1
MODEL 206-PG / S206-PG
SINGLE CHAMBER, HYDRAULICALLY OPERATED VALVE

ANSI VALVE DATA (METRIC UNITS)


S ize D WG S t a nda rd R o lling D ia phra gm S ys t e m
mm R EF A N SI 300 mm 400 mm 450 mm 500 mm 600 x 400 600 x 500 750 mm 900 mm 12 0 0 m m
G lo be D im e ns io ns A ll f igure s s ho wn in m m unle s s o t he rwis e s t a t e d.
Lay Length A FNP T - - - - - - - - -
Centerline to B o tto m D FNP T - - - - - - - - -
Lay Length A 150F 699 914 1067 1143 1283 1562 1776 1776 2026
Centerline to B o tto m D 150F 241 298 318 354 419 435 525 603 781
Lay Length A 300F 737 956 1108 1184 1327 1607 - - -
Centerline to B o tto m D 300F 260 324 356 387 457 499 - - -
A ngle D im e ns io ns
Center Inlet to Discharge B FNP T - - - - - - - - -
Center Discharge to Inlet F FNP T - - - - - - - - -
Center Inlet to Discharge B 150F - - - - - - - - -
Center Discharge to Inlet F 150F - - - - - - - - -
Center Inlet to Discharge B 300F - - - - - - - - -
Center Discharge to Inlet F 300F - - - - - - - - -
C o m m o n D im e ns io ns ( G lo be & A ngle )
Width C 562 660 795 800 914 914 1264 1264 1638
Height (To Stem Cap) Glo be E 592 679 797 797 797 875 1162 1162 1550
Height (To Stem Cap) A ngle E - - - - - - - - -
B o dy P o rt Tapping FNP T Inches 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 1
Stem Cap P lug M NP T Inches 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 1
Co ver P o rt Tapping FNP T Inches 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 1
Valve Stro ke mm 83 95 120 120 120 141 150 150 229
Displaced B o nnet Vo lume (Litres) 6 9 26 26 26 34 56 56 163
A ppro ximate Shipping Weight (Kilo grams) 408 635 1089 1179 1270 2155 2812 3175 8165
F lo w C a pa c it ie s ( L/ s ) G lo be & A ngle
Kv - Glo be 370 520 780 810 830 1210 1850 1870 3875
Kv - A ngle - - - - - - - - -
Co ntinuo us (Glo be) 404 582 1041 1041 1041 1370 2120 2132 3500
Intermittent (Glo be) 465 661 1320 1320 1320 1640 2362 2375 4375
M o mentary (Glo be) 833 1211 1893 1896 1899 2460 4255 4267 7867
M a xim um P re s s ure R a t ings
B ar FNP T - - - - - - - -
B ar 150F 17 17 17 17 17 17 17 17 17
B ar1 300F 27.6 27.6 27.6 27.6 27.6 27.6 27.5 27.5 -
M a xim um T e m pe ra t ure
Celcius 82º 82º 82º 82º 82º 82º 82º 82º 82º
1 Valves rated and stamped 27.6 bar as standard. Valves rated and stamped 41bar o n request

Angle Style Globe Style


Rolling Diaphragm Rolling Diaphragm

'E'
Flow
'E' 'E'
'E'
'E' 'E' Flange
Flow
'C' Diameter
'F' 'C'
'F' 'D' 'D' 'D' Dim
'D' 'F'
'A' 'B' Flange Feet
'A' 'B' 'B'
'A' for Safety and Standard Opposite
Convenience

See pilot system information, page 207.


For additional Engineering notes, see page 242.

2016.1 25
MODEL 206-PG / S206-PG
SINGLE CHAMBER, HYDRAULICALLY OPERATED VALVE

ISO VALVE DATA (METRIC UNITS)


Size DWG Standard Flat Diaphragm System
mm REF ISO 80 mm 100 mm 150 mm 200 mm 250 mm
Globe Dimensions BS4504 All figures show in mm unless otherwise stated
Lay Length A BSPT - - - - -
Centerline to Bottom D BSPT - - - - -
Lay Length A PN10 / PN16 305 381 511 635 622
Centerline to Bottom D PN10 / PN16 102 117 142 171 217
Lay Length A PN25 / PN40 - 397 533 660 657
Centerline to Bottom D PN25 / PN40 - 127 161 191 236
Angle Dimensions
Center Inlet to Discharge B BSPT - - - - -
Center Discharge to Inlet F BSPT - - - - -
Center Inlet to Discharge B PN10 / PN16 - 192 259 318 -
Center Discharge to Inlet F PN10 / PN16 - 151 157 229 -
Center Inlet to Discharge B PN25 / PN40 - 200 270 330 -
Center Discharge to Inlet F PN25 / PN40 - 159 173 241 -
Common Dimensions (Globe & Angle)
Width C 208 238 318 406 508
Height (To Stem Cap) Globe E 191 244 267 359 473
Height (To Stem Cap) Angle E - 197 224 287 -
Body Port Tapping FNPT Inches 3/8 3/8 3/8 3/8 1/2
Stem Cap Plug MNPT Inches 3/8 3/8 3/8 3/8 3/8
Cover Port Tapping FNPT Inches 3/8 3/8 3/8 1/2 1/2
Valve Stroke mm 14 29 37 43 73
Displaced Bonnet Volume (Litres) 0.08 0.3 0.8 2.1 6.3
Approximate Shipping Weight (Kilograms) 34 45 113 227 295
Flow Capacities (L/s) Globe & Angle
Kv - Globe 14 36 60 120 230
Kv - Angle - 36 60 133 -
Continuous (Globe) 19 37 65 145 259
Intermittent (Globe) 24 44 75 170 295
Momentary (Globe) 36 78 136 303 530
Maximum Pressure Ratings
Bar BSPT - - - - -
Bar PN16 16 16 16 16 16
Bar PN25 25 25 25 25 25
Maximum Temperature
Celcius 82º 82º 82º 82º 82º
*
Valves rated and stamped 27.6 bar as standard. Valves rated and stamped 41 bar on request

Globe Style
Flat Diaphragm 'E'
Flow
'E' 'E'
'E'
'E' Flange
Flow
'C' Diameter
'F' 'C'
'D' 'F' 'D' 'D' Dim
'D'
Flange Feet'A'
'A' 'A' 'B' 'B' for Safety and Standard Opposite
Convenience

See pilot system information, page 207.


For additional Engineering notes, see page 242.

26 2016.1
MODEL 206-PG / S206-PG
SINGLE CHAMBER, HYDRAULICALLY OPERATED VALVE

ISO VALVE DATA (METRIC UNITS)


S ize D WG S t a nda rd R o lling D ia phra gm S ys t e m
mm R EF IS O 200mm 250mm 300 mm 400 mm 450 mm 500 mm 600 x 400 mm 600 x 500 mm 700 mm 800 mm 900 mm 10 0 0 m m
G lo be D im e ns io ns B S4504 A ll f igure s s ho wn in m m unle s s o t he rwis e s t a t e d.
Lay Length A B SP T - - - - - - - - - - - -
Centerline to B o tto m D B SP T - - - - - - - - - - - -
Lay Length A P N10 / P N16 635 660 699 914 1067 1143 1283 1562 1607 1776 1776 1890 / 1911
Centerline to B o tto m D P N10 / P N16 178 217 241 298 318 354 419 435 499 526 603 629 / 641
Lay Length A P N25 / P N40 660 695 699 956 1108 1184 1327 1607 - - - 1930 / ---
Centerline to B o tto m D P N25 / P N40 197 236 241 324 356 387 457 499 - - - 673 / ---
A ngle D im e ns io ns

Center Inlet to Discharge B B SP T - - - - - - - - - - - -


Center Discharge to Inlet F B SP T - - - - - - - - - - - -
Center Inlet to Discharge B P N10 / P N16 - - - - - - - - - - - -
Center Discharge to Inlet F P N10 / P N16 - - - - - - - - - - - -
Center Inlet to Discharge B P N25 / P N40 - - - - - - - - - - - -
Center Discharge to Inlet F P N25 / P N40 - - - - - - - - - - - -
C o m m o n D im e ns io ns G lo be
Width C 381 450 562 660 800 775 914 914 1262 1262 1262 1624
Height (To Stem Cap) Glo be E 368 480 592 679 797 797 797 875 1162 1162 1162 1550
Height (To Stem Cap) A ngle E - - - - - - - - - - - -
B o dy P o rt Tapping FNP T Inches 3/8 3/8 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 1
Stem Cap P lug M NP T Inches 3/8 3/8 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 1
Co ver P o rt Tapping FNP T Inches 1/2 1/2 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 1
Valve Stro ke mm 43 48 83 95 120 120 120 141 150 150 150 229
Displaced B o nnet Vo lume (Litres) 2 5 6 9 26 26 26 34 56 56 56 163
A ppro ximate Shipping Weight (Kilo grams) 180 324 408 635 1089 1179 1270 2155 2721 2993 3175 6350
F lo w C a pa c it ie s ( L/ s ) G lo be

Kv - Glo be 120 230 370 520 780 810 830 1210 1850 1870 1900 3875
Kv - A ngle - - - - - - - - - - - -
Co ntinuo us (Glo be) 145 259 404 582 1041 1041 1041 1370 2120 2126 2132 3500
Intermittent (Glo be) 170 295 465 661 1320 1320 1320 1640 2362 2368 2375 4375
M o mentary (Glo be) 303 530 833 1211 1893 1896 1899 2460 4255 4261 4267 7867
M a xim um P re s s ure R a t ings

B ar B SP T - - - - - - - - - - -
B ar P N16 16 16 16 16 16 16 16 16 16 16 16 16
B ar P N25 25 25 25 25 25 25 25 25 25 25 25 -
M a xim um T e m pe ra t ure
Celcius 82º 82º 82º 82º 82º 82º 82º 82º 82º 82º 82º 82º

*
Valves rated and stamped 27.6 bar as standard. Valves rated and stamped 41 bar on request

Angle Style Globe Style


Rolling Diaphragm Rolling Diaphragm

'E'
Flow
'E' 'E'
'E'
'E' 'E' Flange
Flow
'C' Diameter
'F' 'C'
'F' 'D' 'D' 'D' Dim
'D' 'F'
'A' 'B' Flange Feet
'A' 'B' 'B'
'A' for Safety and Standard Opposite
Convenience

See pilot system information, page 207.


For additional Engineering notes, see page 242.

2016.1 27
MAIN VALVES

MODEL 106-PT / 106-PTC / S106-PT / S106-PTC


DOUBLE CHAMBER HYDRAULICALLY OPERATED VALVE
KEY FEATURES
• Maintains positive control under all operating pressures
• Precise positioning
• Internal drop check option included on the PTC model
• Available in globe and angle style

PRODUCT OVERVIEW
The 106-PT and 106-PTC series control valves are hydraulically operated
by introducing or releasing water from the control chambers. PT and PTC
valves have two operating chambers that are divided from each other by the
diaphragm, and are separated from the flowing media by an adaptor plate.
106-PTC is an enhancement of the 106-PT and includes an internal drop check
feature. This mechanical check provides non-slam closure on reverse flow,
independently of the stem position or the pilot operation.
PT and PTC valves are usually combined with Singer Valve specific purpose pilots
and accessories to provide control for a wide range of functions: typically pump
control and solenoid control applications. Refer to Main Valve Options on page
62 and Pilots & Accessories on page 207 to further customize the valve to suit specific applications.and accessories
options. Customize for functions like controlling pressure, flow or level or in almost limitless combinations to suit specific
applications.

PRODUCT LINE DRAWING ALTERNATIVE MODELS


1. Optional Model X129 Limit Switch Assembly
2. Double Chambers Separated From The Flowing Media
3. ASTM A536 Ductile Iron Construction
4. Diaphragm Buna-N or EPDM
5. Optional Internal Check Feature (for PT series)
6. Buna-N or EPDM Resilient Disc
7. AISI 316 Stainless Steel Seat
8. AISI 316 Stainless Steel Stem A106-PT Angle
9. NSF 61 Fusion Bonded Epoxy Coating

SELECTION
1 The 106-PT and 106-PTC valves operate by introducing
or exhausting water from the upper and lower
2 chambers at controlled rates. Since the operating
chambers are separated from the flowing media,
3 a positive and precise differential pressure can be
established across the diaphragm. Valves are sized
4
to provide an appropriate pressure drop for each
5 application. Valves usually exhaust to atmosphere
6 Sizing is ultimately determined by the specific
7 application. Refer to the capacity charts for general
guidelines.
8

28 2016.1
MODEL 106-PT / 106-PTC / S106-PT / S106-PTC
DOUBLE CHAMBER HYDRAULICALLY OPERATED VALVE

VALVE SIZES & MATERIALS


Valve Materials
Standard Optional
Available Sizes Threaded Flanged -
Globe 2 in to 3 in (50-80 mm) 2 in to 24 in (50-600 mm) -
Angle 2 in to 3 in (50 mm-80 mm) 2 in to 12 in, 16 in (50-300 mm, 400 mm) -
Valve Components
1. Valve Body, Cover 65-45-12 Ductile Iron 316 Stainless Steel (limited sizes)
2. Seat Ring 316 Stainless Steel -
3. Disc Retainer B16 Brass / B62 Bronze / A536 Ductile Iron 316 Stainless Steel
4. Stem 316 Stainless Steel -
5. Stem Nut B16 Brass 316 Stainless Steel
6. Spring 316 Stainless Steel -
7. Guide Bushings B16 Brass or SAE 660 Bronze 316 Stainless Steel
8. Diaphragm EPDM Buna-N / Viton (limited sizes)
9. Resilient Disc EPDM Buna-N / Viton (limited sizes)
10. Coating NSF61 Approved Fusion Bonded Epoxy - Thickness 10-14 mils (250-350 microns) Consult factory
11. Fasteners 18-8 Stainless Steel 316 Stainless Steel

Double-chambered automatic control valves are


typically used for pump control. Other uses would
PILOTS & ACCESSORIES, REFER TO PG. 207
include but not be limited to low-pressure differential
applications. 106-PT and 106-PTC valves are MATERIALS OF CONSTRUCTION
particularly well suited for applications that require
valves to open fully regardless of flow or pressure Individual components can be upgraded from ductile
drop or any application where more relatively iron, bronze and brass to stainless steel, for most
constant, controlled speed is required. sizes. Consult with Singer Valve.

AVAILABLE OPTIONS ANTI-CAVITATION TRIM


Further customize the valve by adding any of the Model 106-AC allows very high pressure drops in one
available options below. valve, while retaining the standard 106 valve features.
See page 78.
Not available on PTC valves.
MAIN VALVE OPTIONS, REFER TO PAGE 62
Position Indicators (Available for install at Singer
Valve or as a field modification) ORDERING INSTRUCTIONS
• Model X107 stem mounted position indicators Refer to page 244 for the order form and ordering
instructions.
• Model X129 limit switch assembly with Single Pole
Double Throw limit switch (Double Pole Double
Throw optional)
• Model X156 analog position transmitters (4 - 20 mA)
Oxy-Nitride Stem
Internal Drop Check
Grooved Ends
Reclaimed Water

2016.1 29
MODEL 106-PT / 106-PTC / S106-PT / S106-PTC
DOUBLE CHAMBER HYDRAULICALLY OPERATED VALVE

ANSI VALVE DATA (US UNITS)


Size DWG Standard Flat Diaphragm System
Inches REF ANSI 2 in 2-1/2 in 3 in 4 in 6 in 8 in
Globe Dimensions All figures show in inches unless otherwise stated
Lay Length A FNPT 9.38 11.00 13.50 - - -
Centerline to Bottom D FNPT 2.75 3.38 3.68 - - -
Lay Length A 150F 9.38 11.00 12.00 15.00 20.00 25.38
Centerline to Bottom D 150F 3.00 3.50 3.75 4.60 5.60 7.88
Lay Length A 300F 10.00 11.63 13.25 15.63 21.00 26.38
Centerline to Bottom D 300F 3.25 3.75 4.13 5.09 6.34 7.88
Angle Dimensions
Center Inlet to Discharge B FNPT 4.69 5.50 6.63 - - -
Center Discharge to Inlet F FNPT 3.25 4.00 4.63 - - -
Center Inlet to Discharge B 150F 4.75 5.50 6.06 7.50 10.00 12.75
Center Discharge to Inlet F 150F 3.25 4.00 4.06 5.00 6.00 8.00
Center Inlet to Discharge B 300F 5.00 5.88 6.43 7.88 10.50 13.25
Center Discharge to Inlet F 300F 3.50 4.31 4.43 5.31 6.50 8.50
Common Dimensions (Globe & Angle)
Width C 6.50 8.19 9.25 10.88 16.75 21.63
Height (To Stem Cap) Globe E 6.13 8.93 9.75 10.88 13.88 17.75
Height (To Stem Cap) Angle E 6.13 8.93 9.75 10.88 13.88 17.75
Body Port Tapping FNPT 3/8 3/8 3/8 3/8 3/8 1/2
Stem Cap Plug MNPT 3/8 3/8 3/8 3/8 3/8 3/8
Cover Port Tapping FNPT 3/8 3/8 3/8 3/8 1/2 1/2
Valve Stroke 9/16 1 1-1/8 1-7/16 1-11/16 2-7/8
Displaced Bonnet Volume (Gallons) 0.02 0.1 0.1 0.2 0.6 1.7
Approximate Shipping Weight (Lbs) 40 65 100 175 400 650
Flow Capacities (USGPM) Globe & Angle
Cv - Globe 55 80 110 200 460 800
Cv - Angle 63 90 135 230 535 950
Continuous (Globe) 210 300 460 800 1800 3100
Intermittent (Globe) 260 375 575 1000 2250 3875
Momentary (Globe) 470 670 1030 1800 4000 7000
Maximum Pressure Ratings (Ductile Only)
PSI1 FNPT 400 400 400 - - -
PSI 150F 250 250 250 250 250 250
PSI1 300F 400 400 400 400 400 400
Maximum Temperature
Fahrenheit 180º 180º 180º 180º 180º 180º
Valves rated and stamped 400 psi as standard. Valves rated and stamped 600 psi on request.
1

Globe Style Angle Style


Flat Diaphragm Flat Diaphragm
'E'
'E' 'E'
'E' Flow
'E''E' 'E' 'E' 

'E'  'E' 


Flange 'C' Flow
'C' Diameter
'C'
'F' 'F' 'D' 'F'
'D'
'D' 'F' 'D' 'D' Dim
'F' 'D'
'A' 'B' 'A' Flange Feet
'B' 'A'
'A' 'B'
'B' 'A' for Safety and
'B'
Standard Opposite
Convenience

See pilot system information, page 207.


For additional Engineering notes, see page 242.

30 2016.1
MODEL 106-PT / 106-PTC / S106-PT / S106-PTC
DOUBLE CHAMBER HYDRAULICALLY OPERATED VALVE

ANSI VALVE DATA (US UNITS)


Size DWG Standard Rolling Diaphragm System
Inches REF ANSI 6 in 8 in 10 in 12 in 14 in 16 in 20 in 24 in
Globe Dimensions All figures shown in inches unless otherwise stated
Lay Length A FNPT - - - - - - - -
Centerline to Bottom D FNPT - - - - - - - -
Lay Length A 150F 29.75 34.00 31.00 41.38 52.00 61.50
Centerline to Bottom D 150F Consult with Singer Valve 8.56 9.50 10.50 11.75 14.43 17.13
Lay Length A 300F for availability 31.12 35.50 32.50 43.50 53.62 63.25
Centerline to Bottom D 300F 9.31 10.25 11.50 12.75 15.75 19.65
Angle Dimensions
Center Inlet to Discharge B FNPT - - - - - - - -
Center Discharge to Inlet F FNPT - - - - - - - -
Center Inlet to Discharge B 150F - - 11.50 13.75 - 18.00 - -
Center Discharge to Inlet F 150F - - 12.50 12.50 - 15.69 - -
Center Inlet to Discharge B 300F - - 12.19 14.50 - 18.81 - -
Center Discharge to Inlet F 300F - - 13.19 13.25 - 16.50 - -
Common Dimensions (Globe & Angle)
Width C - - 22.13 26.00 26.00 32.00 35.00 49.68
Height (To Stem Cap) Globe E - - 22.63 27.00 27.00 32.50 41.75 44.30
Height (To Stem Cap) Angle E - - 19.34 24.00 - 29.50 - -
Body Port Tapping FNPT - - 3/4 3/4 3/4 3/4 3/4 3/4
Stem Cap Plug MNPT - - 3/4 3/4 3/4 3/4 3/4 3/4
Cover Port Tapping FNPT - - 3/4 3/4 3/4 3/4 3/4 3/4
Valve Stroke - - 3-1/4 3-3/4 3-3/4 4-3/4 5-9/16 6
Displaced Bonnet Volume (Gallons) - - 1.5 2.3 2.3 6.8 9.0 14.8
Approximate Shipping Weight (Lbs) - - 900 1300 1400 2300 3670 5000
Flow Capacities (USGPM) Globe & Angle
Cv - Globe - - 1300 2100 2575 3300 5100 7600
Cv - Angle - - 1400 2450 - 4000 - -
Continuous (Globe) - - 4900 7000 8500 11000 17500 25000
Intermittent (Globe) - - 6100 8800 11500 14250 21700 31200
Momentary (Globe) - - 11000 16000 19000 25000 39000 56200
Maximum Pressure Ratings (Ductile Only)
PSI1 FNPT - - - - - - - -
PSI 150F - - 250 250 250 250 250 250
PSI1 300F - - 400 400 400 400 400 400
Maximum Temperature
Fahrenheit - - 180º 180º 180º 180º 180º 180º
1
Valves rated and stamped 400 psi as standard. Valves rated and stamped 600 psi on request.

Globe Style Angle Style


Rolling Diaphragm Rolling Diaphragm

'E' 'E'
'E'
'E' 'E''E' Flow
'E' 'E'
'E' Flange
Flow
'C' 'C' 'C'
Diameter
'F' 'F'
'F' 'D' Dim
'F' 'F' 'F' 'D''D''D'
Flange Feet
'B' 'B' 'B' 'A' 'A'
'A' 'B'
'B' 'B' for Safety and
Convenience
Standard Opposite

See pilot system information, page 207.


For additional Engineering notes, see page 242.

2016.1 31
MODEL 106-PT / 106-PTC / S106-PT / S106-PTC
DOUBLE CHAMBER HYDRAULICALLY OPERATED VALVE

ANSI VALVE DATA (METRIC UNITS)


Size DWG Standard Flat Diaphragm System
mm REF ANSI 50 mm 65 mm 80 mm 100 mm 150 mm 200 mm
Globe Dimensions All figures show in mm unless otherwise stated
Lay Length A FNPT 238 279 343 - - -
Centerline to Bottom D FNPT 70 86 93 - - -
Lay Length A 150F 238 279 305 381 508 645
Centerline to Bottom D 150F 76 89 95 117 142 200
Lay Length A 300F 254 295 337 397 533 670
Centerline to Bottom D 300F 83 95 105 129 161 200
Angle Dimensions
Center Inlet to Discharge B FNPT 119 140 168 - - -
Center Discharge to Inlet F FNPT 83 102 118 - - -
Center Inlet to Discharge B 150F 121 140 154 191 254 324
Center Discharge to Inlet F 150F 83 102 103 127 152 203
Center Inlet to Discharge B 300F 127 149 163 200 267 337
Center Discharge to Inlet F 300F 89 109 113 135 165 216
Common Dimensions (Globe & Angle)
Width C 165 208 235 276 425 549
Height (To Stem Cap) Globe E 156 227 248 276 353 451
Height (To Stem Cap) Angle E 156 227 248 276 353 451
Body Port Tapping FNPT Inches 3/8 3/8 3/8 3/8 3/8 1/2
Stem Cap Plug MNPT Inches 3/8 3/8 3/8 3/8 3/8 3/8
Cover Port Tapping FNPT Inches 3/8 3/8 3/8 3/8 1/2 1/2
Valve Stroke mm 14 25 29 37 43 73
Displaced Bonnet Volume (Litres) 0.1 0.3 0.3 0.8 2.1 6.3
Approximate Shipping Weight (Kilograms) 18 29 45 79 181 295
Flow Capacities (L/s) Globe & Angle
Kv - Globe 13 19 26 47 110 190
Kv - Angle 15 21 32 55 123 225
Continuous (Globe) 13 19 29 50 114 196
Intermittent (Globe) 16 24 36 63 142 244
Momentary (Globe) 30 42 65 114 252 442
Maximum Pressure Ratings
Bar1 FNPT 27.6 27.6 27.6 - - -
Bar 150F 17 17 17 17 17 17
Bar 300F 27.6 27.6 27.6 27.6 27.6 27.6
Maximum Temperature
Celcius 82º 82º 82º 82º 82º 82º
Valves rated and stamped 27.6 bar as standard. Valves rated and stamped 41 bar on request
1

Globe Style Angle Style


Flat Diaphragm Flat Diaphragm
'E'
'E' 'E'
'E' Flow
'E''E' 'E' 'E' 

'E'  'E' 


Flange 'C' Flow
'C' Diameter
'C'
'F' 'F' 'D' 'F'
'D'
'D' 'F' 'D' 'D' Dim
'F' 'D'
'A' 'B' 'A' Flange Feet
'B' 'A''A' 'B''B' 'A' for Safety and
'B'
Standard Opposite
Convenience

See pilot system information, page 207.


For additional Engineering notes, see page 242.

32 2016.1
MODEL 106-PT / 106-PTC / S106-PT / S106-PTC
DOUBLE CHAMBER HYDRAULICALLY OPERATED VALVE

ANSI VALVE DATA (METRIC UNITS)


Size DWG Standard Rolling Diaphragm System
mm REF ANSI 150 mm 200 mm 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm
Globe Dimensions All figures shown in mm unless otherwise stated
Lay Length A FNPT - - - - - -
Centerline to Bottom D FNPT - - - - - -
Lay Length A 150F Consult with Singer Valve 756 864 787 1051 1321 1562
Centerline to Bottom D 150F for availability 217 241 267 298 367 435
Lay Length A 300F 790 902 826 1105 1362 1607
Centerline to Bottom D 300F 243 260 292 324 400 499
Angle Dimensions
Center Inlet to Discharge B FNPT - - - - - - - -
Center Discharge to Inlet F FNPT - - - - - - - -
Center Inlet to Discharge B 150F - - 292 349 - 457 - -
Center Discharge to Inlet F 150F - - 318 318 - 399 - -
Center Inlet to Discharge B 300F - - 310 368 - 478 - -
Center Discharge to Inlet F 300F - - 335 337 - 419 - -
Common Dimensions (Globe & Angle)
Width C - - 562 660 660 813 889 1262
Height (To Stem Cap) Globe E - - 575 686 686 826 1060 1125
Height (To Stem Cap) Angle E - - 491 610 - 749 - -
Body Port Tapping FNPT Inches - - 3/4 3/4 3/4 3/4 3/4 3/4
Stem Cap Plug MNPT Inches - - 3/4 3/4 3/4 3/4 3/4 3/4
Cover Port Tapping FNPT Inches - - 3/4 3/4 3/4 3/4 3/4 3/4
Valve Stroke mm - - 83 95 95 120 141 150
Displaced Bonnet Volume (Litres) - - 6 9 9 26 34 56
Approximate Shipping Weight (Kilograms) - - 480 590 635 1043 1665 2268
Flow Capacities (L/s) Globe & Angle
Kv - Globe - - 310 500 610 780 1210 1800
Kv - Angle - - 332 581 - 948 - -
Continuous (Globe) - - 309 442 536 694 1104 1577
Intermittent (Globe) - - 385 555 726 899 1370 1968
Momentary (Globe) - - 694 1009 1199 1577 2460 3546
Maximum Pressure Ratings
Bar1 FNPT - - - - - - - -
Bar 150F - - 17 17 17 17 17 17
Bar1 300F - - 27.6 27.6 27.6 27.6 27.6 27.6
Maximum Temperature
Celcius - - 82º 82º 82º 82º 82º 82º
Valves rated and stamped 27.6 Bar as standard. Valves rated and stamped 41 Bar on request.
1

Globe Style Angle Style


Rolling Diaphragm Rolling Diaphragm

'E' 'E'
'E'
'E' 'E''E' Flow
'E' 'E'
'E' Flange
Flow
'C' 'C' 'C'
Diameter
'F' 'F'
'F' 'D' Dim
'F' 'F' 'F' 'D''D''D'
Flange Feet
'B' 'B' 'B' 'A' 'A'
'A' 'B'
'B' 'B' for Safety and
Convenience
Standard Opposite

See pilot system information, page 207.


For additional Engineering notes, see page 242.

2016.1 33
MODEL 106-PT / 106-PTC / S106-PT / S106-PTC
DOUBLE CHAMBER HYDRAULICALLY OPERATED VALVE

ISO VALVE DATA (METRIC UNITS)


Size DWG Standard Flat Diaphragm System
mm REF ISO 50 mm 65 mm 80 mm 100 mm 150 mm 200 mm
Globe Dimensions All figures shown in mm unless otherwise stated
Lay Length A BSPT 238 279 343 - - -
Centerline to Bottom D BSPT 70 86 93 - - -
Lay Length A PN10 / PN16 238 279 318 381 508 645
Centerline to Bottom D PN10 / PN16 76 89 100 117 142 200
Lay Length A PN25 / PN40 238 279 318 397 533 670
Centerline to Bottom D PN25 / PN40 76 89 100 129 161 200
Angle Dimensions
Center Inlet to Discharge B BSPT 119 140 168 - - -
Center Discharge to Inlet F BSPT 83 102 118 - - -
Center Inlet to Discharge B PN10 / PN16 121 140 163 191 254 324
Center Discharge to Inlet F PN10 / PN16 83 102 113 127 152 203
Center Inlet to Discharge B PN25 / PN40 121 140 163 200 267 337
Center Discharge to Inlet F PN25 / PN40 83 102 113 135 165 216
Common Dimensions (Globe & Angle)
Width C 165 208 235 276 425 549
Height (To Stem Cap) Globe E 156 227 248 276 353 451
Height (To Stem Cap) Angle E 156 227 248 276 353 451
Body Port Tapping FNPT Inches 3/8 3/8 3/8 3/8 3/8 1/2
Stem Cap Plug MNPT Inches 3/8 3/8 3/8 3/8 3/8 3/8
Cover Port Tapping FNPT Inches 3/8 3/8 3/8 3/8 1/2 1/2
Valve Stroke mm 14 25 29 37 43 73
Displaced Bonnet Volume (Litres) 0.1 0.3 0.3 0.8 2.1 6.3
Approximate Shipping Weight (Kilograms) 18 29 45 79 181 295
Flow Capacities (L/s) Globe & Angle
Kv - Globe 13 19 26 47 110 190
Kv - Angle 15 21 32 55 123 225
Continuous (Globe) 13 19 29 50 114 196
Intermittent (Globe) 16 24 36 63 142 244
Momentary (Globe) 30 42 65 114 252 442
Maximum Pressure Ratings
Bar BSPT 27.6 27.6 27.6 - - -
Bar PN16 16 16 16 16 16 16
Bar PN25 25 25 25 25 25 25
Maximum Temperature
Celcius 82º 82º 82º 82º 82º 82º
*
Valves rated and stamped 27.6 bar as standard. Valves rated and stamped 41 bar on request

Globe Style Angle Style


Flat Diaphragm Flat Diaphragm
'E'
'E' 'E'
'E'
'E' Flow
'E' 'E' 'E' 
'E'  'E' 
Flange 'C' Flow
'C' Diameter
'C'
'F' 'F'
'D' 'F' 'D' 'D' Dim
'F' 'D' 'D' 'F' 'D'
'A' 'B' 'A' Flange Feet
'B' 'A''A' 'B''B' 'A' for Safety and
'B'
Standard Opposite
Convenience

See pilot system information, page 207.


For additional Engineering notes, see page 242.

34 2016.1
MODEL 106-PT / 106-PTC / S106-PT / S106-PTC
DOUBLE CHAMBER HYDRAULICALLY OPERATED VALVE

ISO VALVE DATA (METRIC UNITS)


Size DWG Standard Rolling Diaphragm System
mm REF ANSI 150 mm 200 mm 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm
Globe Dimensions All figures shown in mm unless otherwise stated
Lay Length A FNPT - - - - - -
Centerline to Bottom D FNPT - - - - - -
Lay Length A 150F Consult with Singer Valve 756 864 787 1051 1321 1562
Centerline to Bottom D 150F for availability 217 241 267 298 367 435
Lay Length A 300F 790 902 826 1105 1362 1607
Centerline to Bottom D 300F 243 260 292 324 400 499
Angle Dimensions
Center Inlet to Discharge B FNPT - - - - - - - -
Center Discharge to Inlet F FNPT - - - - - - - -
Center Inlet to Discharge B 150F - - 292 349 - 457 - -
Center Discharge to Inlet F 150F - - 318 318 - 399 - -
Center Inlet to Discharge B 300F - - 310 368 - 478 - -
Center Discharge to Inlet F 300F - - 335 337 - 419 - -
Common Dimensions (Globe & Angle)
Width C - - 562 660 660 813 889 1262
Height (To Stem Cap) Globe E - - 575 686 686 826 1060 1125
Height (To Stem Cap) Angle E - - 491 610 - 749 - -
Body Port Tapping FNPT Inches - - 3/4 3/4 3/4 3/4 3/4 3/4
Stem Cap Plug MNPT Inches - - 3/4 3/4 3/4 3/4 3/4 3/4
Cover Port Tapping FNPT Inches - - 3/4 3/4 3/4 3/4 3/4 3/4
Valve Stroke mm - - 83 95 95 120 141 150
Displaced Bonnet Volume (Litres) - - 6 9 9 26 34 56
Approximate Shipping Weight (Kilograms) - - 480 590 635 1043 1665 2268
Flow Capacities (L/s) Globe & Angle
Kv - Globe - - 310 500 610 780 1210 1800
Kv - Angle - - 332 581 - 948 - -
Continuous (Globe) - - 309 442 536 694 1104 1577
Intermittent (Globe) - - 385 555 726 899 1370 1968
Momentary (Globe) - - 694 1009 1199 1577 2460 3546
Maximum Pressure Ratings
Bar1 FNPT - - - - - - - -
Bar 150F - - 17 17 17 17 17 17
Bar1 300F - - 27.6 27.6 27.6 27.6 27.6 27.6
Maximum Temperature
Celcius - - 82º 82º 82º 82º 82º 82º
Valves rated and stamped 27.6 Bar as standard. Valves rated and stamped 41 Bar on request.
1

Globe Style Angle Style


Rolling Diaphragm Rolling Diaphragm

'E' 'E'
'E'
'E' 'E''E' Flow
'E' 'E'
'E' Flange
Flow
'C' 'C' 'C'
Diameter
'F' 'F'
'F' 'D' Dim
'F' 'F' 'F' 'D''D''D'
Flange Feet
'B' 'B' 'B' 'A' 'A'
'A' 'B'
'B' 'B' for Safety and
Convenience
Standard Opposite

See pilot system information, page 207.


For additional Engineering notes, see page 242.

2016.1 35
MAIN VALVES

MODEL 206-PT / 206-PTC / S206-PT / S206-PTC


DOUBLE CHAMBER HYDRAULICALLY OPERATED VALVE
KEY FEATURES
• Positive control, even with low operating pressure
• Precise positioning
• Internal drop check included on the PTC model
• Available in globe and angle style

PRODUCT OVERVIEW
The 206-PT and 206-PTC series control valves are
hydraulically operated by introducing or releasing water
from the control chambers. PT and PTC valves have two operating chambers which are divided from each other by
the diaphragm, and are separated from the flowing media by an adaptor plate.
206-PTC is an enhancement of the 206-PT and includes an internal drop check feature. This mechanical check
provides non-slam closure on reverse flow, independently of the stem position or the pilot operation.
PT and PTC valves are usually combined with Singer Valve specific purpose pilots and accessories to provide
control for a wide range of functions: typically pump control and solenoid control applications.
Refer to Main Valve Options on page 62 and Pilots & Accessories on page 207 to further customize the valve to suit
specific applications.

PRODUCT LINE DRAWING ALTERNATIVE MODELS


1. Optional Model X129 Limit Switch Assembly
2. Double Chambers Separated From
The Flowing Media
3. ASTM A536 Ductile Iron Construction
4. Optional Internal Check Feature (PT)
5. EPDM Resilient Disc
6. AISI 316 Stainless Steel Seat
A206-PT Angle
7. AISI 316 Stainless Steel Stem
8. NSF 61 Fusion Bonded Epoxy Coating

1
SELECTION
2 The 206-PT and 206-PTC valves operate by
introducing or exhausting water from the upper
3 and lower chambers at controlled rates. Since the
4 operating chambers are separated from the flowing
media, a positive and precise differential pressure can
5 be established across the diaphragm. Valves are sized
to provide an appropriate pressure drop for each
6
application. Valves usually exhaust to atmosphere.
Sizing is ultimately determined by the specific
7
application. Refer to the capacity charts for general
8 guidelines.

36 2016.1
MODEL 206-PT / 206-PTC / S206-PT / S206-PTC
DOUBLE CHAMBER HYDRAULICALLY OPERATED VALVE

VALVE SIZES & MATERIALS:


Valve Materials
Standard Optional
Available Sizes Flanged -
Globe 3 in to 36 in (80-900 mm) -
Angle 4 in to 8 in (100 mm-200 mm) -
Valve Components
1. Valve Body, Cover 65-45-12 Ductile Iron 316 Stainless Steel (limited sizes)
2. Seat Ring 316 Stainless Steel -
3. Disc Retainer B16 Brass / B62 Bronze / A536 Ductile Iron 316 Stainless Steel
4. Stem 316 Stainless Steel -
5. Stem Nut B16 Brass 316 Stainless Steel
6. Spring 316 Stainless Steel -
7. Guide Bushings B16 Brass or SAE 660 Bronze 316 Stainless Steel
8. Diaphragm EPDM Buna-N / Viton (limited sizes)
9. Resilient Disc EPDM Buna-N / Viton (limited sizes)
10. Coating NSF61 Approved Fusion Bonded Epoxy - Thickness 10-14 mils (250-350 microns) Consult factory
11. Fasteners 18-8 Stainless Steel 316 Stainless Steel

Double-chambered automatic control valves are


typically used for pump control. Other uses would
PILOTS & ACCESSORIES, REFER TO PG. 207
include but not be limited to low-pressure differential
applications. 206-PT and 206-PTC valves are MATERIALS OF CONSTRUCTION
particularly well suited for applications that require
valves to open fully regardless of flow or pressure Individual components can be upgraded from ductile
drop or any application where more relatively iron, bronze and brass to stainless steel, for most
constant, controlled speed is required. sizes. Consult with Singer Valve.

AVAILABLE OPTIONS ORDERING INSTRUCTIONS


Further customize the valve by adding any of the Refer to page 244 for the order form and ordering
available options below. instructions.

MAIN VALVE OPTIONS, REFER TO PAGE 62


Position Indicators (Available for install at Singer
Valve or as a field modification)
• Model X107 stem mounted position indicators
• Model X129 limit switch assembly with Single Pole
Double Throw limit switch (Double Pole Double
Throw optional)
• Model X156 analog position transmitters (4 - 20 mA)
Oxy-Nitride Stem
Grooved Ends
Reclaimed Water

2016.1 37
MODEL 206-PT / 206-PTC / S206-PT / S206-PTC
DOUBLE CHAMBER HYDRAULICALLY OPERATED VALVE

VALVE DATA (US UNITS)


Size DWG Standard Flat Diaphragm System
Inches REF ANSI 3 in 4 in 6 in 8 in 10 in
Globe Dimensions All figures shown in inches unless otherwise stated
Lay Length A FNPT - - - - -
Centerline to Bottom D FNPT - - - - -
Lay Length A 150F 12.00 15.00 20.13 25.00 24.50
Centerline to Bottom D 150F 4.00 4.60 5.62 6.75 8.56
Lay Length A 300F - 15.63 21.00 26.00 25.88
Centerline to Bottom D 300F - 5.00 6.34 7.50 9.31
Angle Dimensions
Center Inlet to Discharge B FNPT - - - - -
Center Discharge to Inlet F FNPT - - - - -
Center Inlet to Discharge B 150F - 7.56 10.19 12.50 -
Center Discharge to Inlet F 150F - 5.94 6.19 9.00 -
Center Inlet to Discharge B 300F - 7.88 10.63 13.00 -
Center Discharge to Inlet F 300F - 6.25 6.81 9.50 -
Common Dimensions (Globe & Angle)
Width C 8.19 10.00 12.50 16.00 20.00
Height (To Stem Cap) Globe E 8.93 11.28 12.25 16.25 21.38
Height (To Stem Cap) Angle E - 9.50 10.50 13.43 -
Body Port Tapping FNPT 3/8 3/8 3/8 1/2 1/2
Stem Cap Plug MNPT 3/8 3/8 3/8 3/8 3/8
Cover Port Tapping FNPT 3/8 3/8 3/8 1/2 1/2
Valve Stroke 15/16 1-1/8 1-7/16 1-11/16 2-7/8
Displaced Bonnet Volume (Gallons) 0.02 0.1 0.2 0.6 1.7
Approximate Shipping Weight (Lbs) 75 100 250 500 650
Flow Capacities (USGPM) Globe & Angle
Cv - Globe 60 150 250 505 985
Cv - Angle - 150 250 560 -
Continuous (Globe) 300 580 1025 2300 4100
Intermittent (Globe) 373 690 1190 2700 4670
Momentary (Globe) 564 1236 2160 4800 8400
Maximum Pressure Ratings (Ductile Only)
PSI FNPT - - - - -
PSI 150F 250 250 250 250 250
PSI1 300F 400 400 400 400 400
Maximum Temperature
Fahrenheit 180º 180º 180º 180º 180º
Valves rated and stamped 400 psi as standard. Valves rated and stamped 600 psi on request.
1

Globe Style Angle Style


Flat Diaphragm Flat Diaphragm

'E' 'E' Flow


'E' 'E'
'E' 
'E'  Flow

'C'
Flange
Diameter 'C'
'F'
'F' 'D'
'D' 'F' 'D' 'D' Dim

Flange Feet
'B' 'A'
'A' 'B'
'B' 'A' for Safety and
Convenience
Standard Opposite

See pilot system information, page 207.


For additional Engineering notes, see page 242.

38 2016.1
MODEL 206-PT / 206-PTC / S206-PT / S206-PTC
DOUBLE CHAMBER HYDRAULICALLY OPERATED VALVE

VALVE DATA (US UNITS)


Size DWG Standard Rolling Diaphragm System
Inches REF ANSI 12 in 16 in 18 in 20 in 24 in x 16 in 24 in x 20 in 30 in 36 in
Globe Dimensions All figures shown in inches unless otherwise stated.
Lay Length A FNPT - - - - - - - -
Centerline to Bottom D FNPT - - - - - - - -
Lay Length A 150F 27.50 36.00 42.00 45.00 50.50 61.50 69.93 69.93
Centerline to Bottom D 150F 9.50 11.75 12.50 13.93 16.50 17.13 20.69 23.75
Lay Length A 300F 29.00 37.63 43.63 46.63 52.25 63.25 - -
Centerline to Bottom D 300F 10.50 12.75 14.00 15.25 18.00 19.65 - -
Angle Dimensions
Center Inlet to Discharge B FNPT - - - - - - - -
Center Discharge to Inlet F FNPT - - - - - - - -
Center Inlet to Discharge B 150F - - - - - - - -
Center Discharge to Inlet F 150F - - - - - - - -
Center Inlet to Discharge B 300F - - - - - - - -
Center Discharge to Inlet F 300F - - - - - - - -
Common Dimensions (Globe & Angle)
Width C 22.13 26.00 31.31 31.50 36.00 36.00 49.75 49.75
Height (To Stem Cap) Globe E 22.63 27.00 32.38 32.38 32.38 41.75 45.75 45.75
Height (To Stem Cap) Angle E - - - - - - - -
Body Port Tapping FNPT 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Stem Cap Plug MNPT 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Cover Port Tapping FNPT 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Valve Stroke 3-1/4 3-3/4 4-3/4 4-3/4 4-3/4 5-9/16 6 6
Displaced Bonnet Volume (Gallons) 1.5 2.3 6.8 6.8 14.8 9.0 14.8 14.8
Approximate Shipping Weight (Lbs) 900 1400 2400 2600 2800 3240 6200 7000
Flow Capacities (USGPM) Globe & Angle
Cv - Globe 1550 2200 3300 3400 3500 5100 7800 8000
Cv - Angle - - - - - - - -
Continuous (Globe) 6400 9230 16500 16500 16500 21700 33650 33800
Intermittent (Globe) 7320 10470 20915 20915 20915 26000 37490 37640
Momentary (Globe) 13200 19200 30000 30050 30100 39000 67490 67640
Maximum Pressure Ratings (Ductile Only)
PSI FNPT - - - - - - - -
PSI 150F 250 250 250 250 250 250 250 250
PSI1 300F 400 400 400 400 400 400 400 400
Maximum Temperature
Fahrenheit 180º 180º 180º 180º 180º 180º 180º 180º
1
Valves rated and stamped 400 psi as standard. Valves rated and stamped 600 psi on request.

Globe Style
Rolling Diaphragm

'E'
'E' 'E' Flow

'E' 'E' 'E' 


Flow
 Flange
'C''C'Diameter
'F' 'D' Dim
'F' 'F' 'D' 'D'
'D'
Flange Feet
'B' 'A' 'B' for Safety and Standard Opposite
'B' 'A' Convenience

See pilot system information, page 207.


For additional Engineering notes, see page 242.

2016.1 39
MODEL 206-PT / 206-PTC / S206-PT / S206-PTC
DOUBLE CHAMBER HYDRAULICALLY OPERATED VALVE

ANSI VALVE DATA (METRIC UNITS)


Size DWG Standard Flat Diaphragm System
mm REF ANSI 80 mm 100 mm 150 mm 200 mm 250 mm
Globe Dimensions All figures shown in mm unless otherwise stated
Lay Length A FNPT - - - - -
Centerline to Bottom D FNPT - - - - -
Lay Length A 150F 305 381 511 635 622
Centerline to Bottom D 150F 102 117 143 171 217
Lay Length A 300F - 397 533 660 657
Centerline to Bottom D 300F - 127 161 191 236
Angle Dimensions
Center Inlet to Discharge B FNPT - - - - -
Center Discharge to Inlet F FNPT - - - - -
Center Inlet to Discharge B 150F - 192 259 318 -
Center Discharge to Inlet F 150F - 151 157 229 -
Center Inlet to Discharge B 300F - 200 270 330 -
Center Discharge to Inlet F 300F - 159 173 241 -
Common Dimensions (Globe & Angle)
Width C 208 254 318 406 508
Height (To Stem Cap) Globe E 227 287 311 413 543
Height (To Stem Cap) Angle E - 241 267 341 -
Body Port Tapping FNPT Inches 3/8 3/8 3/8 3/8 1/2
Stem Cap Plug MNPT Inches 3/8 3/8 3/8 3/8 3/8
Cover Port Tapping FNPT Inches 3/8 3/8 3/8 1/2 1/2
Valve Stroke mm 14 29 37 43 73
Displaced Bonnet Volume (Litres) 0.1 0.3 0.8 2.1 6.3
Approximate Shipping Weight (Kilograms) 34 45 113 227 295
Flow Capacities (L/s) Globe & Angle
Kv - Globe 14 36 60 120 230
Kv - Angle - 36 59 138 -
Continuous (Globe) 19 37 65 145 259
Intermittent (Globe) 24 44 75 170 295
Momentary (Globe) 36 78 136 303 530
Maximum Pressure Ratings (Ductile Only)
Bar FNPT - - - - -
Bar 150F 17 17 17 17 17
Bar1 300F 27.6 27.6 27.6 27.6 27.6
Maximum Temperature
Celcius 82º 82º 82º 82º 82º
1
Valves rated and stamped 27.6 bar as standard. Valves rated and stamped 41 bar on request

Globe Style Angle Style


Flat Diaphragm Flat Diaphragm

'E' 'E' Flow


'E' 'E'
'E' 
'E'  Flow

'C'
Flange
Diameter 'C'
'F'
'F' 'D'
'D' 'F' 'D' 'D' Dim

Flange Feet
'B' 'A'
'A' 'B'
'B' 'A' for Safety and
Convenience
Standard Opposite

See pilot system information, page 207.


For additional Engineering notes, see page 242.

40 2016.1
MODEL 206-PT / 206-PTC / S206-PT / S206-PTC
DOUBLE CHAMBER HYDRAULICALLY OPERATED VALVE

ANSI VALVE DATA (METRIC UNITS)


Size DWG Standard Rolling Diaphragm System
mm REF ANSI 300 mm 400 mm 450 mm 500 mm 600 x 400 mm 600 x 500 mm 900 mm
Globe Dimensions All figures shown in mm unless otherwise stated.
Lay Length A FNPT - - - - - -
Centerline to Bottom D FNPT - - - - - -
Lay Length A 150F 699 914 1067 1143 1283 1562 1776
Centerline to Bottom D 150F 241 298 318 354 419 435 588
Lay Length A 300F 737 956 1108 1184 1327 1607 -
Centerline to Bottom D 300F 267 324 356 387 457 499 -
Angle Dimensions
Center Inlet to Discharge B FNPT - - - - - - -
Center Discharge to Inlet F FNPT - - - - - - -
Center Inlet to Discharge B 150F - - - - - - -
Center Discharge to Inlet F 150F - - - - - - -
Center Inlet to Discharge B 300F - - - - - - -
Center Discharge to Inlet F 300F - - - - - - -
Common Dimensions Globe
Width C 562 660 795 800 914 914 1262
Height (To Stem Cap) Globe E 575 686 822 822 822 1060 1162
Height (To Stem Cap) Angle E - - - - - - -
Body Port Tapping FNPT Inches 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Stem Cap Plug MNPT Inches 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Cover Port Tapping FNPT Inches 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Valve Stroke mm 83 95 120 120 120 141 150
Displaced Bonnet Volume (Litres) 6 9 26 26 26 34 56
Approximate Shipping Weight (Kilograms) 408 635 1089 1179 1270 1470 3175
Flow Capacities (L/s) Globe
K v - Globe 370 520 780 810 830 1210 1870
Kv - Angle - - - - - - -
Continuous (Globe) 404 582 1041 1041 1041 1370 2132
Intermittent (Globe) 465 661 1320 1320 1320 1640 2375
Momentary (Globe) 833 1211 1893 1896 1899 2460 4267
Maximum Pressure Ratings (Ductile Only)
Bar FNPT - - - - - -
Bar 150F 17 17 17 17 17 17 17
Bar* 300F 27.6 27.6 27.6 27.6 27.6 27.6 27.6
Maximum Temperature
Celcius 82º 82º 82º 82º 82º 82º 82º
1
Valves rated and stamped 27.6 bar as standard. Valves rated and stamped 41 bar on request

Globe Style
Rolling Diaphragm

'E'
'E' 'E' Flow

'E' 'E' 'E' 


Flow
 Flange
'C''C'Diameter
'F' 'D' Dim
'F' 'F' 'D' 'D'
'D'
Flange Feet
'B' 'A' 'B' for Safety and Standard Opposite
'B' 'A' Convenience

See pilot system information, page 207.


For additional Engineering notes, see page 242.

2016.1 41
MODEL 206-PT / 206-PTC / S206-PT / S206-PTC
DOUBLE CHAMBER HYDRAULICALLY OPERATED VALVE

ISO VALVE DATA (METRIC UNITS)


Size DWG Standard Flat Diaphragm System
mm REF ANSI 80 mm 100 mm 150 mm 200 mm 250 mm
Globe Dimensions All figures shown in mm unless otherwise stated
Lay Length A FNPT - - - - -
Centerline to Bottom D FNPT - - - - -
Lay Length A 150F 305 381 511 635 622
Centerline to Bottom D 150F 102 117 143 171 217
Lay Length A 300F - 397 533 660 657
Centerline to Bottom D 300F - 127 161 191 236
Angle Dimensions
Center Inlet to Discharge B FNPT - - - - -
Center Discharge to Inlet F FNPT - - - - -
Center Inlet to Discharge B 150F - 192 259 318 -
Center Discharge to Inlet F 150F - 151 157 229 -
Center Inlet to Discharge B 300F - 200 270 330 -
Center Discharge to Inlet F 300F - 159 173 241 -
Common Dimensions (Globe & Angle)
Width C 208 254 318 406 508
Height (To Stem Cap) Globe E 227 287 311 413 543
Height (To Stem Cap) Angle E - 241 267 341 -
Body Port Tapping FNPT Inches 3/8 3/8 3/8 3/8 1/2
Stem Cap Plug MNPT Inches 3/8 3/8 3/8 3/8 3/8
Cover Port Tapping FNPT Inches 3/8 3/8 3/8 1/2 1/2
Valve Stroke mm 14 29 37 43 73
Displaced Bonnet Volume (Litres) 0.1 0.3 0.8 2.1 6.3
Approximate Shipping Weight (Kilograms) 34 45 113 227 295
Flow Capacities (L/s) Globe & Angle
Kv - Globe 14 36 60 120 230
Kv - Angle - 36 59 138 -
Continuous (Globe) 19 37 65 145 259
Intermittent (Globe) 24 44 75 170 295
Momentary (Globe) 36 78 136 303 530
Maximum Pressure Ratings (Ductile Only)
Bar FNPT - - - - -
Bar PN16 17 17 17 17 17
Bar1 PN25 27.6 27.6 27.6 27.6 27.6
Maximum Temperature
Celcius 82º 82º 82º 82º 82º
Valves rated and stamped 27.6 bar as standard. Valves rated and stamped 41 bar on request
1

Globe Style Angle Style


Flat Diaphragm Flat Diaphragm

'E' 'E' Flow


'E' 'E'
'E' 
'E'  Flow

'C'
Flange
Diameter 'C'
'F'
'F' 'D'
'D' 'F' 'D' 'D' Dim

Flange Feet
'B' 'A'
'A' 'B'
'B' 'A' for Safety and
Convenience
Standard Opposite

See pilot system information, page 207.


For additional Engineering notes, see page 242.

42 2016.1
MODEL 206-PT / 206-PTC / S206-PT / S206-PTC
DOUBLE CHAMBER HYDRAULICALLY OPERATED VALVE

ISO VALVE DATA (METRIC UNITS)


Size DWG Standard Rolling Diaphragm System
mm REF ANSI 300 mm 400 mm 450 mm 500 mm 600 x 400 mm 600 x 500 mm 900 mm
Globe Dimensions All figures shown in mm unless otherwise stated.
Lay Length A FNPT - - - - - -
Centerline to Bottom D FNPT - - - - - -
Lay Length A 150F 699 914 1067 1143 1283 1562 1776
Centerline to Bottom D 150F 241 298 318 354 419 435 588
Lay Length A 300F 737 956 1108 1184 1327 1607 -
Centerline to Bottom D 300F 267 324 356 387 457 499 -
Angle Dimensions
Center Inlet to Discharge B FNPT - - - - - - -
Center Discharge to Inlet F FNPT - - - - - - -
Center Inlet to Discharge B 150F - - - - - - -
Center Discharge to Inlet F 150F - - - - - - -
Center Inlet to Discharge B 300F - - - - - - -
Center Discharge to Inlet F 300F - - - - - - -
Common Dimensions Globe
Width C 562 660 795 800 914 914 1262
Height (To Stem Cap) Globe E 575 686 822 822 822 1060 1162
Height (To Stem Cap) Angle E - - - - - - -
Body Port Tapping FNPT Inches 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Stem Cap Plug MNPT Inches 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Cover Port Tapping FNPT Inches 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Valve Stroke mm 83 95 120 120 120 141 150
Displaced Bonnet Volume (Litres) 6 9 26 26 26 34 56
Approximate Shipping Weight (Kilograms) 408 635 1089 1179 1270 1470 3175
Flow Capacities (L/s) Globe
Kv - Globe 370 520 780 810 830 1210 1870
Kv - Angle - - - - - - -
Continuous (Globe) 404 582 1041 1041 1041 1370 2132
Intermittent (Globe) 465 661 1320 1320 1320 1640 2375
Momentary (Globe) 833 1211 1893 1896 1899 2460 4267
Maximum Pressure Ratings (Ductile Only)
Bar FNPT - - - - - -
Bar PN16 17 17 17 17 17 17 17
Bar* PN25 27.6 27.6 27.6 27.6 27.6 27.6 27.6
Maximum Temperature
Celcius 82º 82º 82º 82º 82º 82º 82º
1
Valves rated and stamped 27.6 bar as standard. Valves rated and stamped 41 bar on request

Globe Style
Rolling Diaphragm

'E'
'E' 'E' Flow

'E' 'E' 'E' 


Flow
 Flange
'C''C'Diameter
'F' 'D' Dim
'F' 'F' 'D' 'D'
'D'
Flange Feet
'B' 'A' 'B' for Safety and Standard Opposite
'B' 'A' Convenience

See pilot system information, page 207.


For additional Engineering notes, see page 242.

2016.1 43
MAIN VALVES

MODEL 106-PGM / S106-PGM


INTEGRAL BACK-UP, DUAL DIAPHRAGM,
HYDRAULICALLY OPERATED VALVE

KEY FEATURES
• Ideal for applications requiring redundant and
back-up security
• Virtually uninterrupted control under a variety of
system failures
• Remote annunciation option available
• Available in globe and angle style

The PGM series valves may be combined with


PRODUCT OVERVIEW additional Singer Valve specific accessories to add
The 106-PGM and S106-PGM series valves are further customization such as:
designed for particularly sensitive applications or
• Back-up pilot system
situations where valves are difficult to access and
maintain. • Annunciation with an Single Pole Double Throw
Limit Switch
The PGM series valves provide integral back-up
control and the ability to signal should the desired Refer to Main Valve Options on page 62 and Pilots &
function move off limits. It can also provide an Accessories on page 207 to customize the valve to suit
independent and very positive override. specific applications.
It is a variation of the standard single chamber 106-
PG valve with modifications that add the following
features:
• Back-up diaphragm
ALTERNATIVE MODELS
• Completely self-contained
• Modulating or emergency close back-up
• Back-up components kept out of the main stream
until required
• Extremely positive shut-off
• Emergency close for security breach or earthquake
With SRD technology the valve becomes incredibly
steady throughout a complete range of flows and
eradicates the need of additional low flow bypass 106-PGM Angle
valves.

44 2016.1
MODEL 106-PGM / S106-PGM
INTEGRAL BACK-UP, DUAL DIAPHRAGM, HYDRAULICALLY OPERATED VALVE

PRODUCT LINE DRAWING 1. Primary Stem / Position Indicator


1 2. Secondary Stem
3. ASTM A536 Ductile Iron Construction
2
4. Buna-N or EPDM Secondary Diaphragm
3 5. Back-up Secondary Assembly
4
5
6. Open to Atmosphere
6
7 7. Sliding guide
8. Buna-N / EPDM Primary Diaphragm
8
9. Buna-N or EPDM Resilient Disc
9
10. AISI 316 Stainless Steel Seat
10
11. AISI 316 Stainless Steel Stem
11 12. NSF 61 Fusion Bonded Epoxy Coating
12

VALVE SIZES & MATERIALS


Valve Materials
Standard Optional
Available Sizes Threaded Flanged -
Globe 3 in (80 mm) 3 in to 24 in (80-600 mm) -
Angle 3 in (80 mm) 3 in to 12 in, 16 in (80-300 mm, 400 mm) -
Valve Components
1. Valve Body, Cover 65-45-12 Ductile Iron 316 Stainless Steel (limited sizes)
2. Seat Ring 316 Stainless Steel -
3. Disc Retainer B16 Brass / B62 Bronze / A536 Ductile Iron 316 Stainless Steel
4. Stem 316 Stainless Steel -
5. Stem Nut B16 Brass 316 Stainless Steel
6. Spring 316 Stainless Steel -
7. Guide Bushings B16 Brass or SAE 660 Bronze 316 Stainless Steel
8. Diaphragm EPDM Buna-N / Viton (limited sizes)
9. Resilient Disc EPDM Buna-N / Viton (limited sizes)
10. Coating NSF61 Approved Fusion Bonded Epoxy - Thickness 10-14 mils (250-350 microns) Consult factory
11. Fasteners 18-8 Stainless Steel 316 Stainless Steel

SELECTION
The Singer Model 106-PGM incorporates a second The primary pilot function can be duplicated in the
actuator. If the primary system and / or the main secondary pilot system to provide continuing back-up
valve fails then the back-up pilot system takes over. operations or the secondary system can be used for
Under normal operating conditions, there is no override functions. Consult with Singer Valve with
external discharge from the PGM. In modulating your specific application requirements.
applications, when the back-up pilot system operates, Sizing of PGM valves are based on the same criteria as
there is a small (less than 1 USGPM / 0.06 L/s) standard PG models.
continuous discharge that should be taken to drain.

2016.1 45
MODEL 106-PGM / S106-PGM
INTEGRAL BACK-UP, DUAL DIAPHRAGM, HYDRAULICALLY OPERATED VALVE

AVAILABLE OPTIONS PILOTS & ACCESSORIES, REFER TO PG. 207


Further customize the valve by adding any of the
available options below. MATERIALS OF CONSTRUCTION
Individual components can be upgraded from ductile
MAIN VALVE OPTIONS, REFER TO PAGE 62 iron, bronze and brass to stainless steel, for most
Position Indicators (Available for install at Singer sizes. Consult with Singer Valve.
Valve or as a field modification)
• Model X129 limit switch assembly with Single Pole ANTI-CAVITATION TRIM
Double Throw limit switch (Double Pole Double Model 106-AC allows very high pressure drops in one
Throw optional) valve, while retaining the standard 106 valve features.
• Model X156 analog position transmitters (4-20 mA) See page 78.
Oxy-Nitride Stem
Internal Drop Check ORDERING INSTRUCTIONS
Grooved Ends Refer to page 244 for the order form and ordering
instructions.
Reclaimed Water

46 2016.1
MODEL 106-PGM / S106-PGM
INTEGRAL BACK-UP, DUAL DIAPHRAGM, HYDRAULICALLY OPERATED VALVE

ANSI VALVE DATA (US UNITS)


Size DWG Standard Flat Diaphragm System
Inches REF ANSI 3 in 4 in 6 in 8 in
Globe Dimensions All figures shown in inches unless otherwise stated
Lay Length A FNPT 13.50 - - -
Centerline to Bottom D FNPT 3.68 - - -
Lay Length A 150F 12.00 15.00 20.00 25.38
Centerline to Bottom D 150F 3.75 4.60 5.60 7.88
Lay Length A 300F 13.25 15.63 21.00 26.38
Centerline to Bottom D 300F 4.13 5.09 6.34 7.88
Angle Dimensions
Center Inlet to Discharge B FNPT 6.63 - - -
Center Discharge to Inlet F FNPT 4.63 - - -
Center Inlet to Discharge B 150F 6.06 7.50 10.00 12.75
Center Discharge to Inlet F 150F 4.06 5.00 6.00 8.00
Center Inlet to Discharge B 300F 6.43 7.88 10.50 13.25
Center Discharge to Inlet F 300F 4.43 5.31 6.50 8.50
Common Dimensions (Globe & Angle)
Width C 9.25 10.88 16.75 21.63
Height (To Indicator) Globe E 17.63 19.43 21.00 26.88
Height (To Indicator) Angle E 17.63 19.13 20.63 27.38
Body Port Tapping FNPT 3/8 3/8 3/8 1/2
Stem Cap Plug MNPT 3/8 3/8 3/8 3/8
Cover Port Tapping FNPT 3/8 3/8 1/2 1/2
Valve Stroke 1-1/8 1-7/16 1-11/16 2-7/8
Displaced Bonnet Volume (Gallons) 0.1 0.2 0.6 1.7
Approximate Shipping Weight (Lbs) 150 210 450 705
Flow Capacities (USGPM) Globe & Angle
Cv - Globe 110 200 460 800
Cv - Angle 135 230 535 950
Continuous (Globe) 460 800 1800 3100
Intermittent (Globe) 575 1000 2250 3875
Momentary (Globe) 1030 1800 4000 7000
Maximum Pressure Ratings (Ductile Only)
PSI1 FNPT 400 - - -
PSI 150F 250 250 250 250
PSI1 300F 400 400 400 400
Maximum Temperature
Fahrenheit 180º 180º 180º 180º
Valves rated and stamped 400 psi as standard. Valves rated and stamped 600 psi on request.
1

Globe Style Angle Style


Flat Diaphragm Flat Diaphragm 'E'
'E'

'E'
E
E Flow
'E' SINGER SINGER

'E' Flange
Flow
SINGER
SINGER
'C' Diameter 'F'
'C'
'F'
F 'D' 'D' Dim
'F' D 'D'

Flange Feet
'B' A'A'
'B'B 'A'
for Safety and 'B' Standard Opposite
Convenience

See pilot system information, page 207.


For additional Engineering notes, see page 242.

2016.1 47
MODEL 106-PGM / S106-PGM
INTEGRAL BACK-UP, DUAL DIAPHRAGM, HYDRAULICALLY OPERATED VALVE

ANSI VALVE DATA (US UNITS)


Size DWG Standard Rolling Diaphragm System
Inches REF ANSI 6 in 8 in 10 in 12 in 14 in 16 in 20 in 24 in
Globe Dimensions All figures shown in inches unless otherwise stated.
Lay Length A FNPT - - - - - -
Centerline to Bottom D FNPT - - - - - -
Lay Length A 150F Consult with Singer 29.75 34.00 31.00 41.38 52.00 61.50
Centerline to Bottom D 150F Valve for availability 8.56 9.50 10.50 11.75 14.43 17.13
Lay Length A 300F 31.12 35.50 32.50 43.50 53.62 63.25
Centerline to Bottom D 300F 9.31 10.25 11.50 12.75 15.75 19.65
Angle Dimensions
Center Inlet to Discharge B FNPT - - - - - - - -
Center Discharge to Inlet F FNPT - - - - - - - -
Center Inlet to Discharge B 150F - - 11.50 13.75 - 18.00 - -
Center Discharge to Inlet F 150F - - 12.50 12.50 - 15.69 - -
Center Inlet to Discharge B 300F - - 12.19 14.50 - 18.81 - -
Center Discharge to Inlet F 300F - 13.19 13.25 - 16.50 - -
Common Dimensions (Globe and Angle)
Width C - - 22.13 26.00 26.00 32.00 35.00 49.68
Height (To Indicator) Globe E - - 39.38 44.50 44.63 52.13 59.50 61.50
Height (To Indicator) Angle E - - 36.00 41.50 - 49.13 - -
Body Port Tapping FNPT - - 1/2 3/4 3/4 3/4 3/4 3/4
Stem Cap Plug MNPT - - 3/4 3/4 3/4 3/4 3/4 3/4
Cover Port Tapping FNPT - - 3/4 3/4 3/4 3/4 3/4 3/4
Valve Stroke - - 3-1/4 3-3/4 3-3/4 4-3/4 5-9/16 6
Displaced Bonnet Volume (Gallons) - - 1.5 2.3 2.3 6.8 9.0 14.8
Approximate Shipping Weight (Lbs) - - 1000 1365 1500 2600 4315 7500
Flow Capacities (USGPM) Globe & Angle
Cv - Globe - - 1300 2100 2575 3300 5100 7600
Cv - Angle - - 1400 2450 - 4000 - -
Continuous (Globe) - - 4900 7000 8500 11000 17500 25000
Intermittent (Globe) - - 6100 8800 11500 14250 21700 31200
Momentary (Globe) - - 11000 16000 19000 25000 39000 56200
Maximum Pressure Ratings (Ductile Only)
PSI1 FNPT - - - - - - - -
PSI 150F - - 250 250 250 250 250 250
PSI1 300F - - 400 400 400 400 400 400
Maximum Temperature
Fahrenheit - - 180º 180º 180º 180º 180º 180º
1
Valves rated and stamped 400 psi as standard. Valves rated and stamped 600 psi on request.

Globe Style Angle Style


Rolling Diaphragm Rolling Diaphragm

'E'
'E' Flow
'E'
'E'

'E' Flange
Flow
E
'C' Diameter
'F' 'D' Dim
'F' SINGER
'D' SINGER

'F' Flange Feet


'B' 'A' 'B' 'C'
for Safety and Standard Opposite
F 'D' Convenience

'A' 'B'

See pilot system information, page 207.


For additional Engineering notes, see page 242.

48 2016.1
MODEL 106-PGM / S106-PGM
INTEGRAL BACK-UP, DUAL DIAPHRAGM, HYDRAULICALLY OPERATED VALVE

ANSI VALVE DATA (METRIC UNITS)


Size DWG Standard Flat Diaphragm System
mm REF ANSI 80 mm 100 mm 150 mm 200 mm
Globe Dimensions All figures shown in mm unless otherwise stated
Lay Length A FNPT 343 - - -
Centerline to Bottom D FNPT 93 - - -
Lay Length A 150F 305 381 508 645
Centerline to Bottom D 150F 95 117 142 200
Lay Length A 300F 337 397 533 670
Centerline to Bottom D 300F 105 129 161 200
Angle Dimensions
Center Inlet to Discharge B FNPT 168 - - -
Center Discharge to Inlet F FNPT 118 - - -
Center Inlet to Discharge B 150F 154 191 254 324
Center Discharge to Inlet F 150F 103 127 152 203
Center Inlet to Discharge B 300F 163 200 267 337
Center Discharge to Inlet F 300F 113 135 165 216
Common Dimensions (Globe & Angle)
Width C 235 276 425 549
Height (To Indicator) Globe E 448 494 533 683
Height (To Indicator) Angle E 448 486 524 695
Body Port Tapping FNPT Inches 3/8 3/8 3/8 1/2
Stem Cap Plug MNPT Inches 3/8 3/8 3/8 3/8
Cover Port Tapping FNPT Inches 3/8 3/8 1/2 1/2
Valve Stroke mm 29 37 43 73
Displaced Bonnet Volume (Litres) 0.3 0.8 2.1 6.3
Approximate Shipping Weight (Kilograms) 68 95 204 320
Flow Capacities (L/s) (Globe &Angle)
Kv - Globe 26 47 110 190
Kv - Angle 32 55 123 225
Continuous (Globe) 29 50 114 196
Intermittent (Globe) 36 63 142 244
Momentary (Globe) 65 114 252 442
Maximum Pressure Ratings (Ductile Only)
Bar1 FNPT 27.6 - - -
Bar 150F 17 17 17 17
Bar1 300F 27.6 27.6 27.6 27.6
Maximum Temperature
Celcius 82º 82º 82º 82º
1
Valves rated and stamped 27.6 bar as standard. Valves rated and stamped 41 bar on request

Globe Style Angle Style


Flat Diaphragm Flat Diaphragm 'E'
'E'

'E'
E
E Flow
'E' SINGER SINGER

'E' Flange
Flow
SINGER
SINGER
'C' Diameter 'F'
'C'
'F'
F 'D' 'D' Dim
'F' D 'D'

Flange Feet
'B' A'A'
'B'B 'A'
for Safety and 'B' Standard Opposite
Convenience

See pilot system information, page 207.


For additional Engineering notes, see page 242.

2016.1 49
MODEL 106-PGM / S106-PGM
INTEGRAL BACK-UP, DUAL DIAPHRAGM, HYDRAULICALLY OPERATED VALVE

ANSI VALVE DATA (METRIC UNITS)


Size DWG Standard Rolling Diaphragm System
mm REF ANSI 150 mm 200 mm 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm
Globe Dimensions All figures shown in mm unless otherwise stated
Lay Length A FNPT - - - - - -
Centerline to Bottom D FNPT - - - - - -
Lay Length A 150F Consult with Singer Valve 756 864 787 1051 1321 1562
Centerline to Bottom D 150F for availability 217 241 267 298 367 435
Lay Length A 300F 790 902 826 1105 1362 1607
Centerline to Bottom D 300F 236 260 292 324 400 499
Angle Dimensions
Center Inlet to Discharge B FNPT - - - - - - - -
Center Discharge to Inlet F FNPT - - - - - - - -
Center Inlet to Discharge B 150F - - 292 349 - 457 - -
Center Discharge to Inlet F 150F - - 318 318 - 399 - -
Center Inlet to Discharge B 300F - - 310 368 - 478 - -
Center Discharge to Inlet F 300F - - 335 337 - 419 - -
Common Dimensions (Globe & Angle)
Width C - - 562 660 660 813 889 1262
Height (To Indicator) Globe E - - 1000 1130 1134 1324 1551 1562
Height (To Indicator) Angle E - - 914 1054 - 1248 - -
Body Port Tapping FNPT Inches - - 1/2 3/4 3/4 3/4 3/4 3/4
Stem Cap Plug MNPT Inches - - 3/4 3/4 3/4 3/4 3/4 3/4
Cover Port Tapping FNPT Inches - - 3/4 3/4 3/4 3/4 3/4 3/4
Valve Stroke mm - - 83 95 95 120 141 150
Displaced Bonnet Volume (Litres) - - 6 9 9 26 34 56
Approximate Shipping Weight (Kilograms) - - 454 619 680 1179 1957 3400
Flow Capacities (L/s) (Globe &Angle)
Kv - Globe - - 310 500 610 780 1210 1800
Kv - Angle - - 332 581 - 948 - -
Continuous (Globe) - - 309 442 536 694 1104 1577
Intermittent (Globe) - - 385 555 726 899 1370 1968
Momentary (Globe) - - 694 1009 1199 1577 2460 3546
Maximum Pressure Ratings (Ductile Only)
Bar1 FNPT - - - - - - -
Bar 150F - - 17 17 17 17 17 17
Bar1 300F - - 27.6 27.6 27.6 27.6 27.6 27.6
Maximum Temperature
Celcius - - 82º 82º 82º 82º 82º 82º
Valves rated and stamped 27.6 bar as standard. Valves rated and stamped 41 bar on request
1

Globe Style Angle Style


Rolling Diaphragm Rolling Diaphragm

'E'
'E'
'E'
Flow
'E'
E
'E' Flange
Flow
'C'
SINGER SINGER
Diameter
'F'
'F' 'D' Dim
'F' 'D' 'C'
F 'D'
Flange Feet
'B' 'A' 'B' for Safety and Standard Opposite
'A' 'B' Convenience

See pilot system information, page 207.


For additional Engineering notes, see page 242.

50 2016.1
MODEL 106-PGM / S106-PGM
INTEGRAL BACK-UP, DUAL DIAPHRAGM, HYDRAULICALLY OPERATED VALVE

ISO VALVE DATA (METRIC UNITS)


Size DWG Standard Flat Diaphragm System
mm REF ANSI 80 mm 100 mm 150 mm 200 mm
Globe Dimensions All figures shown in mm unless otherwise stated
Lay Length A FNPT 343 - - -
Centerline to Bottom D FNPT 93 - - -
Lay Length A 150F 305 381 508 645
Centerline to Bottom D 150F 95 117 142 200
Lay Length A 300F 337 397 533 670
Centerline to Bottom D 300F 105 129 161 200
Angle Dimensions
Center Inlet to Discharge B FNPT 168 - - -
Center Discharge to Inlet F FNPT 118 - - -
Center Inlet to Discharge B 150F 154 191 254 324
Center Discharge to Inlet F 150F 103 127 152 203
Center Inlet to Discharge B 300F 163 200 267 337
Center Discharge to Inlet F 300F 113 135 165 216
Common Dimensions (Globe & Angle)
Width C 235 276 425 549
Height (To Indicator) Globe E 448 494 533 683
Height (To Indicator) Angle E 448 486 524 695
Body Port Tapping FNPT Inches 3/8 3/8 3/8 1/2
Stem Cap Plug MNPT Inches 3/8 3/8 3/8 3/8
Cover Port Tapping FNPT Inches 3/8 3/8 1/2 1/2
Valve Stroke mm 29 37 43 73
Displaced Bonnet Volume (Litres) 0.3 0.8 2.1 6.3
Approximate Shipping Weight (Kilograms) 68 95 204 320
Flow Capacities (L/s) (Globe &Angle)
Kv - Globe 26 47 110 190
Kv - Angle 32 55 123 225
Continuous (Globe) 29 50 114 196
Intermittent (Globe) 36 63 142 244
Momentary (Globe) 65 114 252 442
Maximum Pressure Ratings (Ductile Only)
Bar1 FNPT 27.6 - - -
Bar 150F 17 17 17 17
Bar1 300F 27.6 27.6 27.6 27.6
Maximum Temperature
Celcius 82º 82º 82º 82º
1
Valves rated and stamped 27.6 bar as standard. Valves rated and stamped 41 bar on request

Globe Style Angle Style


Flat Diaphragm Flat Diaphragm
'E'
'E'

'E'
E
E Flow
'E' SINGER SINGER

'E' Flange
Flow
SINGER
SINGER
'C' Diameter 'F'
'C'
'F'
F 'D' 'D' Dim
'F' D 'D'

Flange Feet
'B' A'A'
'B'B 'A'
for Safety and 'B' Standard Opposite
Convenience

See pilot system information, page 207.


For additional Engineering notes, see page 242.

2016.1 51
MODEL 106-PGM / S106-PGM
INTEGRAL BACK-UP, DUAL DIAPHRAGM, HYDRAULICALLY OPERATED VALVE

ISO VALVE DATA (METRIC UNITS)


Size DWG Standard Rolling Diaphragm System
mm REF ANSI 150 mm 200 mm 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm
Globe Dimensions All figures shown in mm unless otherwise stated
Lay Length A FNPT - - - - - -
Centerline to Bottom D FNPT - - - - - -
Lay Length A 150F Consult with Singer Valve 756 864 787 1051 1321 1562
Centerline to Bottom D 150F for availability 217 241 267 298 367 435
Lay Length A 300F 790 902 826 1105 1362 1607
Centerline to Bottom D 300F 236 260 292 324 400 499
Angle Dimensions
Center Inlet to Discharge B FNPT - - - - - - - -
Center Discharge to Inlet F FNPT - - - - - - - -
Center Inlet to Discharge B 150F - - 292 349 - 457 - -
Center Discharge to Inlet F 150F - - 318 318 - 399 - -
Center Inlet to Discharge B 300F - - 310 368 - 478 - -
Center Discharge to Inlet F 300F - - 335 337 - 419 - -
Common Dimensions (Globe & Angle)
Width C - - 562 660 660 813 889 1262
Height (To Indicator) Globe E - - 1000 1130 1134 1324 1551 1562
Height (To Indicator) Angle E - - 914 1054 - 1248 - -
Body Port Tapping FNPT Inches - - 1/2 3/4 3/4 3/4 3/4 3/4
Stem Cap Plug MNPT Inches - - 3/4 3/4 3/4 3/4 3/4 3/4
Cover Port Tapping FNPT Inches - - 3/4 3/4 3/4 3/4 3/4 3/4
Valve Stroke mm - - 83 95 95 120 141 150
Displaced Bonnet Volume (Litres) - - 6 9 9 26 34 56
Approximate Shipping Weight (Kilograms) - - 454 619 680 1179 1957 3400
Flow Capacities (L/s) (Globe &Angle)
Kv - Globe - - 310 500 610 780 1210 1800
Kv - Angle - - 332 581 - 948 - -
Continuous (Globe) - - 309 442 536 694 1104 1577
Intermittent (Globe) - - 385 555 726 899 1370 1968
Momentary (Globe) - - 694 1009 1199 1577 2460 3546
Maximum Pressure Ratings (Ductile Only)
Bar1 FNPT - - - - - - -
Bar 150F - - 17 17 17 17 17 17
Bar1 300F - - 27.6 27.6 27.6 27.6 27.6 27.6
Maximum Temperature
Celcius - - 82º 82º 82º 82º 82º 82º
Valves rated and stamped 27.6 bar as standard. Valves rated and stamped 41 bar on request
1

Globe Style Angle Style


Rolling Diaphragm Rolling Diaphragm

'E'
'E' Flow
'E'
'E'

'E' Flange
Flow
E
'C' Diameter
'F' 'D' Dim
'F'
SINGER
'D' SINGER

'F'
'C'
Flange Feet
'B' 'A' 'B' for Safety and Standard Opposite
F 'D' Convenience

'A' 'B'

See pilot system information, page 207.


For additional Engineering notes, see page 242.

52 2016.1
MAIN VALVES

MODEL 206-PGM / S206-PGM


INTEGRAL BACK-UP, DUAL DIAPHRAGM,
HYDRAULICALLY ACTUATED VALVE

KEY FEATURES
• Ideal for applications requiring redundant and back-up security
• Virtually uninterrupted control under a variety of system failures
• Remote annunciation option available
• Available in globe and angle style

Refer to Main Valve Options on page 62 and Pilots &


PRODUCT OVERVIEW Accessories on page 207 to customize the valve to suit
The 206-PGM and S206-PGM valves are designed for specific applications.
particularly sensitive applications or situations where
valves are difficult to access and maintain.
The PGM series valves provide integral back-up
control and the ability to signal should the desired
function move off limits. It can also provide an
independent and very positive override.
It is a variation of the standard single chamber 206- ALTERNATIVE MODELS
PG valve with modifications that add the following
features:
• Back-up diaphragm
• Completely self-contained
• Modulating or emergency close back-up
• Back-up components kept out of the main stream
until required
• Extremely positive shut-off
• Emergency close for security breach or earthquake
The PGM series valves may be combined with
additional Singer Valve specific accessories to add
further customization such as:
• Back-up pilot system A206-PGM Angle
• Annunciation with a Single Pole Double Throw
Limit Switch

2016.1 53
MODEL 206-PGM / S206-PGM
INTEGRAL BACK-UP, DUAL DIAPHRAGM, HYDRAULICALLY ACTUATED VALVE

PRODUCT LINE DRAWING


1
1. Primary Stem / Position Indicator
2 2. Secondary Stem
3
3. ASTM A536 Ductile Iron Construction
4
4. Buna-N or EPDM Secondary Diaphragm
5 5. Back-Up Secondary Assembly
6 6. Atmosphere
7 7. Sliding Guide
8 8. Buna-N or EPDM Primary Diaphragm
9 9. Buna-N or EPDM Resilient Disc
10 10. AISI 316 Stainless Steel Seat
11 11. AISI 316 Stainless Steel Stem
12. NSF 61 Fusion Bonded Epoxy Coating
12

VALVE SIZES & MATERIALS


Valve Materials
Standard Optional
Available Sizes Flanged -
Globe 4 in to 36 in (100-900 mm) -
Angle 4 in to 8 in (100 mm-200 mm) -
Valve Components
1. Valve Body, Cover 65-45-12 Ductile Iron -
2. Seat Ring 316 Stainless Steel -
3. Disc Retainer B16 Brass / B62 Bronze / A536 Ductile Iron 316 Stainless Steel
4. Stem 316 Stainless Steel -
5. Stem Nut B16 Brass 316 Stainless Steel
6. Spring 316 Stainless Steel -
7. Guide Bushings B16 Brass or SAE 660 Bronze 316 Stainless Steel
8. Diaphragm EPDM Buna-N / Viton (limited sizes)
9. Resilient Disc EPDM Buna-N / Viton (limited sizes)
10. Coating NSF61 Approved Fusion Bonded Epoxy - Thickness 10-14 mils (250-350 microns) -
11. Fasteners 18-8 Stainless Steel 316 Stainless Steel

54 2016.1
MODEL 206-PGM / S206-PGM
INTEGRAL BACK-UP, DUAL DIAPHRAGM, HYDRAULICALLY ACTUATED VALVE

SELECTION PILOTS & ACCESSORIES, REFER TO PG. 207


The Singer Model 206-PGM incorporates a second
actuator. If the primary system and/or the main valve
fails then the back-up pilot system takes over. Under
MATERIALS OF CONSTRUCTION
normal operating conditions, there is no external Most individual components can be upgraded from
discharge from the PGM. In modulating applications, ductile iron, bronze and brass to stainless steel.
when the back-up pilot system operates, there is Consult with Singer Valve.
a small (less than 1 USGPM / 0.06 L/s) continuous
discharge that should be taken to drain.
ORDERING INSTRUCTIONS
The primary pilot function can be duplicated in the
Refer to page 244 for the order form and ordering
secondary pilot system to provide continuing back-up
instructions.
operations or the secondary system can be used for
override functions. Consult with Singer Valve with
your specific application requirements.
Sizing of PGM valves is based on the same criteria as
standard PG models.

AVAILABLE OPTIONS
Further customize the valve by adding any of the
available options below.

MAIN VALVE OPTIONS, REFER TO PAGE 62


Position Indicators (Available for install at Singer
Valve or as a field modification)
• Model X129 limit switch assembly with Single Pole
Double Throw limit switch (Double Pole Double
Throw optional)
• Model X156 analog position transmitters
(4 - 20 mA)
Oxy-Nitride Stem
Internal Drop Check
Grooved Ends
Reclaimed Water

2016.1 55
MODEL 206-PGM / S206-PGM
INTEGRAL BACK-UP, DUAL DIAPHRAGM, HYDRAULICALLY ACTUATED VALVE

ANSI VALVE DATA (US UNITS)


Size DWG Standard Flat Diaphragm System
Inches REF ANSI 4 in 6 in 8 in 10 in
Globe Dimensions All figures shown in inches unless otherwise stated
Lay Length A FNPT - - - -
Centerline to Bottom D FNPT - - - -
Lay Length A 150F 15.00 20.13 25.00 24.50
Centerline to Bottom D 150F 4.60 5.60 6.75 8.56
Lay Length A 300F 15.63 21.00 26.00 25.88
Centerline to Bottom D 300F 5.00 6.25 7.50 9.31
Angle Dimensions
Center Inlet to Discharge B FNPT - - - -
Center Discharge to Inlet F FNPT - - - -
Center Inlet to Discharge B 150F 7.56 10.19 12.50 -
Center Discharge to Inlet F 150F 5.94 6.19 9.00 -
Center Inlet to Discharge B 300F 7.88 10.63 13.00 -
Center Discharge to Inlet F 300F 6.25 6.81 9.50 -
Common Dimensions (Globe & Angle)
Width C 10.00 12.50 16.00 20.00
Height (To Indicator) Globe E 19.13 20.88 23.38 30.63
Height (To Indicator) Angle E 17.38 19.25 20.50 -
Body Port Tapping FNPT 3/8 3/8 3/8 1/2
Stem Cap Plug MNPT 3/8 3/8 3/8 3/8
Cover Port Tapping FNPT 3/8 3/8 1/2 1/2
Valve Stroke 1-1/8 1-7/16 1-11/16 2-7/8
Displaced Bonnet Volume (Gallons) 0.1 0.2 0.6 1.7
Approximate Shipping Weight (Lbs) 150.0 210.0 385.0 585.0
Flow Capacities (USGPM) Globe & Angle
Cv - Globe 150 250 505 985
Cv - Angle 150 250 560 -
Continuous (Globe) 580 1025 2300 4100
Intermittent (Globe) 690 1190 2700 4670
Momentary (Globe) 1236 2160 4800 8400
Maximum Pressure Ratings (Ductile Only)
PSI FNPT - - - -
PSI 150F 250 250 250 250
PSI1 300F 400 400 400 400
Maximum Temperature
Fahrenheit 180º 180º 180º 180º
Valves rated and stamped 400 psi as standard. Valves rated and stamped 600 psi on request.
1

Globe Style Angle Style


Flat Diaphragm Flat Diaphragm

'E' 'E'

'E'
'E' 'E'
'E' 'E'
'E' Flow

'E' Flange
Flow
'C' Diameter
'C' 'C'
'F' 'F''F' 'D' Dim
'F' 'D'
'D' 'D' 'D' 'D'
Flange Feet
B' 'A' 'A'
'A' 'B'
'B' 'B' 'A' 'A' for Safety and Standard Opposite
Convenience

See pilot system information, page 207.


For additional Engineering notes, see page 242.

56 2016.1
MODEL 206-PGM / S206-PGM
INTEGRAL BACK-UP, DUAL DIAPHRAGM, HYDRAULICALLY ACTUATED VALVE

ANSI VALVE DATA (US UNITS)


Size DWG Standard Rolling Diaphragm System
Inches REF ANSI 12 in 16 in 18 in 20 in 24 in x 16 in 24 in x 20 in 30 in 36 in
Globe Dimensions All figures shown in inches unless otherwise stated.
Lay Length A FNPT - - - - - - - -
Centerline to Bottom D FNPT - - - - - - - -
Lay Length A 150F 27.50 36.00 42.00 45.00 50.50 61.50 69.93 69.93
Centerline to Bottom D 150F 9.50 11.75 12.50 13.93 16.50 17.13 20.68 23.75
Lay Length A 300F 29.00 37.63 43.63 46.63 52.25 63.25 - -
Centerline to Bottom D 300F 10.25 12.75 14.00 15.25 18.00 19.65 - -
Angle Dimensions
Center Inlet to Discharge B FNPT - - - - - - - -
Center Discharge to Inlet F FNPT - - - - - - - -
Center Inlet to Discharge B 150F - - - - - - - -
Center Discharge to Inlet F 150F - - - - - - - -
Center Inlet to Discharge B 300F - - - - - - - -
Center Discharge to Inlet F 300F - - - - - - - -
Common Dimensions (Globe and Angle)
Width C 22.13 26.00 31.50 31.50 36.00 36.00 49.75 49.75
Height (To Indicator)
E 39.38 44.56 53.00 53.00 53.00 59.50 61.50 61.50
Globe
Height (To Indicator)
E - - - - - - - -
Angle
Body Port Tapping FNPT 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Stem Cap Plug MNPT 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Cover Port Tapping FNPT 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Valve Stroke 3-1/4 3-3/4 4-3/4 4-3/4 4-3/4 5-9/16 6 6
Displaced Bonnet Volume (Gallons) 1.5 2.3 6.8 6.8 6.8 9.0 14.8 14.8
Approximate Shipping Weight (Lbs) 880 1540 2530 2730 2980 4750 7300 7500
Flow Capacities (USGPM) Globe & Angle
Cv - Globe 1550 2200 3300 3400 3500 5100 7800 8000
Cv - Angle - - - - - - - -
Continuous (Globe) 6400 9230 16500 16500 16500 21700 33650 33800
Intermittent (Globe) 7370 10470 20915 20915 20915 26000 37490 37640
Momentary (Globe) 13200 19200 30000 30050 30100 39000 67490 67640
Maximum Pressure Ratings (Ductile Only)
PSI FNPT - - - - - - - -
PSI 150F 250 250 250 250 250 250 250 250
PSI1 300F 400 400 400 400 400 400 400 400
Maximum Temperature
Fahrenheit 180º 180º 180º 180º 180º 180º 180º 180º
1
Valves rated and stamped 400 psi as standard. Valves rated and stamped 600 psi on request.

Globe Style
Rolling Diaphragm

'E'
'E' Flow
'E'
'E' 'E' Flange
Flow
E' 'C' Diameter
'F' 'D' Dim
'F' 'D'
'C' Flange Feet
'B' 'F'
'A' 'B' 'D' for Safety and Standard Opposite
Convenience

'B' 'A'
See pilot system information, page 207.
For additional Engineering notes, see page 242.

2016.1 57
MODEL 206-PGM / S206-PGM
INTEGRAL BACK-UP, DUAL DIAPHRAGM, HYDRAULICALLY ACTUATED VALVE

ANSI VALVE DATA (METRIC UNITS)


Size DWG Standard Flat Diaphragm System
mm REF ANSI 100 mm 150 mm 200 mm 250 mm
Globe Dimensions All figures shown in mm unless otherwise stated
Lay Length A FNPT - - - -
Centerline to Bottom D FNPT - - - -
Lay Length A 150F 381 511 635 622
Centerline to Bottom D 150F 117 142 171 217
Lay Length A 300F 397 533 660 657
Centerline to Bottom D 300F 127 159 191 236
Angle Dimensions
Center Inlet to Discharge B FNPT - - - -
Center Discharge to Inlet F FNPT - - - -
Center Inlet to Discharge B 150F 192 259 318 -
Center Discharge to Inlet F 150F 151 157 229 -
Center Inlet to Discharge B 300F 200 270 330 -
Center Discharge to Inlet F 300F 159 173 241 -
Common Dimensions (Globe & Angle)
Width C 254 318 406 508
Height (To Indicator)
E 486 530 594 778
Globe
Height (To Indicator)
E 441 489 521 -
Angle
Body Port Tapping FNPT Inches 3/8 3/8 3/8 1/2
Stem Cap Plug MNPT Inches 3/8 3/8 3/8 3/8
Cover Port Tapping FNPT Inches 3/8 3/8 1/2 1/2
Valve Stroke mm 29 37 43 73
Displaced Bonnet Volume (Litres) 0.3 0.8 2.1 6.3
Approximate Shipping Weight (Kilograms) 68 95 175 265
Flow Capacities (L/s) Globe & Angle
K v - Globe 36 60 120 230
Kv - Angle 36 60 133 -
Continuous (Globe) 37 65 145 259
Intermittent (Globe) 44 75 170 295
Momentary (Globe) 78 136 303 530
Maximum Pressure Ratings (Ductile Only)
Bar FNPT - - - -
Bar 150F 17 17 17 17
Bar1 300F 27.6 27.6 27.6 27.6
Maximum Temperature
Celcius 82º 82º 82º 82º
Valves rated and stamped 27.6 bar as standard. Valves rated and stamped 41 bar on request
1

Globe Style Angle Style


Flat Diaphragm Flat Diaphragm

'E' 'E'

'E'
'E' 'E'
'E' 'E'
'E' Flow

'E' Flange
Flow
'C' Diameter
'C' 'C'
'F' 'F''F' 'D' Dim
'F' 'D'
'D' 'D' 'D' 'D'
Flange Feet
B' 'A' 'A'
'A' 'B'
'B' 'B' 'A' 'A' for Safety and Standard Opposite
Convenience

See pilot system information, page 207.


For additional Engineering notes, see page 242.

58 2016.1
MODEL 206-PGM / S206-PGM
INTEGRAL BACK-UP, DUAL DIAPHRAGM, HYDRAULICALLY ACTUATED VALVE

ANSI VALVE DATA (METRIC UNITS)


Size DWG Standard Rolling Diaphragm System
600 x 500
MM REF ANSI 300 mm 400 mm 450 mm 500 mm 600 x 400 mm 750 mm 900 mm
mm
Globe Dimensions All figures shown in mm unless otherwise stated.
Lay Length A FNPT - - - - - - - -
Centerline to Bottom D FNPT - - - - - - - -
Lay Length A 150F 699 914 1067 1143 1283 1562 1776 1776
Centerline to Bottom D 150F 241 298 318 354 419 435 525 603
Lay Length A 300F 737 956 1108 1184 1327 1607 - -
Centerline to Bottom D 300F 260 324 356 387 457 499 - -
Angle Dimensions
Center Inlet to Discharge B FNPT - - - - - - - -
Center Discharge to Inlet F FNPT - - - - - - - -
Center Inlet to Discharge B 150F - - - - - - - -
Center Discharge to Inlet F 150F - - - - - - - -
Center Inlet to Discharge B 300F - - - - - - - -
Center Discharge to Inlet F 300F - - - - - - - -
Common Dimensions (Globe & Angle)
Width C 562 660 800 800 914 914 1264 1264
Height (To Indicator)
E 1000 1132 1346 1346 1346 1511 1162 1562
Globe
Height (To Indicator) Angle E - - - - - - - -
Body Port Tapping FNPT Inches 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Stem Cap Plug MNPT Inches 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Cover Port Tapping FNPT Inches 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Valve Stroke mm 83 95 120 120 120 141 150 150
Displaced Bonnet Volume (Litres) 5.67 8.69 25.55 25.55 25.55 34.00 55.76 55.83
Approximate Shipping Weight (Kilograms) 399 699 1148 1238 1352 2155 2812 3400
Flow Capacities (L/s) Globe & Angle
Kv - Globe 370 520 780 810 830 1210 1850 1870
Kv - Angle - - - - - - - -
Continuous (Globe) 404 582 1041 1041 1041 1370 2120 2132
Intermittent (Globe) 465 661 1320 1320 1320 1640 2362 2375
Momentary (Globe) 833 1211 1893 1896 1899 2460 4255 4267
Maximum Pressure Ratings (Ductile Only)
Bar FNPT - - - - - - - -
Bar 150F 17 17 17 17 17 17 17 17
Bar1 300F 27.6 27.6 27.6 27.6 27.6 27.6 27.6 27.6
Maximum Temperature
Celcius 82º 82º 82º 82º 82º 82º 82º 82º
1
Valves rated and stamped 27.6 Bar as standard. Valves rated and stamped 41 Bar on request.

Globe Style
Rolling Diaphragm

'E'
'E' Flow
'E'
'E' 'E' Flange
Flow
' 'C' Diameter
'F' 'D' Dim
'F' 'D'
'C' Flange Feet
'B' 'F'
'A' 'B' 'D' for Safety and Standard Opposite
Convenience

'B' 'A'
See pilot system information, page 207.
For additional Engineering notes, see page 242.

2016.1 59
MODEL 206-PGM / S206-PGM
INTEGRAL BACK-UP, DUAL DIAPHRAGM, HYDRAULICALLY ACTUATED VALVE

ISO VALVE DATA (METRIC UNITS)


Size DWG Standard Flat Diaphragm System
mm REF ISO 100 mm 150 mm 200 mm 250 mm
Globe Dimensions All figures shown in mm unless otherwise stated
Lay Length A BSPT - - - -
Centerline to Bottom D BSPT - - - -
Lay Length A PN10 / PN16 381 511 635 622
Centerline to Bottom D PN10 / PN16 117 143 171 217
Lay Length A PN25 / PN40 397 533 660 657
Centerline to Bottom D PN25 / PN40 127 161 191 236
Angle Dimensions
Center Inlet to Discharge B BSPT - - - -
Center Discharge to Inlet F BSPT - - - -
Center Inlet to Discharge B PN10 / PN16 192 259 318 -
Center Discharge to Inlet F PN10 / PN16 151 157 229 -
Center Inlet to Discharge B PN25 / PN40 200 270 330 -
Center Discharge to Inlet F PN25 / PN40 159 173 241 -
Common Dimensions (Globe & Angle)
Width C 254 318 406 508
Height (To Indicator) Globe E 486 530 594 778
Height (To Indicator) Angle E 441 489 521 -
Body Port Tapping FNPT Inches 3/8 3/8 3/8 1/2
Stem Cap Plug MNPT Inches 3/8 3/8 3/8 3/8
Cover Port Tapping FNPT Inches 3/8 3/8 1/2 1/2
Valve Stroke mm 29 37 43 73
Displaced Bonnet Volume (Litres) 0.3 0.8 2.1 6.3
Approximate Shipping Weight (Kilograms) 68 95 175 265
Flow Capacities (L/s) Globe & Angle
Kv - Globe 36 60 120 230
Kv - Angle 36 60 133 -
Continuous (Globe) 37 65 145 259
Intermittent (Globe) 44 75 170 295
Momentary (Globe) 78 136 303 530
Maximum Pressure Ratings
Bar BSPT - - - -
Bar PN16 16 16 16 16
Bar* PN25 25 25 25 25
Maximum Temperature
Celcius 82º 82º 82º 82º
*Valves rated and stamped 27.6 Bar as standard. Valves rated and stamped 41 Bar upon request

Globe Style Angle Style


Flat Diaphragm Flat Diaphragm

'E' 'E'

'E'
'E' 'E'
'E' 'E'
'E' Flow

'E' Flange
Flow
'C' Diameter
'C' 'C'
'F' 'F''F' 'D' Dim
'F' 'D'
'D' 'D' 'D' 'D'
Flange Feet
B' 'A' 'A'
'A' 'B'
'B' 'B' 'A' 'A' for Safety and Standard Opposite
Convenience

See pilot system information, page 207.


For additional Engineering notes, see page 242.

60 2016.1
MODEL 206-PGM / S206-PGM
INTEGRAL BACK-UP, DUAL DIAPHRAGM, HYDRAULICALLY ACTUATED VALVE

ISO VALVE DATA (METRIC UNITS)


Size DWG Standard Rolling Diaphragm System
600 x 400 600 x 500
MM REF ISO 300 mm 400 mm 450 mm 500 mm 700 mm 800 mm 900 mm
mm mm
Globe Dimensions All figures shown in mm unless otherwise stated.
Lay Length A BSPT - - - - - - - - -
Centerline to Bottom D BSPT - - - - - - - - -
Lay Length A PN10 / PN16 699 914 1067 1143 1283 1562 1607 1776 1776
Centerline to Bottom D PN10 / PN16 241 298 318 354 419 435 499 526 603
Lay Length A PN25 / PN40 737 956 1108 1184 1327 1607 - - -
Centerline to Bottom D PN25 / PN40 267 324 356 387 457 499 - - -
Angle Dimensions
Center Inlet to Discharge B BSPT - - - - - - - - -
Center Discharge to Inlet F BSPT - - - - - - - - -
Center Inlet to Discharge B PN10 / PN16 - - - - - - - - -
Center Discharge to Inlet F PN10 / PN16 - - - - - - - - -
Center Inlet to Discharge B PN25 / PN40 - - - - - - - - -
Center Discharge to Inlet F PN25 / PN40 - - - - - - - - -
Common Dimensions (Globe & Angle)
Width C 562 660 795 800 914 914 1262 1262 1262
Height (To Indicator)
E 1000 1132 1346 1346 1346 1511 1562 1562 1562
Globe
Height (To Indicator)
E - - - - - - - - -
Angle
Body Port Tapping FNPT Inches 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Stem Cap Plug MNPT Inches 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Cover Port Tapping FNPT Inches 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Valve Stroke mm 83 95 120 120 120 141 150 150 150
Displaced Bonnet Volume (Litres) 6 9 26 26 26 34 56 56 56
Approximate Shipping Weight (Kilograms) 399 699 1148 1238 1352 2155 2812 2993 3175
Flow Capacities (L/s) Globe & Angle
Kv - Globe 370 520 780 810 830 1210 1850 1870 1900
Kv - Angle - - - - - - - - -
Continuous (Globe) 404 582 1041 1041 1041 1370 2120 2126 2132
Intermittent (Globe) 465 661 1320 1320 1320 1640 2362 2368 2375
Momentary (Globe) 833 1211 1893 1896 1899 2460 4255 4261 4267
Maximum Pressure Ratings
Bar BSPT - - - - - - - - -
Bar PN16 16 16 16 16 16 16 16 16 16
Bar* PN25 25 25 25 25 25 25 25 25 25
Maximum Temperature
Celcius 82º 82º 82º 82º 82º 82º 82º 82º 82º
*
Valves rated and stamped 27.6 Bar as standard. Valves rated and stamped 41 Bar on request.

Globe Style
Rolling Diaphragm

'E'
'E' Flow
'E'
'E' 'E' Flange
Flow
' 'C' Diameter
'F' 'D' Dim
'F' 'D'
'C' Flange Feet
'B' 'F'
'A' 'B' 'D' for Safety and Standard Opposite
Convenience

'B' 'A'
See pilot system information, page 207.
For additional Engineering notes, see page 242.

2016.1 61
MAIN VALVES - OPTIONS

MODEL 106-GE / 206-GE


GROOVED ENDS

KEY FEATURES
• Convenient system and equipment access for ease of
alignment and installation
• Improved flexibility with expansion, contraction and
deflection
• Seismic stress absorption
• Eliminates unions

PRODUCT OVERVIEW
For use with grooved Iron Pipe Size (IPS) Pipe Coupling Grooved ends come in the following size ranges:
Products, grooved ends allows you to benefit from • 2 in / 50 mm – 8 in / 200 mm
the simplicity and convenience of grooved end piping
• Angle ranges from 2 in / 50 mm – 3 in / 80 mm
and fittings in an automatic control valve. There are
a wide range of applications where grooved ends are Standard cut groove specifications for steel and
relevant, but typical applications include municipal other IPS pipe will apply, unless otherwise specified
water, waste water, fire protection and plumbing.

62 2016.1
MODEL 106-GE / 206-GE
GROOVED ENDS

VALVE DATA (US UNITS)


DWG Standard Flat Diaphragm System
8 in
Inches REF Grooved Ends 2 in 2-1/2 in 3 in 4 in 6 in 8 in
(206)
Globe Dimensions All figures shown in inches unless otherwise stated
Lay Length A 9.38 11.63 13.25 15.00 20.00 25.38 26.00
Centerline to Bottom D 2.75 3.25 3.68 4.00 5.60 7.50 4.63
Common Dimensions (Globe)
Width C 6.00 8.19 9.25 10.88 16.75 21.63 16.00
Height (To Stem Cap) Globe E 4.75 7.50 8.00 9.15 11.75 14.91 14.13
Body Port Tapping FNPT 3/8 3/8 3/8 3/8 3/8 1/2 3/8
Stem Cap Plug MNPT 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Cover Port Tapping FNPT 3/8 3/8 3/8 3/8 3/8 1/2 1/2
Valve Stroke 9/16 15/16 1 1/8 1 7/16 1 11/16 2 7/8 1 11/16
Displaced Bonnet Volume (Gallons) 0.02 0.07 0.1 0.2 0.6 1.7 0.6
Approximate Shipping Weight (Lbs) 40 65 100 175 400 650 500
Flow Capacities (USGPM) Globe
Cv 55 80 110 200 460 800 505
Continuous (Globe) 210 300 460 800 1800 3100 2300
Intermittent (Globe) 260 375 575 1000 2250 3875 2700
Momentary (Globe) 470 670 1030 1800 4000 7000 4800
Maximum Pressure Ratings (Ductile Only)
PSI1 Grooved Ends 400 400 400 400 400 400 400
Maximum Temperature
Fahrenheit 180º 180º 180º 180º 180º 180º 180º
Valves rated and stamped 400 psi as standard. Valves rated and stamped 600 psi on request.
1

SINGER

2016.1 63
MODEL 106-GE / 206-GE
GROOVED ENDS

VALVE DATA (METRIC UNITS)


DWG Standard Flat Diaphragm System
200 mm
MM REF Grooved Ends 50 mm 65 mm 80 mm 100 mm 150 mm 200 mm
(206)
Globe Dimensions All figures shown in millimeters unless otherwise stated
Lay Length A 238 295 337 381 508 645 660
Centerline to Bottom D 70 83 93 102 142 191 118
Common Dimensions (Globe)
Width C 152 208 235 276 425 549 406
Height (To Stem Cap) Globe E 121 191 203 232 298 379 359
Body Port Tapping FNPT Inches 3/8 3/8 3/8 3/8 3/8 1/2 3/8
Stem Cap Plug MNPT Inches 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Cover Port Tapping FNPT Inches 3/8 3/8 3/8 3/8 3/8 1/2 1/2
Valve Stroke mm 14 25 29 37 43 73 43
Displaced Bonnet Volume (Litres) 0.1 0.3 0.3 0.8 2.1 6.3 2.1
Approximate Shipping Weight (Kilograms) 18 29 45 79 181 295 227
Flow Capacities (L/s) Globe
Kv (Globe) 13 19 26 47 110 190 120
Continuous (Globe) 13 19 29 50 114 196 145
Intermittent (Globe) 16 24 36 63 142 244 170
Momentary (Globe) 30 42 65 114 252 442 300
Maximum Pressure Ratings (Ductile Only)
Bar1 Grooved Ends 27.6 27.6 27.6 27.6 27.6 27.6 27.6
Maximum Temperature
Celcius 82º 82º 82º 82º 82º 82º 82º
1
Valves rated and stamped 27.6 Bar as standard. Valves rated and stamped 41 Bar on request.

SINGER

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering
instructions.

64 2016.1
MAIN VALVES -OPTIONS

MODEL 106-PG
STAINLESS STEEL, SINGLE CHAMBER,
HYDRAULICALLY OPERATED VALVE

KEY FEATURES
• Anti-cavitation option is ideal for high pressure drop
situations
• Available in globe style

PRODUCT OVERVIEW PRODUCT LINE DRAWING


The 106-PG series control valve is designed to suit 1. AISI 316 Stainless Steel Construction Valve Body,
a large variety of applications such as pressure, Cover
flow or level control. This hydraulically operated 2. 316 Stainless Steel Seat Ring
valve introduces or releases water from the control
chamber above the diaphragm to effectively maintain 3. 316 Stainless Steel Stem
accurate water control. 4. 316 Stainless Steel Spring
Refer to Main Valve Options on page 62 and Pilots
5. Diaphragm Buna-N or EPDM
& Accessories on page 207 to further customize the
valve to suit specific applications. 6. Buna-N or EPDM Resilient Disc

4. 1.

5.

6.

2.

3.

2016.1 65
MODEL 106-PG
STAINLESS STEEL, SINGLE CHAMBER, HYDRAULICALLY OPERATED VALVE

VALVE SIZES & MATERIALS


Valve Materials
Standard Optional
Available Sizes Threaded Flanged -
Globe 1/2 in to 1-1/2 in (15-40 mm) 1-1/2 in to 6 in (40-150 mm) -
Valve Components
1. Valve Body, Cover 316 Stainless Steel -
2. Seat Ring 316 Stainless Steel -
3. Disc Retainer 316 Stainless Steel -
4. Stem 316 Stainless Steel -
5. Stem Nut 316 Stainless Steel -
6. Spring 316 Stainless Steel -
7. Guide Bushings 316 Stainless Steel -
8. Diaphragm EPDM Buna-N / Viton (limited sizes)
9. Resilient Disc EPDM Buna-N / Viton (limited sizes)
10. Fasteners 18-8 Stainless Steel 316 Stainless Steel

66 2016.1
MODEL 106-PG
STAINLESS STEEL, SINGLE CHAMBER, HYDRAULICALLY OPERATED VALVE

ANSI VALVE DATA (US UNITS)


Size DWG Standard Flat Diaphragm System
Inches REF ANSI 1/2 in 3/4 in 1 in 1 1/4 in 1 1/2 in 2 in 2 1/2 in 3 in 4 in 6 in
Globe Dimensions All figures shown in inches unless otherwise stated
Lay Length A FNPT 4.25 4.25 6.75 6.75 6.75 - - - - -
Centerline to Bottom D FNPT 0.83 0.83 2.50 2.50 2.50 - - - - -
Lay Length A 150F - - - - 8.50 9.38 11.00 12.00 15.00 20.00
Centerline to Bottom D 150F - - - - 2.75 3.00 3.50 3.75 4.60 5.60
Lay Length A 300F - - - - 9.00 10.00 11.63 13.25 15.63 21.00
Centerline to Bottom D 300F - - - - 3.25 3.25 3.75 4.13 5.09 6.34
Common Dimensions (Globe & Angle)
Width C 3.00 3.00 4.88 4.88 6.13 6.50 8.19 9.25 10.88 16.75
Height (To Stem Cap) Globe E 3.06 3.06 4.38 4.38 4.38 4.75 7.50 8.00 9.15 11.75
Height (To Stem Cap) Angle E - - 4.38 4.38 4.38 4.75 7.50 8.00 9.15 11.75
Body Port Tapping FNPT 1/4 1/4 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Stem Cap Plug MNPT 1/4 1/4 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Cover Port Tapping FNPT - - 3/8 3/8 3/8 3/8 3/8 3/8 3/8 1/2
Valve Stroke 1/4 1/4 1/2 1/2 1/2 9/16 15/16 1 1/8 1 7/16 1 11/16
Displaced Bonnet Volume (Gallons) 0.002 0.002 0.007 0.007 0.007 0.018 0.066 0.090 0.20 0.56
Approximate Shipping Weight (Lbs) 10 10 20 20 20 40 65 100 175 400
Capacities (USPGM) Globe & Angle
Cv - Globe 6.4 6.4 28 30 32 55 80 110 200 460
Cv - Angle - - 24 24 26 63 90 135 230 535
Continuous (Globe) 12 19 49 93 125 210 300 460 800 1800
Intermittent (Globe) 15 20 61 120 160 260 375 575 1000 2250
Momentary (Globe) 28 43 110 170 250 470 670 1030 1800 4000
Maximum Pressure Ratings (Ductile Only)
PSI1 FNPT 400 400 400 400 400 400 400 400 - -
PSI 150F - - - - 250 250 250 250 250 250
PSI1 300F - - - - 400 400 400 400 400 400
Maximum Temperature
Fahrenheit 180º 180º 180º 180º 180º 180º 180º 180º 180º 180º
1
Valves rated and stamped 400 psi as standard. Valves rated and stamped 600 psi on request.

Globe Style
Flat Diaphragm 'E'
'E' 'E'
Flow
'E' 'E'
'E'
Flange 'C'Flow
'C' Diameter 'F'
'D' 'F' 'F' 'D' 'D' Dim
'D'
Flange Feet
'A'
'A' 'B'
'B' 'A' for Safety and 'B' Standard Opposite
Convenience

See pilot system information, page 207.


For additional Engineering notes, see page 242.

2016.1 67
MODEL 106-PG
STAINLESS STEEL, SINGLE CHAMBER, HYDRAULICALLY OPERATED VALVE

ANSI VALVE DATA (METRIC UNITS)


Size DWG Stnd Flat Diaphragm System
100 150
mm REF ANSI 15 mm 20 mm 25 mm 32 mm 40 mm 50 mm 65 mm 80 mm
mm mm
Globe Dimensions All figures show in mm unless otherwise stated
Lay Length A FNPT 108 108 171 171 171 - - - - -
Centerline to Bottom D FNPT 21 21 64 64 64 - - - - -
Lay Length A 150F - - - - 216 238 279 305 381 508
Centerline to Bottom D 150F - - - - 70 76 89 95 117 142
Lay Length A 300F - - - - 229 254 295 337 397 533
Centerline to Bottom D 300F - - - - 83 83 95 105 129 161
Common Dimensions (Globe & Angle)
Width C 76 76 124 124 156 165 208 235 276 425
Height (to stem cap)
E 78 78 111 111 111 121 191 203 232 298
Globe
Height (to stem cap)
E - - 111 111 111 121 191 203 232 298
Angle
Body Port Tapping FNPT in 1/4 1/4 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Stem Cap Plug MNPT in 1/4 1/4 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Cover Port Tapping FNPT in - - 3/8 3/8 3/8 3/8 3/8 3/8 3/8 1/2
Valve Stroke mm 6.4 6.4 13 13 13 14 25 29 37 43
Displaced Bonnet Volume (Litres) 0.01 0.01 0.03 0.03 0.03 0.07 0.25 0.34 0.76 2.12
Approximate Shipping Weight (Kilograms) 5.00 5.00 9.00 9.00 9.00 18.00 29.00 45.00 79.00 181.00
Capacities (L/s) Globe & Angle
Kv - Globe 1.5 1.5 6.6 7.1 7.6 13.0 19.0 26.1 47.4 109.0
Kv - Angle - - 5.7 5.7 6.2 14.9 21.3 32.0 54.5 126.8
Continuous (Globe) 0.76 1.20 3.09 5.87 7.89 13.25 18.93 29.02 50.47 113.56
Intermittent (Globe) 0.95 1.26 3.85 7.57 10.09 16.40 23.66 36.28 63.09 141.95
Momentary (Globe) 1.77 2.71 6.94 10.73 15.77 29.65 42.27 64.98 113.56 252.36
Maximum Pressure Ratings (Ductile Only)
Bar1 FNPT 27.6 27.6 27.6 27.6 27.6 27.6 27.6 27.6 - -
Bar 150F - - - - 17 17 17 17 17 17
Bar1 300F - - - - 27.6 27.6 27.6 27.6 27.6 27.6
Maximum Temperature
Celcius 82º 82º 82º 82º 82º 82º 82º 82º 82º 82º
1
Valves rated and stamped 27.6 bar as standard. Valves rated and stamped 41 bar on request

Globe Style
Flat Diaphragm 'E'
'E' 'E'
Flow
'E'
'E' 'E'
Flange 'C'Flow
'C' Diameter
'F'
'F' 'F' 'D'
'D' 'D' 'D' Dim

Flange Feet
'A' 'A' 'B' 'B' 'A' for Safety and 'B' Standard Opposite
Convenience

See pilot system information, page 207.


For additional Engineering notes, see page 242.

68 2016.1
MODEL 106-PG
STAINLESS STEEL, SINGLE CHAMBER, HYDRAULICALLY OPERATED VALVE

ISO VALVE DATA (METRIC UNITS)


Size DWG Stnd Flat Diaphragm System
100 150
mm REF ISO 15 mm 20 mm 25 mm 32 mm 40 mm 50 mm 65 mm 80 mm
mm mm
Globe Dimensions All figures show in mm unless otherwise stated
Lay Length A BSPT 108 108 171 171 171 - - - - -
Centerline to
D BSPT 21 21 64 64 64 - - - - -
Bottom
Lay Length A PN10 / PN16 - - - - 229 238 279 318 381 508
Centerline to
D PN10 / PN16 - - - - 83 76 89 100 117 142
Bottom
Lay Length A PN25 / PN40 - - - - 229 238 279 318 397 533
Centerline to
D PN25 / PN40 - - - - 83 76 89 100 129 161
Bottom
Common Dimensions (Globe & Angle)
Width C 76 76 124 124 156 165 208 235 276 425
Height (To Stem
E 78 78 111 111 111 121 191 203 232 298
Cap) Globe
Height (To Stem
E - - 111 111 111 121 191 203 232 298
Cap) Angle
Body Port Tapping FNPT Inches 1/4 1/4 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Stem Cap Plug MNPT Inches 1/4 1/4 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Cover Port Tapping FNPT Inches - - 3/8 3/8 3/8 3/8 3/8 3/8 3/8 1/2
Valve Stroke mm 6.4 6.4 13 13 13 14 25 29 37 43
Displaced Bonnet Volume (Litres) 0.01 0.01 0.03 0.03 0.03 0.07 0.25 0.34 0.76 2.12
Approximate Shipping Weight (Kilograms) 5 5 9 9 9 18 29 45 79 181
Capacities (L/s) Globe & Angle
Kv - Globe 1.5 1.5 6.6 7.1 7.6 13.0 19.0 26.1 47.4 109.0
Kv - Angle - - 5.7 5.7 6.2 14.9 21.3 32.0 54.5 126.8
Continuous (Globe) 0.76 1.20 3.09 5.87 7.89 13.25 18.93 29.02 50.47 113.56
Intermittent (Globe) 0.95 1.26 3.85 7.57 10.09 16.40 23.66 36.28 63.09 141.95
Momentary (Globe) 1.77 2.71 6.94 10.73 15.77 29.65 42.27 64.98 113.56 252.36
Maximum Pressure Ratings (Ductile Only)
Bar1 BSPT 27.6 27.6 27.6 27.6 27.6 27.6 27.6 27.6 - -
Bar PN16 - - - - 16 16 16 16 16 16
Bar1 PN25 - - - - 25 25 25 25 25 25
Maximum Temperature
Celcius 82º 82º 82º 82º 82º 82º 82º 82º 82º 82º
1
Valves rated and stamped 27.6 bar as standard. Valves rated and stamped 41 bar on request

2016.1 69
MAIN VALVES - OPTIONS

MODEL 106-IDC / 206-IDC


INTERNAL DROP CHECK

KEY FEATURES
• Prevents reverse flow and reduces surges
• Completely mechanical and has no dependency on the pilot system
• Silent operation

PRODUCT OVERVIEW ORDERING INSTRUCTIONS


The Internal Drop Check (IDC) ensures quick positive Refer to page 244 for the order form and ordering
shut-off whenever normal forward flow stops, this instructions.
action will prevent reverse flow while reducing surge Note:
events.
• PTC valves include the IDC
The IDC assembly is a spring assisted, silent,
mechanical check option for standard Singer main • this IDC may be included as standard with
valves and comes in sizes ranging from 2 in / 50 mm – some products
36 in / 900 mm.
The IDC is a standard feature on the 106-PTC and 206-
PTC series control valves and is available as on optional
add-on for control valves larger than 2 in / 50 mm.

STANDARD MATERIAL
Inner Valve: ASTM A536 Ductile Iron
Inner Valve Sleeve: B-62 Bronze or AISI 316 Stainless
Steel
Stem: AISI 316 Stainless Steel
O-Ring Seals: Buna-N
Spring is optional on 106 series valves larger than 10
in / 250 mm and 206 series valves larger than 12 in /
300 mm. (On all other sizes, the spring is included.)

70 2016.1
MODEL 106-IDC / 206-IDC INTERNAL DROP CHECK |
106-NYM / 206-NYM INTERNAL DROP CHECK NO YELLOW METAL

PRODUCT LINE DRAWING


1. IDC - Internal Drop Check
2. IDC Stem
3. Spring (optional) in sizes 10 in / 250 mm and larger 106
4. Inner Valve
5. Disc Retainer
6. Inner Valve Sleeve Main valve fully open:
Diaphragm and inner valve assembly controlled
by the pilot system.

Valve fully closed:


Pressure above diaphragm drives
diaphragm assembly and IDC
down to seal the valve.

1
2

4
5
6

Should forward flow stop for any reason, the IDC moves down to
seal against reverse flow, regardless of the valve position.

MAIN VALVES - OPTIONS

MODEL 106-NYM / 206-NYM


INTERNAL DROP CHECK NO YELLOW METAL

NO YELLOW METAL UPGRADE OPTION ORDERING INSTRUCTIONS


Yellow metal components such as Brass, Bronze and Refer to page 244 for the order form and ordering
Copper may not be acceptable materials in harsh instructions.
water conditions or in specific specifications for a
variety of reasons. All or any portion of yellow metals Note: The -NYM option may be included as standard
in the internals of main valves may be upgraded to with some products.
stainless steel. All or any portion of yellow metals
Include -NYM addendum to main valve order.
on pilots or pilot tubing and fittings may also be
upgraded to stainless steel.

2016.1 71
MAIN VALVES - OPTIONS

MODELS 106-RW / 206-RW


RECLAIMED WATER VALVE

KEY FEATURES
• Resists corrosion from chlorine chloramine and
other corrosive elements typically found in grey or
reclaimed water
• Can be used in all standard and special applications

PRODUCT OVERVIEW
The 106-RW and 206-RW series control valves offer superior corrosion resistance performance in grey or
reclaimed water applications and can be used in all standard and special applications.
It’s constructed from materials which are selected specifically to address corrosion concerns from chlorine,
chloramine, and other corrosive elements typically found in grey or reclaimed water.

MAIN VALVES - OPTIONS

MODELS X107
POSITION INDICATOR

KEY FEATURES
• Manually purge trapped air through the pet cock
• Simple and safe retrofit installation through the main valve stem cap
• Stainless steel indicator rod and pin for longevity

PRODUCT OVERVIEW
The X107 position indicator stem is designed to provide direct indication of the diaphragm /
inner valve position. The indicator stem moves up and down within its protective hexagonal
brass housing. Within the housing is clear Pyrex sight glass, which allows viewing from both
sides.
Singer main control valves are designed with a separate stem cap that makes installation of
the X107 safe and simple to do in the field.

72 2016.1
MODELS X107
POSITION INDICATOR

PRODUCT LINE DRAWING STANDARD MATERIALS


1. Cap and Bleed Valve (SST) Body: Brass
2. O Ring Seal (Buna-N) Bleed Valve: SST
3. Buna/EPDM Indicator Rod: SST
4. Open Notch Sight O ring Seals: Buna-N

5. Tube (Pyrex) Indicator Body: Brass


Sight Tube: PYREX
6. Closed Notch
Indicator Pin: SST
7. Indicator Body (Brass)
8. Main Valve Stem Cap (Ductile Iron)
ORDERING INSTRUCTIONS
9. Indicator Pin and Retaining Pin (Stainless Steel)
Refer to page 244 for the order form and ordering
instructions.
1
Note: this X107 may be included as standard with
2
some products
3
4
5
6

Valve Stroke

SIZES & HEIGHTS


106-X107 Dimension ‘G’ Height
Sizes (in) 1 in 1-1/4 in 1-1/2 in 2’ 2-1/2 in 3 in 4 in 6 in 8 in 10 in 12 in 14 in 16 in 20 in 24 in 36 in
25 32 40 50 65 80 100 150 200 250 300 350 400 500 600 900
Sizes (mm) mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm
Height (in) 3.5 in 3.5 in 3.5 in 3.5 in 4.75 in 4.75 in 4.75 in 4.75 in 6 in 6.88 in 6.88 in 6.88 in 7.93 in 9.75 in 9.75 in 13.0 in

89 89 89 89 121 121 121 121 153 175 175 175 201 248 248 330
Height (mm) mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm

206-X107 Dimension ‘G’ Height


Sizes (in) 3 in 4 in 6 in 8 in 10 in 12 in 16 in 18 in 20 in 24 in 28 in 30 in 32 in 36 in 40 in
80 100 150 200 250 300 400 450 500 600 700 750 800 900 1000
Sizes (mm) mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm
Height (in) 4.75 in 4.75 in 4.75 in 4.75 in 6 in 6.88 in 6.88 in 7.93 in 7.93 in 7.93 in 9.75 in 9.75 in 9.75 9.75 in 13.0 in

121 121 121 121 153 175 175 201 201 201 248 248 248 248 330
Height (mm) mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm
CF = Consult Factory

2016.1 73
MAIN VALVES - OPTIONS

MODEL X156
LINEAR INDUCTIVE VALVE POSITION TRANSMITTER

KEY FEATURES
• The stainless steel actuator stem is pinned directly to
the main valve stem
G
• Stems on main valves larger than 2 1/2 in / 65 mm are
pre-drilled for easy installation
• Separate stem cap permits easy field installation
• Combination water-tight rated enclosure to NEMA 4X
and NEMA 6

PRODUCT OVERVIEW STANDARD MATERIALS


The X156 Linear Inductive Valve Position Transmitter Adapter: ASTM B-16
electronically indicates the position of the valve and Target: AISI 416 stainless steel
is ideal for applications where precision and accuracy
is required. It is mounted directly to the main valve Actuator Stem: AISI 316 stainless steel
stem and uses an external source of 24VDC power, O ring Seals: Buna-N
a 4 to 20mA signal proportional to valve stroke is
Seal Bushing: ASTM B-16 brass
generated and transmitted. The zero and span are
fully adjustable over the complete range of stroke. Mounting Plate: Coated steel
Actuator Stem Pin: 18-8 stainless steel
SIZES & HEIGHTS
Dimension G in the above image is the height added
to the valve by the assembly.

106-X156 Dimension ‘G’ Height


Sizes (in) 2 1/2 in 3 in 4 in 6 in 8 in 10 in 12 in 14 in 16 in 20 in 24 in 36 in
Sizes ( mm) 65 mm 80 mm 100 mm 150 mm 200 mm 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm 900 mm
Height (in) 9 in 9 in 9 in 9 in 9 in 9 in 9 in 9 in 9 in 12.5 in 12.5 in 31 in
Height ( mm) 230 mm 230 mm 230 mm 230 mm 230 mm 230 mm 230 mm 230 mm 230 mm 318 mm 318 mm 788 mm

206-X156 Dimension ‘G’ Height


Sizes (in) 3 in 4 in 6 in 8 in 10 in 12 in 16 in 18 in 20 in 24 in 28 in 30 in 32 in 36 in 40 in
Sizes ( mm) 80 mm 100 mm 150 mm 200 mm 250 mm 300 mm 400 mm 450 mm 500 mm 600 mm 700 mm 750 mm 800 mm 900 mm 1000 mm
Height (in) 9 in 9 in 9 in 9 in 9 in 9 in 9 in 9 in 9 in 9 in 12.5 in 12.5 in 12.5 in 12.5 in 31 in
Height ( mm) 230 mm 230 mm 230 mm 230 mm 230 mm 230 mm 230 mm 230 mm 230 mm 230 mm 318 mm 318 mm 318 mm 318 mm 788 mm

74 2016.1
MODEL X156 LINEAR INDUCTIVE VALVE POSITION TRANSMITTER |
MODEL OXY-NITRIDE STEM

ORDERING INSTRUCTIONS
• Available without 4-20mA rescaler
• Available with optional external limit switches

Refer to page 244 for the order form and ordering


instructions.
Additionally, include the following information for this
product:
• Integrated discrete switch output (optional)

MAIN VALVES - OPTIONS

MODEL OXY-NITRIDE STEM

PRODUCT OVERVIEW ORDERING INSTRUCTIONS


The Oxy-Nitride stem is ideally suited to reclaimed Refer to page 244 for the order form and ordering
water applications and a wide range of other instructions.
applications where mineral-build up is a concern.
When minerals build-up on stems, it can cause Note: this Oxy-Nitride Stem may be included as stan-
potential maintenance problems and operational dard with some products
malfunctions. The Oxy-Nitride treated stainless
steel stem is the perfect solution. Its specialized
proprietary aerated salt bath treatment will reduce or
prevent mineral build-up allowing the stem to stroke
freely as it passes through the guide bushing. The
Oxy-Nitride stem also increases surface hardness for
wear, fatigue and lubricity.

2016.1 75
MAIN VALVES - OPTIONS

MODEL X129
LIMIT SWITCH INDICATOR

KEY FEATURES
• All main valve stems are pre-drilled ready to accept this option
• The Single Pole Double Throw limit switch is rated up to 10A, 250V,
NEMA 4 enclosure with UL and CSA listings.
• Maximum Working Pressure: 400 psi / 27.6 bar

PRODUCT OVERVIEW
The X129 limit switch is actuated by the opening and closing of a main
valve. The assembly is fully adjustable over the entire valve stroke.
Layout variations allow up to four separate switches to be mounted
and actuated off the same stem.

PRODUCT LINE DRAWING STANDARD MATERIALS


1. Stem Hat Adapter: Brass
2. Adapter and Seal Bushing Bleed Screw Stem Hat: Brass
(vent air) Actuator Stem: SST
3. Limit Switch O’ring Seals: Buna-N
4. Limit Switch Mounting Assembly Seal Bushing: Brass
5. Actuator Stem and Retaining Pin Mounting Plate: Brass
6. Main Valve Stem Cap (separate and removable) Actuator Pin: SST

Model X129 Limit Switch Assembly OPTIONAL


• Stainless Steel
3 • Double Pole Double Throw (DPDT)
'G'
1 (see • Up to 4 Switches
below)
• Explosion proof housing
4
• Nema 6/6P rating
2

76 2016.1
MODEL X129
LIMIT SWITCH INDICATOR

SIZES & HEIGHTS


Dimension G is the height added to the valve by the assembly.

106-X129 Dimension ‘G’ Height


Sizes (inches) 2 in 2-1/2 in 3 in 4 in 6 in 8 in 10 in 12 in 14 in 16 in 20 in 24 in 36 in
Sizes (mm) 50 mm 65 mm 80 mm 100 mm 150 mm 200 mm 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm 900 mm
Height (inches) 7 7 7 7.38 7.75 8.75 9.63 9.63 9.63 11.06 12.25 12.25 15.25
Height (mm) 178 178 178 187 197 222 245 245 245 281 311 311 387

206-X129 Dimension ‘G’ Height


Sizes (inches) 3 in 4 in 6 in 8 in 10 in 12 in 16 in 18 in 20 in 24 in 28 in 30 in 32 in 36 in
Sizes (mm) 80 mm 100 mm 150 mm 200 mm 250 mm 300 mm 400 mm 450 mm 500 mm 600 mm 700 mm 750 mm 800 mm 900 mm
Height (inches) 7 7 7.38 7.75 8.75 9.63 9.63 11.06 11.06 11.06 12.25 12.25 12.25 12.25
Height (mm) 178 178 187 197 222 245 245 281 281 281 311 311 311 311

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering
instructions.
Additionally, include the following information for this
product:
1. Quantity of Limit Switches
2. Actuation positions
3. SPDT or DPDT contacts
4. Optional explosion proof housing
Note:
• For retrofit, please include serial number
• This may be included as standard with some
products

2016.1 77
MAIN VALVES - OPTIONS

MODEL 106-AC
ANTI-CAVITATION CONTROL VALVE

KEY FEATURES
• Solves cavitation problems
• Controls variable flows and vibration
• Reduces noise significantly
• Every valve optimized for actual operating conditions

PRODUCT OVERVIEW
The 106-AC series control valve solves cavitation problems by
taking the pressure drop in two stages and at higher pressure
drops allowing and containing cavitation inside the Recovery
Chamber. Reduced velocity out of the Recovery Chamber
prevents cavitation and reduces noise and vibration.

PRODUCT LINE DRAWING


1. Removable Stem Cap
2. ASTM A536 Ductile Iron Construction
3. 316 Stainless Steel Stem
4. Buna-N / EPDM Diaphragm
5. Buna-N / EPDM Resilient Disc
6. 316 Stainless Steel Seat
7. Cavitation Recovery Chamber - AISI 316
8. NSF 61 Fusion Bonded Epoxy Coating

78 2016.1
MODEL 106-AC
ANTI-CAVITATION CONTROL VALVE

TYPICAL APPLICATION SELECTION


Pressure Reducing: 6 in / 150 mm Singer model
PRESSURE REDUCING 106-PR-AC, ANSI Class 150 flange, range 10 – 80 psi /
Your application has a maximum continuous design 0.7 bar – 5.5 bar, set at 30 psi / 2 bar
flow of 1200 USGPM (76 l/s) and a minimum of 100
USGPM (6.3 l/s). Inlet pressure ranges from 200 psi
(13.8 bar) at maximum flow to 250 psi (17.2 bar) at
minimum flow. You need a relatively constant outlet
pressure of 30 psi (2 bar). There is a possibility of
demand for 2000 USGPM (130 l/s).

Large elevation head cre-


Singer model 106-PR-AC ating 200 - 250 psi / 13.8
- 17.2 bar

Distribution to users at a relatively constant 30 psi / 2.06 bar over


the flow range of 100 to 1,200 USGPM / 6.3 to 75.7 L/s

5. Referring to Graph 106-415 on page 82 or 239,


SELECTION AND SIZING intersection of minimum pressure drop of
1. Referring to page 240 Cavitation Chart, 250 psi 170 psi (11.7 bar) and maximum flow of
(17.2 bar) to 30 psi (2 bar) is deep in the severe 1200 GPM (76 l/s) is right on the line for 4”
cavitation zone. Anti-Cavitation valve is required. (100mm) valve. If a capacity of 2000 GPM (130 l/s)
2. There seems to be no reason for the downstream is required, a 6” valve would be selected.
pressure to go sub-atmospheric. Application is 6. Referring to pages 14 to 19, maximum
OK. recommended continuous flow for a 4” 106
3. 200 psi (13.8 bar) is 80% of 250 psi (17.2 bar). valve is 800 GPM (50 l/s). If it is expected that
Application is OK. flows of more than 800 GPM (50 l/s) will take
place more than intermittently, a 6” valve
4. 220 psi (15 bar) pressure drop is acceptable for should be selected. Referring to page
an outlet pressure of 30 psi (2 bar). 100, 100 GPM (6.3 l/s) is higher than minimum
recommended flow for 4” (100mm) or 6”
(150mm) pressure reducing valve.

2016.1 79
MODEL 106-AC
ANTI-CAVITATION CONTROL VALVE

TYPICAL APPLICATION
CONTINUOUS SUSTAINING
Your application requires the discharge pressure of
a fixed speed pump to be limited to a pressure that
keeps the pressure in an old distribution zone to a
maximum of 110 psi (7.6 bar). The pump is designed
for 1200 USGPM (76 l/s) at 140 psi (9.6 bar) Shut-off
head is 450 ft (137 m) or 195 psi (13.5 bar). The zone Tank Supply
is 55 ft (34m) above the pump outlet. Insufficient
to meet Peak
Demand
Old distribution zone to users:
Maximum 110 psi / 7.6 bar

Singer model 106-RPS-AC set at 132 psi / 9.1 bar

SELECTION AND SIZING


To keep the pressure in the distribution zone to a 5. Referring to Graph 106-415 on page 82 or 239,
maximum of 110 psi (7.6 bar), we must limit the intersection of 132 psi (9.1 bar) and 1200 GPM (76 l/s)
pressure on the pump discharge header to 110 psi is above the line for 4” (100mm) valve but below the
(7.6 bar) + 50 ft (34m) or 132 psi (9.1 bar). line for 6” (150mm) line. Select a 6” (150mm) valve.
1. Referring to Cavitation Chart on page 240, 132 psi 6. Referring to pages 11 to 19, recommended
(9.1 bar) is in the very severe cavitation zone. Anti- continuous flow for 6” (150mm) valve is 1800 GPM
Cavitation valve is a must. (114 l/s). 6” (150mm) valve is OK. Referring to page
120, minimum recommended flow for 6” (150mm)
2. It is likely that sub-atmospheric pressure will
106-RPS pressure sustaining valve is 20 USGPM (1.3
develop on the outlet of the valve. A vacuum breaker
l/s) for flat diaphragm valve and 1 USGPM (0.06 l/s)
is required.
for rolling diaphragm valve. Low flow should not be a
3. Pressure drop is constant. Application is OK. problem.
4. 132 psi (9.1 bar) to atmosphere is OK.

80 2016.1
MODEL 106-AC
ANTI-CAVITATION CONTROL VALVE

106-AC VALVE SIZES AND MATERIALS


Valve Materials
Standard Optional
Available Sizes Threaded Flanged -
Globe 1 in to 3 in (25-80 mm) 1-1/2 in to 36 in (40-900 mm) -
Valve Components
1. Valve Body, Cover 65-45-12 Ductile Iron 316 Stainless Steel (limited sizes)
2. Seat Ring 316 Stainless Steel -
4. Stem 316 Stainless Steel -
5. Stem Nut B16 Brass 316 Stainless Steel
6. Spring 316 Stainless Steel -
7. Guide Bushings B16 Brass or SAE 660 Bronze AISI 316 Stainless Steel
8. Diaphragm EPDM Buna-N / Viton (limited sizes)
9. Resilient Disc EPDM Buna-N / Viton (limited sizes)
10. Coating NSF61 Approved Fusion Bonded Epoxy - Thickness 10-14 mils (250-350 microns) Consult factory
11. Fasteners 18-8 Stainless Steel 316 Stainless Steel
12. Anti-Cavitation Cage 316 Stainless Steel -

5. Refer to Graph 106-415 on pages 82 or 239.


SELECTION AND SIZING Locate intersection of minimum pressure
1. Check Cavitation Chart on page 240. If the drop on the horizontal axis and maximum flow
intersection of inlet pressure and outlet pressure on the vertical axis. Select the next valve size
is inside the cavitation zone, Anti-Cavitation above this intersection.
valve is recommended. As a guide, if the pressure
6. Refer to pages 14 to 19 for recommended
drop is more that 2/3 of the inlet pressure,
limitations for Continuous and Intermittent flows
cavitation may occur.
and description of standard valve for minimum
2. If there is any possibility that the outlet pressure stable flow where applicable.
can be sub-atmospheric even occasionally,
consult with Singer Valve or one of our
representatives for a possible solution. ORDERING INSTRUCTIONS
3. If the pressure drop varies more than 25%, Refer to page 244 for the order form and ordering
consult Singer Valve or one of our instructions.
representatives for a solution. Additionally, include the following information for this
4. If the outlet pressure is less than 20 psi (1.38 bar), product:
pressure drop should be limited to 200 psi Inlet / outlet pressure range
(13.8 bar) for continuous service.
Minimum / maximum differential pressure
Minimum / maximum flow rate

2016.1 81
MODEL 106-AC
ANTI-CAVITATION CONTROL VALVE

Flow vs. Pressure Differential


Model 106 Series (PG-AC, PGX-AC, PT-AC, PGM-AC) – Full Port, Globe Body, Flat / Rolling Diaphragm
Anti-Cavitation Valve Curve 106-415 (1 in / 25 mm – 36 in / 900 mm)
l/s USGPM
9000 150000 36" - 900 mm
8000
7000
100000
6000 90000
5000 80000
70000
4000 60000
50000
3000
2500 40000 24" - 600 mm
2000
• Differential Pressures over 300 psi / 21 bar, check with Singer Valve.

30000

1500
20" - 500 mm
20000
• Solid line and below suitable for continuous service.

16" - 400 mm
1000 15000
900
800
700 12" - 300 mm
10000
600 9000
8000 10" - 250 mm
500
7000
400 6000 8" - 200 mm
5000

Valve Sizes
300
4000
Flow

200 3000
6" - 150 mm
150
2000

100 1500
90
4" - 100 mm
80
70
1000
60 900
50 800 3" - 80 mm
700
40 600
2.5" - 65 mm
500
30
400

20 300
2" - 50 mm
15
200
1.50" - 40 mm
10 150 1.25" - 32 mm
9.0 1" - 25 mm
8.0
7.0
100
90
80
70
60
50
40 50 60 70 80 90 100 150 200 300 psi
30 40 50 60 70 80 10 15 20 bar
Pressure Differential

82 2016.1
MODEL 106-AC
ANTI-CAVITATION CONTROL VALVE

VALVE DATA (US UNITS)


Size DWG Standard Flat Diaphragm System
Inches REF ANSI 1 in 1-1/4 in 1-1/2 in 2 in 2-1/2 in 3 in 4 in 6 in 8 in
Globe Dimensions All figures shown in inches unless otherwise stated
Lay Length A FNPT 6.75 6.75 6.75 9.38 11.00 13.50 - - -
Centerline to Bottom D FNPT 2.50 2.50 2.50 2.75 3.38 3.68 - - -
Lay Length A 150F - - 8.50 9.38 11.00 12.00 15.00 20.00 25.38
Centerline to Bottom D 150F - - 2.75 3.00 3.50 3.75 4.60 5.60 7.88
Lay Length A 300F - - 9.00 10.00 11.63 13.25 15.63 21.00 26.38
Centerline to Bottom D 300F - - 3.25 3.25 3.75 4.13 5.09 6.34 7.88
Common Dimensions (Globe)
Width C 4.88 4.88 6.13 6.50 8.19 9.25 10.88 16.75 21.63
Height (To Stem Cap) Globe E 4.38 4.38 4.38 4.75 7.50 8.00 9.15 11.75 14.91
Body Port Tapping FNPT 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 1/2
Stem Cap Plug MNPT 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Cover Port Tapping FNPT 3/8 3/8 3/8 3/8 3/8 3/8 3/8 1/2 1/2
Valve Stroke 9/16 9/16 9/16 9/16 15/16 1-1/8 1-7/16 1-11/16 2-7/8
Displaced Bonnet Volume (Gallons) 0.007 0.007 0.007 0.02 0.07 0.09 0.20 0.56 1.67
Approximate Shipping Weight (Lbs) 25 25 25 45 80 125 250 400 700
Capacities Please consult Singer Valve
Maximum Pressure Ratings (Ductile Only)
PSI1 FNPT 400 400 400 400 400 400 - - -
PSI 150F - - - 250 250 250 250 250 250
PSI1 300F - - - 400 400 400 400 400 400
Maximum Temperature
Fahrenheit 180º 180º 180º 180º 180º 180º 180º 180º 180º
Valves rated and stamped 400 psi as standard. Valves rated and stamped 600 psi on request.
1

Globe Style
Flat Diaphragm

B'E'
Flow
'E' SINGER

'E' SINGER
ansi@QUP Flange
Flow
ansi@QUP
sQPVpgMac
'C' Diameter C
QPVpg
D'F' D
'D' Dim
'F' 'D'
S I NG E R
Flange Feet
'A' 'B' A for Safety and Standard Opposite
A Convenience

See pilot system information, page 207.


For additional Engineering notes, see page 242.

2016.1 83
MODEL 106-AC
ANTI-CAVITATION CONTROL VALVE

VALVE DATA (US UNITS)


Size DWG Standard Rolling Diaphragm System
Inches REF ANSI 6 in 8 in 10 in 12 in 16 in 20 in 24 in 36 in
Globe Dimensions All figures shown in inches unless otherwise stated
Lay Length A FNPT - - - - - - - -
Centerline to Bottom D FNPT - - - - - - - -
Lay Length A 150F 20.00 25.38 29.75 34.00 41.38 52.00 61.50 76.00
Centerline to Bottom D 150F 5.60 7.63 8.25 9.62 12.13 14.43 17.13 23.50
Lay Length A 300F 21.00 26.38 31.13 35.50 43.50 53.62 63.25 78.00
Centerline to Bottom D 300F 6.34 7.88 9.00 10.38 13.13 15.75 19.65 25.50
Common Dimensions (Globe & Angle)
Width C 12.75 16.09 18.00 21.25 27.06 35.00 49.68 64.50
Height (To Stem Cap) Globe E 15.43 20.19 22.13 23.75 30.31 35.50 45.75 61.00
Body Port Tapping FNPT 3/8 1/2 3/4 3/4 3/4 3/4 3/4 1
Stem Cap Plug MNPT 3/8 3/8 3/4 3/4 3/4 3/4 3/4 1
Cover Port Tapping FNPT 1/2 1/2 3/4 3/4 3/4 3/4 3/4 1
Valve Stroke 1-11/16 2-7/8 3-1/4 3-3/4 4-3/4 5-9/16 6 9
Displaced Bonnet Volume (Gallons) 0.5 1.0 1.5 2.3 6.8 9.0 14.8 43.0
Approximate Shipping Weight (Lbs) 360 660 900 1400 2400 3450 5300 13500
Flow Capacities Please consult Singer Valve
Maximum Pressure Ratings (Ductile Only)
PSI1 FNPT - - - - - - - -
PSI 150F 250 250 250 250 250 250 250 250
PSI1 300F 400 400 400 400 400 400 400 400
Maximum Temperature
Fahrenheit 180º 180º 180º 180º 180º 180º 180º 180º
Valves rated and stamped 400 psi as standard. Valves rated and stamped 600 psi on request.
1

Globe Style
Rolling Diaphragm

E
'E'
B Flow
'E'
SINGER
SINGER 'E' Flange
Flow
ansi@QUP
sQPVpgMac 'C' Diameter
ansi@QUP
'F' C
QPVpg
D D 'D' Dim
'F' 'D'
S I NG E R Flange Feet
'A' 'B' for Safety and Standard Opposite
A A Convenience

See pilot system information, page 207.


For additional Engineering notes, see page 242.

84 2016.1
MODEL 106-AC
ANTI-CAVITATION CONTROL VALVE

VALVE DATA (METRIC UNITS)


Size DWG Standard Flat Diaphragm System
MM REF ANSI 25 mm 32 mm 40 mm 50 mm 65 mm 80 mm 100 mm 150 mm 200 mm
Globe Dimensions All figures shown in mm unless otherwise stated
Lay Length A FNPT 171 171 171 238 279 343 - - -
Centerline to Bottom D FNPT 64 64 64 70 86 93 - - -
Lay Length A 150F - - 216 238 279 305 381 508 645
Centerline to Bottom D 150F - - 70 76 89 95 117 142 200
Lay Length A 300F - - 229 254 295 337 397 533 670
Centerline to Bottom D 300F - - 83 83 95 105 129 161 200
Common Dimensions (Globe)
Width C 124 124 156 165 208 235 276 425 549
Height (To Stem Cap) Globe E 111 111 111 121 191 203 232 298 379
Body Port Tapping FNPT Inches 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 1/2
Stem Cap Plug MNPT Inches 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Cover Port Tapping FNPT Inches 3/8 3/8 3/8 3/8 3/8 3/8 3/8 1/2 1/2
Valve Stroke mm 14 14 14 14 25 29 37 43 73
Displaced Bonnet Volume (Litres) 0.03 0.03 0.03 0.1 0.3 0.3 0.8 2.1 6.3
Approximate Shipping Weight (Kilograms) 11 11 11 20 36 57 113 181 317
Capacities Please consult Singer Valve
Maximum Pressure Ratings (Ductile Only)
Bar1 FNPT 27.6 27.6 27.6 27.6 27.6 27.6 - - -
Bar 150F - - - 17 17 17 17 17 17
Bar1 300F - - - 27.6 27.6 27.6 27.6 27.6 27.6
Maximum Temperature
Celcius 82º 82º 82º 82º 82º 82º 82º 82º 82º
1
Valves rated and stamped 27.6 bar as standard. Valves rated and stamped 41 bar on request

Globe Style
Flat Diaphragm

B'E'
Flow
'E' SINGER

'E' SINGER
ansi@QUP Flange
Flow
ansi@QUP
sQPVpgMac
'C' Diameter C
QPVpg
D'F' D
'D' Dim
'F' 'D'
S I NG E R
Flange Feet
'A' 'B' A for Safety and Standard Opposite
A Convenience

See pilot system information, page 207.


For additional Engineering notes, see page 242.

2016.1 85
MODEL 106-AC
ANTI-CAVITATION CONTROL VALVE

VALVE DATA (METRIC UNITS)


Size DWG Standard Rolling Diaphragm System
mm REF ANSI 150 mm 200 mm 250 mm 300 mm 400 mm 500 mm 600 mm 900 mm
Globe Dimensions All figures shown in mm unless otherwise stated.
Lay Length A FNPT - - - - - - - -
Centerline to Bottom D FNPT - - - - - - - -
Lay Length A 150F 508 645 756 864 1051 1321 1562 1930
Centerline to Bottom D 150F 142 194 210 244 308 367 435 597
Lay Length A 300F 533 670 791 902 1105 1362 1607 1981
Centerline to Bottom D 300F 161 200 229 264 334 400 499 648
Common Dimensions (Globe)
Width C 324 409 460 540 687 889 1262 1422
Height (To Stem Cap) Globe E 346 455 562 603 770 902 1162 1550
Body Port Tapping FNPT Inches 3/8 1/2 3/4 3/4 3/4 3/4 3/4 1
Stem Cap Plug MNPT Inches 3/8 3/8 3/4 3/4 3/4 3/4 3/4 1
Cover Port Tapping FNPT Inches 1/2 1/2 3/4 3/4 3/4 3/4 3/4 1
Valve Stroke mm 43 73 83 95 120 141 150 229
Displaced Bonnet Volume (Litres) 2 4 6 9 26 34 56 163
Approximate Shipping Weight (Kilograms) 163 300 408 635 1089 1565 2268 6124
Flow Capacities Please consult Singer Valve
Maximum Pressure Ratings (Ductile Only)
Bar* FNPT - - - - - - - -
Bar 150F 17 17 17 17 17 17 17 17
Bar* 300F 27.6 27.6 27.6 27.6 27.6 27.6 27.6 27.6
Maximum Temperature
Celcius 82º 82º 82º 82º 82º 82º 82º 82º
Valves rated and stamped 400 psi as standard. Valves rated and stamped 600 psi on request.
1

Globe Style
Rolling Diaphragm

E
'E'
B Flow
'E'
SINGER
SINGER 'E' Flange
Flow
ansi@QUP
sQPVpgMac 'C' Diameter
ansi@QUP
'F' C
QPVpg
D D 'D' Dim
'F' 'D'
S I NG E R Flange Feet
'A' 'B' for Safety and Standard Opposite
A A Convenience

See pilot system information, page 207.


For additional Engineering notes, see page 242.

86 2016.1
MODEL 106-AC
ANTI-CAVITATION CONTROL VALVE

AC VALVE DATA (ISO UNITS)


Size DWG Standard Flat Diaphragm System
MM REF ISO 25 mm 32 mm 40 mm 50 mm 65 mm 80 mm 100 mm 150 mm 200 mm
Globe Dimensions All figures shown in mm unless otherwise stated
Lay Length A BSPT 171 171 171 238 279 343 - - -
Centerline to Bottom D BSPT 64 64 64 70 86 93 - - -
Lay Length A PN10 / PN16 - - 229 238 279 318 381 508 645
Centerline to Bottom D PN10 / PN16 - - 83 76 89 100 117 142 200
Lay Length A PN25 / PN40 - - 229 238 295 318 397 533 670
Centerline to Bottom D PN25 / PN40 - - 83 76 89 100 129 161 200
Common Dimensions (Globe)
Width C 124 124 156 152 208 235 276 425 549
Height (To Stem Cap) Globe E 111 111 111 121 191 203 232 298 379
Body Port Tapping FNPT Inches 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 1/2
Stem Cap Plug MNPT Inches 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Cover Port Tapping FNPT Inches 3/8 3/8 3/8 3/8 3/8 3/8 3/8 1/2 1/2
Valve Stroke mm 14 14 14 14 25 29 37 43 73
Displaced Bonnet Volume (Litres) 0.03 0.03 0.03 0.1 0.3 0.3 0.8 2.1 6.3
Approximate Shipping Weight (Kilograms) 11 11 11 20 36 57 113 181 317
Capacities Please consult Singer Valve
Maximum Pressure Ratings (Ductile Only)
Bar BSPT 27.6 27.6 27.6 27.6 27.6 27.6 - - -
Bar PN16 - - - 16 16 16 16 16 16
Bar PN25 - - - 25 25 25 25 25 25
Maximum Temperature
Celcius 82º 82º 82º 82º 82º 82º 82º 82º 82º
Valves rated and stamped 27.6 bar as standard. Valves rated and stamped 41 bar on request
*

Globe Style
Flat Diaphragm

B'E'
Flow
'E' SINGER

'E' SINGER
ansi@QUP Flange
Flow
ansi@QUP
sQPVpgMac
'C' Diameter C
QPVpg
D'F' D
'D' Dim
'F' 'D'
S I NG E R
Flange Feet
'A' 'B' A for Safety and Standard Opposite
A Convenience

See pilot system information, page 207.


For additional Engineering notes, see page 242.

2016.1 87
MODEL 106-AC
ANTI-CAVITATION CONTROL VALVE

AC VALVE DATA (ISO UNITS)


Size DWG Standard Rolling Diaphragm System
mm REF ISO 150 mm 200 mm 250 mm 300 mm 400 mm 500 mm 600 mm 900 mm
Globe Dimensions All figures shown in mm unless otherwise stated
Lay Length A BSPT - - - - - - - -
Centerline to Bottom D BSPT - - - - - - - -
Lay Length A PN10 / PN16 508 645 756 864 1051 1321 1562 1930
Centerline to Bottom D PN10 / PN16 142 200 210 244 308 367 435 597
Lay Length A PN25 / PN40 533 670 791 902 1105 1362 1607 1981
Centerline to Bottom D PN25 / PN40 161 200 229 264 334 400 499 648
Common Dimensions (Globe)
Width C 324 409 460 540 687 889 1262 1422
Height (To Stem Cap) Globe E 346 455 562 603 770 902 1162 1550
Body Port Tapping FNPT Inches 3/8 1/2 3/4 3/4 3/4 3/4 3/4 1
Stem Cap Plug MNPT Inches 3/8 3/8 3/4 3/4 3/4 3/4 3/4 1
Cover Port Tapping FNPT Inches 1/2 1/2 3/4 3/4 3/4 3/4 3/4 1
Valve Stroke mm 43 73 83 95 120 141 150 229
Displaced Bonnet Volume (Litres) 2 4 6 9 26 34 56 163
Approximate Shipping Weight (Kilograms) 163 300 408 635 1089 1565 2268 6124
Flow Capacities Please consult Singer Valve
Maximum Pressure Ratings (Ductile Only)
Bar BSPT - - - - - - - -
Bar PN16 16 16 16 16 16 16 16 16
Bar PN25 25 25 25 25 25 25 25 25
Maximum Temperature
Celcius 82º 82º 82º 82º 82º 82º 82º 82º

Globe Style
Rolling Diaphragm

E
'E'
B Flow
'E'
SINGER
SINGER 'E' Flange
Flow
ansi@QUP
sQPVpgMac 'C' Diameter
ansi@QUP
'F' C
QPVpg
D D 'D' Dim
'F' 'D'
S I NG E R Flange Feet
'A' 'B' for Safety and Standard Opposite
A A Convenience

See pilot system information, page 207.


For additional Engineering notes, see page 242.

88 2016.1
When faced with extreme pressures or anything in between, our pressure
reducing valves maintain a uniform downstream pressure. Regardless of the
problem, regardless of the application, our valves perform under pressure.

Want extra security? That’s a job for our PR-SM, a PR valve fitted with an
integral back-up system. Need to reduce high nighttime pressure? Our
Pressure/Flow Control valve works wonders. Do you have a tricky application
without a reliable solution in sight? Contact us. We welcome the challenge.

Pressure Reducing Valves


PRESSURE REDUCING

MODELS 106-PR-SM / 206-PR-SM


PRESSURE REDUCING CONTROL VALVE WITH INTEGRAL BACK-UP

KEY FEATURES
• Ideal for applications where failure is not an option
• Includes a back-up system to protect against diaphragm
or pilot failure
• Reduces requirement for immediate service
• Provides downstream surge protection

PRODUCT OVERVIEW
The 106-PR-SM and 206-PR-SM series control valves Should the primary pilot system and / or main
are engineered to be used anywhere pressure valve fail to control the downstream pressure, the
reducing valve failure is unacceptable. These valves independent back-up pilot system will begin to
have a second and independent operating system operate. It controls the pressure above the diaphragm
superimposed upon the standard primary system. in the second operating chamber. The back-up pilot
With the assurance of a back-up system, maintenance is set slightly higher than the primary pilot. The forces
schedules may be extended as pressures will continue now operating in the top chamber assume control
to be controlled even in the event of failure with the of the inner valve assembly and maintain pressure
primary system. reducing control. During back-up operation only,
Under normal pressure reducing conditions, the there is a small (1 USGPM / 0.063 L/s) continuous
primary pilot senses the downstream pressure discharge that should be taken to drain.
through a connection at the valve outlet. Under The secondary pilot continually senses the
flowing conditions, the pilot reacts to small changes downstream pressure. Should there be a rapid rise in
in pressure to control the valve position by downstream pressure for any reason, the secondary
modulating the pressure above the diaphragm in the pilot will respond quickly, and will pressurize the top
lower operating chamber. The downstream pressure chamber. This will compliment the primary pressure
is maintained virtually steady at the pilot set-point reducing controls and provide faster response.
that is adjustable.

90 2016.1
MODELS 106-PR-SM / 206-PR-SM
PRESSURE REDUCING CONTROL VALVE WITH INTEGRAL BACK-UP
TYPICAL APPLICATION

Low flow PR-SM and / or service


by-pass during maintenance periods
Relatively steady lower
downstream pressure

Manual by-pass

High pressure
supply main
Singer Valve model 106-PR-SM or 206-PR-SM

SCHEMATIC DRAWING STANDARD MATERIALS


1. Main Valve - 106-PGM or 206-PGM Standard materials for pilot system components are:
2, 8, 9. Isolation Valves - (2A, 2B, 8, 9A, 9B) ASTM B-62 bronze or ASTM B-16 brass
3. Strainer - 40 mesh stainless steel screen AISI 303 / 316 stainless steel trim
(3A, 3B)
4. Model 81-RP Pilot (Back-up) SELECTION SUMMARY
5, 11. Fixed Restriction 1. Select the valve series and size with sufficient
6. Model 26 Flow Stabilizer capacity
(sizes 8 in / 200 mm 106, 10 in / 250 mm 206 2. Check the operating flow against valve minimum.
and smaller is included)
3. Provide a smaller valve in parallel to facilitate
7. Model 160 PR Pilot (Primary) maintenance and low flow capability, if required.
10. Limit Switch Assembly - SPDT - Optional 4. If the outlet pressure is less than 35% of the inlet
pressure, check for cavitation.
5. Ensure that the valve and flange working
pressure rating exceeds the maximum operating
pressure.

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering
instructions.
Additionally, include the following information for this
product:
1. Single chamber (106) or (206)
2. Outlet pressure range

Schematic A-7697D

2016.1 91
MODELS 106-PR-SM / 206-PR-SM
PRESSURE REDUCING CONTROL VALVE WITH INTEGRAL BACK-UP

Flow Capacity
106-PR-SM
(See 106-PGM in Main Valve section for other valve data)
Size (inches) 3 in 4 in 6 in 8 in 10 in 12 in 14 in 16 in 20 in 24 in
80 250 350
Size (mm) 100 mm 150 mm 200 mm 300 mm 400 mm 500 mm 600 mm
mm mm mm
Minimum (USGPM) Flat Diaphragm 5 10 20 40 - - - - - -

Minimum (USGPM) Rolling Diaphragm - - 1 1 3 3 3 3 10 10

Minimum (L/s) Flat Diaphragm 0.32 0.63 1.26 2.52 - - - - - -

Minimum (L/s) Rolling Diaphragm - - 0.06 0.06 0.19 0.19 0.19 0.19 0.63 0.63

Maximum Continuous (USGPM) 460 800 1800 3100 4900 7000 8500 11000 17500 25000

Maximum Continuous (L/s) 29 50 114 196 309 442 536 694 1104 1577

Flow Capacity
206-PR-SM
(See 206-PGM in Main Valve section for other valve data)
Size (inches) 4 in 6 in 8 in 10 in 12 in 16 in 18 in 20 in 24 x 16 in 24 x 20 in 28 in 30 in 32 in 36 in
300 450 600 x 400 600 x 500
Size (mm) 100 mm 150 mm 200 mm 250 mm 400 mm 500 mm 700 mm 750 mm 800 mm 900 mm
mm mm mm mm
Minimum (USGPM) Flat Diaphragm 5 10 20 40 - - - - - - - - - -

Minimum (USGPM) Rolling Diaphragm - - - - 3 3 3 3 3 3 10 10 10 10

Minimum (L/s) Flat Diaphragm 0.32 0.63 1.26 2.52 - - - - - - - - - -

Minimum (L/s) Rolling Diaphragm - - - - 0.19 0.19 0.19 0.19 0.19 0.19 0.63 0.63 0.63 0.63

Maximum Continuous (USGPM) 580 1025 2300 4100 6400 9230 16500 16500 16500 21700 33600 33650 33700 33800

Maximum Continuous (L/s) 37 65 145 259 404 582 1041 1041 1041 1370 2120 2123 2126 2132

92 2016.1
PRESSURE REDUCING

MODELS 106-PFC / 206-PFC


PRESSURE FLOW CONTROL (MODULATION) VALVE

KEY FEATURES
• Reduces downstream pressure when demand is low to
reduce leakage and pipe breaks.
• Compensates for pressure loss in the pipe to keep a fairly
constant pressure at a distant point. This reduces the
pressure during low flow in most of the system.
• Simple to set-up and adjust.
• Maximum pressure increase can be limited by simple
adjustment.
• Pressure increase is adjustable.

PRODUCT OVERVIEW TYPICAL APPLICATION


The 106-PFC / 206-PFC Pressure Flow Control Valve An orifice plate immediately downstream of the PFC
is a pressure reducing valve with a special (Patented) Control Valve produces 3 psi / 0.2 bar pressure drop,
pilot that increases downstream pressure as flow at maximum flow. This pressure differential is applied
increases. to each side of an actuating diaphragm which is
The PFC valve controls the downstream pressure as a connected to the yoke of the pressure reducing pilot.
function of flow. This increased downstream pressure Increasing the differential raises the pilot setting and
compensates partially for pipe friction and therefore raises downstream pressure to maintain virtually
maintains a relatively constant pressure at some steady pressure on a critical distance user.
remote location. The PFC valve will deliver consistent
performance without any electrical components and
is not affected by flooding. The valve can be used
wherever a standard PRV is installed.
Please note that the downstream (controlled)
pressure increases from low flow to selected
Main Supply
maximum flow but reduces at flows higher than Remote users
the selected maximum. This is due to the increased PFC
pressure drop of the orifice plate. If this reduction of
the controlled pressure past the design maximum
flow is a problem, contact Singer Valve or your Singer
Valve representative for an engineered solution.

Critical User
(extended distance)

2016.1 93
MODELS 106-PFC / 206-PFC
PRESSURE FLOW CONTROL (MODULATION) VALVE

SCHEMATIC DRAWING SELECTION SUMMARY


1. Main Valve - 106-PG or 206-PG 1. The Singer model 106-PFC / 206-PFC should be
2. Isolation Valve (2A, 2B, 2C) sized as a normal pressure reducing valve. Refer
to section 106-PR / 206-PR, page 96, for size
3. Strainer - 40 Mesh selection and main pilot spring ranges.
4. Model 26 Flow Stabilizer / Opening speed Control 2. Installation is the same as a standard pressure
• Standard on 8” (200 mm) 106 / 10” (250 mm) reducing valve. See section 106-PR / 206-PR,
206 and smaller page 96.
• Optional on 10” (250 mm) 106 / 12” (300 mm) 3. Maximum pressure increase over base setting:
206 and larger 35 psi / 2.4 bar.
5. Fixed Restriction 4. For correct application provide
6. Model 160-PFC Pressure/Flow Control Pilot i. Maximum & minimum inlet pressure and
base (minimum) outlet pressure setting
7. Orifice housing and plate
ii. Maximum & minimum flow rates
8. Test Valve
iii. Pressure increase _____ psi / _____ bar at
9. Speed Control
_____ USGPM / L/s
10. Fixed Restriction
iv. Maximum pressure increase at any flow
11. PIP Adjustment - Model 852-B _____ psi / _____ bar.
5. Ensure the flange ratings exceed the maximum
working pressure.

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering
instructions.
Additionally, include the following information for this
product:
1. Single chamber (106) or (206)
2. Outlet pressure range
3. Minimum / maximum flow rate
4. Pressure increase at high flow

Schematic A-8270D12

94 2016.1
MODELS 106-PFC / 206-PFC
PRESSURE FLOW CONTROL (MODULATION) VALVE

Flow Capacity
106-PFC
(See 106-PG in Main Valve section for other valve data)

Size (inches) 3 in 4 in 6 in 8 in 10 in 12 in 14 in 16 in 20 in 24 in 36 in
80 100 150 200 250 300 350 400 500 600 900
Size (mm)
mm mm mm mm mm mm mm mm mm mm mm
Minimum Continuous (USGPM) Flat Diaphragm 5 10 20 40 - - - - - - -

Minimum Continuous (USGPM) Rolling Diaphragm - - 1 1 3 3 3 3 10 10 20

Minimum Continuous (L/s) Flat Diaphragm 0.3 0.6 1.3 2.5 - - - - - - -

Minimum Continuous (L/s) Rolling Diaphragm - - 0.1 0.1 0.2 0.2 0.2 0.2 0.6 0.6 0.6

Maximum Continuous (USGPM) 460 800 1800 3100 4900 7000 8500 11000 17500 25800 55470

Maximum Continuous (L/s) 29 50 114 196 309 442 536 694 1104 1628 3500

Flow Capacity
206-PFC
(See 206-PG in Main Valve section for other valve data)

24 x
24 x 6
Size (inches) 4 in 6 in 8 in 10 in 12 in 16 in 18 in 20 in 20 28 in 30 in 32 in 36 in 40 in
in
in
600 x 600 x
100 150 200 250 300 400 450 500 700 750 800 900 1000
Size (mm) 400 500
mm mm mm mm mm mm mm mm mm mm mm mm mm
mm mm
Minimum Continuous (USGPM) Flat Diaphragm 5 10 20 40 - - - - - - - - - - -

Minimum Continuous (USGPM) Rolling Diaphragm - - - - 3 3 3 3 3 3 10 10 10 10 20

Minimum Continuous (L/s) Flat Diaphragm 0.3 0.6 1.3 2.5 - - - - - - - - - - -

Minimum Continuous (L/s) Rolling Diaphragm - - - - 0.2 0.2 0.2 0.2 0.2 0.2 0.6 0.6 0.6 0.6 0.6

Maximum Continuous (USGPM) 580 1025 2300 4100 6400 9230 16500 16500 16500 21700 33600 33650 33700 33800 62000

Maximum Continuous (L/s) 37 65 145 259 404 582 1040 1040 1040 1370 2120 2123 2126 2132 3912

2016.1 95
PRESSURE REDUCING

MODELS 106-PR / 206-PR


PRESSURE REDUCING VALVE

KEY FEATURES
• Ideal for maintaining accurate downstream pressure
• Responds quickly and effectively

PRODUCT OVERVIEW
The 106-PR and 206-PR series pressure reducing valves are based on the
106-PG or 206-PG main valves.
The pilot valves sense the downstream pressure through a connection
at the valve outlet. Under flowing conditions, the pilot reacts to small
changes in pressure to control the valve position by modulating the
pressure above the diaphragm. The downstream pressure is maintained
virtually steady at the pilot set-point.
In typical pressure reducing applications, the standard port model 206-PR
is often the best selection.

TYPICAL APPLICATION
Smaller PR valve
High pressure for low flow, if required
supply main
Lower relatively steady pressure
supply to users

Main Valve Model 106-PR


or Model 206-PR
Manual by-pass line

Note: The smaller PR valve by-passing the main valve helps


control low flows and provides service during maintenance.
It should be set 3 – 5 psi / 0.2 – 0.35 bar higher than the
larger valve setting.

Singer Valve single rolling diaphragm technology 6 in / 150


mm and larger have extremely precise control, even at low
flows, making smaller by-pass valves unnecessary except for
possible bypass during maintenance.

96 2016.1
MODELS 106-PR / 206-PR
PRESSURE REDUCING VALVE

SCHEMATIC DRAWING
1. Main Valve - 106-PG or 206-PG
STANDARD MATERIALS
Standard materials for pilot system components are:
2. Isolation Valve - standard 4 in / 100 mm
and larger • ASTM B62 bronze or ASTM B16 brass
3. Strainer - standard 4 in / 100 mm and larger • AISI 303 / 316 stainless steel trim
4*. Model 26 Flow Stabilizer / Opening Speed Control • Buna-N / EPDM diaphragm and seals
• Standard on valves 8 in / 200 mm 106,
10” / 250 mm 206 and smaller
SELECTION SUMMARY
5. Fixed Restriction
1. Select the valve series and size with sufficient
6. Isolation Valve - standard 4 in / 100 mm capacity
and larger
2. Check the operating flow against valve minimum.
7. Model 160 pilot
3. If the outlet pressure is less than 35% of the inlet
• Specify for 5 to 50 psi / 0.35 to 3.5 bar,
pressure, check for cavitation.
10 to 80 psi / 0.70 to 5.5 bar,
4. Ensure that the flange rating exceeds the
20 to 200 psi / 1.38 to 13.8 bar, maximum operating pressure.
100 to 300 psi / 6.9 to 20.7 bar.
8. Isolation Valve - standard all sizes ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering
Note: SRD shown is available for 6” 106-PG and larger. instructions.
Additionally, include the following information for this
product:
1. 106 or 206
2. Pilot range

INLET

Schematic A-0306C

2016.1 97
MODELS 106-PR / 206-PR
PRESSURE REDUCING VALVE

Flow Capacity
106-PR
(See 106-PG in Main Valve section for other valve data)
Size (inches) 1/2 in 3/4 in 1 in 1-1/4 in 1-1/2 in 2 in 2-1/2 in 3 in 4 in

Size (mm) 15 mm 19 mm 25 mm 32 mm 40 mm 50 mm 65 mm 80 mm 100 mm

Minimum (USGPM) Flat Diaphragm 1 1 1 1 1 5 5 5 10

Minimum (L/s) Flat Diaphragm 0.1 0.1 0.1 0.1 0.1 0.3 0.3 0.3 0.6

Maximum Continuous (USGPM) 12 19 49 93 125 210 300 460 800

Maximum Continuous (L/s) 0.8 1 3 6 8 13 19 29 50

Flow Capacity
106-PR
(See 106-PG in Main Valve section for other valve data)

Size (inches) 6 in 8 in 10 in 12 in 14 in 16 in 20 in 24 in 36 in

Size (mm) 150 mm 200 mm 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm 900 mm

Minimum (USGPM) Flat Diaphragm 20 40 - - - - - - -

Minimum (USGPM) Rolling Diaphragm 1 1 3 3 3 3 10 10 20

Minimum (L/s) Flat Diaphragm 1.3 2.5 - - - - - - -

Minimum (L/s) Rolling Diaphragm 0.1 0.1 0.2 0.2 0.2 0.2 0.6 0.6 1.3

Maximum Continuous (USGPM) 1800 3100 4900 7000 8500 11000 17500 25800 55470

Maximum Continuous (L/s) 114 196 309 442 536 694 1104 1628 3500

Flow Capacity
206-PR
(See 206-PG in Main Valve section for other valve data)
Size (inches) 3 in 4 in 6 in 8 in 10 in 12 in 16 in 18 in 20 in

Size (mm) 80 mm 100 mm 150 mm 200 mm 250 mm 300 mm 400 mm 450 mm 500 mm

Minimum (USGPM) Flat Diaphragm 5 5 10 20 40 - - - -

Minimum (USGPM) Rolling Diaphragm - - - - - 3 3 3 3

Minimum (L/s) Flat Diaphragm 0.3 0.3 0.6 1.3 2.5 - - - -

Minimum (L/s) Rolling Diaphragm - - - - - 0.2 0.2 0.2 0.2

Maximum Continuous (USGPM) 300 580 1025 2300 4100 6400 9230 16500 16500

Maximum Continuous (L/s) 19 37 65 145 260 404 582 1040 1040

Flow Capacity
206-PR
(See 206-PG in Main Valve section for other valve data)

Size (inches) 24 x 16 in 24 x 20 in 28 in 30 in 32 in 36 in 40 in

Size (mm) 600 x 400 mm 600 x 500 mm 700 mm 750 mm 800 mm 900 mm 1000 mm

Minimum (USGPM) Rolling Diaphram 3 3 10 10 10 10 20

Minimum (L/s) Rolling Diaphragm 0.2 0.2 0.6 0.6 0.6 0.6 0.6

Maximum Continuous (USGPM) 16500 21700 33600 33650 33700 33800 62000

Maximum Continuous (L/s) 1041 1370 2120 2123 2126 2132 3912

98 2016.1
PRESSURE REDUCING

MODELS 106-PR-48 / 206-PR-48


PRESSURE REDUCING VALVE WITH LOW FLOW BY-PASS

KEY FEATURES
• Maintains stable flow right down to zero
• Precise and reliable pressure setting
• By-pass piped in parallel to reduce space requirements

PRODUCT OVERVIEW TYPICAL APPLICATION


The 106-PR-48 and 206-PR-48 series pressure
reducing valves with low flow by-pass are based on
the 106-PG or 206-PG main valve. In addition, a direct
acting pressure reducing valve is piped in parallel, Lower, relatively steady
using the main valve back port connections. pressure supply to users
The pilot valve senses the downstream pressure
through a connection at the main valve outlet. Under
flowing conditions, the pilot reacts to small changes Manual by-pass line
in pressure to control the main valve position by
modulating the pressure above the diaphragm. The High pressure
downstream pressure is maintained virtually steady at supply main
the pilot set-point. Direct acting by-pass
The by-pass valve is set 5 psi / 0.35 bar higher than
the main valve. Under low flow conditions, the Main Valve
main PR valve closes and the by-pass stays open, Model 106-PR-48 or model 206-PR-48
controlling the pressure at very low flows without seat
chatter.
In typical pressure reducing applications, the standard
port Model 206-PR-48 is often the best selection.

2016.1 99
MODELS 106-PR-48 / 206-PR-48
PRESSURE REDUCING VALVE WITH LOW FLOW BY-PASS

SCHEMATIC DRAWING STANDARD MATERIALS


1. Main Valve - 106-PG or 206-PG Standard materials for pilot system components are:
2. Isolation Valves - standard 4 in / 100 mm • ASTM B-62 bronze or ASTM B-16 brass;
and larger • AISI 303 / 316 stainless steel trim
3. Strainer - standard 4 in / 100 mm and larger
4.* Model 26 Flow Stabilizer / Opening Speed Control
• Standard on valves 8 in / 200 mm 106,
SELECTION SUMMARY
10” / 250 mm 206 and smaller 1. Select the main PR valve series and size with
sufficient capacity. Note that large Singer valves
5. Fixed Restriction (6 in / 150 mm 106 & 12 in / 300 mm 206 and up)
6. Isolation Valves - standard 4 in / 100 mm have extremely precise control, even at low flows,
and larger making by-pass valves generally unnecessary for
7. Model 160 Pilot stable control, due to Single Rolling Diaphragm
technology. Model PR-48 valves are usually
• Specify for 5 to 50 psi / 0.35 to 3.5 bar, required only for valve sizes with significant
10 to 80 psi / 0.70 to 5.5 bar, minimum flows. (3 in / 80 mm to 8 in / 200 mm
20 to 200 psi / 1.38 to 13.8 bar, 106 and 4 in / 100 mm to 10 in / 250 mm 206).
100 to 300 psi / 6.9 to 20.7 bar.
2. If the outlet pressure is less than 35% of the inlet
8. Isolation Valve - standard all sizes pressure, check for cavitation.
9. Direct Acting by-pass - range 30 – 145 psi / 2.07 – 3. Ensure that the flange rating exceeds the
10 bar maximum operating pressure.
10. Isolation Valve - standard all sizes 4. Consider using a manual main by-pass line
if necessary for service during maintenance
periods

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering
instructions.
Additionally, include the following information for this
product:
1. Single chamber (106) or (206)
2. Pilot range

Schematic A-8063E

100 2016.1
MODELS 106-PR-48 / 206-PR-48
PRESSURE REDUCING VALVE WITH LOW FLOW BY-PASS

Flow Capacity
106-PR-48
(See 106-PG in Main Valve section for other valve data)

Size (inches) 3 in 4 in 6 in 8 in

Size (mm) 80 mm 100 mm 150 mm 200 mm

Minimum (USGPM) Flat Diaphragm 0 0 0 0

Minimum (L/s) Flat Diaphragm 0 0 0 0

Maximum Continuous (USGPM) Flat Diaphragm 460 800 1800 3100

Maximum Continuous (L/s) Flat Diaphragm 29 50 114 196

Flow Capacity
206-PR-48
(See 206-PG in Main Valve section for other valve data)

Size (inches) 4 in 6 in 8 in 10 in

Size (mm) 100 mm 150 mm 200 mm 250 mm

Minimum (USGPM) Flat Diaphragm 0 0 0 0

Minimum (L/s) Flat Diaphragm 0 0 0 0

Maximum Continuous (USGPM) Flat Diaphragm 580 1025 2300 4100

Maximum Continuous (L/s) Flat Diaphragm 37 65 145 259

2016.1 101
PRESSURE REDUCING

MODELS 106-PR-C / 206-PR-C


PRESSURE REDUCING AND CHECK VALVE

KEY FEATURES
• Excellent low flow stability
• Drip-tight closing on return flow
• Easily and precisely set downstream pressure

PRODUCT OVERVIEW
The 106-PR-C and 206-PR-C pressure reducing and The pilot check valves direct downstream pressure
check valves are based on the 106-PG or 206-PG main above the diaphragm to close the valve when the
control valve. system pressures reverse (when the downstream
The pilot valve senses the downstream pressure pressure is higher than the upstream).
through a connection at the valve outlet. Under In typical pressure reducing applications, the standard
flowing conditions, the pilot reacts to small changes in port model 206-PR-C is often the best selection.
pressure to control the valve position by modulating
the pressure above the diaphragm. The downstream
pressure is maintained relatively steady at the pilot
set-point.

Smaller PR-C valve


TYPICAL APPLICATION for low flow, if required

Lower relatively steady


pressure supply to users.
High Pressure Supply Main Check against reverse flow
should pressures reverse.

Main Valve
Model 106-PR-C
or 206-PR-C
Manual
by-pass line

102 2016.1
MODELS 106-PR-C / 206-PR-C
PRESSURE REDUCING AND CHECK VALVE

SCHEMATIC DRAWING STANDARD MATERIALS


1. Main Valve - 106-PG or 206-PG Standard materials for pilot system components are:
2. Isolation Valve - standard 4 in / 100 mm • ASTM B62 bronze or ASTM B16 brass
and larger • AISI 303/316 stainless steel trim
3. Strainer - standard 4 in / 100 mm and larger • Buna-N / EPDM diaphragm and seals
4.* Model 26 Flow Stabilizer / Opening
Speed Control
• Standard on valves 8 in / 200 mm 106, SELECTION SUMMARY
10” / 250 mm 206 and smaller 1. Select the valve series and size with sufficient
5. Fixed Restriction capacity
6. Isolation Valve - standard 4 in / 100 mm 2. Check the operating flow against valve
and larger minimum
7. Model 160 pilot 3. Provide a smaller valve in parallel to facilitate
maintenance and low flow capability, if required.
•S
 pecify for 5 to 50 psi / 0.35 to 3.5 bar,
10 to 80 psi / 0.70 to 5.5 bar, 4. If the outlet pressure is less than 35% of the inlet
20 to 200 psi / 1.38 to 13.8 bar, pressure, check for cavitation.
100 to 300 psi / 6.9 to 20.7 bar. 5. Ensure that the flange rating exceeds the
8. Isolation Valve - standard all sizes maximum operating pressure.
9. Check valve - model 10
10. Check valve - model 10 ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering
instructions.
Additionally, include the following information for this
product:
1. Full port (106) or standard port (206)
2. Pilot range

Schematic A-0309A

2016.1 103
MODELS 106-PR-C / 206-PR-C
PRESSURE REDUCING AND CHECK VALVE

106-PR-C Flow Capacity (See 106-PG in Main Valve section for other valve data)

Size (inches) 1/2 in 3/4 in 1 in 1-1/4 in 1-1/2 in 2 in 2-1/2 in 3 in 4 in

Size (mm) 15 mm 19 mm 25 mm 32 mm 40 mm 50 mm 65 mm 80 mm 100 mm

Minimum (USGPM) Flat Diaphragm 1 1 1 1 1 5 5 5 10

Minimum (L/s) Flat Diaphragm 0.1 0.1 0.1 0.1 0.1 0.3 0.3 0.3 0.6

Maximum Continuous (USGPM) 12 19 49 93 125 210 300 460 800

Maximum Continuous (L/s) 0.8 1 3 6 8 13 19 29 50

106-PR-C Flow Capacity (See 106-PG in Main Valve section for other valve data)

Size (inches) 6 in 8 in 10 in 12 in 14 in 16 in 20 in 24 in 36 in

Size (mm) 150 mm 200 mm 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm 900 mm

Minimum (USGPM) Flat Diaphragm 20 40 - - - - - - -

Minimum (USGPM) Rolling Diaphragm 1 1 3 3 3 3 10 10 20

Minimum (L/s) Flat Diaphragm 1.3 2.5 - - - - - - -

Minimum (L/s) Rolling Diaphragm 0.1 0.1 0.2 0.2 0.2 0.2 0.6 0.6 1.3

Maximum Continuous (USGPM) 1800 3100 4900 7000 8500 11000 17500 25800 55470

Maximum Continuous (L/s) 114 196 309 442 536 694 1104 1628 3500

206-PR-C Flow Capacity (See 206-PG in Main Valve section for other valve data)

Size (inches) 3 in 4 in 6 in 8 in 10 in 12 in 16 in 18 in 20 in

Size (mm) 80 mm 100 mm 150 mm 200 mm 250 mm 300 mm 400 mm 450 mm 500 mm

Minimum (USGPM) Flat Diaphragm 5 5 10 20 40 - - - -

Minimum (USGPM) Rolling Diaphragm - - - - - 3 3 3 3

Minimum (L/s) Flat Diaphragm 0.3 0.3 0.6 1.3 2.5 - - - -

Minimum (L/s) Rolling Diaphragm - - - - - 0.2 0.2 0.2 0.2

Maximum Continuous (USGPM) 300 580 1025 2300 4100 6400 9230 16500 16500

Maximum Continuous (L/s) 19 37 65 145 260 404 582 1040 1040

206-PR-C Flow Capacity (See 206-PG in Main Valve section for other valve data)

Size (inches) 24 x 16 in 24 x 20 in 28 in 30 in 32 in 36 in 40 in

Size (mm) 600 x 400 mm 600 x 500 mm 700 mm 750 mm 800 mm 900 mm 1000 mm

Minimum (USGPM) Rolling Diaphragm 3 3 10 10 10 10 20

Minimum (L/s) Rolling Diaphragm 0.2 0.2 0.6 0.6 0.6 0.6 1.3

Maximum Continuous (USGPM) 16500 21700 33600 33650 33700 33800 62000

Maximum Continuous (L/s) 1041 1370 2120 2123 2126 2132 3912

104 2016.1
PRESSURE REDUCING

MODELS 106-PR-R / 206-PR-R


PRESSURE REDUCING AND PRESSURE SUSTAINING VALVE

KEY FEATURES
• Excellent low flow stability
• Ensures minimum upstream pressure
• Easily and precisely set downstream pressure

PRODUCT OVERVIEW
The 106-PR-R and 206-PR-R pressure reducing and Should high demand cause the inlet pressure to fall
pressure sustaining valves are based on the to the 81-RP pilot setting, the upstream pressure has
106-PG or 206-PG main valve with the addition of the priority and the valve will modulate to prevent the
sustaining pilot 81-RP and pressure reducing 160 PR. upstream pressures from dropping below the
set-point.
Provided the upstream pressure setting is satisfied,
the 81-RP pilot is kept open, permitting the valve to When the valve is modulating to sustain upstream
be controlled by the 160 pilot. The 160 pilot senses pressure above the minimum 81-RP pilot set-point,
downstream pressure and under flowing conditions, the downstream 160 PR pilot may try to open the
it reacts to small changes in pressure to control the valve to maintain its set-point, but upstream has
valve position by modulating the pressure above priority and downstream pressures will fall below
the diaphragm. expectations.
In typical applications, the standard port model 206-
Reservoir PR-R is often the best selection.
TYPICAL APPLICATION tower
Important user assured
minimum pressure
Altitude Valve Vault

Smaller PR valve for low flow and /


Flow or service during maintenance

Throttles main valve if


the inlet pressure falls Main model 106-PR-R
to the assured or model 206-PR-R
minimum pressure

Throttles main valve to maintain a relatively


steady lower downstream pressure, if the Manual by-pass line
minimum upstream pressure is satisfied.

2016.1 105
MODELS 106-PR-R / 206-PR-R
PRESSURE REDUCING AND PRESSURE SUSTAINING VALVE

SCHEMATIC DRAWING STANDARD MATERIALS


1. Main Valve - 106-PG or 206-PG Standard materials for pilot system components are:
2. Isolation Valve - standard 4 in / 100 mm ASTM B62 bronze or ASTM B16 brass
and larger AISI 303/316 stainless trim
3. Strainer - standard 4 in / 100 mm and larger
4. Model 26 Flow Stabilizer / Opening Speed Control
• Standard on valves 8 in / 200 mm 106,
SELECTION SUMMARY
10” / 250 mm 206 and smaller 1. Select the valve series and size with sufficient
capacity
5. Fixed Restriction
2. Check the operating flow against valve minimum.
6. Isolation Valve - standard 4 in / 100 mm
and larger 3. If the outlet pressure is less than 35% of the inlet
pressure, check for cavitation.
7. Model 160 PR pilot
4. Ensure that the flange rating exceeds the
•S
 pecify for 5 to 50 psi / 0.35 to 3.5 bar, maximum operating pressure.
10 to 80 psi / 0.70 to 5.5 bar,
20 to 200 psi / 1.38 to 13.8 bar,
100 to 300 psi / 6.9 to 20.7 bar. ORDERING INSTRUCTIONS
8. Isolation Valve - standard all sizes Refer to page 244 for the order form and ordering
9. Model 81-RP pilot - specify for 5 to 50 psi / 0.35 to instructions.
3.5 bar; 10 to 80 psi / 0.7 to 5.5 bar; 100 to 300 psi Additionally, include the following information for this
/ 6.9 to 20.7 bar; 20 to 200 psi / 1.38 to 13.8 bar product:
standard.
1. Single chamber (106) or (206)
2. Pilot ranges

Schematic A-0332C

106 2016.1
MODELS 106-PR-R / 206-PR-R
PRESSURE REDUCING AND PRESSURE SUSTAINING VALVE

Flow Capacity
106-PR-R
(See 106-PG in Main Valve section for other valve data)
Size (inches) 1/2 in 3/4 in 1 in 1-1/4 in 1-1/2 in 2 in 2-1/2 in 3 in 4 in

Size (mm) 15 mm 19 mm 25 mm 32 mm 40 mm 50 mm 65 mm 80 mm 100 mm

Minimum (USGPM) Flat Diaphragm 1 1 1 1 1 5 5 5 10

Minimum (L/s) Flat Diaphragm 0.1 0.1 0.1 0.1 0.1 0.3 0.3 0.3 0.6

Maximum Continuous (USGPM) 12 19 49 93 125 210 300 460 800

Maximum Continuous (L/s) 0.8 1 3 6 8 13 19 29 50

Flow Capacity
106-PR-R
(See 106-PG in Main Valve section for other valve data)

Size (inches) 6 in 8 in 10 in 12 in 14 in 16 in 20 in 24 in 36 in

Size (mm) 150 mm 200 mm 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm 900 mm

Minimum (USGPM) Flat Diaphragm 20 40 - - - - - - -

Minimum (USGPM) Rolling Diaphragm 1 1 3 3 3 3 10 10 20

Minimum (L/s) Flat Diaphragm 1.3 2.5 - - - - - - -

Minimum (L/s) Rolling Diaphragm 0.1 0.1 0.2 0.2 0.2 0.2 0.6 0.6 1.3

Maximum Continuous (USGPM) 1800 3100 4900 7000 8500 11000 17500 25800 55470

Maximum Continuous (L/s) 114 196 309 442 536 694 1104 1628 3500

Flow Capacity
206-PR-R
(See 206-PG in Main Valve section for other valve data)
Size (inches) 3 in 4 in 6 in 8 in 10 in 12 in 16 in 18 in 20 in

Size (mm) 80 mm 100 mm 150 mm 200 mm 250 mm 300 mm 400 mm 450 mm 500 mm

Minimum (USGPM) Flat Diaphragm 5 5 10 20 40 - - - -

Minimum (USGPM) Rolling Diaphragm - - - - - 3 3 3 3

Minimum (L/s) Flat Diaphragm 0.3 0.3 0.6 1.3 2.5 - - - -

Minimum (L/s) Rolling Diaphragm - - - - - 0.2 0.2 0.2 0.2

Maximum Continuous (USGPM) 300 580 1025 2300 4100 6400 9230 16500 16500
Maximum Continuous (L/s) 19 37 65 145 260 404 582 1040 1040

Flow Capacity
206-PR-R
(See 206-PG in Main Valve section for other valve data)

Size (inches) 24 x 16 in 24 x 20 in 28 in 30 in 32 in 36 in 40 in

Size (mm) 600 mm 600 mm 700 mm 750 mm 800 mm 900 mm 1000 mm

Minimum (USGPM) Rolling Diaphragm 3 3 10 10 10 10 20

Minimum (L/s) Rolling Diaphragm 0.2 0.2 0.6 0.6 0.6 0.6 1.3

Maximum Continuous (USGPM) 16500 21700 33600 33650 33700 33800 62000

Maximum Continuous (L/s) 1040 1370 2120 2123 2126 2132 3912

2016.1 107
PRESSURE REDUCING

MODELS 106-PR-S / 206-PR-S


PRESSURE REDUCING VALVE WITH DOWNSTREAM SURGE PROTECTION

KEY FEATURES
• Excellent low flow stability
• Automatically reduces downstream surges during
sudden demand reductions
• Easily and precisely set downstream pressure

PRODUCT OVERVIEW
The 106-PR-S and 206-PR-S pressure reducing valves modulating the pressure above the diaphragm. The
with downstream surge control are based on the 106- downstream pressure is maintained relatively steady
PG or 206-PG main valve. at the pilot set-point.
Pressure reducing pilot valve senses the downstream The surge pilot senses the downstream pressure. If
pressure through a connection at the valve outlet. the pressure rises above the pressure reducing pilot
Under flowing conditions, the pilot reacts to small setting and reaches the surge pilot setting, the surge
changes in pressure to control the valve position by pilot opens in order to close the main valve rapidly.

TYPICAL APPLICATION High pressure supply main

Smaller PR-S valve


for low flow, if required

Main Valve
Model 106-PR-S
or 206-PR-S

Manual by-pass line

Lower relatively steady pressure


supply to users. Closes rapidly if
demand is suddenly reduced.

108 2016.1
MODELS 106-PR-S / 206-PR-S
PRESSURE REDUCING VALVE WITH DOWNSTREAM SURGE PROTECTION

SCHEMATIC DRAWING STANDARD MATERIALS


1. Main Valve 106-PG or 206-PG Standard materials for pilot system components are:
2. Isolation Valve - standard 4 in / 100 mm ASTM B62 bronze or ASTM B16 brass
and larger AISI 303/316 stainless steel trim
3. Strainer - standard 4 in / 100 mm and larger Buna-N / EPDM diaphragm and seals
4. Model 26 Flow Stabilizer
(sizes 8 in / 200 mm 106, 10 in / 250 mm 206
and smaller) SELECTION SUMMARY
5. Fixed Restriction 1. Select the valve series and size with sufficient
capacity
6. Isolation Valve - standard 4 in / 100 mm
and larger 2. Check the operating flow against valve minimum.
7. Model 160 pilot 3. Surge pilot typically set 5 psi / 0.35 bar higher
than reducing pilot.
•S
 pecify for 5 to 50 psi / 0.35 to 3.5 bar,
10 to 80 psi / 0.70 to 5.5 bar, 4. If the outlet pressure is less than 35% of the inlet
20 to 200 psi / 1.38 to 13.8 bar, pressure, check for cavitation.
100 to 300 psi / 6.9 to 20.7 bar. 5. Ensure that the flange rating exceeds the
8. Isolation Valve - standard all sizes maximum operating pressure.
9. Model 81 RP Surge Pilot - standard spring 20 to
200 psi / 1.38 to 13.8 bar -specify for 5 to 50 psi / ORDERING INSTRUCTIONS
0.35 to 3.5 bar, 10 to 80 psi / 0.7 to 5.5 bar, 100 to
Refer to page 244 for the order form and ordering
300 psi / 6.9 to 20.7 bar.
instructions.
Additionally, include the following information for this
product:
1. Single chamber (106) or (206)
2. Pilot ranges

A-0336D--PR-S V2.dxf

Schematic A-0336D

2016.1 109
MODELS 106-PR-R / 206-PR-R
PRESSURE REDUCING AND PRESSURE SUSTAINING VALVE

106-PR-S Flow Capacity (See 106-PG in Main Valve section for other valve data)

Size (inches) 1/2 in 3/4 in 1 in 1-1/4 in 1-1/2 in 2 in 2-1/2 in 3 in 4 in

Size (mm) 15 mm 19 mm 25 mm 32 mm 40 mm 50 mm 65 mm 80 mm 100 mm

Minimum (USGPM) Flat Diaphragm 1 1 1 1 1 5 5 5 10

Minimum (L/s) Flat Diaphragm 0.1 0.1 0.1 0.1 0.1 0.3 0.3 0.3 0.6

Maximum Continuous (USGPM) 12 19 49 93 125 210 300 460 800

Maximum Continuous (L/s) 0.8 1 3 6 8 13 19 29 50

106-PR-S Flow Capacity (See 106-PG in Main Valve section for other valve data)

Size (inches) 6 in 8 in 10 in 12 in 14 in 16 in 20 in 24 in 36 in

Size (mm) 150 mm 200 mm 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm 900 mm

Minimum (USGPM) Flat Diaphragm 20 40 - - - - - - -

Minimum (USGPM) Rolling Diaphragm 1 1 3 3 3 3 10 10 20

Minimum (L/s) Flat Diaphragm 1.3 2.5 - - - - - - -

Minimum (L/s) Rolling Diaphragm 0.1 0.1 0.2 0.2 0.2 0.2 0.6 0.6 1.3

Maximum Continuous (USGPM) 1800 3100 4900 7000 8500 11000 17500 25800 55470

Maximum Continuous (L/s) 114 196 309 442 536 694 1104 1628 3500

206-PR-S Flow Capacity (See 206-PG in Main Valve section for other valve data)

Size (inches) 3 in 4 in 6 in 8 in 10 in 12 in 16 in 18 in 20 in

Size (mm) 80 mm 100 mm 150 mm 200 mm 250 mm 300 mm 400 mm 450 mm 500 mm

Minimum (USGPM) Flat Diaphragm 5 5 10 20 40 - - - -

Minimum (USGPM) Rolling Diaphragm - - - - - 3 3 3 3

Minimum (L/s) Flat Diaphragm 0.3 0.3 0.6 1.3 2.5 - - - -

Minimum (L/s) Rolling Diaphragm - - - - - 0.2 0.2 0.2 0.2

Maximum Continuous (USGPM) 300 580 1025 2300 4100 6400 9230 16500 16500

Maximum Continuous (L/s) 19 37 65 145 259 404 582 1041 1041

206-PR-S Flow Capacity (See 206-PG in Main Valve section for other valve data)

Size (inches) 24 x 16 in 24 x 20 in 28 in 30 in 32 in 36 in 40 in

Size (mm) 600 mm 600 mm 700 mm 750 mm 800 mm 900 mm 1000 mm

Minimum (USGPM) Rolling Diaphragm 3 3 10 10 10 10 20

Minimum (L/s) Rolling Diaphragm 0.2 0.2 0.6 0.6 0.6 0.6 1.3

Maximum Continuous (USGPM) 16500 21700 33600 33650 33700 33800 62000

Maximum Continuous (L/s) 1040 1370 2120 2123 2126 2132 3912

110 2016.1
PRESSURE REDUCING

MODELS 106-PR-SC / 206-PR-SC


PRESSURE REDUCING VALVE WITH SOLENOID SHUT-OFF

KEY FEATURES
• Excellent low flow stability
• Fast-acting solenoid override
• Operates as normally open or closed
• Easily and precisely set downstream pressure

PRODUCT OVERVIEW
The 106-PR-SC and 206-PR-SC pressure reducing The solenoid shut-off / override interrupts the PR
valves with solenoid shut-off are based on the 106-PG function to close off the main valve. The valve is
or 206-PG main valve. available as either normally open where the solenoid
The pilot valve senses the downstream pressure is energized to close the main valve or as normally
through a connection at the valve outlet. Under closed where the solenoid is de-energized to close the
flowing conditions, the pilot reacts to small changes in main valve.
pressure to control the valve position by modulating
the pressure above the diaphragm. The downstream
pressure is maintained relatively steady at the pilot
set-point.

TYPICAL APPLICATION
Electrical supply required
High pressure supply main

Flow

Main Valve model 106-PR-SC


or 206-PR-SC
Manual by-pass line

Lower relatively steady pressure supply


to users, on demand; i.e. timed irrigation

2016.1 111
MODELS 106-PR-SC / 206-PR-SC
PRESSURE REDUCING VALVE WITH SOLENOID SHUT-OFF

SCHEMATIC DRAWING STANDARD MATERIALS


1. Main Valve - 106-PG or 206-PG Standard materials for pilot system components are:
2. Isolation Valve - standard 4 in / 100 mm) • ASTM B62 bronze or ASTM B16 brass
and larger • AISI 303/316 stainless steel trim
3. Strainer - standard 4 in / 100 mm and larger • Buna-N / EPDM diaphragm and seals
4.* Model 26 Flow Stabilizer
• Standard on valves 8 in / 200 mm 106,
10” / 250 mm 206 and smaller SELECTION SUMMARY
5. Fixed Restriction 1. Select the valve series and size with sufficient
capacity.
6. Isolation Valve - standard 4 in / 100 mm
and larger 2. Check the operating flow against valve minimum.
7. Model 160 pilot 3. If the outlet pressure is less than 35% of the inlet
pressure, check for cavitation.
•S
 pecify for 5 to 50 psi / 0.35 to 3.5 bar,
10 to 80 psi / 0.70 to 5.5 bar, 4. Determine whether operation is energized or de-
20 to 200 psi / 1.38 to 13.8 bar, energized to close the main valve.
100 to 300 psi / 6.9 to 20.7 bar. 5. Select the voltage (120VAC standard) for solenoid
8. Isolation Valve - standard all sizes and advise maximum operating differential
pressure.
9. Closing Speed Control - model 852-B
6. Ensure that the flange rating exceeds the
10. Solenoid Valve - 2 way maximum operating pressure.

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering
instructions.
Additionally, include the following information for this
product:
1. Single chamber (106) or (206)
2. Pilot range

Schematic A-0335C

112 2016.1
MODELS 106-PR-SC / 206-PR-SC
PRESSURE REDUCING VALVE WITH SOLENOID SHUT-OFF

106-PR-SC Flow Capacity (See 106-PG in Main Valve section for other valve data)

Size (inches) 1/2 in 3/4 in 1 in 1-1/4 in 1-1/2 in 2 in 2-1/2 in 3 in 4 in

Size (mm) 15 mm 19 mm 25 mm 32 mm 40 mm 50 mm 65 mm 80 mm 100 mm

Minimum (USGPM) Flat Diaphragm 1 1 1 1 1 5 5 5 10

Minimum (L/s) Flat Diaphragm 0.1 0.1 0.1 0.1 0.1 0.3 0.3 0.3 0.6

Maximum Continuous (USGPM) 12 19 49 93 125 210 300 460 800

Maximum Continuous (L/s) 0.8 1 3 6 8 13 19 29 50

106-PR-SC Flow Capacity (See 106-PG in Main Valve section for other valve data)

Size (inches) 6 in 8 in 10 in 12 in 14 in 16 in 20 in 24 in 36 in

Size (mm) 150 mm 200 mm 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm 900 mm

Minimum (USGPM) Flat Diaphragm 20 40 - - - - - - -

Minimum (USGPM) Rolling Diaphragm 1 1 3 3 3 3 10 10 20

Minimum (L/s) Flat Diaphragm 1.3 2.5 - - - - - - -

Minimum (L/s) Rolling Diaphragm 0.1 0.1 0.2 0.2 0.2 0.2 0.6 0.6 1.3

Maximum Continuous (USGPM) 1800 3100 4900 7000 8500 11000 17500 25800 55470

Maximum Continuous (L/s) 114 196 309 442 536 694 1104 1628 3500

206-PR-SC Flow Capacity (See 206-PG in Main Valve section for other valve data)

Size (inches) 3 in 4 in 6 in 8 in 10 in 12 in 16 in 18 in 20 in

Size (mm) 80 mm 100 mm 150 mm 200 mm 250 mm 300 mm 400 mm 450 mm 500 mm

Minimum (USGPM) Flat Diaphragm 5 5 10 20 40 - - - -

Minimum (USGPM) Rolling Diaphragm - - - - - 3 3 3 3

Minimum (L/s) Flat Diaphragm 0.3 0.3 0.6 1.3 2.5 - - - -

Minimum (L/s) Rolling Diaphragm - - - - - 0.19 0.19 0.19 0.19

Maximum Continuous (USGPM) 300 580 1025 2300 4100 6400 9230 16500 16500

Maximum Continuous (L/s) 19 37 65 145 260 404 582 1040 1040

206-PR-SC Flow Capacity (See 206-PG in Main Valve section for other valve data)

Size (inches) 24 x 16 in 24 x 20 in 28 in 30 in 32 in 36 in 40 in

Size (mm) 600 x 400 mm 600 x 500 mm 700 mm 750 mm 800 mm 900 mm 1000 mm

Minimum (USGPM) Rolling Diaphragm 3 3 10 10 10 10 20

Minimum (L/s) Rolling Diaphragm 0.2 0.2 0.6 0.6 0.6 0.6 1.3

Maximum Continuous (USGPM) 16500 21700 33600 33650 33700 33800 62000

Maximum Continuous (L/s) 1040 1370 2120 2123 2126 2132 3912

2016.1 113
PRESSURE REDUCING

MODEL 106-2PR-630 / 206-2PR-630


PRESSURE MANAGEMENT VALVE

KEY FEATURES
• Valve switches between high and low pressure pilots
based on flow rate.
• Pressure reducing pilots independently adjustable to
suit the desired downstream pressure.
• Orifice is upstream of control valve so downstream
pressure setting is unaffected by flow.
• Standard components completely submersible - no
electrical power required.
• Simple field retrofit is possible using the paddle style
orifice plate.

PRODUCT OVERVIEW
The Singer 106/206-2PR-630 Pressure Management demand. High flow demand or fire flow will cause
Valve is a simple package to save water loss and the differential pilot to automatically switch control
money. It meets system needs by providing higher from the low pressure to the higher pressure pilot.
pressure when called for 24/7 and reduced pressure The action is then reversed when flow demand falls
to save water leakage (and money) at all other times. below the differential pilot set point.valve position by
An orifice with a low pressure drop 1.0 psi, (0.07 Bar) modulating the pressure above the diaphragm. The
is installed upstream of a standard pressure reducing downstream pressure is maintained relatively steady
valve fitted with an extra pressure reducing pilot and at the pilot set-point.
a sensitive differential pilot which switches between
2 pressure reducing pilots to suit the system flow

TYPICAL APPLICATION
Orifice plate installed Low flow by-pass
ahead of both Reducing Pressure Reducing
Valves Valve (Optional)

Main High Flow Pressure


Management Valve

Manual by-pass line

114 2016.1
MODEL 106-2PR-630/206-2PR-630
PRESSURE MANAGEMENT VALVE

SCHEMATIC DRAWING BENEFITS


1. Main Valve - 106-PG or 206-PG • Substantially reduces water loss (non-revenue
2. Isolation Valve water) due to leakage

3. Strainer - 40 mesh • Decreases downstream pipe bursts and associated


repair costs
4*. Model 26 Flow Stabilizer / Opening Speed
Control • Allows constant reliable pressure to users,
minimizing over pressure at off peak (flow)
5. Closing Speed Control periods.
6. Fixed Restriction
7. Differential Pilot – Normal Closed – Model 630-
RPD
SELECTION SUMMARY
8. Pressure Reducing Pilot – Model 160 Higher
Setting 1. Sizes: 4 - 12” (100mm -300mm) for other sizes
please consult factory
9. Pressure Reducing Pilot – Model 160 Lower
Setting 2. Pressures: Minimum pressure of 29 psi (2 Bar)
at valve inlet, (Consult factory for lower pressure
10. Orifice Plate – Paddle style standard – optional applications).
with housing
3. Differential required across Orifice plate: 1.45 – 2
psi (0.1 – 0.14 Bar)
An optional differential gauge is available to indicate 4. Fire Flow: if fire flow is greater than twice the
flow and simplify adjustment. normal high flow rate set point, please consult factory.

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering
instructions.
Additionally, include the following information for this
product:
1. Single chamber (106) or (206)
2. Pilot range

Schematic A-10496A2

2016.1 115
You can count on Singer valves to do exactly what they are designed to do.
Relieve pressure. Sustain differential pressure. Anticipate surges. Plus more.
Whatever their purpose, our valves give you the protection your application
needs. What a relief.

Relief / Sustaining / Surge


RELIEF / SUSTAINING / SURGE

MODELS 106-RPS / 206-RPS


PRESSURE RELIEF VALVE

KEY FEATURES
• Limits system pressure by relieving excess flow
• Quick opening relief
• Easily adjustable pressure setting

PRODUCT OVERVIEW
The 106-RPS and 206-RPS pressure relief valves are adjustable speed, when the pressure returns below
based on the 106-PG and 206-PG main valves. the set-point. The upstream pressure is limited to the
The 81-RP pilot senses the upstream pressure pilot set-point.
through a connection to the valve inlet. The valve and
pilot remain closed until the inlet pressure exceeds
the pilot setting. The valve opens rapidly to relieve
damaging overpressure and closes smoothly at an

TYPICAL APPLICATION
The Singer model 106-RPS and
Isolation valve 206-RPS pressure relief valve is
Singer model 106-BPC
Booster Pump Control Valve mounted in a tee off the pressure
with Internal Drop Check pipe or header.

Booster
pump

Singer model
106-RPS pressure relief
Pump suction Line

118 2016.1
MODELS 106-RPS / 206-RPS
PRESSURE RELIEF VALVE

SCHEMATIC DRAWING STANDARD MATERIALS


1. Main Valve - 106-PG or 206-PG Standard materials for pilot system components are:
2. Isolation Valve - standard 4 in / 100 mm • ASTM B62 bronze or ASTM B16 brass
and larger • AISI 303/316 stainless steel trim
3. Strainer - standard 4 in / 100 mm and larger • Buna-N / EPDM diaphragm and seals
4. Fixed Restriction- 1/8 in / 3.2 mm
5. Model 852-B Closing Speed Control SELECTION SUMMARY
6. Model 81-RP pilot 1. Select the valve with sufficient capacity using the
•S
 pecify for 5 to 50 psi / 0.35 to 3.5 bar, available pressure drop across the valve.
10 to 80 psi / 0.70 to 5.5 bar, 2. Usually operating in the momentary “M” service
20 to 200 psi / 1.38 to 13.8 bar, range.
100 to 300 psi / 6.9 to 20.7 bar.
3. For extended or continuous relief applications,
7. Isolation Valve - standard 4 in / 100 mm use model 106-RPS-AC: Pressure Relief with Anti-
and larger Cavitation Cages.
8. Isolation Valve - standard all sizes 4. Ensure that the maximum working pressure
rating for the valve and for the flanges exceeds
the maximum operating pressure.
5. Select a standard globe style body or the optional
angle style body.

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering
instructions.
Additionally, include the following information for this
product:
1. Single chamber (106) or (206)
2. Relief pressure range
3. Outlet pressure

Schematic A-0423F

2016.1 119
MODELS 106-RPS / 206-RPS
PRESSURE RELIEF VALVE

FLOW CAPACITY - RELIEF


Flow Capacity 45 ft / s or 14 m / s
106-RPS
(See 106-PG in Main Valve section for other valve data)
Size (inches) 1/2 in 3/4 in 1 in 1-1/4 in 1-1/2 in 2 in 2-1/2 in 3 in 4 in

Size (mm) 15 mm 19 mm 25 mm 32 mm 40 mm 50 mm 65 mm 80 mm 100 mm

Momentary (USGPM) 28 43 110 170 250 470 670 1030 1800

Momentary (L/s) 2 3 7 11 16 30 42 65 114

Flow Capacity 45 ft / s or 14 m / s
106-RPS
(See 106-PG in Main Valve section for other valve data)

Size (inches) 6 in 8 in 10 in 12 in 14 in 16 in 20 in 24 in 36 in

Size (mm) 150 mm 200 mm 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm 900 mm

Momentary (USGPM) 4000 7000 11000 16000 19000 25000 39000 56200 124700

Momentary (L/s) 252 442 694 1009 1199 1577 2461 3546 7868

Flow Capacity 45 ft / s or 14 m / s
206-RPS
(See 206-PG in Main Valve section for other valve data)
Size (inches) 3 in 4 in 6 in 8 in 10 in 12 in 16 in 18 in 20 in

Size (mm) 80 mm 100 mm 150 mm 200 mm 250 mm 300 mm 400 mm 450 mm 500 mm

Momentary (USGPM) 564 1236 2160 4800 8400 13200 19200 30000 30050

Momentary (L/s) 36 78 136 303 530 833 1211 1893 1896

Flow Capacity 45 ft / s or 14 m / s
206-RPS
(See 206-PG in Main Valve section for other valve data)

Size (inches) 24 x 16 in 24 x 20 in 28 in 30 in 32 in 36 in 40 in

Size (mm) 600 x 400 mm 600 x 500 mm 700 mm 750 mm 800 mm 900 mm 1000 mm

Momentary (USGPM) 30100 39000 67440 67490 67540 67640 62000

Momentary (L/s) 1899 2461 4255 4258 4261 4268 3912

120 2016.1
RELIEF / SUSTAINING / SURGE

MODELS 106-RPS / 206-RPS


PRESSURE SUSTAINING VALVES

KEY FEATURES
• Ensures minimum upstream pressure for critical use
• Easily adjustable pressure setting
• Closes if inlet pressure drops below set-point

PRODUCT OVERVIEW TYPICAL APPLICATION


The 106-RPS and 206-RPS pressure sustaining valves The 106-RPS or 206-RPS valve prevents high demand
are based on the model 106-PG or 206-PG main valve. in the residential area from dropping the pressure
The 81-RP pilot senses the upstream pressure available to the critical user.
through a connection to the valve inlet. The valve and Valve modulates to assure minimum upstream
pilot remain closed until the inlet pressure exceeds pressure and if need be, closes tight.
the pilot setting.
Under flowing conditions, the pilot reacts to small
changes in pressure to control the valve position by
modulating the pressure above the diaphragm.
Critical User
Should the upstream pressure fall below the set-
point, the valve will close or modulate to ensure that
the set-point is maintained.

Singer Model 106-RPS or


206-RPS Pressure Sustaining Valve

Residential

2016.1 121
MODELS 106-RPS / 206-RPS
PRESSURE SUSTAINING VALVES

SCHEMATIC DRAWING STANDARD MATERIALS


1. Main Valve - 106-PG or 206-PG Standard materials for pilot system components are:
2. Isolation Valve - standard 4 in / 100 mm • ASTM B62 bronze or ASTM B16 brass
and larger • AISI 303/316 stainless steel trim
3. Strainer - standard 4 in / 100 mm and larger • Buna-N / EPDM diaphragm and seals
4. Fixed Restriction- 1/8 in / 3.2 mm
5. Model 852-B Closing Speed Control SELECTION SUMMARY
6. Model 81-RP pilot 1. Select the valve with sufficient capacity using the
• Specify for 5 to 50 psi / 0.35 to 3.5 bar, minimum available pressure drop across
10 to 80 psi / 0.70 to 5.5 bar, the valve.
20 to 200 psi / 1.38 to 13.8 bar,
100 to 300 psi / 6.9 to 20.7 bar. 2. Usually operating in the continuous “C” service
range up to 20 ft/s / 6 m/s - see below and/
7. Isolation Valve - standard 4 in / 100 mm or performance curves (see Technical & Sizing
and larger Information section, page 231).
8. Isolation Valve - standard all sizes 3. If the outlet pressure is less than 35% of the inlet
9. Opening Speed Control, optional pressure and operating for extended periods,
check for cavitation.

Note: SRD shown is available for 6” 106-PG and larger. 4. For sustaining applications with high pressure
drops, a model 106-RPS-AC: Pressure
Sustaining with anti-cavitation cages may be
required. Refer to 106-AC section (page 78) and
consult Singer Valve.
5. Ensure that the maximum working pressure
rating for the valve and for the flanges exceeds
the maximum operating pressure.

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering
instructions.
Additionally, include the following information for this
product:
Free Flow

1. Single chamber (106) or (206)


2. Outlet pressure
3. Inlet pressure pilot range

INLET

Schematic A-0423F

122 2016.1
MODELS 106-RPS / 206-RPS
PRESSURE SUSTAINING VALVES

106-RPS-Sustaining Flow Capacity (See 106-PG in Main Valve section for other valve data)

Size (inches) 1/2 in 3/4 in 1 in 1-1/4 in 1-1/2 in 2 in 2-1/2 in 3 in 4 in

Size (mm) 15 mm 19 mm 25 mm 32 mm 40 mm 50 mm 65 mm 80 mm 100 mm

Minimum (USGPM) Flat Diaphragm 1 1 1 1 1 5 5 5 10

Minimum (L/s) Flat Diaphragm 0.1 0.1 0.1 0.1 0.1 0.3 0.3 0.3 0.6

Maximum Continuous (USGPM) 12 19 49 93 125 210 300 460 800

Maximum Continuous (L/s) 0.8 1 3 6 8 13 19 29 50

106-RPS-Sustaining Flow Capacity (See 106-PG in Main Valve section for other valve data)

Size (inches) 6 in 8 in 10 in 12 in 14 in 16 in 20 in 24 in 36 in

Size (mm) 150 mm 200 mm 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm 900 mm

Minimum (USGPM) Flat Diaphragm 20 40 - - - - - - -

Minimum (USGPM) Rolling Diaphragm 1 1 3 3 3 3 10 10 20

Minimum (L/s) Flat Diaphragm 1.3 2.5 - - - - - - -

Minimum (L/s) Rolling Diaphragm 0.1 0.1 0.2 0.2 0.2 0.2 0.6 0.6 1.3

Maximum Continuous (USGPM) 1800 3100 4900 7000 8500 11000 17500 25800 55470

Maximum Continuous (L/s) 114 196 309 442 536 694 1104 1628 3500

206-RPS-Sustaining Flow Capacity (See 206-PG in Main Valve section for other valve data)

Size (inches) 3 in 4 in 6 in 8 in 10 in 12 in 16 in 18 in 20 in

Size (mm) 80 mm 100 mm 150 mm 200 mm 250 mm 300 mm 400 mm 450 mm 500 mm

Minimum (USGPM) Flat Diaphragm 5 5 10 20 40 - - - -

Minimum (USGPM) Rolling Diaphragm - - - - - 3 3 3 3

Minimum (L/s) Flat Diaphragm 0.3 0.3 0.6 1.3 2.5 - - - -

Minimum (L/s) Rolling Diaphragm - - - - - 0.2 0.2 0.2 0.2

Maximum Continuous (USGPM) 300 580 1025 2300 4100 6400 9230 16500 16500

Maximum Continuous (L/s) 19 37 65 145 260 404 582 1040 1040

206-RPS-Sustaining Flow Capacity (See 206-PG in Main Valve section for other valve data)
Size (inches) 24 x 16 in 24 x 20 in 28 in 30 in 32 in 36 in 40 in
Size (mm) 600 x 400 mm 600 x 500 mm 700 mm 750 mm 800 mm 900 mm 1000 mm

Minimum (USGPM) Rolling Diaphragm 3 3 10 10 10 10 20

Minimum (L/s) Rolling Diaphragm 0.2 0.2 0.6 0.6 0.6 0.6 1.3

Maximum Continuous (USGPM) 16500 21700 33600 33650 33700 33800 62000

Maximum Continuous (L/s) 1041 1370 2120 2123 2126 2132 3912

2016.1 123
RELIEF / SUSTAINING / SURGE

MODELS 106-RPS-D / 206-RPS-D


PRESSURE DIFFERENTIAL SUSTAINING VALVE

KEY FEATURES
• Maintains a minimum differential pressure
• Easily adjustable differential pressure setting
• Valve closes drip-tight when the pressure differential is
less than the pilot setting

PRODUCT OVERVIEW
TThe 106-RPS-D and 206-RPS-D pressure differential Under flowing conditions, the pilot reacts to small
sustaining valves are based on the 106-PG or 206-PG changes in pressure to control the valve position by
main valve. modulating the pressure above the diaphragm. The
The RPS-D uses the 81-RPD pilot valve and has two pilot setting establishes a differential pressure that
sensing connections. The valve and pilot remain is held relatively steady despite changes in system
closed until the difference between the two pressures pressure or flow.
exceeds the pilot setting.

TYPICAL APPLICATIONS
Parallel Application Series Application
As the number of operating heat exchangers in the In a booster pump application, the Singer RPS-D
circuit vary, the Singer RPS-D maintains a relatively ensures the pump operates near its best efficiency
steady differential for maximum chiller efficiency. and without cavitation or overload, should the suction
conditions vary.
Singer Valve Model 106-RPS-D
pressure differential sustaining valve

Singer Valve Model


106-SC or 206-SC

124 2016.1
MODELS 106-RPS-D / 206-RPS-D
PRESSURE DIFFERENTIAL SUSTAINING VALVE

SCHEMATIC DRAWING STANDARD MATERIALS


1. Main Valve - 106-PG or 206-PG Standard materials for pilot system components are:
2. Isolation Valve - standard 4 in / 100 mm • ASTM B-62 bronze or ASTM B-16 brass
and larger • AISI 316 stainless steel trim
3. Strainer - standard 4 in / 100 mm and larger
4. Fixed Restriction - 1/8 in / 3.2 mm SELECTION SUMMARY
5. Model 852-B Closing Speed Control 1. Select the valve with sufficient capacity using the
6. Model 81-RPD Pilot available pressure drop.
• Specify for 5 to 50 psi / 0.35 to 3.5 bar, 2. Usually operating in the continuous, “C”, service
10 to 80 psi / 0.70 to 5.5 bar, range up to 20 ft/s / 6 m/s
20 to 200 psi / 1.38 to 13.8 bar,
100 to 300 psi / 6.9 to 20.7 bar. 3. If the outlet pressure is less than 35% of the inlet
pressure, check for cavitation.
7. Isolation Valve - standard 4 in / 100 mm
and larger 4. Ensure that the maximum working pressure
rating of the valve and of the flange exceeds the
8. Isolation Valve - standard all sizes maximum operating pressure.
9. Opening Speed Control (optional)

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering
instructions.
Additionally, include the following information for this
Optional product:
Connection: 1. Single chamber (106) or (206)
Remote eg.
pump suction 2. Pilot range

Standard
Connection:
Downstream

Schematic A-0428B

2016.1 125
MODELS 106-RPS-D / 206-RPS-D
PRESSURE DIFFERENTIAL SUSTAINING VALVE

106-RPS-D Flow Capacity (See 106-PG in Main Valve section for other valve data)

Size (inches) 1/2 in 3/4 in 1 in 1-1/4 in 1-1/2 in 2 in 2-1/2 in 3 in 4 in

Size (mm) 15 mm 19 mm 25 mm 32 mm 40 mm 50 mm 65 mm 80 mm 100 mm

Minimum (USGPM) Flat Diaphragm 1 1 1 1 1 5 5 5 10

Minimum (L/s) Flat Diaphragm 0.1 0.1 0.1 0.1 0.1 0.3 0.3 0.3 0.6

Maximum Continuous (USGPM) 12 19 49 93 125 210 300 460 800

Maximum Continuous (L/s) 0.8 1 3 6 8 13 19 29 50

106-RPS-D Flow Capacity (See 106-PG in Main Valve section for other valve data)

Size (inches) 6 in 8 in 10 in 12 in 14 in 16 in 20 in 24 in 36 in

Size (mm) 150 mm 200 mm 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm 900 mm

Minimum (USGPM) Flat Diaphragm 20 40 - - - - - - -

Minimum (USGPM) Rolling Diaphragm 1 1 3 3 3 3 10 10 20

Minimum (L/s) Flat Diaphragm 1.3 2.5 - - - - - - -

Minimum (L/s) Rolling Diaphragm 0.1 0.1 0.2 0.2 0.2 0.2 0.6 0.6 1.3

Maximum Continuous (USGPM) 1800 3100 4900 7000 8500 11000 17500 25800 55470

Maximum Continuous (L/s) 114 196 309 442 536 694 1104 1628 3500

206-RPS-D Flow Capacity (See 206-PG in Main Valve section for other valve data)

Size (inches) 3 in 4 in 6 in 8 in 10 in 12 in 16 in 18 in 20 in

Size (mm) 80 mm 100 mm 150 mm 200 mm 250 mm 300 mm 400 mm 450 mm 500 mm

Minimum (USGPM) Flat Diaphragm 5 5 10 20 40 - - - -

Minimum (USGPM) Rolling Diaphragm - - - - - 3 3 3 3

Minimum (L/s) Flat Diaphragm 0.3 0.3 0.6 1.3 2.5 - - - -

Minimum (L/s) Rolling Diaphragm - - - - - 0.2 0.2 0.2 0.2

Maximum Continuous (USGPM) 300 580 1025 2300 4100 6400 9230 16500 16500

Maximum Continuous (L/s) 19 37 65 145 260 404 582 1040 1040

206-RPS-D Flow Capacity (See 206-PG in Main Valve section for other valve data)

Size (inches) 24 x 16 in 24 x 20 in 28 in 30 in 32 in 36 in 40 in

Size (mm) 600 x 400 mm 600 x 500 mm 700 mm 750 mm 800 mm 900 mm 1000 mm

Minimum (USGPM) Rolling Diaphragm 3 3 10 10 10 10 20

Minimum (L/s) Rolling Diaphragm 0.2 0.2 0.6 0.6 0.6 0.6 1.3

Maximum Continuous (USGPM) 16500 21700 33600 33650 33700 33800 62000

Maximum Continuous (L/s) 1040 1370 2120 2123 2126 2132 3912

126 2016.1
RELIEF / SUSTAINING / SURGE

MODELS 106-RPS-L&H / 206-RPS-L&H


SURGE ANTICIPATING RELIEF VALVE

KEY FEATURES
• Protects against power failure surges or pressure waves
caused by velocity changes
• Quick opening relief
• Easily adjustable pressure setting
• No electrical services required

PRODUCT OVERVIEW
The 106-RPS-L&H and 206-RPS-L&H anticipating The RPS-L&H pilot system is comprised of two pilots,
surge relief valves are based on the 106-PG or 206-PG the 81-RP and the 82-PR. Both pilots sense pressure
main valve. through a connection to the header pipe. The 81-RP
The valve is mounted in a tee, downstream of the high pressure pilot opens the valve to relieve excess
pump check valve(s). It is designed to anticipate pressure. The model 82-PR low pressure pilot opens
surges to avoid the severe water hammer often quickly on below normal pressures prior to the return
associated with power failure surges. of a surge wave, initiating the opening of the main
valve in anticipation of the high pressure wave’s arrival.

Header Pipeline
TYPICAL APPLICATION
Isolation Gate Valve

Singer Model 106-BPC


Pump Control Valve
with Internal Drop Check

Booster
Pump Singer Model
106-RPS-L&H
Surge Anticipating
Relief Valve

Connect in field to station header


for reliable pressure signal

Pump Suction Line

2016.1 127
MODELS 106-RPS-L&H / 206-RPS-L&H
SURGE ANTICIPATING RELIEF VALVE

SCHEMATIC DRAWING STANDARD MATERIALS


1. Main Valve - 106-PG or 206-PG Standard materials for pilot system components are:
2. Isolation Valve (2A, 2B, 2C), standard all sizes ASTM B-62 bronze or ASTM B-16 brass
3. Strainer - 40 mesh screen AISI 303 / 316 stainless steel trim
4. Closing Speed Control - model 852-B
5. Test Needle Valve - normal position fully open SELECTION SUMMARY
6. Pressure Gauge - 1/4 in / 6.35 mm, NPT - By 1. Anticipating surge relief valves should be sized
Others from information provided by an engineer’s
7. Test Needle Valve - normal position fully closed surge analysis of the system.

8. Model 82-PR - Low Surge pilot 2. In the absence of such information, as a general
-S
 pecify for 7 to 50 / 0.48 to 3.5 bar, 45 to 200 psi guide, a valve selected to pass 25% of the
/ 3.1 to 13.8 bar or 100 to 300 psi / 6.9 to 20.7 maximum normal flow when the valve is fully
bar open, calculated with the static pressure as
the pressure drop across the valve, has been
9. Model 81-RP - High Surge Pressure pilot successful in practice. Over sizing may cause
- specify for 5 to 50 psi / 0.35 to 3.5 bar, 10 to 80 problems. Valve may not close if oversized.
psi / 0.7 to 5.5 bar, 100 to 300 psi / 6.9 to 20.7
bar. Standard 20 to 200 psi / 1.38 to 13.8 bar. 3. Ensure that the recovered header pressure
(static) exceeds the low pressure relief pilot
10. Pipe Plug for Gauge Connection setting, otherwise the valve will not close. As a
11. Swing Check Valve - 1/2 in / 15 mm guide, a setting at 60% of static pressure has
been suitable.
4. Ensure the maximum working pressure rating
of the valve and flanges exceeds the maximum
operating pressure.
5. Select either a standard globe style body or the
optional angle style body.
6. If the RPS-L&H is sized properly, a hydraulic travel
limiter is unnecessary. Should an engineer insist
that the travel limiter be included, then it will be
offered as an option (add HFL to model number).
7. Should only be used on static pressures greater
than 100 ft / 30 m / 43.5 psi.

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering
instructions.
Additionally, include the following information for this
product:
Schematic A-0400C
Note: Schematic shown is for 2 in / 50 mm to 6 in / 150 mm
1. Single chamber (106) or (206)
For 8 in / 200 mm and higher refer to Schematic A-0401C 2. Pilot ranges
3. HFL – Hydraulic Flow Limiter available

128 2016.1
MODELS 106-RPS-L&H / 206-RPS-L&H
SURGE ANTICIPATING RELIEF VALVE

106-RPS-L&H Flow Capacity 45 ft / s or 14 m / s (See 106-PG in Main Valve section for other valve data)

Size (inches) 1/2 in 3/4 in 1 in 1-1/4 in 1-1/2 in 2 in 2-1/2 in 3 in 4 in

Size (mm) 15 mm 19 mm 25 mm 32 mm 40 mm 50 mm 65 mm 80 mm 100 mm

Momentary (USGPM) - - - - - 470 670 1030 1800

Momentary (L/s) - - - - - 30 42 65 114

106-RPS-L&H Flow Capacity 45 ft / s or 14 m / s (See 106-PG in Main Valve section for other valve data)

Size (inches) 6 in 8 in 10 in 12 in 14 in 16 in 20 in 24 in 36 in

Size (mm) 150 mm 200 mm 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm 900 mm

Momentary (USGPM) 4000 7000 11000 16000 19000 25000 39000 56200 124700

Momentary (L/s) 252 442 694 1009 1199 1577 2461 3546 7868

206-RPS-L&H Flow Capacity 45 ft / s or 14 m / s (See 206-PG in Main Valve section for other valve data)

Size (inches) 3 in 4 in 6 in 8 in 10 in 12 in 16 in 18 in 20 in

Size (mm) 80 mm 100 mm 150 mm 200 mm 250 mm 300 mm 400 mm 450 mm 500 mm

Momentary (USGPM) 564 1236 2160 4800 8400 13200 19200 30000 30050

Momentary (L/s) 36 78 136 303 530 833 1211 1893 1896

206-RPS-L&H Flow Capacity 45 ft / s or 14 m / s (See 106-PG in Main Valve section for other valve data)

Size (inches) 24 x 16 in 24 x 20 in 28 in 30 in 32 in 36 in 40 in

Size (mm) 600 x 400 mm 600 x 500 mm 700 mm 750 mm 800 mm 900 mm 1000 mm

Momentary (USGPM) 30100 39000 67440 67490 67540 67640 62000

Momentary (L/s) 1899 2461 4255 4258 4261 4268 3912

2016.1 129
RELIEF / SUSTAINING / SURGE

MODELS 106-RPS-RR / 206-RPS-RR


SURGE ANTICIPATING ON RATE OF RISE OF PRESSURE RELIEF VALVE

KEY FEATURES
• Protects against power failure surges or pressure waves
caused by velocity changes
• Unaffected by header pressure and over sizing
• Quick opening relief
• Easily adjustable pressure setting
• No electrical services required

PRODUCT OVERVIEW
The 106-RPS-RR and 206-RPS-RR surge anticipating pressure increase. The flow into the accumulator
relief on rate of rise valves are based on the 106-PG creates a pressure drop across the fixed restriction,
or 206-PG main valve. which lowers the pressure in the connection between
The valve is installed downstream of the pump check the fixed restriction and the pilot. The pilot senses
valve(s) and has two pilots, the 81-RP and the 81-RPD. the pressure difference between this lower pressure
Both pilots sense pressure through a connection and the header pressure. This difference occurs at
to the header pipe. The 81-RP high pressure pilot the initiation of the pressure surge, providing the time
acts as a standard relief pilot, opening on excessive necessary for the valve to open in anticipation of the
pressure. The 81-RPD differential pilot responds high pressure.
to the pressure differential across its diaphragm. A
pressure differential is created when there is a system

TYPICAL APPLICATION Header pipeline


Isolation gate valve
Singer Model 106-BPC
Pump Control valve Singer Model 106-RPS-RR control valve
with Internal Drop Check Surge anticipating on Rate of Rise of
Pressure Relief valve
Booster
pump

Long pipe lines and or low recovery pressure Connect in field to station header
after the surge valve opens may not guarantee for reliable pressure signals
conventional surge valves will close. Since the
RPS-RR is closing when the system pressure has
stabilized, oversizing is not a problem. Pump suction line

130 2016.1
MODELS 106-RPS-RR / 206-RPS-RR
SURGE ANTICIPATING ON RATE OF RISE OF PRESSURE RELIEF VALVE

SCHEMATIC DRAWING SELECTION SUMMARY


1. Main Valve - 106-PG or 206-PG, complete with 1. Anticipating surge relief valves should be sized
X107 Position Indicator from information provided by an engineer’s
4. Strainer Flush Valve - Normal Position Closed surge analysis of the system.

5. Flow Control - J0077A 2. In the absence of such information, as a general


guide, a valve selected to pass 25% of the
6. Connection To Header maximum normal flow when the valve is fully
7. Isolating Valve - Normal Position Open open, calculated with the static pressure as
the pressure drop across the valve, has been
8. Strainer - 40 Mesh - J0098A
successful in practice.
9. Pressure Gauge
3. Ensure the maximum working pressure rating
10. Pressure Gauge of the valve and flanges exceeds the maximum
11. Bladder Accumulator - M1408A operating pressure.
12. Differential Pilot - Model 81-RPD - 4. Select either a standard globe style body or the
Normally Closed optional angle style body.
13. Relief Pilot - Model 81-RP 5. Surge anticipating valves usually relieve to
atmosphere which ensures high operating
14. Isolating Valve (14A, 14B) - Normal Position Open differential pressure and rapid response times.
15. Fixed Restriction - 1/16 in / 1.58 mm Momentary, “M”, service range up to 45 ft/s /
16. Check Valve - J0040A 14 m/s is suitable for sizing selection. Other
supplementary functions are available, consult
with Singer Valve.

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering
instructions.
Additionally, include the following information for this
product:
1. Single chamber (106) or (206)
2. Pilot range

B
A

Schematic A-7340F
Note: Schematic shown is for 2 in / 50 mm to 6 in / 150 mm
106, and 3 in / 80 mm to 8 in / 200 mm 206
For 8 in / 200 mm and higher, refer to Schematic A-7340F1

2016.1 131
MODELS 106-RPS-RR / 206-RPS-RR
SURGE ANTICIPATING ON RATE OF RISE OF PRESSURE RELIEF VALVE

Flow Capacity 45 ft / s or 14 m / s
106-RPS-RR
(See 106-PG in Main Valve section for other valve data)
Size (inches) 1/2 in 3/4 in 1 in 1-1/4 in 1-1/2 in 2 in 2-1/2 in 3 in 4 in

Size (mm) 15 mm 19 mm 25 mm 32 mm 40 mm 50 mm 65 mm 80 mm 100 mm

Momentary (USGPM) - - - - - 470 670 1030 1800

Momentary (L/s) - - - - - 30 42 65 114

Flow Capacity 45 ft / s or 14 m / s
106-RPS-RR
(See 106-PG in Main Valve section for other valve data)

Size (inches) 6 in 8 in 10 in 12 in 14 in 16 in 20 in 24 in 36 in

Size (mm) 150 mm 200 mm 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm 900 mm

Momentary (USGPM) 4000 7000 11000 16000 19000 25000 39000 56200 124700

Momentary (L/s) 252 442 694 1009 1199 1577 2461 3546 7868

Flow Capacity 45 ft / s or 14 m / s
206-RPS-RR
(See 206-PG in Main Valve section for other valve data)
Size (inches) 3 in 4 in 6 in 8 in 10 in 12 in 16 in 18 in 20 in
Size (mm) 80 mm 100 mm 150 mm 200 mm 250 mm 300 mm 400 mm 450 mm 500 mm

Momentary (USGPM) 564 1236 2160 4800 8400 13200 19200 30000 30050

Momentary (L/s) 36 78 136 303 530 833 1211 1893 1896

Flow Capacity 45 ft / s or 14 m / s
206-RPS-RR
(See 206-PG in Main Valve section for other valve data)

Size (inches) 24 x 16 in 24 x 20 in 28 in 30 in 32 in 36 in 40 in

Size (mm) 600 x 400 mm 600 x 500 mm 700 mm 750 mm 800 mm 900 mm 1000 mm

Momentary (USGPM) 30100 39000 67440 67490 67540 67640 62000

Momentary (L/s) 1899 2461 4255 4258 4261 4268 3912

132 2016.1
RELIEF / SUSTAINING / SURGE

MODEL A106-DL
DYNAMIC LIFTER® SPRING PRESSURE RELIEF VALVE

KEY FEATURES
• Low maintenance
• Hygienic and minimal time to flush and test operations
• Premium materials reduce maintenance, providing the
lowest long-term cost of ownership

PRODUCT OVERVIEW TYPICAL APPLICATION


The A106-Dynamic Lifter (DL) sewage/dirty water
pressure relief valve is a direct acting spring
Singer Valve
loaded relief valve. The valve is adjusted to open Dynamic Lifter Spring
when the pressure exceeds the set-point, which is
approximately 10% above the normal operating Check
pressure. The valve closes drip-tight when pressure valves
falls below the set-point.
The DL is connected on a tee off the main line and
usually discharges relief flow back to the main sump
to reduce the surge over-pressure. A speed control
permits adjustment of the closing speed.
The opening force is boosted by the line pressure
operating, via the separation chamber, on the
piston. By applying external pressure to the test
Sewage
connection, the valve may be cycled open for routine
pumps
maintenance.
Ideal for:
• raw water that contains organics
• lower pressure sewage lift stations
• booster sewage stations

2016.1 133
MODEL A106-DL
DYNAMIC LIFTER® SPRING PRESSURE RELIEF VALVE

SCHEMATIC DRAWING SCHEMATIC DRAWING -


1. Model A106-DL - Body OPERATIONAL DETAILS
2. Diaphragm isolator • Operating oil is separated from sewage by the
3. Closing speed control chamber and diaphragm isolator (2).
4. Isolating valve • System pressure is applied to piston by mineral oil
and isolator (2).
5. Oil filled isolating valve
– Piston and closing speed controls operate in
6. Pressure gauge clean non-contaminating environment
7. Isolating valve • System (over) pressure is applied to the opening
8. Teflon seated swing check valve piston throughout the full stroke.
– Allows more relief flow as it does not lose opening
9. Isolating valve – external pressure force as the inner valve leaves the seat.
for test and flush cycle
• By closing valve (4), external pressure may be
10. 3/8 NPT flexible hose applied through port and on to piston by the
11. Isolating valve mineral oil opening of the Dynamic Lifter (1).
12. Gauge cock – A tire pump or compressed air may be used to
open the valve and check the relief setting or flush
stringy material from the seat.
• Where conventional spring operated valves allow
build-up of waste-water residue (dry pack) on
the valve’s downstream and exhaust pipe to sump,
Singer’s A106-DL can easily be opened fully,
through the actuator, to flush out these unwanted
build-ups.
• Heat fused, heavy epoxy coating inside and out, 316
stainless steel seat and stem. The stem is also Oxy-
Nitride coated to reduce mineral or debris build-up

12
ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering
instructions.
Additionally, include the following information for this
product:
• Inlet / outlet pressure range

A-8640C

134 2016.1
MODEL A106-DL
DYNAMIC LIFTER SPRING PRESSURE RELIEF VALVE
®

VALVE SIZING & MEASUREMENTS


A106-DL ANSI DATA (US UNITS) SINGLE SPRING STACK DOUBLE SPRING STACK
Size 3 in 4 in 6 in 8 in 6 in 8 in
Relief Setings (psi)
MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX
25 90 20 65 15 30 10 15 40 90 30 50
Spring Specific Ranges
70 200 60 145 25 60 15 30 90 160 50 80
Other ranges available, consult with Singer Valve
Lift / Opening 2 in 2 in 2 1/2 in 3 in 2 1/2 in 3 in
Dimension A 9 in 10 in 11.5 in 14 in 11.5 in 14 in
Dimension B 38.5 in 39.5 in 43.75 in 45.75 in 25.25 in 26.75 in
Dimension C 30.5 in 30.5 in 32’’ 32 in 32’’ 32 in
Dimension D 4.75 in 5.75 in 7.5 in 10 in 15.25 in 18.25 in

A106-DL ANSI DATA


(METRIC UNITS) SINGLE SPRING STACK DOUBLE SPRING STACK
Size 80 mm 100 mm 150 mm 200 mm 150 mm 200 mm
Relief Setings (bar)
MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX
1.72 6.21 1.38 4.48 1.03 2.07 0.69 1.03 2.76 6.21 2.07 3.45
Spring Specific Ranges
4.83 13.79 4.14 10.00 1.72 4.14 1.03 2.07 6.21 11.03 3.45 5.52
Other ranges available, consult with Singer Valve
Lift / Opening 50 mm 50 mm 64 mm 76 mm 64 mm 76 mm
Dimension A 229 mm 254 mm 292 mm 356 mm 292 mm 356 mm
Dimension B 978 mm 1004 mm 1112 mm 1162 mm 641 mm 680 mm
Dimension C 775 mm 775 mm 813 mm 813 mm 813 mm 813 mm
Dimension D 121 mm 146 mm 191 mm 254 mm 387 mm 464 mm

'D' DIM
'D' DIM (SINGLE)

(DOUBLE)
'B' DIM
'B' DIM

'A' DIM
'A' DIM

'C' DIM
(CONFIRM LOCATION)

'D' DIM
'A' DIM A' DIM

2016.1 135
RELIEF / SUSTAINING / SURGE

MODELS A106-DL-AIR / A106-DL-AIR-ET


DYNAMIC LIFTER® AIR OPERATED PRESSURE RELIEF VALVE
SURGE ANTICIPATING ELECTRONICALLY TIMED DL PRESSURE RELIEF VALVE

KEY FEATURES
A106-DL-AIR:
• Eliminates surges and prolongs pipe life
• Adjustable closing speed
• Utilizes compress air or plant air
• Smaller profile allows installation into limited space
• Ideal for higher pressures

A106-DL-AIR-ET:
• All key features of the A106-DL-Air
• Solenoid valve anticipates surges resulting from power failures

PRODUCT OVERVIEW TYPICAL APPLICATION


The Model A106-DL-Air is a compact sewage relief Application drawing is applicable to both A-106-DL-Air
valve that is suitable for high pressures up to 200 psi and A-106-DL-Air-ET.
/ 13.8 bar, responds very quickly and retains all the
features and benefits of the Model A106-DL Spring–
Hydraulic version. It is an attractive solution to what
may be otherwise a difficult application due to higher Waste water plant
pressures or space height limitations.
The Model A106-DL-Air-ET retains all the features and
benefits of the Model A106-DL-Air with the additional
feature of two 3-way solenoid valves which forces the
valve open upon power failure.

Dynamic Lifter Air Compact profile is ideal for space


restrictions in the waste water
pump station

136 2016.1
MODEL A106-DL-AIR
DYNAMIC LIFTER AIR OPERATED PRESSURE RELIEF VALVE
®

SCHEMATIC DRAWING A106-DL-AIR SCHEMATIC DRAWING A106-DL-AIR –


1. Model A106-DL-Air OPERATION DETAILS
2. Isolating Valve (2A, 2B) Operates using separate compressed air supply
3. Needle Valve -A
 n inexpensive 120 psi / 8.3 bar air compressor may
be used for 200 psi / 13.8 bar or higher relief
4. Pressure Reducing Pilot - Model 160
pressures by using a large diameter closing piston.
5. Relief Pilot - Model 81-RP
Using a chamber and diaphragm isolator (9), an
6. Pressure Gauge (6A, 6B) accurate hydraulic pilot (5) opens reliably and
7. Fixed Restriction repeatedly at its set pressure (gauge 6A)
-F
 ull operational (including pilot) check is quickly and
8. Isolating Valve cleanly performed by closing valve (8) and
9. Diaphragm Isolator applying pressure at (18). For quick flush open (3).
10. Bleed Valve The check valve (11) maintains air in the operating
11. Check Valve, J0040A cylinder should the air supply fail.
- Provided the air supply is above minimum, variations
12. Bleed Valve in pressure do not affect the valve operation,
13. Manual Override Valve which is controlled independently by the accurate
pilot (5).
14. Fixed Restriction
The main valve (1) is constructed of the same
15. Air Supply
premium materials as the Hydraulic Dynamic Lifter
16. 852B Needle Valve for long life and minimum maintenance.
17. Air Charge Valve
18. Isolating Valve
19. Isolating Valve

Schematic A-8736A

2016.1 137
MODEL A106-DL-AIR-ET
SURGE ANTICIPATING ELECTRONICALLY TIMED DYNAMIC LIFTER® PRESSURE RELIEF VALVE

SCHEMATIC DRAWING A106-DL-AIR-ET SCHEMATIC DRAWING A106-DL-AIR-ET –


1. Model A106-DL-Air OPERATION DETAILS
2. Isolating Valve (2A, 2B) Operates using separate compressed air supply
3. Needle Valve -A
 n inexpensive 120 psi / 8.3 bar air compressor may
be used for 200 psi / 13.8 bar or higher relief
4. Pressure Reducing Pilot - Model 160
pressures by using a large diameter closing piston.
5. Relief Pilot - Model 81-RP
Using a chamber and diaphragm isolator (9), an
6. Pressure Gauge (6A, 6B) accurate hydraulic pilot (5) opens reliably and
7. Fixed Restriction repeatedly at its set pressure (gauge 6A)
-F
 ull operational (including pilot) check is quickly and
8. Isolating Valve cleanly performed by closing valve (8) and
9. Diaphragm Isolator applying pressure at (18). For quick flush open (3).
10. Bleed Valve The check valve (11) maintains air in the operating
11. Check Valve, J0040A cylinder should the air supply fail.
- Provided the air supply is above minimum, variations
12. Bleed Valve in pressure do not affect the valve operation, which
13. Solenoid Valve - 3 way - NC is controlled independently by the accurate pilot.The
main valve (1) is constructed of the same premium
14. Solenoid Valve - 3 way - NO
materials as the Hydraulic Dynamic Lifter for long
15. Air Supply life and minimum maintenance.
16. 852B Needle Valve Two 3-way solenoids are included to force the valve
17. Air Charge Valve open on power failure. A backup control panel is
required to time the reclosure.
18. Isolating Valve
The solenoids convert the relief valve function to a
19. Optional SAP control panel surge anticipating valve if needed, particularly if there
is a risk of the system going sub-atmospheric. Air
pressure through solenoid holds the valve open until
closed by the electrical controls

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering
instructions.

A106-DL-Air-ET
Schematic A-8809A

138 2016.1
MODEL A106-DL-AIR DYNAMIC LIFTER® AIR OPERATED PRESSURE RELIEF VALVE
MODEL A106-DL-AIR-ET SURGE ANTICIPATING ELECTRONICALLY TIMED DL PRESSURE RELIEF VALVE

A106-DL ANSI DATA (US UNITS) AIR OPERATED


Size 3 in 4 in 6 in 8 in
Relief Setings (psi)
Pressure Ranges Options Available up to 200 PSI, consult with Singer Valve
Lift / Opening 2 in 2 in 2 1/2 in 3 in
Dimension A 9 in 10 in 11.5 in 14 in
Dimension B* 22.5 in 23.5 in 25.5 in 28.88 in
Dimension C 30.5 in 30.5 in 32 in 32 in
Dimension D 4.75 in 5.75 in 7.5 in 10 in

A106-DL ANSI DATA


(METRIC UNITS) AIR OPERATED
Size 80 mm 100 mm 150 mm 200 mm
Relief Setings (bar)
Pressure Ranges Options Available up to 13.8 Bar, consult with Singer Valve
Lift / Opening 50 mm 50 mm 64 mm 76 mm
Dimension A 229 mm 254 mm 292 mm 356 mm
Dimension B* 572 mm 597 mm 648 mm 734 mm
Dimension C 775 mm 775 mm 813m 813 mm
Dimension D 121 mm 146 mm 191 mm 254 mm

Pneumatic operational ranges up to 200 psi / 13.8 bar.


Consult Singer Valve for more information on higher pressures.

*Dimension B reflects clearance allowed for pilot system and accessories

'B' DIM

'D' DIM
(SINGLE)

'A DIM 'C' DIM


(CONFIRM LOCATION)

ASSEMBLY CLEARANCE
'A' DIM

AIR OPERATED

2016.1 139
MODEL A106-DL DYNAMIC LIFTER® SPRING
MODEL A106-DL-ET DYNAMIC LIFTER® AIR

Dynamic Lifter Sizing Graph Curve: 3 in / 80 mm – 8 in / 200 mm


Conventional relief valves for sewage are typically sized “larger” than a
Singer Valve Dynamic Lifter due to opening forces being lost as the inner valve leaves the seat.
L/S USGPM
1262 20000
8"
(200 mm)
1000
900
800
700 6"
10000 (150 mm)
600
9000
500 8000
7000
400
6000

5000
300 4"
(100 mm)
4000

200
3000
Q- Pipeline Maximum Flow

3"
(80 mm)
Q-Pipeline Maximum Flow

Valve Size Selection


2000

Valve Size Selection


100
90
80
70
1000
60
900

50 800
700
40
600

500
30

400

20
300

200

10

6.3 100
10 20 30 40 50 60 70 80 90 100 200 Psi

1 2 3 4 5 6 7 8 9 10 13.8 bar

∆P - Minimum pressure drop across dynamic lifter.


Examples of valve size selection:P - Mimumum Pressure Drop Across Dynamic Lifter
1) Relief setting 80 psi / 5.5 bar - discharge to atmosphere: Max. flow in main pipeline 1,200 USGPM / 75.7 l/s - Find intersect
of 80 psi / 5.5 bar ∆P and 1200 USGPM / 75.7 l/s flow. Select next larger size Dynamic Lifter, for example, 3 in / 80 mm size.
2) Relief setting 55 psi / 3.8 bar - discharge 20 psi / 1.38 bar back pressure: Max. flow in main pipeline 4,000 USGPM / 252.4 l/s
Find intersect of 55 psi – 20 = 35 psi / 2.4 bar ∆P and 4000 USGPM / 252.4 l/s flow. Select next larger size Dynamic Lifter,
for example, 6 in / 150 mm size.
Note:
if the discharge was to atmosphere, ∆P = 55 psi / 3.8 bar and 4 in / 100 mm size would be selected.
this graph is based on current practice for standard applications. It is intended to be a guide only and no selection guarantee
is implied or intended.

140 2016.1
Our pump control valves substantially reduces surges that occur when a
pump starts or stops. How? Because they’re smart and they’re smooth. They
know when to open, when to close and they do it effortlessly.

Pump Control Valves


PUMP CONTROL

MODELS 106-PG-BPC / 206-PG-BPC


BOOSTER PUMP CONTROL VALVE – SINGLE CHAMBER

KEY FEATURES
• Substantially reduces pump starting and stopping surges
• Separate opening and closing speed controls
• Cost effective pump control system
• Optional internal mechanical drop check reduces power
failure surge

PRODUCT OVERVIEW TYPICAL APPLICATION


The 106-PG-BPC or 206-PG-BPC booster pump control
valve is installed in-line directly downstream of the
pump discharge. Singer model 106-PG-BPC
Booster Pump Control valve
The valve is normally closed, and, on pump start-up, Single Chamber with
a pilot solenoid is energized to slowly open the valve, Internal Drop Check (optional)
at a rate governed by the opening speed control. The
pipeline flow is gradually increased.
When shut-down is required, the pilot solenoid is
Isolation valve
de-energized to close the main valve and reduce the
flow. The pump is kept running while the booster
pump control valve slowly closes. When the valve is
almost fully closed and flow is virtually stopped, a cam Booster
triggers the limit switch to stop the pump. pump

With the internal drop check option, the built-in


mechanical drop check closes immediately when the Singer model 106-RPS
Pressure Relief Valve
flow stops, regardless of the valve position. Whether
due to a control malfunction, normal operation or
a pump motor power failure, by closing before flow
reverses, surges are minimized.
The single chamber construction facilitates
supplemental modulating functions such as pressure
sustaining, pressure reducing, rate of flow control.
Being a single chamber design, the control forces are
generated by the differential across the valve. When
a modulating function is included there are more
positive initial closing results.

142 2016.1
MODELS 106-PG-BPC / 206-PG-BPC
BOOSTER PUMP CONTROL VALVE – SINGLE CHAMBER

SCHEMATIC DRAWING STANDARD MATERIALS


1. Main Valve - 106-PG or 206-PG Standard materials for pilot system components are:
2. Isolation Valve • ASTM B-62 bronze and ASTM B-16 brass
3. Strainer - 40 mesh stainless steel screen • AISI 303 / 316 stainless steel trim
4. Check Valve - model 10 Refer to Electronic Control section (SPC product), see
5. Micrometer Needle Valve - closing speed page 203, and consult Singer Valve for pump control
panel options.
6. Solenoid Valve - three way, NEMA 4
7. Micrometer Needle Valve - opening speed
SELECTION SUMMARY
8. Check Valve - model 10
1. The model PG-BPC, booster pump control valve
9. Strainer - 40 mesh stainless steel screen incurs continuous head loss while the pump
10. Isolation Valve is operating. Refer to the 106 or 206 performance
curves (see Technical & Sizing Information
11. Model X129 Limit Switch Assembly -
section, page 231). Use drooping portion of
NEMA 4, SPDT
curve. Select the smallest size with a pressure
12. Isolation Valve drop that is acceptable.
2. With no modulating pilot functions added, care
Internal Drop Check Feature (optional, not shown) should be exercised not to oversize the valve,
especially if pumps are operating in parallel.
With very low differential across the valve, initial
closing speed will be slow. Sections 106-PG and
206-PG (Main Valve section, page 11), provide
specifications and details of construction of
the standard main valves while bulletin IDC -
Internal Drop Check (see Main Valve Options
section, page 70) provides details on the internal
mechanical check option.
3. Standard configuration provides for NEMA 4
watertight enclosures for the Honeywell model
OP-AR, Single Pole Double Throw limit switch
and the ASCO solenoid with 120VAC / 60Hz (or
220VAC / 50HZ or 240VAC / 60Hz) coil. For other
electrical service or higher pressure ratings
consult with Singer Valve. A manual override is
available upon request.

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering
instructions.
Additionally, include the following information for this
Schematic A-7254C product:
1. Single chamber (106) or (206)
2. Solenoid voltage
3. Maximum inlet pressure

2016.1 143
MODELS 106-PG-BPC / 206-PG-BPC
BOOSTER PUMP CONTROL VALVE – SINGLE CHAMBER

Flow Coefficient Cv
106-PG-BPC
(See 106-PG in Main Valve Section for other Valve Data)

Size (inches) 2 in 2-1/2 in 3 in 4 in

Size ( mm) 50 mm 65 mm 80 mm 100 mm

Cv1 55 80 110 200

Kv2 13 19 26 47

Flow Coefficient Cv
106-PG-BPC
(See 106-PTC in Main Valve section for other valve data)

Size (inches) 6 in 8 in 10 in 12 in 14 in 16 in 20 in 24 in 36 in

Size (mm) 150 mm 200 mm 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm 900 mm

Cv1 460 800 1300 2100 2575 3300 5100 7600 16340

Kv 2
110 190 310 500 610 780 1210 1800 3875

Flow Coefficient Cv
206-PG-BPC
(See 206-PG in Main Valve Section for other Valve Data)

Size (inches) 4 in 6 in 8 in 10 in

Size ( mm) 100 mm 150 mm 200 mm 250 mm

Cv1 150 250 505 985

Kv2
36 60 120 230

Flow Coefficient Cv
206-PG-BPC
(See 206-PTC in Main Valve section for other valve data)

Size (inches) 12 in 16 in 18 in 20 in 24 x 16 in 24 x 20 in 36 x 24 in 40 x 36 in

Size (mm) 300 mm 400 mm 450 mm 500 mm 600 x 400 mm 600 x 500 mm 900 x 600 mm 1000 x 900 mm

Cv1 1550 2200 3300 3400 3500 5300 7800 18000

Kv2 370 520 780 810 830 1210 1850 4265

*CV = USGPM at 1 psi pressure drop

**KV = L / s at 1 bar pressure drop

(Q=CV P )

144 2016.1
PUMP CONTROL

MODELS 106-BPC / 206-BPC


BOOSTER PUMP CONTROL VALVE – DOUBLE CHAMBER

KEY FEATURES
• Suitable for most pumping applications including suction
lift and low differential head
• Prevents pump starting and stopping surges
• Built-in non-slam mechanical check reduces surges on
loss of power
• Separate opening and closing speed controls

PRODUCT OVERVIEW TYPICAL APPLICATION


The 106-BPC and 206-BPC booster pump control
valves are installed in-line, directly downstream of the
pump discharge.
The pump control valve is normally closed and
on pump start-up, a pilot solenoid is energized to
open the valve, at a rate governed by the opening
speed control. When shut-down is required the pilot
solenoid on the valve is de-energized to commence
closing. The pump is kept running while the valve Isolation Valve Motor
slowly closes. When the valve is almost fully closed
Starter
and flow is virtually zero, a stem mounted cam Panel
triggers the limit switch to stop the pump.
In the event of a power failure, the built-in mechanical
drop check closes immediately when the flow stops, Singer model
independently of the valve position. Surges are 106-BPC
minimized by closing the valve before reverse flow Booster Pump
occurs. Control Valve

Singer model 106-RPS


Pressure Relief

Booster
Pump

2016.1 145
MODELS 106-BPC / 206-BPC
BOOSTER PUMP CONTROL VALVE – DOUBLE CHAMBER

SCHEMATIC DRAWING STANDARD MATERIALS


1. Main Valve - 106-PTC or 206-PTC Standard materials for pilot system components are:
2. Strainer - (2A,2B) - 40 mesh stainless steel • ASTM B-62 bronze or ASTM B-16 brass
3. Check Valves - (3A,3B) • AISI 303 / 316 stainless steel trim
4. Isolation Valves - (4A,4B) Refer to Electronic Control section (SPC product), see
5. Micrometer Flow Control Valves - (5A Opening page 203, and consult Singer Valve for pump control
Speed Control, 5B Closing Speed Control) panel options.

6. Model X129 Limit Switch Assembly -


NEMA 4, SPDT SELECTION SUMMARY
7. Solenoid Valve - four way, NEMA 4 1. In-line pump control valves incur continuous
head loss while the pump is running. Refer to the
106 or 206 performance curves (straight line) (See
Technical and Sizing section, page 231). Select the
smallest size meeting the capacity requirements,
with a pressure drop that is acceptable.
2. Standard configuration provides for NEMA 4
watertight enclosures for the Honeywell model
OP-AR, SPDT limit switch and the ASCO solenoid
with 120 VAC / 60 Hz (or 220 VAC/ 50 Hz or 240
VAC / 60 Hz) coil. For other electrical service or
higher pressure ratings consult Singer Valve. A
manual override is available upon request.
3. Other functions may be combined with Booster
Pump Control valves, usually in conjunction
with single chamber main valves, e.g. model
106-BPC-R, pump control with pressure
sustaining feature.

ORDERING INSTRUCTIONS
Schematic A-0426H Refer to page 244 for the order form and ordering
instructions.
Additionally, include the following information for this
product:
1. Double chamber (106) or (206)
2. Solenoid voltage
3. Maximum inlet pressure

146 2016.1
MODELS 106-BPC / 206-BPC
BOOSTER PUMP CONTROL VALVE – DOUBLE CHAMBER

Flow Coefficient Cv
106-BPC
(See 106-PTC in Main Valve section for other valve data)
Size (in) 2 in 2-1/2 in 3 in 4 in 6 in 8 in 10 in 12 in 14 in 16 in 20 in 24 in

Size (mm) 50 mm 65 mm 80 mm 100 mm 150 mm 200 mm 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm

Cv1 55 80 110 200 460 800 1300 2100 2575 3300 5100 7600

Kv2 13 19 26 47 110 190 310 500 610 780 1210 1800

Flow Coefficient Cv
206-BPC
(See 206-PTC in Main Valve section for other valve data)
Size (in) 3 in 4 in 6 in 8 in 10 in 12 in 16 in 18 in 20 in 24 x 16 in 24 x 20 in 28 in 30 in 32 in 36 in

Size (mm) 80 mm 100 mm 150 mm 200 mm 250 mm 300 mm 400 mm 450 mm 500 mm 600 x 400 mm 600 x 500 mm 700 mm 750 mm 800 mm 900 mm

Cv1 60 150 250 505 985 1550 2200 3300 3400 3500 5100 7800 7800 7900 8000

Kv2 14 36 60 120 230 370 520 780 810 830 1210 1850 1850 1870 1900

*CV = USGPM at 1 psi pressure drop

**KV = L / s at 1 bar pressure drop

(Q=CV P )

2016.1 147
PUMP CONTROL

MODELS 106-DW / 206-DW


DEEP WELL PUMP CONTROL VALVE – DOUBLE CHAMBER

KEY FEATURES
• Prevents pump starting and stopping surges
• No energy loss while pump is running
• Separate opening and closing speed controls
• Discharges initial air/water silt to waste, on well applications
• Discharges stagnant water at start-up from dormant wells

PRODUCT OVERVIEW TYPICAL APPLICATION


The 106-DW and 206-DW deep well pump control
valves are installed in a tee between the pump
discharge and the check valve. Deep Well Isolation valve
Vertical Turbine
The valve is normally open, and, on pump start-up, a Pump Non-slam
pilot solenoid is energized to start closing the valve at check valve
a rate governed by the closing speed control.
Initially, the valve discharges air, water and sand to
waste. The open valve discharges all pump flow. As
Pilot pressure sensing
the valve closes slowly, flow is transferred to the main line connected to pipeline
line smoothly, increasing the pipeline flow without downstream of header
surges. When the valve is fully closed, all pump flow is check valve
in the pipeline, with no control valve losses.
When shut-down is required, the pilot solenoid on
the valve is de-energized to commence opening. The Provision should
pump is kept running while the valve slowly opens. be made to drain
Increasing proportion of the flow is diverted to waste the small volume of
with less passing through the check valve, until all water released with Singer model 106-DW
flow is diverted through the nearly fully open DW each operation Deep Well, Pump
Control valve
valve. The pipeline check valve closes quietly without
discharges back to
surges. When the DW valve is almost fully open, a sump or to waste
stem mounted cam triggers the limit switch to stop (atmosphere)
the pump.

148 2016.1
MODELS 106-DW / 206-DW
DEEP WELL PUMP CONTROL VALVE – DOUBLE CHAMBER

SCHEMATIC DRAWING SELECTION SUMMARY


1. Main Valve - 106-PT or 206-PT 1. The Singer model DW deep well pump control
valve is sized to ensure that the pump discharge
2. Closing speed control
pressure is less than the system static pressure
3. Strainer - 40 mesh stainless steel screen when the pump starts; that the main check
4. Isolation Valve valve will remain closed and no surges will be
generated.
5. Connection to the pipeline system side of header
check valve - complete in the field 2. From the pump performance curve, determine
the pump flow when the pressure at the pump
6. Exhaust to drain - complete in the field discharge is 80% of the static pressure against
7. Solenoid Valve - four way, NEMA 4 the check valve. When the pump is discharging at
8. Opening speed control full start-up flow, the combined losses of the DW
control valve, the piping and the discharge losses
9. Model X129 Limit Switch Assembly - must be less than 80% of the static pressure.
NEMA 4, SPDT
3. For pump control other than deep well
applications - by-pass control - the discharge
from the DW control valve can be returned to the
wet well, tank or even the pump suction header.
Providing there is sufficient static differential
pressure (e.g., 70 to 80% of the pumping
differential pressure) the DW control valve should
be considered preferable to a BPC, in-line booster
pump control valve because of reduced sizing
and operating benefits.
4. Refer to the 106 and 206 performance curves,
page 231, angle or globe style (straight lines) (see
Technical & Sizing Information section, page 231)
and select the smallest size with the pressure
drop that is acceptable. Bulletins 106-PT(C) and
206-PT(C) (see Main Valves section, page 28)
provide / specifications and details of construction
of the main valves. Standard configuration
provides for NEMA 4 watertight enclosures for
the Honeywell model OP-AR, SPDT limit switch
and the ASCO solenoid with 120 VAC / 60 Hz (or
220 VAC / 50 Hz or 240 VAC / 60 Hz) coil. For other
electrical service or higher pressure ratings consult
Schematic A-7514C with Singer Valve. A manual override is available
upon request. Other functions may be combined
with DW valves, e.g. model 106-DW-RPS, pump
control with pressure sustaining feature.

STANDARD MATERIALS ORDERING INSTRUCTIONS


Standard materials for pilot system components are: Refer to page 244 for the order form and ordering
• ASTM B-62 bronze or ASTM B-16 brass instructions.

• AISI 303 /316 stainless steel trim Additionally, include the following information for this
product:
Refer to Electronic Control section (SPC product), see
page 203, and consult Singer Valve for pump control 1. Double chamber (106) or (206)
panel options. 2. Solenoid voltage
3. Maximum inlet pressure

2016.1 149
MODELS 106-DW / 206-DW
DEEP WELL PUMP CONTROL VALVE – DOUBLE CHAMBER

Flow Coefficient Cv
106-DW (See 106-PT in Main Valve section for other valve data)
Size (inches) 2 in 2-1/2 in 3 in 4 in
Size ( mm) 50 mm 65 mm 80 mm 100 mm
Cv1 - Globe 55 80 110 200
Kv - Globe
2
13 19 26 47
Cv1 - Angle 61 90 135 230
Kv2 - Angle 15 21 32 55

Flow Coefficient Cv
106-DW
(See 106-PT in Main Valve section for other valve data)
Size (inches) 6 in 8 in 10 in 12 in 14 in 16 in 20 in 24 in
Size ( mm) 150 mm 200 mm 250 mm 300 mm 350 mm 400 mm 50 mm 600 mm
Cv1 - Globe 460 800 1300 2100 2575 3300 5100 7600
Kv2 - Globe 110 190 310 500 610 780 1210 1800
Cv1 - Angle 520 950 1400 2400 - 3000 - -
Kv2 - Angle 123 225 332 570 - 710 - -

Flow Coefficient Cv
206-DW (See 206-PT in Main Valve section for other valve data)
Size (inches) 4 in 6 in 8 in 10 in
Size ( mm) 100 mm 150 mm 200 mm 250 mm
Cv1 - Globe 150 250 505 985
Kv2 - Globe 36 60 120 230
Cv1 - Angle 150 250 580 -
Kv2 - Angle 36 60 138 -

Flow Coefficient Cv
206-DW
(See 206-PT in Main Valve section for other valve data)
Size (inches) 12 in 16 in 18 in 20 in 24 x 16 in 24 x 20 in 28 in 30 in 32 in 36 in
Size ( mm) 300 mm 400 mm 450 mm 500 mm 600 x 400 mm 600 x 500 mm 700 mm 750 mm 800 mm 900 mm
Cv1 - Globe 1550 2200 3300 3400 3500 5100 7800 7800 7900 8000
Kv2 - Globe 370 520 780 810 830 1210 1850 1850 1870 1900
Cv1 - Angle - - - - - - - - - -
Kv2 - Angle - - - - - - - - - -

*CV = USGPM at 1 psi pressure drop

**KV = L / s at 1 bar pressure drop

(Q=CV P )

150 2016.1
PUMP CONTROL

MODELS 106-HC / 206-HC


HYDRAULIC CHECK VALVE
KEY FEATURES
• Drip-tight seat
• Independently adjustable opening and closing speed controls

PRODUCT OVERVIEW
The 106-HC and 206-HC hydraulic check valves are based on the 106-
PG or 206-PG main valve. The valve functions as a two position valve
- either fully open or fully closed.
The HC allows one way flow only. Under normal forward flow, the
valve opens as the higher inlet pressure lifts the inner valve assembly
and the fluid in the upper chamber is discharged to the lower
pressure, downstream side of the valve.
When pressure is reversed, the now higher downstream pressure is
applied to the upper operating chamber as flow reversal occurs.
The diaphragm / inner valve assembly moves down and the valve
closes tightly.

TYPICAL APPLICATION
Primary use as a simple, effective way to start and
stop pumps without surges. No electrical supply or
interconnections required. Power failure shutdown is
the same as normal operation. Best used when the
pump is electric motor driven and has positive suction
head. A system relief valve is recommended for sizes Reservoir
6 in / 150 mm and larger or when velocities exceed 6 Tank
ft/s / 2 m/s.
Important Note:
To provide smooth “non-slam” shutdown when the
pump stops, the flow reverses for a short period. Singer Model 106-RPS Booster
Install with forward flow over the seat. Most pumps Pump
and motors can accept reverse rotation (consult
with pump manufacturer before selecting hydraulic
check valves). Engine drivers will be damaged by
reverse rotation - include a non-reverse clutch or Singer Model 106-HC
similar device. No other check or foot valves should
be installed to prevent reverse flow. When there
is suction lift on the pump inlet, a separate form
of priming is necessary. See BPC or DW valves for
alternate methods of starting or stopping flows
exceeding 13 f/s / 4 m/s).

2016.1 151
MODELS 106-HC / 206-HC
HYDRAULIC CHECK VALVE

SCHEMATIC DRAWING STANDARD MATERIALS


1. Main Valve 106-PG or 206-PG - “Flow Over Seat” Standard materials for pilot system components are:
2. Closing Speed Control • ASTM B-62 bronze or ASTM B-16 brass
3. Opening Speed Control • AISI 303 / 316 stainless steel trim
4. Swing Check Valve - opening
5. Swing Check Valve - closing SELECTION SUMMARY
1. Generally select size to minimize losses during
The standard valve is normally installed in a normal forward flow.
horizontal pipeline with the stem oriented vertically
up. Confirm other orientations before ordering. 2. Use the performance curves and sizing bulletin
(see Technical and Sizing Information Section
page 231) to check the pressure drop across
Type Pressure Rating* the valve at normal flow rate. Use the same
performance curves for flow over the seat or flow
300 SCR. 200 psi / 13.8 bar under
the seat.
150 FLG. 200 psi / 13.8 bar
3. Check the maximum operating pressure. The
300 FLG. 300 psi / 20.7 bar pilot system limits the rating.
4. Standard construction provides: 200 psi /
* Pressure ratings are limited by the choice of pilot 13.8 bar
components. 5. Rating for ANSI 150 flanged and NPT screwed
ends; 300 psi / 20.7 bar rating for ANSI 300
flanged. Consult Singer Valve for applications
requiring higher pressure ratings.

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering
instructions.
Additionally, include the following information for this
product:
Single chamber (106) or (206)

Schematic A-0422D

152 2016.1
MODELS 106-HC / 206-HC
HYDRAULIC CHECK VALVE

Flow Capacity
106-HC
(See 106-PG in Main Valve section for other valve data)
Size (inches) 1/2 in 3/4 in 1 in 1-1/4 in 1-1/2 in 2 in 2-1/2 in 3 in 4 in

Size (mm) 15 mm 19 mm 25 mm 32 mm 40 mm 50 mm 65 mm 80 mm 100 mm

Max. Continuous (USGPM) 12 19 49 93 125 210 300 460 800

Max. Continuous (L/s) 0.8 1 3 6 8 13 19 29 50

Flow Capacity
106-HC
(See 106-PG in Main Valve section for other valve data)

Size (inches) 6 in 8 in 10 in 12 in 14 in 16 in 20 in 24 in 36 in

Size (mm) 150 mm 200 mm 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm 900 mm

Max. Continuous (USGPM) 1800 3100 4900 7000 8500 11000 17500 25000 55470

Max. Continuous (L/s) 114 196 309 442 536 694 1104 1577 3500

Flow Capacity
206-HC
(See 206-PG in Main Valve section for other valve data)
Size (inches) 3 in 4 in 6 in 8 in 10 in 12 in 16 in 18 in 20 in

Size (mm) 80 mm 100 mm 150 mm 200 mm 250 mm 300 mm 400 mm 450 mm 500 mm

Max. Continuous (USGPM) 300 580 1025 2300 4100 6400 9230 16500 16500

Max. Continuous (L/s) 19 37 65 145 260 404 582 1040 1040

Flow Capacity
206-HC
(See 206-PG in Main Valve section for other valve data)

Size (inches) 24 x 16 in 24 x 20 in 28 in 30 in 32 in 36 in 40 in

Size (mm) 600 x 400 mm 600 x 500 mm 700 mm 750 mm 800 mm 900 mm 1000 mm

Max. Continuous (USGPM) 16500 21700 33600 33650 33700 33800 62000

Max. Continuous (L/s) 1040 1370 2120 2123 2126 2132 3912

2016.1 153
Our level control valves are the ideal solution for preventing overflow in tanks,
towers and reservoirs. Repeatable, reliable operation each and every time! Our
float valves directly control the maximum water level and our altitude valves
control water levels from ground level. Because we hate overflow as much as
you do.

Level Control Valves


LEVEL CONTROL

MODELS 106-A-TYPE 1 / 206-A-TYPE 1


TWO-WAY FLOW ALTITUDE CONTROL VALVE
KEY FEATURES
• No overflows
• Superior repeatability
• Positive shut-off
• Easily serviceable at ground level

PRODUCT OVERVIEW
The 106-A-Type 1 and 206-A-Type 1 altitude control valves are based on
the 106-PG or 206-PG main valve and are ideal for maintaining a preset
maximum water level.
The valve functions as a two position control valve, either fully open or
fully closed. The Type 1 allows normal forward flow to fill the reservoir to
the maximum level and then closes drip-tight at the set-point. It opens to
allow reverse flow through the valve when the supply pressure drops a
fixed amount below the reservoir head. When a higher supply pressure is
restored, the Type 1 valve will then allow normal forward flow to refill the
tank to the maximum level.

TYPICAL APPLICATION
Reservoir
tower

Sensing connected to drain line or to the reser-


voir directly (completed by others). Sensing line
minimum recommended size is 3/4 in / 20 mm.
Slope to avoid air pockets.

Drain

Provides connection
to drain for displaced
water from bonnet

Higher supply pressure


(e.g. from pumps) and
distribution to users Singer 106-A-1, Two-Way
Flow Altitude Control Valve

156 2016.1
MODELS 106-A-TYPE 1 / 206-A-TYPE 1
TWO-WAY FLOW ALTITUDE CONTROL VALVE

SCHEMATIC DRAWING STANDARD MATERIALS


1. Main Valve - 106-PG or 206-PG - with X107 Standard materials for pilot system components are:
position indicator • Ductile Iron
2. Isolation Valve • Stainless Steel
3. Strainer - 40 mesh stainless steel screen • Brass
4. Model 10 Check Valve • Copper
5. Closing Speed Control
6. Model 12 Check Valve SELECTION SUMMARY
7. Model 301-4 Altitude Pilot 1. Generally select line size to minimize losses
8. Altitude Gauge during normal forward flow.
9. Fixed Restriction - 1/8 in / 3.2 mm, 1/16 in / 2. Use the performance curves and sizing bulletin to
1.58 mm determine the pressure drop across the valve.
10. Union 3. Limit maximum continuous flow velocity to 20
11. Isolation Valve ft/s / 6 m/s for 106 and 16 ft/s / 5 m/s for 206.
Consult Singer Valve if higher flows are expected.
12. Connection to Reservoir - complete in field
4. The pilot system exhausts to atmosphere,
13. Model 12 Check Valve ensuring the valve opens fully; requires that the
14. Isolation Valve displaced volume of water be taken to drain with
each opening.
5. Select pilot spring range: 4 to 20 ft / 1 to 6 m; 10
to 60 ft / 3 to 18 m; 40 to 125 ft / 12 to 38 m; 60
to 220 ft / 18 to 67 m.
6. There is a non-adjustable differential required
between the reservoir head and the supply
pressure in order for the valve to open. It ranges
from 1 ft / 0.3 m to 3 ft / 0.90 m for the pilot
spring ranges listed.

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering
instructions.
Additionally, include the following information for this
product:
1. Single chamber (106) or (206)
2. Pilot range

Schematic A-0412D

2016.1 157
MODELS 106-A-TYPE 1 / 206-A-TYPE 1
TWO-WAY FLOW ALTITUDE CONTROL VALVE

Flow Coefficient Cv
106-A-Type 1
(See 106-PG in Main Valve section for other valve data)

Size (inches) 3 in 4 in 6 in 8 in

Size (mm) 80 mm 100 mm 150 mm 200 mm

Cv1 110 200 460 800

Kv2 26 47 110 190

Flow Coefficient Cv
106-A-Type 1
(See 106-PG in Main Valve section for other valve data)

Size (inches) 10 in 12 in 14 in 16 in 20 in 24 in 36 in

Size (mm) 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm 900 mm

Cv1 1300 2100 2575 3300 5100 7600 16340

Kv 2
310 500 610 780 1210 1800 3875

Flow Coefficient Cv
206-A-Type 1
(See 206-PG in Main Valve section for other valve data)

Size (inches) 3 in 4 in 6 in 8 in

Size (mm) 80 mm 100 mm 150 mm 200 mm

Cv1 60 150 250 505

Kv2 14 36 60 120

Flow Coefficient Cv
206-A-Type 1
(See 206-PG in Main Valve section for other valve data)

Size (inches) 10 in 12 in 16 in 18 in 20 in 24 x 16 in 24 x 20 in 28 in 30 in 32 in 36 in 40 in

Size (mm) 250 mm 300 mm 400 mm 450 mm 500 mm 600 x 400 mm 600 x 500 mm 700 mm 750 mm 800 mm 900 mm 1000 mm

Cv1 985 1550 2200 3300 3400 3500 5100 7800 7800 7900 8000 18000

Kv2 230 370 520 780 810 830 1210 1850 1850 1870 1900 4265

*CV = USGPM at 1 psi pressure drop

**KV = L / s at 1 bar pressure drop

(Q=CV P )

Note: based on fully open valve

158 2016.1
LEVEL CONTROL

MODELS 106-A-TYPE 2 / 206-A-TYPE 2


ONE-WAY FLOW ALTITUDE CONTROL VALVE

KEY FEATURES
• No overflows - high level shut-off maintained to close tolerances
• Superior repeatability
• Positive shut-off
• Easily serviceable at ground level

PRODUCT OVERVIEW
The 106-A-Type 2 and 206-A-Type 2 altitude control valves are based on the
106-PG or 206-PG main valve and are ideal for maintaining a preset maximum water level.
The valve functions as a two position control valve, either fully open or fully closed. The Type 2 valve allows
normal forward flow to fill the reservoir to the maximum level and then closes drip-tight at the set-point. It
opens to refill the tank once the level drops a fixed distance below the high water level.
Note: This valve does not operate as a check valve to prevent reverse flow.

TYPICAL APPLICATION

Non-adjustable
Reservoir drawdown
tank

Sensing connected to drain line or to the


reservoir directly (completed by others).
Sensing line minimum recommended size is
3/4 in / 20 mm. Slope to avoid air pockets. Drain

Distribution
to users

Provide connection to drain for


displaced water from bonnet
Higher pressure
supply
Singer 106-A-2, one-way flow
altitude control valve, with a
manual by-pass

2016.1 159
MODELS 106-A-TYPE 2 / 206-A-TYPE 2
ONE-WAY FLOW ALTITUDE CONTROL VALVE

SCHEMATIC DRAWING STANDARD MATERIALS


1. Main Valve - 106-PG or 206-PG - with X107 Standard materials for pilot system components are:
position indicator • Ductile Iron
2. Strainer - 40 mesh stainless steel screen • Stainless Steel
3. Model 301-4 Altitude Pilot • Brass
4. Closing Speed Control • Copper
5. Altitude Gauge
6. Isolation Valve SELECTION SUMMARY
7. Union 1. Generally select line size to minimize losses
8. Isolation Valve during normal forward flow.
9. Sensing connection to reservoir 2. Use the performance curves and sizing bulletin
(complete in field by others) to determine the pressure drop across the
10. Isolation Valve valve.
3. Maximum continuous flow - 106 is 20 ft/s / 6
m/s, 206 is 16 ft/s / 5 m/s. Consult Singer Valve if
higher flows are expected.
4. The pilot system exhausts to atmosphere
ensuring the valve opens fully; requires that the
displaced volume of water be taken to drain with
each opening.
5. Select pilot spring range. Standard (301-4) is 10 to
60 ft / 3 to 18 m. Specify for 301-4 ranges 4 to 20
ft / 1 to 6 m, 40 to 125 ft / 12 to 38 m, 60 to 220 ft
/ 18 to 67 m.
6. Level drop required to open: 1 ft to 3 ft / 0.3 m to
0.91 m approximate.
7 If the fill line discharges below the reservoir
surface, an internal drop check or separate check
valve is suggested. This prevents return flow on
loss of supply pressure.

Schematic A-0413C ORDERING INSTRUCTIONS


Refer to page 244 for the order form and ordering
instructions.
Additionally, include the following information for this
product:
1. Single chamber (106) or (206)
2. Pilot range

160 2016.1
MODELS 106-A-TYPE 2 / 206-A-TYPE 2
ONE-WAY FLOW ALTITUDE CONTROL VALVE

106-A-Type2 Flow Coefficient Cv (See 106-PG in Main Valve section for other valve data)

Size (inches) 3 in 4 in 6 in 8 in

Size (mm) 80 mm 100 mm 150 mm 200 mm

Cv1 110 200 460 800

Kv2 26 47 110 190

106-A-Type2 Flow Coefficient Cv (See 106-PG in Main Valve section for other valve data)

Size (inches) 10 in 12 in 14 in 16 in 20 in 24 in 36 in

Size (mm) 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm 900 mm

Cv1 1300 2100 2575 3300 5100 7600 16340

Kv2 310 500 610 780 1210 1800 3875

206-A-Type 2 Flow Coefficient CV (See 206-PG in Main Valve section for other valve data)

Size (inches) 3 in 4 in 6 in 8 in

Size (mm) 80 mm 100 mm 150 mm 200 mm

Cv1 60 150 250 505

Kv2 14 36 60 120

206-A-Type 2 Flow Coefficient Cv (See 206-PG in Main Valve section for other valve data)

Size (inches) 10 in 12 in 16 in 18 in 20 in 24 x 16 in 24 x 20 in 28 in 30 in 32 in 36 in 40 in

Size (mm) 250 mm 300 mm 400 mm 450 mm 500 mm 600 x 400 mm 600 x 500mm 700 mm 750 mm 800 mm 900 mm 1000 mm

Cv1 985 1550 2200 3300 3400 3500 5100 7800 7800 7900 8000 18000

Kv2 230 370 520 780 810 830 1210 1850 1850 1870 1900 4265

*CV = USGPM at 1 psi pressure drop

**KV = L / s at 1 bar pressure drop

(Q=CV P )

Note: based on fully open valve

2016.1 161
LEVEL CONTROL

MODELS 106-A-TYPE 3 / 206-A-TYPE 3


TWO-WAY FLOW ALTITUDE CONTROL VALVE WITH DIFFERENTIAL CONTROL
KEY FEATURES
• No overflows
• Superior repeatability while operating within close limits
• Positive shut-off

PRODUCT OVERVIEW
The 106-A-Type 3 and 206-A-Type 3 altitude control valves are based on
the 106-PG or 206-PG main valve, and are ideal for maintaining preset
maximum level.
The Type 3 allows normal forward flow to fill the reservoir to the maximum
level, then closes drip-tight at the set-point. The valve opens to permit
reverse flow through the valve when the supply pressure drops an
adjustable amount below the reservoir head.
The Type 3 will then allow normal forward flow to refill the tank to the maximum level, when a higher supply
pressure is restored.

TYPICAL APPLICATION

Reservoir tank / tower

Sensing connected to
drain line or to the reser-
voir directly (completed
by others).
Sensing line minimum
Singer 106-A-3, Two-Way Flow
recommended size is
Altitude Valve,with differential
3/4 in / 20 mm. Slope to
control, installed with a manual
avoid air pockets.
by-pass

Drain

Provides connection to
Higher pressure supply drain for displaced water
(e.g. from pumps) from bonnet
and distribution to users

162 2016.1
MODELS 106-A-TYPE 3 / 206-A-TYPE 3
TWO-WAY FLOW ALTITUDE CONTROL VALVEWITH DIFFERENTIAL CONTROL

SCHEMATIC DRAWING STANDARD MATERIALS


1. Main Valve - 106-PG or 206-PG - with X107 Standard materials for pilot system components are:
position indicator • Ductile Iron
2. Isolation Valve • Stainless Steel
3. Strainer - 40 mesh stainless steel screen
4. Model 10 Check Valve SELECTION SUMMARY
5. Closing Speed Control 1. Generally select line size to minimize losses
6. Model 625-RPD Differential Relief Pilot during normal forward flow.
7. Altitude Gauge 2. Use the performance curves to determine the
8. Isolation Valve pressure drop across the valve.

9. Sensing connection to reservoir - complete 3. Limit maximum continuous flow velocity to less
in field than 20 ft/s / 6 m/s for 106 and less than 16 ft/s /
5 m/s for 206.
10. Union
4. The pilot system exhausts to atmosphere
11. Fixed Restriction - 1/8 in / 3.2 mm ensuring the valve opens fully; requires that the
12. Model 301-4 Altitude Pilot; displaced volume of water be taken to drain with
each opening - refer to section 106-PG or 206-PG,
13. Isolation Valve
page 12, for displaced volume
5. Select pilot spring range. Standard (301-4) is 10 to
60 ft / 3 to 18 m. Specify for 301-4 ranges 4 to 20
ft / 1 to 6 m, 40 to 125 ft / 12 to 38 m, 60 to 220 ft
/ 18 to 67 m.
6. Select the adjustable differential pilot spring
range. Standard is 5 to 15 ft / 2 to 5 m. Specify for
12 to 30 ft / 3.7 to 9.1 m or 25 to 50 / 8 to 15 m.
The total differential includes the non-adjustable
differential of the altitude pilot.

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering
instructions.
Additionally, include the following information for this
product:
1. Single chamber (106) or (206)
2. Pilot ranges

Schematic A-0414D

2016.1 163
MODELS 106-A-TYPE 3 / 206-A-TYPE 3
TWO-WAY FLOW ALTITUDE CONTROL VALVEWITH DIFFERENTIAL CONTROL

Flow Coefficient Cv
106-A-Type3
(See 106-PG in Main Valve section for other valve data)
Size (inches) 3 in 4 in 6 in 8 in
Size (mm) 80 mm 100 mm 150 mm 200 mm

Cv1 110 200 460 800

Kv2 26 47 110 190

Flow Coefficient Cv
106-A-Type3
(See 106-PG in Main Valve section for other valve data)

Size (in) 10 in 12 in 14 in 16 in 20 in 24 in 36 in

Size (mm) 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm 900 mm

Cv1 1300 2100 2575 3300 5100 7600 16340

Kv2 310 500 610 780 1210 1800 3875

Flow Coefficient Cv
206-A-Type 3
(See 206-PG in Main Valve section for other valve data)
Size (inches) 3 in 4 in 6 in 8 in
Size (mm) 80 mm 100 mm 150 mm 200 mm

Cv1 60 150 250 505

Kv2 14 36 60 120

Flow Coefficient Cv
206-A-Type 3
(See 206-PG in Main Valve section for other valve data)

Size (in) 10 in 12 in 16 in 18 in 20 in 24 x 16 in 24 x 20 in 28 in 30 in 32 in 36 in 40 in

Size (mm) 250 mm 300 mm 400 mm 450 mm 500 mm 600 x 400 mm 600 x 500 mm 700 mm 750 mm 800 mm 900 mm 1000 mm

Cv1 985 1550 2200 3300 3400 3500 5100 7800 7800 7900 8000 18000

Kv 2
230 370 520 780 810 830 1210 1850 1850 1870 1900 4265

*CV = USGPM at 1 psi pressure drop

**KV = L / s at 1 bar pressure drop

(Q=CV P )

Note: based on fully open valve

164 2016.1
LEVEL CONTROL

MODELS 106-A-TYPE 4 / 206-A-TYPE 4


ONE-WAY FLOW ALTITUDE CONTROL VALVE WITH DIFFERENTIAL CONTROL
KEY FEATURES
• No overflows
• Adjustable draw-down level (differential) set-point
• Superior repeatability
• Positive shut-off
• Adjustable draw-down for improved water cycling

PRODUCT OVERVIEW
The 106-A-Type 4 and 206-A-Type 4 altitude control valves are based on
the 106-PG or 206-PG main valve, and are ideal for maintaining a preset
maximum water level. The valve functions as a two position control valve,
either fully open or fully closed.
The Type 4 allows normal forward flow to fill the reservoir to the maximum
level, then closes drip-tight at the set-point. It opens to refill the tank once
the level drops an adjustable amount below the high water level.
Distribution from the reservoir is through a separate pipeline.
Note: This valve does not operate as a check valve to prevent reverse flow.

TYPICAL APPLICATION

Maximum
(Closed)

Adjustable Drawdown
Reservoir
Tank
Minimum
(Open)

Singer 106-A-4, One-Way Flow Altitude Valve,


with Differential Control, installed with a Distribution to users
manual by-pass

Static Drain

Sensing connected to drain line or to the


reservoir directly (completed by others).
Sensing line minimum recommended size is
3/4 in / 20 mm. Slope to avoid air pockets.

Higher Pressure Supply Provide connection to drain for


e.g. from pumps displaced water from bonnet

2016.1 165
MODELS 106-A-TYPE 4 / 206-A-TYPE 4
ONE-WAY FLOW ALTITUDE CONTROL VALVE WITH DIFFERENTIAL CONTROL

SCHEMATIC DRAWING STANDARD MATERIALS


1. Main Valve - 106-PG or 206-PG - with X107 Standard materials for pilot system components are:
position indicator • Ductile Iron
2. Isolation Valve • Stainless Steel
3. Strainer - 40 mesh stainless steel screen • Brass
4. Closing Speed Control • Copper
5. Model 301-4 Altitude Pilot
6. Model 106-RD Differential Pilot SELECTION SUMMARY
7. Altitude Gauge - dual scale - feet and meter 1. Generally select line size to minimize losses
8. Isolation Valve during normal forward flow.
9. Sensing connection to reservoir - complete 2. Use the performance curves to determine the
in field pressure drop across the valve.
10. Model 10 Check Valve 3. Limit maximum continuous flow velocity to less
11. Union than 20 ft/s / 6 m/s for 106 and less than 16 ft/s /
5 m/s for 206.
12. Isolation Valve
4. The pilot system exhausts to atmosphere
ensuring the valve opens fully; requires that the
displaced volume of water be taken to drain with
each opening. Refer to section 106-PG or 206-PG,
page 12, for the displaced volume.
5. Select pilot spring range. Standard (301-4) is 10 to
60 ft / 3 to 18 m. Specify for 301-4 ranges 4 to 20
ft / 1 to 6 m, 40 to 125 ft / 12 to 38 m), 60 to 220 ft
/ 18 to 67 m.
6. Select differential pilot spring range. Standard
is 5 to 15 ft / 1.5 to 4.6 m and 10 to 50 ft / 3 to
15 m. Specify for 12 to 50 ft / 3.7 to 15 m. The
total differential includes the non-adjustable
differential of the altitude pilot.
7. If the fill line discharges below the reservoir
surface, an internal drop check or separate check
valve is suggested. This prevents return flow on
loss of supply pressure.

Schematic A-0415C
ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering
instructions.
Additionally, include the following information for this
product:
1. Single chamber (106) or (206)
2. Pilot range

166 2016.1
MODELS 106-A-TYPE 4 / 206-A-TYPE 4
ONE-WAY FLOW ALTITUDE CONTROL VALVE WITH DIFFERENTIAL CONTROL

Flow Coefficient Cv
106-A-Type 4
(See 106-PG in Main Valve section for other valve data)

Size (inches) 3 in 4 in 6 in 8 in

Size (mm) 80 mm 100 mm 150 mm 200 mm

Cv1 110 200 460 800

Kv2 26 47 110 190

Flow Coefficient Cv
106-A-Type 4
(See 106-PG in Main Valve section for other valve data)

Size (inches) 10 in 12 in 14 in 16 in 20 in 24 in 36 in

Size (mm) 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm 900 mm

Cv1 1300 2100 2575 3300 5100 7600 16340

Kv2 310 500 610 780 1210 1800 3875

Flow Coefficient Cv
206-A-Type 4
(See 206-PG in Main Valve section for other valve data)

Size (inches) 3 in 4 in 6 in 8 in

Size (mm) 80 mm 100 mm 150 mm 200 mm

Cv1 60 150 250 505

Kv2 14 36 60 120

Flow Coefficient Cv
206-A-Type 4
(See 206-PG in Main Valve section for other valve data)

Size (inches) 10 in 12 in 16 in 18 in 20 in 24 x 16 in 24 x 20 in 28 in 30 in 32 in 36 in 40 in

Size (mm) 250 mm 300 mm 400 mm 450 mm 500 mm 600 x 400 mm 600 x 500 mm 700 mm 750 mm 800 mm 900 mm 1000 mm

Cv1 985 1550 2200 3300 3400 3500 5100 7800 7800 7900 8000 18000

Kv2
230.0 370.0 520.0 780.0 810.0 830.0 1210.0 1850.0 1850.0 1870.0 1900.0 4265

*CV = USGPM at 1 psi pressure drop

**KV = L / s at 1 bar pressure drop

(Q=CV P )

Note: based on fully open valve

2016.1 167
LEVEL CONTROL

MODELS 106-F-TYPE 4 / 206-F-TYPE 4


MODULATING FLOAT VALVE
KEY FEATURES
• Maintains relatively constant level
• Automatic compensation for level draw-down
• Standard integral damping reduces hunting
• Drip-tight at high level shut-off
• Low supply pressure options

PRODUCT OVERVIEW
The Singer model 106-F-Type 4 and 206-F-Type 4 modulating float valves are based on the 106-PG or 206-PG
main valve. They are ideal for balancing the inflow and outflow demand into the reservoir and maintaining level
at the designated maximum.
The valve closes drip-tight at the maximum level and modulates to maintain the tank level. The float pilot is
remotely installed at the high level in the reservoir tank. Pilot connections to the main valve are connected in the
field. As the reservoir level drops the main valve is opened proportionally to increase the filling rate. Movement
of the main stem alters the size of the closing restriction, interrupting the tendency of the valve to hunt.

TYPICAL APPLICATION

R400 pilot

Singer 106-F-Type 4

Tubing supplied by others.

168 2016.1
MODELS 106-F-TYPE 4 / 206-F-TYPE 4
MODULATING FLOAT VALVE

SCHEMATIC DRAWING STANDARD MATERIALS


1. Main Valve - 106-PG or 206-PG, Internal Needle Standard materials for pilot system components are:
Stem Valve (INSV) built into stem • Stainless Steel
2. Isolation Valve • Plastic float
3. Strainer - 40 mesh stainless steel screen • Brass, Copper, Iron
4. Isolation Valve Note: The stilling well and the connections between
5. R400 Float Pilot comes with plastic float the main valve and the R-400 pilot are provided
by others.
Note: Schematic shown for 2.5 in / 65 mm and larger
For 2 in / 50 mm and smaller, refer to Schematic
A-0399C.
SELECTION SUMMARY
1. Generally select line size to minimize losses
during normal forward flow.
2. Use the performance curves and sizing bulletin
to check the pressure drop across the valve at
normal flow rate.
3. Check the maximum operating pressure against
the maximum working pressure rating of
the flanges.
4. If the outlet pressure is less than 35% of the inlet
pressure, check for cavitation.
5. If the inlet pressure is less than 10 psi / 0.7 bar
higher than the maximum reservoir head, consult
with Singer Valve.
6. Assisted opening may be required for full flow.
Schematic A-0608D - for non-modulating (on-off) service, refer to
model 106-F-Type 5 / 206-F-Type 5 float valve
- f or high tower reservoir, refer to models
106-A-Type 1 / 206-A-Type 1, or 2, or 3, or 4
Altitude Control valves.

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering
instructions.
Additionally, include the following information for this
product:
Single chamber (106) or (206)

2016.1 169
MODELS 106-F-TYPE 4 / 206-F-TYPE 4
MODULATING FLOAT VALVE

106-F-Type 4 Flow Capacity (See 106-PG in Main Valve section for other valve data)

Size (inches) 1/2 in 3/4 in 1 in 1-1/4 in 1-1/2 in 2 in 2-1/2 in 3 in 4 in

Size (mm) 15 mm 19 mm 25 mm 32 mm 40 mm 50 mm 65 mm 80 mm 100 mm

Maximum Continuous (USGPM) 12 19 49 93 125 210 300 460 800

Maximum Continuous (L/s) 0.8 1 3 6 8 13 19 29 50

Pressure Drop (PSI) 20 20 20 15 15 20 15 16 15

Pressure Drop (Bar) 1.4 1.4 1.4 1.0 1.0 1.4 1 1.1 1.0

106-F-Type 4 Flow Capacity (See 106-PG in Main Valve section for other valve data)

Size (inches) 6 in 8 in 10 in 12 in 14 in 16 in 20 in 24 in 36 in

Size (mm) 150 mm 200 mm 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm 900 mm

Maximum Continuous (USGPM) 1800 3100 4900 7000 8500 11000 17500 25000 55470

Maximum Continuous (L/s) 114 196 309 442 536 694 1104 1577 3500

Pressure Drop (PSI) 15 15 15 16 11 17 8.6 9.6 8.6

Pressure Drop (Bar) 1.0 1.0 1.0 1.1 0.8 1.2 0.6 0.7 0.6

206-F-Type 4 Flow Capacity (See 206-PG in Main Valve section for other valve data)

Size (inches) 3 in 4 in 6 in 8 in 10 in 12 in 16 in 18 in 20 in

Size (mm) 80 mm 100 mm 150 mm 200 mm 250 mm 300 mm 400 mm 450 mm 500 mm

Maximum Continuous (USGPM) 300 580 1025 2300 4100 6400 9230 16500 16500

Maximum Continuous (L/s) 19 37 65 145 260 404 582 1040 1040

Pressure Drop (PSI) 19 15 17 21 17 17 18 23 22

Pressure Drop (Bar) 1.3 1.0 1.2 1.4 1.2 1.2 1.2 1.6 1.5

206-F-Type 4 Flow Capacity (See 206-PG in Main Valve section for other valve data)

Size (inches) 24 x 16 in 24 x 20 in 28 in 30 in 32 in 36 in 40 in

Size (mm) 600 x 400 mm 600 x 500 mm 700 mm 750 mm 800 mm 900 mm 1000 mm

Maximum Continuous (USGPM) 16500 21700 33600 33650 33700 33800 55470

Maximum Continuous (L/s) 1040 1370 2120 2123 2126 2132 3500

Pressure Drop (PSI) 21 21 17 17 17 17 17

Pressure Drop (Bar) 1.4 1.4 1.2 1.2 1.2 1.2 1.2

170 2016.1
LEVEL CONTROL

MODELS 106-F-TYPE 5 / 206-F-TYPE 5


NON-MODULATING FLOAT VALVE
KEY FEATURES
• No overflow, drip-tight close
• Adjustable draw down
• Easily adjustable level settings
• Low supply pressure options

PRODUCT OVERVIEW
The 106-F-Type 5 and 206-F-Type 5 non-modulating float valves are based on the 106-PG or 206-PG main valve.
It is ideal for allowing normal forward flow to fill water reservoirs to a desired high level and where the pilot and
valve of the reservoirs are easily accessible.
The valve functions as a two position valve, either open or closed. The valve remains closed when the reservoir
level drops, until the float reaches the pre-determined adjustable minimum reservoir level. The F-Type 5 valve
then opens to refill the reservoir and closes tightly when high water level is achieved.

TYPICAL APPLICATION
Non-modulating float valves are typically used in buildings with reservoir tanks or installations where the
valve and pilot are readily accessible.
The on / off service ensures that the reservoir contents are cycled. It will also prevent over cycling of the
supply pumps as the minimum quantity per cycle is adjustable.

Model 43 float
pilot with 4 ft /
1.2 m SST rod
and float

Singer model 106-F-Type 5


Non-Modulating Float Valve

Note:
Per illustration, Float Valves greater than 4 in / 100 mm cannot be positioned
on its side.

2016.1 171
MODELS 106-F-TYPE 5 / 206-F-TYPE 5
NON-MODULATING FLOAT VALVE

SCHEMATIC DRAWING STANDARD MATERIALS


1. Main Valve - 106-PG or 206-PG Standard materials for pilot system components are:
2. Isolation Valve • ASTM B-62 bronze or ASTM B-16 brass
3. Strainer - 40 mesh stainless steel screen • Copper float
4. Opening / Closing Speed Control Note: The stilling well and the connections between
5. Model 43 Float Pilot c/w SST float, main valve and pilot completed by others.
4 ft / 1.2 m SST rod
SELECTION SUMMARY
1. Generally select line size to minimize losses
during normal forward flow - see chart of
maximum continuous flow below.
2. Use the performance curves and sizing bulletin to
determine the pressure drop across the valve at
normal flow rate.
3. Check the maximum operating pressure against
the maximum working pressure rating
Stilling
of the flanges.
Well
4. For pressures greater than 80 psi / 5.5 bar,
consult factory
 .
5 If the outlet pressure is less than 35% of the
inlet pressure, check for cavitation.
Schematic A-0421C 6. If the inlet pressure is less than 10 psi / 0.70 bar
higher than the reservoir head, consult with
Singer Valve. Assisted opening may be required
for full flow.
 – T
 o maintain a relatively steady tank level,
refer to model 106-F-Type 4 / 206-F-Type 4:
Modulating Float Valve, see page 166.
– f or SCADA or electronic level control, refer
to model 106-2SC-PCO / 206-2SC-PCO Dual
Solenoid Control Valve

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering
instructions.
Additionally, include the following information for this
product:
1. Single chamber (106) or (206)
2. Pilot range

172 2016.1
MODELS 106-F-TYPE 5 / 206-F-TYPE 5
NON-MODULATING FLOAT VALVE

Flow Capacity
106-F-Type 5
(See 106-PG in Main Valve section for other valve data)
Size (inches) 1/2 in 3/4 in 1 in 1-1/4 in 1-1/2 in 2 in 2-1/2 in 3 in 4 in

Size (mm) 15 mm 19 mm 25 mm 32 mm 40 mm 50 mm 65 mm 80 mm 100 mm

Maximum Continuous (USGPM) 12 19 49 93 125 210 300 460 800

Maximum Continuous (L/s) 0.8 1 3 6 8 13 19 29 50

Pressure Drop (PSI) 20 20 20 15 15 20 15 16 15

Pressure Drop (Bar) 1.4 1.4 1.4 1.0 1.0 1.4 1 1.1 1.0

Flow Capacity
106-F-Type 5
(See 106-PG in Main Valve section for other valve data)

Size (inches) 6 in 8 in 10 in 12 in 14 in 16 in 20 in 24 in 36 in

Size (mm) 150 mm 200 mm 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm 900 mm

Maximum Continuous (USGPM) 1800 3100 4900 7000 8500 11000 17500 25000 55470

Maximum Continuous (L/s) 114 196 309 442 536 694 1104 1577 3500

Pressure Drop (PSI) 15 15 15 16 11 17 8.6 9.6 8.6

Pressure Drop (Bar) 1.0 1.0 1.0 1.1 0.8 1.2 0.6 0.7 0.6

Flow Capacity
206-F-Type 5
(See 206-PG in Main Valve section for other valve data)
Size (inches) 3 in 4 in 6 in 8 in 10 in 12 in 16 in 18 in 20 in

Size (mm) 80 mm 100 mm 150 mm 200 mm 250 mm 300 mm 400 mm 450 mm 500 mm

Maximum Continuous (USGPM) 300 580 1025 2300 4100 6400 9230 16500 16500

Maximum Continuous (L/s) 19 37 65 145 260 404 582 1040 1040

Pressure Drop (PSI) 19 15 17 21 17 17 18 23 22

Pressure Drop (Bar) 1.3 1.0 1.2 1.4 1.2 1.2 1.2 1.6 1.5

Flow Capacity
206-F-Type 5
(See 206-PG in Main Valve section for other valve data)

Size (inches) 24 x 16 in 24 x 20 in 28 in 30 in 32 in 36 in 40 in

Size (mm) 600 x 400 mm 600 x 500 mm 700 mm 750 mm 800 mm 900 mm 1000 mm

Maximum Continuous (USGPM) 16500 21700 33600 33650 33700 33800 55470

Maximum Continuous (L/s) 1040 1370 2120 2123 2126 2132 3500

Pressure Drop (PSI) 21 21 17 17 17 17 17

Pressure Drop (Bar) 1.4 1.4 1.2 1.2 1.2 1.2 1.2

2016.1 173
Want to allow flow to meet a predetermined demand? How about limiting the
flow to a pre-set maximum? Or, preventing water loss from a catastrophic
downstream pipe break? Never fear. Our flow control valves are here.

Flow Control Valves


FLOW CONTROL

MODELS 106-RF / 206-RF


FLOW LIMITING CONTROL VALVE

KEY FEATURES
• Accurately limits flow to a pre-set maximum
• Easily adjustable flow limit
• Paddle-style orifice plate included
• Optional orifice plate housing

PRODUCT OVERVIEW TYPICAL APPLICATION


The 106-RF and 206-RF flow limiting control valves
are based on the 106-PG or 206-PG main valves. The Storage Tank
valve is ideal for limiting the flow to a pre-determined
maximum (via maintaining a continuous pressure Standard paddle style orifice
differential across an orifice). plate
When the pressure differential is less than the - install between downstream
flanges and connect pilot
set-point, the valve opens, allowing flow to meet
sensing to downstream tap
pre-determined demand. At the desired maximum in pipeline
set-point, the pilot reacts to small changes in sensing - completed in field by others
pressure and controls the main valve position by
modulating the pressure above the diaphragm.
When the pressure drop across the orifice exceeds
the set-point, the valve closes slightly, limiting the flow Isolation valve
to the pre-set maximum. The orifice is usually sized to
generate a pressure differential of 3 to 5 psi / 0.2 to
0.35 bar at the desired flow. Adjusting the pilot setting Singer Valve model 106-RF
permits the maximum flow to be changed in the field or model 206-RF
above or below the original point.

176 2016.1
MODELS 106-RF / 206-RF
FLOW LIMITING CONTROL VALVE

SCHEMATIC DRAWING STANDARD MATERIALS


1.  Main Valve - 106-PG or 206-PG with X107 Standard materials for pilot system components are:
position indicator
• ASTM B62 bronze or ASTM B-16 brass
2. Isolation Valves (2A, 2B, 2C) standard
• Stainless steel
3. Strainer - 40 mesh - standard on all sizes
• Copper
4.  Model 26 Flow Stabilizer
• Standard on valves 8 in / 200 mm 106,
10” / 250 mm 206 SELECTION SUMMARY
5. Fixed Restriction 1. Determine the flow range and limit (setting) for
the application - standard range 2:1 -
6. Orifice Plate - paddle style - fits inside
maximum to minimum.
bolt pattern
2. Determine the pressure drop available to provide
7.  Model 160-RF Rate of Flow Pilot - specify for
control at the flow limit - valve plus orifice losses.
2 to 20 psi / 0.138 to 1.38 bar; 25 to 50 psi / 1.72
to 3.4 bar 3. For the most positive control, the orifice is sized
in combination with the valve to use the full
8.  1/2 in / 15 mm Ball valve and Flare fittings - for
pressure drop available at the maximum
downstream connection of sensing line to header
flow setting.
- field install
4. To calculate the pressure drop across the orifice,
9.  3/8 in / 10 mm Sensing Tubing - supply and
use the formula P = 3 psi (Qmax/Qmin)2.
installation by others
3 psi / 0.2 bar is a standard minimum but 2 psi
10. Optional: Closing Speed Control - model 852-B / 0.138 bar is acceptable if necessary. With the
11. Optional: Orifice Plate and Housing Assembly orifice plate designed for a 2:1 flow adjustment
(not shown) range, the orifice loss would then range from 3 to
12 psi / 0.2 to 0.8 bar.
Note: SRD shown is available for 6” 106-PG and larger. 5. Use the performance curves (see Technical &
Sizing Information section, page 231, and / or
the chart above, to determine the valve size
with sufficient capacity, with the pressure drop
available. Consult with Singer Valve for precise
orifice plate calculations.

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering
instructions.
Additionally, include the following information for this
product:
1. Single chamber (106) or (206)
INLET
2. Pilot range

Schematic A-7427C

When the optional orifice plate and housing assembly (item


11) is included, the overall laying length of the valve as-
sembly increases. Add 1 1/4 in / 32 mm to the published ‘A’
dimension for the valve model and size. The assembly is
provided with a full face gasket, but bolts, nuts and washers
are to be provided by others.

2016.1 177
MODELS 106-RF / 206-RF
FLOW LIMITING CONTROL VALVE

Flow Coefficient
106-RF
(See 106-PG in Main Valve section for other valve data)

Size (inches) 1/2 in 3/4 in 1 in 1-1/4 in 1-1/2 in 2 in 2-1/2 in 3 in 4 in

Size (mm) 15 mm 19 mm 25 mm 32 mm 40 mm 50 mm 65 mm 80 mm 100 mm

Maximum Continuous (USGPM) 125 210 300 460 800


Not available in these sizes
Maximum Continuous (L/s) 8 13 19 29 50

Flow Coefficient Cv
206-RF
(See 206-PG in Main Valve section for other valve data)

Size (inches) 3 in 4 in 6 in 8 in 10 in 12 in 16 in 18 in 20 in

Size (mm) 80 mm 100 mm 150 mm 200 mm 250 mm 300 mm 400 mm 450 mm 500 mm

Maximum Continuous (USGPM) 300 580 1025 2300 4100 6400 9230 16500 16500

Maximum Continuous (L/s) 19 37 65 145 260 404 582 1040 1040

Flow Capacity
106-RF
(See 106-PG in Main Valve section for other valve data)

Size (inches) 6 in 8 in 10 in 12 in 14 in 16 in 20 in 24 in 36 in

Size (mm) 150 mm 200 mm 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm 900 mm

Maximum Continuous (USGPM) 1800 3100 4900 7000 8500 11000 17500 25000 55470

Maximum Continuous (L/s) 114 196 309 442 536 694 1104 1577 3500

Flow Capacity
206-RF
(See 206-PG in Main Valve section for other valve data)

Size (inches) 24 x 16 in 24 x 20 in 28 in 30 in 32 in 36 in 40 in

Size (mm) 600 x 400 mm 600 x 500 mm 700 mm 750 mm 800 mm 900 mm 1000 mm

Maximum Continuous (USGPM) 16500 21700 33600 33650 33700 33800 62000

Maximum Continuous (L/s) 1040 1370 2120 2123 2126 2132 3912

178 2016.1
FLOW CONTROL

MODELS 106-EF-8837BX / 206-EF-8837BX


EXCESS FLOW (BURST CONTROL) VALVE

KEY FEATURES
• Tight shut-off when flow exceeds a pre-determined amount
• Manual re-activation required after failure
• “Failure Signal” options available

PRODUCT OVERVIEW TYPICAL APPLICATION


The 106-EF-8837BX and 206-EF-8837BX excess flow
valves are based on the 106-PT and 206-PT Double
Reservoir
Chamber main valves. The valve is designed to
shut-off tightly when flow exceeds a pre-determined
amount.
The 625-RPD pilot senses the pressure drop of the
valve and closes the valve when the tripping flow is Excess Flow Valve
reached. Typical pressure drop at tripping is 5 psi /
0.35 bar.
Tripping flow is adjusted by limiting the valve opening
with the X102 Stroke Limiter. 10 psi / 0.7 bar inlet
pressure must be maintained at the valve inlet when
the valve has tripped to prevent self re-setting. This
valve closes fast and from a significant velocity. If the
upstream pipe is longer than 2,000 ft / 600 m, closing
speed control should be included. When tripped
(closed), this valve has a continuous exhaust of about
1 GPM / 0.063 L/sec to drain.

2016.1 179
MODELS 106-EF-8837BX / 206-EF-8837BX
EXCESS FLOW (BURST CONTROL) VALVE

SCHEMATIC DRAWING SELECTION SUMMARY


1. Model 106-PT-EF / 206-PT-EF Main Valve c/w X102 1. Confirm that the application calls for a valve
Stroke Limiter that closes and remains closed if the flow
2. Strainer momentarily exceeds the set-point, regardless of
what the cause of the high flow is.
3. Model 625-RPD Normally Closed Pilot
2. Using sizing charts for fully open valves, select
4. Fixed Restriction - 1/16 in / 1.6 mm (4A, 4B) a valve size and model that has a higher flow
5. Check Valve at 5 psi / 0.345 bar pressure drop than any
anticipated tripping flow. Consider both 106 and
206 style valves. Avoid over-sizing.
3. Remember that this valve closes fast and from a
significant velocity. Closing Speed Control
may be required.
4. A drain may be required in chamber due to
continuous exhaust when valve has tripped.
5. Ensure that flange pressure rating exceeds
maximum operating pressure.

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering
instructions.
Additionally, include the following information for this
product:
Tripping flow

Schematic A-8837BX

180 2016.1
MODELS 106-EF-8837BX / 206-EF-8837BX
EXCESS FLOW (BURST CONTROL) VALVE

Flow Capacity
106-EF
(See 106-PT in Main Valve section for other valve data)
Size (inches) 3 in 4 in 6 in 8 in 10 in
Size (mm) 80 mm 100 mm 150 mm 200 mm 250 mm
Maximum tripping (USGPM) 250 440 1000 1700 2700
Maximum tripping (L/s) 16 28 63 107 170

Flow Capacity
206-EF
(See 206-PT in Main Valve section for other valve data)
Size (inches) 3 in 4 in 6 in 8 in 10 in 12 in
Size (mm) 80 mm 100 mm 150 mm 200 mm 250 mm 300 mm
Maximum tripping (USGPM) 135 320 560 1100 2200 3400
Maximum tripping (L/s) 9 20 35 69 139 215

2016.1 181
The secret of many of our valve solutions lies with their electronic control
capability. Whether it’s through radio, direct wire connections, cellular
networks, satellite or telephone lines, our electronic control management
products interface seamlessly and effortlessly with SCADA. Have a single
process application? Need to control multiple processes? We customize
solutions to meet the demands of unique applications.

For complete specifications on electronics products, please refer to the


Electronic Control Solutions Catalogue.

Electronic Control
ELECTRONIC CONTROL

MODELS 106-SC / 206-SC


SOLENOID CONTROL VALVE

KEY FEATURES
• Positive, drip-tight shut-off
• Simple, on-off operation
• Globe or angle style body

PRODUCT OVERVIEW
Singer models 106-SC and 206-SC solenoid control valves are based on
the Singer model 106-PG or 206-PG main valve. The solenoid control
valve provides on-off position operation. The solenoid either admits
inlet pressure into the main valve operating chamber or releases pressure from the operating chamber. The pilot
system is usually piped to discharge at the valve outlet, but can be piped to discharge to drain (atmosphere). This
valve is available either with the main valve closed when the solenoid is de-energized (NC - Normally Closed) or
with the main valve open when the solenoid is de-energized (NO- Normally Open). (NC or NO refers to the main
valve, not the solenoid.)

TYPICAL APPLICATION

Timer on truck fill station


Tank level control

Singer model 106-SC or


206-SC solenoid control valve

184 2016.1
MODELS 106-SC / 206-SC
SOLENOID CONTROL VALVE

SCHEMATIC DRAWING SELECTION SUMMARY


1. Main Valve - 106-PG or 206-PG 1. Select the valve with sufficient capacity, using the
2. Isolating Valves - (2A, 2B, 2C - (optional on 3 in / allowable operating pressure drop across
80 mm and smaller). the valve.

3. Strainer - 40 mesh stainless steel screen 2. If the outlet pressure is less than 35% of the inlet
pressure, check for cavitation.
4. Closing Speed Control - model 852-B (optional on
3 in / 80 mm and smaller). 3. Ensure the maximum working pressure rating of
the valve exceeds the maximum
5. Solenoid Pilot Valve - 3 way - operating pressure.
120 VAC / 60 Hz standard, other voltages
available 4. Continuous, “C”, service up to 20 ft /s / 6 m/s
is generally suitable. Refer to chart and/or
6. Opening Speed Control - model 852-B (optional performance curves (see Technical & Sizing
on 3 in / 80 mm and smaller). Information section, page 231).
5. Provide system maximum and minimum
operating pressures, electrical voltage, etc for
correct solenoid selection.
6. If control fluid is from a separate source, provide
Singer Valve with details.
-F or valve positioning - process control, see
section 2SC-PCO, Dual Solenoid Control Valve,
page 185.
- For two (2) stage opening or closing, consult
with Singer Valve.
- Most pilot functions may be combined with the
model SC, consult Singer Valve.

ORDERING INSTRUCTIONS
Schematic A-0593C Refer to page 244 for the order form and ordering
instructions.
1 Single chamber (106) or (206)
2. Solenoid voltage

STANDARD MATERIALS 3.

Energize or de-energize solenoid to close
main valve
Standard materials for pilot system components are:
• ASTM B62 bronze or ASTM B-16 brass
• Stainless steel trim
• Standard solenoid coil is rated as NEMA 1, 2, 3, 3S,
4 and 4X, combination general purpose and
watertight
• Other voltages, ratings and constructions are
available, consult with Singer Valve.

2016.1 185
MODELS 106-SC / 206-SC
SOLENOID CONTROL VALVE

Flow Capacity
106-SC
(See 106-PG in Main Valve section for other valve data)
Size (inches) 1/2 in 3/4 in 1 in 1-1/4 in 1-1/2 in 2 in 2-1/2 in 3 in 4 in
Size (mm) 15 mm 19 mm 25 mm 32 mm 40 mm 50 mm 65 mm 75 mm 100 mm
Minimum (USGPM) Fflat Diaphragm 1 1 1 1 1 5 5 5 10
Minimum (L/s) Flat Diaphragm 0.1 0.1 0.1 0.1 0.1 0.3 0.3 0.3 0.6
Maximum Continuous (USGPM) 12 19 49 93 125 210 300 460 800
Maximum Continuous (L/s) 0.8 1 3 6 8 13 19 29 50

Flow Capacity
106-SC
(See 106-PG in Main Valve section for other valve data)
Size (inches) 6 in 8 in 10 in 12 in 14 in 16 in 20 in 24 in 36 in
Size (mm) 150 mm 200 mm 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm 900 mm
Minimum (USGPM) Flat Diaphragm 20 40 - - - - - - -
Minimum (USGPM) Rolling Diaphragm 1 1 3 3 3 3 10 10 20
Minimum (L/s) Flat Diaphragm 1.3 2.5 - - - - - - -
Minimum (L/s) Rolling Diaphragm 0.1 0.1 0.2 0.2 0.2 0.2 0.6 0.6 1.3
Maximum Continuous (USGPM) 1800 3100 4900 7000 8500 11000 17500 25000 55470
Maximum Continuous (L/s) 114 196 309 442 536 694 1104 1577 3500

Flow Capacity
206-SC
(See 206-PG in Main Valve section for other valve data)
Size (inches) 3 in 4 in 6 in 8 in 10 in 12 in 16 in 18 in 20 in
Size (mm) 80 mm 100 mm 150 mm 200 mm 250 mm 300 mm 400 mm 450 mm 500 mm
Minimum (USGPM) Flat Diaphrgam 5 5 10 20 40 - - - -
Minimum (USGPM) Rolling Diaphrgam - - - - - 3 3 3 3
Minimum (L/s) Flat Diaphragm 0.3 0.3 0.6 1.3 2.5 - - - -
Minimum (L/s) Rolling Diaphragm - - - - - 0.2 0.2 0.2 0.2
Maximum Continuous (USGPM) 300 580 1025 2300 4100 6400 9230 16500 16500
Maximum Continuous (L/s) 19 37 65 145 260 404 582 1040 1040

Flow Capacity
206-SC
(See 206-PG in Main Valve section for other valve data)
Size (inches) 24 x 16 in 24 x 20 in 28 in 30 in 32 in 36 in 40 in
600 x 400 600 x 500
Size (mm) 700 mm 750 mm 800 mm 900 mm 1000 mm
mm mm
Minimum (USGPM) Rolling Diaphragm 3 3 10 10 10 10 20
Minimum (L/s) Rolling Diaphragm 0.2 0.2 0.6 0.6 0.6 0.6 1.3
Maximum Continuous (USGPM) 16500 21700 33600 33650 33700 33800 62000
Maximum Continuous (L/s) 1040 1370 2120 2123 2126 2132 3912

186 2016.1
ELECTRONIC CONTROL

MODELS 106-2SC-PCO / 206-2SC-PCO


DUAL SOLENOID CONTROL FOR POSITIONING AND SCADA CONTROLS

KEY FEATURES
• Precise control from remote locations
• Process controller compatible
• Minimal power needed for stand-by operation
• Complete service in-line
• Manual controls for emergencies

PRODUCT OVERVIEW TYPICAL APPLICATION


The Singer models 106-2SC-PCO and 206-2SC-PCO The two pilot solenoids are operated to keep two
dual solenoid electronic valves are based on the independent signals matched. In this case, the valve
Singer model 106-PG or 206-PG main valve. is operated to ensure the “process variable signal”
The flow into and out of the upper operating chamber follows the “SCADA set-point command signal”.
is controlled by the two pilot solenoids. The electronic Typically this mode is used when the process variable
control determines whether the opening solenoid signal is from a flow meter, pressure sensor or
or the closing solenoid is operated. The change in similarly quick changing process. This is referred to as
valve position is dependent upon which solenoid is “set-point control”.
operated and the duration of the energized period.
The electronic control determines the valve function.
Virtually any hydraulic function can be achieved using Singer model
the “open-close” output from the SCADA controller to SCP-TP controller
the valve.
The Singer Model 2SC-PCO is designed for use with
Singer MCP Multi-Process Control Panel or the EPC
Single-Process Control Panel.
4-20 mA
SCADA
set-point
signal

Pressure transmitter

Singer model 106-2SC-PCO


dual solenoid control valve

2016.1 187
MODELS 106-2SC-PCO / 206-2SC-PCO
DUAL SOLENOID CONTROL FOR POSITIONING AND SCADA CONTROLS

SCHEMATIC DRAWING STANDARD MATERIALS


1. Main Valve - 106-PG or 206-PG Standard materials for pilot system components are:
2. Isolating Valves - (2A, 2B, 2C) • ASTM B-16 brass
3. Strainer - 40 mesh stainless steel screen • AISI 316 or 18-8 stainless steel trim
4. Closing Speed Control - micrometer needle valve • NEMA 4X rated solenoid coils
5. Closing Solenoid Pilot Valve -
120 VAC / 60 Hz standard, other voltages
available
SELECTION SUMMARY
1. Select a valve with sufficient capacity, using the
6. Opening Solenoid Pilot Valve - allowable operating pressure drop across the
120 VAC / 60 Hz standard, other voltages valve.
available
2. Usually operating in the continuous, “C”, service
7. Manual Closing Bypass range up to 20 ft /s / 6 m / s - (refer Technical &
8. Manual Opening Bypass Sizing Section, page 231).
9. Opening Speed Control - micrometer 3. If the outlet pressure is less than 35% of the inlet
needle valve pressure, check for cavitation.
10*. Optional X156 Analog Position Transmitter 4. Ensure the max working pressure rating of the
(4 to 20 mA) valve exceeds the max operating pressure.
5. Ensure the solenoid coils are compatible with the
*Note*: All 106 series 2 1/2 in / 65 mm to 4 in / electronic controllers - 120 VAC / 60 Hz standard.
100 mm and all 206 series 4 in / 100 mm to 6 in / 150
mm will be fitted with heavy springs. 6. Verify that the electronic controls are properly
configured to provide the functions required.
Note: SRD shown is available for 6” 106-PG and larger.
• for compatible electronic controls, refer to
Singer Process Control Panels, pages 203, 204
• for applications requiring high pressure drops,
refer to Singer model 106-AC, page 78.
• standard hydraulic pilots can provide back-up
control should the system go off limits
• for applications where electric service and
electronic controls are unsuitable, refer to the
standard hydraulic model
• addition of Position Transmitter and
Differential Pressure Transmitter or SPI-MV
are required for metering function.

INLET

Schematic A-7637A

188 2016.1
MODELS 106-2SC-PCO / 206-2SC-PCO
DUAL SOLENOID CONTROL FOR POSITIONING AND SCADA CONTROLS

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering
instructions.
Additionally, include the following information for this
product:
1. Single chamber (106) or (206)
2. Inlet / outlet pressure range
3. Solenoid voltage
4. Standard power failure mode is fail at last
position – specify options
a. Fail open on power failure
b. Fail close on power failure

Flow Capacity
106-2SC-PCO
(See 106-PG in Main Valve section for other valve data)

Size (inches) 2-1/2 in 3 in 4 in 6 in 8 in 10 in 12 in 14 in 16 in 20 in 24 in 36 in


Size (mm) 65 mm 80 mm 100 mm 150 mm 200 mm 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm 900 mm
Minimum (USGPM) Flat Diaphragm CF CF 10 20 40 - - - - - - -
Minimum (USGPM) Rolling
- - - 1 1 3 3 3 3 10 10 20
Diaphragm
Minimum (L/s) Flat Diaphragm CF CF 0.63 1.26 2.52 - - - - - - -
Minimum (L/s) Rolling Diaphragm - - - 0.1 0.1 0.2 0.2 0.2 0.2 0.6 0.6 1.3
Maximum Continuous (USGPM) CF CF 800 1800 3100 4900 7000 8500 11000 17500 25000 55470
Maximum Continuous (L/s) CF CF 50 114 196 309 442 536 694 1104 1577 3500

Flow Capacity
206-2SC-PCO
(See 206-PG in Main Valve section for other valve data)

24 x 16 24 x 20
Size (inches) 3 in 4 in 6 in 8 in 10 in 12 in 16 in 18 in 20 in 28 in 30 in 32 in 36 in 40 in
in in
80 100 150 200 250 300 400 450 500 600 x 600 x 700 750 800 900 1000
Size (mm)
mm mm mm mm mm mm mm mm mm 400 mm 500 mm mm mm mm mm mm
Minimum (USGPM) Flat Diaphragm CF 5 10 20 40 - - - - - - - - - - -
Minimum (USGPM) Rolling
- - - - - 3 3 3 3 3 3 10 10 10 10 20
Diaphragm
Minimum (L/s) Flat Diaphragm CF 0.3 0.6 1.3 2.5 - - - - - - - - - - -
Minimum (L/s) Rolling Diaphragm - - - - - 0.19 0.19 0.19 0.19 0.19 0.19 0.63 0.63 0.63 0.63 1.3
Maximum Continuous (USGPM) CF 580 1025 2300 4100 6400 9230 16500 16500 16500 21700 33600 33650 33700 33800 62000
Maximum Continuous (L/s) CF 37 65 145 260 404 582 1040 1040 1040 1370 2120 2123 2126 2132 3912
Note: CF = Consult Singer Valve on all sizes 3” (80 mm) and under

2016.1 189
ELECTRONIC CONTROL

MODELS 106 2PR-SC-BT / 206 2PR-SC-BT


DUAL ADJUSTABLE SET POINT PRESSURE REDUCING VALVE USING
SOLENOID CONTROL
KEY FEATURES
• Two Adjustable Outlet Pressure Set Points (Daytime / Night)
• Selectable Using Battery Operated Control
• Pressure Reducing Valve with two set points, high pressure and low
pressure
• Time-based selection via latching solenoid and timer
• Self-contained, powered by a 9-volt battery (1 controller, 1
programmer)
• 24/7 time settings (can skip days)
• Multiple time selection possible (up to 10 time settings per 24 hour
period)
• Reduces system pressure when not needed (low flow demand or
night time), supplies increased pressure when required (high flow
demand or day time)
• Recommended for systems where no external power source is
available

PRODUCT OVERVIEW
The 106 2PR-SC-BT and 206 2PR-SC-BT dual adjustable - Optional on rolling (S106 or S206) diaphragm valves
set point pressure reducing valve using solenoid 5. Fixed Restriction
control is based on the 106-PG or 206-PG valve.
6. Isolation Valve
The valve is installed with two PR pressure reducing
pilots, one set to low pressure, the other to high 7. Pressure Reducing Pilot – 160 model
pressure. The pilot senses the downstream pressure 7A. High setting
through a connection to the valve outlet. Under 7B. Low setting
flowing conditions, the pilot reacts to small changes in
pressure to control the valve position by modulating 8. Isolation Valve
relatively steady as the pilot set points. 9. Closing speed control – Model 852-B – Optional
The high pressure pilot can be isolated by means of 10. Solenoid Valve and Controller
a battery operated latching solenoid. This solenoid
10A. Low Flow valve with Potted Latching Solenoid
is controlled using a fully programmable controlled
which is user set to give higher and lower pressure 10B. Control module with bracket, 9VDC
based on time. The solenoid is energized to open and
switch to the high pressure pilot from the normal low
pressure pilot setting.

SCHEMATIC DRAWING
1. Main Valve – 106-PG or 206-PG
2. Isolation Valve
3. Strainer
4. Model 26 Flow Stabilizer / Opening speed control
- Standard (106 or 206) on flat diaphragm
Schematic A-8487A51

190 2016.1
MODELS 106 2PR-SC-BT / 206 2PR-SC-BT
DUAL ADJUSTABLE SET POINT PRESSURE REDUCING VALVE USING SOLENOID CONTROL

STANDARD MATERIALS ORDERING INSTRUCTIONS


Standard materials for pilot system components are: Refer to page 244 for the order form and ordering
• ASTM B62 bronze or ASTM B16 brass instructions.

• AISI 303/316 stainless steel trim Additionally, include the following information for this
product:
• Buna-N / EPDM diaphragm and seals
1. Single chamber (106) or (206)
2. Pilot range
SELECTION SUMMARY
1. Select the valve series and size with sufficient
capacity.
2. Check the operating flow against valve minimum.
3. If the outlet pressure is less than 35% of the inlet
pressure, check for cavitation.
4. Ensure that the flange rating exceeds the
maximum operating pressure.

106-PR-SC Flow Capacity (See 106-PG in Main Valve section for other valve data)
Size (inches) 1/2 in 3/4 in 1 in 1-1/4 in 1-1/2 in 2 in 2-1/2 in 3 in 4 in
Size (mm) 15 mm 19 mm 25 mm 32 mm 40 mm 50 mm 65 mm 80 mm 100 mm
Minimum (USGPM) Flat Diaphragm 1 1 1 1 1 5 5 5 10
Minimum (L/s) Flat Diaphragm 0.1 0.1 0.1 0.1 0.1 0.3 0.3 0.3 0.6
Maximum Continuous (USGPM) 12 19 49 93 125 210 300 460 800
Maximum Continuous (L/s) 0.8 1 3 6 8 13 19 29 50

106-PR-SC Flow Capacity (See 106-PG in Main Valve section for other valve data)
Size (inches) 6 in 8 in 10 in 12 in 14 in 16 in 20 in 24 in 36 in
Size (mm) 150 mm 200 mm 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm 900 mm
Minimum (USGPM) Flat Diaphragm 20 40 - - - - - - -
Minimum (USGPM) Rolling Diaphragm 1 1 3 3 3 3 10 10 20
Minimum (L/s) Flat Diaphragm 1.3 2.5 - - - - - - -
Minimum (L/s) Rolling Diaphragm 0.1 0.1 0.2 0.2 0.2 0.2 0.6 0.6 1.3
Maximum Continuous (USGPM) 1800 3100 4900 7000 8500 11000 17500 25800 55470
Maximum Continuous (L/s) 114 196 309 442 536 694 1104 1628 3500

206-PR-SC Flow Capacity (See 206-PG in Main Valve section for other valve data)
Size (inches) 3 in 4 in 6 in 8 in 10 in 12 in 16 in 18 in 20 in
Size (mm) 80 mm 100 mm 150 mm 200 mm 250 mm 300 mm 400 mm 450 mm 500 mm
Minimum (USGPM) Flat Diaphragm 5 5 10 20 40 - - - -
Minimum (USGPM) Rolling Diaphragm - - - - - 3 3 3 3
Minimum (L/s) Flat Diaphragm 0.3 0.3 0.6 1.3 2.5 - - - -
Minimum (L/s) Rolling Diaphragm - - - - - 0.19 0.19 0.19 0.19
Maximum Continuous (USGPM) 300 580 1025 2300 4100 6400 9230 16500 16500
Maximum Continuous (L/s) 19 37 65 145 260 404 582 1040 1040

206-PR-SC Flow Capacity (See 206-PG in Main Valve section for other valve data)
Size (inches) 24 x 16 in 24 x 20 in 28 in 30 in 32 in 36 in 40 in
Size (mm) 600 x 400 mm 600 x 500 mm 700 mm 750 mm 800 mm 900 mm 1000 mm
Minimum (USGPM) Rolling Diaphragm 3 3 10 10 10 10 20
Minimum (L/s) Rolling Diaphragm 0.2 0.2 0.6 0.6 0.6 0.6 1.3
Maximum Continuous (USGPM) 16500 21700 33600 33650 33700 33800 62000
Maximum Continuous (L/s) 1040 1370 2120 2123 2126 2132 3912

2016.1 191
ELECTRONIC CONTROL

MODEL 106-SPI-MV
SINGLE POINT INSERTION FLOW METERING VALVE

KEY FEATURES
• Accurate flow metering, combined with control valve to
save space/cost
• Supplied with Flow Convertor for local display with
4-20mA output measurement or can be combined with
PLC-based control panel for flow control applications
• +/- 2% of rate accuracy, NIST traceable

PRODUCT OVERVIEW SCHEMATIC DRAWING


The Singer Model 106-SPI-MV is a Single Point 1. Main Valve - Model 106-PG
Insertion Electromagnetic Flow Meter, installed 2. Model SPI - Single Point Insertion Meter
and calibrated in conjunction with a Singer Valve to
provide an accurate flow rate that can be utilized with 3. Local Converter - Flow Indicating Transmitter
the metering valve as a stand alone option or built
into a 106-2SC-PCO pilot system to provide complete Note: Local IP67 Converter is standard.
flow-based valve control.
Optional enclosures are:
The sensor is available for one-inch taps, depending • Stainless Steel IP66 - NEMA 4 - Panel Mounted
upon valve size and application. (optional)
The compact insertion design fits in confined spaces • Fibreglass NEMA 4X - Panel Mounted (optional)
and offers complete accessibility. The flow meter can • SS IP66 - NEMA 4X - Panel Mounted (optional)
be removed for easy inspection, cleaning, calibrating • Polycarbonate IP67 NEMA 6 - Panel Mounted
or verification. (optional)
This cost effective flow meter option is available
for valve sizes from 3” (80mm) to 36” (900mm)
inches. The flow sensor comes pre-calibrated from
McCrometer’s NIST traceable Calibration Lab and
requires no recalibration in the field. With no moving
parts and a single-piece design, the SPI Mag’s sensor
contains nothing to wear or break, and it is generally
immune to clogging by sand, grit or other debris.
The 106-SPI-MV Mag is profiled for the valve body,
further enhancing its measurement accuracy by
allowing precise determination of mean velocities.

192 2016.1
MODEL 106-SPI-MV
SINGLE POINT INSERTION FLOW METERING VALVE

STANDARD MATERIALS ORDERING INSTRUCTIONS


Standard materials for converter enclosures are: Refer to page 245 for the order form. Please be
• IP67 Die cast aluminum - Local prepared to provide the following information:

• SS IP66 - NEMA 4 - Panel Mounted (optional) • Valve size

• Fibreglass NEMA 4X - Panel Mounted (optional) • Pressure

• Polycarbonate IP67 NEMA 6 - Panel Mounted • Minimum flow


(optional) • Fluid
• Cable length
SELECTION SUMMARY • Temperature
1. Allow 3 pipe diameters minimum upstream
of sensor
2. These units can be installed with Singer AC
(Anti-Cav) cages
3. Sensor can be installed on either side of valve
- inlet only

Flow Capacity
106-SPI-MV
(See 106-PG in Main Valve section for other valve data)
Size (inches) 3 in 4 in 6 in 8 in 10 in 12 in 16 in 20 in 24 in 28 in 36 in
500 600 700 900
Size (mm) 80 mm 100 mm 150 mm 200 mm 250 mm 300 mm 400 mm
mm mm mm mm
Minimum (USGPM)
Flat Diaphragm 5 10 20 40 - - - - - - -
Minimum (USGPM)
Rolling Diaphragm - - 0.5 1 3 3 3 10 10 10 20

Minimum (L/s) Flat Diaphragm 0.3 0.6 - - - - - - - - -


Minimum (L/s) Rolling Diaphragm - - 0.03 0.06 0.2 0.2 0.2 0.6 0.6 0.6 1.3
Maximum Continuous (USGPM) 460 800 1,800 3,100 4,900 7,000 11,000 17,500 25,000 33,600 55,470
Maximum Continuous (L/s) 29 50 114 196 309 442 694 1,104 1,577 2,120 3,500

2016.1 193
ELECTRONIC CONTROL

MODELS 106-2SC-MV / 206-2SC-MV


ELECTRONIC FLOW CONTROL AND METERING VALVE

KEY FEATURES
• Combines precise flow control with relatively accurate
flow metering, save space / cost
• PLC-based control panel is compatible with your SCADA system
• Manual control is available in case of emergencies
• Re-transmission capabilities
• Can be field retrofitted to existing valves
• +/- 3% accuracy, certified by NIST approved testing laboratory
(on select sizes)

PRODUCT OVERVIEW
The Singer models 106-2SC-MV and 206-2SC-MV The Singer MV1-TP control panel computes the flow
electronic flow control and metering valves are based rate based on valve differential pressure and position
on the 106-PG or 206-PG main valve. and operates the pilot solenoids to match the flow
The pressure in the upper operating chamber is rate to the customer’s pre-determined (adjustable)
controlled by operating the pilot solenoids. The PLC set-point. Flow is totalized and displayed via panel
within the MV1-TP control panel determines whether readout. In addition, the MV1-TP panel includes a pre-
the opening solenoid or the closing solenoid is programmed logic controller, touch screen display,
operated. The change in valve position is dependent labelled wiring and terminal strip.
upon which solenoid is operated and the duration of
the energized period.

TYPICAL APPLICATION
Singer model MV1 -TP electronic
flow control and metering panel

Power supply:
120 VAC / 60 Hz
Set-point signal:
local or remote

To and from
SCADA.
Singer model 106-2SC-MV electronic flow control and
See available metering valve with X156 analog position transmitter,
SCADA interface options analog differential pressure transmitter, MV1-TP flow
(page 197) limiting and metering panel, dual solenoid control
pilot system.

194 2016.1
MODELS 106-2SC-MV / 206-2SC-MV
ELECTRONIC FLOW CONTROL AND METERING VALVE

SCHEMATIC DRAWING STANDARD MATERIALS


1. Main Valve - 106-PG or 206-PG Standard materials for pilot system components are:

2. Isolating Valves - (2A, 2B, 2C, 2D, 2E) • ASTM B-16 brass fittings, copper tubing

3. Strainer - 40 mesh stainless steel screen • NEMA 4X solenoid coils

4. Closing Speed Control • NEMA panel enclosure

5. Opening Speed Control


6. Closing Solenoid Pilot Valve - SELECTION SUMMARY
120 VAC / 60 Hz standard, other voltages 1. Select a valve with sufficient capacity, using the
available allowable operating pressure drop across the
7. Opening Solenoid Pilot Valve - valve. Usually line size.
120 VAC / 60 Hz standard, other voltages 2. Usually operating in the continuous “C”, service
available range up to 20 ft /s / 6 m/s - refer to chart and/
8. Model X156 Analog (4-20 mA) or performance curves (see Technical and Sizing
Position Transmitter Information section, page 231).

9. Differential Pressure Transmitter 3. If the outlet pressure is less than 35% of the inlet
pressure, check for cavitation.
10. Manual By-Pass Valves - (10A, 10B) -
normally closed 4. Ensure the maximum working pressure rating of
the valve exceeds the maximum
11. Model MV1-TP Electronic Flow Control Panel operating pressure.
5. Ensure the solenoid coils are compatible with the
electronic controllers - 120 VAC / 60 Hz standard.
6. If the operating pressure differential across the
valve will exceed 100 psi / 6.9 bar, consult Singer
Valve. For applications requiring high pressure
drops, refer to Singer model PG-AC (see page 78).

ORDERING INSTRUCTIONS
1

Refer to page 244 for the order form and ordering


instructions.
Additionally, include the following information for this
product:
1. Single chamber (106) or (206)
2. Inlet / outlet pressure range
3. Solenoid voltage
4. Optional NEMA 4x control panel enclosure

Schematic A-8450C

2016.1 195
MODELS 106-2SC-MV / 206-2SC-MV
ELECTRONIC FLOW CONTROL AND METERING VALVE

Flow Capacity
106-2SC-MV
(See 106-PG in Main Valve section for other valve data)

Size (inches) 2-1/2 in 3 in 4 in 6 in 8 in 10 in 12 in 14 in 16 in 20 in 24 in 36 in


Size (mm) 65 mm 80 mm 100 mm 150 mm 200 mm 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm 900 mm
Minimum (USGPM) Flat Diaphragm CF CF 10 20 40 - - - - - - -
Minimum (USGPM) Rolling Diaphragm - - - 1 1 3 3 3 3 10 10 20
Minimum (L/s) Flat Diaphragm CF CF 0.6 1.3 2.5 - - - - - - -
Minimum (L/s) Rolling Diaphragm - - - 0.1 0.1 0.2 0.2 0.2 0.2 0.6 0.6 1.3
Maximum Continuous (USGPM) CF CF 800 1800 3100 4900 7000 8500 11000 17500 25000 55470
Maximum Continuous (L/s) CF CF 50 114 196 309 442 536 694 1104 1577 3500

Flow Capacity
206-2SC-MV
(See 206-PG in Main Valve section for other valve data)

Size (inches) 3 in 4 in 6 in 8 in 10 in 12 in 16 in 18 in 20 in 24 x 16 in 24 x 20 in 28 in 30 in 32 in 36 in
80 100 150 200 250 300 400 450 500 600 x 400 600 x 500 700 750 800 900
Size (mm)
mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm
Minimum (USGPM) Flat Diaphragm CF 5 10 20 40 - - - - - - - - - -
Minimum (USGPM) Rolling
- - - - - 3 3 3 3 3 3 10 10 10 10
Diaphragm
Minimum (L/s) Flat Diaphragm CF 0.3 0.6 1.3 2.5 - - - - - - - - - -
Minimum (L/s) Rolling Diaphragm - - - - - 0.2 0.2 0.2 0.2 0.2 0.2 0.6 0.6 0.6 0.6
Maximum Continuous (USGPM) CF 580 1025 2300 4100 6400 9230 16500 16500 16500 21700 33600 33650 33700 33800
Maximum Continuous (L/s) CF 37 65 145 260 404 582 1040 1040 1040 1370 2120 2123 2126 2132
Note: CF = Consult Singer Valve on all sizes 3” (80 mm) and under

196 2016.1
ELECTRONIC CONTROL

SCP-TP
SINGLE-PROCESS CONTROL PANEL

KEY FEATURES
• Compatibility with remote SCADA Modbus,
Hardwired 4 to 20 mA or local set-pointadjustment
• Simplified single loop process controller with P.I.D.
implementation, ON/OFF or 4-20mA motor control
• Selectable input controls and output alarms
• IP 66, 67 NEMA 4X rated panel
• Colour touch screen interface display
• Equipped with data logging features
• For indoor use only. For outdoor applications,
consult factory.

PRODUCT OVERVIEW IDEAL FOR


The SCP-TP Controller is a simplified process • Level control
controller designed to complement the Dual Solenoid • Pressure control
Control Valve. It offers quick and easy configuration
for any single process application as well as on/ • Flow control
off applications. The SCP-TP is also equipped to be • Position control
configured to control the Singer 420DC Motor. Range
• Data logging
of application is dependent on the process variable
(feedback) transmitter used, which includes (but not • 420-DC/AC Control
limited to) common automatic control valve functions
with conventional pilots. The SCP-TP Controller reads
and compares the process feedback (process variable)
Maximum water level
4 to 20 mA signal to the desired setting (set-point) 4
Valve 100% closed
to 20 mA signal. The SCP-TP then accurately positions
the valve to bring the process variable towards the
set-point until they coincide. The SCP-TP is also Level transmitter
equipped with data logging features than when (power by others)
Span
enabled can log all sensor feedback and setpoint data
Minimum water level
with a time stamp. Valve 100% open

Singer SCP-TP Control Panel


(SCADA or local controls)

Distribution to users

Singer Model 106-2SC-PCO /


206-2SC-PCO with X156 valve
position transmitter

2016.1 197
ELECTRONIC CONTROL

LCP-TP
LEVEL CONTROL PANEL

KEY FEATURES
• Compatibility with remote SCADA Modbus, Hardwired 4 to
20 mA or local set-point adjustment
• Simplified ON/OFF level controller for 4-20mA sensor or
high/low level switch implementation
• Selectable input controls and output alarms
• IP 66, 67 NEMA 4X rated panel
• Black and white interactive button display screen
• Equipped with data logging features

PRODUCT OVERVIEW IDEAL FOR


The LCP-TP Level Controller is a single process • Level control
level controller designed to complement Singer’s • Data logging
Single Solenoid Operated/Override Control Valves
and 4-20mA level sensor or High/Low Level
Switches. This combination package is ideal for
filling any kind of tank with water that requires
filling to a level setpoint and then drawing down
the level of the tank to a secondary setpoint before TYPICAL APPLICATION
activating the fill cycle again thus ensuring tank Level transmitter
turnover. (power by others)
The LCP-TP offers quick and easy configuration that
Maximum water level
allows the LCP-TP Controller to read and compare Valve 100% closed
the level 4 to 20 mA signal to the desired setpoint.
The LCP-TP then opens or closes the Singer control Span
valve to achieve the desired level setpoint. If a
High/Low level switch system is preferred the Minimum water level
Valve 100% open
LCP-TP can easily switch configuration to allow
for level switch inputs and control the Singer Singer LPC-TP Control Panel
Valve accordingly. Additionally the LCP-TP is also (SCADA or local controls)
equipped with data logging features than when
enabled can log all sensor feedback and setpoint
data with a time stamp allowing for system
analysis. Distribution to users

Singer model 106/206-SC

198 2016.1
ELECTRONIC CONTROL

MODEL MCP-TP
MULTI PROCESS CONTROL PANEL SERIES

KEY FEATURES
• Compatibility with remote SCADA , Hardwired 4 to 20 mA or
local set-point(s) adjustment
• Flexibility of single or multiple process monitoring and control
• Optional 1 panel for multi- valve application
• Precise valve positioning and visual status indication
• Robust and self-contained in NEMA 4X rated panel
• Colour touch screen interface display

For indoor use only. For outdoor applications, consult factory.

PRODUCT OVERVIEW TOUCH PANEL


The MCP-TP Series is a multiple process loop control Model (MCP-TP) touch panel screen is a user-friendly
panel designed to complement the Singer Model 2SC- operator interface that enables intuitive control and
PCO Dual Solenoid Control Valve. Range of application monitoring. Model (MCP-TP) touch panel screen
is dependent on the feedback (process variables) eliminates the need for mechanical push buttons,
transmitters used, which is similar to (but not limited switches, and indicator lights and readouts. The
to) combination automatic control valve functions screen is custom tailored to customer-specific
with conventional pilots. The MCP-TP control panel application requirements.
has the ability to monitor multiple processes and Touch Panel Details
remotely control the dual solenoid control valve Dimensions: 7 in / 175 mm W x 5 in / 125 mm L
based on system conditions. The MCP-TP control
panel can function as a simple single loop controller Display: 256 Color TFT
(eg. pressure reducing, flow control, level control) or Protection: NEMA 4X rain-tight (indoor use only)
as a multiple loop controller (eg. flow and pressure, or
Screen can be customized to application
reducing and sustaining).
The MCP-TP reads transmitted signals and energizes
the dual solenoid pilots on the Singer control valve. ORDERING INSTRUCTIONS
The MCP-TP can react to any change in conditions by Refer to page 244 for the order form and ordering
monitoring the system continuously and comparing instructions.
actual process values to desired set-point values.
Additionally, include the following information for this
The Multi-Process Control Panel incorporates a product:
high performance PLC-based control with P.I.D.
optimization to provide control of multiple processes, 1. Application details
such as pressure reducing, flow control, level and 2. Solenoid voltage
sustaining. Singer will customize the program to 3. Source of set-point signal (4-20 mA)
match your specific application needs. Optional alarm
outputs for SCADA is available. 4. Source of process variable signal(s)
5. Number of processes to be controlled

2016.1 199
MODEL MCP-TP
MULTI PROCESS CONTROL PANEL SERIES

TYPICAL APPLICATION
MCP-TP monitors inlet pressure while filling tank at a relatively steady flow rate. If tank is full, valve closes. If inlet
pressure drop below normal, valve will modulate to close to keep inlet pressure from dropping further.

Tank level transmitter 4 to 20 mA Water Tower


(process variable feedback) #3.

Singer MCP-TP
- SCADA flow set-point
- Local upstream pressure set-point

Set-point signal
from remote site
To and from SCADA
(See available SCADA
interface options, In-line flow meter with continuous
page 197) 4 to 20 mA signal transmitter
(process variable - feedback) #1.
Power supplied by others 24 VDC.

Singer model
Upstream pressure 4 to 20 mA 106-2SC-PCO / 206-2SC-PCO
signal transmitter (process variable feedback) #2.

200 2016.1
ELECTRONIC CONTROL

SAP PANEL FOR MODEL RPS-L&H-ET


SURGE ANTICIPATOR PANEL

KEY FEATURES
• Automatically interfaces pressure switch and control valve to
protect system from destructive pressure surges
• Visual indication of operational status
• Simple to install
• Minimizes field wiring costs

For indoor use only. For outdoor applications, consult factory.

PRODUCT OVERVIEW
The SAP Surge Anticipator Panel provides the The SAP panel comes equipped with a long life, high
interface between a customer supplied, system capacity 12 VDC battery, industrial grade battery
pressure switch and the Singer Surge Anticipating charger with over current and polarity protection,
control valve. Together they provide protection door mounted volt meter, and battery test feature.
against destructive pressure surges. The logical arrangement of indicator lights and the
The SAP panel energizes the control valve pilot volt meter provide easy supervision of the sequencing
solenoid on an abnormally low pressure reading and the operating status.
and/or power failure of pumps. The 12 VDC pilot
solenoid is energized to open the main valve and
relieve the surge pressure from the system. The RPS- ORDERING INSTRUCTIONS
L&H-ET (ET - Electronically Timed) valve is equipped Refer to page 244 for the order form and ordering
with a hydraulic pilot to relieve on abnormally high instructions.
pressures.
Additionally, include the following information for this
The SAP panel is equipped with adjustable digital product:
delay timers that permit coordination of valve
• Optional pressure switch
operation with pump start-ups, shutdowns, power
failures and down surges.

2016.1 201
SAP PANEL FOR MODEL RPS-L&H-ET
SURGE ANTICIPATOR PANEL

TYPICAL APPLICATION

Pressure
Singer Valve Switch
Surge Anticipator
Panel Model SAP
as shown

RPS-L&H-ET
Valve

Singer Valve 106-BPC


Pump Control valve

Solenoid
120 VAC / 60 Hz
Power Supply

SCHEMATIC DRAWING
1. Main Valve - 106 / 206-PG
2. Isolating Valve (2A, 2B, 2C)
3. Strainer - 40 mesh, J0097A
4. Fixed Restriction - 3/32 in / 2.4 mm
5. Closing Speed Control - 852-B
6. Pressure Switch - supplied by others
12
7. Manual Test Valve - 3-way ball valve with
11
lockable handle
8. Solenoid Valve - 12 VDC Normally Closed
9. Model 81-RP, Relief Pilot
10. Swing Check Valve - 1/2 in / 15 mm
11. Limit Switch Assembly - optional
12. Connection to Header by others
14. Pressure Gauge 1/4 in / 6 mm NPT

Note: Schematic A-7606C


Singer Surge Anticipator Control Panel - not shown in
schematic but shown in above typical application

202 2016.1
ELECTRONIC CONTROL

SPC
SINGER PUMP CONTROL PANEL

KEY FEATURES
• Simple to install and reduces field wiring costs
• Automatically interfaces pump and control valve to avoid
starting and stopping surges
• Suitable for use with either in-line booster or deep well by
pass pump control valves
• Control switches for easy system operational execution

For indoor use only. For outdoor applications, consult factory.

PRODUCT OVERVIEW
The SPC Pump Control Panel provides the interface The logical arrangement of Hand/Automatic selector,
between the pump motor starter and the Singer start, stop and emergency stop switches make the
pump control valve. The SPC ensures that the pump operating simple and easy to execute.
starts and stops without causing line surges.
The SPC Pump Control Panel energizes the control
valve pilot solenoid simultaneously with pump
start. When pump shut-down is required the panel ORDERING INSTRUCTIONS
keeps the pump running while the pilot solenoid is Refer to page 244 for the order form and ordering
de-energized. The panel turns the pump off just as instructions.
the control valve completes its full stroke travel. It
Additionally, include the following information for this
is equipped with delay timers and emergency fault
product:
contacts to provide the customer with local and
remote indication for various operational failure • Solenoid voltage
conditions. • SPC-IDC-2LS or SPC-EC-LS configuration
The SPC Pump Control Panel is connected to the
pilot solenoid and limit switch that are standard
components in the control valve pilot system. The
panel is also connected to the customer supplied
pump discharge pressure switch and the pump
motor starter. A second limit switch and emergency
shutdown solenoid are optional components for the
control valve pilot system.
The logical arrangement of indicator lights with the
Hand Off Automatic (HOA) selector switch provides
easy supervision of the sequencing and the operating
status.

2016.1 203
SPC
SINGER PUMP CONTROL PANEL

TYPICAL APPLICATION

Singer Pump Control Panel Pump Motor Starter


Model SPC-EC-LS as shown

Pump
Start
Contacts

Limit Switch

Solenoid

Note: Wiring done by others


120 VAC / 60 Hz
Power Supply

204 2016.1
ELECTRONIC CONTROL

MODEL 420-DC / 420-AC


AUTOMATED PILOT CONTROL
KEY FEATURES
• Easily programmable range via USB cable and custom software
• Built in surge suppression and reverse polarity protection
• IP68, 7 ft/24 hours (2.134 m/24 hours)
• High-torque motors increase actuator’s operational life
• Downstream pressure follows the control signal within +/- 1 psi
/ 0.068 bar
• 4 -20 mA setpoint input and 4 – 20mA position feedback

PRODUCT OVERVIEW ORDERING INSTRUCTIONS


Refer to page 246 for the order form and ordering
The 420DC/AC provides a reliable, simple and cost instructions.
efficient way to automate today’s water systems. A
sturdy slow speed 24 VDC motor actuator drive can Additionally, include the following information for this
be installed on a variety of Singer pilots. The motor product:
actuator responds to a 4-20 mA signal, rotating the 1. Application (Singer Valve Model #)
pilot adjusting screw corresponding to the change in
2. Pilot utilized
signal. The number of turns is adjustable and may be
programmed to suit the pressure changes required 3. Pilot spring range
for the application. The 420-DC or 420-AC requires 4. Required adjustable operating pressure range
less than 2 amps of power to operate, controlled
by the 4-20 mA signals from the water distribution 4.25 inch
SCADA system. The very low power requirement lends (108 mm)
itself well to a solar powered self-contained station.
Extended power failure would result in relatively
steady pressure at the last setting. Optional freeze or
default to high or low pressure is available on loss of
signal. 5.5 inch
(140 mm)

IDEAL FOR
• Pressure Management Systems – utilizing pressure
reducing pilot to give adjustable pressure settings
based on system demand. 4.75 inch
(121 mm)
• Remote or difficult to reach control valves where
adjustments need to be made, and using SCADA
is the best option.

2016.1 205
Customize. Accessorize. Specialize.
At Singer Valve, our pilots and accessories offer you options and choices. Like
customizing a Singer float valve with our rotary float pilot or adding a Singer
internal drop check assembly to a main valve for quick, positive shut-off when
normal forward flow stops. To resist corrosion, you can upgrade components to
stainless steel or to prevent mineral build-up and premature valve failure, you can
choose our flexible stainless steel braided hose. Pilots. Needles. Tubing. Strainers.
Options we design. Accessories you specify.

Oxy-Nitride Stem – Main Valve Option


Prevents build-up. Resists corrosion. Reduces maintenance.
Our proprietary oxy-nitride treated 316 stainless steel stem is ideal when mineral
build-up on stems may cause maintenance problems or operational malfunctions.
The stem is treated in an aerated salt bath so it reduces or prevents mineral build-
up, allowing the stem to stroke freely as it passes through the guide bushing.

Ideal for:
• Reclaimed water applications

Pressure Reducing Pilot PR-160


Self-cleaning. Self-flushing. Non-clogging.
This normally open pilot is spring and diaphragm operated. It has a non-clogging
pilot guide stem above the diaphragm, which is removed from the flow of water in
the main pilot chamber. Because the outlet is located in the bottom of the pilot, 90
degrees to the inlet, the pilot is self-cleaning and self-flushing, thereby eliminating
debris build-up. It also minimizes turbulence and false readings. This is the
standard pressure reducing pilot for all our pressure reducing valves.

Ideal for:
• Regulating water pressure

Pilots and Accessories


PILOTS AND ACCESSORIES

MODEL 160
PRESSURE REDUCING PILOT (NORMALLY OPEN)

PRODUCT OVERVIEW
The 160 Pressure Reducing Pilot is a spring and diaphragm operated, normally
open pilot. The inner valve is held open by the spring and when the control
pressure below the diaphragm exceeds the force of the spring, the pilot valve
closes.
Model 160 is the standard pressure reducing pilot on all 106 and 206 series
valves.

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering instructions.

1. Adjusting Screw (Stainless Steel)


2. Locknut (Stainless Steel)
3. Spring Step (Stainless Steel)
4. Spring (Steel)
5. Spring Casing Stem (Bronze)
6. Stem (Stainless Steel)
7. Guide Bushing (Delrin)
8. Retaining Ring (Stainless Steel)
9. Clamp Plate Seal (Brass)
10. Diaphragm (EPDM)
12. Yoke (Stainless Steel)
13. Seat Ring Seal (Buna-N)
14. Seat Ring (Stainless Steel)
15. Inner Valve (Stainless Steel and EPDM)
16. Body (Bronze)
17. Outlet Connector (Brass)
SCHEMATIC A0708E
Available in all Stainless Steel construction.
Viton or Buna-N Elastomers
Spring Ranges Approximate psi per turn
Standard 20 to 200 psi (1.38 to 13.8 bar) 30 psi (2 bar) per turn
5 to 50 psi (0.345 to 3.45 bar) 9 psi (0.62 bar) per turn
Optional 10 to 80 psi (0.7 to 5.5 bar) 14 psi (0.96 bar) per turn
100 to 300 psi (6.9 to 20.7 bar) 42 psi (2.9 bar) per turn

208 2016.1
PILOTS AND ACCESSORIES

MODEL 160 RF
RATE OF FLOW PILOT (NORMALLY OPEN)

PRODUCT OVERVIEW
The 160-RF pilot is a spring and diaphragm operated pilot designed to sense a
differential across an external orifice plate. It is a normally open pilot that also
has a sensing port is in the spring casing, above the diaphragm and is available
in stainless steel.
The inner valve is held open by the spring and when the control pressure below
the diaphragm exceeds the combined forces of the spring and the sensing
pressure, the pilot valve closes. The 160-RF is the standard rate of flow control
pilot on all 106 and 206 series valves.

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering instructions.

*5. Inner Valve (Stainless Steel & EPDM)


6. Yoke (Stainless Steel)
7. Clamp Plate (Brass)
8. Spring Casing (Bronze)
9. Retaining Ring (Stainless Steel)
10. Guide Bushing (DELRIN)
11, 16, 17. Fasteners (Stainless Steel)
*12, 19. Seal (Buna-N)
13, 21. Spring (Spring Steel)
14, 20. Spring Step (Stainless Steel)
15. Thread Seal (Steel & Buna-N)
18. Seat Ring (Stainless Steel)
**21. Bucking Spring (Stainless Steel)
*Recommended Spare Parts - supplied in Parts KIT **22. Bleed Screw (Stainless Steel)
**Range 2- 20 psid only
**23. Bleed Screw Seal (Stainless Steel and Neoprene)
1. Body (Bronze)
*2. Diaphragm (EPDM)
4. Stem (Stainless Steel)

Spring Ranges Approximate psi per turn


Standard 25 to 50 psi (1.72 to 3.45 bar) 2 psi (0.138 bar) per turn
Optional 5 to 50 psi (0.345 to 3.45 bar) 3.4 psi (0.23 bar) per turn

2016.1 209
PILOTS AND ACCESSORIES

MODEL 81-RP
PRESSURE RELIEF PILOT (NORMALLY CLOSED)

PRODUCT OVERVIEW
The 81-RP is a remote sensing, high capacity, spring and diaphragm operated,
normally closed pilot. The inner valve is held closed by the spring. When the sensed
pressure increases above the spring setting, the pilot opens.
Model 81-RP pilot is used as the standard pressure relief/sustaining pilot on all 106
and 206 series valves.

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering instructions.

1 1. Adjusting Screw (Stainless Steel)


2 2. Lock Nut (Stainless Steel)
3 3. Spring Casing (Bronze)
4
4. Upper Spring Step (Stainless Steel)
5
5. Spring (Steel)
6
7” (175 MM) 7 6. Lower Spring Step (Stainless Steel)
Max. 8
7. Stem Locknut (Stainless Steel)
9
8. Clamp Plate Seal (Buna-N)
SENSING
1/4” NPT
10
11
9. Clamp Plate (Brass)
OUTLET 3/8” NPT 10. Diaphragm (EPDM)
12 11. Body Seal (Buna-N)
13
12. Inner Valve (Stainless Steel and EPDM)
INLET 14
3/8” NPT
15 13. Body (Brass)
SCHEMATIC A0661C
14. Seat Ring Seal (Buna-N)
Options: All Stainless Steel construction.
Viton or Buna-N Elastomers 15. Seat (Stainless Steel)

Spring Ranges Approximate psi per turn


Standard 20 to 200 psi (1.38 to 13.8 bar) 25 psi (1.7 bar) per turn
5 to 50 psi (0.345 to 3.45 bar) 9 psi (0.62 bar) per turn
Optional 10 to 80 psi (0.7 to 5.5 bar) 14 psi (0.96 bar) per turn
100 to 300 psi (6.9 to 20.7 bar) 42 psi (2.9 bar) per turn

210 2016.1
PILOTS AND ACCESSORIES

MODEL 83-RP
HIGH PRESSURE RELIEF PILOT (NORMALLY CLOSED)

PRODUCT OVERVIEW
The 83-RP is a spring and diaphragm operated, normally closed pilot specifically
designed for high pressure applications. The inner valve is held closed by the
spring. When the control sensed pressure below the diaphragm exceeds the
force of the spring, the pilot valve opens.
Model 83-RP pilot is used as the standard pressure relief pilot where the
operating pressures are excessive, such as a 300 psi / 20.7 bar level.

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering instructions.

1 1. Adjusting Screw (Stainless Steel)

2
2. Spring Casing (Brass)
3A 3. Spring Steps (3A, 3B) (Stainless Steel)
4 4. Spring (Steel)
3B 5. Diaphragm (EPDM)
7” (175mm)
Max. 5
6. Clamp Plates (Brass)
10
6 7. Inner Valve ((Stainless Steel and EPDM)
7
8
8. Body (Brass)
1/4” NPT
OUTLET 3/8” NPT 9. Seat (Stainless Steel)
10. O Ring Seals (Buna-N)
9 Options: Available in all Stainless Steel construction
INLET
3/8” NPT

3” (80mm)

SCHEMATIC A0781A

Spring Ranges Approximate psi per turn


Standard 200 to 500 psi (13.8 to 34.5 bar) 80 psi (5.5 bar) per turn

2016.1 211
PILOTS AND ACCESSORIES

MODEL 81-RPD
DIFFERENTIAL PRESSURE RELIEF PILOT (NORMALLY CLOSED)

PRODUCT OVERVIEW
The 81-RPD is a remote sensing, high capacity, spring and diaphragm operated,
normally closed, differential pilot. The inner valve is held closed by the spring. When
the pressure under the diaphragm overcomes the combined forces of the spring
setting and the pressure above the diaphragm, the pilot opens. The 81-RPD valve is
used for remote sensing of a differential pressure for normally closed applications.

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering instructions.

1
4. Spring Casing (Brass)
2
3 5. Spring Step (Stainless Steel)
4
6. Spring (Stainless Steel)
5
6 7. Stem Lock Nut (Stainless Steel)
7” (175mm)
Max.
7 8. Spring Casing Capscrew (Stainless Steel)
8
9. Diaphragm (EPDM)
SENSING 1/4” NPT 9
10 10. Clamp Plate (Brass)
11
12 11. Clamp Plate Seal (Buna-N)
13 12. Stem Seal (Buna-N)
14
INLET
15
13. Inner Valve (Stainless Steel and EPDM)
3/8” NPT
16 14. Seat Ring Seal (Buna-N)
SCHEMATIC A0662D 3”
15. Body (Brass)
(80mm) OUTLET 3/8” NPT
16. Seal (Stainless Steel)
1. Adjusting Screw (Stainless Steel) Options: Available in all Stainless Steel construction.
2. Lock Nut (Stainless Steel)
3. Thread Seal (Steel and Buna-N)

Spring Ranges Approximate psi per turn


Standard 20 to 200 psi (1.38 to 13.8 bar) 30 psi (2 bar) per turn
5 to 25 psi (0.345 to 1.72 bar) 3 psi (0.2 bar) per turn
Optional 10 to 80 psi (0.7 to 5.5 bar) 10 psi (0.7 bar) per turn
100 to 350 psi (6.9 to 24 bar) 41 psi (2.82 bar) per turn

212 2016.1
PILOTS AND ACCESSORIES

MODEL 301-4
ALTITUDE PILOT VALVE

PRODUCT OVERVIEW
An altitude pilot valve is spring and diaphragm operated; it controls the water
level in a reservoir by sensing the hydrostatic head. When the hydrostatic head
equals the spring force, the pilot connects port “X” (connection to main valve inlet
) to port “K” (connection to main valve bonnet). The main valve closes. When the
hydrostatic pressure decreases slightly, the port “X to K” connection is closed by
the inner valve. When the hydrostatic pressure is reduced even further, the pilot
connects port “K” (main valve bonnet) to “EX” (exhaust to atmosphere). Then the
main valve opens.
Model 301-4 pilot is used as the standard pilot on all 106 and 206 series altitude
valves.

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering instructions.

1. Stem (Stainless Steel)


2. Spring (Steel)
1 3. Diaphragm Casing (Ductile Iron)
4. Diaphragm (Buna-N)
5. Inner Valve (Stainless Steel and EPDM)
27-3/8” 2
(695 mm)
Sensing 6. Body (Stainless Steel)
Connection
to Reservoir 3
1/4 NPT
4
Standard Materials:
Exhaust to Drain
Connection to
‘EX’ 1/4 NPT EX
Bonnet “K” port Other standard material of the pilot construction
3/4 NPT
Upstream Sup-
ply Connection
include brass, aluminum, stainless steel, Buna-N
5
‘X’ 3/8 NPT
6

15-5/8”
(395 mm)

SCHEMATIC A0847A

Approximate fixed differential


Model Spring Range / Elevation Delayed opening Approximate feet per turn
301-4 4 to 20 ft (1 to 6 m) 1 ft (0.3 m) 1 ft (0.3 m) per turn
301-4 10 to 60 ft (3 to 18 m) 1 ft (0.3 m) 2 ft (0.6 m) per turn
301-4 40 to 125 ft (12 to 38 m) 2 ft (0.6 m) 3 ft (0.9 m) per turn
301-5 60 to 225 ft (18 to 69 m) 3 ft (0.9 m) 6 ft (1.8 m) per turn

2016.1 213
PILOTS AND ACCESSORIES

MODEL R-400
MODULATING FLOAT PILOT

PRODUCT OVERVIEW
The R-400 is a modulating float pilot with a plastic float, suitable for
remote installation on a tank or reservoir. It positions the main valve in
proportion to the reservoir level. Standard configuration is for the pilot to
close on rising level.
Specify “Reverse Acting” for the pilot to open on rising level. The
polypropylene float connects to the pilot on a 10 in / 250 mm brass rod.
The R-400 pilot is used as the standard float pilot on all 106 and 206
series modulating float valves.

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering instructions.

17-1/2”
(445mm)
3-1/8”
(80mm)
1. Body (Bronze)
1-3/16” 2. Inner Valve (Buna-N)
(30mm)
3/8”
5 3. 3 / 8 in NPT Outlet
NPT Inlet Pilot
6 Closed 4. Stem (Brass)
1 7 5. Lever (Brass)
Modulation
8
2 Range 6. Serrated Arm (Brass)
4 9 7. Float Rod (Brass)
3
8. Lock Nut (Stainless Steel)
Float 9. Float (Polypropylene)
5” (127mm)
Diameter Options: Copper float; Stainless Steel Rod.
Pilot
Fully
SCHEMATIC A0714D Open

214 2016.1
PILOTS AND ACCESSORIES

MODEL 34
MODULATING FLOAT PILOT WITH VERTICAL ROD

PRODUCT OVERVIEW
The 34 modulating float pilot is comprised of a copper float and brass rod assembly which moves vertically.
As the level rises, the float lifts and the valve closes. The 34 pilot is optional pilot, available for modulating
applications where the float and rod are installed in a still well and / or vertical action
is preferred.

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering instructions.

4-3/16” 1. Body (Bronze)


(106mm)
1 2. Inner Valve (Stainless Steel)
OUTLET
INLET 1/2”
1/2”
3. Valve Stem (Stainless Steel)
2 4. Connector Bar (Brass)
13” 5. Mounting Bracket (Brass)
(330mm) 3
8 6. Counter Weight (Cast Iron)
4 9 7. Guide Bar (Brass)
5
8. Float Rod (Brass)
6 9. Lever Arm (Brass)
10-5/16”
(261mm)
Options: Available with stainless steel float and rod
7 Note: When ordered as a part and/or when shipping
via air freight, the 1/4 in / 6.35 mm)diameter x 4 ft /
7” 1.2 m round brass rod is not included.
(175mm)
float

SCHEMATIC A0606B

2016.1 215
PILOTS AND ACCESSORIES

MODEL 35
MODULATING FLOAT PILOT

PRODUCT OVERVIEW
Model 35 is a Stainless Steel modulating float pilot with a Stainless Steel
float, suitable for remote installation on a tank or reservoir.
It positions the main valve in proportion to the Reservoir level. Standard
configuration is for the pilot to close on rising level.
Specify reverse acting for the pilot to open on rising level. Reverse acting
Inlet pressure on pilot is a minimum of 60 psi with main valve inlet press
maximum of 10 psi. Consult Singer staff for installations outside these
parameters.
The Stainless Steel float connects to the pilot using a 10 in / 250 mm
Stainless Steel rod.

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering instructions.

1. Body (Stainless Steel AISI 303)


2. Cam (Stainless Steel AISI 303)
3. Inner valve (Stainless Steel AISI 303)
4. Locknut (2) (Stainless Steel 18-8)
5. Stop pin (Stainless Steel AISI 302)
6. Pivot pin (Stainless Steel AISI 302)
7. Float rod (Stainless Steel AISI 303)
8. (Stainless Steel 18-8)

SCHEMATIC A0797B

216 2016.1
PILOTS AND ACCESSORIES

MODEL 39
NON-MODULATING FLOAT PILOT WITH VERTICAL ROD

PRODUCT OVERVIEW
The 39 non-modulating float pilot is designed to operate an On-Off float
valve. The differential between the level where the valve opens and the
level where the valve closes, is adjustable. The standard configuration is
for the pilot valve to close on high level and open at a low level.
The 39 pilot is used as the standard pilot on all non-modulating F-Type 5,
106 and 206 series
float valves.

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering instructions.

5” 10.5” 1. Body (Brass)


(125mm) (270mm)
“x” 2. Inner Valve O-rings (Buna-N)
1 “b”
2 “in” 8 3. Inner Valve (Brass)
3
10” 4 4. Connector Bar
(250mm)
5
9 5. Mounting Bracket (Brass)
6 10
6. Guide Bar (Brass)
7 11
7. Counter Weight (Cast Iron - Epoxy Coating)
7” (178mm) 8. Float Rod (Brass)
Diameter
“in”: inlet to upstream boss of main valve 9. Lever Arm (Brass)
“b”: to bonnet of main valve
“x”: exhaust to drain 10. Adjustable Stop (Brass)
11. Float (Copper)
12. Adjustable Stop Opening (Brass)
SCHEMATIC A0411A
Options: Available in Stainless Steel construction.
12

2016.1 217
PILOTS AND ACCESSORIES

MODEL 43
ROTARY FLOAT PILOT (ON/OFF)

PRODUCT OVERVIEW
The 43 stainless steel float actuated pilot with non-modulating rotary motion,
provides non-modulating On-Off operation of the main valve. It has higher
capacity and faster response time than other non-modulating float pilots. The
differential between the level where the main valve opens and the level where
the main valve closes, is adjustable. The 43 pilot allows for faster operation of the
main valve over traditional float pilots, due to increased port size. The standard
configuration is for the pilot to close the main valve on high level and open the
main valve on low level. The 43 pilot is used on all non-modulating model F-Type
5, 106 and 206 series float valves.
The 43 pilot has a higher pressure rating 150 psi / 10.35 bar as compared to
Model 39 (80 psi / 5.5 bar).

1 1. Mounting Bracket (Brass)


2. Counter Weight (Stainless Steel)
2
3. Float Rod (SST)
4. Float (SST)

3 Standard Materials: SST pilot, inner valve,


SST float, 4 ft / 1.2 m SST rod.

Model 43 Detail
43

43

218 2016.1
MODEL 43
ROTARY FLOAT PILOT (ON/OFF)

SCHEMATIC DRAWING
FRONT
3.13” 2.38”
BACK (80mm) (60mm)

3 1
2
IN
4
6
4.88”
X B
(124mm)
BODY 14

7
IN: Connect to upstream boss of main valve
B: Connect to bonnet of main valve 8
X: Exhaust to drain

9
10
13

11

12
7” (178mm)

SCHEMATIC A0986A

1. Mounting Bracket (Stainless Steel)


2. Main Lever Arm (Stainless Steel)
3. Counterweight (Stainless Steel)
4. Counterweight Rod (Stainless Steel)
5. Lower Lever Arm (Stainless Steel
6. Space Bar (Stainless Steel)
7. Float Rod (Stainless Steel) ORDERING INSTRUCTIONS
8. Adjustable Stop (Stainless Steel) Refer to page 244 for the order form and ordering
9. Inner Valve (Teflon) instructions.
10. Casing (Stainless Steel)
11. Stem (Stainless Steel)
12. Wave Spring Washer (Stainless Steel)
13. Body (Stainless Steel)
14. Lock Nut (Stainless Steel)

2016.1 219
PILOTS AND ACCESSORIES

MODEL 106-RD
DIFFERENTIAL RELIEF PILOT (NORMALLY CLOSED)

PRODUCT OVERVIEW
The model 106-RD is a spring and diaphragm operated, normally closed pilot
designed to allow flow when the inlet pressure exceeds the outlet pressure by a
predetermined amount. The model 106-RD is used as a differential control valve on
Singer model 106-A-Type 4 altitude control valves.

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering instructions.

1
1. Adjusting Screw (Stainless Steel)
2 2. Locknut (Stainless Steel)

3
3. Thread Seal (Stainless Steel & Buna-N)
4. Spring Step (Brass)
4
5. Spring (Stainless Steel)
5
6. Spring Casing (Brass)
6
7. Spring Casing Screws (Stainless Steel)
7 8. Spring Cup (Brass)
1/8 NPT 9. Diaphragm (EPDM)
8 10. Body (Brass)

INLET & OUTLET


1/4 NPT

10

FLOW

SCHEMATIC A0556B

220 2016.1
PILOTS AND ACCESSORIES

MODEL 625-RPD
DIFFERENTIAL PILOT (NORMALLY CLOSED)

PRODUCT OVERVIEW
The model 625-RPD is a remote sensing, spring and diaphragm operated,
normally closed pilot with large diaphragm area for increased sensitivity.
The pilot opens when the control pressure exceeds the spring force or the
differential established by the spring.
The model 625 is used for special applications where a low pressure set point
or highly sensitive and responsive pilot is required.

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering instructions.

1. Adjusting Screw (Stainless Steel)


19

16 2. Locknut (Stainless Steel)


20 3. Thread Seal (Steel & Buna-N)
8

7
4. Spring Step (Brass)
9

10
5. Spring (Stainless Steel)
21

B
6. Clamp Plate Nut (Stainless Steel)
14 3
7. Clamp Plates (Brass)
24
13 8. Diaphragm Flange (Ductile Iron)
5
22
9. Bonnet (Brass)
15 5 10. Body (Bronze)
B
6 11. Seat Ring (Stainless Steel)
12. Bottom Cap (Brass)
12 1 17 18 11 13. Spring Casing (Ductile Iron)

Standard Materials:
Other standard material of the pilot construction
include stainless steel, Buna-N, and brass

X - RPD High Pressure Sensing Connection - 1/4 in NPT


Y - RPD Low Pressure Sensing Connection - 1/4 in NPT

2016.1 221
PILOTS AND ACCESSORIES

MODEL 82-PR
PILOT (NORMALLY OPEN)

PRODUCT OVERVIEW
The model 82-PR is a spring and diaphragm operated, normally open pilot valve, with
the sensing chamber(s) separated from the operating chambers. It closes when the
control pressure below the diaphragm exceeds the force of the spring. The model 82-
PR is used as the standard low pressure pilot on model RPS-L&H anticipating surge
valves.

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering instructions.

1. Adjusting Screw (Stainless Steel)


2. Locknut (Stainless Steel)
3. Spring Step (Stainless Steel)
4. Spring Casing (Brass)
5. Spring (Stainless Steel)
6. Stem Locknut (Stainless Steel)
7. Diaphragm (EPDM)
(200 mm)
8. Body (Brass)
9. Bottom Cap (Brass)
10. Disc Retainer (Stainless)
11. Resilient Disc (Buna-N)
12. Inner Valve (Stainless Steel)
13. Spring Casing Screws (Stainless Steel)
14. Clamp Plate (Brass)
15. O-Ring Seals (Buna-N)
FLOW

SCHEMATIC A0667C Standard Materials:


Other standard material of the pilot construction
include stainless steel, Buna-N, and brass

222 2016.1
PILOTS AND ACCESSORIES

MODEL 167
PROPORTIONAL PILOT

PRODUCT OVERVIEW
The 167 Proportional Pilot is a direct acting, diaphragm operated pressure reducing valve.
The valve is held open by the lower diaphragm, opposes the force of the upper diaphragm
to close the valve.

SPECIFICATIONS
• Pilot is available in four models: 16%, 30%, 42% and 60% (outlet pressure vs inlet pressure)
• Max pressure: 400 psi (27.6 bar)
• Max temperature: 180° F (82° C)

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering instructions.

3.2" (81 mm) 1. Body Pilot 167 Stainless Steel


2. Seat 167 Stainless Steel Pilot
6
F

9
4 3. EPDM O-Ring
4. Screw HEX HD 10-32 X 5/8 SST 18-8
4.85" (123 mm)

12
4

5
10
5. Poppet 167 Stainless Steel
14

6. Cap 167 Brass


11
13
3

7. Yoke Pilot 167 316 Stainless Steel


2

7 8. Seat Inner Valve Pilot EPDM / 167


8
Stainless Steel
F
Model 167
1

9. Stem 167 Stainless Steel


10. Clamp Plate 167 PR Brass
11. Adaptor 167
12. Guide Bushing 167
13. Snap Ring
14. EPDM Diaphragm Upper

2016.1
2017.12 223
PILOTS AND ACCESSORIES

MODEL J0223A
BUILDING TRADES REDUCING PILOT

PRODUCT OVERVIEW
• Compact design, corrosion resistant construction
• Brass body with brass bonnet
• Miniature brass 1/8”, 1/4” PTF
• Brass bonnet equipped with pressure adjusting screw
• Indoor applications only
• For use on 3” pressure reducing valves & smaller

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering instructions.

1. Adjusting Screw (Steel)


2. Nut, lock (Brass)
3. Springrest (Steel)
4. Bonnet (Brass)
5. Spring (Steel)
6. Slip ring (Polyethylene)
7. Diaphragm ASSY (Buna-N, Brass, Stainless)
8. Seat-Valve (Acetal)
9. Gasket-Seat (Nitrile)
10. Valve ASSY (Brass, Buna-N)
11. Spring-Valve (Stainless)
12. Body, 1/4 PTF (Brass)
13. Pipe Plug (Brass) *Not shown

Specifications
Fluid: Water Maximum pressure: 400 psig (27 bar)
Gauge Ports: 1/8” PTF
1.50 (38) Operating temperature: Water service 35° to 175° F
(2° to 80° C) Typical flow for water service at 100 psig
(7 bar) inlet pressure, 60 psig (4 bar) set pressure
3.01 (77)

3.41 (87)

and a drop of 15 psig (1 bar) from set 1.3 gpm (4.9 lpm)
1.50 (38)

1.50 (38)

1.03 (26)

Materials
Body: Brass Bonnet: Brass Valve: Brass/nitrile
1.57 (40)
Valve seat: Acetal resin Elastomers: Nitrile
Warranty 2 years Range: 0-125 psig (0-8 bar)

224 2016.1
PILOTS AND ACCESSORIES

STAINLESS STEEL HOSE


STAINLESS STEEL BRAIDED HOSE

COPPER
Standard material for tubing
Corrosion resistant
Reliable and long-term performance

STAINLESS STEEL
Optional upgrade
Significantly stronger and more durable
Corrosion and oxidation resistant

STAINLESS STEEL BRAIDED HOSE


Optional upgrade • Available with stainless or brass ends
Completely flexible
Significantly stronger and more durable
Corrosion and oxidation resistant

Working Connection
Size Lengths
Pressure Type
1/4 in / 6 mm 1/4 in: 1,406 psi / 96.9 bar
3/8 in / 9.5 mm 3/8 in: 984 psi / 67.8 bar
Copper Standard Any SAE
1/2 in / 12.7 mm 1/2 in: 727 psi / 50.1 bar
3/4 in / 19 mm 3/4 in: 511 psi / 35.2 bar
1/4 in / 6 mm 1/4 in: 21,000 psi / 1,447.3 bar
Stainless Optional 3/8 in / 9.5 mm 3/8 in: 14,000 psi / 965.5 bar
Any Compression
Steel Upgrade 1/2 in / 12.7 mm 1/2 in: 10,500 psi / 724.1 bar
3/4 in / 19 mm 3/4 in: 7,000 psi / 482.8 bar
1/4 in / 6 mm 1/4 in: 3,000 psi / 206.8 bar
Braided
Optional 3/8 in / 9.5 mm 3/8 in: 2,500 psi / 172.4 bar
Hose Any SAE / JIC
Upgrade 1/2 in / 12.7 mm 1/2 in: 2,000 psi / 137.9 bar
3/4 in / 19 mm 3/4 in: 1,500 psi / 103.4 bar

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering instructions.
Additionally, include the following information for this product:
• Material(s)

2016.1 225
PILOTS AND ACCESSORIES

MODEL 26
OPERATING SPEED CONTROL

PRODUCT OVERVIEW
The 26 Opening Speed Control is a self-cleaning, opening
speed control. It is used in conjunction with a fixed
restriction orifice that is usually threaded into port 3. The
26 stabilizer allows free flow down to the bonnet (port 1)
and restricts flow up from port 1.
The 26 Opening Speed Control is used as the standard
flow stabilizer (opening speed control) on model 106-PR
or 206-PR pressure reducing valves or any other model
that requires low flow stabilization.

PRODUCT LINE DRAWING STANDARD MATERIALS


1 Body: AISI 303 SST
2 Spring Retainer: ASTM B16 Brass
3/8” 3
(9.5mm) Locknut: ASTM B16 Brass
Adjusting Screw: AISI 303 SST
PORT 2 26 Inner Valve: AISI 303 SST
PORT 3
2” Spring: AISI 303 SST
(50mm)
4 Screw Seal: Buna-N
5
6
ORDERING INSTRUCTIONS
7
Refer to page 244 for the order form and ordering
1-1/4” instructions.
(32mm)
PORT 1

1. Adjusting Screw
2. Locknut
3. Screw Seal
4. Body
5. Inner Valve
6. Spring
7. Spring Retainer

226 2016.1
PILOTS AND ACCESSORIES

FIXED RESTRICTION

PRODUCT OVERVIEW
The fixed restriction is a 303 stainless steel bodied fitting with a stainless steel orifice plug. The fixed restriction
controls the flow rate in the pilot system.
The orifices are sized to provide the proper control to a select series of valve sizes only. This all-stainless steel
version replaces all previous versions of the brass body, with stainless steel insert.

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering instructions.

SIZES
‘A’ 1 / 8 in / 3.2 mm orifice
‘B’ 1 / 16 in / 1.6 mm orifice
‘C’ 3 / 32 in / 2.4 mm orifice
‘D’ 1 / 4 in / 6.35 mm orifice
‘E’ 7 / 64 in / 2.8 mm orifice

'A' = 1/8" 'B' = 1/16"


(3.2MM) (1.6MM)

'C' = 3/32" 'D' = 1/4"


(2.4MM) (6.4MM)

'E' = 7/64"
(2.8MM)

2016.1 227
SPEED CONTROL / NEEDLE VALVES
FLOW CONTROL VALVES / PILOT CHECK VALVES

MODEL 852-B NEEDLE VALVE


The 852-B needle valve is a pilot speed control valve. The body is brass and the stem is stainless steel with a
fine thread for controlling flow. O ring packing assures leak proof, trouble free service. 1/4 in / 6.35 mm NPT
female to female end connections.
Specifications
• Maximum operating temperature: 180° F / 82° C
• Maximum working pressure: 400 psi / 27.6 bar

MODEL MICROMETER NEEDLE VALVES


Micrometer needle valves allow for precise speed control. There is virtually infinite flow adjustment in both
directions. Standard end connections are female-to-female 1/4 in / 6.35 mm NPT.
Standard Materials
Forged brass body, Buna-N seals and stainless steel stem
Specifications
• Maximum fluid temperature: 180° F / 82° C
• Maximum pressure rating: 2000 psi / 138 bar

MODEL MICROMETER FLOW CONTROL VALVES


Micrometer flow control valves allow for precise flow control. There is full flow in one direction and
adjustable restricted flow in the opposite direction. They are standard on certain models, such as BPC pump
control valves and available as an option for other applications. Standard end connections are female-to-
female 1/4 in / 6.35 mm NPT.

Standard Materials
Forged brass body Urethane disc
Stainless steel stem Stainless Retaining Ring Buna-N seals
Specifications
• Maximum fluid temperature: 140° F / 60° C
• Maximum pressure rating: 2000 psi / 138 bar

MODEL 10 &12 PILOT CHECK VALVES


The 10 pilot check valve is standard on all 106 and 206 series valves requiring a pilot check function such as
BPC, PR-C, RPS-C types. It is designed to require a low “cracking” differential pressure to open. The 12 has a
higher “cracking” pressure and requires more differential pressure to open.

Standard Materials:
Body: ASTM B16 brass Seat Ring: ASTM B-16 brass
Inner Valve: Lexan Seals: Buna-N
Specifications:
• Maximum working temperature: 180° F / 82° C
• Maximum working pressure: 400 psi / 27.6 bar

228 2016.1
PILOTS AND ACCESSORIES

MODELS J0098B & J0097B


STRAINERS

PRODUCT OVERVIEW
There are two versions of the standard AISI 316 stainless steel strainer
with 40 mesh stainless steel screens. The standard strainer J0098B
has a 3/8 in / 9.5 mm blowdown/maintenance port for access to the
screen and the 3/8 in / 10 mm NPT inlet and outlet connections. The
J0097B strainer provides a standard 1/4 in / 6.35 mm sensing / gauge
connection.

ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering instructions.

STANDARD MATERIALS
Body: Stainless Steel 316
Screen Retainer: Stainless Steel 316
Screen (40 Mesh): Stainless Steel 316
Screen Retainer Seal: Buna
Blow Down Plug: Stainless Steel 316

Model J0097B

2016.1 229
PILOTS AND ACCESSORIES

MODELS J1521G & J1521M


ARION STRAINERS

PRODUCT OVERVIEW
The Arion series strainers are more suited to dirty water
applications. The dirt is trapped on the inside of the double
mesh screens and collects in the bowl. The double port
construction of the housing prevents the particles from re-
entering the flow stream.
The collected dirt can be flushed directly out to drain by
opening the blowdown. The J1521G strainer has a glass
collection bowl, while the J1521M strainer has a metal bowl.
Standard pressure rating for the strainer is 232 psi / 16 bar.
Body connections are 1/2 in / 15 mm NPT and it comes
complete with a 3/8 in / 9.5 mm blowdown valve and a
discharge tube.

PRODUCT LINE DRAWING STANDARD MATERIALS


Body: Brass
1 Cap: Brass
2
Screens: 18-8 SST
3
(40 mesh optional;
4
80 mesh optional)
12 in 5 Seals: Buna-N
(300 mm)
Packing: P.T.F.E.
6
Bowls: Standard - Trogamid T (Glass)
7
Optional - brass
8
Nuts: Brass
2.5 in Drain Valve: Brass
(65 mm)

1. Blowdown (drain) valve ORDERING INSTRUCTIONS


2. Discharge Tube Refer to page 244 for the order form and ordering
3. Double Mesh 18-8 Stainless Steel Screens instructions.

4. ‘A’ 1/2 in NPT Inlet and Outlet Connections Additionally, include the following information for this
product:
5. Low Velocity Settling Zone
Metal or glass bowl
6. 1/4 in NPT Gauge Connections
May be included as standard with some products
7. Double Neck, Housing Directs Particles Onwards
8. Collection Bowl - Glass (Optional Brass)

230 2016.1
Technical Sizing & Information
TECHNICAL & SIZING INFORMATION

INTRODUCTION
Sizing and selection of the automatic control valve that will meet all of your system design and performance
requirements is critically important. Singer Valve offers the following guidelines and notes to provide a basic
understanding of the operating principals and to assist in the selection process.

FULL AND STANDARD PORTS


Singer Valve manufactures two distinct model series – 106 Full Port and 206 Standard Port valves. Model 206
series valves are similar to Model 106 series except that the seats are one standard pipe size smaller than the
flange sizes. For example, a 6 in / 150 mm 206-PG valve has a 4 in / 100 mm seat diameter. The Model 206 is
often a preferred selection when the flow ranges are suitable. Most sizes are also available in angle (A) pattern
and valves larger than 6 in / 150 mm are also available with the Single Rolling Diaphragm (S) technology.

S106 Series Full Port S206 Series Standard Port SA106 Series Full Port
(6 in / 150 mm PG model shown) (6 in / 150 mm PG model shown) (4 in / 100 mm PG model shown)

Flange Bore
6 in / 150 mm

Seat Bore Seat Bore


6 in / 150 mm 4 in / 100 mm

Guidelines for using the flow versus pressure drop curves:


106-412 106 Series Full Port, Globe Style Valves
106-413 A106 Series Full Port, Angle Style Valves
206-414 206 Series Standard Port , Globe Style Valves
206-414 A206 Series Standard Port , Angle Style Valves

CV AND KV FACTOR & THE STRAIGHT LINE


The flow through a fully open valve may be calculated using the formula:
On-off control directs inlet
Imperial Measure pressure to valve bonnet.
Valve fully closed. Metric Measure
Q (USGPM) = Cv (Valve Constant) Q (L / s) = Kv (Valve Constant)
*√∆P (psi) *√∆P(bar)
where the Cv is the flow in USGPM where the Kv is the flow in l / s when
when there is a 1 psi pressure drop there is a 1 bar pressure drop across
across a fully open valve. a fully open valve.
From the Singer performance curves, Valves that open fully on low
the straight lines indicate the flow vs. pressure drop require their control
On-off control relieves
pressure drop through a fully open pressure from valve chambers (bonnets) to be vented to
valve. The Y axis is drawn at the 1 psi bonnet. Valve fully open. atmosphere. Commonly, altitude and
pressure drop value. Consequently, pump control valves (BPC and DW)
the intersection between the flow are vented to atmosphere and may
curve and the Y axis represents the be selected from the straight line
Cv factor for each valve size. performance curves.

232 2016.1
TECHNICAL & SIZING INFORMATION

DROOPING PORTION OF THE CURVES


As mentioned in the previous section, Cv and Kv Factor & the Straight
Line, the straight lines represent the pressure drop for fully open
Poutlet Poutlet valves.
Should the pressure drop across the valve be low (less than 10 psi / 0.7
Pout Pout
bar) and the control chamber be connected to downstream, the flow
through the valve will be less than when the control chamber is venting
to atmosphere and the valve is fully open.
Pinlet Poutlet When the bonnet is at the same pressure as the downstream (e.g. the
same pressure is on both sides of the diaphragm) there is no resulting
opening force from the diaphragm. The force of the main spring and
the weight of the inner valve (stem vertical) tend to close the valve.
The opening force results from the pressure drop (between upstream
and downstream) acting on the seat area. Flow commences when the
pressure drop is sufficient to overcome the force of the spring and
the weight of the inner valve assembly. Increasing the pressure drop
increases the opening force on the inner valve, permitting greater flow;
at approximately 10 psi / 0.7 bar pressure drop the valve is fully open.
The drooping portion of the curves represent how the flow increases as
the pressure drop increases from zero.

Pilot

WHEN ACTUAL FLOW IS LESS THAN THE VALUE SHOWN BY


THE GRAPH
Bonnet
Usually, required flow is less than that shown on the curves—typically,
pressure reducing valves. The curves show only the maximum flow
available under a given pressure drop. When less than maximum flow
is required, the valve will automatically open the required amount.
Relatively
steady
pressure

Singer Model 106-PR / 206-PR


Pressure Reducing Valve OPERATING RANGES
The letters C, I and M are industry standard designations for
• Relatively steady continuous, intermittent and momentary flows.
pressure downstream C maximum for continuous flow
• Varying inlet pressure I maximum for intermittent flow (peak flow for short duration)
• Varying flow demand M maximum for momentary flow (such as relief valve)

2016.1 233
TECHNICAL & SIZING INFORMATION
Flow vs. Minimum Pressure Drop – 106 Series (PG, PGX, PT / PTC, PGM)
Globe Body, Flat Diaphragm
l/s USGPM Curve 106-412 (1/2 in / 15 mm – 8 in / 200 mm)
700
10000
600 9000
8000 8" (200mm)
500
7000

400
M
6000

5000
300 6" (150mm)
4000
I M
200 3000
C
I
Straight Lines—Flow For a Fully Open Valve (Bonnet vented to atmosphere)

150
2000 4" (100mm)

C M
100 1500
90
80
Curved Lines—Bonnet vented to downstream

70 3" (80mm)

60
1000
900 I M
800 2-1/2" (65mm)
50
700
C
40 600 M
I 2" (50mm)
500
30
C M

Valve Sizes
400

I 1-1/2" (40mm)
20 300 1-1/4" (32mm)
C 1" (25mm)
I M
15

200 C
I M
10 150
9.0
8.0 C
I
7.0
100 M
6.0 90
80
5.0
70
4.0 60 3/4" (20mm)
1/2" (15mm)
50
3.0
M
40

2.0 30

1.5

20
I
1.0 15

0.6 10
1 1.5 2 3 4 5 6 7 8 9 10 15 20 30 40 50 60 70 80 90 100 psi

0.07 0.10 0.15 0.2 0.3 0.4 0.5 0.6 0.7 0.8 1.0 1.5 2.0 3.0 4.0 5.0 6.0 7.0 bar

Minimum Pressure Drop


C = Continuous Service I = Intermittent Service M = Momentary Service
20 ft/s / 6 m/s 25 ft/s / 7.5 m/s 45 ft/s / 14 m/s

234 2016.1
TECHNICAL & SIZING INFORMATION
Flow vs. Minimum Pressure Drop – 106 Series (PG, PGX, PT / PTC, PGM)
Globe Body, Rolling Diaphragm
l/s USGPM Curve 106-412 (6 in / 150 mm – 36 in / 900 mm)
200000

36" (900mm)
10000
150000
9000
8000
M
7000
100000
6000
90000
80000 24" (600mm)
5000
70000
I
4000
60000
C M 20" (500mm)
Straight Lines—Flow For a Fully Open Valve (Bonnet vented to atmosphere)

50000
3000

40000
M
16" (400mm)
2000 30000 I
14" (350mm)
Curved Lines—Bonnet vented to downstream

1500
C
I 12" (300mm)
20000
M M
C
1000
15000 M
900 I 10" (250mm)
800
I

Valve Sizes
700
10000
C M
600
9000
C I 8" (200mm)
8000
500
7000
C M
400
6000 I
5000
300 C 6" (150mm)

4000
I M
200
3000 C

150
I
2000

C
100
1500
90
80

70
1000
60 900
800
50
700
40
600

500
30

400
1 1.5 2 3 4 5 6 7 8 9 10 15 20 30 40 50 60 70 80 90 100 psi

0.07 0.10 0.15 0.2 0.3 0.4 0.5 0.6 0.7 0.8 1.0 1.5 2.0 3.0 4.0 5.0 6.0 7.0 bar

Minimum Pressure Drop


C = Continuous Service I = Intermittent Service M = Momentary Service
20 ft/s / 6 m/s 25 ft/s / 7.5 m/s 45 ft/s / 14 m/s

2016.1 235
TECHNICAL & SIZING INFORMATION
Flow vs. Pressure Drop – 106 Series (PG, PGX, PT/PTC, PGM)
Angle Body, Flat & Rolling Diaphragm
Curve 106-413 (1 in / 25 mm – 20 in / 500 mm)
l/s USGPM

2524 40000 16" (400mm)

2000
30000

12" (300mm)
1500

20000
M
1000 15000 M 10" (250mm)
900
800
I
700
10000
M
8" (200mm)
600 9000
C I
Straight Lines—Flow For a Fully Open Valve Bonnet vented to atmosphere

500 8000
7000
C M
400
6000 I
6" (150mm)

300
5000
C M
4000
I
Curved Lines—Bonnet vented to downstream

200 3000 C
150
I 4" (100mm)

2000

C M
100
1500
90

Valve Sizes
80 3" (80mm)
70

60
1000 I M 2-1/2" (65mm)
900
50 800 C
700
40 M 2" (50mm)
600
I
500
30
C M
400
I
20
300 C 1-1/2" (40mm)
I M 1" & 1-1/4"
15 (25mm & 32mm)
200
C

10 I M
150
9.0
8.0 C I
7.0
100
6.0
90 C
5.0 80
70
4.0
60

50
3.0

40

2.0
30

1.5

20
1 1.5 2 3 4 5 6 7 8 9 10 15 20 30 40 50 60 70 80 90 100 psi

0.07 0.10 0.15 0.2 0.3 0.4 0.5 0.6 0.7 0.8 1.0 1.5 2.0 3.0 4.0 5.0 6.0 7.0 bar
Minimum Pressure Drop
C = Continuous Service I = Intermittent Service M = Momentary Service
20 ft/s / 6 m/s 25 ft/s / 7.5 m/s 45 ft/s / 14 m/s

236 2016.1
TECHNICAL & SIZING INFORMATION
Flow vs. Pressure Drop – 206 Series (PG, PGX, PT / PTC, PGM)
Globe & Angle, Flat & Rolling Diaphragm
Bodies Curve 206-414 (3 in / 80 mm – 40 in / 1000 mm)
l/s USGPM
12620 200000
48" & 40"
(1200 & 1000mm)
10000 150000
9000 M
8000
7000
100000
6000 90000 36", 32", 30" & 28"
5000 80000
I (900, 800, 750 &
700mm)
70000
M
4000
60000 C
24" x 20"
50000
Straight Lines—Flow For a Fully Open Valve (Bonnet vented to atmosphere)

(600 x 500mm)
3000

40000
I 24"x16", 20" & 18"
(600 x 400mm,
2000 C 500 & 450mm)
30000
M M
16" (400mm)
1500
Curved Lines—Bonnet vented to downstream

20000 I
M
I
1000
15000 C C 12" (300mm)

900
800 M
700
10000
I 10" (250mm)
600 9000 C

Sizes
Valve Sizes
500
8000 M
7000 I
C

Valve
400 8" Angle
6000
8" Globe
5000 M (200mm)
300 I
M
4000 C

200 3000
I I 6" Globe
& Angle
C
150
C (150mm)
2000 M

4" Globe
100
1500 & Angle
90
(100mm)
80
I M
70
1000 C
60
900

50 800

700 I 3" Globe


40
600
C (80mm)

500 M
30

400
I
20
300
C
15

200
1 1.5 2 3 4 5 6 7 8 9 10 15 20 30 40 50 60 70 80 90 100 psi

0.07 0.10 0.15 0.2 0.3 0.4 0.5 0.6 0.7 0.8 1.0 1.5 2.0 3.0 4.0 5.0 6.0 7.0 bar

Minimum Pressure Drop


C = Continuous Service I = Intermittent Service M = Momentary Service
20 ft/s / 6 m/s 25 ft/s / 7.5 m/s 45 ft/s / 14 m/s

2016.1 237
TECHNICAL & SIZING INFORMATION
Dynamic Lifter Sizing Graph Curve: 3 in / 80 mm – 8 in / 200 mm
Traditional relief valves for sewage are typically sized larger than a Singer Dynamic Lifter
due to opening forces being lost as the inner valve leaves the seat.
Benefits: Smaller size, smaller footprint and reduced cost
L/S USGPM
1262 20000
8"
(200 mm)
1000
900
800
700 6"
10000 (150 mm)
600
9000
500 8000
7000
400
6000

5000
300 4"
(100 mm)
4000

200
3000
3"
(80 mm)
Maximum Flow
Q- Pipeline Maximum Flow

2000

Valve Size Selection


Valve Size Selection
100
90
80
70
1000
60
900
Q-Pipeline

50 800
700
40
600

500
30

400

20
300

200
Consult Singer Valve
for higher pressures.
10

6.3 100
10 20 30 40 50 60 70 80 90 100 200 Psi

1 2 3 4 5 6 7 8 9 10 13.8 bar

∆P - Minimum Pressure Drop Across Dynamic Lifter


Examples of valve size selection
1) Relief setting 80 psi / 5.5 bar - discharge to atmosphere: Max. flow in main pipeline 1,200 USGPM / 75.7 l / s - Find intersect of 80 psi / 5.5 bar ∆P and
1200 USGPM / 75.7 l / s flow. Select next larger size Dynamic Lifter, e.g., 3 in / 80 mm size.
P - Mimumum Pressure Drop Across Dynamic Lifter
2) Relief setting 55 psi / 3.8 bar - discharge 20 psi / 1.38 bar back pressure: Max. flow in main pipeline 4,000 USGPM / 252.4 l / s
Find intersect of 55 psi – 20 = 35 psi / 2.4 bar ∆P and 4000 USGPM / 252.4 l / s flow. Select next larger size Dynamic Lifter, e.g., 6 in / 150 mm size.
Note:
• If the discharge was to atmosphere, ∆P = 55 psi / 3.8 bar and 4 in / 100 mm size would be selected.
• This graph is based on current practice for standard applications. It is intended to be a guide only and no selection guarantee is implied or intended

238 2016.1
TECHNICAL & SIZING INFORMATION
Flow vs. Pressure Differential
Model 106 Series (PG-AC, PGX-AC, PT-AC, PGM-AC) – Full Port, Globe Body, Flat / Rolling Diaphragm
Anti-Cavitation Valve Curve 106-415 (1 in / 25 mm – 36 in / 900 mm)

l/s USGPM
9000 150000 36" - 900 mm
8000
7000
100000
6000 90000
5000 80000
70000
4000 60000
50000
• Differential Pressures over 300 psi / 21 bar, check with Singer Valve.

3000
2500 40000 24" - 600 mm
2000 30000
• Solid line and below suitable for continuous service.

1500
20" - 500 mm
20000
16" - 400 mm
1000 15000
900
800
700 12" - 300 mm
10000
600 9000
8000 10" - 250 mm
500
7000
400 6000 8" - 200 mm

Valve Sizes
5000
300
Flow

4000

200 3000
6" - 150 mm
150
2000

100 1500
90
4" - 100 mm
80
70
1000
60 900
50 800 3" - 80 mm
700
40 600
2.5" - 65 mm
500
30
400

20 300
2" - 50 mm
15
200
1.50" - 40 mm
10 150 1.25" - 32 mm
9.0 1" - 25 mm
8.0
7.0
100
90
80
70
60
50
40 50 60 70 80 90 100 150 200 300 psi
30 40 50 60 70 80 10 15 20 bar

Pressure Differential

2016.1 239
240
This chart applies to cold water only.
Sigma
Cavitation Chart (Guide Only)
kpa bar psi
0.15 0.5 0.8 Value
2,758 27.58 400

Consult Severe Moderate No Cavitation


2,413 24.14 350 Singer Valve 1,000 – 5,000 hours 5,000+ hours
Unpredictable before failure before failure
2,068 20.7 300
TECHNICAL & SIZING INFORMATION

1,724 17.24 250

1,379 13.8 200

Inlet Pressure
1,034 10.34 150

689 6.89 100


P2 - (- Pv)
345 3.45 50
Sigma (σ) =
∆P
172.4 1.72 25
0
0 20 40 60 80 100 120 140 160 180 200 psi
1.38 2.76 4.14 5.52 6.89 8.27 9.65 10.03 12.41 13.8 bar
138 276 41.4 552 689 827 965 1,103 1,241 1,379 kpa

Downstream Pressure
Failure times are for non-AC valves
Where P2 = Downstream pressure
ΔP = Differential pressure
Pv = 14.4 Psi / 1 Bar / 103 KPa

2016.1
FLANGE DIMENSIONS—DUCTILE IRON VALVES

STANDARD: ANSI B16.42 - 1998 - CLASS 150 AND 300


Nominal Diameter Diameter of Number Diameter
Pipe Size of Flange Bolt Circle of Bolts of Bolt Holes
Pressure Class 150# 300# 150# 300# 150# 300# 150# 300#
1.5 5.00 6.12 3.88 4.50 4 4 5/8" 7/8"
2 6.00 6.50 4.75 5.00 4 8 3/4" 3/4"
2.5 7.00 7.50 5.50 5.88 4 8 3/4" 7/8"
3 7.50 8.25 6.00 6.62 4 8 3/4" 7/8"
4 9.19 10.19 7.50 7.88 8 8 3/4" 7/8"
6 11.19 12.69 9.50 10.62 8 12 7/8" 7/8" FLANGE
DIAMETER
8 13.50 15.00 11.75 13.00 8 12 7/8" 1"
10 16.00 17.50 14.25 15.25 12 16 1" 1-1/8" 'D' DIM
12 19.00 20.50 17.00 17.75 12 16 1" 1-1/4"
14 21.00 23.00 18.75 20.25 12 20 1-1/8" 1-1/4"
16 23.50 25.50 21.25 22.50 16 20 1-1/8" 1-3/8" FLANGE FEET
FOR SAFETY
18 25.00 28.00 22.75 24.75 16 24 1-1/4" 1-3/8" AND CONVENIENCE

20 27.50 30.50 25.00 27.00 20 24 1-1/4" 1-3/8"


24 33.00 36.00 29.50 32.00 20 24 1-3/8" 1-5/8"
30 38.75 43.00 36.00 39.25 28 28 1-3/8" 2"
36 46.50 50.00 42.75 46.00 32 32 1-5/8" 2-1/4"
Dimension in (inches)

STANDARD: ISO 7005-2 - 1998


Nominal
Diameter of Flange Diameter of Bolt Circle Diameter of Bolt Holes Number of Bolts
Pipe Size
PN-10 PN-16 PN-25 PN-40 PN-10 PN-16 PN-25 PN-40 PN-10 PN-16 PN-25 PN-40 PN-10 PN-16 PN-25 PN-40
40 155 155 155 155 110 110 110 110 19 19 19 19 4 4 4 4
50 152 152 152 152 125 125 125 125 19 19 19 19 4 4 4 4
65 178 178 178 178 145 145 145 145 19 19 19 19 4 4 8 8
80 200 200 200 200 160 160 160 160 19 19 19 19 8 8 8 8
100 233 233 260 260 180 180 190 190 19 19 23 23 8 8 8 8
150 285 285 310 310 240 240 250 250 23 23 28 28 8 8 8 8
200 343 343 381 381 295 295 310 320 23 23 28 31 8 12 12 12
250 406 406 445 445 350 355 370 385 23 28 31 34 12 12 12 12
300 483 483 483 520 400 410 430 450 23 28 31 34 12 12 16 16
350 533 533 584 584 460 470 490 510 23 28 34 37 16 16 16 16
400 597 597 648 648 515 525 550 585 28 31 37 40 16 16 16 16
500 699 699 775 775 620 650 660 670 28 34 37 43 20 20 20 20
600 838 838 838 915 725 770 770 795 31 37 40 49 20 20 20 20
700 895 910 960 995 840 840 875 900 31 37 43 48 24 24 24 24
800 1,015 1,025 1,085 1,140 950 950 990 1,030 34 40 49 56 24 24 24 24
900 1,115 1,125 1,185 1,285 1,050 1,050 1,090 1,170 34 40 49 56 28 28 Dimension
28 in28
(mm)

Note:
ISO flange diameters may vary slightly from the standard, as the flange bolt pattern is drilled on an ANSI
valve flange.

2016.1 241
ENGINEERING NOTES

In this section, you will find additional engineering notes for the main valves and also the
anti-cavitation valve.

MAIN VALVES DATA (US & METRIC UNITS & ISO)


Engineering Notes:
• Drilled as per ANSI B16.42 or threaded as per ANSI B1.20.1
• ANSI flanges drilled to ISO 7005-2 - 1998 / BS54504 PN 10, 16, 25, or 40, or threaded BSPT
• Class 150 machined flat faced / Class 300 machined raised faced.
• Castings are based on ANSI Class 150 or Class 300 standards.
• For conditions where working pressures exceed 300 psi / 20.7 bar, consult with Singer Valve
• Allow 1/8 in / 3 mm for machining tolerance.
• Allow one to three feet for installation and maintenance clearances. Consult Singer Valve for
certified dimensions.
• Preferred method of stem installation is vertically; on valves 10 in / 250 mm and larger the vertical
installation method is mandatory.
• Add a minimum 6 in / 150 mm on one side, for Pilot System.

ANTI-CAVITATION DATA

106-AC / 206-AC (206 IN LARGE VALVE SIZES ONLY)


As a guide, if downstream pressure of an automatic control valve is less than 35% of the inlet
pressure, there is a risk of cavitation damage occurring. Use 106-415 to select the valve size.
Cavitation chart on page 240 can also be used to determine if a valve is cavitating. Plot the maximum inlet
pressure against the minimum outlet pressure.
• If this plotted point is to the right of the 0.8 line (e.g. you are in the “No Cavitation” zone) then use
performance curves from chart 106-412, 106-413 and 106-414 on pages 234 - 237 to select the valve
size.
• If this plotted point is to the left of the 0.8 line then use performance curves 106-415 to select the
valve size.

Refer to Singer Performance Curves and Cavitation Charts in the Technical & Sizing Information section page
231 or contact Singer Valve.

242 2016.1
HOW TO ORDER

HOW TO ORDER
Order forms can be found on page 244-246.
FAX/EMAIL: Complete the order form, and fax OR email it to your local Singer
Valve Sales Representative. Refer to singervalve.com/find-a-rep for sales
representative contact information.
WEBSITE: Complete a Request a Quote form on singervalve.com AND attach a
scanned PDF copy of the completed order form.
When completing your order form, please include as much detail as possible.
Specifically, always include the following:
• Product model number
• Globe or angle pattern
• End connections
• Valve size
Please note that some products will require additional information, refer to the specific product page sheet
for clarification.

PARTS AND REPAIR KITS


To order Parts and Repair Kits, please complete the order form and include the following information:
• Valve model
• Revision
• Valve size (inches or millimeters)
• Maximum inlet pressure (psi or bar)
• Serial number

This information can be found on the identification plate on the product.


SINGER VALVE INC. REV.
MODEL
Identification Plate Sample
MAX
SIZE IN. INLET PSI
SER. NO

Essential information required includes valve function, material, pressure rating, end connections, pilot
controls and control adjustment ranges.

TO SPECIFY SINGER PRODUCTS


Singer Specifications are set up in a modular fashion.
1. Select the product you require. Refer to the specification which accompanies that product.
2. Refer to the Main Valves section (page 11). Add the specification for the Singer Main Valve
Body selected.
3. Refer to the Main Valves Options section (page 62). Add the addendum to your Main Valve specification
(if applicable).
4. Refer to the Pilots & Accessories section (page 207). Add the specification for the Singer pilot and/or
accessory selected (if applicable).

2016.1 243
CONTROL VALVE & ACCESSORIES ORDER FORM
EMAIL OR FAX TO YOUR LOCAL SINGER VALVE SALES REPRESENTATIVE.
REFER TO SINGERVALVE.COM/FIND-A-REP FOR CONTACT INFORMATION.

X156

244
SPI-MV ORDER FORM

245
420-DC / 420-AC ORDER FORM

246
SINGER VALVE INC. GLOBAL OFFICES

CANADA HEAD OFFICE USA OFFICE UNITED ARAB EMIRATES OFFICE

12850 – 87th Avenue Singer Valve LLC Singer Valve Middle East FZE
Surrey, BC V3W 3H9 1873 Scott Futrell Drive PO Box 121326
Canada Charlotte, NC 28208 SAIF Free Zone, Q3 – Unit 94
Sharjah International Airport
Tel: (604) 594 5404 Tel: (704) 391 5785 FREE ZONE
Fax: (604) 594 8845 Fax: (704) 391 5768 Sharjah, UAE
Toll Free Fax (Canada & USA): Toll Free (USA):
1 800 663 7266 1 888 764 7858 Tel: +971 6 557 8116
singer@singervalve.com mark@singervalve.com Fax: +971 6 557 8117
canadian@singervalve.com

COLOMBIA OFFICE MALAYSIA OFFICE CHINA OFFICE

Singer Valve Latin America SVM Water Controls Sdn. Bhd. Singer Valve (Taicang)
Carrera 45, No. 16 Sur 190 No 6, Jalan MJ 4, Medan Maju Company Ltd.
Opalo 1105 – El Poblado Jaya, No.88 East Dalian Road,
Medellin, Colombia Batu 7, Jalan Kelang Lama Taicang, Jiangsu, China
46200 Petaling Jaya
Tel: +57 310 4194165 Selangor Darul Ehsan, Tel: 86 512 5320 6188
pegan@singervalve.com Malaysia Fax: 86 512 5320 6099
lijun@singervalve.com
Tel: 603 7784 4043 / 7784 4044
Fax: 603 7781 8312
svmwc@svm.com.my

SINGERVALVE.COM

2016.1
LET US PROVIDE YOU A
SINGER SOLUTION.

Connect with us today.


singervalve.com
Canada • USA • Colombia • UAE • Malaysia • China

You might also like