Tender/ Proposal Description: Supply, installation, testing & commissioning of Electrical Equipments
(11/0.415KV,1500 KVA Sub-Station and 500 KVA Generator)
Invitation Reference No. : DRBPI/Electrical Equipments/2021/271, Date: 07-03-2021
Tender Package No: DRBPI/Electrical Equipments/2020-21/3ka-5
Tender/Proposal ID No: 550238

Item Name of Goods Detailed Technical Specification and Standards Inspection and/or Country of
No. required tests required and Origin
test place
1. 1500 KVA OIL Three phase oil immersed, naturally air cooled Energypac Engineering Energypac
IMMERSED Type transformer according to DVE/IEC/DIN/BSS Standard Ltd. Baruipar, Savar, Engineering Ltd.
Indoor with 3 nos. HT Bushings and 4 nos. LT Bushings Dhaka, Bangladesh Bangladesh
Distribution
arranged on tank top, conservator, oil level-indicator,
Transformer
drain and fitting valves, lifting lugs, bi-directional
rollers with first filling of oil in Transformer.

Rated Capacity : 1500KVA


Rated Frequency : 50Hz
Rated Voltage & Current : 11000V & 78.75 A
(Primary)
Secondary : 415V & 2085 A (Secondary)
Installation : Indoor
Vector Group : Dyn 11
HV Connections : 03 Porcelain Bushing
LV Connections : 04 Porcelain Bushing
Off Load tap Changer : +2.5%, 0, -2.5%, -5%, -7.5%
Ambient Temperature : 40 0C

Temperature Rise
In Oil : 60 0C (Max)
In Coil : 65 0C (Max)
Star point brought out & loadable up to: 100%
Max. Service altitude : 1000 Meters
Installation : Indoor/Outdoor
No Load Losses : 2900W
Full Load Losses : 19500W
Impedance : 6% (approx)
Efficiency : 98%; Cooling: ONAN
Tolerances, As per IEC 600076
Total Losses : +10% of the total losses
Component losses : +15% of each
Component loss, Provided that the tolerance for total
losses is not exceeded

Accessories:
Silicagel Breather
Thermometer
Bucholz Relay (For Temperature Protection)

Origin:
Core : Kawasaki, Japan/Posco, Korea/Cofid, Germany
or Equivalent.
Insulating Materials : Origin: Italy, Wiedmann
Switzerland.
Copper Strip : BRB, Singapore.
Bucholz Relay : Q J, P & T, Origin: Brand & Country of
Origin: Italy, Germany.
Transformer Oil : Transol (Sabita Chemicals Company)
India/ Hyrex, Malaysia.
Super Enamelled Copper Wire: GAZI; Painting: Powder
Coated.
Manufacturer By: Energypac Engineering Ltd.,
Bangladesh.
2. 11 KV HT Supply, Installation, Testing & Commissioning of 11KV, Energypac Engineering Energypac
SWITCHGEAR 50Hz, TPN+E Electrical H.T Switchgear enclosure made Ltd. Baruipar, Savar, Engineering Ltd.
With VCB by 14 SWG sheet steel clad powder coated, dust and Dhaka, Bangladesh Bangladesh
vermin proof, free standing, floor mounting, indoor
type with three phase hard drawn electrolytic copper
bus-bars & internal wiring with anti rust paint The H.T
Switchgear will be supplied with the following Vacuum
Circuit Breaker & Accessories.
Vacuum Circuit Breaker (Fixed Type)
01 No. 11KV, 630A, 50Hz, 20KA (3sec) with Motor
operated mechanism, closing solenoid, shunt releases,
auxiliary contacts 5NO+5NC, limit switch (1NO+1NC)
for indication "Closing spring charged", mechanical
ON/OFF/TRIP indicator.
Brand & Country of Origin: ABB, Italy

02 Nos. Cast resin insulated Potential Transformer,


ratio: 11/.11KV, Class 0.5, 50VA.
01 No. MCB, TP of Adequate rating for PT secondary
Protection.
03 Nos. Cast resin insulated double core CT, ratio:
150/5/5A, 1st core for metering & 2nd core for
protection.
Core 1: 10VA, Class 0.5M5
Core 2: 15VA, Class 10P10
01, No. Digital Ammeter (0-150A) with selector switch ;
02 Nos. ON/OFF Push Button.
01 No. Digital Voltmeter (0-15KV) with selector switch ;
03 Nos. Indicating Lamps ON/OFF/TRIP.
01 No. Panel Heater
01 No. Triple Pole IDMT Relay for Over Current, Short
Circuit & Earth fault protection.

Brand & Country of Origin: ABB, Italy, Siemens


Germany, France.
CT, PT- Siemens, Germany or France or Italian made
brand.
IDMT Relay – ABB, Italy, Siemens, Germany.
Digital Ammeter & Voltmeter: Russian;
CB: TP MCB for PT secondary Protection, Siemens.

Assembly By: Energypac Engineering Ltd.,


Bangladesh.
3. LT SWITCHGEAR Supply, Installation & Commissioning of 415V, 50Hz Energypac Engineering Energypac
hard drawn electrolytic copper bus-bars TPN (2800A) & Ltd. Baruipar, Savar, Engineering Ltd.
ECC (Half) Electrical Panel Board made by 16 SWG Dhaka, Bangladesh Bangladesh
Sheet steel clad, dust & vermin proof floor mounted
indoor type & painted with powder coated paint. The
board will be manufactured under IEC compliance
stated in design & specification. All component &
circuit breaker must comply with IEC & BS Standard
stated in design & specification. The contactor should
have to provide shop drawings which will be collected
from manufacturer and will submit it to the consultant
for approval.
The Low Tension Switchgear (L.T Panel) will be
supplied with the following circuit breakers &
accessories.
02 Nos. 1600A Electrolytic tinned coated hard drawn
Copper bus-bar. (For TPN each)
01 Nos. 1600A Electrolytic tinned coated hard drawn
copper bus-bar as earth bar.
All bus-bar will be installed at separated chamber.
All copper bus-bar will be covered by bus-bar tapping
(Red, Yellow & Blue).
01 No. Ammeter with Selector Switch (0-2500A).
01 No. Voltmeter with Selector Switch (0-500V).
03 Nos. Current Transformer (2500:5A).
03 Nos. Inducting lamp (Red, Yellow & Blue).
03 Nos. Control Fuse with carrier.

Circuit Breaker:
Brand & Country of Origin: ABB, Italy, Siemens
Germany, France made another brand can be accepted
Incoming:
01x2500A TP ACB, 100KA (DESCO) & 01x2000A TP ACB,
65KA (GEN LIMITED LOAD) OR Enhance With stored
energy motor charged operating mechanism having
special features: Microprocessor controlled adjustable
thermal overload, adjustable electromagnetic short
circuit releases; Electronic trip unit with DIP Switch
setting PR121/P which has operation without the need
for an external power supply; L : Protection against
overload with inverse long time delay trip; I :
Protection against Instantaneous short circuit with
adjustable trip current threshold.
Outgoing:
01x1600A TP ACB, 65KA FOR FLOOR MDB {GF FLR. M/C
& Services, HVAC (1st, GF), office (GF,1st)} (ACB
Technical specification as per above mention)
01x1600A TP MCCB, 70KA (For PFI), in the drawing
shown 1250A TP MCCB, it will be changed by 1600A TP
MCCB.
01x1000A TP MCCB, 50KA (with adjustable thermal
overload and adjustable magnetic short-circuit
releases) for future expansion or Depend on
management requirement.
01x320A TP MCCB, 36KA (with adjustable thermal
overload and adj. magnetic short circuit releases)
01x250A TP MCCB, 36KA (with adjustable thermal
overload and adj. magnetic short circuit releases)
01x63A TP MCCB, 25KA (with adjustable thermal
overload and adj. magnetic short circuit releases)
01x100A TP MCCB, 25KA (with adjustable thermal
overload and adj. magnetic short circuit releases)
01x20A SP MCB, 6KA
01x20A SP MCB, 6KA
01x20A SP MCB, 6KA
01x20A SP MCB, 6KA
01x32A TP MCB, 6KA
Brand & Country of Origin: ABB, Italy, Siemens
Germany, France.
CT. PT: Siemens, Germany or France or Italian Made
brand.

Assembly By: Energypac Engineering Ltd.,


Bangladesh.
4. 900KVAr The Automatic Power Factor Improvement Plant (PFI) Energypac Engineering Energypac
Ltd. Baruipar, Savar, Engineering Ltd.
Automatic PFI will be supplied with the following materials.
Dhaka, Bangladesh Bangladesh
Plant 01 No. 1800A Electrolytic tinned coated hard drawn
copper bus-bar.
1 No. 900A Electrolytic tinned coated hard drawn
copper bus-bar as earth bar.
All Bus-bar will be installed at separate chamber.
All copper bus-bar will be covered by bus-bar tapping
(Red, Yellow & Blue).
15 Nos. Inducting lamp (Red, Yellow & Blue).
16 SWG power coated Sheet steel clad, dust and
vermin proof, free standing, floor mounting, 415V, 50
Hz, 900 KVAR Indoor type Automatic Power Factor
Improvement Plant, comprising:
Capacitor Bank:
Brand & Country of Origin: Iskra,
Slovenia/ABB/EPCOS, India/Equivalent
7 Nos. 4*25 KVAR Bank of TP dry type Power
Capacitors with built-in discharge coil.
3 Nos. 2*25 KVAR Bank of TP dry type Power
Capacitors with built-in direct discharge register.
2 Nos. 1*12.5 KVAR Bank of TP dry type Power
Capacitors with built-in direct discharge register.
1 No. 1*25 KVAR Bank of TP dry type Power Capacitors
with built-in direct discharge register.
1 No. 1*12.5 KVAR Bank of TP dry type Power
Capacitors with built-in direct discharge register.
Relay:
Brand: Mikro Malaysia or Equivalent
13 Stage Power Factor Control Relay.
01 No. 13 Step reactive power factor control relay
which perform the switching of capacitor in automatic
power correction equipment depending on changing
reactive power complete with Luminescent Indicator
and Digital Power Factor Meter.
Magnetic Contactor:
Brand & Country of Origin: ABB, Italy, Siemens
Germany, France.
13 Nos. Magnetic Contactor with adequate rating as
per Capacitor Bank.
14 Nos. Circuit breaker of adequate rating. Brand &
Country of Origin: ABB, Italy, Siemens Germany,
France.
13 Nos. Indicator lamps
01 set control fuses (4 nos. SP MCB)

Assembly By: Energypac Engineering Ltd., Bangladesh.


5. HT Heat Shrink Supply and Fitting/Fixing of Heat Shrink kit as per Local Source, Moon Moon Power
Power Engineering, Engineering,
KIT drawing, design & instruction of engineer-in-charge.
Bangladesh Bangladesh
Supply & Installation by: MPE
6. Installation of INSTALLATION, TESTING & COMMISSIONING OF SS Moon Power Moon Power
Substation EQUIPMENT WITH RELEVANCE: 11 KV HT SWITCHGEAR: Engineering, Bangladesh Engineering,
Equipment Installation, testing & commissioning of 11 KV, 50Hz, indoor Bangladesh
type High Tension (HT) Switchgear on prepared foundation
including conducting all kinds of tests of the circuit, safety
devices, various components etc, of the switchgear by
placing the same designed place with the help of manual
labour & also with chain pulley & other mechanical devices
including covering all risks by working agency as per
manufacturer’s instruction manual & also as per direction of
the Engineer-in charge Complete as required Excluding
supply of consumables like: Angle frame, Cable support,
Controll cable, U-channels, Foundation Nuts, Bolts, etc.
1500KVA Transformer
Installation, testing & commissioning of 3-phase above
mentioned capacity 11KV/415KV, prepared all kinds of
platform/C.C foundation including conduction all kinds of
test, such as the insulation of coil, di-electric strength of oil &
commissioning the same complete as required including
placing the Transformer in designed place with the help of
manual labour & also with Chain pulley or other light
mechanical devices including covering all risks by instruction
of the Engineer-in charge completed as required. Excluding
supply of consumables like: Angle frame, Cable support,
controll cable, U-channels, foundation Nuts, Bolts, etc.
Supply & Installation by: MPE
LT SWITCHGEAR: Moon Power Moon Power
Installation, testing & commissioning of 3-phase 415V, 50Hz, Engineering, Bangladesh Engineering,
indoor type Low Tension (LT) Switch gear on prepared C.C Bangladesh
foundation including conducting all kinds of test of LT
Switchgear & commissioning the same by placing it in
designed place with the help of manual labour & mechanical
devices as per manufacturer’s instruction manual & also as
per direction as the Engineer-in-charge complete as required
excluding Supply of consumables like: Angle frame, cable
support, control cable, U-Channels, foundation Nuts, Bolts,
etc.
Supply & Installation by: MPE
PFI PLANT: Moon Power Moon Power
Installation, testing & commissioning of 3-phase 415KV, Engineering, Bangladesh Engineering,
50Hz, indoor type power factor improvement (PFI) Plant on Bangladesh
prepared C.C foundation including conducting all kinds of
test of PFI & commissioning the same by placing it in
designed place with the help of manual labour & required
mechanical devices as manufacturer’s instruction manual &
also as per direction of the Engineer in charge completed as
required. Ex cluding supply of consumables like: Angle frame,
Cable Support, Controll cable, U-Channels, Foundation Nuts,
Bolts, etc.
10. 11 KV DROPOUT 11 KV DROPOUT FUSE : Local Source Origin: UK/ Moon Power
FUSE : Technical Specification : France/Switzerland/ Engineering,
Rated Voltage (Nominal) : 11 kV Pakistan Bangladesh
Rated Maximum Voltage : 15 kV
Rated Frequency : 50 Hz
B I L : 75 kV
Rated Current RMS : 30A
Interrupting Current RMS : 10 kA
Withstand Test Voltage
Dry, 1 Min. : 35 kV
Wet, 10 sec. :30 kV
Supply & Installation by: MPE
11. 11 KV LIGHTING 11 KV LIGHTING ARRESTOR : Local Source Origin: UK/ Moon Power
ARRESTOR Technical Specification : France/Switzerland/ Engineering,
Rated Voltage (RMS) : 9 kV Pakistan Bangladesh
Frequency : 50 Hz
Minimum Spark Over (RMS) : 14 kV
Maximum Spark Over (RMS) : 40 kV
Maximum Impulse Spark (Crest) : 45 kV
Withstand Voltage
Rated system voltage: 12KV
Wet, 10 sec. : 24 kV
Dry, 1 min. : 28 kV
Discharge 33 kV (Crest) : 5 kA
Impulse Current Withstand : 55 kA

Supply & Installation by: MPE


12. Cable Ladder Cable Ladder (SS Related) Moon Power Moon Power
Engineering, Bangladesh Engineering,
Bangladesh
13. 11KV PT RATIO 11kv Pt ration; as per mentioned capacity with testing in REB REB ,Bangladesh Moon Power
lab & REB line connection, carrying with fitting materials Engineering,
(1Set=03Nos) Bangladesh
14. 11KV CT RATIO 11kv Ct ration; as per mentioned capacity with testing in REB REB, Bangladesh MPE,
lab & REB line connection, carrying with fitting materials Bangladesh
(1Set=03Nos)
15. On grid Solar On grid Solar System Capacity: As per Drawing REB, Bangladesh MPE,
System Bangladesh
16. EARTHING FOR Earthing For Substation MPE, Bangladesh MPE,
SUBSTATION Bangladesh
17. EARTH Installation of 1x20’, 1 ½” dia GI Pipe having ¼” hole at
ELECTRODE required’ interval buried upto the depth of 120’-0” (depend
on value 1ohm) (with connecting copper link 16mm) in the
damp soil including 12.7mm copper rod from up to
connecting copper link through GI Pipe. Transformer Body,
Neutral, HT panel, HT meter body etc.
18. EARTHING BLOCK Installation, testing and commissioning of copper earthing MPE, Bangladesh MPE,
block with required nos. of ¼” hole one for ECC connection Bangladesh
Size -300mm x 30mm x 12mm and another for transformer
neutral earthing.
19. EARTHING LEAD Installation of earthing lead, 12.7mm copper wire thorough MPE, Bangladesh MPE,
Thorouth 1” dia GI Pipe/Surface from earthing block to earth Bangladesh
electrode in duding interconnection between two electrodes
20. EARTH Installation of 12.7 mm copper earth continuity conductor MPE, Bangladesh MPE,
CONTNUITY ruining from the bodies of substation equipment to the Bangladesh
CONDUCTOR earthing block.
Supply & Installation by: MPE
21. HT Power Cable HT Power cable size: 3x120rm (N2XSEYFGby) (can be BSCIC Industrial State BRB Cable
varied) Kushtia-7000, Industries Ltd.
Bangladesh Bangladesh
22. LT Power Cable LT Power cable size: 4x1C-3x500rm NYY [TPN] BSCIC Industrial State BRB Cable
Kushtia-7000, Industries Ltd.
Bangladesh Bangladesh
23. PFI Power Cable PFI Power cable size: 3x1C-2x400rm NYY [TP] BSCIC Industrial State BRB Cable
Kushtia-7000, Industries Ltd.
Bangladesh Bangladesh
24. Earth Continuity 26.0 EARTH CONTINUITY CONDUCTOR CABLE 1*1CX50RM BSCIC Industrial State BRB Cable
Conductor Cable BYA Kushtia-7000, Industries Ltd.
Bangladesh Bangladesh
25. 500KVA GEN:01 With Foreign Made Canopy France/Germany/Italy D G Power Ltd.
Generator with Supply, installation testing and commissioning of /USA/ Japan/ Korea/ Bangladesh.
foreign Made 500KVA (Prime rating), 415V, 50Hz, P.f, o.8, 3-phase 4- UK.
Canopy wire diesel generator for parallel operation with
Foreign made acoustic canopy (sound level max. 85
dB@ 7m), battery, Battery charger. The control panels
of generators must have auto synchronizing and load
sharing facilities for parallel operation. The engine
Alternator, Set mounted control panel; module etc.
must be manufactured assembled and tested from
France/Germany/Italy /USA/ Japan/ Korea/ UK. The
diesel generator and its accessories must comply with
the technical requirement of relevant local authority.
Water cooled radiator with blower fan (water cooled
engine only) with fan guards and fuel and injection
pump and additional fuel tank with necessary pumping
system etc. electrically operated with ammeter
lubricating oil pump, auto- speed governor air cleaner
fuel and oil tank, automatic safely shut off for high
water temperature, low oil pressure, over speed etc.
water temperature gauge, oil pressure gauge
tachometer, hour meter, start and stop switch,
exhaust silencer, fly wheel coupling steel disc.
vibration isolator mounding steel base frame to
support radiator, including all equipment and
accessories complete for operation. All complete in all
respect as per direction of the engineer-in-charge.

Full set of tools & kits necessary for operation &


maintenance (O&M). All complete in all respect as per
direction of the engineer-in- charge. List of spares
requirement for two years to be enclosed and supplied
as cost of maintenance to considered as free service
maintenance warranty period with free spare
replacement. And also a 7 years spares available after
free period.

Service & maintenance fee for each year for this 7 year
period excluding the cost of spare. The cost of spares
but including the cost consumables & auxiliaries.

26. Synchronizing SYNCHORONIXING PANEL:


Panel Controller: 2 no Deep sea 8610; income : 1 no

800Amp, MCCB, brand: shown above


1 no 800 amp, MCCB, Brand: shown above
Outgoing ACB:
1 No 1600ACB, Brand: shown above
Cupper BUS bar capacity as per drawing
Relay(AC/DC)- Schneider electric/ equivalent
Box made with 16 SWG steel sheet powder
Coted paint.

Thanking You,