FUJI IRISDEL
PARAMETROS NVAS380
– Parameter
INTEGRATED


 Speed curve configuration : F00 ~ F05
F00
F01
 F28
F02 S Jerk T0(S curve jerk start at start T0)
F03 S Jerk T1(S curve jerk at end of acceleration T1)
F04 S Jerk T2(S curve jerk at start of deceleration T2)
F05 S Jerk T3(S curve jerk at end of deceleration T3)

F03 F04
Speed

F00 F01

F02 F05

Time
2
FUJI IRISDEL
PARAMETROS NVAS380
– Parameter
INTEGRATED

 F06 ~ F08
F06 Rated speed Unit: mm/s
F07 Rated speed of the elevator Unit: RPM on the data plate of the motor
F08 Encoder Pulses 8192 (by using T010 PG card)

Motor Type Load(Kg) Speed (m/min) Speed (mm/s) RPM


BOMCO 630 60 1000 96
BOMCO 630 90 1500 144
BOMCO 630 105 1750 168
BOMCO 800 60 1000 96
BOMCO 800 90 1500 144
BOMCO 800 105 1750 168
BOMCO 1000 60 1000 96
BOMCO 1000 90 1500 144
BOMCO 1000 105 1750 168
YTW2-260GF 1150 60 1000 91
YTW2-260GF 1150 90 1500 136.5
YTW2-260GF 1150 105 1750 159.2
YTW2-260GF 1350 60 1000 91
YTW2-260GF 1350 90 1500 136.5
YTW2-260GF 1350 105 1750 159.2
YTW2-260GF 1650 60 1000 91
YTW2-260GF 1650 90 1500 136.5
YTW2-260GF 1650 105 1750 159.2
3
FUJI IRISDEL
PARAMETROS NVAS380
– Parameter
INTEGRATED

 F06 ~ F08
F09 Parking floor by parking switch Eg. If 3rd floor, set “3” as decimal
F10 Floor offset
F11 Total number of floor Eg. If 25 floor, set “25”

Example) Lift A Lift B Lift C

9 9 9 Lift A Lift B Lift C


8 8 8 F10 2 1 0
7 7 7 F11 9 10 11
6 6 6
5 5 5
4 4 4
3 3 3
2 2 2
1 1 1
-1 -1
-2
4
FUJI IRISDEL
PARAMETROS NVAS380
– Parameter
INTEGRATED

 F12 ~ F17
F12 Rescue speed & inspection speed Unit: mm/s  Fixed value (0.250 – 15m/min)
F13 Re-leveling speed (creeping speed) Unit: m/s  Fixed value (0.020 – 0.060m/s)
F14 Door-closing delay for hall calls Unit: 0.1 second
F15 Door-closing delay for car calls Unit: 0.1 second

Example) Time to set 3 seconds 5 seconds 15 seconds


Data 3 5 15

F16 Brake delay Unit: 0.1 second


F17 Operation removal delay Unit: 0.1 second

Operation command
F16 F17
Brake contactor
5
FUJI IRISDEL
PARAMETROS NVAS380
– Parameter
INTEGRATED

 F18 ~ F24
F18 Fire homing floor
F19 Second fire homing floor
F20 Homing delay time If no any call, elevator return after setting time
F21 Leveling switch delay Unit: mm (Fixed value  6)
F22 1st homing floor If no any call, elevator return to setting floor
F23 Group mode setting Unit: 0.1 second
F24 NA

Example)
Homing floor setting (F22)

F22  1st homing floor


F196  2nd homing floor
(In case of duplex system, F196 works as a dispersion floor)

Group mode setting (F23)

2  Group control (more than 3 elevators)


3  Duplex or simplex
6
FUJI IRISDEL
PARAMETROS NVAS380
– Parameter
INTEGRATED

 F25 ~ F28
F25 Input Type 1(X0-X15 Input N/O,N/C setup) Standard  12531
F26 Input Type 2(X16-X31 Input N/O,N/C setup) Standard  13184
F27 Input type 3(N.O./ N.C. setting for GX0- GX15 input point) Standard  0
F28 Input type 4(N.O./ N.C. setting for HX0- HX15 input point) Standard  671
1 2 4 8 16 32 64 128 256 512 1024 2048 4096 8192 16384 32768
X0 X1 X2 X3 X4 X5 X6 X7 X8 X9 X10 X11 X12 X13 X14(X6) X15(X7)
F25 Up Dec1 Dn Dec1 Up Dec2 Dn Dec2 Up Lmt. Dn Lmt. Up Lvl. Dn Lvl.
Inspect1 Inspect2 UP Down KMY Rly KMB Rly BS1 BS2
(2LS)(SSU) (1LS)(SSD) (4LS) (3LS) (UL) (DL) (2LV) (1LV)
Display * * - - * * * * - - - - * * - -
Binary value 1 1 0 0 1 1 1 1 0 0 0 0 1 1 0 0
X16 X17 X18 X19 X20 X21 X22 X23 X24 X25 X26 X27 X28 X29 X30 X31
F26 DZ SW. Fire Brake Brk SW L Brk SW R Overheat Dr Lock
Pre.open Fireman KMC Rly SW Rly EthQuak ALP UCM Rly Fire1Rly .
(Door Zone) (Fire Return) (BY) (BS1) (BS2) (THB) (KAD)
Display - - - - - - - * * * - - * * - -
Binary value 0 0 0 0 0 0 0 1 1 1 0 0 1 1 0 0
GX1 GX2 GX3 GX4 GX5 GX6 GX7 GX8 GX9 GX10 GX11 GX12 GX13 GX14 GX15
F27
Chg Dir Att Svc VIP Bypass Fireman2 Holdbtn C-Callp AntiCrm

Display - - - - - - - - - - - - - - - -
Binary value 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
HX0 HX1 HX2 HX3 HX4 HX5 HX6 HX7 HX8 HX9 HX10 HX11 HX12 HX13 HX14 HX15

F28 LgtCurF
ClsLmtF OpnLmtF DrBlkF SafEgF
(PSGS ZeroLoad FullLoad OverLoad OpnLmtR ClsLmtR DrBlkR LgtCurR SafEgR
(DCL) (DOL) (DB) (SGS/SES)
/PSES)
Display * * * * * - - * - * - - - - - -
Binary value 1 1 1 1 1 0 0 1 0 1 0 0 0 0 0 0
7
FUJI IRISDEL
PARAMETROS NVAS380
– Parameter
INTEGRATED

 F29 ~ F31, F190


F29 Service floor setting 1(whether stop on floor 1-16) Standard  65535
F30 Service floor setting 2(whether stop on floor 17-32) Standard  65535
F31 Service floor setting 3(whether stop on floor 33-48) Standard  65535
F190 Service floor setting 4(whether stop on floor 49-64) Standard  65535
1 2 4 8 16 32 64 128 256 512 1024 2048 4096 8192 16384 32768

Floor 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

F29 Display * * * * * * * * * * * * * * * *

Binary 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Floor 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

F30 Display * * * * * * * * * * * * * * * *

Binary 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Floor 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48

F31 Display * * * * * * * * * * * * * * * *

Binary 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Floor 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64

F190 Display * * * * * * * * * * * * * * * *

Binary 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
8
FUJI IRISDEL
PARAMETROS NVAS380
– Parameter
INTEGRATED

 F32 ~ F35
F32 Specification of elevator integrated drive controller
F33 Interval between trips in automatic running test Unit: Second
F34 Number of trips in automatic running test # of automatic running
F35 Special firefighter mode Standard  0

Motor Type Load(Kg) Speed(m/min) F32


BOMCO 630 60 0 Example) F33 5
BOMCO 630 90 2
BOMCO 630 105 2 F34 100
BOMCO 800 60 1
BOMCO 800 90 2 • An elevator will run 100 times with 5
BOMCO 800 105 2
seconds interval between door opening
BOMCO 1000 60 1
BOMCO 1000 90 3 timing & closing timing
BOMCO 1000 105 3
YTW2-260GF 1150 60 2
YTW2-260GF 1150 90 3
YTW2-260GF 1150 105 3
YTW2-260GF 1350 60 2
YTW2-260GF 1350 90 3
YTW2-260GF 1350 105 4
YTW2-260GF 1650 60 2
YTW2-260GF 1650 90 4
YTW2-260GF 1650 105 5
9
FUJI IRISDEL
PARAMETROS NVAS380
– Parameter
INTEGRATED

 F36, F40, F41, F43, F44, F48, F49

F36 Brake switch detection mode 1: Brake switch exists, 2: For Hong Kong code

F40 Weight data bias 48%

F41 Load Device Learn function 1: 0% load setting, 2: 100% load setting
F43 Bit function parameter
F44 Monitor Address Car ID for Step EMS
F48 Zero Load Value Around 150~200
F49 Full Load Value Around 300~400

Bit setting (F43)

Bit15 …… Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0


0: Waiting with 0: No button 0: No button
0: No hall IND display
0: Without car 0: No anti-crime 0: No car call door open in flash in buzzing in
in case of any fault
call priority function button buzzing attendant mode attendant attendant
Standby …… 1: Hall IND flash is
1: With car call 1: Anti-crime 1: Car call 1: Waiting with 1: Button 1: Button
available in case of
priority function button buzzing door close in flash in buzzing in
any fault
attendant mode attendant attendant
10
FUJI IRISDEL
PARAMETROS NVAS380
– Parameter
INTEGRATED

Load Device Learn (F41, 48, 49)

• Set “1” at F41 with 0% load in a car and set “2” with 100% load in a car.
• If Learn is successfully made:

 The data (“1” or “2”) at F41 will be changed to “0” again once setting “1” or “2”.

 Data at F48 will be automatically changed to 50 ~ 150 for 0% load setting.

 Data at F49 will be automatically changed to 200 ~ 350 for 100% load setting
11
FUJI IRISDEL
PARAMETROS NVAS380
– Parameter
INTEGRATED

 F50 ~ F55, F191, F192


F50 Front door-opening allowed 1 for floor 1-16
F51 Front door-opening allowed 2 for floor 17-32
F52 Front door-opening allowed 3 for floor 33-48
F191 Front door-opening allowed 4 for floor 49-64
F53 Rear door-opening allowed 1 for floor 1-16 0
F54 Rear door-opening allowed 2 for floor 17-32 0
F55 Rear door-opening allowed 3 for floor 33-48 0
F192 Rear door-opening allowed 4 for floor 49-64 0
1 2 4 8 16 32 64 128 256 512 1024 2048 4096 8192 16384 32768
F50 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
F51 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
F52 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
Front
F191 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64
Display * * * * * * * * * * * * * * * *
Binary 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
F53 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
F54 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
F55 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
Rear
F192 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64
Display - - - - - - - - - - - - - - - -
Binary 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
12
FUJI IRISDEL
PARAMETROS NVAS380
– Parameter
INTEGRATED

 F56 ~ F62
F56 Leveling adjustment up 50 for baseline (Within 15mm)
F57 Leveling adjustment down 50 for baseline (Within 15 mm)
F58 Speed curve delay at start (Default)
F59 Zero-speed band brake delay (Default)
F61 Distance for triggering arrival gong/chime Chime interval fixed as 1200
F62 Time limit for anti-slippage operation For Chinese code (Max. 45 sec)

Interval for F58, F59


KMB

KMZ

KMY

DIR

ENC

RUN
F58 F59
SPEED
13
FUJI IRISDEL
PARAMETROS NVAS380
– Parameter
INTEGRATED

 F56 ~ F62 (Continuous)

Setting for F56, F57

Elevator direction Elevator direction

Car level ‘A’ Car level ‘A’


Landing sill level Landing sill level
Car level ‘B’ Car level ‘B’

F56 Up direction F57 Down direction


Car level ‘A’ Decrease the value Car level ‘A’ Increase the value
Car level ‘B’ Increase the value Car level ‘B’ Decrease the value
14
FUJI IRISDEL
PARAMETROS NVAS380
– Parameter
INTEGRATED

 F65 ~ F112
F65 1st floor name display
F66 2nd floor name display
F67 3rd floor name display
~

F111 47th floor name


F112 48th floor name

Example)

F65 B2 1. Go to F65 (or respective floor) by Para Setup.


F66 -2 2. The default floor name will be displayed.
3. Press ENTER on SVC tool.
F67 G 4. Cursor will be displayed for changing.
F68 M 5. Press ▲ or ▼ to see available character.
F69 1 6. Press ► or ◄ to move the curser to another digit.
F70 2 7. Repeat step #5 and press ENTER to close.
15
FUJI IRISDEL
PARAMETROS NVAS380
– Parameter
INTEGRATED

 F115 ~ F121
F115 Open door overtime Open lock timer (Max. 30S)
F116 Close door overtime Close lock timer (Max. 30S)
F117 Holding time before forced door closing Button jam & keep pressing button
F118 Holding time for the handicapped Open time for handicapped call
F120 Number of registrations for anti-nuisance If 3, from 4th call will be cancelled
F121 Forced door-closing enable For nudging operation: 1

Example)

Overtime (F115, F116)


If door is not closed (or opened) within setting value, close (or open) lock error is arisen.

Holding time (F118)


Door will be closed in setting value after fully opening in case of handicapped call.

Anti-nuisance function (F120)


1. If setting value is 3, car calls will be cancelled from the 4th call.
2. Load detection shall be less than 20%.
16
FUJI IRISDEL
PARAMETROS NVAS380
– Parameter
INTEGRATED

 F123 ~ F130
F123 Landing call classification
F124 Failure time of light curtain Photo disable time (Unit: Second)
F125 Rear door light curtain disable time Photo disable time (Unit: Second)
F127 Force stop floor setting
F128 Separate door control for through type entrance
F129 Micro leveling and/or running open function (Default : 0)
F130 Holding door-opening/closing torque 04

Example)
F123 Meaning F129 Meaning
0 Only front entrance 1 Running open
1 Front & rear 2 Micro leveling
F127 Meaning 3 Both function
0 Not functioned F130 Meaning
1 Force stopped at 1st floor 0 No holding torque
5 Force stopped at 5th floor 1 Holding open
F128 Meaning 2 Holding close
0 Open separately (Front & rear) 3 Both
1 Open together 4 Holding in lift running
17
FUJI IRISDEL
PARAMETROS NVAS380
– Parameter
INTEGRATED

 F131 ~ F133, F161


1~64: Floor setting
F131 65: Arrival chime cancel (Y)
66: 2nd homing floor time (Y)
F132 Start time 0~2359
F133 End time 0~2359
F161 To use for above function 0: Not use, 1: use

Example)
F131
1. 1 ~ 64  Non-stop floor in setting time (F132, F133)
2. 65  Chime cancel in setting time (F132, F133)
3. 66  2nd homing floor in setting time (F132, F133)

F132 & F133


1230 means 12H30M
2359 means 23H59M
18
FUJI IRISDEL
PARAMETROS NVAS380
– Parameter
INTEGRATED

 F137 ~ F139, 199


Service floor setting 1 (whether stop on Fl. 1-16)
F137
by NS-SW
Service floor setting 2 (whether stop on Fl. 17-32)
F138
by NS-SW This floor can be selected
Service floor setting 3 (whether stop on Fl. 33-48) by non stop switch at COP
F139
by NS-SW
Service floor setting 4 (whether stop on Fl. 49-64)
F199
by NS-SW

Example)
1 2 4 8 16 32 64 128 256 512 1024 2048 4096 8192 16384 32768
F137 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

F138 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

F139 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48

F199 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64

Display * * * * * * * * * * * * * * * *

Binary 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
19
FUJI IRISDEL
PARAMETROS NVAS380
– Parameter
INTEGRATED

 F140 ~ F147
F140 Weighing value of full load Set ‘80’ then hall call by-passed from 80% load
F141 KMY release delay Refer to graph
Goes to this floor in case of no calling from
F142 Anti-crime floor
outside
F145 Bus voltage gain Fixed valve: 100
Allowed gap between actually Real detecting floor & system stored floor is diffe
F146
position and learned position rent, lift goes to terminal floor
Selection of the protection 0: Contactor cannot run with contactor error
F147
method for contactor fault 1: Car can run even detection of contactor error
20
FUJI IRISDEL
PARAMETROS NVAS380
– Parameter
INTEGRATED

 F148 ~ F155

F148 Door open time of the base floor Unit: 0.1S (30 means 3 seconds)

F150 Indicator message selection (SM.0412/A, VS/T)

F151 Indicator message selection (SM.0412/B)

SM.04 12/A SM.04 12/B

0 Upper  Full, Lower  Out of SVC 0 Left  Full, Right  Out of SVC

1 Upper  Fire, Lower  Out of SVC 1 Left  Fire, Right  Out of SVC

2 Upper  Full, Lower  Fire 2 Left  Full, Right  Fire

3 Upper  Full, Left  VIP, Right  Out of SVC 3 Left(U)  Out of SVC, Left(D)  Full, Right  VIP

4 Upper  Fire, Left  VIP, Right  Out of SVC 4 Left(U)  Out of SVC, Left(D)  Fire, Right  VIP
21
FUJI IRISDEL
PARAMETROS NVAS380
– Parameter
INTEGRATED

 F148 ~ F155

Delay for car-lighting before automatically


F152 Ajuste de fabrica- 180 seg (VOLVER)
switching off car-lighting and fan

F153 Hall door lock check enable 0: No checking, 1: Checking

F154 Voice announcement setting 0 ~ 65535

F155 Voice announcement setting 0 ~ 65535


22
FUJI IRISDEL
PARAMETROS NVAS380
– Parameter
INTEGRATED

 F160 ~ F172
Bit 0: Double click car call, Bit 1:
F160 Cancelling car call Double for hall call, 2: Single click for
car call, 3: Single for hall call

F163 Lift running by generator power 0  Return, 1  Continue

7: JP9.2 (Signal received)  PTM1 EA


F164 Load type setting 8: JP9.3 (Signal received)
9: Both (Signal received)  PTM 2 EA

0: Door open in inspection


F165 Door open mode
1: Door close in inspection

F168 Elevator numbering for IC card service IC Card Key 0  Unused, 1 Use

F169 Setting landings for up/down calls by IC card 0: Up call, 1: Down call

With IC control in car, 1-16 Fl. for selection of


F170
identification by IC card
With IC control in car, 17-32 Fl. for selection of
F171
identification by IC card
With IC control in car, 33-48 Fl. for selection of
F172
identification by IC card
23
FUJI IRISDEL
PARAMETROS NVAS380
– Parameter
INTEGRATED

 F175 ~ F186

F175 Creeping speed at start Don’t change

F180 Velocity increment Default : 100

F181 Elevator numbering in duplex control 0: Main elevator, 1: Sub elevator

F182 Steps of speed reduction switches No. of slow down switch (Default : 1)

F183 Speed for shaft teach mode Default : 0.8 (45 m/min) (Volver)

F186 Creeping time at start Don’t change


24
FUJI IRISDEL
PARAMETROS NVAS380
– Parameter
INTEGRATED

 F187

F187 SVC Tool display function

0: Running times 1: Eevaluation of encoder interference

2: Evaluation of CAN1 interference 3: Evaluation of CAN2 interference

4: Speed of motor 5: Voltage of DC bus

6: Output current (A) 7: Output torque

8: Position of pole 9: Encoder position 1

10: Encoder position 2 11: Pre-torque

12: Radiator temperature 1 13: Radiator temperature 2

14: Load-weight value 15: Weighing value JP9.2 of SM.02/I

16: Weighing value JP9.3 of SM.02/I


25
FUJI IRISDEL
PARAMETROS NVAS380
– Parameter
INTEGRATED

 F196 ~ F203

F196 2nd homing or dispersion floor in Duplex

F200 DSP software revision number Don’t change

F202 Auto turn for SINCOS Encoder Don’t change

F203 No-load current, for the asynchronous motor Don’t change

Example)
F196 (Dispersion floor)

Dispersion floor

Homing floor
26
FUJI IRISDEL
PARAMETROS NVAS380
– Parameter
INTEGRATED

 F204 ~ F215

F204 Zero speed proportion ASR P0 F210 Medium speed proportion ASR P3
F205 Zero speed integral ASR I0 F211 Medium speed Integral ASR I3
F206 Low speed proportion ASR P1 F212 High speed proportion ASR P4
F207 Lower speed integral ASR I1 F213 High speed Integral ASR I4
F208 Low speed proportion ASR P2 F214 Low speed switchover frequency 1
F209 Low speed Integral ASR I2 F215 High speed switchover frequency 2
27
FUJI IRISDEL
PARAMETROS NVAS380
– Parameter
INTEGRATED

 F218 ~ F222 Motor Type Load(Kg) Speed(m/min) F219 F221 F222


BOMCO 630 60 20 96 10.4
F218 Motor Type
BOMCO 630 90 20 144 17.8
F219 Motor Poles
BOMCO 630 105 20 168 17.8
F220 Rated motor voltage BOMCO 800 60 20 96 12.7
F221 Rated motor rotate speed BOMCO 800 90 20 144 21.7
BOMCO 800 105 20 168 21.7
F222 Rated motor current
BOMCO 1000 60 20 96 14.9
BOMCO 1000 90 20 144 26
BOMCO 1000 105 20 168 26
YTW2-260GF 1150 60 16 91 17.9
YTW2-260GF 1150 90 16 136.5 26.9
YTW2-260GF 1150 105 16 159.2 31.4
YTW2-260GF 1350 60 16 91 21.1
YTW2-260GF 1350 90 16 136.5 31.6
YTW2-260GF 1350 105 16 159.2 36.8
YTW2-260GF 1650 60 16 91 25
YTW2-260GF 1650 90 16 136.5 37.4
YTW2-260GF 1650 105 16 159.2 43.7
28
FUJI IRISDEL
PARAMETROS NVAS380
– Parameter
INTEGRATED

 F223 ~ F231

F223 Max. output torque It should be more than 200 unless vibration

F224 Motor slip frequency Default: 1.4

F225 Carrier frequency Default: 8

F226 Encoder type Default: 4

F227 Encoder pulses Default: 8192

F228 Magnetic pole phase Not used

F229 Regulator mode Default: 1, Speed 2m/s & above: 0

0: No PTM
F230 Pre-load type
2: PTM use

F231 Max. elevator speed Automatic record


29
FUJI IRISDEL
PARAMETROS NVAS380
– Parameter
INTEGRATED

 F231 ~ F249
0/1
F233 Encoder Direction

Motor phase
F234 0/1

F241 Weighing mode, overload up gain Full load UP (50)

F242 Weighing mode, overload down gain Full load DOWN (50)

F245 Weighing mode, light load up gain Empty load UP (80)


EMpty load DOWN ( ~ 5.5kw : 250 ~ 300
 7.5 ~ 15kw : 150 ~ 160
F246 Current gain 2
 18.5kw : 100
 Increase data by 5)
F247 Balance value Half load data (512)

F248 load analogue gain Default: 80, Adjsutable for motor vibration

F249 Power code Same as F32


30
FUJI IRISDEL
PARAMETROS NVAS380
– Parameter
INTEGRATED

 F231 ~ F249
Confirmation of voltage for charging
F253 65
relay failure

F234 0/1

F241 Full load UP (50)

F242 Full load DOWN (50)

F245 Weighing mode, light load up gain Empty load UP (80)


EMpty load DOWN ( ~ 5.5kw : 250 ~ 300
 7.5 ~ 15kw : 150 ~ 160
F246 Current gain 2
 18.5kw : 100
 Increase data by 5)
F247 Balance value Half load data (512)

F248 load analogue gain Default: 80, Adjsutable for motor vibration

F249 Power code Same as F32