Relays
Relays
In an over current relay or o/c relay the actuating quantity is only current. There is only one current
operated element in the relay, no voltage coil etc. are required to construct this protective relay.
In an over current relay or o/c relay the actuating quantity is only current.
There is only one current operated element in the relay, no voltage coil etc. are
required to construct this protective relay.
In an over current relay, there would be essentially a current coil. When normal
current flows through this coil, the magnetic effect generated by the coil is not
sufficient to move the moving element of the relay, as in this condition the
restraining force is greater than deflecting force. But when the current through
the coil increased, the magnetic effect increases, and after certain level of
current, the deflecting force generated by the magnetic effect of the coil, crosses
the restraining force, as a result, the moving element starts moving to change
the contact position in the relay.
Although there are different types of over current relays but basic working
principle of over current relay is more or less same for all.
Depending upon time of operation, there are various types of OC relays, such
as,
Inverse time over current relay or simply inverse OC relay is again subdivided
as inverse definite minimum time (IDMT), very inverse time, extremely inverse
time over current relay or OC relay.
The preset value of current in the relay coil is referred as pick up setting
current. This relay is referred as instantaneous over current relay, as ideally,
the relay operates as soon as the current in the coil gets higher than pick up
setting current. There is no intentional time delay applied. But there is always
an inherent time delay which can not be avoided practically. In practice the
operating time of an instantaneous relay is of the order of a few milliseconds.
Fig.
1. When fault current can flow in both the directions through the relay,
at its location. Therefore, it is necessary to make the relay respond for a
particular defined direction, so that proper discrimination is possible. This can
be achieved by introduction of directional control elements.
1. It is the reference against which the phase angle of the other quantity
is compared. Consequently the phase angle of the polarizing quantity must
remain fixed when other quantity suffers wide change in phase angle.
• Prev Page
•
Distance relay
Principle of operation of distance relay: The basic principle of measurement involves the comparison of
fault current seen by the relay with the voltage at relaying point; by comparing these two quantities.
Distance relay
Distance relay is used for the protection of transmission line & feeders In a
distance relay, instead of comparing the local line current with the current at
far end of line, the relay compares the local current with the local voltage in the
corresponding phase or suitable components of them
• Impedance Relay
• Mho Relay
• Reactance Relay
Impedance Relay
The torque equation T, for such a relay the current actuates the operating torque and the voltage
actuates the restraining torque, with the usual spring constant K4.
Impedance Relay:
The torque equation T, for such a relay the current actuates the operating
torque and the voltage actuates the restraining torque, with the usual spring
constant K4.
1. It is not directional.
Differential Relay
Differential Relay
During normal condition and external fault the protection system is balanced
and the CT's ratios are such that secondary currents are equal. These current
circulate in pilot wires. The vector differential current I1- I2 which flow through
the relay coil is zero. I1-I2 = 0 (normal condition or external faults) This balance
is disturbed for internal faults. When fault occurs in the protected zone, the
current entering the protected winding is no more equal to the leaving the
winding because some current flows to the fault. The differential I1-I2 flows
through the relay operating coil and the relay operates if the operating torque
is more than the restraining torque. The current I1 and I2 circulate in the
secondary circuit. Hence CT's does not get damaged. Polarities of CT's should
be proper, otherwise the currents I1 and I2 would add up even for normal
condition and mal operate the relay.
The CTs at both ends of the protected circuit connected so that for through load
or through fault conditions current circulates between the interconnected CTs.
The over-current relay is normally connected across equipotential points and
therefore doesn‟t operate.
• Circulating current balance methods are widely used for apparatus protection
where CTs are within the same substation area and interconnecting leads
between CTs are short (e.g. generator stator windings, Transformer, Bus bars
etc.)
To alter the voltage and current ratios between high voltage and low voltage
sides of a power transformer, a tap changing equipment is used. This is an
important feature of a power transformer. This equipment effectively alters the
turns ratio. This causes unbalance on both sides. To compensate for this effect,
the tapping can be provided on C.T.s also which are to be varied similar to the
main power transformer. But this method is not practicable. The percentage
differential relays ensure relays ensure the stability with respect to the amount
of unbalance occurring at the extremities of the tap change range.
Due to the difference in lengths of the pilot wires on both sides, the unbalance
condition may result. The difficulty is overcome by connecting the adjustable
resistors in pilot wires on both sides. These are called balancing resistors. With
the help of these resistors, equipotential points on the pilot wires can be
adjusted. In percentage differential relays the taps are provided on the
operating coil and restraining coil to achieve an accurate balance.
The factors which affect the magnitude and direction of the magnetizing inrush
current can be one of the following reasons.
If the transformer is energized when the voltage wave is passing through zero,
the magnetizing current inrush is maximum. At this instant, the current and flux
should be maximum in highly inductive circuit. And in a half wave flux reversal
must take place to attain maximum value in the other half cycles. If the residual
flux exists, the required flux may be in same or opposite direction. Due to this
magnetizing current inrush is less or more. If it is more, it is responsible to
saturate the core which further increases its component. This current decays
rapidly for first few cycles and then decays slowly. The time constant L/R of the
circuit is variable as inductance of circuit varies due to the change in
permeability of the core. The losses in the circuit damp the inrush currents.
Depending on the size of the transformer, the time constant of inrush current
varies from 0.2 sec to 1 sec. The waveforms of magnetizing inrush current in
three phases are shown in the figure below.
Static relays
Due to the amplification of energizing signals obtainable, the sources need only provide low power.
Therefore the size of the associated current and voltage transformers could be reduced.
Static relays
• Timers
• Phase comparators
• Amplitude Comparator
• Level detectors
• Integrators
• Polarity detectors
High reliability operational amplifiers are used for realizing the basic
components of static relays.
It is customary to have two elements of over current and one element of earth
fault protection system in the most elementary form of protection of three
phase feeders. Different types of feeders employ the over current protection
along with the directional relay so that proper discrimination of an internal
fault is possible. Some examples are illustrated below.
It may be seen from the below given parallel feeders that the relays placed at
the load side of both the lines use directional element which respond to a
direction away from the bus bars. Similarly, the relays placed at the source side
do not require any directional element.
A similar concept of discrimination is also utilized in the below given ring main
feeder and a feeder fed from both the sides. It can be observed that relays
placed near the bus connecting the sources, don not have any directional
feature, where as the rest of the buses, respond to a direction always away from
the source. It is good practice to locate a fault any where among different
sections of the feeders and check whether that particular section only is
isolated without disrupting the power flow in other sections.
Pilot wire schemes for feeder protection
In differential protection scheme, the current entering at one end of the line and
leaving from other end of the line is compared. The pilot wires are used to
connect the relays. Under normal working condition, the two currents at both
ends are equal and pilot wires do not carry any current, keeping relays
inoperative. Under an internal fault condition, the two currents at both the ends
are no longer same, this causes circulating current flow through pilot wires and
makes the relay to trip. The various schemes used with this method of
protection are, 1. Merz-Price Voltage Balance System 2. Translay Scheme
The figure below shows Merz-Price voltage balance system used for the three
phase feeders.
Under normal condition, current entering the line at one end is equal to current
leaving from the other end. Therefore, equal and opposite voltages are induced
in the secondaries of C.T.s. at the two ends resulting in no current flow, through
the relay. Under fault condition, two currents at the two ends are different. Thus
the secondary voltages of both the end C.T.s differ from each other. This
circulates a circulating current through the pilot wires and the relays. Thus the
relays trip the circuit breakers to isolate the faulty section.
3. Economically not suitable as the cost is high due to long pilot wires.
4. Due to long pilot wires, capacitive effects adversely bias the operation of the
relays.
5. The large voltage drop in the pilot wires requiring better insulation.
Translay Scheme
The advantages of this scheme are, 1. Only two pilot wires are required.
2. The cost is very low.
4. The capacitive effects of pilot wire currents do not affect the operation of the
relays.
The Wave traps ( also known as Line Trap) are inserted between the busbar
and the connection of the CU. These traps are L and C elements connected in
parallel, and they are tuned in such a manner that they offer low reactance to
the power frequency signals and high reactance to the carrier waves. They
ensure that neither of these different frequency signals get mixed up before
being received at the bus bar. Both the CU and the Wave traps are protected
from switching and lightening surges, with the help suitably designed Spark
Gaps or Varistors. Frequency spacing Different frequencies are used in adjacent
lines and the wave traps ensure that carrier signals of other lines do not enter
a particular line section. Therefore, proper choice of frequency bands for
different lines are adopted.
Transmitter Unit
The Receiver unit consists of an attenuator and a Band pass filter, which
restricts the acceptance of any unwanted signals. The unit also has matching
transformer to match the line impedance and that of the receiver unit.
• Prev Page
•
Transformer Protection
The power transformer is one of the most important links in a power transmission and distribution
system.
TRANSFORMER PROTECTION
INTRODUCTION
• adequate design
• careful erection
• proper maintenance
1. Surge diverters
3. Electrical relays.
• Only the simplest protection such as fuses can be justified for transformers
of lower ratings.
• THROUGH FAULTS
a) Overload conditions.
The transformer must be disconnected when such faults occur only after allowing
a predetermined time during which other protective gears should have operated.
• INTERNAL FAULTS
5. So called „incipient‟ faults which are initially minor faults, causing gradually
developing fault. These types of faults are not easily detectable at the winding
terminals by unbalance current or voltage.
Following distinct cases are examined below (1) Star connected winding with
neutral point earthed through an impedance
Basic discussions related to the Merz-Price Scheme and its limitations which are
taken care by the biased differential scheme, are omitted for repetition
Basic considerations
a. Transformation ratio
• The nominal currents in the primary and secondary sides of the transformer
vary in inverse ratio to the corresponding voltages. This should be compensated for
by using different transformation ratios for the CTs on the primary and secondary
sides of the transformer.
b. Current Transformer Connections
• If the transformer has the benefit of a tap changer, it is possible to vary its
transformation ratio for voltage control.
• • The differential protection system should be able to cope with this
variation.
• • This is because if the CTs are chosen to balance for the mean ratio of the
power transformer, a variation in ratio from the mean will create an unbalance
proportional to the ratio change. At maximum through fault current, the spill
output produced by the small percentage unbalance may be substantial
• • Differential protection should be provided with a proportional bias of an
amount which exceeds in effect the maximum ratio deviation. This stabilizes the
protection under through fault conditions while still permitting the system to have
good basic sensitivity.
d. Magnetization Inrush
• The magnetizing inrush produces a current flow into the primary winding
that does not have any equivalent in the secondary winding. The net effect is thus
similar to the situation when there is an internal fault on the transformer.
• Since the differential relay sees the magnetizing current as an internal fault,
it is necessary to have some method of distinguishing between the magnetizing
current and the fault current using one or all of the following methods.
• Using a differential relay with a suitable sensitivity to cope with the
magnetizing current, usually obtained by a unit that introduces a time delay to
cover the period of the initial inrush peak.
• • Using a harmonic-restraint unit, or a supervisory unit, in conjunction with
a differential unit.
• • Inhibiting the differential relay during the energizing the transformer.
Compared to the differential protection used in generators, there are certain
important points discussed below which must be taken care of while using such
protection for the power transformers.
1. In a power transformer, the voltage rating of the two windings is different. The
high voltage winding is low current winding while low voltage winding is high
current winding. Thus there always exists difference in current on the primary and
secondary sides of the power transformer. Hence if C.T.s of same ratio are used on
two sides, then relay may get operated through there is no fault existing.
To compensate for this difficulty, the current ratios of C.T.s on each side are
different. These ratios depend on the line currents of the power transformer and
the connection of C.T.s. Due to the different turns ratio, the currents fed into the
pilot wires from each end are same under normal conditions so that the relay
remains inoperative. For example if K is the turns ratio of a power transformer then
the ratio of C.T.s on low voltage side is made K times greater than that of C.T.s on
high voltage side.
In case of power transformers, there is an inherent phase difference between the
voltages induced in high voltage winding and low voltage winding. Due to this,
there exists a phase difference between the line currents on primary and secondary
sides of a power transformer. This introduces the phase difference between the
C.T. secondary currents, on the two sides of a power transformer. Through the
turns ratio of C.T.s are selected to compensate for turns ratio of transformer, a
differential current may result due to the phase difference between the currents
on two sides. Such a different current may operate the relay though there is no
fault. Hence it is necessary to correct the phase difference. To compensate for this,
the C.T. connections should be such that the resultant currents fed into the pilot
wires from either sides are displaced in phase by an angle equal to the phase shift
between the primary and secondary currents. To achieve this, secondaries of C.T.s
on star connected side of a power transformer are connected in delta while the
secondaries of C.T.s on delta connected side of a power transformer are connected
in star.
Buchholz relay
All faults below the oil in transformer result in the localized heating & breakdown
of the oil, some degree of arcing will always take place in a winding fault & the
resulting decomposition of it will release gases such as hydrogen, carbon monoxide
& hydrocarbons.
• When the fault is of a very minor type, such as hot joints gas is released slowly,
but a major fault involving severe arcing causes rapid release of large volumes of
gas as well as oil vapour.
Operation
There are many types of internal faults such as insulation fault, core heating, bad
switch contacts, faulty joints etc. which can occur. When the fault occurs the
decomposition of oil in the main tank starts due to which the gases are generated.
As mentioned earlier, major component of such gases is hydrogen. The hydrogen
tries to rise up towards conservator but in its path it gets accumulated in the upper
part of the Buchholz relay. Through passage of the gas is prevented by the flap
valve.
When gas gets accumulated in the upper part of housing, the oil level inside the
housing falls. Due to which the hollow float tilts and closes the contacts of the
mercury switch attached to it. This completes the alarm circuit to sound an alarm.
Due to this operator knows that there is some incipient fault in the transformer.
The transformer is disconnected and the gas sample is tested. The testing results
give the indication, what type of fault is started developing in the transformer.
Hence transformer can be disconnected before grows into a serious one. The alarm
circuit does not immediately disconnect the transformer but gives only an
indication to the operator. This is because sometimes bubbles in the oil circulating
system may operate the alarm circuit even though actually there is no fault.
However if a serious fault such as internal short circuit between phases, earth fault
inside the tank etc. occurs then the considerable amount of gas gets generated. In
that case, due to a fast reduction in the level of oil, the pressure in the tank
increases. Due to this the oil rushes towards the conservator. While doing so it
passes through the relay where flap valve is present. The flap valve gets deflected
due to the rushing oil and operates the mercury switch, thereby energizing the trip
circuit which opens the circuit breaker of transformer is totally disconnected from
the supply. The connecting pipe between the tank and the conservator should be
as straight as possible and should slope upwards conservator at a small angle from
the horizontal. This angle should be around 100. For the economic considerations,
Buchholz relays are not provided for the transformer having rating below 500 KVA.
Advantages
1. Normally a protective relay does not indicate the appearance of the fault.
It operates when fault occurs. But Buchholz relay gives an indication of the fault at
very early stage, by anticipating the fault and operating the alarm circuit. Thus the
transformer can be taken out of service before any type of serious damage occurs.
Limitations
1. Can be used only for oil immersed transformers having conservator tanks.
3. Setting of the mercury switches cannot be kept too sensitive otherwise the relay
can operate due to bubbles, vibration, earthquakes mechanical shocks etc.
4. The relay is slow to operate having minimum operating time of 0.1 seconds and
average time of 0.2 seconds.
Applications
The following types of transformer faults can be protected by the Buchholz relay
and are indicated by alarm:
1. Local overheating
9. Bushing puncture
10. Winding earth fault.
Generator protection
The range of size of generators extends from a few hundred KVA to more than 500MVA
Generator protection
INTRODUCTION
• The range of size of generators extends from a few hundred KVA to more
than 500MVA
This is most commonly used protection scheme for the alternator stator
windings. The scheme is also called biased differential protection and
percentage differential protection. The figure below shows a schematic
arrangement of Merz-Price protection scheme for a star connected alternator.
The differential relay gives protection against short circuit fault in the stator
winding of a generator. When the neutral point of the windings is available
then, the C.T.s may be connected in star on both the phase outgoing side and
the neutral earth side, as shown in the above figure. But, if the neutral point is
not available, then the phase side CTs are connected in a residual connection,
so that it can be made suitable for comparing the current with the generator
ground point CT secondary current. The restraining coils are energized from
the secondary connection of C.T.s in each phase, through pilot wires. The
operating coils are energized by the tappings from restraining coils and the C.T.
neutral earthing connection.
The similar arrangement is used for the delta connected alternator stator
winding, as shown below.
This scheme provides very fast protection to the stator winding against phase
to phase faults and phase to ground faults. If the neutral is not grounded or
grounded through resistance then additional sensitive earth fault relay should
be provided. The advantages of this scheme are, 1. Very high speed operation
with operating time of about 15 msec. 2. It allows low fault setting which
ensures maximum protection of machine windings. 3. It ensures complete
stability under most severe through and external faults. 4. It does not require
current transformers with air gaps or special balancing features.
Earth fault protection of Generators
In a high voltage transmission system, the bus bars are at very high voltages
than the generators. The generators are directly connected to step up
transformer to which it is connected, together from a generator transformer
unit. The protection of such a unit is achieved by differential protection scheme
using circulating current principle. While providing protection to such a unit, it
is necessary to consider the phase shift and current transformation in the step
up transformer. The figure in the following page, shows a biased differential
protection scheme used for generator transformer unit. The zone of such a
scheme includes the stator windings, the step up transformer and the
intervening connections. The transformer is delta-star hence the current
transformers on high voltage side are delta connected while those on generator
side are star connected. This cancels the displacement between line currents
introduced by the delta connected primary of the transformer. Where there is
no fault, the secondary currents of the current transformer connected on
generator side are equal to the currents in the pilot wires from the secondaries
of the delta connected current transformers on the secondary of main
transformer. When a fault occurs, the pilot wires carry the differential current
to operate the percentage differential relay.
For the protection against the earth faults, an earth fault relays is put in the
secondary winding of the main step up transformers as shown. In such a case,
differential protection acts as
a backup protection to the restricted earth fault protection. This overall
differential protection scheme does not include unit transformer as a separate
differential scheme is provided it.
PHASE FAULT
• Phase-phase faults clear of earth are less common. They may occur on
the end portion of stator coils or in the slots if the winding involves two coil
sides in the same slot. In the later case the fault will involve earth in a very short
time.
The protection scheme for a power system should cover the whole system
against all probable types of faults. Unrestricted forms of line protection such
as over current and distance systems, meet this requirement, although faults in
the Bus bar zone are cleared only after some time delay. If unit protection is
applied to feeder and plant the bus bars are not inherently protected. Bus bars
have been left without specific protection. Different bus bar faults are as
follows. BUSBAR FAULTS
• Majority of bus faults involve one phase and earth, but faults arise from
many causes and a significant number are inter-phase clear of earth.
• With fully phase-segregated metal clad gear, only earth faults are
possible ,and a protective scheme need have earth fault sensitivity only.
• Differential protection
SYSTEM PROTECTION
Frame-earth Protection
• When a fault occurs within the boundary of a particular zone, then the
protection system responsible for the protection of the zone acts to isolate (by
tripping the Circuit Breakers) every equipment within that zone from the rest
of the system.
• The circuit Breakers are inserted between the component of the zone and
the rest of the power system. Thus, the location of the circuit breaker helps to
define the boundaries of the zones of protection.
• Different neighbouring zones of protection are made to overlap each
other, which ensure that no part of the power system remains without
protection. However, occurrence of the fault with in the overlapped region will
initiate a tripping sequence of different circuit breakers so that the minimum
necessary to disconnect the faulty element
Primary Protection
The primary protection scheme ensures fast and selective clearing of any fault
within the boundaries of the circuit element, that the zone is required to
protect. Primary Protection as a rule is provided for each section of an electrical
installation.
However, the primary protection may fail. The primary cause of failure of the
Primary Protection system are enumerated below.
1. Current or voltage supply to the relay.
3. Protective relays
4. Tripping circuit
5. Circuit Breaker
Back-up Protection
Back-up protection is the name given to a protection which backs the primary
protection whenever the later fails in operation. The back-up protection by
definition is slower than the primary protection system. The design of the back-
up protection needs to be coordinated with the design of the primary
protection and essentially it is the second line of defence after the primary
protection system.
Thus the current transformer steps up (increases) the voltage while stepping
down (lowering) the current. Now, the secondary current is measured with the
help of an AC ammeter. The turns ratio of a transformer is NP / NS = IS / IP
• UPS systems
• Transfer switches
• Motor-generator sets
• Commercial sub-metering,
Potential transformers are also known as voltage transformers and they are
basically step down transformers with extremely accurate turns ratio. Potential
transformers step down the voltage of high magnitude to a lower voltage which
can be measured with standard measuring instrument. These transformers
have large number of primary turns and smaller number of secondary turns. A
potential transformer is typically expressed in primary to secondary voltage
ratio. For example, a 600:120 PT would mean the voltage across secondary is
120 volts when primary voltage is 600 volts.
• Prev Page
•
Whenever, the contacts of circuit breaker open while carrying load there is an
arc in the medium between the separating contacts of the circuit breaker. As
long as this arc is sustained in between the contacts, the current through the
circuit breaker will not be interrupted totally. For total interruption of current,
the arc needs to be quenched as quickly as possible. The main designing criteria
of a circuit breaker is to provide appropriate technology of arc quenching in
circuit breaker to fulfill quick and safe current interruption. So before going
through different arc quenching techniques employed in circuit breaker, it is
first necessary to understand the phenomena of arc in circuit breaker.
At high temperature the charged particles in a gas move rapidly and randomly,
but in absence of electric field, no net motion occurs. Whenever an electric field
is applied in the gas, the charged particles gain drift velocity superimposed on
their random thermal motion. The drift velocity is proportional to the voltage
gradient of the field and particle mobility. The particle mobility depends upon
the mass of the particle, heavier particles, lower the mobility. The mobility also
depends upon mean free paths available in the gas for random movement of the
particles. Since every time a particle collides, it loses its directed velocity and
has to be re-accelerated in the direction of electric field again. Hence net
mobility of the particles is reduced. If the medium has high pressure, it becomes
denser and hence, the gas molecules come closer to each other, therefore
collision occurs more frequently which lowers the mobility particles. The total
current by charged particles is directly proportional to their mobility.
Therefore the mobility of charged particles depends upon the temperature,
pressure of the gas and as well as nature of the gas. Again the mobility of gas
particles determines the degree ionization of gas.
So from above explanation we can say that ionization process of gas depends
upon nature of gas (heavier or lighter gas particles), pressure of gas and
temperature of gas. As we said earlier the intensity of arc column depend up on
the presence of ionized media between separated electrical contacts, hence,
special attention should be given in reducing ionization or increasing
deionization of media between contacts. That is why the main designing feature
of circuit breaker is to provide different pressure control methods, cooling
methods for different arc media in between circuit breaker contacts.
Heat loss from an arc in circuit breaker takes place through conduction,
convection as well as radiation. In circuit breaker with plain break arc in oil, arc
in chutes or narrow slots nearly all the heat loss due to conduction. In air blast
circuit breaker or in breaker where a gas flow is present between the electrical
contacts, the heat loss of arc plasma occurs due to convection process. At
normal pressure the radiation is not a significant factor but at higher pressure
the radiation may become a very important factor of heat dissipation from arc
plasma. During opening of electrical contacts, the arc in circuit breaker is
produced and it is extinguished at every zero crossing, getting established again
during the next cycle. The final arc extinction or arc quenching in circuit
breaker can be achieved by rapid increase of the dielectric strength in the
medium between the contacts so that the arc gets quenched after the first zero
crossing. This rapid increase of dielectric strength in between circuit breaker
contacts is achieved either by deionization of gas in the arc media or by
replacing ionized gas by cool and fresh gas. There are various deionization
processes applied for arc extinction in circuit breaker, let us discussed in brief.
DEIONIZATION OF GAS DUE TO INCREASING PRESSURE
If pressure of the arc path increases, the density of the ionized gas is increased
which means, the particles in the gas come closer to each other and as a result
the mean free path of the particles is reduced. This increases the collision rate
and as we discussed earlier at every collision the charged particles loss their
directed velocity along electric field and again they are re-accelerated towards
field. It can be said that over all mobility of the charged particles is reduced so
the voltage required to maintain the arc is increased. Another effect of the
increased density of particles is a higher rate of deionization of gas due to the
recombination of oppositely charged particles.
The rate of ionization of gas depends upon the intensity of impact during
collision of gas particles. The intensity of impact during collision of particles
again depends upon velocity of random motions of the particles. This random
motion of a particle and its velocity increases with increase of temperature of
the gas. Hence it can be concluded like that if temperature of a gas is increased;
its ionization process is increased and opposite statement is also true that is if
the temperature is decreased the rate of ionization of gas is decreased means
deionization of gas is increased. Therefore more voltage required to maintain
arc plasma with a decreased temperature. Finally it can be said that the cooling
effectively increases the resistance of the arc.
The insulating material ( may be fluid or air) used in circuit breaker should
serve two important functions as follows:
2. It should extinguish the arc occurring between the contacts when circuit
breaker opens.
Limitations of high resistance method: Arc discharge has a resistive nature due
to this most of the energy is received by circuit breaker itself hence proper care
should be taken during the manufacturing of circuit breaker like mechanical
strength etc. Therefore this method is applied in dc power circuit breaker, low
and medium ac power circuit breaker.
Low resistance method is applicable only for ac circuit and it is possible there
because of presence of natural zero of current. The arc gets extinguished at the
natural zero of the ac wave and is prevented from restricting again by rapid
building of dielectric strength of the contact space.
There are two theories which explains the phenomenon of arc extinction:
Restriking voltage: It may be defined as the voltage that appears across the
breaking contact at the instant of arc extinction.
Recovery voltage :
It may be defined as the voltage that appears across the breaker contact after
the complete removal of transient oscillations and final extinction of arc has
resulted in all the poles.
Arc voltage :
It may be defined as the voltage that appears across the contact during the
arcing period, when the current flow is maintained in the form of an arc. It
assumes low value except for the point at which the voltage rise rapidly to a
peak value and current reaches to zero.
• Prev Page
•
DC circuit breakers and AC breaker main difference is the ability to arc. Because
the exchange of each cycle, have had zero, zero easy to extinction in the past,
but has not been zero DC switching, arc extinguishing ability is poor, so to add
additional interrupter device. DC arc is generally difficult, but the exchange has
zero, breaking easily. Exchange can be derived for the DC circuit breaker
protection, attention to three changes: 1, overload and short circuit protection.
same.
• If the circuit breaker contacts are opened at time when the current passed
through zero and dielectric strength of the medium is build up rapidly so that
arc cannot strike again then arc can be extinguished successfully.
It is the transient voltage that appears across the contacts at or near current
zero during arcing period.If dielectric strength rise is greater than the rise of
restriking voltage then the arc will not restrike.
RestrikingVoltage :
it is the transient voltage that exists during the arcing time. ( natural frequency
kHz ).
Recovery Voltage :
it is the rms voltage after final arc extinction. ( normal frequency 50 or 60 Hz).
both voltages appear between circuit breaker poles.
• A circuit breaker is a piece of equipment which can Make or break a
circuit either manually or by remote control under normal conditions.
• Under normal operating condition these contacts remain closed and will
not open automatically unless the system becomes faulty .These contacts can
be opened manually or by remote control.
• When a fault occurs in a circuit the trip coils of the circuit breaker get
energized and the moving contacts are pulled apart by some mechanism ,thus
opening the circuit.
• Prev Page
•
It is R.R.R.V, which decides whether the arc will re-strike. If R.R.R.V is greater
than the rate of rise of dielectric strength between the contacts, the arc will re-
strike. The arc will fail to re-strike if R.R.R.V is less than the rate of increase of
dielectric strength between the contacts of the breaker.
• Recovery voltage
Resistance switching
This is known as resistance switching. The resistance is in parallel with the arc.
A part of the arc current flows through this resistance resulting in a decrease in
the arc current and increase in the deionization of the arc path and resistance
of the arc.
This process continues and the current through the shunt resistance increases
and arc current decreases. Due to the decrease in the arc current, restriking
voltage and RRRV are reduced. The resistance may be automatically switched
in with the help of a sphere gap as shown in Fig. The resistance switching is of
great help in switching out capacitive current or low inductive current.
The analysis of resistance switching can be made to find out the critical value
of the shunt resistance to obtain complete damping of transient oscillations.
Figure 5.8 shows the equivalent electrical circuit for such an analysis.
Unipolar switching
Unipolar systems usually have a dielectric that is a simple TMO. Examples are
NiO [12], CuO, CoO, Fe2O3 , HfO, TiO2Ta2O5 , Nb2O5 [10,11]. These systems
are good insulators with a large resistivity. They would normally not show any
RS effect. To get the systems into the switching regime it is usually required to
perform and initial ‗electroforming‘ step. In this process, a strong electric field
is applied, which brings the system close to the dielectric break down. A full
break down is prevented by a current limitation or compliance. After this ‗SET‘
procedure, the resistance of the device shows a significant decrease, reaching a
‗low resistance‘ state, RLO , which is stable, i.e., non-volatile. This state has an
ohmic I-V characteristic at low bias. To switch the system to the ‗high
resistance‘ state, RHI ,a voltage has to be applied to the device, with either the
same or opposite polarity than the previously applied ‗forming‘ voltage. In this
‗RESET‘ step, the resistance of the system suddenly increases, back to a ‗high
resistance‘ value close to the original one.
No current compliance should be used in the RESET step. In fact, the resistance
change occurs when the current through the device becomes larger than the
value of the compliance. To SET the system again in the low resistance state, a
voltage with current compliance has to be once again applied, similarly to the
forming step. The system‘s resistance suddenly decreases down to a value close
to RLO at a threshold voltage Vth , which is smaller that the forming one. The
SET and RESET switching process can be repeated may times. The magnitude
of resistance change typically remains within well-defined values, however
some dispersion is often observed. An example of a typical electroforming and
successive RESET and SET steps are shown in Fig
Bipolar switching
Faults are of two type · Short circuit fault- current · Open circuit fault- voltage
• Risk of synchronous motors in large industrial premises falling out of step and
tripping out. The general layout of a protection system may be viewed as given
in the following figure
Impedance Diagram
The impedance diagram on single-phase basis for use under balanced conditions can be easily drawn
from the SLD. The following assumptions are made in obtaining the impedance diagrams.
IMPEDANCE DIAGRAM
Assumptions:
1. The single phase transformer equivalents are shown as ideals with
impedance on appropriate side (LV/HV),
Example system
As per the list of assumptions as above and with reference to the system of
figure 2, the impedance diagram can be obtained as shown in figure
Reactance Diagram
With some more additional and simplifying assumptions, the impedance diagram can be simplified
further to obtain the corresponding reactance diagram. The following are the assumptions made.
REACTANCE DIAGRAM
Additional assumptions:
➢ The resistance is often omitted during the fault analysis. This causes a very
negligible error since, resistances are negligible
Example system
as per the assumptions given above and with reference to the system of figure
2 and Figure, the reactance diagram can be obtained as shown in figure
Definition: Per Unit value of a given quantity is the ratio of the actual value in
any given unit to the base value in the same unit. The percent value is 100
times the pu value. Both the pu and percentage methods are simpler than the
use of actual values. Further, the main advantage in using the pu system of
computations is that the result that comes out of the sum, product, quotient,
etc. of two or more pu values is expressed in per unit itself.
The per unit value of any quantity is defined as the ratio of the actual value of
the any quantity to the base value of the same quantity as a decimal.
iii. The p.u systems are ideal for the computerized analysis and simulation of
complex power system problems.
vi. The circuit laws are valid in p.u systems, and the power and voltages
equations are simplified since the factors of √3 and 3 are eliminated.
In an electrical power system, the parameters of interest include the current,
voltage, complex power (VA), impedance and the phase angle. Of these, the
phase angle is dimensionless and the other four quantities can be described
by knowing any two of them. Thus clearly, an arbitrary choice of any two base
values will evidently fix the other base values.
Normally the nominal voltage of lines and equipment is known along with the
complex power rating in MVA. Hence, in practice, the base values are chosen
for complex power (MVA) and line voltage (KV). The chosen base MVA is the
same for all the parts of the system. However, the base voltage is chosen with
reference to a particular section of the system and the other base voltages
(with reference to the other sections of the systems, these sections caused by
the presence of the transformers) are then related to the chosen one by the
turns-ratio of the connecting transformer.
If Ib is the base current in kilo amperes and Vb, the base voltage in kilo volts,
then the base MVA is, Sb = (VbIb). Then the base values of current & impedance
are given by
= Zohms (MVAb/KVb2)
In 3-phase systems, KVb is the line-to-line value & MVAb is the 3-phase MVA.
[1-phase MVA = (1/3) 3-phase MVA].
• Prev Page
•
Change of Base
It is observed from equation that the pu value of impedance is proportional directly to the base MVA and
inversely to the square of the base KV.
CHANGE OF BASE.
On the other hand, the change of base can also be done by first converting the
given pu impedance to its ohmic value and then calculating its pu value on the
new set of base values.
Merits:
➢ The pu value is the same for both 1-phase and & 3-phase systems
➢ The pu value once expressed on a proper base, will be the same when
refereed to either side of the transformer. Thus the presence of transformer
is totally eliminated
➢ Usually the nameplate ratings will be marked in pu on the base of the name
plate ratings, etc.
Demerits:
➢ If proper bases are not chosen, then the resulting pu values may be highly
absurd (such as 5.8 pu, -18.9 pu, etc.). This may cause confusion to the user.
However, this problem can be avoided by selecting the base MVA near the
high-rated equipment and a convenient base KV in any section of the system.
For a given power system with all its data with regard to the generators,
transformers, transmission lines, loads, etc., it is possible to obtain the
corresponding impedance or reactance diagram as explained above. If the
parametric values are shown in pu on the properly selected base values of the
system, then the diagram is referred as the per unit impedance or reactance
diagram. In forming a pu diagram, the following are the procedural steps
involved:
Frames of Reference:
Of the various network matrices refered above, the bus admittance matrix (YBUS )
and the bus impedance matrix (ZBUS ) are determined for a given power system
by the rule of inspection as explained next.
Rule of Inspection
Consider the 3-node admittance network as shown in figure5. Using the basic
branch relation:
I = (YV), for all the elemental currents and applying Kirchhoff’s Current Law
principle at the nodal points, we get the relations as under:
These are the performance equations of the given network in admittance form
and they can be represented in matrix form as:
In other words, the relation of equation (9) can be represented in the form I BUS =
YBUS EBUS
Where, YBUS is the bus admittance matrix, I BUS & EBUS are the bus current and bus
voltage vectors respectively.
By observing the elements of the bus admittance matrix, YBUS of equation (9), it
is observed that the matrix elements can as well be obtained by a simple
inspection of the given system diagram:
Diagonal elements: A diagonal element (Yii) of the bus admittance matrix, YBUS, is
equal to the sum total of the admittance values of all the elements incident at the
bus/node i,
Off Diagonal elements: An off-diagonal element (Yij) of the bus admittance matrix,
YBUS, is equal to the negative of the admittance value of the connecting element
present between the buses I and j, if any.
This is the principle of the rule of inspection. Thus the algorithmic equations for
the rule of inspection are obtained as:
Yii = yij (j = 1,2,…….n)
Yij = - yij (j = 1,2,…….n)
For i = 1,2,….n, n = no. of buses of the given system, yij is the admittance of
element connected between buses i and j and yii is the admittance of element
connected between bus i and ground (reference bus).
In cases where, the bus impedance matrix is also required, then it cannot be
formed by direct inspection of the given system diagram. However, the bus
admittance matrix determined by the rule of inspection following the steps
explained above, can be inverted to obtain the bus impedance matrix, since the
two matrices are inter-invertible.
Note: It is to be noted that the rule of inspection can be applied only to those
power systems that do not have any mutually coupled elements.
Problem #1: Obtain the bus admittance matrix for the admittance network shown
aside by the rule of inspection
Problem #2: Obtain YBUS and ZBUS matrices for the impedance network shown
aside by the rule of inspection. Also, determine YBUS for the reduced network
after eliminating the eligible unwanted node. Draw the resulting reduced system
diagram.
EXAMPLES ON PER UNIT ANALYSIS:
Problem #1:
Two generators rated 10 MVA, 13.2 KV and 15 MVA, 13.2 KV are connected in
parallel to a bus bar. They feed supply to 2 motors of inputs 8 MVA and 12 MVA
respectively.
The operating voltage of motors is 12.5 KV. Assuming the base quantities as 50
MVA, 13.8 KV, draw the per unit reactance diagram. The percentage reactance
for generators is 15% and that for motors is 20%.
Solution:
The one line diagram with the data is obtained as shown in figure
• Prev Page
•
• The operating voltage of motors is 12.5 KV. Assuming the base quantities as 50
MVA, 13.8 KV, draw the per unit reactance diagram. The percentage reactance
for generators is 15% and that for motors is 20%.
•
• Solution:
• The one line diagram with the data is obtained as shown in figure
•
•
•
•
• Problem #1:
•
• Two generators rated 10 MVA, 13.2 KV and 15 MVA, 13.2 KV are connected
in parallel to a bus bar. They feed supply to 2 motors of inputs 8 MVA and 12
MVA respectively. The operating voltage of motors is 12.5 KV. Assuming the
base quantities as 50 MVA, 13.8 KV, draw the per unit reactance diagram. The
percentage reactance for generators is 15% and that for motors is 20%.
•
• Solution:
•
• The one line diagram with the data is obtained as shown in figure P1(a).
•
• Selection of base quantities: 50 MVA, 13.8 KV (Given)
•
• Calculation of pu values:
• XG1 = j 0.15 (50/10) (13.2/13.8)2 = j 0.6862 pu.
• XG2 = j 0.15 (50/15) (13.2/13.8)2 = j 0.4574 pu.
• Xm1 = j 0.2 (50/8) (12.5/13.8)2 = j 1.0256 pu.
• Xm2 = j 0.2 (50/12) (12.5/13.8)2 = j 0.6837 pu.
•
•
•
• Problem #2:
•
• Draw the per unit reactance diagram for the system shown in figure below.
Choose a base of 11 KV, 100 MVA in the generator circuit.
•
• Solution:
•
• The one line diagram with the data is considered as shown in figure.
•
• Calculation of pu values:
• Calculation of pu values:
• XG = j 0.1 pu, Xm = j 0.2 (100/90) (6.6/6.31)2 = j 0.243 pu.
• Xt1 =Xt2 = j 0.1 (100/50) (11.5/11)2 = j 0.2185 pu.
• Xt3 =Xt4 = j 0.1 (100/50) (6.6/6.31)2 = j 0.219 pu.
• Xlines = j 20 (100/1102) = j 0.1652 pu.
• Eg = 1.0∠00 pu, Em = (6.6/6.31) = 1.045∠00 pu
• Thus the pu reactance diagram can be drawn as shown in figure P2(b).
•
•
• Problem #3:
•
• A 30 MVA, 13.8 KV, 3-phase generator has a sub transient reactance of 15%.
The generator supplies 2 motors through a step-up transformer - transmission
line – step-down transformer arrangement. The motors have rated inputs of 20
MVA and 10 MVA at 12.8 KV with 20% sub transient reactance each. The 3-
phase
•
• Solution:
•
• The one line diagram with the data is obtained as shown in figure P3(a).
•
• Selection of base quantities:
•
• XG = j 0.15 pu.
•
•
•
• Problem #4:
•
• A 33 MVA, 13.8 KV, 3-phase generator has a sub transient reactance of 0.5%.
The generator supplies a motor through a step- up transformer - transmission
line – step-down transformer arrangement. The motor has rated input of 25
MVA at 6.6 KV with 25% sub transient reactance. Draw the equivalent per unit
impedance diagram by selecting 25 MVA (3φ), 6.6 KV (LL) as base values in
the motor circuit, given the transformer and transmission line data as under:
•
• Step up transformer bank: three single phase units, connected ∆–Y, each rated
10 MVA, 13.2/6.6 KV with 7.7 % leakage reactance and 0.5 % leakage
resistance;
•
• Solution:
•
• The one line diagram with the data is obtained as shown in figure P4(a).
•
• 3-phase ratings of transformers:
•
• T1: 3(10) = 30 MVA, 13.2/ 66.4√3 KV = 13.2/ 115 KV, X = 0.077, R = 0.005
pu.
• T2: 3(8.33) = 25 MVA, 110/ 3.98√3 KV = 110/ 6.8936 KV, X = 0.08, R =
0.008 pu.
•
• 25 MVA, 6.6 KV in the motor circuit (Given); the voltage bases in other sections
are: 6.6 (110/6.8936) = 105.316 KV in the transmission line circuit and 105.316
(13.2/115) = 12.09 KV in the generator circuit.
•
• Calculation of pu values:
• Xm = j 0.25 pu; Em = 1.0∠00 pu.
•
•
•
•
• Problems
•
• [Answers: XG1 = j 0.1778, Xg2 = j 0.089, Xg3 = j 0.16 all in per unit]
•
• 2. A 100 MVA, 33 KV, 3-phase generator has a sub transient reactance of 15%.
The generator supplies 3 motors through a step-up transformer - transmission
line – step- down transformer arrangement. The motors have rated inputs of 30
MVA, 20 MVA and 50 MVA, at 30 KV with 20% sub transient reactance each.
The 3 -phase transformers are rated at 100 MVA, 32 KV-∆ /110 KV-Y with 8
% leakage reactance. The line has a reactance of 50 ohms. By selecting the
generator ratings as base values in the generator circuit, determine the base
values in all the other parts of the system. Hence evaluate the corresponding pu
values and draw the equivalent per unit reactance diagram.
•
• [Answers: X G = j 0.15, Xm1 = j 0.551, Xm2 = j 0.826, Xm3 = j 0.331, Eg1=1.0 ∠00,
Em1 = Em2 = Em3 = 0.91∠00, Xt1 = Xt2 = j 0.0775 and Xline = j 0.39 all in per unit]
•
•
•
•
•
•
•
• Problem #1:
•
• Two generators rated 10 MVA, 13.2 KV and 15 MVA, 13.2 KV are connected
in parallel to a bus bar. They feed supply to 2 motors of inputs 8 MVA and 12
MVA respectively. The operating voltage of motors is 12.5 KV. Assuming the
base quantities as 50 MVA, 13.8 KV, draw the per unit reactance diagram. The
percentage reactance for generators is 15% and that for motors is 20%.
•
• Solution:
•
• The one line diagram with the data is obtained as shown in figure P1(a).
•
• Selection of base quantities: 50 MVA, 13.8 KV (Given)
•
• Calculation of pu values:
• XG1 = j 0.15 (50/10) (13.2/13.8)2 = j 0.6862 pu.
• XG2 = j 0.15 (50/15) (13.2/13.8)2 = j 0.4574 pu.
• Xm1 = j 0.2 (50/8) (12.5/13.8)2 = j 1.0256 pu.
• Xm2 = j 0.2 (50/12) (12.5/13.8)2 = j 0.6837 pu.
•
•
•
• Problem #2:
•
• Draw the per unit reactance diagram for the system shown in figure below.
Choose a base of 11 KV, 100 MVA in the generator circuit.
•
• Solution:
•
• The one line diagram with the data is considered as shown in figure.
•
• Calculation of pu values:
• Calculation of pu values:
• XG = j 0.1 pu, Xm = j 0.2 (100/90) (6.6/6.31)2 = j 0.243 pu.
• Xt1 =Xt2 = j 0.1 (100/50) (11.5/11)2 = j 0.2185 pu.
• Xt3 =Xt4 = j 0.1 (100/50) (6.6/6.31)2 = j 0.219 pu.
• Xlines = j 20 (100/1102) = j 0.1652 pu.
• Eg = 1.0∠00 pu, Em = (6.6/6.31) = 1.045∠00 pu
• Thus the pu reactance diagram can be drawn as shown in figure P2(b).
•
•
• Problem #3:
•
• A 30 MVA, 13.8 KV, 3-phase generator has a sub transient reactance of 15%.
The generator supplies 2 motors through a step-up transformer - transmission
line – step-down transformer arrangement. The motors have rated inputs of 20
MVA and 10 MVA at 12.8 KV with 20% sub transient reactance each. The 3-
phase
•
• Solution:
•
• The one line diagram with the data is obtained as shown in figure P3(a).
•
• Selection of base quantities:
•
• XG = j 0.15 pu.
•
•
•
• Problem #4:
•
• A 33 MVA, 13.8 KV, 3-phase generator has a sub transient reactance of 0.5%.
The generator supplies a motor through a step- up transformer - transmission
line – step-down transformer arrangement. The motor has rated input of 25
MVA at 6.6 KV with 25% sub transient reactance. Draw the equivalent per unit
impedance diagram by selecting 25 MVA (3φ), 6.6 KV (LL) as base values in
the motor circuit, given the transformer and transmission line data as under:
•
• Step up transformer bank: three single phase units, connected ∆–Y, each rated
10 MVA, 13.2/6.6 KV with 7.7 % leakage reactance and 0.5 % leakage
resistance;
•
• Solution:
•
• The one line diagram with the data is obtained as shown in figure P4(a).
•
• 3-phase ratings of transformers:
•
• T1: 3(10) = 30 MVA, 13.2/ 66.4√3 KV = 13.2/ 115 KV, X = 0.077, R = 0.005
pu.
• T2: 3(8.33) = 25 MVA, 110/ 3.98√3 KV = 110/ 6.8936 KV, X = 0.08, R =
0.008 pu.
•
• 25 MVA, 6.6 KV in the motor circuit (Given); the voltage bases in other sections
are: 6.6 (110/6.8936) = 105.316 KV in the transmission line circuit and 105.316
(13.2/115) = 12.09 KV in the generator circuit.
•
• Calculation of pu values:
• Xm = j 0.25 pu; Em = 1.0∠00 pu.
•
•
•
•
• Problems
•
• [Answers: XG1 = j 0.1778, Xg2 = j 0.089, Xg3 = j 0.16 all in per unit]
•
• 2. A 100 MVA, 33 KV, 3-phase generator has a sub transient reactance of 15%.
The generator supplies 3 motors through a step-up transformer - transmission
line – step- down transformer arrangement. The motors have rated inputs of 30
MVA, 20 MVA and 50 MVA, at 30 KV with 20% sub transient reactance each.
The 3 -phase transformers are rated at 100 MVA, 32 KV-∆ /110 KV-Y with 8
% leakage reactance. The line has a reactance of 50 ohms. By selecting the
generator ratings as base values in the generator circuit, determine the base
values in all the other parts of the system. Hence evaluate the corresponding pu
values and draw the equivalent per unit reactance diagram.
•
• [Answers: X G = j 0.15, Xm1 = j 0.551, Xm2 = j 0.826, Xm3 = j 0.331, Eg1=1.0 ∠00,
Em1 = Em2 = Em3 = 0.91∠00, Xt1 = Xt2 = j 0.0775 and Xline = j 0.39 all in per unit]
•
•
•
•
•
•
•
• Problem #1:
•
• Two generators rated 10 MVA, 13.2 KV and 15 MVA, 13.2 KV are connected
in parallel to a bus bar. They feed supply to 2 motors of inputs 8 MVA and 12
MVA respectively. The operating voltage of motors is 12.5 KV. Assuming the
base quantities as 50 MVA, 13.8 KV, draw the per unit reactance diagram. The
percentage reactance for generators is 15% and that for motors is 20%.
•
• Solution:
•
• The one line diagram with the data is obtained as shown in figure P1(a).
•
• Selection of base quantities: 50 MVA, 13.8 KV (Given)
•
• Calculation of pu values:
• XG1 = j 0.15 (50/10) (13.2/13.8)2 = j 0.6862 pu.
• XG2 = j 0.15 (50/15) (13.2/13.8)2 = j 0.4574 pu.
• Xm1 = j 0.2 (50/8) (12.5/13.8)2 = j 1.0256 pu.
• Xm2 = j 0.2 (50/12) (12.5/13.8)2 = j 0.6837 pu.
•
•
•
• Problem #2:
•
• Draw the per unit reactance diagram for the system shown in figure below.
Choose a base of 11 KV, 100 MVA in the generator circuit.
•
• Solution:
•
• The one line diagram with the data is considered as shown in figure.
•
• Calculation of pu values:
• Calculation of pu values:
• XG = j 0.1 pu, Xm = j 0.2 (100/90) (6.6/6.31)2 = j 0.243 pu.
• Xt1 =Xt2 = j 0.1 (100/50) (11.5/11)2 = j 0.2185 pu.
• Xt3 =Xt4 = j 0.1 (100/50) (6.6/6.31)2 = j 0.219 pu.
• Xlines = j 20 (100/1102) = j 0.1652 pu.
• Eg = 1.0∠00 pu, Em = (6.6/6.31) = 1.045∠00 pu
• Thus the pu reactance diagram can be drawn as shown in figure P2(b).
•
•
• Problem #3:
•
• A 30 MVA, 13.8 KV, 3-phase generator has a sub transient reactance of 15%.
The generator supplies 2 motors through a step-up transformer - transmission
line – step-down transformer arrangement. The motors have rated inputs of 20
MVA and 10 MVA at 12.8 KV with 20% sub transient reactance each. The 3-
phase
•
• Solution:
•
• The one line diagram with the data is obtained as shown in figure P3(a).
•
• Selection of base quantities:
•
• XG = j 0.15 pu.
•
•
•
• Problem #4:
•
• A 33 MVA, 13.8 KV, 3-phase generator has a sub transient reactance of 0.5%.
The generator supplies a motor through a step- up transformer - transmission
line – step-down transformer arrangement. The motor has rated input of 25
MVA at 6.6 KV with 25% sub transient reactance. Draw the equivalent per unit
impedance diagram by selecting 25 MVA (3φ), 6.6 KV (LL) as base values in
the motor circuit, given the transformer and transmission line data as under:
•
• Step up transformer bank: three single phase units, connected ∆–Y, each rated
10 MVA, 13.2/6.6 KV with 7.7 % leakage reactance and 0.5 % leakage
resistance;
•
• Solution:
•
• The one line diagram with the data is obtained as shown in figure P4(a).
•
• 3-phase ratings of transformers:
•
• T1: 3(10) = 30 MVA, 13.2/ 66.4√3 KV = 13.2/ 115 KV, X = 0.077, R = 0.005
pu.
• T2: 3(8.33) = 25 MVA, 110/ 3.98√3 KV = 110/ 6.8936 KV, X = 0.08, R =
0.008 pu.
•
• 25 MVA, 6.6 KV in the motor circuit (Given); the voltage bases in other sections
are: 6.6 (110/6.8936) = 105.316 KV in the transmission line circuit and 105.316
(13.2/115) = 12.09 KV in the generator circuit.
•
• Calculation of pu values:
• Xm = j 0.25 pu; Em = 1.0∠00 pu.
•
•
•
•
• Problems
•
• [Answers: XG1 = j 0.1778, Xg2 = j 0.089, Xg3 = j 0.16 all in per unit]
•
• 2. A 100 MVA, 33 KV, 3-phase generator has a sub transient reactance of 15%.
The generator supplies 3 motors through a step-up transformer - transmission
line – step- down transformer arrangement. The motors have rated inputs of 30
MVA, 20 MVA and 50 MVA, at 30 KV with 20% sub transient reactance each.
The 3 -phase transformers are rated at 100 MVA, 32 KV-∆ /110 KV-Y with 8
% leakage reactance. The line has a reactance of 50 ohms. By selecting the
generator ratings as base values in the generator circuit, determine the base
values in all the other parts of the system. Hence evaluate the corresponding pu
values and draw the equivalent per unit reactance diagram.
•
• [Answers: X G = j 0.15, Xm1 = j 0.551, Xm2 = j 0.826, Xm3 = j 0.331, Eg1=1.0 ∠00,
Em1 = Em2 = Em3 = 0.91∠00, Xt1 = Xt2 = j 0.0775 and Xline = j 0.39 all in per unit]
•
•
•
5. Write the equation for converting the p.u. impedance expressed in one base to
another.
• The p.u. values of widely different rating machines lie within a narrow
range eventhough the ohmic values has a very large range.
1. What is a bus?
7. What are the methods available for forming bus impedances matrix?
(1)Form the bus admittances matrix and then take its inverse to get bus
impedance matrix.
The information obtained from a load flow study is magnitude and phase
angle of voltages, real and reactive power flowing in each line and the line
losses. The load flow solution also gives the initial conditions of the system
when the transient behavior of the system is to be studied.
The load flow study of a power system is essential to decide the best operation
of existing system and for planning the future expansion of the system. It is
also essential for designing a new power system.
Each bus in a power system is associated with four quantities and they are
real power (P), reactive power (Q), magnitude of voltage (V), and phase angle
of voltage (δ).
Work involved (or) to be performed by a load flow study
(i). Representation of the system by a single line diagram
(ii). Determining the impedance diagram using the information in single line
diagram (iii). Formulation of network equation
The load flow equations are non linear algebraic equations and so explicit
solution as not possible. The solution of non linear equations can be obtained
only by iterative numerical techniques.
In iterative method of load flow solution, the initial voltages of all buses except
slack bus assumed as 1+j0 p.u. This is referred to as flat voltage start
Classification of Buses
Bus: The meeting point of various components in a power system is called a bus. - Different types of
buses in a power system
CLASSIFICATION OF BUSES
Bus
The matrix consisting of the self and mutual admittance of the network of the
power system is called bus admittance matrix (Ybus).
The slack bus is needed to account for transmission line losses. In a power
system the total power generated will be equal to sum of power consumed by
loads and losses. In a power system only the generated power and load power
are specified for buses. The slack bus is assumed to generate the power
required for losses. Since the losses are unknown the real and reactive power
are not specified for slack bus.
If the reactive power constraint of a generator bus violates the specified limits
then the generator is treated as load bus.
Step1: Assume all bus voltage be 1+ j0 except slack bus. The voltage of the
slack bus is a constant voltage and it is not modified at any iteration
Step 2: Assume a suitable value for specified change in bus voltage which is
used to compare the actual change in bus voltage between K th and
(K+1) th iteration
Step 3: Set iteration count K = 0 and the corresponding voltages are V 10, V20,
V30, …… Vn0 except slack bus
Step 4: Set bus count P = 1
Step 5: Check for slack bus. It is a slack bus then goes to step 12 otherwise go
to next step
Step 7: Set │VPK│= │VP│ specified and phase of │VPK│ as the K th iteration
value if the bus P is a generator bus where │VP│ specified is the specified
magnitude of voltage for bus P. Calculate reactive power rating
Step 16: Calculate the line flows and slack bus power by using the bus
voltages
Step 1: Assume a suitable solution for all buses except the slack bus. Let V p =
a+j0 for P
= 2,3,……n V1 = a+j0
Step 2 : Set the convergence criterion = ε0
Step 9 : Advance bus count P = P+1 and check if all buses taken in to account
if not go to step 5
Step 12: Evaluate the element of Jacobin matrices J 1, J2, J3, J4, J5 and J6
Step 14: Calculate ePK+1 = ePK + ΔePK and fPK+1 = fPK + ΔfPK
Step 16: Evaluate bus and line power and print the result
• Prev Page
Step 1: Assume a suitable solution for all buses except the slack bus. Let Vp
=1+j0 for P=2,3,...................n and V=a+j0
Step 6: Compute the real and reactive power mismatches ΔPK and ΔQK. If the
mismatches Are with in desirable tolerance the iteration end
Step 7: Normalize the mismatches by dividing each entry by its respective bus
voltage
[B’] δK = ΔPK
[B”]ΔQK = ΔQK
δK+1 = δK +ΔδK
VK+1 = VK +ΔVK
Step 10: Check if all the buses are taken into account if yes go to next step
otherwise go to next step. Otherwise go to step 4
Step 12: Evaluate bus and load powers and print the results
Compare the Gauss Seidel and Newton Raphson
Methods of Load Flow Study
Y matrix of the sample power system as shown in fig. Data for this system is given in table.
Advantages: Faster, more reliable and results are accurate, require less
number of iterations; Disadvantages: Program is more complex, memory is
more complex.
2. What are the informations that are obtained from a load flow study?
The information obtained from a load flow study are magnitude and phase
of bus voltages, real and reactive power flowing in each line and the line losses. The
load flow solution also gives the initial conditions of the system when the transient
behaviour of the system is to be studied.
The load flow study of a power system is essential to decide the best
operation of existing system and for planning the future expansion of the system.
Also essential for designing a new system.
Ø What are the works involved in a load flow study? (i)Representation of the
system by single line diagram.
Ø What are the quantities that are associated with each bus in a system?
Each bus in a system are associated with four quantities and they are real
power,reactive power, magnitude of voltage and phase angle of voltage.
Ø What are the different types of buses? (i)Load bus or PQ bus
A bus is called voltage controlled bus if the magnitude of voltage and real
power are specified. The magnitude of voltage is not allowed to change.
8. What is PQ bus?
A bus is called PQ are load bus when real and reactive components of power
are specified for the bus. In a load bus the voltage is allowed to vary within the
permissible value.
Ø What are the iterative methods used for solution of load flow problems? Guass-
Seidal (GS) method and Newton Raphson(NR) method.
The load flow equations are nonlinear algebraic equations and so explicit
solution is not possible. The solution of nonlinear equations can be obtained only
by iterative numerical techniques.
If the reactive power of a generator bus violates the specified limits then the
generator bus is treated as load bus.
14. What are the advantages of GS method?
(iii)Computation time per iteration is higher due to large number of calculations per
iterations.
Fault
A fault in a circuit is any failure which interferes with the normal flow of
current. The faults are associated with abnormal change in current, voltage
and frequency of the power system.
Faults occur in a power system
The faults occur in a power system due to
(i). Insulation failure of equipment
(ii) Shunt fault or short circuit fault. Symmetrical fault or balanced fault
▪ Three phase fault
This type of fault is defined as the simultaneous short circuit across all the
three phases. It occurs infrequently, but it is the most severe type of fault
encountered. Because the network is balanced, it is solved by per phase basis
using Thevenins theorem or bus impedance matrix or KVL, KCL laws.
(iv). Shunt elements in the transformers model that account for magnetizing
current and core loss are neglected
Short circuit studies are essential in order to design or develop the protective
schemes for various parts of the system .To estimate the magnitude of fault
current for the proper choice of circuit breaker and protective relays.
Doubling effect
If a symmetrical fault occurs when the voltage wave is going through zero then
the maximum momentary short circuit current will be double the value of
maximum symmetrical short circuit current. This effect is called doubling
effect.
• Prev Page
•
Symmetrical Fault
In symmetrical faults all the three phases are short circuited to each other and to earth also.
SYMMETRICAL FAULT
In symmetrical faults all the three phases are short circuited to each other and
to earth also. Such faults are balanced and symmetrical in the sense that the
voltage and current of the system remains balanced even after the fault and it
is enough if we consider any one phase
The synchronous reactance is the ratio of induced emf and the steady state
rms current. It is the sum of leakage reactance (Xl) and the armature reactance
(Xa).
The synchronous reactance is the ratio of induced emf on no load and the sub
transient symmetrical rms current.
Transient reactance
The synchronous reactance is the ratio of induced emf on no load and the
transient symmetrical rms current.
Fault current in fig., if the Pre-fault voltage at the fault point is 0.97 p.u.
Thevenin’s theorem:
(i). Fault current = Eth / (Zth+Zf)
(ii). Determine current contributed by the two generators IG 1 = If *
(Z2/(Z1+Z2))
IG2 = If * (Z1 / (Z1+Z2))
(iii). Determine Post fault voltage Vif = Vi°+ΔV = V°+(-Zi2*IGi)
(iv). Determine post fault voltage line flows Iij = (Vi –Vj) / Zij series
(v). Short circuit capacity If = │Eth│2 / Xth
• Prev Page
•
Symmetrical Fault
In symmetrical faults all the three phases are short circuited to each other and to earth also.
SYMMETRICAL FAULT
In symmetrical faults all the three phases are short circuited to each other and
to earth also. Such faults are balanced and symmetrical in the sense that the
voltage and current of the system remains balanced even after the fault and it
is enough if we consider any one phase
Short circuit capacity (SCC) or Short circuit MVA or fault level at a bus is
defined as the product of the magnitude of the pre fault bus voltage and the
post fault current
The synchronous reactance is the ratio of induced emf on no load and the sub
transient symmetrical rms current.
Transient reactance
The synchronous reactance is the ratio of induced emf on no load and the
transient symmetrical rms current.
Fault current in fig., if the Pre-fault voltage at the fault point is 0.97 p.u.
Thevenin’s theorem:
(i). Fault current = Eth / (Zth+Zf)
(ii). Determine current contributed by the two generators IG 1 = If *
(Z2/(Z1+Z2))
IG2 = If * (Z1 / (Z1+Z2))
(iii). Determine Post fault voltage Vif = Vi°+ΔV = V°+(-Zi2*IGi)
(iv). Determine post fault voltage line flows Iij = (Vi –Vj) / Zij series
(v). Short circuit capacity If = │Eth│2 / Xth
• Prev Page
•
SOLVED PROBLEMS
Problem 1
A radial power system network is shown in fig. a three phase balanced fault
occurs at F. Determine the fault current and the line voltage at 11.8 KV bus
under fault condition.
Problem : 2
2. What are the informations that are obtained from a load flow study?
Each bus in a system are associated with four quantities and they
are real power,reactive power, magnitude of voltage and phase angle of
voltage.
8. What is PQ bus?
A bus is called PQ are load bus when real and reactive components
of power are specified for the bus. In a load bus the voltage is allowed to
vary within the permissible value.
A bus is called Swing bus when the magnitude and phase of the
voltage are specified for it. Swing bus is the reference bus for load flow
solution and it is required for accounting line losses.
10. What is the need for slack bus?
The sequence impedances are the impedances offered by the power system
components or elements to +ve, -ve and zero sequence current.
b) What value of resistance in the neutral will serve the same purpose?
d) What will be the magnitudes of the line currents when the ground
current is restricted as above?
A fault in a circuit is any failure which interferes with the normal flow of
current. The faults are associated with abnormal change in current, voltage and
frequency of the power system.
3. List the various types of shunt and series faults. The various types of shunt faults
are:
The fault is called symmetrical fault if the fault current is equal in all the
phases.The fault is called unsymmetrical fault if the fault current is not equal in all
the phases.
The short circuit studies are essential in order to design or develop the
protective schemes for various parts of the system. The protective schemes
consists of current and voltage sensing devices , protective relays and circuit
breakers. The selection of these devices mainly depends on various currents that
may flow in the fault conditions.
The synchronous reactance is the ratio of induced emf and the steady rms
current. It is the sum of leakage reactance and the reactance representing armature
reaction.
The subtransient reactance is the ratio of induced emf on no load and the
transient symmetrical rms current.
11. Name the fault in which positive, negative and zero sequence component
currents are equal.
12. Name the fault in which positive and negative sequence component currents
together is equal to zero sequence current in magnitude.
Va = 0 ; I b = I c = 0
I a = 0 ; I b + I c = 0 ; V b = Vc
17. Write down the boundary condition in double line to ground fault. I a = 0 ; Vb = 0
; Vc= 0
Part-B
1.A balanced delta connected load is connected to a three phase system and
supplied to it is a current of 15 amps. If the fuse is one of the lines melts, compute
the symmetrical components of line currents
3.A 50MVA, 11KV, synchronous generator has a sub transient reactance of 20%.The
generator supplies two motors over a transmission line with transformers at both
ends as shown in fig. The motors have rated inputs of 30 and 15 MVA, both 10KV,
with 25% sub transient reactance. The three phase transformers are both rated
60MVA, 10.8/121KV, with leakage reactance of 10% each. Assume zero sequence
reactance for the generator and motors of 6% each. Current limiting reactors of 2.5
ohms each are connected in the neutral of the generator and motor number 2. The
zero sequence reactance of the transmission line is 300 ohms. The series reactance
of the line is 100 ohms. Draw the positive, negative and zero sequence networks.
4.A 30 MVA, 13.2KV synchronous generator has a solidly grounded neutral. Its
positive, negative and zero sequence impedances are 0.30, 0.40 and 0.05 p.u
respectively. Determine the following:
i. What value of reactance must be placed in the generator neutral so that the fault
current for a line to ground fault of zero fault impedance shall not exceed the rated
line current?
ii. What value of resistance in the neutral will serve the same purpose?
iii. What value of reactance must be placed in the neutral of the generator to
restrict the fault current to ground to rated line current for a double line to ground
fault?
iv. What will be the magnitudes of the line currents when the ground current is
restricted as above?
Steady state stability is defined as the ability of the power system to bring it
to a stable condition or remain in synchronism after a small disturbance.
Steady state stability limit
The steady sate stability limit is the maximum power that can be transferred
by a machine to receiving system without loss of synchronism
Transient stability
The transient stability limit is the maximum power that can be transferred by
a machine to a fault or a receiving system during a transient state without loss
of synchronism.Transient stability limit is always less than steady state
stability limit
Dynamic stability
Voltage stability
• Prev Page
δ - Rotor angle.
• Prev Page
This is the maximum short circuit current which a circuit breaker can withstand
before it. Finally cleared by opening its contacts. When a short circuit flows
through a circuit breaker, there would be thermal and mechanical stresses in
the current carrying parts of the breaker. If the contact area and cross-section
of the conducting parts of the circuit breaker are not sufficiently large, there
may be a chance of permanent damage in insulation as well as conducting parts
of the CB. The short circuit current has a certain value at the instant of contact
separation. The breaking current refers to value of current at the instant of the
contact separation. The rated values of transient recovery voltage are specified
for various rated voltage of circuit breakers. For specified conditions of rated
TRV and rated power frequency recovery voltage, a circuit breaker has a certain
limit of breaking current. This limit is determined by conducting short circuit
type tests on the circuit breaker. The waveforms of short circuit current are
obtained during the breaking test. The evaluation of the breaking current is
explained in Fig. 3. The breaking current is expressed by two values. The r.m.s
values of a.c. components are expressed in KA. the standard values being 8, 10,
12.5, 16, 20, 25, 31.5, 40, 45, 63, 80 and 100KA. The earlier practice was to
express the rated breaking capacity of a circuit breaker in terms of MVA given
as follows Rated Breaking MVA capacity = √3 x KV x KA Where MVA = Breaking
capacity of a circuit breaker kV KV = Rated voltage KA = Rated breaking current.
The short circuit making capacity of circuit breaker is expressed in peak value
not in rms value like breaking capacity.It may so happen that circuit breaker
may close on an existing fault. In such cases the current increase to the
maximum value at the peak of first current loop. The circuit breaker should be
able to close without hesitation as contact touch. The circuit breaker should be
able to withstand the high mechanical forces during such a closure. These
capabilities are proved by carrying out making current test. The rated short
circuit making current of a circuit breaker is the peak value of first current loop
of short circuit current (I pk)Which the circuit breaker is capable of making at
its rated voltage. The rated short circuit making current should be least 2.5
times the r.m.s. value of a.c. component of rated breaking current . Rated
making current = 1.8 x √2 x Rated short circuit breaking = 2.5 x Rated short
circuit breaking current In the above equation the factor √2 convert the r.m.s
value to peak value. Factor 1.8 takes into account the doubling effect of short
circuit current with consideration to slight drop in current during the first
quarter cycle .
This is the current limit which a circuit breaker can carry safely for certain
specific time without any damage.
The circuit breakers do not clear the short circuit current as soon as any fault
occurs in the system. There always some intentional and an intentional time
delays present between the instant of occurrence of fault and instant of clearing
the fault by CB. This delay is present because of time of operation of protection
relays, time of operation of circuit breaker and also there may be some
intentional time delay imposed in relay for proper coordination of power
system protection. Hence, after fault, a circuit breaker has to carry the short
circuit for certain time. The summation of all time delays should not be more
than 3 seconds, hence a circuit breaker should be capable of carrying a
maximum fault current for at least this short period of time.
The short circuit current may have two major affects inside a circuit breaker.
1. Because of the high electric current, there may be high thermal stress
in the insulation and conducting parts of CB.
The rated short time current of a circuit breaker is at least equal to rated short
circuit breaking current of the circuit breaker.
Rated voltage of circuit breaker
Rated voltage of circuit breaker depends upon its insulation system. For below
400 KV system, the circuit breaker is designed to withstand 10% above the
normal system voltage. For above or equal 400 KV system the insulation of
circuit breaker should be capable of withstanding 5% above the normal system
voltage. That means, rated voltage of circuit breaker corresponds to the highest
system voltage. This is because during no load or small load condition the
voltage level of power system is allowed rise up to highest voltage rating of the
system.
1) Sudden disconnection of huge load for any other cause, the voltage
imposed on the CB and also between the contacts when the CB is open, may be
very high compared to higher system voltage. This voltage may be of power
frequency but does not stay for very long period as this high voltage situation
must be cleared by protective switchgear. But a circuit breaker may have to
withstand this power frequency over voltage, during its normal life span.
The Circuit Breaker must be rated for power frequencies withstand voltage for
a specific time only. Generally the time is 60 seconds. Making power frequency
withstand capacity, more than 60 second is not economical and not practically
desired as all the abnormal situations of electrical power system are definitely
cleared within much smaller period than 60 seconds.
• Prev Page
The working principle of this breaker is rather different from those in any other
types of circuit breakers. The main aim of all kind of circuit breaker is to prevent
the reestablishment of arcing after current zero by creating a situation where
in the contact gap will withstand the system recovery voltage. The air circuit
breaker does the same but in different manner. For interrupting arc it creates
an arc voltage in excess of the supply voltage. Arc voltage is defined as the
minimum voltage required maintaining the arc. This circuit breaker increases
the arc voltage by mainly three different ways,
1. It may increase the arc voltage by cooling the arc plasma. As the temperature
of arc plasma is decreased, the mobility of the particle in arc plasma is reduced,
hence more voltage gradient is required to maintain the arc.
2. It may increase the arc voltage by lengthening the arc path. As the length of
arc path is increased, the resistance of the path is increased, and hence to
maintain the same arc current more voltage is required to be applied across the
arc path. That means arc voltage is increased.
3. Splitting up the arc into a number of series arcs also increases the arc voltage.
The first objective is usually achieved by forcing the arc into contact with as
large an area as possible of insulating material. Every air circuit breaker is fitted
with a chamber surrounding the contact. This chamber is called „arc chute‟. The
arc is driven into it. If inside of the arc chute is suitably shaped, and if the arc
can conform to the shape, the arc chute wall will help to achieve cooling. This
type of arc chute should be made from some kind of refractory material
The second objective that is lengthening the arc path is achieved concurrently
with the first objective. If the inner walls of the arc chute is shaped in such a
way that the arc is not only forced into close proximity with it but also driven
into a serpentine channel projected on the arc chute wall. The lengthening of
the arc path increases the arc resistance.
The third objective is achieved by using metal arc slitter inside the arc chute.
The main arc chute is divided into numbers of small compartments by using
metallic separation plates. These metallic separation plates are actually the arc
splitters and each of the small compartments behaves as individual mini arc
chute. In this system the initial arc is split into a number of series arcs, each of
which will have its own mini arc chute.
1. Main contacts
2. Arcing contacts
3. Arc rifling in the direction of the arrow
4. Arcsplitterplates
The contacts travel through a short distance against the spring pressure. At the
end of contacts travel the part for outgoing air is closed by the moving contacts
and the entire arc extinction chamber is filled with high pressure air, as the air
is not allowed to go out. However, during the arcing period the air goes out
through the openings and takes away the ionized air While closing, the valve is
turned so as to close connection between the hollow of the insulator and the
reservoir.
The valve lets the air from the hollow insulator to the atmosphere. As a result
the pressure of air in the arc extinction chamber is dropped down to the
atmospheric pressure and the moving contacts close over the fixed contacts by
virtue of the spring pressure, the opening is fast because the air takes a
negligible time to travel from the reservoir to the moving contact. The arc is
extinguished within a cycle. Therefore, air blast circuit breaker is very fast in
breaking the current. Closing is also fast because the pressure in the arc
extinction chamber drops immediately as the value operates and the contacts
close by virtue of the spring pressure.
Advantages:
• How air blast circuit breaker is better than oil circuit breaker:
• The growth of dielectric strength is so rapid that final contact gap needed
for arc extinction is very small, this reduces the size of device.
• Due to lesser arc energy, air blast circuit breakers are very suitable for
conditions where frequent operation is required.
• The arcing products are completely removed by the blast whereas the oil
deteriorates with successive operations; the expense of regular oil is
replacement is avoided.
• The energy supplied for arc extinction is obtained from high pressure air
and is independent of the current to be interrupted.
• The arcing time is very small due to the rapid buildup of dielectric
strength between contacts. Therefore, the arc energy is only a fraction that in
oil circuit breakers, thus resulting in less burning of contacts.
Disadvantages:
• Air blast circuit breakers are very sensitive to the variations in the rate
of restriking voltage.
• Air blast circuit breakers are finding wide applications in high voltage
installations.Majority of circuit breakers for voltages beyond 110 kV are of this
type.
In the former type no means is available for controlling the arc and the contacts
are exposed to the whole of the oil in the tank. In the latter special arc control
devices are employed to get the beneficial action of the arc as efficiently as
possible
which use minimum amount of oil. In such circuit breakers oil is used only for
arc extinction, the current conducting parts are insulated by air or porcelain or
organic insulating material.
Construction
There are two chambers in a low oil circuit breaker; the oil in each chamber is
separated from each other. The main advantage of this is that low oil is required
and oil in second chamber won‘t get polluted. Upper chamber is called the
circuit breaker chamber and lower one is called the supporting chamber.
Circuit breaking chamber consists of moving contact and fixed contact.
Moving contact is connected with a piston it‘s just for the movement of the
contact and no pressure build due to its motion. There are two vents on fixed
contact they are axial vent for small current produced in oil due to heating of
arc and radial vents for large currents. The whole device is covered using
Bakelite paper and porcelain for protection. Vents are placed in a tabulator.
Operation
Under normal operating conditions, the moving contacts remain engaged with
the upper fixed contact. When a fault occurs, the moving contact is pulled down
by the tripping springs and an arc is struck. The arc vaporizes oil and produces
gases under high pressure. This action constrains the oil to pass through a
central hole in the moving contact and results in forcing series of oil through
the respective passages of the turbulator.The process of tabulation is orderly
one, in which the sections of arc are successively quenched by the effect of
separate streams of oil, moving across each section in turn and bearing away
its gases
constrains the oil to pass through a central hole in the moving contact and
results in forcing series of oil through the respective passages of the
turbulator.The process of tabulation is orderly one, in which the sections of arc
are successively quenched by the effect of separate streams of oil, moving
across each section in turn and bearing away its gases
Advantages
A low oil circuit breaker has following advantages compared to bulk oil circuit
breaker
Disadvantages
• Low oil circuit breaker has following disadvantages compared to bulk oil
circuit breaker
• There is a difficulty of removing the gases from the contact space in time
• Prev Page
• Next P
SF6 circuit breaker: Construction, Operation,
Advantages, Disadvantages
At this point we are aware that the medium in which arc extinction of the circuit breaker takes place
greatly influences the important characteristics and life of the circuit breaker.
At this point we are aware that the medium in which arc extinction of the circuit
breaker takes place greatly influences the important characteristics and life of
the circuit breaker. the working of a vacuum circuit breaker was illustrated. We
already know that the use of vacuum circuit breaker is mainly restricted to
system voltage below 38 kV. The characteristics of vacuum as medium and cost
of the vacuum CB does not makes it suitable for voltage exceeding 38 kV. In the
past for higher transmission voltage Oil Circuit Breaker (OCB) and Air Blast
Circuit Breaker (ABCB) were used. These days for higher transmission voltage
levels SF6 Circuit Breakers are largely used. OCB and ABCB have almost become
obsolete. In fact in many installations SF6 CB is used for lower voltages like 11
kV, 6 kV etc.. i)sulphur Hexafluoride symbolically written as SF6 is a gas which
satisfy the requirements of an ideal arc interrupting medium. So SF6 is
extensively used these days as an arc interrupting medium in circuit breakers
ranging from 3 kv upto 765 kv class. In addition to this SF6 is used in many
electrical equipments for insulation. Here first we discuss in brief, some of the
essential properties of SF6 which is the reason of it's extensive use in circuit
breakers
SF6 gas has high dielectric strength which is the most important quality of a
material for use in electrical equipments and in particular for breaker it is one
of the most desired properties. Moreover it has high Rate of Rise of dielectric
strength after arc extinction.
• SF6 has high thermal conductivity which means the heat dissipation
capacity is more. This implies greater current carrying capacity when
surrounded by SF6 .
Advantages:
• Due to superior arc quenching property of sf6 , such breakers have very
short arcing time
• Dielectric strength of sf6 gas is 2 to 3 times that of air, such breakers can
interrupt much larger currents.
• Gives noiseless operation due to its closed gas circuit
• Closed gas enclosure keeps the interior dry so that there is no moisture
problem
• sf6 breakers are totally enclosed and sealed from atmosphere, they are
particularly suitable where explosion hazard exists
Disadvantages:
The construction and working principles of SF6 circuit breaker varies from
manufacturer to manufacturer. In the past double pressure type of SF6
breakers were used. Now these are obsolete. Another type of SF6 breaker
design is the self blast type, which is usually used for medium transmission
voltage. The Puffer type SF6 breakers of single pressure type are the most
favored types prevalent in power industry. Here the working principle of Puffer
type breaker is illustrated (Fig-A)
As illustrated in the figure the breaker has a cylinder and piston arrangement.
Here the piston is fixed but the cylinder is movable. The cylinder is tied to the
moving contact so that for opening the breaker the cylinder along with the
moving contact moves away from the fixed contact (Fig-A(b)). But due to the
presence of fixed piston the SF6 gas inside the cylinder is compressed. The
compressed SFe gas flows through the nozzle and over the electric arc in axial
direction. Due to heat convection and radiation the arc radius reduces gradually
and the arc is finally extinguished at current zero.
The gas pressure inside the cylinder is maintained at around 5 kgf per sq. cm.
At higher pressure the dielectric strength of the gas increases. But at higher
pressure the SF6 gas liquify at higher temperature which is undesired. So
heater is required to be arranged for automatic control of the temperature for
circuit breakers where higher pressure is utilised. If the SF6 gas will liquify then
it loses the ability to quench the arc. Like vacuum breaker, SF6 breakers are
also available in modular design form so that two modules connected in series
can be used for higher voltage levels. SF6 breakers are available as both live
tank and dead tank types. In Fig-B above a live tank outdoor type 400 kV SF6
breaker is shown.
In this breaker, vacuum is being used as the arc quenching medium. Vacuum
offers highest insulating strength, it has far superior arc quenching properties
than any other medium. When contacts of a breaker are opened in vacuum, the
interruption occurs at first current zero with dielectric strength between the
contacts building up at a rate thousands of times that obtained with other
circuit breakers. Principle: When the contacts of the breaker are opened in
vacuum (10 -7 to 10 -5 torr), an arc is produced between the contacts by the
ionization of metal vapours of contacts. The arc is quickly extinguished because
the metallic vapours, electrons, and ions produced during arc condense quickly
on the surfaces of the circuit breaker contacts, resulting in quick recovery of
dielectric strength. As soon as the arc is produced in vacuum, it is quickly
extinguished due to the fast rate of recovery of dielectric strength in vacuum
Construction:
Fig shows the parts of a typical vacuum circuit breaker. It consists of fixed
contact, moving contact and arc shield mounted inside a vacuum chamber. The
movable member is connected to the control mechanism by stainless steel
bellows .This enables the permanent sealing of the vacuum chamber so as to
eliminate the possibility of leak. A glass vessel or ceramic vessel is used as the
outer insulating body. The arc shield prevents the deterioration of the internal
dielectric strength by preventing metallic vapours falling on the inside surface
of the outer insulating cover.
Working:
When the breaker operates the moving contacts separates from the fixed
contacts and an arc is struck between the contacts. The production of arc is due
to the ionization of metal ions and depends very much upon the material of
contacts. The arc is quickly extinguished because the metallic vapours,
electrons and ions produced during arc are diffused in short time and seized by
the surfaces of moving and fixed members and shields. Since vacuum has very
fast rate of recovery of dielectric strength, the arc extinction in a vacuum
breaker occurs with a short contact separation.
Advantages:
• They can interrupt any fault current. The outstanding feature of a VCB is
that it can break any heavy fault current perfectly just before the contacts reach
the definite open position.
• They require little maintenance and are quiet in operation
• Low inertia and hence require smaller power for control mechanism.
Applications:
In this breaker, vacuum is being used as the arc quenching medium. Vacuum
offers highest insulating strength, it has far superior arc quenching properties
than any other medium. When contacts of a breaker are opened in vacuum, the
interruption occurs at first current zero with dielectric strength between the
contacts building up at a rate thousands of times that obtained with other
circuit breakers. Principle: When the contacts of the breaker are opened in
vacuum (10 -7 to 10 -5 torr), an arc is produced between the contacts by the
ionization of metal vapours of contacts. The arc is quickly extinguished because
the metallic vapours, electrons, and ions produced during arc condense quickly
on the surfaces of the circuit breaker contacts, resulting in quick recovery of
dielectric strength. As soon as the arc is produced in vacuum, it is quickly
extinguished due to the fast rate of recovery of dielectric strength in vacuum
Construction:
Fig shows the parts of a typical vacuum circuit breaker. It consists of fixed
contact, moving contact and arc shield mounted inside a vacuum chamber. The
movable member is connected to the control mechanism by stainless steel
bellows .This enables the permanent sealing of the vacuum chamber so as to
eliminate the possibility of leak. A glass vessel or ceramic vessel is used as the
outer insulating body. The arc shield prevents the deterioration of the internal
dielectric strength by preventing metallic vapours falling on the inside surface
of the outer insulating cover.
Working:
When the breaker operates the moving contacts separates from the fixed
contacts and an arc is struck between the contacts. The production of arc is due
to the ionization of metal ions and depends very much upon the material of
contacts. The arc is quickly extinguished because the metallic vapours,
electrons and ions produced during arc are diffused in short time and seized by
the surfaces of moving and fixed members and shields. Since vacuum has very
fast rate of recovery of dielectric strength, the arc extinction in a vacuum
breaker occurs with a short contact separation.
Advantages:
• They can interrupt any fault current. The outstanding feature of a VCB is
that it can break any heavy fault current perfectly just before the contacts reach
the definite open position.
• They require little maintenance and are quiet in operation
• Low inertia and hence require smaller power for control mechanism.
Applications:
Electrical Drives
Motion control is required in large number of industrial and domestic applications like transportation
systems, rolling mills, paper machines, textile mills, machine tools, fans, pumps, robots, washing
machines etc.
Electrical Drives:
Systems employed for motion control are called DRIVES, and may employ
any of prime movers such as diesel or petrol engines, gas or steam turbines, steam
engines, hydraulic motors and electric motors, for supplying mechanical energy for
motion control. Drives employing electric motors are known as Electrical Drives.
An Electric Drive can be defined as an electromechanical device for
converting electrical energy into mechanical energy to impart motion to different
machines and mechanisms for various kinds of process control.
✓ Manual
✓ Semi-automatic
✓ Automatic
✓ Individual drive
✓ Group drive
✓ Multi-motor drive
They have flexible control characteristics. The steady state and dynamic
characteristics of electric drives can be shaped to satisfy the load requirements.
This drive consists of a single motor, which drives one or more line shafts
supported on bearings. The line shaft may be fitted with either pulleys and belts or
gears, by means of which a group of machines or mechanisms may be operated. It
is also sometimes called as SHAFT DRIVES.
Advantages
Disadvantages
There is no flexibility. If the single motor used develops fault, the whole process
will be stopped.
In this drive system, there are several drives, each of which serves to actuate
one of the working parts of the drive mechanisms.
E.g. Complicated metal cutting machine tools
✓ DC drive
✓ AC drive
Applications
✓ Paper mills
✓ Cement Mills
✓ Textile mills
✓ Sugar Mills
✓ Steel Mills
✓ Electric Traction
✓ Petrochemical Industries
✓ Electrical Vehicles
Load speed may be different from that of motor, and if the load has many
parts, their speed may be different and while some parts rotate others may go
through a translational motion.
Load torque includes friction and wind age torque of motor. Motor-load
system shown in figure can be described by the following fundamental torque
equation.
Equation (1) is applicable to variable inertia drives such as mine winders, reel
drives, Industrial robots.