03 - Line Distance Protection P44x
03 - Line Distance Protection P44x
03 - Line Distance Protection P44x
Line Distance
P74x
Protection
JULY 2016
MICOM Products
MICOM Protection Portfolio
MICOM Relays
Hardware & Software Platform
MICOM Relays
Hardware & Software Platform
MICOM Relays
Hardware & Software Platform
MICOM Relays
Approximate Guidance: Characteristics
MICOM Distance Protection :
Characteristics Available
MICOM P44X Series :
Product Selector
P441/P442/P443 Summary
Typical HV/EHV Product Selection
Overview of Protection Features
MICOM P44x Functional Diagram
MICOM P442/P444 Relay Front view
MICOM P444 Hardware Description
MICOM P444 Hardware Description
MICOM P444 Hardware Description
MICOM P441&P442 Architecture
MICOM P444 Architecture
MICOM P44x Distance protection : Integrated Functions
Distance Protection Algorithms
Distance Protection Algorithms:
Delta Algorithm
Distance Protection Algorithms:
Delta Algorithm
Distance Protection Algorithms:
Conventional Algorithm
Impedance Measurement Algorithms:
R and X Measurements
Impedance Measurement Algorithms:
Gauss-Seidel
Impedance Measurement Algorithms:
R and X Measurements for Phase to Earth Fault
Impedance Measurement Algorithms:
R and X Measurements for Phase to Earth Fault
Impedance Measurement Algorithms:
R and X Measurements for Phase to Earth Fault
Impedance Measurement Algorithms:
R and X Measurements for Phase to Earth Fault
Z1 : Direct impedance
Z1, Z2, Z3, Zp, Z4 Zones limits
R1G, R2G, R3G, RpG Resistance extremity for zones Z1, Z2, Z3, Zp (earth default)
K01, K02, K03, K0p Residual compensation factor for zones Z1, Z2, Z3, Zp
For the bi-phase characteristic, all zones have the same angle : argument of Z1
(direct impedance )
Distance Protection Algorithms:
Full Scheme Distance Protection
Distance Protection Algorithms:
Full Scheme Distance Protection
Z3 = 100% of the hole line length + 120% of the hole next line
tZ3 = 800ms
Zone P - Programmable
directionality. Selectable as a
directional forward or reverse zone.
Zp direction programmable
The copied settings are initially placed in the temporary scratchpad, and will
only be used by the relay following confirmation.
Protection settings
The protection settings include all the following items that become active
once enabled in the configuration column of the relay menu database:
There are four groups of protection settings, with each group containing the
same setting cells. One group of protection settings is selected as the active
group, and is used by the protection elements.
The settings for group 1 is shown. The settings are discussed in the same
order in which they are displayed in the menu.
Line Parameters
These settings are used by the fault locator as the base data for input to the
distance to fault algorithm, and also as the reference for all distance zones
when the Distance set up is preferred in the ‘Simple’ setting mode.
It also accommodates the system phase rotation and defines the single or
three pole tripping mode.
Distance setup
In ‘Simple’ setting mode, ‘Distance Elements’ setting can be viewed, but not
edited here.
Distance elements
Distance elements
Scheme logic (basic and aided scheme logic)
Power systems are operated with such tight stability margins that when a power system
experiences a fault or disturbance, the generator rotors are subject to severe oscillations.
These oscillations in the generator rotor angle translate into severe power flow
oscillations (or power swings) across the system. The occurrence of a power swing
condition on a power system must be detected, and the appropriate protective action
needs to be taken.
For a stable power swing, it is possible that the positive- sequence impedance trajectory
will traverse the operating region of a distance element. In this case, the distance element
needs to be blocked from operating using power swing blocking (PSB); otherwise, an
unwanted operation of a distance element can occur, further weakening an already
weakened system. Therefore, it is important that all power swing conditions be detected
as rapidly as possible to prevent any unwanted operation of the protection system.
The main purpose of the PSB function is to differentiate between power faults and power
swings, and block distance or other relay elements from operations during a power swing.
Out Of Step
Definition
Stability studies determine the locations where it is best to detect the out-of-step
conditions and separate the network into islands. All other locations need to
implement PSB so as not to separate the system at unwanted locations.
OST comes with its own challenges, such as when a trip command should be
issued or if the system can regain stability after experiencing a pole slip.
Power Swing Detection
Stable swing / Out of step
Unblocking for faults during Power Swing
Unblocking for faults during Power Swing
Channel Aided Distance Schemes
Channel Aided Distance Schemes
Channel Aided Distance Schemes
Channel Aided Distance Schemes
Channel Aided Distance Schemes
Channel Aided Distance Schemes
Channel Aided Distance Schemes
Channel Aided Distance Schemes
Zone1 Extended
Switch on to Fault (SOTF)
Switch on to Fault (SOTF)
Trip on Reclose (TOR)
Directional/Non-Directional Overcurrent
Directional/Non-Directional Overcurrent
Directional/Non-Directional Overcurrent
Autoreclose and Check Synchronism
Autoreclose :
Time delayed and high speed auto-reclosing
In addition, the user can selectively decide to auto-reclose for trips from
time-delayed distance zones, overcurrent and earth (ground) elements, and
DEF aided schemes.
The auto-reclose function offers multi-shot auto-reclose control, selectable
to perform up to a four shot cycle.
Dead times (Note 1) for all shots (Note 2) are independently adjustable.
Note 1 - “Dead Time” denotes the open (dead) interval delay of the CB.
Note 2 - A “Shot” is a reclosure attempt
Autoreclose :
Time delayed and high speed auto-reclosing
Should the CB close successfully at the end of the dead time, a “Reclaim
Time” starts.
If the circuit breaker does not trip again, the auto-reclose function resets at
the end of the reclaim time.
If the protection trips again during the reclaim time the relay advances to
the next shot in the programmed cycle, or, if all programmed reclose
attempts have been made, goes to lockout.
Autoreclose :
Auto-reclose logic inputs
The auto-reclose function uses inputs in the logic, which can be assigned and
activated from any of the opto-isolated inputs on the relay via the
programmable scheme logic (PSL).
These logic inputs can also be assigned and activated from other sources.
CB Healthy :
The majority of circuit breakers are only capable of providing one trip-close-
trip cycle. Following this, it is necessary to re-establish sufficient energy in
the circuit breaker before the CB can be reclosed.
BAR :
The “BAR” input will block auto-reclose and cause a lockout if auto-reclose is
in progress. It can be used when protection operation without auto-reclose is
required.
Autoreclose :
Auto-reclose logic inputs
Reset lockout :
The “Reset Lockout” input can be used to reset the auto-reclose function
following lockout and reset any auto-reclose alarms, provided that the
signals which initiated the lockout have been removed.
Pole discrepancy :
CBs with independent mechanisms for each pole normally incorporate a
‘phases not together’ or ‘pole discrepancy’ protection device which
automatically trips all three phases if they are not all in the same position i.e.
all open or all closed.
During single pole auto-reclosing a pole discrepancy condition is deliberately
introduced and the pole discrepancy device must not operate for this
condition. This may be achieved by using a delayed action pole discrepancy
device with a delay longer than the single pole autoreclose dead time, ‘1
Pole Dead Time’. Alternatively, a signal can be given from the relay during the
single pole auto-reclose dead time, “AR 1 Pole In Progress”, to inhibit the
pole discrepancy device.
The “Pole Discrepancy” input is activated by a signal from an external device
indicating that all three poles of the CB are not in the same position.
The “Pole Discrepancy” input forces a 3 pole trip which will cancel any single
pole auto-reclose in progress and start three pole auto-reclose in progress.
Autoreclose :
Auto-reclose logic inputs
External trip:
The “External Trip 3Ph” input and the “External Trip A”, “External Trip B” and
“External Trip C” inputs can be used to initiate three or single phase auto-
reclose.
Note, these signals are not used to trip the CB but do initiate auto-reclose. To
trip the CB directly they could be assigned to the trip contacts of the relay in
the PSL.
The “CB Closed 3 ph”, “CB Closed A ph”, “CB Closed B ph” and “CB Closed C
ph”, signals are used to indicate if a CB is closed three or single phase. These
are driven from the internal pole dead logic and the CB auxiliary inputs.
Check Synchronism
In some situations it is possible for both “bus” and “line” sides of a circuit
breaker to be live when the circuit breaker is open, for example at the ends
of a feeder which has a power source at each end. Therefore, when closing
the circuit breaker, it is normally necessary to check that the network
conditions on both sides are suitable, before giving a CB Close command.
This applies to both manual circuit breaker closing and auto-reclosure.
If a circuit breaker is closed when the line and bus are both live, with a large
phase angle, frequency or magnitude difference between them, the system
could be subjected to an unacceptable shock, resulting in loss of stability,
and possible damage to connected machines.
Line characteristics :
Rd = 0.0613 Ω/km
Xd = 0.295 Ω/km
R0 = 0.184 Ω/km
X0 = 0.885 Ω/km
CT : 600/1A
VT : 132000/100V
Z1 = ZL x 0.8
Z2 = ZL x 1.2