What Is The Substation Automation System (SAS) and What You MUST Know About It
What Is The Substation Automation System (SAS) and What You MUST Know About It
What Is The Substation Automation System (SAS) and What You MUST Know About It
What is the substation automation system (SAS) and what you MUST know about it
1/24
In a few years, the next generation of substations will begin to massively appear in many
countries worldwide. At that time, the station bus will connect the IEDs that are used for
protection, control, and monitoring with the devices that are located at the station level,
and the process bus will connect the bay units with the devices that are located in the
switchyard.
Also, the devices known as condition monitoring and diagnosis systems, which are
designed for the supervision and diagnosis of primary equipment, are going to garner an
increasing amount of consumer interest. With them, traditional maintenance procedures
will transition from the preventive and reactive approaches that are currently used to a
predictive strategy that is more efficient financially.
In conclusion, the utilization of Ethernet network architectures would be expanded
in order to facilitate communication inside substations as well as between those
substations and the control center.
Ok, let’s get into the subject, and that’s the basics of Substation Automation. To begin,
let’s discuss the fundamental concepts that underpin such a system. After that, we’ll
examine the most important tasks that an SAS completes, and the final section will focus
on the primary components of an SAS.
Table of Contents:
The secondary system is the collective name for all of these low-voltage components.
2/24
The secondary system consists of a set of devices that are less visible to the naked eye.
These devices include components and facilities required by the power system operator to
make changes in the power system configuration (such as opening or closing
switchgear), relays to protect power system segments from short-circuits, overloads, and
other potentially hazardous conditions, internal power sources to serve all substation
electricity requirements, and various other components that are used to support the
substations.
The foundation of substation automation systems, also known as SASs, is a large amount
of specialized software that is kept in hardware components that are part of a set of
substation secondary components.
3/24
Figure 1 – Advanced relay control and protection panel used in SASs (photo credit: Kamran Ansari via
Linkedin)
SASs can be built utilizing a straightforward method that makes use of more
contemporary technology by integrating three distinct sets of devices together with two
local area networks.
4/24
The application devices group is comprised of all of the computers and other components
that are necessary to successfully operate control features and interface with both internal
and external subsystems.
5/24
The following are the most significant functions that an SAS performs:
Control Function:
Monitoring Function:
Alarming Function:
Measurement Function:
6/24
Voltage Regulation:
In a nutshell, SASs are responsible for handling the data acquisition process, as well
as the control, monitoring, and alarming functions associated with high voltage
equipment that is primary equipment. In addition, SASs are also responsible for handling
the similar functions that are associated with secondary substation systems.
The operator is presented with control and monitoring information via a graphical
interface that displays overview diagrams, control means, alerts, measurement, trends,
and event sequences on user-friendly screens.
7/24
Figure 3 – Newly installed IED for bay control in a 220 kV substation
8/24
2.1 Control Function
The system operator, using the SAS, opens (or closes) circuit breakers and
disconnectors situated at the substation to make changes in the primary arrangements
essential for power system functioning.
The SAS displays various screens with various features. At least one of them includes a
control dialog box that allows the substation operator to choose whether to open or
close a circuit breaker or disconnector. The switching command is then given as a second
phase.
A previous check synchronization process occurs when the switching command is for the
closing activity of a circuit breaker. This procedure verifies the voltage values on both
sides of the specified circuit breaker, as well as the voltage differential across it and the
phase shift between voltages.
The following requirements must be met before one or more of the following operations
on a circuit breaker can be authorized:
1. Voltage is only present in the substation busbar; that is, the feeder is dead.
9/24
2. Voltage is only present in the feeder; that is, the substation busbar is dead.
3. Voltages are present in both substation busbar and feeder and lie within
permissible ranges for the conditions.
10/24
Figure 6 – Sample 380 kV Bay view
The SAS includes a collection of mimic diagrams that represent different areas of the
substation. These diagrams include color-coded symbols and information regarding the
position of principal equipment and secondary pertinent components. In this substation,
there is a provision for displaying lists of messages and alarms, as well as lists of events
that are happening in the substation and are related to the transmission lines.
The position of the switchgear can be effectively depicted visually by ways such as the
following examples:
11/24
Disconnector in motion: Flashing light, symbol empty or filled out according to
direction of movement.
Disagreement in position information: Steady light, symbol half filled out.
In addition to this, SAS diagrams will typically include all of the data pertaining to the
feeders at each voltage level, such as the following:
1. Voltages
2. Currents
3. Powers
4. Temperatures.
12/24
5. Software procedures
6. Memories capabilities
7. Timing periods
8. Agreement of actual switchgear status and displayed status.
It is recommended that substation events that occur during operation (e.g., changes or
updating of switchgear position, changes in alarm status, circuit breaker trips caused by
protective relays) be displayed on the screen and also available in printed copy
through a printer.
At the very least, event messages must include the following information:
1. Event description
2. Date and time of event
3. Related voltage level
4. Supplementary information.
All occurrences with the potential to significantly impact the substation and associated
transmission lines must be recorded in chronological order on the event list.
In addition to controlling the substation from a local control room and the main control
house and processing the return confirmation signals from the switchgear, the SAS
processes and displays defect signals and other anomalous condition signals that require
acknowledgment.
It also serves as the basis for the substation operator’s decision regarding what
additional action should be taken, and it processes the return confirmation signals from
the switchgear.
13/24
Alarm signals are often classified as major or minor based on their potential influence on
substation operation. An additional device (alarm annunciator) may be added in
addition to the control system screen to show alarm signals.
This component improves alert perception and recognition by the substation operator.
1. Active powers
2. Reactive powers
3. Voltages
4. Currents
14/24
5. Temperatures on power transformers.
In most cases, the values are displayed in measurement dialog windows that are
specifically devoted to each voltage level of the substation.
The operator of the power system can use the facilities provided by SAS to either fix or
alter those reference parameters.
Figure 9 – An example of setting of control and protection relays in a substation (on photo: Micom
P643 Final settings test with Freja 543; full credit: Abdelrahman Fayyad via Linkedin)
15/24
Go back to the Contents Table ↑
Internal electrical loads at substations include things like motors for circuit breakers
and power transformers, lighting circuits, and air conditioning equipment.
These loads require alternating current (AC) power service. In addition to this, DC power
sources are required so that IEDs and other secondary devices can be supplied with
electricity.
In today’s world, the functions for control and monitoring of such systems are wholly
incorporated into the solutions provided by SAS.
In addition, malfunction may occur if the voltage that is applied is lower than the value
that is permitted.
The procedure that ensures that the voltage of the power system remains within the
parameters that have been set is known as voltage regulation. With the use of a
transformer subsystem known as a tap changer, it modifies the number of winding turns
that power transformers include.
The following list includes examples of control instructions and signals that are associated
with such a subsystem and managed by the SAS:
16/24
Further Study – Instructions for making specifications and selecting the main
components of an HV substation
3. SAS Components
3.1 Servers
Speaking using simple words, SAS servers are the secure computers running SCADA
software that talk to IEDs to monitor and operate the power grid. The block diagram for a
transmission SAS is depicted in simplified form in Figure 10.
The main SCADA application software is installed on the database (DB) server. It
interfaces with field IEDs to collect data and deliver control commands. Real-time analog
values, indications, alarms, controls, and set points comprise data.
17/24
This data are shown on the SCADA HMI by the computer. Because the servers are
critical, the optimal setup is to have them redundant inside a master-standby (hot-cold)
arrangement. Furthermore, dependent on the number of voltage levels and IEDs, the
number of redundant sets of database servers can be raised.
The gateway (GW) server is in charge of communicating outside of the substation (for
example, to a master station) in order to supervise the operation of all substations in a
certain geographical area. The gateway server also has the SCADA application database
configured.
The primary function of this machine is to act as a protocol converter between IEC 61850
and numerous other substation protocols and the protocols used in the master station
(primarily IEC 60870-5-101 and IEC 60870-5-104).
The gateway server plays an important role; it is critical that a backup machine be
supplied. Nonetheless, both GW servers are always in contact with the field. The master
station provides redundancy by selecting which gateway server to interact with. In other
words, both gateway servers are set up as master-slave (hot-hot).
18/24
Figure 12 depicts a typical SAS database and gateway server configuration.
Managed ethernet switches are network-switching devices that link all SAS components
to a network and transmit/receive data according to the defined and necessary
functionality. These are multiport devices that can be configured at each port level.
A controlled Ethernet switch has two distinguishing features: VLAN awareness and
support for the Rapid Spanning Tree Protocol (RSTP).
19/24
An IED is a smart device in power system automation that may perform both basic and
advanced activities relating to protection, automation, monitoring, and control.
Any IED in an IEC 61850 context can connect independently with SCADA, which acts as
an intelligent interface for field devices.
Bay control units, protection relays, transformer tap changer control modules, smart
metering devices, and IEC 61850 compliant I/O modules are examples of IEDs used in
transmission substations to integrate outdated devices into the SAS.
20/24
Figure 13 – IEDs – Intelligent Electronic Devices
3.3 Workstations
Grid operators are provided with two main workstations to execute routine maintenance
and undertake operational duties. These are operator and engineering workstation.
The operator workstation machine includes a graphical user interface (GUI) that is
linked to the database servers. The operator workstations (OWS) are not linked to field-
level IEDs; instead, the IEDs rely entirely on the integrity of the database servers for
proper data representation.
21/24
The operator workstation is set up to only communicate with the master database server.
The engineering workstation (EWS) communicates with all substation devices. The EWS
is responsible for configuring or modifying IED configuration parameters and Substation
Configuration Description (SCD) files for all IEDs in the substation. It is not responsible
for any SCADA functions.
This computer must be extremely secure because it has access to any IED in the
substation.
22/24
In SCADA applications, time synchronization is critical for properly analyzing
data acquired via any distributed control system or network. Installing a dedicated
Simple Network Time Protocol (SNTP) server that can obtain proper, precise time via
Global Positioning System (GPS) and Global Navigation Satellite System (GLONASS)
satellites allows for time synchronization.
There are benefits to installing an SNTP server. It lowers the cost of physical layer
implementation and makes use of the same local-area network (LAN) over which IEDs
interact. Inter-Range Instrumentation Group (IRIG)-based protocol is also utilized in
critical applications needing great accuracy.
The SAS used in modern substations is built with the capability to connect with each
remote-control center using either a serial or an Ethernet-based protocol. This gives
the SAS greater flexibility.
To protect the option of using Ethernet-based communication, security gateways that are
up to date with the latest cybersecurity standards are set up according to the
specifications of the customer.
23/24
Watch Video At: https://youtu.be/gj7XgWvXDOw
References:
24/24