FY400/600/700/800/900
FU400/FU48/72/86/96
Operation Manual
Ver 1.0
台灣儀控股份有限公司
TAIWAN INSTRUMENT & CONTROL CO., LTD
Warning
1. Beware of Electric Shock!
2. Once controller is activated, do not touch AC power wiring terminals to avoid electric shock!
3. First to confirm power is OFF, before working on the wiring of controller power supply!
4. Before using this product, please read through this operating manual thoroughly to understand the correct usage based on
the fundamentals of its conten.
5. This product can be used in industrial equipment, working terminal, measurement equipment, but not in life-saving-
related medical equipment.
6. In order to ensure safety even if the temperature controller fails, please set up another alarm system or safety redundancy.
Caution
1. Before the controller transmits power, make sure that the position of the AC power assembly leg is correct. Otherwise,
the controller may be seriously damaged after power transmission is initiated.
2. Before powering on, please confirm whether the power supply voltage is in accordance with the controller's specification
(AC 85~265V or DC 24V.) Otherwise, the controller may be seriously damaged after power transmission is initiated.
3. Check if the wiring is connected to the terminal for the correct terminals (Input, Output.)
4. Please use crimp terminals suitable for M3 screws, as shown below:
3.2mm 3.2mm
5. Do not install the controller in places subject to high-frequency interference, corrosive gases, and high temperature and
humidity (normal working environment: 0 ~ 50°C, 20 ~ 90% RH.)
6. To avoid noise interference, please keep the sensor wiring away from the power cord and the loading power cord.
7. When the thermocouple lead is extended, please use the compensation lead of the corresponding type to this thermocouple.
8. When the RTD lead wire is extended, please use those with lower resistance value. Please use the same wire between the
three Wires.
2. Order Information
Model Output 1 Output 2 Alarm TRS Remote COMM Input type Power Accessories
NFY900(Red/Green light) 1 0 1 0 0 0 0 1 A N
FY901(Blue/White light)
PFY900(Program) See
0 None 0 None 0 None 0 None 0 None 0 None input A AC 85~265V N None
Range
type
FY/FU400 48x48mm 1 Relay 1 Relay 1 1 Set 1 4~20mA 1 4~20mA 3 TTL code D DC 24V T Terminal Cover
NFY600 96x48mm
FY700/FU72 72x72mm 2 Voltage Pulse 2 Voltage Pulse 2 2 Sets 2 0~20mA 2 0~20mA B RS-485 W IP65
FY800/ FU86 48x96mm (SSR Drive) (SSR Drive)
FY900/FU96 96x96mm
3 4~20mA 3 4~20mA 3 3 Sets A 0~5V A 0~5V R Terminal Cover
PFY400 / FU400 48x48mm +IP65
PFY600 96x48mm 4 0~20mA 4 0~20mA B 0~10V B 0~10V
PFY700 / FU72 72x72mm
PFY800 / FU86 48x96mm
A 0~5V A 0~5V C 1~5V C 1~5V
PFY900 / FU96 96x96mm
B 0~10V B 0~10V A HBA D 2~10V D 2~10V
※ Boxed-in items are optional functions, which shall incur extra charges.
Dimension (mm) W48 x H48 x D95 W96 x H48 x D95 W72 x H72 x D95 W48 x H96 x D95 W96 x H96 x D95
weight Appox.120g Appox.170g Appox.150g Appox.170g Appox.230g
Range
Types of input Code
°C °F
K1 01 -50.0~600.0 -58.0~999.9
K
K2 02 -50~1200 -58~2192
J1 03 -50.0~400.0 -58.0~752.0
J
J2 04 -50~1200 -58~2192
R R 05 -50~1760 -58~3200
S S 06 -50~1760 -58~3200
B B 07 -50~1820 -58~3308
Thermalcouple
E E 08 -50~900 -58~1652
N N 09 -50~1300 -58~2372
T1 10 -199.9~400.0 -199.9~752.0
T
T2 11 -199~400 -326~752
W W 12 -50~2320 -58~4208
PL PL 13 -50~1200 -58~2192
L L 14 -50~800 -58~1472
PT1 15 -199.9~850.0 -199.9~999.9
RTD PT100 PT2 16 -199~850 -326~1562
PT3 17 0~850 32~1562
AN1 0~25mV 18
0~50mV 19
0~20mA 20
0~1V 21
AN2
0~2V 22 -1.999~9.999
0~5V 23 -19.99~99.99
Linear 0~10V 24 -199.9~999.9
-1999~9999
AN3 0~70mV 25
4~20mA 26
10~50mV 27
AN4
1~5V 28
2~10V 29
FY400/600/700/800/900
(1)
(4)
(2)
(3)
5.2.2 FY700/FU72
(1)
(2)
(4)
(3)
(1)
(2)
(4)
(3)
8.8.8.8
8.8.8.8 8.8.8.8
8.8.8.8 8.8.8.8
8.8.8.8
8.8.8.8
8.8.8.8
8.8.8.8
8.8.8.8
8.8.8.8
( Green )
Lamp lit when Auto tuning is activated
AT
(Orange)
8.8.8.8 3 LED
AL1
AL2
Lamp lit when Alarm 1 is activated (Red)
Lamp lit when Alarm 2 is activated (Red)
AL3 Lamp lit when Alarm 3 is activated (Red)
Lamp lit when controller in manual mode
MAN
or get error condition (Orange)
When the program is executed, this light
PRO
is on (orange)
OUT1% OUT1% bar-graph indicator(Green)
For parameter call-up and set value
SET
registration
UP Increase numerals
Mounting fixture
Caution
When implementing wiring for the controller power supply, please make sure that the power supply
is turned off to avoid electric shock!
Do not touch the live parts, such as the terminals, while the power is on. Otherwise death or
serious injury may be resulted from short circuit of the contact electrode.
Power supply
AC 85~265V
DC 24V
1 6
T/R (B) 11
Relay
2 COMM 7 B
OUT2
(AL1) SSR T/R (A) 12
mA/V 3 8
13 INPUT
B
Relay 4 AL2 9
OUT1 SSR 14
mA/V
5 10 A
AL1 AL2
1 L 1 or
Alarm-1 2 11 13
Power AC 85~265V DC 24V
Alarm-2
6 N 6 3 12 14
4 4 4 11 T/R (B)
Output-1 Relay SSR mA / V Communication RS-485
5 5 5 12 T/R (A)
2 2 2 11
Output-2 Relay SSR mA / V Transmission mA / V
3 3 3 12
11 G1 11
Remote SV mA / V
12 K1 12
1ϕ Zero cross
13 G2 11
CT CT
14 K2
12
2
7 B 7
3 CLOSE
Motor
valve Input 9 9 B RTD 9 mA / V
4 OPEN TC / mV
10 10 A 10
5 COM
Remote
mA/V INPUT
mA/V
AL2
COMM
B B A RTD
T/R (B) T/R (A)
NC NO COM TC/mV
11 12 13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10
NC NO COM NO NC COM
Relay
Power supply SSR
AC 85~265V AL1 mA/V Relay
DC 24V
OUT2 SSR
(AL3) mA/V
OUT1
1 L 1 14 T/R (B)
Power AC 85~265V DC 24V Communication RS-485
2 N 2 15 T/R (A)
8 NO 12 14
Transmission mA / V mA / V
Output-1 9 NC 9 9 13 15
SSR mA / V
10 COM 10 10
14 14
Remote SV/
mA / V CT
CT Input
6 6 6
15 15
Output-2 Relay SSR mA / V
20 20 A 20
COM
1 T/R (B) 15 8
Power supply
AC 85~265V COMM
DC 24V NO
2 T/R (A) 16 9 AL2
NC
OUT2 3 17 10
Relay (AL1)
SSR
mA/V 4 18 11 B
Relay NO TRS
mA/V
5 19 12
INPUT
OUT1 NC 20 13
6 B
Output-1 6 NC 6 6
SSR mA / V 15 T/R (B)
7 COM 7 7 Communication RS-485
16 T/R (A)
3 3 3
Output-2 Relay SSR mA / V
18
4 4 4 Transmission mA / V
19
15 G1
9 15 18
16 K1
Remote SV mA / V mA / V mA / V
1ϕ Zero cross/
Phase angle 10 16 19
17 G2
15 18
18 K2 CT
CT CT
Input
16 19
3
4 CLOSE
11 B 11
Motor
valve 5 OPEN B
Input 13 13 RTD 13 mA / V
TC / mV
6
14 14 A 14
7 COM
NC
Power supply 1 11
AC 85~265V
DC 24V NO
2 12 AL2
NC COM
3 13
NO
AL1 4 14 T/R (B)
COMM Remote
COM mA/V
5 15 T/R (A)
Relay
6 16
OUT2
SSR
(AL3)
mA/V
7 17 B
Relay NO
8 18
INPUT
OUT1 NC
9
B
19
SSR
mA/V
COM
10 20 A
1 L 1 14 T/R (B)
Power AC 85~265V DC 24V Communication RS-485
2 N 2 15 T/R (A)
8 NO 12 14
Transmission mA / V mA / V
Output-1 9 NC 9 9 13 15
SSR mA / V
10 COM 10 10
14 14
Remote SV/
mA / V CT
CT Input
6 6 6
15 15
Output-2 Relay SSR mA / V
20 20 A 20
NC
Power supply 1 21 T/R (B) 31 11
AC 85~265V
COMM
DC 24V NO
2 22 T/R (A) 32 12 AL2
NC COM
3 23 33 13
NO
AL1 4 24 34 14 T/R (B)
COMM Remote
COM mA/V
5 25 35 15 T/R (A)
6 26 36 16
Relay
OUT2
SSR
(AL3)
mA/V
7 27 37 17 B
Relay NO
8 28 38 18
INPUT
OUT1 NC
9 29 39 19 B
SSR
TRS
mA/V COM
1030 mA/V
40 20
A
1 L 1 6
Power AC 85~265V DC 24V
7 CLOSE
2 N 2
Motor
valve 8 OPEN
8 NO
9
Output-1 9 NC 9 9
10 COM
SSR mA / V
5 COM 13 COM
31 RG1
34 RK2
3ϕ
Zero cross 39
35 TG1
Transmission mA / V
36 TK1 40
37 TG2
14 14
38 TK2
Remote SV/
mA / V CT
CT Input
15 15
31 G1
17 B 17
32 K1
1ϕ Zero
/Phase angle 19 19 19
33 Input B RTD mA / V
G2
TC / mV
34 K2 20 20 A 20
PV
PV Press key and
Press key the lower
3. 4. key to enter the intended
SV display flashes. SV input type.
PV
Modify input type needs to interchange of jumper location,
5. Press key to store new and it needs to recalibration for linear input type change.
SV value of INP1. Please refer to chapter 15. “Input type modification”.
PV PV
When key is pressed,
1. Display after power-on. 2.
the lower display flashes.
SV SV
PV PV
Press key and Press key to store new
3. 4.
key to adjust set value. value of SV.
SV SV
PV PV
Press key until show
1. Display after power-on. 2.
SV “AT”。
SV
PV
PV Press key or key
When key is pressed,
3. 4. to select auto tuning
SV the lower display flashes. SV execution or not.
PV
When auto tuning AT LED lamp lit and start to output,
5. Press key to store new through a few circles to get new PID value with the precise
SV value of AT. control, if finished the AT LED will be lamp off.
PV
PV Press key and
When key is pressed,
3. 4. key to set the intended P1
SV the lower display flashes. SV value.
PV
Press key to store new By the same procedure, use the same ways to set integral
5.
SV value of P1. value(I1) and derivative value(D1).
PV
When key is pressed, PV
Press key until
3. the lower display flashes, 4.
SV upper display. SV P1 = 0.0
PV
PV
Press key to store new Press key until show
5. 6.
SV value. “HYS1”。
SV
PV
PV Press key and
When key is pressed,
7. 8.
SV the lower display flashes. key to set the intended HYS1
SV value.
PV PV
Press key until show When key is pressed,
3. 4.
SV “ALD1”。 SV the lower display flashes
PV PV
Press key until show
1. Display after power-on. 2.
SV “AL1”。
SV
PV
PV Press key and
When key is pressed,
3. 4. key to set the intended AL1
SV the lower display flashes. SV value.
PV
5. Press key to store new value of AL1.
SV
PV PV
1. Display after power-on. 2. Hold 2 seconds.
SV
SV
PV
PV Press key and
When key is pressed,
3. 4. key to set the intended
SV the lower display flashes. SV output% value.
Level 3
(Input Level)
press SET + key 3
seconds
Level 4
press SET + key (SET Level)
3 seconds
※ : If no key is pressed within 60 seconds, it will automatically return to LEVEL 1 (user level) and display PV/SV.
LEVEL
LCK Level_1 Level_2 Level_3 Level_4 Descriptions
USER Level PID Level INPUT Level SET Level
All parameters of Level 1, 2 & 3 are able to be modified
0000 ◎ ◎ ◎ X (Factory default setting)
1111 ◎ ◎ X ◎ All parameters of Level 1, 2 & 4 are able to be modified
0100 ◎ ◎ X X All parameters of Level 1, 2 are able to be modified
0110 ◎ ◎ X X Only parameters of Level 1 and LCK can be modified
0001 ◎ ◎ X X Only SV, LCK can be modified
0101 ◎ ◎ X X Only LCK can be modified
Once jumping to other levels, LCK will be automatically
Other ◎ ◎ ◎ X restored to 0000
Level 1
PV / SV
OUTL
Output percentage
AT
Auto tuning
AL1/SOAK/HBAC
AL1 Alarm1 set value
SOAK Alarm1 soak time
HBAC HBA current setting value
AL2/SOAK/HBAC
AL2 Alarm2 set value
SOAK Alarm2 soak time
HBAC HBA current setting value
AL3/SOAK
RATE/RAMP
AL3 Alarm3 set value
SOAK Alarm3 soak time
RATE Slave SV rate
RAMP SV ramp operation
PV / SV
※ : If no key is pressed within 60 seconds, it will automatically return to LEVEL 1 (user level) and display PV/SV
EX1: When alarm1 is used as HBA function, original AL1 will become HBAC display
EX2: When alarm2 is used as SOAK_B function(ALDX= 19), original AL2 will become SOAK display
EX3: When alarm3 is used as RAMP function, original AL3 will become RAMP display
Level 2
CYT2
P1 HYS2
Main output Hysteresis for
proportional band sub output
I1 GAP1
Main output Control gap
integral time (for main output)
D1 GAP2
Main output Control gap
derivative time (for sub output)
AT.VL LCK
Auto tuning offset value Function or level lock
CYT1 P1
Main output
control cycle
HYS1
Hysteresis for
main output
P2
sub output
proportional band
I2
sub output integral time
D2
sub output
derivative time
CYT2
sub output control cycle
HYS2
※ If no key is pressed within 60 seconds, it will automatically return to LEVEL 1 (user level) and display PV/SV
Level 3
SETA OUD
DP ALT3
Alarm special function setting Control action selection
Decimal point position Alarm3 time setting
PSL OPAD
USPL HYSA
Protocol selection Super SV function enable
Input scale high Hysteresis setting
BITS HZ
LSPL CLO1
Main output Data format Power frequency
Input scale low
zero calibration
IDNO INP1
ANL2 CHO1
sub input Main output Controller station
zero calibration span calibration
BAUD
ANH2 CLO2
sub input sub output Baud rate
span calibration zero calibration
SVOS
ALD1 CHO2
sub output SV bias
Alarm1 mode selection
span calibration
PVOS
ALT1 CLO3
Retransmission PV bias
Alarm1 time setting
zero calibration
UNIT
ALD2 CHO3
※ If no key is pressed within 60 seconds, it will automatically return to LEVEL 1 (user level) and display PV/SV
ANH2 Sub input span calibration (hex display) 0x7FFF 0x0000 0x5FFF SET2.4
Alarm1 mode selection
ALD1 19 0 11 SET3.1
(Please refer to Chapter 12.1 Alarm Mode)
Alarm1 time setting
0.00:Flicker
ALT1 99.59:Continued ON 99.59 0.00 99.59 SET3.2
0.01~99.58:delay time
Time format:min . sec
Alarm2 mode selection
ALD2 19 0 0 SET3.3
(Please refer to Chapter 12.1 Alarm Mode)
Alarm2 time setting
0.00:Flicker
ALT2 99.59:Continued ON 99.59 0.00 99.59 SET3.4
0.01~99.58:delay time
Time format:min . sec
Alarm3 mode selection
ALD3 18 0 0 SET4.1
(Please refer to Chapter 12.1 Alarm Mode)
Alarm3 time setting
0.00:Flicker
ALT3 99.59:Continued ON 99.59 0.00 99.59 SET4.2
0.01~99.58:delay time
Time format:min . sec
PV2 Use for motor valve feedback value --- --- --- SET7.1
Control action selection
OUD 0 : HEAT reverse action COOL HEAT HEAT SET7.2
1 : COOL direct action
Super SV function enable
OPAD 0 : OFF ON OFF ON SET7.3
1 : ON
Power frequency
HZ 0 : 50HZ 50HZ 60HZ 60HZ SET7.4
1 : 60HZ
Level 4
SET1 INP2
Parameters
sub input type selection
Hide/Display
SET2 OUTY
Parameters Hardware drive
Hide/Display selection
SET3 PROG
Parameters Program function
Hide/Display enable
SET4 SET1
Parameters
Hide/Display
SET5
Parameters
Hide/Display
SET6
Parameters
Hide/Display
SET7
Parameters
Hide/Display
SET8
Parameters
Hide/Display
SET9
Parameters
Hide/Display
SET0
Parameters
Hide/Display
INP2
※ If no key is pressed within 60 seconds, it will automatically return to LEVEL 1 (user level) and display PV/SV
SET1 _4 _3 _2 _1
0 Hide OUTL
SET1_1
1 Display OUTL
0 Hide AT
SET1_2
1 Display AT
0 Hide AL1
SET1_3
1 Display AL1
0 Hide AL2
SET1_4
1 Display AL2
0 Hide AL3
SET2_1
1 Display AL3
0 Hide ANL1 ANH1 DP
SET2_2
1 Display ANL1 ANH1 DP
0 Hide LSPL USPL
SET2_3
1 Display LSPL USPL
0 Hide ANL2 ANH2
SET2_4
1 Display ANL2 ANH2
0 Hide ALD1
SET3_1
1 Display ALD1
0 Hide ALT1
SET3_2
1 Display ALT1
0 Hide ALD2
SET3_3
1 Display ALD2
0 Hide ALT2
SET3_4
1 Display ALT2
0 Hide ALD3
SET4_1
1 Display ALD3
0 Hide ALT3
SET4_2
1 Display ALT3
0 Hide HYSA
SET4_3
1 Display HYSA
0 Hide CLO1 CHO1
SET4_4
1 Display CLO1 CHO1
0 Hide SVOS
SET6_1
1 Display SVOS
0 Hide PVOS
SET6_2
1 Display PVOS
0 Hide UNIT
SET6_3
1 Display UNIT
0 Hide PVFT
SET6_4
1 Display PVFT
0 Hide PV2
SET7_1
1 Display PV2
0 Hide OUD
SET7_2
1 Display OUD
0 Hide OPAD
SET7_3
1 Display OPAD
0 Hide HZ
SET7_4
1 Display HZ
0 reserve
SET9_1
1 reserve
SET9_2 0 Program Timer Unit = “Hour : Minute”
1 Program Timer Unit = “Minute : Second”
0 Disable transmission SV
SET9_3
1 Enable transmission SV
0 Disable transmission PV
SET9_4
1 Enable transmission PV
Any Level
Press key
3 seconds
BITS
RHTC/RUCY IDNO
RHTC Dehumidification temperature
RUCY Motor valve operating time Controller station
RHPO/WAIT BAUD
RHPO Dehumidification manipulated value
WAIT Program execution standby temperature Baud rate
CYT1 RHTC/RUCY
Main output control cycle
HYS1
Hysteresis for main output
PV2
remote function or motor valve
feedback value
CLO1
Main output zero calibration
CHO1
Main output span calibration
PSL
Protocol selection
BITS
Data format
IDNO
11.1 PV bias
Description
The FY series controller offers PV bias for input calibration, PV bias functions correct
the deviation of each sensor, as well as PV difference between controllers.
Function Diagram
PV bias
Temperature
200°
C
198°
C
Controller PV
Sensor PV
PVOS=+2°
C
2°
C
0°
C time
Parameter
Range Hide/
Parameter Symbol Content Default Level
MAX MIN Display
PV bias
PVOS 100.0 -100.0 0 Level 3 SET6.2
PV = PV + PVOS
Examples
PV bias (PV.OS) adds bias to the Measured value(PV):
When two controllers measure the temperature of the same type of load, the measured values of the respective characteristics
of the sensors are displayed as
Controller A : 200°C Controller B : 195°C
As shown above, Controller B is compensated by PV offset (PV.OS) The PV.OS parameter value must be corrected by +5°C.
The display value will be changed to 200°C, Same as Controller A, but Controller B will show 5°C at 0°C.
Parameter setting
Level Parameter Set value Description
4 SET6.2 1 Display PVOS
3 PVOS 5 PV adds +5°C
Function Diagram
PV
100.0
Sensor input
SV
200.0 Retransmission output
OUT1 OUT2 ATAL1 A L2 AL3M AN PRO
OUT1 %
0 20 40 60 80 100
SET A/M
Electric
furnace TAIE FY900
12.00
Sensor
mA
ammeter
Parameter
Range Hide/
Parameter Symbol Content Default Level
MAX M IN Display
0 : Retransmission SV disable
SET9.3 1 0 0 Level 4 ---
1 : Retransmission SV enable
0 : Retransmission PV disable
SET9.4 1 0 0 Level 4 ---
1 : Retransmission PV enable
Examples
Assume the input range (LSPL & USPL) = -50.0~600.0 retransmit PV
When the PV value is between -50.0 and 600.0, the retransmission signal is based on the PV value,
and the linear output analog signal is presented.
When the PV is less than -50.0, the retransmission signal remains at 4mA
When the PV value is greater than 600.0, the retransmission signal remains at 20mA
Parameter setting
Level Parameter Set value Description
3 SET9.4 1 Retransmission PV
Retransmission signal low point calibration value
3 CLO3 3133 (each controller calibrate value is different)
Retransmission signal high point calibration value
3 CHO3 3508
(each controller calibrate value is different)
mA
20
Measured
value(PV)
4
Scaling value
0
50.0(LSPL) 200.0(USPL)
Notes
1. To order TRS function, please confirm the type of retransmission output signal and retransmit signal range.
2. The user can select the source to be transmitted according to the parameter SET9.4 or SET9.3. The factory default is
to retransmit the PV.
3. Modify the parameter INP1/UNIT will reset the retransmission range.
4. CLO3 & CHO3 are the calibration parameters of the re-transmission signal. It has been calibrated before leaving the factory.
Do not change this parameter value.
5. The user only needs to set SET9.4 or SET9.3, the rest of the parameters will be set & calibrated at the factory.
Function Diagram
PV 50.0
SV 100.0
OUT1 OUT2 AT AL1 AL2 AL3 MAN PRO
SET A/M
TAIE FY900
Electric
Control
output 20.00 mA
furnace
PLC AO module / transmitter
+ -
SSR
Power
Parameter
Range Hide/
Parameter Symbol Content Default Level
MAX M IN Display
0 : Remote SV disable
SET0.3 1 0 0 Level 4 ---
1 : Remote SV enable
Sub input type selection
0 : none
1 : 10~50mV / 4~20mA / 1~5V /
2~10V (remote SV use)
INP2 2 : 0~50mV / 0~20mA / 0~5V / 4 0 0 Level 4 ---
0~10V (remote SV use)
3 : valve feedback
4 : CT input
Examples
Input signal is K1 and its range is -50.0~600.0. When an external analog signal is input to the Remote
SV terminal, the signal will be based on the range presents linear display of SV parameters
When the signal input value is less than 4mA, the PV position shows nnn2, indicating that the signal of Remote SV is lower than
the lower limit value
When the signal input value is greater than 20mA, the PV position shows uuu2, indicating that the signal of Remote SV is higher
than the upper limit value
sca le
600.0
SV
-50.0
mA
4 20
Parameter setting
Level Parameter Set value Description
4 SET0.3 1 Enable Remote SV function
4 INP2 1 Remote SV signal=4~20mA
Remote SV signal low point calibration value
3 ANL2 744 (each controller calibrate value is different)
Remote SV signal high point calibration value
3 ANH2 0x657C (each controller calibrate value is different)
Notes
1. To order Remote SV function, please confirm signal type and Remote SV input range first.
2. Modify the parameter INP1 & UNIT will reset the input range
3. The ANL2 and ANH2 are the calibration parameters of Remote SV. It has been calibrated before
leaving the factory. Please do not change this parameter.
Function Diagram
PV
KBA(
SV 10.0
Sensor input
OUT1 OUT2 ATAL1 AL2AL3 MANPRO
OUT1 %
HBA alarm 0 20 40 60 80100
SET A/M
TAIE FY900
Control output
CT
+ -
SSR
SC 80-T
Heater
se
AC power nsor
Electric furnace
Parameter
Range Hide/
Parameter Symbol Content Default Level
MAX MIN Display
HBA current setting value
INP2=4
*HBAC Upper : heater current display 100.0 0.0 1.0 Level 1
Down : current setting value
&
ALD1=9
unit : ampere(A)
* when ALD1=9,original AL1 become HBAC display
Examples
Heating system with SSR as control element, set HBAC=1.0(down area)
1. The heater current display value HBAC = 0.0(upper area), when a heater disconnection occurs
The heater current is less than the set value of HBAC=1.0. At this point, the operating condition 1 is satisfied.
2. The heater no longer heats when the heater disconnection occurs, and the gap between the PV and SV will become
larger and larger.
The manipulated value of OUT1 is also getting larger and larger, and eventually exceeds 90%. At this point, action condition
2 is satisfied.
3. The AL1 alarm will be activated when both 1 & 2 conditions are met and continue for more than 20 seconds.
Parameter setting
Level Parameter Set value Description
1 HBAC 1.0 HBA Action Current Set Value (Unit: A)
4 INP2 4 CT current input
3 ALD1 9 HBA Alarm
Current low-point calibration value
3 ANL2 -12 (each controller calibrate value is different)
Current High-point calibration value
3 ANH2 0x4527 (each controller calibrate value is different)
1. ANL2 & ANH2 is the current signal calibration parameters. It has been calibrated before leaving the factory.
Do not change this parameter value.
2. The user only needs to set HBAC, the rest of the parameters will be set & calibrated at the factory.
3. CT has two specifications: SC 80-T & SC 100-T. Please check heater wire diameter and specify required CT.
CT Specifications
Item Specifications
Model number SC 80-T SC 100-T
Max. continuous current 80A 100A
Accuracy 3% 5%
Aperture 5.9mm 12.6mm
Dieiectric Withstanding Voltage(Hi-pot) 2500Vrms / 1 minute 4000Vrms / 1 minute
Vibration resistance 50 HZ, 98 m/s 2
Weight Approx. 12 g Approx. 30 g
Dimensions (UNIT:mm)
SC 80-T
SC 100-T
Function Diagram
scale(%)
100.0 COUT
15.0
RHPO
temperature
RHTC
Parameter
Range Hide/
Parameter Symbol Content Default Level
MAX M IN Display
Dehumidification temperature
If PV less than RHTC manipulated
*RHTC value = RHPO 200.0 0.0 0.5 Level 3 SET5.3
(Please refer to Chapter 11.5)
Dehumidification manipulated value
0 : OFF disable dehumidification
function
*RHPO Other values : 0.1~100.0 100.0 OFF OFF Level 3 SET5.3
manipulated value
(Please refer to Chapter 11.5)
* This parameter is multi-display, wnen OUTY≠3 display RHTC
* This parameter is multi-display, wnen PROG=OFF display RHPO
Example
After the controller is turned on, when the PV does not reach 50°C, output will be 20% of the operation time. When the time
exceeds 15 minutes or the PV is greater than 50°C, the controller will produce output of normal PID gain.
Parameter setting
Level Parameter Set value Description
4 SET5.3 1 Display parameter RHTC、RHPO
1 SV 100.0 Target temperature
Execute de-humidifying function when PV is
3 RHTC 50.0 lower than this temperature
20% operation output when executing
3 RHPO 20.0 de-humidifying function
Function Diagram
Motor valve
FY600/800/900
COM Controller
R
RC RC
CLOSE
CLOSE
7 6
OPEN
no
8 9
feedback
(NFMV) OPEN 10
COM
FY600/800/900
Motor valve
Controller
CLOSE
14 CLOSE
COM
1KΩ 15 WIPER signal feedback
OPEN
16 OPEN
COM
R
RC RC
CLOSE
CLOSE
7 6
feedback
(FBMV) OPEN
8 9
OPEN 10
COM
※ It is recommended to install spark killer at the relay junction to prolong the service life of the relay.
Spark killer connection
spark killer
Motor valve
COM FY600/800/900
Controller
CLOSE
CLOSE
7 6
AC spark killer
OPEN OPEN
8 9
10
COM
Parameter
Range Hide/
Parameter Symbol Content Default Level
MAX M IN Display
ALD1=10
SOAK Alarm1 soak time
99.59 0.00 0.10 Level 1 or
(AL1) Time format : hr.min ALD1=19
ALD2=10
SOAK Alarm2 soak time
99.59 0.00 0.10 Level 1 or
(AL2) Time format : hr.min ALD2=19
SOAK Alarm3 soak time
99.59 0.00 0.10 Level 1 ALD3=10
(AL3) Time format : hr.min
The rate of change during SV ramp
RAMP
operation 99.99 -19.99 99.99 Level 1 ALD3=9
(AL3)
format : °C / minute
※ when ALD1=10 or 19, original AL1 become SOAK display
when ALD2=10 or 19, original AL2 become SOAK display
when ALD3=10, original AL3 become SOAK display when
ALD3=9, original AL3 become RAMP display
Boot completed, the alarm1 is ON, when PV≥SV start the timer,
10
(SOAK_A ) alarm and control function are turned OFF in timed out.
(In this mode, the time format is fixed to “hour.minute”)
ALDX
Boot completed, the alarm is ON, when PV≥SV start the timer,
19 alarm is turned ON and the control function keep ON in timed
(SOAK_B ) out.
(In this mode, the time format is fixed to “hour.minute”)
X:1 / 2(SOAK function available in alarm1 or alarm2)
Parameter setting
Level Parameter Set value Description
1 SV 100.0 Target temperature
4 SET2.1 1 Display AL3
4 SET4.1 1 Display ALD3
3 ALD1 10 AL1 as soak alarm
3 ALD3 9 Enable RAMP function
1 SOAK(AL1) 0.10 10 minute temperature maintain
1 RAMP(AL3) 5.00 5.00°C rise per minute
Temperature
Time up
Alarm=OFF
PV
100.0
ramp start
alarm=ON
25.0
ON
AL1 time chart time
OFF
Parameter setting
Level Parameter Set value Description
1 SV 100.0 Target temperature
4 SET2.1 1 Display AL3
4 SET4.1 1 Display ALD3
3 ALD1 19 AL1 as soak alarm
3 ALD3 9 Enable RAMP function
1 SOAK(AL1) 0.10 10 minute temperature maintain
1 RAMP(AL3) 5.00 5.00°C rise per minute
Temperature
Time up
Alarm=ON
PV
100.0
PV follows SV up 5°C
per minute
ramp start
alarm=ON
25.0
Action
ON
time
AL1 time chart OFF
Parameter setting
Level Parameter Set value Description
1 SV 100.0 Target temperature
3 ALD1 10 AL1 as soak alarm
1 SOAK(AL1) 00.10 10 minute temperature maintain
Temperature
Time up
Alarm=OFF
PV
100.0
Temperature rise
Alarm=ON
25.0
Action
ON
Parameter setting
Level Parameter Set value Description
1 SV 100.0 Target temperature
3 ALD1 10 AL1 as soak alarm
1 SOAK(AL1) 00.10 10 minute temperature maintain
Temperature
Time up
Alarm=ON
PV
100.0
Temperature rise
Alarm=OFF
25.0
Action
ON
Function Diagram
PV
100.0 Alarm 1
SV
200.0
OUT1 OUT2AT AL1 AL2 AL3MAN PRO
OUT1 %
0 20 40 60 80 100
Alarm 2
SET A/M
TAIE FY900
Alarm 3
Parameter setting
Range Hide/
Parameter Symbol Content Default Level
MAX M IN Display
HYSA Hysteresis setting for alarm1~3 100.0 -100.0 1.0 Level 3 SET4.3
Alarm special function setting
SETA 1111 0000 0000 Level 3 SET5.3
(Please refer to Chapter 12.2)
0 No alarm function Not drive any alarm relays and the corresponding LED lamp.
HYSX ON
OFF
Deviation high SV ALX
1
(With hold action)
PV ≥ (SV+ALX) → Alarm ON
Formula
PV ≤ (SV+ALX-HYSA) → Alarm OFF
ON HYSX
OFF
Deviation low ALX SV
2
(With hold action) * ALX must to be set to a negative value
PV ≤ (SV+ALX) → Alarm ON
Formula
PV ≥ (SV+ALX+HYSA) → Alarm OFF
ON
OFF OFF
ALX SV ALX
Band
4
(With hold action) PV ≤ (SV+ALX) → Alarm ON
PV > (SV-ALX) → Alarm ON
Formula PV ≥ (SV+ALX) → Alarm OFF
PV < (SV-ALX) → Alarm OFF
HYSX ON
PV ≥ ALX→ Alarm ON
Formula
PV ≤ (ALX-HYSA) → Alarm OFF
ON HYSX
PV ≤ ALX→ Alarm ON
Formula
PV ≥ (ALX+HYSA) → Alarm OFF
Activated conditions:
1. Heater current is less the HBAC set value
2. OUT1 manipulated value exceed 90%
HBA
3. Conditions of 1 & 2 above are established and continue to
(Heater Break Alarm) exceed 20 seconds.
9 * Please refer to Chapter 11.4
HYSX ON
OFF
11 Deviation high SV ALX
PV ≥ (SV+ALX) → Alarm ON
Formula
PV ≤ (SV+ALX-HYSA) → Alarm OFF
ON HYSX
OFF
ALX SV
12 Deviation low
* ALX must to be set to a negative value
PV ≤ (SV+ALX) → Alarm ON
Formula
PV ≥ (SV+ALX+HYSA ) → Alarm OFF
ALX SV ALX
13 Deviation high/low
PV ≥ (SV+ALX) → Alarm ON
PV ≤ (SV-ALX) → Alarm ON
Formula PV ≥ (SV-ALX+HYSA) → Alarm OFF
PV ≤ (SV+ALX-HYSA) → Alarm OFF
ON
OFF OFF
ALX SV ALX
14 Band
PV ≤ (SV+ALX) → Alarm ON
PV > (SV-ALX) → Alarm ON
Formula PV ≥ (SV+ALX) → Alarm OFF
PV < (SV-ALX) → Alarm OFF
HYSX ON
OFF
15 Process high ALX
PV ≥ ALX→ Alarm ON
Formula
PV ≤ (ALXH-HYSA) → Alarm OFF
ON HYSX
OFF
16 Process low ALX
PV ≤ ALX→ Alarm ON
Formula
PV ≥ (ALX+HYSA) → Alarm OFF
temperature temperature
PV PV
time time
Program No.18
Up to 18 programs
SV
Program No.2
SV
time
第一段 0(起
Program No.1 點)
SV
Soak
Ramp(up)
time
Segment 1 (starting point)
Operation started in Program SV mode
Program
Initial Setting
Program execute
start address
Level 1
.
PV / SV
PTN group setting
. Press SET Key
1 2 3 18
1 1 1 1
MAX Segment =8
TIMR TIMR TIMR TIMR
OUT1 O U T1 O U T1 O U T1
OUT2 O U T2 O U T2 O U T2
. . . .
. . . .
. . . .
SV-8 SV-8 SV-8 SV-8
OUT8 O U T8 O U T8 O U T8
START
Set PTN
Set
SV_n
Set
TM_n
Set
OUTn
Return
PV/SV
END ※ n : 1~8
TM setting explain:
In segment_5(SEG_5) setting TM =END When the program finishes segment_4(SEG_4), program end and display “END”
message, can’t enter next segment.
In segment_5(SEG_5) setting TM =0.00 When the program finishes segment_4(SEG_4), enter next segment, SV
change suddenly.
In segment_5(SEG_5) setting TM =10.00 When the program finishes segment_4(SEG_4), enter next segment
and executing TM_5 setting value.
In segment_5(SEG_5) setting TM =99.59 When the program finishes segment_4(SEG_4) , enter next segment and executing
continuously.
The program can be up to 18 patterns. If you connect all the patterns, up to 144 segments.
Measured value(PV)
SEG_3
SEG_4
250ºC
SEG_2
200ºC
SEG_5
SEG_1
SEG_6 SEG_7
80ºC
Initial setting
SET9.2 = 1 SET8.3 = 0 SET8.1 = 0 SET8.2 = 1 WAIT = 0.5
Program edit
Segment_1 Segment_2 Segment_3 Segment_4 Segment_5 Segment_6 Segment_7
PTN = 1 PTN = 1 PTN = 1 PTN = 1 PTN = 1 PTN = 1 PTN = 1
SV_1 = 200 SV_2 = 200 SV_3 = 250 SV_4 = 250 SV_5 = 80 SV_6 = 80 SV_7 = 0
TM_1 = 60.00 TM_2 = 30.00 TM_3 = 0.00 TM_4 = 30.00 TM_5 = 40.00 TM_6 = 45.00 TM_7 = END
OUT1 = 100.0 OUT2 = 100.0 OUT3 = 100.0 OUT4 = 100.0 OUT5 = 100.0 OUT6 = 100.0 OUT7 = 0.0
Coil
OJE-SS-124LMH
250VAC, 8A Parameter set as “CYT1 =10”
Coil
JQ1P-24V-F
COM Parameter set as “CYT1 =10”
250VAC
N.C.
N.O.
Pb
Parameter set as “CYT1 =1”
P-VT
Start
CLO1=0
Default Value
CHO1=3600
Set controller
SV=LSPL low setpoint
output%=0%
Set controller
SV=USPL high setpoint
output%=100%
NO
OK?
YES
End
Enter to Level 2
PV / SV monitor
show P1
Start
ANL1 = 0
ANH1 = 5FFF
INP1 = K1 at Input level (level 3)
USPL = 600.0
LSPL = -50.0
NO
OK ?
YES
NO
OK ?
YES
End
Start
ANL1 = 0
ANH1 = 5FFF
INP1 = PT1 at Input level (level 3)
USPL = 850.0
LSPL = -199.9
NO
OK ?
YES
NO
OK ?
YES
End
Start
ANL1 = 0
ANH1 = 5FFF
DP = 0000 at Input level (level 3)
INP1 = AN4
USPL = 5000
LSPL = 0
NO
OK ?
YES
NO
OK ?
YES
End
Enter to Level 2
PV/SV monitor show P1
PV PV PV
press key switching to
press key 3 seconds
display"LCK "
SV SV SV
SET2_2= 1
open ANL1、ANH1、DP
if SET2_2 setting finish
PV
press + key 3 seconds , return to PV/SV monitor
SV XX X
※ X is the default value which doest not require modification
Enter to Level 3
PV/SV monitor
show INP1
PV
PV press + key 3 seconds press key switching to PV
display"ANL1 "
SV SV SV
Enter to Level 3
PV/SV monitor
show INP1
PV
PV press + key 3 seconds press key switching to PV
display"ANH1 "
SV SV SV
S R
Fast Fuse
Controller
K2
G2 SCR
Module G1
G1
K1
K1
G2
K2
U V
Load
Time Chart:
ON OFF
S R
Controller
Fast Fuse
T2 (G2)
G1
TRIAC
Module
K1
G (G1)
G2
T1
K2
U V
Load
R S T
TG1
U V W
TK1
TG2
TK2
Time Chart:
OFF
ON
R S T
Controller
RK1
T2 (RG2) T2 (TG2)
RG2
G (RG1) G (TG1)
RK2
T1 T1
TG1
U V W TK1
TG2
TK2
S R
Fast Fuse
Controller
K2
G2 SCR
Module G1
G1
K1
K1
G2
U V K2
負載
S R
Controller
Fast Fuse
T2 (G2)
G1
TRIAC
Module
K1
G (G1)
G2
T1 (K1)
K2
U V
Load
INLE Input1 Error Check whether input loop is opened or wiring is incorrect.
UUU1 PV is above USPL Check whether the input value or input type is correct or not.
NNN1 PV is below LSPL Check whether the input value or input type is correct or not.
Ambient temperature over
CJOR Decrease ambient temperature
range(>50°C)
AUTF Auto-tunning failure Manually set the PID value
LED Display
Characters 0 1 2 3 4 5 6 7 8 9
LED Display
Characters A B C D E F G H I J
LED Display
Characters K L M N O P Q R S T
LED Display
Characters U V W Y Z °C °F