Trip Simple Alarm Simple Name No
Trip Simple Alarm Simple Name No
Trip Simple Alarm Simple Name No
L26FD
35 LDO Temperature Pump 100 C0 (Change To Second Pump)
PTL2H
L26FU
36 LDO Low pressure L63FL 2.41 bar
37 LDO – Filter (HP) Pressure Differential L63LF1H 1.3 bar
38 LDO – Filter (LP) Pressure Differential L63LF2H 1.5 bar
39 Forwarding LDO Low pressure L63FD1L 6 bar (Transfer To Second Pump)
40 Forwarding (HFO) Low Pressure L63FU1L 4.7 bar Transfer To Second Pump
41 Filter Skid (HFO) Low Pressure L63FU-2 3 bar
42 Filter Skid (HFO) High Pressure L63FU-3 6 bar
L26FU2L L26FU2H
LDO (100 CO – 120 CO) LDO
44 Temperature Heavy Operation
L26FU1L L26FU1H
45 Crude Oil Filter (LP - HFO) L63LF3H 1.5 bar