Sewer Siphon Assessment and Air Jumper Design: WEFTEC®.06
Sewer Siphon Assessment and Air Jumper Design: WEFTEC®.06
Sewer Siphon Assessment and Air Jumper Design: WEFTEC®.06
06
Steve Deering, P.E.* Steve Jepsen,* Alberto Acevedo, P.E.** Mandy Taylor, P.E.**
ABSTRACT
In response to customer complaints about sewer odor, Orange County Sanitation District
(OCSD), California launched a project to investigate the ventilation requirements of existing
sewer siphons, to verify adequacy of existing air jumper operation, and determine the need for
new air jumpers or additional air jumper capacity. The challenge was assessing sewer siphon air
jumper adequacy without clear industry standards or guidance for comparison and to then
develop air jumper sizing guidelines and recommendations for retrofit replacement or addition of
air jumpers at 17 of the existing 87 OCSD sewer siphon locations.
A literature search for sewer siphon air jumper sizing guidance was conducted. For each of the
17 sewer siphons studied: siphon inlet and outlet structures were inspected; sewer flow was
measured; headspace air pressure or vacuum was measured; air flow into or out of the upstream
and downstream siphon structures was measured; and dissolved and headspace hydrogen sulfide
levels were measured. Relationships were theorized and developed between: depth of wastewater
flow in the sewers; velocity of wastewater flow; sewer headspace airflow rates; and sewer
headspace pressure or vacuum with manhole covers in place. General design guidelines for
sewer siphon air jumpers were developed and recommended and these guidelines were applied to
the field data for each of the studied 17 siphons. Sewer siphon air jumper retrofit replacement or
additions are currently in the final design phase with construction scheduled to start in February
2007.
KEYWORDS
Sewer, wastewater, inverted siphon, air jumper, vent, headspace, drag, d/D, depth/diameter,
hydrogen, sulfide, H2S, reduction factor, odor control, vacuum, pressure, water column,
depressed sewer
BACKGROUND
The Orange County Sanitation District consists of a service area of 471 square miles, including
21 city and three special district member agencies. The regional transmission system owned and
3630
WEFTEC®.06
maintained by OCSD includes 475 miles of interceptor and trunk sewer lines. The local
collection sewers are owned and maintained by the member agencies.
The OCSD system also includes 17 pump stations and two regional wastewater treatment plants
treating a total average daily flow of 243 million gallons per day (mgd).
The regional OCSD sewer transmission system includes 87 sewer siphons. These inverted sewer
siphons range in size from 15 to 60 inches in diameter and typically cross under large storm
drain box culverts within heavily congested, multi-lane boulevard intersections in Orange
County, California.
OCSD is very sensitive to odor complaints from the public. It is OCSD’s goal to eliminate all
sources of OCSD sewer system related odor complaints. OCSD has maintained a Geographical
Information System (GIS) tracking of the location of all odor complaints. It was determined that
there are a number of odor complaint “hotspots” in the vicinity of many of the siphons, despite a
very pro-active siphon cleaning and maintenance program. OCSD prioritized the odor complaint
hotspots in the vicinity of siphons and then moved forward with this project to investigate the
adequacy of air jumpers for the siphons with the most odor complaints. The need for air jumpers
and how to adequately size the air jumpers for each of these odor hotspot locations is the subject
of this paper.
In the past, the OCSD’s primary method of sewer siphon odor control has been to provide a
“siphon vent” or “air jumper” and to seal manholes in the vicinity of sewer siphons. Of the 17
siphons reviewed in this project, six siphons do not have an air jumper, due possibly to oversight
or to physical limitations accepted in the original project designs. It was suspected, and
confirmed, that for most of the siphons possessing air jumpers, the existing air jumpers were not
adequately sized to avoid upstream sewer headspace pressurization and release of malodorous
air. This is partially evidenced by the chronic odor complaints for these siphon areas. The
escaping airflow rate, intensity of odor, and location of escape are transitory and very difficult to
determine or control. This often results in a public nuisance in the form of unpleasant odors.
Currently, OCSD utilizes odor control mitigation through sealing upstream and downstream
manholes near the siphons, which drives the release of malodorous air to some other typically
unknown location.
Figure 1 shows a typical OCSD sewer siphon, “Siphon 70.” This particular siphon has a 27-inch
diameter open channel flow gravity sewer approaching the sewer siphon inlet box on the right-
hand side of Figure 1. The space between the water surface in the approach or exit sewer and the
top of the pipe (crown) is defined herein as “headspace” or “headspace air.”
3631
WEFTEC®.06
Figure 1
Typical OCSD Sewer Siphon
As is typical for the sewer siphons in OCSD, a “depressed sewer”, “inverted siphon”, or
“siphon”, equal in diameter, or slightly smaller, to the inlet sewer, is then routed down and under
the intervening obstacle, which is a triple box culvert storm drain in this case. The siphon then
rises to the siphon outlet box at the left-hand side of Figure 1. The siphon runs full between the
siphon inlet and outlet boxes and returns to open channel flow as it continues downstream from
the siphon outlet structure.
The headspace air at the studied siphon locations has hydrogen sulfide concentrations in the
range from 10 to 600 parts per million (ppm) and as a result is quite odorous. The headspace air
typically flows downstream in the same direction as the wastewater, until it reaches a headspace
obstruction, such as siphon. Headspace air cannot pass through a siphon because the hydraulic
grade line is higher than the siphon pipe causing the siphon to flow full and thereby not allowing
the passage of the headspace air.
As a result of the headspace blockage, the upstream sewer headspace air will pressurize
sufficiently to cause an upstream release of odorous headspace air through the path of least
resistance. Odorous air outlets may include pick holes in manhole covers, plumbing vents in
houses and businesses, and compromised sewer joints. It is this discharge of odorous air to which
the public objects.
If all headspace obstructions could be removed, then ultimately in the OCSD system the
headspace air would be transported to mechanically ventilated headworks areas at one of the
OCSD pump stations or at the two regional wastewater treatment plants, where the air would
pass through odor scrubbers before release.
Typically, the headspace air of the downstream siphon outlet structure is under a slight vacuum
caused by movement of headspace air away from the outlet box.
In the case of Figure 1, there is an existing 8-inch diameter air jumper connecting the siphon inlet
and outlet boxes well above the hydraulic grade line of the inlet and outlet gravity sewers. As a
result of the field observations and air jumper design guidelines established in this project, the
existing 8-inch diameter siphon air jumper shown in Figure 1 will be removed and replaced with
a new larger 24-inch diameter air jumper.
3632
WEFTEC®.06
PROJECT APPROACH
OCSD developed a project approach for evaluation of the existing sewer system, siphons, and
siphon air jumpers to determine retrofit requirements necessary to prevent sewer headspace
pressurization and odorous sewer headspace off-gassing. The project steps taken in this process
included:
Upon OCSD acceptance of the Preliminary Design Report and Engineer’s estimate of
construction cost, the project moved into final design with site specific air jumper sizing and
routing.
Office evaluation of the as-built construction drawings and field data for each of the 17 subject
inverted sewer siphons was conducted together with Geographic Information System (GIS)
based aerial photographs and wastewater collection system characteristics.
Air Jumper Design. An extensive literature search for sewer siphon air jumper design was
conducted. There was very little information available regarding sewer siphon design, and even
less available regarding siphon air jumper design. Although the importance of maintaining sewer
ventilation was followed back to medieval times in London, only a couple references were found
recommending a method of air jumper sizing. Those recommendations were based on “rules of
thumb” and empirical criteria not dependent on or adjusted to site specific conditions.
Based on the research and practical experience, there is a net movement of sewer atmosphere
along the headspace of a sewer. The quantity and velocity of the air flow, which determines the
magnitude of required ventilation, is controlled by several factors, including: liquid drag;
barometric pressure differences; temperature differential between sewer headspace and ambient
outdoor temperature; wind eduction; and rise and fall of wastewater with diurnal flow pattern. Of
these factors, liquid drag has been found to be the only consistent and dominant cause of air flow
in sewers under conditions similar to those found at OCSD. Liquid drag causes a movement of
the air in the headspace of the sewer in the same direction as the wastewater flow.
The most applicable literature regarding the dynamics of sewer atmosphere was found in
references by Richard Corsi, et al, discussing the transport of volatile organic compounds
(VOCs) in sewers. The references reported the concept of a Reduction Factor (RF), which is the
measured ratio of the headspace airflow rate to wastewater flow rate ranging from near zero up
to 0.8 at the air/water interface. The conclusions and points of note in the Corsi reference are as
follows:
3633
WEFTEC®.06
1. It was concluded that no single mechanism controls sewer ventilation under all situations,
but environmental conditions, wastewater flow conditions, and physical characteristics of
a collection system were identified as some mechanisms that contribute and control to
varying degrees depending on in situ conditions at the time.
2. Given the complexity of most collection systems it is impossible to accurately calculate
actual ventilation rates and gas flow patterns for any given system. For a specific sewer
reach, release of an inert tracer can be used to estimate gas flow rates.
3. Liquid drag causes gas flow in the same direction as wastewater flow, and is the only
ventilation mechanism that acts continuously.
4. Under conditions of low resistance to ambient air inflow and sewer gas exhaust, liquid
drag can induce maximum gas mean velocities of up to 0.2 meters per second (m/s) (0.2
m/s = 0.66 feet per second (fps)). Actual velocities in sanitary sewers are expected to be
on the order of:
a. 0.04 to 0.2 m/s (0.13 to 0.66 fps) for small pipes up to 0.25 m diameter (10-inch
diameter);
b. 0.003 to 0.20 m/s (0.010 to 0.66 fps) for mid-sized pipes up to 1.0 m diameter
(39-inches); and
c. 0.005 to 0.18 m/s (0.016 to 0.59 fps) for large pipes up to 2.5 m diameter (98-
inches).
In comparison to Corsi, the headspace air velocity measured for OCSD ranged between 0.11 fps
to 2.3 fps with an average field result of 0.55 fps for OCSD over 30 flow rate data points
converted to headspace air velocity for the depth of flow at the time of the measurement.
For purposes of the OCSD air jumper sizing calculations, it was decided to evaluate field
measured wastewater depth and flow rate and headspace air flow rates to calculate a field
Reduction Factor for each studied siphon. Use of a reduction factor applied to headspace cross-
sectional area and wastewater flow rates allowed calculation of estimated headspace air flow
rates.
In the literature, there was a limited discussion of sewer headspace vacuum and pressure having
been measured in other odorous sewers, ranging from -0.10 inches of water (vacuum) to +0.25
inches of water (pressure). It was decided to also include field measurement of headspace
pressure or vacuum at each of the subject siphon inlet and outlet structures.
Sewer Hydraulics. The theoretical relationships between sewer slope, Mannings “n” factor,
actual depth of wastewater flow, and wastewater velocity were studied for open channel sewers.
It was determined that the theoretical maximum cubic feet per minute (cfm) of foul air
movement per headspace cross-sectional area in square feet multiplied by predicted wastewater
velocity in feet per minute for any given slope sewer based on Mannings Equation occurs at a
d/D = 0.3.
3634
WEFTEC®.06
Gravity sewers are designed to flow partially full; this type of flow regime is known as “open
channel” flow. Gravity sewers are also typically designed for projected peak diurnal flow for a
minimum velocity exceeding 2.2 feet per second at a flow depth (d) to sewer diameter (D) ratio
(d/D) of 0.5 to 0.75, depending on sewer size. Maintaining a minimum wastewater velocity
prevents deposition of suspended solids from the wastewater, and promotes entrainment of fresh
air and oxygen into the wastewater.
Over a number of years and review of numerous wastewater collection systems, the authors have
noted that sewers are often sized larger than optimum under present day conditions. To avoid
sewer surcharging and spills, it is the nature of the sewer design process to be generous with unit
flow factors per person or per connection and to be conservative with selection of peak to
average ratios. Additionally, development does not always proceed to the ultimate density
allowed by zoning, or the zoning may be changed to lesser density allowed. Some or all of these
factors can lead to a sewer that is larger than necessary and a sewer that flows with less velocity
than originally anticipated. This may result in excessive deposition of solids, increased potential
for odor release, and a need for increased frequency of sewer cleaning and maintenance.
A well mixed and oxygenated wastewater remains aerobic and discourages anaerobic liquid
phase hydrogen sulfide (H2S) generation. Due to typically conservative planning and hydraulic
design, pipelines are often oversized and wastewater is often not conveyed at sufficient velocity
or with sufficient oxygenation to maintain aerobic conditions, resulting in anaerobic generation
of dissolved H2S. Hydraulic turbulence of wastewater rich in dissolved H2S results in release of
H2S gas to the sewer atmosphere above the open channel flow in sewers. In contrast to open
channel sewers, inverted sewer siphons are designed to flow full and under pressure as they pass
3635
WEFTEC®.06
under obstacles. Sewer siphon diameter is often reduced, compared to the upstream and
downstream sewer, to maintain equal or greater velocity in the full-pipe sewer siphon versus the
open channel sewer. Sewer siphons often include two or three parallel “barrels” with
hydraulically stepped use to maintain higher wastewater velocity in each barrel. This increased
wastewater velocity improves suspension and carry-through of settleable solids and grit,
reducing the need for cleaning. This increased velocity, however, comes at the price of increased
headloss, partially offsetting the original purpose of the siphon.
FIELD EVALUATIONS
The literature review confirmed the proposed field data collection approach for the OCSD
Siphon Rehabilitation Project. The data collection from extensive field evaluations at the
project’s 17 inverted sewer siphon sites included:
• Ambient H2S air testing in the vicinity of the siphons was conducted using Odor Logger
continuous monitoring, with measured H2S results ranging from 0.0 ppm to 0.7 ppm.
Short-term human monitoring assisted by Nasal Ranger Olfactometer analysis was also
conducted.
• Physical inspections of the siphon inlet and outlet manholes; cleaning and CCTV
inspection of air jumpers (if existing); and cleaning and sonar inspection of the inverted
siphons were conducted.
• Wastewater flow was measured and recorded for a minimum 13-days for each siphon
• Instantaneous wastewater dissolved hydrogen sulfide (H2S), dissolved oxygen (DO);
temperature; and pH measurements were made and recorded. The pH of the sewer crown
and manhole interior surface were measured
3636
WEFTEC®.06
• Sewer headspace atmospheric H2S measurements were made over a minimum three day
period, with H2S Odor Loggers suspended in manhole headspace. H2S concentrations as
high as 500 parts per million (ppm) were detected
• Airflow rates into, or out of, siphon inlet and outlet manholes were measured up to 600
cubic feet per minute (cfm)
• Sewer headspace vacuum or pressure was measured at siphon inlet and outlet manholes,
with any existing air jumpers both plugged and unplugged. The measured instantaneous
upstream unplugged range of vacuum/pressure was from .04 inches water column (in.
WC) vacuum to 0.20 in. WC pressure with an average pressure of 0.019 in. WC. The
measured instantaneous downstream unplugged range of vacuum /pressure was from 0.05
in. WC vacuum to +0.02 in. WC pressure. For the few downstream locations with
pressure, there are other likely downstream obstructions to flow other than the adjacent
siphon.
3637
WEFTEC®.06
Correlations between measured wastewater flow rate and measured sewer headspace airflow rate
and vacuum or pressure were determined.
Wastewater Flows and Velocities. Wastewater depth and velocity profile data were collected
continuously for a two week period at each of the 17 siphon sites. From the depth and velocity
profile data, wastewater flow rates were calculated through the siphon using the following
equation:
Q = A x V (Equation 1)
Where:
Q = Flowrate, cubic feet per second
A = Cross-sectional area of flow, square feet
V = Velocity, feet per second
Some of the wastewater flow meters were located on the downstream side of the siphons if
upstream installations were impractical. There was a considerable difference in flow
characteristics for those locations. Downstream of the siphon, wastewater velocities were
generally lower and depth of flow was greater compared to the calculated, normal flow expected
from Manning’s Equation. This could reflect some other downstream hydraulic control
influencing the depth of flow at the siphon outlet.
Manning’s Equation. Manning’s Equation was used with Equation 1 for both open channel and
siphon hydraulic calculations (pg. 7-26, King Handbook of Hydraulics, 4th Edition) to calculate
the flowrate.
1.486
Q = ar 2 / 3 s 1 / 2 (Equation 2)
n
Where:
n = coefficient of roughness in Manning’s Equation
a = area of cross section of water in channel
p = wetted perimeter, square feet
r = a/p = mean hydraulic radius
s = H/l = average loss of head per foot
H = loss of head due to friction in reach
l = length of reach, feet
For similar sections, the value of the expression ar2/3 = a 5/3 / p2/3 varies as the eight-thirds power
of corresponding linear dimensions. Equation 2 can therefore be written in the equivalent form to
solve for flow rate or velocity at a given depth and slope.
3638
WEFTEC®.06
K
Q = d 8 / 3 s1/ 2 (Equation 3)
n
Where:
K = discharge factor of 1.486
d = maximum depth of water
Manning’s Friction Factor (n). The slope and diameter of the sewer upstream of the siphons
was found on either the AS-BUILT drawings provided by OCSD or from the OCSD geographic
information system (GIS) database. All of the AS-BUILT drawings except for two showed the
original sewer design criteria on the plans. All design criteria had the same nomenclature
including the coefficient of roughness, n; diameter, d; maximum depth of flow, D; mean
velocity, v; and flow rate, Q.
A common assumption for sewer hydraulic calculations is to use the value of 0.013 for the
roughness coefficient. The same roughness coefficient was used for the design criteria on every
siphon included in this project, regardless of the type of pipe. Existing sewer pipe materials
found include Vitrified Clay Pipe (VCP) and Polyvinyl Chloride/Plastic Lined Reinforced
Concrete Pipe (PLRCP).
In reality, the roughness coefficient varies with pipe material. Some of the concrete pipe sewers
were originally unlined. The unprotected concrete lining will deteriorate in the corrosive
environment common to sanitary sewer. Lining concrete sewers therefore became necessary to
extend the service life of the sewer system. Once a sewer becomes lined it changes the hydraulic
properties of that sewer. For instance, after a concrete sewer is lined with PVC, it will flow at a
higher velocity and a lower depth with the same flow rate. Age also changes the hydraulics of a
sewer. When pipe is initially installed, it has a lower roughness coefficient than an older sewer
which may have a roughened interior surface. Roughness coefficient sometimes varies with
depth of flow. For the purpose of this study and for most sewer designs, the typical value of the
roughness coefficient is considered constant as depth of flow changes and varies for different
pipe materials.
Pipe Material n
Plastic (PVC) 0.009
Concrete, average value used 0.013
Concrete, with rough joints 0.016-0.017
Concrete, very smooth or PVC lined 0.011-0.012
Clay 0.011-0.015
A roughness coefficient value of 0.013 is not suitable for all types of pipe materials. A roughness
coefficient was calculated for the upstream sewer of each siphon in order to predict wastewater
velocity in the pipe. The roughness coefficient was calibrated using the depth of flow and
velocity measured in the field. Once a roughness coefficient was assigned for each siphon, the
3639
WEFTEC®.06
upstream sewer velocity can be predicted at any depth of flow using Equations 1 through 4. The
velocity is used later to determine the Reduction Factor (RF), as discussed below.
In most cases the flow meters were installed just upstream of the siphons. When the flow meter
was on the downstream side of the siphon and there appeared to be a downstream hydraulic
control, the “n” value was not adjusted based on field data to match the flow depth. Instead, the
Manning’s Equation was used to match the measured flowrate and corresponding wastewater
velocity with theoretical normal depth conditions.
Reduction Factor. The Reduction Factor (RF) is the ratio of the air velocity to the wastewater
velocity. It is the proportionality constant between the wastewater velocity and the air velocity
occurring at the boundary layer.
Vair
RF = (Equation 4)
Vwastewater
Air jumper sizing is based on the fluid dynamics of open channel flow. Friction imparted on the
air as the wastewater travels down the sewer creates an air flow rate and air velocity in the
headspace within the pipe. The wastewater stream in the sewer has two coefficients of friction,
one with the pipe surface and one with the air above the wastewater surface.
Air Velocity. Air velocity is calculated to determine the Reduction Factor. Instantaneous air
flow rate measurements were taken at all siphons locations.
Qair
Vair = (Equation 5)
Aair
Air area is calculated by subtracting the area of the wastewater by the area of the full pipe. The
equation can be written as:
πd 2 Qwastewater
Aair = − (Equation 6)
4 Vwastewater
Where:
Aair = the headspace area within the sewer pipe
d = diameter of the pipe
Wastewater Velocity. The wastewater flow rate, depth, and velocity were reported by MGD in
the flow metering report. Because air flow rates were measured prior to installation of the
wastewater flow meters, the wastewater velocity and flow rate used to determine the headspace
area was approximated. Data taken at the same time of day and day of the week, rounded to the
nearest half hour, was used in the calculation. To calculate a more accurate reduction factor for
existing siphons in the future, it is recommended that the wastewater flow meters be installed and
operating during the entire data collection process.
3640
WEFTEC®.06
Field Measured Reduction Factors. RF values calculated based on the field data for the
evaluated siphons varied between 0.05 and nearly 0.5. The air flow rate measured at Siphon 48
was varying up and down by a factor of 10:1. The cause of this anomaly has not been
determined. Possible reasons may include influence from changes in wastewater flow rate due to
downstream partial pipeline blockage, transient hydraulic surcharging due to sewer design, grit
settlement, grease, mechanical ventilation at pump stations or treatment plants, or other causes.
While a mathematical relationship to calculate RF without field data has yet to be developed,
trends are visible in the following graphs. Figure 3 shows that generally the RF decreases with
pipe diameter. Figure 4 shows that generally the RF decreases with wastewater velocity. Note
that in all field measured / calculated cases, the RF does not exceed 0.5. Figure 5 shows that RF
increases with increasing air velocity, however, whereas wastewater velocity can be calculated in
the hydraulic design of a pipeline, air velocity can be affected by numerous undefined factors
and does not behave consistently. There is poor correlation in all three graphs. Therefore, the
calculation procedure described below utilizes a site specific measured and calculated RF with a
safety factor applied.
3641
WEFTEC®.06
Selecting the Reduction Factor. A default RF of 0.5 was selected as the design basis for sizing
the proposed air jumpers. This value exceeds every field measured value and is at the upper limit
of values found in the literature review. The highest reported RF found in the literature review
was 0.6.
3642
WEFTEC®.06
To size the air jumpers conservatively, a safety factor was included in the sizing calculation. A
minimum safety factor of two was used. Due to the wide variation in RF values, some air
jumpers would be oversized with the default RF of 0.5, and for these locations a maximum safety
factor of five was selected. This was done to account for found sewer headspace conditions that
may have been affected by secondary controls, such as headspace blockage downstream from the
siphon area.
The following procedure was followed when adding a safety factor to air jumper sizing. Only
three scenarios are possible. The RF is initially multiplied by the minimum safety factor of 2. If
the product is greater than 0.5 go to CASE 1. If the product is less than 0.5, do not use that value.
Instead, multiply the calculated RF by a safety factor of five and go to CASE 2.
• CASE 1: When the default RF value of 0.5 results in a safety factor less than two, the
default value is not used. Instead, a safety factor of two is used and the resulting RF value
will exceed 0.5. Siphon 22 is an example of this scenario.
• CASE 2: When the default RF value of 0.5 results in a safety factor greater than five, the
default value is not used. Instead, a safety factor of five is used and the resulting RF value
is less than 0.5. Siphon 17 is an example of this scenario.
• If CASE 1 or CASE 2 does not apply, use the default value of 0.5.
When calculated this way, the upper limit to the selected RF is 1.0. If a maximum calculated RF
greater than 0.5 occurs, other variables besides wastewater velocity must be considered. Such a
situation might occur in the vicinity of a large mechanical ventilation and odor control system,
where the dominant forces for air flow are not frictional drag from wastewater. If this occurs, the
proposed air jumper should be sized based on the flowrate of the mechanical ventilation system.
Calculate Maximum Air Flowrate. The air flowrate within the sewer pipe varies throughout
the day with the daily diurnal fluctuations in wastewater flow. The highest potential air flowrate
must be calculated in order to size the air jumpers. The typical geometry at the entrance and exit
manhole of each siphon, as shown by Figure 1, is used to illustrate the variables of the air and
wastewater balance. The maximum air flowrate used to size the air jumper is calculated with the
following equation:
Qair = RF x V x A x 60 (Equation 8)
Where:
Qair = Air Flowrate in cubic feet per minute
RF = Selected Reduction Factor
V = Wastewater Velocity (at d/D = 0.3) in feet per second
A = Headspace Area (at d/D = 0.3) in square feet
60 = conversion factor from cfm to cfs
3643
WEFTEC®.06
Allowable Air Jumper Headloss. Pressure differentials were measured in the field at the
upstream and downstream manhole of each siphon. The allowable headloss through the proposed
air jumper is based on the pressure differential measured in the field while the existing air
jumpers were blocked. The headloss across the proposed air jumper is calculated using the
maximum air flow rate calculated in the previous section. The air jumper diameter is initially
chosen with a headloss rate of 0.01 inches of water per 100 feet of air pipe per Figure 7. The
maximum pressure differential observed was 0.1 inches of water column. Since most sites have
short air jumpers, they will have a total headloss much less than 0.1 inches of water column.
3644
WEFTEC®.06
Once the pipe diameter is chosen, the as-built drawings were checked to determine if there is
enough vertical clearance to install an air jumper of that diameter. At some sites, there is not
enough vertical clearance to install one air jumper of the recommended diameter. If multiple air
jumpers must be used instead of a single air jumper, then than the total system headloss should
be limited to 0.1 inches of WC for the multi-barrel approach.
The following procedure is recommended for sizing siphon air jumpers at existing siphons. For
new siphon and air jumper installations, a Reduction Factor (RF) of 0.5 should be used as a
default value when field data is unavailable.
1. Install flow meters to measure wastewater flow rates and depths until all air flow rate
measurements have been completed. Usually two weeks of wastewater flow monitoring
is sufficient, provided all other field data is completed within that timeframe.
2. Measure air flow rates and take pressure readings at the upstream and downstream siphon
access manholes.
3. Calibrate a wastewater conduit roughness coefficient based on flow meter data to
determine the wastewater velocity at a depth-to-diameter value ratio of 0.3.
4. Calculate site specific RF values using air flow rate, water velocity and depth of flow (to
get area). Unless a greater RF value is calculated, use the default RF to compare to the
default value.
5. Use the default RF of 0.5 to determine the theoretical air flow rate at a depth-to-diameter
ratio of 0.3.
6. Check the maximum calculated RF with the default of 0.5. This is done by dividing the
maximum calculated value by 0.5, if the result is less than 2, then multiply the maximum
calculated value by 2 and use this new value for the selected RF. If the result is greater
than 5, then multiply the maximum calculated value by 5 and use this new value for the
selected RF.
7. Determine the maximum air flow rate with the selected RF at a depth-to-diameter value
of 0.3.
8. The air jumper diameter should then be selected from the nomograph using a headloss
rate of 0.01 feet per 100 feet.
9. Verify that the site has enough vertical clearance to allow the installation of the air
jumper. If not, use multiple smaller diameter air jumpers.
10. Headloss within the overall air jumper system (pipe friction plus minor losses) should
then be analyzed to confirm total headloss does not exceed 0.10 inches of water column.
3645
WEFTEC®.06
CONCLUSIONS
• If the continuity of the sewer headspace is interrupted by an inverted siphon, then the
sewer headspace pressurizes and releases malodorous air.
• There was a positive correlation between wastewater velocity and sewer headspace
air flowrate in the open channel sewers upstream and downstream of the siphons.
Field interpreted Reduction Factors (RF) in the range from 0.1 to 0.5 were derived
from field measurements.
• Sewer headspace was typically under pressure upstream of the siphons in the range
up to +0.1 inches of water column. Sewer headspace was typically under vacuum
downstream of the siphons in the range down to -0.1 inches of water column.
RECOMMENDATIONS
A procedure for calculating the air flowrate for new siphon air jumpers is recommended by
applying a 0.5 Reduction Factor for theoretical wastewater flowrate for a given sewer size and
slope at d/D = 0.30. For existing siphons, the recommended airflow rate sizing should be field
verified to result in a safety factor not less than 2:1 or greater than 5:1. Air jumpers should then
be sized to carry the recommended air flowrate at a duct headloss not exceeding 0.01 inches
water column per 100 feet of duct and with a total air jumper headloss not exceeding 0.1 inches
water column including minor headloss.
ACKNOWLEDGEMENTS
The authors would like to acknowledge the dedication of the OCSD field operations personnel in
maintaining the OCSD wastewater transmission system, including the project siphons, in
excellent condition.
Steve Deering and Steve Jepsen would like to acknowledge the Project Management and
assistance provided to the consultant team for this project by Alberto Acevedo and Mandy
Taylor, OCSD.
The Dudek Project Team would like to acknowledge the assistance of all of our subconsultants
and service providers on this project including: MGD Technologies for flow measurement and
manhole inspection work; Coastal Traffic Systems for field activity traffic control; Ninyo &
Moore Geotechnical, National Plant Services for CCTV and sonar inspections; HMS
Construction for potholing; Forkert Surveying; and Traffic Management, Inc. for construction
traffic control plans.
3646
WEFTEC®.06
American Society of Civil Engineers, ASCE Manual of Practice No. 60, Gravity Sanitary Sewer
Design and Construction, New York, 1982.
Air Jumpers, page 144, paragraph 3. “To overcome this difficulty, a number of
siphons built in recent years have used air jumpers; that is pipes that take the air off
the top of the inlet structure and return it at the end of the siphon. Usually, the jumper
pipe is a third to a half the diameter of the siphon.”
McQuiston, F.C. & Parker, J.D., Heating, Ventilating, and Air Conditioning, Analysis and
Design, John Wiley & Sons, New York, 2nd Edition, 1982.
11-7 Air Flow In Ducts”, page 385 (friction loss charts for straight, constant area
ducts), 11-8 Air Flow In Fittings”, page 392 (friction loss in fittings)
U.S. Environmental Protection Agency, Office of Research and Development, Handbook, Sewer
System Infrastructure Analysis and Rehabilitation, EPA/625/6-91/030, Cincinnati,
OH, October 1991.
No direct references to the design or use of air jumpers.
U.S. Environmental Protection Agency, Office of Research and Development, Design Manual,
Odor and Corrosion Control in Sanitary Sewerage Systems and Treatment Plants,
EPA/625/1-85/018, Cincinnati, OH, October 1985.
5.2.6 Siphons, page 110, paragraph 4. “One technique that has been successfully
used to minimize odor release at siphons is the use of air jumpers.” “Usually, the
diameter of the air jumper pipe is approximately one-half that of the siphon.”
5.3.2.1 Natural Ventilation, page 111, paragraph 2
“Natural ventilation occurs from the following forces.
1. Change in barometric pressure along the sewer.
2. Wind velocities past vents.
3. Fractional drag of wastewater on sewer air.
4. Rise and fall of the wastewater level in the sewer.
5. Relative density differences of sewer air and outside air.
The degree of natural ventilation which occurs in a sewer is difficult to predict,
since fluctuations in the above variables may change both the direction of
movement and velocity of the air contained in the sewer.”
3647
WEFTEC®.06
U.S. Environmental Protection Agency, Office of Water, Hydrogen Sulfide Corrosion: Its
Consequences, Detection and Control, (WH-595), 832-S-91-100, Washington, D.C.,
September 1991.
No discussion of air jumpers.
U.S. Environmental Protection Agency, Office of Water, Collection Systems O&M Fact Sheet,
Sewer Cleaning and Inspection, EPA 832-F-99-031, Washington, D.C., September
1999.
U.S. Environmental Protection Agency, Office of Water, Technical Report, Hydrogen Sulfide
Corrosion in Wastewater Collection and Treatment Systems, (WH-595), 430/09-91-
010, Washington, D.C., September 1991.
No mention of air jumpers. 4.3.4 Sewer Ventilation, page 4-10. “Sewers are
naturally ventilated through building vents and manholes, occurring from factors such
as changes in barometric pressure, wind, air density differences, and flow
conditions.”
U.S. Environmental Protection Agency, Office of Water, Report to Congress, Hydrogen Sulfide
Corrosion in Wastewater Collection and Treatment Systems, (WH-595), 430/09-91-
009, Washington, D.C., September 1991.
No mention of air jumpers.
Great Lakes-Upper Mississippi River Board of State and Provincial Public Health and
Environmental Managers, Recommended Standards for Wastewater Facilities, 1997
Edition, Health Research, Inc., Albany, N.Y., 1997.
Inverted siphon design criteria, no mention of air jumpers.)
3648
WEFTEC®.06
Blanda, T., Medium to Large Diameter Sewer Siphon Cleaning, Orange County Sanitation
District, CWEA Annual Conference, Palm Springs, CA, April 2005.
Describes siphon cleaning at the Orange County Sanitation District. Included is the
use of a tire with the pull rig to remove heavy debris from the sewer invert.
Water Environment Federation, Identifying and Controlling Municipal Wastewater Odor, Phase
1: Literature Search and Review, WEF, Alexandria, VA, 2003.
Extensive review of literature from 1990 to 2000; reviewed 669 published articles and
155 unpublished (gray) articles.
2.5.2.6 Control of Ventilation, page 2-17. “During the past 10 years, there has been
little published or gray literature related to the ventilation of municipal sewers. In
fact, odor complaints are often acted upon by simply ‘sealing’ a portion of the sewer,
such as sealing manhole cover pick-holes with tar or replacing the cover with one that
does not have holes. This practice often leads to emissions of odorous gases at
another location in the system.”
2.7.3 Odor Control Technology - Research Agenda Items, page 2-22. This section
discussed the importance of developing ventilation “models” to predict the emission
of odorous gases from sewers. “...such models are ultimately limited by a lack of
ability to predict natural ventilation rates.” The proposed project would fund
academic researchers to study this problem.
Water Environment Federation Manual of Practice No. 25, Control of Odors and Emissions from
Wastewater Treatment Plants, WEF, Alexandria, VA, 2004.
Includes a detailed information on analysis and treatment of odors with an emphasis
on treatment plants. Some general comments on collection system odors and sewer
design including using air jumpers.
Page 163-166. Discussion of effect of liquid and vapor phase mass-transfer on odors.
Review of factors in sewer ventilation and some data from studies. Summary states
that it is necessary to understand both the physicochemical properties of the odorous
compounds and the collection system configuration to predict VOC emissions.
Page 253. Comment that air jumpers maybe included in siphon design.
Water Environment Federation, Odor and Corrosion Prediction and Control in Collection
Systems and Wastewater Treatment Plants, compendium of papers presented at
WEFTEC 2000 workshop, WEF, Alexandria, VA, 2001.
City of San Diego, Clean Water Program Guidelines, Guidelines for Design Consultant, Volume
VIII, San Diego, CA, February 1992.
SIPHONS Appendix D, page D9-11. “In general, at least two pipes shall be used in a
siphon so that self-cleaning velocities occur over the full range of flow conditions.”
For the smallest barrel, design for a velocity of 4 to 6 fps at minimum flow. Calculate
3649
WEFTEC®.06
friction loss using the Hazen-Williams formula with a C of 100. There is no comment
on air jumpers.
Koziel, J.A. & Corsi, R.L., VOC Emissions from Municipal Sewers: Hot Spots, Air & Waste
Management Association, 91st Annual Meeting, San Diego, CA, June 1998.
Liquid phase mass transfer coefficients for volatile compounds. A 60 meter long
pilot sewer was used in experiments.
Olson, D.A., Varma, S. & Corsi, R.L., A New Approach For Estimating Volatile Organic
Compound Emissions From Sewers: Methodology and Associated Errors, Water
Environment Research, Vol. 70, No. 3, May/June 1998.
Describes interrelationship of mass transfer of VOC from liquid phase to gas phase
and sewer ventilation rate on odorous emissions from a sewer.
Corsi, R.L. & Quigley, C.J., VOC Emissions from Sewer Junction Boxes and Drop Structures:
Estimation Methods and Experimental Results, Air & Waste Management
Association, 88th Annual Meeting, San Antonio, TX, June 1995.
Describes seventeen pilot experiments of VOC stripping at junction boxes and drop
structures.
Koziel, J.A. & Corsi, R.L., A Novel Approach for Estimating VOC Emissions from Municipal
Sewers: Methodology, Applications, and Implications, Air & Waste Management
Association, 89th Annual Meeting, Nashville TN, June 1996.
No discussion of air velocities in sewer or air jumpers
Corsi, R.L. & Quigley, C.J., Design of Low Emission Sewers, Air & Waste Management
Association, 87th Annual Meeting, Cincinnati, OH, June 1994.
Review of concepts developed for the analysis of discharge of volatile organic
compounds from sewers carrying industrial wastewater. No description of the
relationship of wastewater velocity and air flow.
Olson, D., Corsi, R.L. & Rajagopalan, S., Buoyancy-Induced Ventilation between Industrial
Sewers and the Ambient Atmosphere, Air & Waste Management Association, 89th
Annual Meeting, Nashville, TN, June 1996.
Concerns the discharge of volatile organic hazardous air pollutants.
Corsi, R.L., Volatile Organic Compound Emissions from Wastewater Collection Systems, Doctor
of Philosophy Dissertation, University of California, Davis, CA, December 1989.
The thesis did not specifically study siphons or air jumpers.
Abstract. “It was concluded that no single mechanism dominates sewer ventilation
under all situations, but environmental conditions, wastewater flow conditions, and
physical characteristics of a collection system were identified under which some
mechanisms become dominate.”
8.1 CONCLUSIONS, Ventilation. 1. “Given the complexity of most collection
systems it is impossible to accurately calculate actual ventilation rates and gas flow
3650
WEFTEC®.06
patterns for any given system. For a specific sewer reach, release of an inert tracer
can be used to estimate gas flow rates.”
3. “Liquid drag causes gas flow in the same direction as wastewater flow, and is the
only ventilation mechanism that acts continuously.”
4. “Under conditions of low resistance to ambient air inflow and sewer gas exhaust,
liquid drag can induce maximum gas mean velocities of up to 0.2 m/s. Actual
velocities in sanitary sewers are expected to be on the order of 0.04 to 0.2 m/s for
small pipes (0.25 m diameter); 0.003 to 0.20 m/s for mid-sized pipes (1.0 m
diameter); and 0.005 to 0.18 m/s for large pipes (2.5 m diameter).”
Molseed, A.C., Wolstenholme, P.L., Newman, G.R., Yee, S. & Hiraki, G., Odor and Corrosion
Control in a Large Diameter Sewer Upstream of a Low-Head Structure, Odors and
Toxic Air Emissions 2002, WEF, Alexandria, VA, 2002.
An inverted siphon in an 108-inch sewer caused a stagnant air pocket to form
upstream of the siphon when flows were high. It was decided to treat the resulting
foul air with a biofiltration system. An air jumper was analyzed as an alternative.
Dechant, D., Catlin, C. & Huttes, R., Odor Control Study in a Deep Sewer System with Multiple
Drop Structures, WEFTEC 2000, WEF, Alexandria, VA, 2000.
An 8-mile reach of interceptor sewer was monitored for air flow, sewage flow, air
pressure and hydrogen sulfide. The diameter ranged from three to nine feet.
“The collective experience of the project team indicated that.....wastewater flow in the
interceptors can produce 25 to 250 cfm of air flow per mgd of wastewater flow.”
The following general comments were in the Analysis section. “The primary motive
force for air movement in sewers is friction between the headspace air and the
moving wastewater. The resistance to air movement in a sewer pipe is friction
between the air and the water surface and the stationary walls of the sewer. The
velocity of the air is at a maximum approaching 0.8 times the wastewater velocity
near the surface of the water and decreases rapidly with increasing distance
approaching zero at the pipe wall.”
Davidson, S., Green, J., Mann, J. & Lamb, E., Design Challenges in Sewer Foul Air Extraction
and Treatment, WEF/A & WMA Odors and Air Emissions 2004, WEF, Alexandria,
VA, 2004.
This paper focuses on removing odorous air and treating it. Some typical headspace
pressures are given.
Davidson, S., Green, J., Mann, J. & Lamb, E., Assessing the Effectiveness of Sewer Headspace
Foul Air Extraction, WEFTEC 2002, WEF, Alexandria, VA, 2002.
Tests on Phoenix area sewer 42-inch to 90-inch in diameter exhibited pressures of
+0.10 to +0.25 inches water column. Extraction tests with a mobile trailer-mounted
fan reduced pressures to -0.03 to -0.80 inches water column. The influence distance
of lowered pressure was typically about 5 miles.
3651
WEFTEC®.06
Parker, W.J., & Ryan, H., An Evaluation of Ventilation Patterns in a Regional Collector Sewer,
Odors and VOC Emissions 2000, WEF, Alexandria, VA, 2000.
Report of field tests of the velocities of headspace gas in an 11 km sewer (24”-84”
dia.) using carbon monoxide gas as the tracer. The air velocities ranged from 3.8
m/min (0.21 fps) to 31.5 m/min (1.72 fps). The velocities of the sewage flow were
not reported. “The velocities (of air flow) observed varied substantially with time and
location in the collector.”
Sorensen, H., Joyce, J., Day, D., & Fallara, C.T., Odor Control for Large Diameter Deep Sewer
Tunnels - The City of Columbus Ohio, Odors and VOC Emissions 2000, WEF,
Alexandria, VA, 2000.
Pai, P., Joyce, J. & Sorensen, H., Large Diameter Sewer Ventilation Dynamics Require a Three
Mile-Long Odor Control Duct in Las Vegas, Odors and VOC Emissions 2000, WEF,
Alexandria, VA, 2000.
Analysis of points on a large sewer to withdraw air for treatment. Details of the
calculations were not included in the paper.
McConico, W.E., Wooten, K.G., DuVal, G.A., Bizzarri, R.E., Maisch, F.E. & Guhse, G.L.,
Hydraulic Energy Flushing of Inverted Siphons, WEFTEC 2001, WEF, Alexandria,
VA, 2001.
No air jumper with these siphons.
Quigley, C.J. & Corsi, R.L., Emissions of VOCs from a Municipal Sewer, Journal of the Air &
Waste Management Association, Volume 45, Page 395-403, May 1995.
Field tests on an interceptor sewer in metropolitan Toronto, ON. High ventilation
rates were observed on this sewer resulting in large quantities of VOC emissions.
They studied a 1.6 km reach of a sewer 0.9 to 1.2 m diameter.
City of Los Angeles, F200 Projection of Flows and Hydraulics of Sewers, Sewer Design Manual
- Part F, Bureau of Engineering, City of Los Angeles, June 1992.
Twelve sub-sections of the manual covering various aspects of inverted siphon and
air jumper design. A minimum of two barrels shall be provided for the inverted
siphon and the minimum velocity at PDWF shall be 4 fps at least once per day. The
recommended “n” is 0.014.
The manual states empirical design of air jumpers is the method of choice. The
empirical method determines the cross sectional area (head space) available for gas
3652
WEFTEC®.06
flow in the sewer approaching the siphon. The cross sectional area of the air jumper
shall be two times the cross sectional area for gas flow.
Pescod, M.B. & Price, A.C., Fundamentals of Sewer Ventilation as Applied to the Tyneside
Sewerage Scheme, Water Pollution Control, 17, 1981.
Pescod, M.B. & Price, A.C., Major Factors in Sewer Ventilation, Journal of the Water Pollution
Control Federation, 54, 4, 1982.
3653