SE Current Monitoring Series H908-S6: Danger

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

1

Switches

SE Current Monitoring Series


H908-S6

Specifications
Sensor Power. . . . Induced from monitored conductor The Schneider Electric H908-S6 is a current-sensitive
Amperage Range . . . . . . . . 2.5 to 135 A Continuous switching device that monitors current (amperage)
Status Output Ratings. . . . . N.O. 1.0 A@30 VAC/DC, in the conductor passing through it. A change in the
not polarity sensitive conductor’s amperage that crosses the adjustable
switch threshold plus the hysteresis value causes the
Insulation Class. . . . . . . . . . . . . . . . . 300 VAC RMS,
resistance of the FET status output to change state,
insulated conductors only
similar to the action of a mechanical switch. The
Setpoint . . . . . . . . . . . . . . . . . . . . . . . . . . Adjustable setpoint is adjustable through the action of a twenty
Frequency. . . . . . . . . . . . . . . . . . . . . . . . . . 50/60 Hz turn potentiometer (see the Calibration section). The
Temperature Range. . . . . . -15° to 60°C (5° to 140°F) status output is suitable for connection to building
Humidity Range. . . . . . . 10-90% RH non-condensing controllers or other appropriate data acquisition
Hysteresis. . . . . . . . . . . . . . . 10% of setpoint (typical) equipment operating at up to 30 volts. The H908-S6
Off State Resistance . . . . . . . . . . . . . . . Open switch requires no external power supply to generate its
output.
represents 1+ MΩ
On State Resistance . . . . . . . . . . . . . . Closed switch
represents <200 mΩ
Dimensions
Terminal Block Wire Size . . . . . . . . . . . 0.2 to 2.1 mm2
(24 to14 AWG) Removable Mounting Bracket
Bracket can
Terminal Block Torque . . . . . . . . . . . . . 0.4 to 0.5 N-m 25 mm be mounted
(3.5 to 4.4 in-lb) (1.0 in.) on three sides
for added
Agency Approvals. . . . . . . . . . . CE:EN61010-1:2001 26 mm 21 mm
(1.1 in.) installation
(0.8 in.)
Installation Category. . . . . . . Cat. III, pollution degree 2 flexibility.
79 mm
For CE compliance, conductor shall be insulated (3.1 in.)
according to IEC 61010‑1:2010. The product design
provides for basic insulation only. Do not use LED
Self-gripping
indicators as evidence of applied voltage.
70 mm Iris
(2.8 in.)

DANGER Ø = 8 mm
36 mm
(1.4 in.)
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH (0.3 in.)
• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes. 64 mm
• This equipment must only be installed and serviced by qualified electrical personnel. (2.5 in.)
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment. 76 mm
• Use a properly rated voltage sensing device to confirm power is off.
(3.0 in.)
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
A qualified person is one who has skills and knowledge related to the construction and
operation of this electrical equipment and the installation, and has received safety
training to recognize and avoid the hazards involved. NEC2011 Article 100
No responsibility is assumed by the manufacturer for any consequences arising out of
the use of this material.

NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
2
Switches H908-S6

INSTALLATION
Disconnect and lock out power to the enclosure containing the conductor to be
monitored.
1. Locate a mounting surface for the removable mounting bracket that will CONTACTOR
allow the monitored conductor to pass through the center window when
it is installed and that will keep the product at least 13 mm (½ in.) from Insulated Conductor CONTROLLER
any uninsulated conductors. Determine cable routing for the controller
connection, allowing wiring to reach the mounting location.
2. Drill holes to mount the bracket to the chosen surface using the included Digital
screws. Input
3. Wire the output connections between the sensor and the controller (solid-
state contact).
4. Snap the sensor over the wire to be monitored clip the assembly to the
mounting bracket.
5. Secure the enclosure and reconnect power.
6. Calibrate the current switch (see Calibration section).

MOTOR

Fan or Pump

Calibration
Before beginning calibration, establish normal load conditions.
OK!
OK!

Then choose either A or B below.

A. To monitor under-current (belt loss, coupling shear, status) B. To monitor over-current (mechanical problems, seized impeller)
! OK!
STATUS
STATUS
OK! ! OK!
A OK!

A
1. Turn setpoint screw clockwise until Status Open LED turns on.
1. Turn setpoint screw counter‑clockwise until Status Closed
Setpoint LED turns on.

Status Status
Open Closed Setpoint

Status Status
2. Slowly turn the screw counter‑clockwise until the Status Closed Open Closed

LED just turns on.


2. Slowly turn the setpoint screw clockwise until the Status
Setpoint
Open LED just turns on.

Status Status Setpoint


Open Closed
© 2012 Schneider Electric. All rights reserved.

Status Status
Open Closed
3. Turn the screw an additional 1/4 turn counter‑clockwise for
operational margin.
3. Turn the setpoint screw an additional 1/4 turn clockwise for
Setpoint
operational margin.

Setpoint

¼ Status Status
Open Closed

¼ Status Status
Open Closed

Schneider Electric Telephone Europe: Malmö, Sweden +46 40 38 68 50 Telephone Asia Pacific: Singapore +65 6776 3166 www.schneider-electric.com
00119-01-en November 2012 sr
3
Switches H908-S6

LOW CURRENT APPLICATIONS < 2.5 A (Sensor Min.)


4x
CAUTION
RISK OF EQUIPMENT DAMAGE
For load currents less than sensor minimum 1A • Derate the product’s maximum current for the number of turns
rating, wrap the monitored conductor through the sensing window using the following formula.
Rated Max. Amps ÷ Number of Turns = Max. monitored Amps
through the center window and around
e.g. : 100A ÷ 4 Turns = 25 Amps max. in monitored conductor
the sensor body to produce multiple turns.
• Failure to follow these instructions can result in overheating
This increases the current measured by the and permanent equipment damage.
transducer.

HIGH CURRENT APPLICATIONS


For load currents greater than sensor maximum rating, use a 5 Amp
current transformer (CT) as shown. This technique can be combined with
wrapping (see above) to add range for a low current load on a high current
source.

240A > 135 A (Sensor max.)

300A:5A
4A

DANGER: 5A CTs can present hazardous voltages.


Install CTs in accordance with manufacturer's instructions.
Terminate the CT secondary before applying current.

TROUBLESHOOTING
PROBLEM SOLUTION
No Reading at Controller • Check for control voltage at sensor (<30 V, <1.0 A)
• Check for amperage in monitored conductor (>2.5 A)
• Verify that the setpoint is not above operating amps by turning
screw counter-clockwise (up to 20 turns) until the contacts close
(Status Closed LED turns on). Resume calibration from the beginning.
• Assure that sensor core mating surfaces are clean and that the core
clamp is completely closed.
Setpoint screw has no stops The 20 turn setpoint screw has a slip clutch to prevent damage at
either end. To re-start the calibration process, turn the screw 20 full
turns counter-clockwise. Resume calibration from the beginning.
Both LEDs are lit The screw has been turned too far clockwise. Turn the screw 20 full
© 2012 Schneider Electric. All rights reserved.

turns counter-clockwise and resume calibration from the beginning.

Product Information

Ordering Code Model Number Description


324-0104-000  H908-S6 I-Sw,SP,50A,Out1A@30VAC/DC,NO