Saic M 1070
Saic M 1070
Saic M 1070
EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
The structure shall be plumbed, leveled, and braced before any final 12-SAMSS-008
A2
bolted or welded connections are made. (PIP STS05130, Para. 6.3.2) Sec. I
Leveling plates, leveling nuts and washers and loose baseplates and
bearing plates are set in its correct alignment and elevation. The
12-SAMSS-008
A3 variation in elevation relative to the established grade is equal to or less
Sec. I
than plus or minus 1/8" (3mm). (AISC Code of Standard Practice for
Steel Buildings and Bridges, Para. 7.6, and PIP STS05130, Para. 6.4.1)
All column splices shall be field-bolted and conform to AISC Detailing for 12-SAMSS-007
A5
Steel Construction, Appendix D. Para. 6.2.5.20
REMARKS:
1. All survey and dimensional reports shall be recorded in the Structural Steel Alignment Report, SATR-M-2002 or equivalent.
REFERENCE DOCUMENTS:
1- 12-SAMSS-008 -- Erection of Structural and Miscellaneous Steel, 28 January 2004
Page 1 of 1